This document provides information about an Ethernet Option module for VersaMax Micro PLCs. It describes the module, its configuration and installation, supported communication protocols, and FCC requirements.

Uploaded by

ronytular0
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views8 pages

Template

This document provides information about an Ethernet Option module for VersaMax Micro PLCs. It describes the module, its configuration and installation, supported communication protocols, and FCC requirements.

Uploaded by

ronytular0
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module

September 2019 IC200UEM001

Module Description Configuration


This datasheet describes the Ethernet Option module for a Use of the Port Option module as Port 2 and the protocol
VersaMax Micro-20, -40 or -64 PLC CPU. This module cannot selection must be set up in the configuration software. After
be used with other types of VersaMax Nano or Micro PLCs. making those selections, the communications parameters can
For more information about Option Modules, and about also be configured.
VersaMax Micro-20, -40 and -64 PLCs, please refer to the The option port should be configured for Ethernet. If the
VersaMax Nano and Micro PLCs User’s Manual, GFK-1645J configuration and hardware do not match, the PLC logs a
or later. System Configuration Mismatch fault in the PLC Fault Table.
The configuration options are:
Ordering Information Protocol Parameters Value
RJ 45, 10/100 Mbit Ethernet Option module SRTP Server Port Mode SNP
IC200UEM001
supporting SRTP
Port Type Slave
Data Rate 19.2, 38.4 or 175.0
Ethernet Option Module kbps (default)
Ethernet Module IC200UEM001 can be used with a Micro-20, Flow Control None
-40 or -64 -Point PLC to provide an Ethernet Port.
Parity Odd (default),
Even, None
Stop bits 1 (default) or 2
Time Out Long
Turnaround Time 0
Modbus TCP Port Mode RTU
Client / Server*
Port Type Slave
When installed on the Micro 20, 40 or 64 PLC, the Ethernet Port Data Rate 19.2, 38.4 or 175.0
Option Module becomes Port 2. It supports the following kbps (default)
communications protocols: SRTP, Modbus Server and client Flow Control None
(separate download) and pass- through port (separate Parity Odd (default),
download). Protocol options are available online at Even, None
https://www.emerson.com/Industrial-Automation-Controls/support.
Station Address Valid range
0–247. Default=1
FCC and ICES Requirements for the Modbus/TCP Client Disabled (default)
US and Canada Support (Refer to the or Enabled.
VersaMax Nano and
This device complies with Part 15 of the FCC Rules. Operation is Enabling
Micro PLCs User’s Modbus/TCP Client
subject to the following two conditions: (1) this device may not Manual, GFK-1645J or
cause harmful interference, and (2) this device must accept any Support sets the
later.) %I00488 status bit
interference received, including interference that may cause
ON.
undesired operation.
Pass-Through or Port Mode Serial I/O
Note: This equipment has been tested and found to comply with Tunneling
the limits for a Class A digital device, pursuant to Part 15 of the Data Rate 19.2, 38.4 or 175.0
FCC Rules. These limits are designed to provide reasonable kbps (default)
protection against harmful interference when the equipment is Flow Control None
operated in a commercial environment. This equipment Parity Odd (default),
generates, uses, and can radiate radio frequency energy and, if Even, None
not installed and used in accordance with the instructions, may
Stop bits 1 (default), or 2
cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful Bits/Characters 7 or 8
interference in which case the user will be required to correct the Station Address Valid range:
interference at his own expense. (Byte 1 to Byte 8) 0–F. Default=0
Note: This Class A digital apparatus complies with Canadian * When the Ethernet Option Module is configured for Modbus/TCP
ICES-003. Client, the configured Sequence Number and Command Data
addresses should not overlap or conflict with any other variables
Changes or modifications not expressly approved by Emerson used in the logic. These addresses are reserved exclusively for
could void the user's authority to operate the equipment. communications between the CPU and Ethernet module when
initiating Modbus TCP commands.

1
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

Installation Instructions Setting the Permanent IP Address


Power to the VersaMax Micro PLC must be turned off when 1. Go to C:/ Prompt on your computer and type: Ping [IP
installing or removing Option Modules. address] and press the Enter key. (This step is required to
“establish” the ARP table by creating an entry in the table.)
1. Remove the two doors shown below, by pressing downward The address pinged should reply with Pinged data.
on the latches and lifting them away from the module. (example c:/ Ping 10.10.0.5 and return data)
2. Type: arp –a (space between p and –a). You should see at
least one entry in the ARP table. (example c:/ arp –a)
3. Type: arp –s [IP address, including dots] [MAC
Press Down
Address of the Ethernet module, including dashes].
Latch and You will not see any reply on the screen. (example c:/ arp –s
Remove These
Two Doors 10.10.0.5 00-20-4a-ff-ff-e9)
4. Type: telnet [IP address] 1 (leave space between IP
address and 1) and press the Enter key. You will be
2. If a port-type Option Module is being installed, orient the prompted that the connection failed. This is normal.
connector on the Option Module with the connector in the (example c:/ telnet 10.10.0.5 1)
Micro PLC. Be careful to avoid contact with the exposed
components in the module. 5. Type: telnet [IP address] 9999 (leave space between IP
address and 9999) and press the Enter key. You will be
prompted to Press Enter to go into Setup Mode. You have
two seconds to press the Enter key again. If you get the
Connector for message “Connection to host lost”, re-enter telnet [IP
Option Module Screws for
Option Module address] and press the Enter key twice to get to the setup
screen. (example c:/ telnet 10.10.0.5 9999)
Press 1 to change IP address (Enter the desired IP address)
and Net Mask
3. Press the Option Module downward until it clicks into place.
Press 2 to change Serial Settings. For best performance, set
4. Install the screws provided with the Option Module into the the baud rate to 175000. Setting should be Mode#1, RS232
corners indicated above. 175000, 8, 0, 1. Port 2 needs to be configured with PAC
Machine Edition to match these settings. Machine Edition
should configure Port 2 for Ethernet and baud rate of
Connector for 175000.
Memory Pack
Module When complete, press S to save to the Ethernet module. You will
Port
Connector see a prompt that informs you Parameters saved, Display will
Restart…. and then Connection to host lost. The data is now
stored in the internal Flash of the IC200UEM001. You can
5. If a Memory Pack Module is being installed, orient the change the settings by repeating the above steps.
connector on the back of the Memory Pack Module with the
connector on the Micro PLC or port-type Option Module.
Press the Memory Pack down until it clicks into place.
6. Install the protective cover(s). If only the Memory Pack
Module is used, both covers may be installed. If a port
module is used, the right-hand cover is not installed, and the
port connector remains accessible.

Setting the IP Address


Key items to remember when setting the IP address on the
VersaMax Micro Ethernet module (IC200UEM001):

▪ When connecting via Ethernet point- to-point, a crossover


cable is required.

▪ IP address setting must be saved to the Flash on the


Ethernet module or it will be lost during power cycle.

▪ The second port of the Micro PLC must be configured for


Ethernet.

2
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

Settings are now complete. Verify that Port 2 matches above To download Ethernet drivers:
configuration by connecting to the Micro PLC serial port and
checking hardware configuration. 1 Open the PumpKIN Utility.

Downloading Ethernet Drivers


The Ethernet drivers for the Ethernet Option Module are
downloaded from https://www.emerson.com/Industrial-Automation- 2 If your current firmware version is 3.x, go to step 3.
Controls/support Files and passwords are: Otherwise go to step 2.1.
Upgrade Kit for Destination
Function 2.1 Click on Put File and select “geamxcupg_6104.rom” from
Release 3.3 Password
upgrade kit for release 3.3.
Emerson SRTP 82A1587-MS10-000-B1 G7
2.2 Enter password G5 (case sensitive, must be upper case G)
Modbus TCP 82A1588-MS10-000-B3 G7 in Remote file. For Remote host, enter the IP address of the
(Client and Server Micro PLC (for example: 10.10.0.2).
in single
firmware)*
Tunneling or Pass 82A1589-MS10-000-B1 G7
Thru**

* When the Ethernet option module is loaded with the Modbus


image it cannot communicate with PME.

**When the Tunneling image is loaded, the 175000 baud rate is


configurable only when the CPU Performance parameter is set
to High in Telnet Configurator. The CPU Performance parameter
is available in the Expert Setting menu.

Downloading is done using the PumpKIN utility, which is


included. To download a driver, perform the following procedure.
Only one driver can be present at one time. After the driver has
been downloaded you will have to reconfigure the port using
Telnet.

3
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

2.3 When the file is downloaded, the utility will respond with the 6 When the transfer is accomplished, go back to Telnet and
following, then go to step 3: configure the settings by following the procedure listed
under Setting the Permanent IP Address on page 2. Refer
to GFK-1645 for more information on configuration options.

7 Settings are now complete. Verify that Port 2 matches


above configuration by connecting to the Micro PLC serial
port and checking hardware configuration.

Security Settings
Note: This information replaces the “Security Settings for the
Ethernet Option Module” section in chapter 14 of
GFK-1645J and will be included in the next revision of
that manual.
Security settings are provided to prevent unauthorized access to
3 Click on Put File and Local file to be downloaded the Ethernet Option Module configuration mode.
(Modbus_TCP). Five security parameters are supported for the Ethernet Option
Module (firmware versions 3.3 and later).
4 Enter password G7 (case sensitive, must be upper case G)
Security settings are provided for the three protocols:
in Remote file. For Remote host, enter the IP address of
SNP/SRTP, Modbus TCP and Tunneling.
the Micro PLC (for example: 10.10.0.2).
These parameters allow you to configure the Telnet password,
enable the required ports and disable the unused ports

Note: We strongly recommend configuration of the Telnet


password and closing the unused ports. This will reduce
the exposure to security threats.
These ports are disabled by default. A port must be enabled if
the application needs a service associated with that port.
For firmware upgrade, the TFTP Download must be enabled.
For connection with Device Installer, Port 77FE must be enabled.
For use as web server the configuration for Web Server must be
enabled.
By default, Simple Network Management Protocol (SNMP) is
Disabled.
For Modbus TCP and SRTP protocols, these security settings
5 When the file is downloaded the utility will respond with the options are in the "Network/IP Settings" menu. For Tunneling
following: (Passthrough), these security settings are in "basic
parameters/server" menu.
The maximum password length is 16 characters. These
characters can be alphanumeric or special characters. The
password requires a minimum length of 8 characters.
A password set on a protocol’s firmware remains in effect if the
firmware is changed to that of a different protocol. For example,
if a password is set on Modbus TCP firmware and later the
firmware is changed to SNP/SRTP, the same password set on
Modbus TCP firmware will still apply.

4
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

Status LEDs
Link LED (Amber) Solid Amber: Connection to Micro Revision History
PLC established and network is IC200UEM001-AA Initial release. Compatible with
connected VersaMax Micro 64 firmware release
Activity (Green) Flashing Green when there is any 3.5 and PAC Machine Edition 5.5
activity on the network IC200UEM001-AB Improved noise immunity.
Status (Red) OFF: No errors IC200UEM001-BC Added support for Modbus/TCP
Red ON: Duplicate IP address present Client, enhanced data throughput
or network controller error (175,000bps), and 16-character
Red BLINK (2x/sec): No DHCP password security.
response or Setup menu active Firmware requirements:
Micro 20, 40 and 64 firmware
versions 3.83 and later
Ethernet Option Module firmware
Module Specifications versions 2.0 and later.
Processor Speed DSTni-EX CPU, 48MHz Programmer requirements:
Memory 256 kByte RAM, 512 kByte FLASH PAC Machine Edition Logic
Developer PLC, version 6.0 or
Connection Type RJ 45 10Base-T/100Base-TX Ethernet later.
Entity Type Client/Server
IC200UEM001-CC Labeling change. No changes to
Bus Speed 10/100Mbaud functions, features or compatibility.
Protocols SRTP (preloaded) IC200UEM001-CD Firmware release 3.3 addresses
Supported Modbus TCP Server and Client rare issue of the Ethernet Option
(optional) module stopping communication and
Tunneling (optional) not responding to commands. It also
adds new security settings in the
Number of ▪ Supports up to 8 Modbus TCP/IP Telnet interface.
Connections server channels.
Supported Programmer and Micro CPU
▪ If client configured, then 1 client
firmware requirements: same as
and 7 server channels supported.
version –BC.
▪ Supports 4 SRTP server channels
IC200UEM001-CE Firmware release 3.3.0.6 fixes issue
▪ Supports 1 connection for of Modbus TCP firmware upgrade
Tunneling with CD version of modules.
Mode Full Duplex IC200UEM001-CF Firmware release 3.3.0.7 fixes issue
of inconsistent Modbus
communication for different baud
rate settings.
IC200UEM001-DF Following Emerson’s acquisition of
this product, changes have been
made to apply appropriate branding
and registration of the product with
required certification agencies. No
changes to material, process, form,
fit or functionality.

Upgrades
All previous versions can be upgraded to this firmware version.
Once the module is upgraded to the 3.3 version, it will not
support downgrade to older revision. Attempting to downgrade
firmware may cause the module to fail permanently.
Note: To reduce the risk of this being accidentally or
maliciously used, to permanently disable the module,
Emerson strongly recommends that TFTP be disabled

5
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

by the user, and only enabled via (password-protected)


telnet when a firmware update is required.

Functional Compatibility
The default data rate with Ethernet option module firmware
version 2.0 is 175000 bps. Micro firmware versions below 3.83
do not support 175000 bps. If firmware version 2.0 is to be used
with Micro firmware versions prior to 3.83, the data rate on
Ethernet Option module should be changed to 38400 bps or
less, as per the requirement.

Problems Resolved by this Revision


The Firmware release 3.3.0.7 (IC200UEM001-CF) fixes issue of
inconsistent Modbus communication for different baud rate
settings. This firmware upgrade can be done on CD and earlier
versions of modules.

New Features and Enhancements in this


Revision
None

Telnet Configuration
Note: The Ethernet option module will be power cycled and reset
under the following conditions:
A connection to the Ethernet option module is established
through TELNET and disconnected immediately.
A connection to the Ethernet option module is established
through TELNET, the configuration is edited, and you press "Q"
(Quit without Save).

6
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

Port Number
Serial IO Configurable Parameters
The setting represents the source port number in TCP
Baud Rate
connections. It identifies the channel for remote initiating
The supported baud rates are 19200, 38400 and 175000. This connections. The range is 1-65535, except for the following.
baud rate should match the baud rate of the configuration
software. Port numbers Reserved for

I/F Mode (Interface Mode) 1-1024 Reserved (well known ports)


9999 TELNET Setup
The Interface (I/F) Mode is a bit-coded byte entered in
hexadecimal notation. 14000-14009 Reserved for Redirector
The following table displays available I/F Mode options: 30704 Reserved (77F0h)
Note: All bit positions in the table that are blank represent “don’t 30718 Reserved (77FEh)
care” bits for that particular option, which can be set to either a 0
or 1 value. Only RS-232C is supported and hence Bit 0 and Bit 1
always should be zeros. If you attempt to select an I/F Mode bit
Warning
that pertains to RS-422/485 settings, the WARNING: RS-
422/485 I/F Modes Not Supported” message displays. Do not use the reserved port numbers for this
setting because incorrect operation may result.
I/F Mode Option 7 6 5 4 3 2 1 0
RS-232C 0 0
7 Bit 1 0 Connect Mode
8 Bit 1 1 Connect Mode defines how the unit makes a connection, and
No Parity 0 0 how it reacts to incoming connections over the network.
Even Parity 1 1 Connect Mode Option 7 6 5 4 3 2 1 0
Odd Parity 0 1 a) Incoming Connection
1 Stop bit 0 1 Never accept Incoming 0 0 0
2 stop Bit 1 1 Always Accept 1 1 0
Common Interface Mode Settings b) Response
Common I/F Mode Setting Binary Hex Nothing (quiet) 0
RS-232C, 8-bit, No Parity, 1 0100 1100 4C Character response (C = 1
stop bit Connect,
RS-232C, 7-bit, Even Parity, 1 0111 1000 78 D= disconnect, N =
stop bit Unreachable)
c) Active Startup
Flow With any character 0 0 0 1
Flow control sets the local handshaking method for stopping
serial input/output. This should be set to zero always. Remote IP Address
This setting specifies the remote IP address through which the
communication needs to be established.
Remote Port
The setting represents the destination port number in TCP
connections. It is the number that identifies the channel for
remote initiating connections.
Note: See the reserved port numbers from the table specified in
Port Number section.
DisConn Mode: Set to zero.
FlushMode: Set to zero.
DisConnTime: Set to zero.
SendChar 1: Set to zero
SendChar 2: Set to zero.

7
GFK-2436K VersaMax Micro-20/40/64 PLC Ethernet Option Module
September 2019 IC200UEM001

Examples To change the Serial Parameter Settings in SRTP Protocol:


User entries are shown in bold. ▪ Connect PLC with IC200UEM001 on port2 in the Network.
To configure the Modbus/TCP Client in IC200UEM001 ▪ For this example, the current protocol is SRTP and serial
through TELNET: settings are 175000,8,O,1. The following procedure explains
▪ Connect PLC with IC200UEM001 on port2 in the Network. how to change the existing serial parameters to 38400,8,N,2
▪ For this example, the IP address of the IC200UEM001 is ▪ For this example, the IP address of the IC200UEM001 is
10.10.0.5 10.10.0.5
▪ Load the Ethernet Option Module firmware upgrade kit, ▪ Type TELNET 10.10.0.5 9999 at command prompt. Follow
82A1588-MS10-000-B1 the below procedure to configure the parameters of the
Ethernet Option Module.
▪ Type TELNET 10.10.0.5 9999 at command prompt.
Configure the parameters of the Ethernet Option Module as MAC address XXXXXXXXXXXX
follows: Software version 01.8 (090618) XPTEX
Modbus/TCP to RTU Bridge Press Enter to go into Setup Mode
MAC address XXXXXXXXXXXX VMSE Emerson SNP.
Software version 02.5 (090526) XCARD 1) Network/IP Settings:
Press Enter to go into Setup Mode IP Address .................... 10.10.0.5
Model: Device Server OEM (Firmware Code: G5) Default Gateway ……….10.10.0.1
Netmask ..............……...255.000.000.000
Modbus/TCP to RTU Bridge Setup
1) Network/IP Settings: 2) CH1 Serial & Protocol Settings:
IP Address .......................10.10.0.5 Protocol Mode ..............
Default Gateway ……… 10.10.0.1 Mode#1 SRTP Ethernet to Serial SNP Slave
Netmask .........................255.000.000.000 Serial Interface ....................175000,8,O,1
SNMP is enabled T1, Turn-Around Delay ...... 00002 msec
2) Serial & Mode Settings: T2, ACK/NAK Timeout ........ 09000 msec
Protocol ........................Modbus/RTU, Slave(s) attached T3, Link Idle Timeout .......... 10000 msec
Modbus/TCP Client. ….disabled T4, After Break Delay ......... 00400 msec
Serial Interface ........….38400,8,O,1 3) SNP ID to IP mapping table (not used in this mode)
4) Advanced Modbus Protocol settings: D)efault settings, S)ave, Q)uit without save
Slave Addr/Unit Id Source .. Modbus/TCP header Select Command or parameter set (1..3) to change: Press 2
Modbus Serial Broadcasts .. Disabled (Id=0 auto-mapped 2) CH1 Serial & Protocol Settings:
to 1) Mode#1 SRTP Ethernet to Serial SNP Slave
MB/TCP Exception Codes ..... Yes (return 00AH and 00BH) Mode#2 Serial SNP Master to Remote VMSE
Char, Message Timeout ...... 00050msec, 05000msec Select desired operating mode (1)
D)efault settings, S)ave, Q)uit without save
Enter serial parameters (175000,8,O,1): 38400,8,N,2
Select Command or parameter set (1..4) to change: Press 2. New T1, Line Turn-Around Delay (2-1280 msec, 1ms resolution)
Attached Device (1=Slave 2=Master) (1) Press Enter (2) Press Enter
Modbus/TCP Client Enabled (N) Y New T2, ACK/NAK Timeout (50-12,950 msec, 50ms resolution)
(9000) Press Enter
Close Idle TCP sockets after (3-60 sec, 0=leave open) (10)
Enter New T3, Link Idle Timeout (1000-60,000 msec, 250ms
resolution) (10000) Press Enter
Serial Protocol (1=Modbus/RTU 2=Modbus/ASCII) (1) Enter
New T4, After <BREAK> Delay (5-1280 msec, 5ms resolution)
Enter serial parameters (38400,8,O,1) 175000,8,O,1 (400) Press Enter

After configuring all the parameters, Telnet will display the


configured parameters. Press S to save the configuration to the After configuring all the parameters, Telnet will display the
Ethernet module. You will see the messages, Parameters configured parameters. Press S to save the configuration to the
saved, Restarting…. and then Connection to host lost. Ethernet module. You will see the messages, Parameters
saved, Restarting…. and then Connection to host lost.