SCHEDULE OF LOADS
CKT QT VOLT AMPERE
NO. DESCRIPTION Y VA S S PROTECTION SIZE OF WIRE THW CONDUIT PVC
1 LIGHTING OUTLETS 14 1400 230 6.09 15 AT 2-5.5 mm2 1-20 mmӨ
2 LIGHTING OUTLETS 14 1400 230 6.09 15 AT 2-5.5 mm2 1-20 mmӨ
3 LIGHTING OUTLETS 8 800 230 3.48 15 AT 2-5.5 mm2 1-20 mmӨ
4 CONVENIENCE OUTLETS 8 2880 230 12.52 20 AT 2-3.5 mm 2 1-20 mmӨ
5 CONVENIENCE OUTLETS 8 2880 230 12.52 20 AT 2-3.5 mm 2 1-20 mmӨ
6 WASHING MACHINE 1 1400 230 6.09 15 AT 2-3.5 mm 2 1-20 mmӨ
7 REFRIGERATOR 1 1000 230 4.35 15 AT 2-5.5 mm2 1-20 mmӨ
8 RANGE 1 5000 230 21.74 40 AT 2-3.5 mm 2 1-20 mmӨ
9 1 hp AIR CONDITION UNIT 1 1400 230 6.09 30 AT 2-5.5 mm2 1-20 mmӨ
10 1 hp AIR CONDITION UNIT 1 1400 230 6.09 30 AT 2-5.5 mm2 1-20 mmӨ
11 1 hp AIR CONDITION UNIT 1 1400 230 6.09 30 AT 2-5.5 mm2 1-20 mmӨ
12 SPARE
TOTAL 20960 91.15
SERVICE CONDUCTOR: SERVICE EQUIPMENT:
IFL= [ 91.15 + 0.25 (2760)/230] x 80% DF IFL= [ 91.15 + 2.50 (2760)/230] x 80% DF
IFL= 75.32 A IFL= 96.92 A
USE 2.35 mm2, THW WIRE + 1-20 mmӨ CONDUIT PVC USE 125 A MAIN CIRCUIT BREAKER