Inverter Selection Guide
Inverter Selection Guide
INV-SG-FAP-202301
INV-SG-FAP-V.2
Fuji Electric, a renowned manufacturer of power electronics,
drive engineering and automation technology.
Content
Brand Promise Power and Function Selection
Through our pursuit of innovation in electric and
Application selection 03
thermal energy technology, we develop products that maximize
Power selection 04
energy efficiency and lead to a responsible and sustainable society
Functionality selection 05
Optional item selection 06
Peripheral devices & solution 07
Fuji Electric is a world leader in electronics manufacturing and energy
technology with more than 90 years of accumulated technology and
Inverter
experience. Through our innovation in energy and environment
technology, we are contributing to the creation of responsible and FVR-Micro 08
sustainable societies. FRENIC-Mini 09
FRENIC-eHVAC 10
Fuji Electric, the pioneer in the industry to develop general purpose FRENIC-Ace 11
Variable Speed Drive in 1976. Since then, the company continues to FRENIC-HVAC 12
design and develop an energy efficient low & medium voltage drives FRENIC-AQUA 13
and extensive increase it’s product line-up that suit to the industrial and FRENIC-MEGA (G2) 14
commercial needs. FRENIC-VG (unit type) 15
FRENIC-VG (stack type) 16
Fuji Electric Asia Pacific (Singapore) was established in 1989 as a
regional headquarter and sales company, provides innovative energy Harmonic Mitigation
technology products and solutions across the Southeast Asia, Oceania PWM Converter (unit type) 17
and Middle East, covering Singapore, Malaysia, Thailand, Indonesia, PWM Converter (stack type) 18
Philippines, Vietnam, Myanmar, Cambodia, Sri Lanka, Bangladesh, ecoWAVE Advance-Line PHF (50Hz) 19
Australia, New Zealand and Gulf Corporation Council. ecoWAVE Advance-Line PHF (60Hz) 20
ecoWAVE Econ-Line PHF (50Hz) 21
In this Selection Guide, you will find Fuji Electric’s Low Voltage Inverter ecoWAVE Econ-Line PHF (60Hz) 22
and their peripheral devices. ecoWAVE Advance-Line Skid Type (50Hz) 23
ecoWAVE Advance-Line Skid Type (60Hz) 24
IORA3000 Active Harmonic Filter 25
Operation Option
Optional keypad & Keypad accessories 26
Selection Guide DC Reactor 27
AC Reactor 28
Output Circuit Filter (OFL) 29
Get more information online. Optional Card
Speak to your local Fuji Electric. Relay Output Interface Card 30
Digital Interface Card 30
Analog Interface Card 31
Pulse Generator Feedback Card 32
Synchronized Interface Card 33
/
sia
v/a
Disclainer:
The information provided in this documentation contains general descriptions and/or function characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant
specific application or use thereof. Neither Fuji Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained
herein.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
Application selection
Specislized models can maximize the performance for each application
Representative Application
instrument image example e
Exhaust fan Fan
Pump
Fluid Blower
machine
Compressor
Gear pump
Drilling machine Drilling machine
Turning machine
Grinding machine
Machin e tool
Tool changer
Milling machine
Machining centre
Pressing Pressing machine
machine
Metal Winder
processing Wire drawing machine
machine
Shearing machine
Dicer
Hoist Elevator
crane
Escalator
Conveyor Multi-level storage
machine
(vertical) Multi-level parking lot
Crane
Hoist crane
Conveyor Conveyor transport
Conveyor
machine Chain transport
(horizontal)
Ball screw
Noodle making machine Noodle making machine
Motor
Inverter
Confectionery machine
Food Roller
(motor, inverter) Tea making machine
processing
machine Bread making machine
Mixer
Conveyor Cutting machine
(motor, inverter) (motor, inverter)
Slicer
Labeler Labeler
Inner packing machine
Packing and Outer packing machine
bookbinding
machine Bookbinding machine
Wrapping machine
Paper machine
Printing Winder
machine
Printing Slitter
machine O
Rotary printing machine
Treadmill Stair lift
Health, medical, Treadmill
welfare care
Care bed
instruments
Bubble bath
Commercial laundry machine Commercial laundry machine
Car washing machine
Food waste disposer
Others
Conveyor-belt sushi
Stage installation
Pachinko ball feeder
* Options may be required for application.
3
Power Selection
Select the right overload capability and control terminal to suit your application.
Digital Digital
input X output Y
terminal terminal
Motor capacity including Analog
Overload Analog Output
Inverter Series Input voltage class range +
capability FWD input output frequency range
[kW] /REV *1 *1
terminal Relay
output
e Three-phase 400V 0.75 to 280kW 120% for 1min. 7 3+2 3 2 0.1 to 120Hz
Single-phase 200V (HHD) 0.1 to 2.2kW 150% for 1min. 0.1 to 500Hz
Three-phase 400V 0.75 to 710kW 110% for 1min. 9 4+2 3 2 0.1 to 120Hz
Three-phase 400V (MD) 110 to 450kW 150% for 1min. 0.1 to 500Hz
Three-phase 200V (LD) 37 to 110kW
120% for 1min.
Three-phase 400V (LD) 37 to 710kW 11 4+2 3 3
Three-phase 400V (MD) 30 to 800kW
150% for 1min.
Stack Type
4
Auto-restart after momentary power failure
PID control
Torque limiter
3
4
2
2
Number of motor switching options
Hit-and-stop control
*2
5
Dancer roll control
Servo lock
Calendar function
Traceback function
*1 The behaviour of analog input and output can be switched by settings. Refer to the catalogue of each series.
Online tuning
Pump control
*3 The inverter trips when the output frequency upper limit of 599Hz is exceeded due to a review of export control regulations (frequency converter).
Functionality selection
Optional item selection
The optional item provide flexibility on interfacing and communication
Applicable Inverter
e
Control
option Analog Interface Card
card
PG Interface Card
RS-485 Communications Card Built-in Built-in Built-in Built-in*1 Built-in Built-in Built-in Built-in
Operation
Remote touch panel with USB
option
*1 The number of connectors of the RS-485 port can be changed from 1 to 2 by mounting an option card.
6
Peripheral devices & solution
The diagram shows the complete solution peripheral structure and option
Consult *1
PC Loader Software for Windows
[
Fuji Electric U V W
support communication with inverter [OPC-■
enable to set the function codes of the
Suppresses induced lightning surges from the X Y Z digital signals
inverter from a PC, to manage the data.
power source to protect entire equipment
Connection via
connected to the power source.
Mini-B USB [OPC-■
Only appliable for keypad
signals
TP-E1U, TP-E2 &
TP-A2SW
Used to reduce radio noise. Suppressive effect to the
[OPC-■ □
Consult
[ resistor, and capacitor.
Fuji Electric ■ -□□
Dedicated filter for RHC series
for highly frequent stopping A filter dedicated for RHC series, An attachment for mounting to IEC rail
● Used to reduce the input harmonic which is used when other electronic with a width of 35 mm
and large moment of inertia.
devices are connected to the same
power supply.
Consult
Fuji Electric
■ -□□
* Use this filter in combination with the
the connection terminal of dedicated filter reactor, filter condenser An attachment for taking the cooling
and filter resistor as a set.
fin of the inverter out of the board
* The series names (C2, E2, F2, G2, AR1, AQ1, VG1) are put in the place of ■ in the type names.
NOTE: Some accessories not feature in this selection guide, please consult your local Fuji Electric.
7
[AS1S] Simple Compact Inverter
Overview
It's small and strong. The design is held especially simple, so the user benefits from an easy installation and
smooth operations. Its conceptual design ensures saving space and energy, as well as costs.
FRENIC-Micro AS1S is a highly economic inverter for general purpose applications. It matches perfectly any
application with limited space and where small capacities are needed, such as e.g. conveyor transports, mixer
machines, or small woodworking machineries with basic functions.
Standard Frequency
type potentiometer
control
Features
o/
icr
m
r_
• Sink/source selectable
ric
ct
le
jie
Dimensions (External)
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
8
[C2] Compact Inverter For Simple Machine
Overview
With its rich functionality, compact design, simple operation and global compatibility, the new FRENIC-Mini C2
series elevates the performance of a wide range of devices and equipment which include conveyors, fans,
pumps, centrifugal separators and food processing machines. It enables system integration, energy efficiency,
reduced labour, lower overall costs and achieve competitiveness.
Synchronous
motor driving
Features
/
c2
i-
in
• Overload capability: 150% of rated current for 1min or 200% of rated current for 0.5s
-m
ic
n
re
Dimensions (External)
Power supply Standard Motor Dimensions (mm) Ingress
Inverter Model
voltage (kW) Protection
W H D
0.4 FRN0002C2 - 4A 158 W D
110 130
0.75 FRN0004C2 - 4A
1.5 FRN0005C2 - 4A
3-phase 2.2 FRN0007C2 - 4A 140 180 182
50/60Hz IP20
H
3.7 FRN0011C2 - 4A
Class
400 VAC 5.5 FRN0013C2 - 4A
180 230 158
7.5 FRN0018C2 - 4A
11 FRN0024C2 - 4A Low capacity
220 270 190
15 FRN0030C2 - 4A
0.1 FRN0001C2S - 2A
80
0.2 FRN0002C2S - 2A W D
80 120
0.4 FRN0004C2S - 2A 95
0.75 FRN0006C2S - 2A 120
200 VAC
5.5 FRN0025C2S - 2A
180 220 158
7.5 FRN0033C2S - 2A
11 FRN0047C2S - 2A
220 260 190
15 FRN0060C2S - 2A
0.1 FRN0001C2 - 7A High capacity
100
0.2 FRN0002C2 - 7A 80 120
1-phase
50/60Hz 0.4 FRN0004C2 - 7A 115
IP20
Class 0.75 FRN0006C2 - 7A 110 130 139
200 VAC
1.5 FRN0010C2 - 7A
140 180 182
2.2 FRN0012C2 - 7A
For more detail, please refer to model series catalog. S : Standard / E : EMC Filter
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
9
[F2E] Inverter for easy HVAC applications
Overview
Offers optimum capability in terms of energy saving for fans and pumps used in HVAC applications,
eliminates waste through appropriate flow rate and air flow adjustments, and greatly influences power
conservation and cost reductions through energy saving. An EMC filter is built-in as standard, catering to
a variety of environments. PM Motor drive with sensorless vector control is now possible. Unique functions
tailored to the application can be constructed.
Features
/
ac
hv
• Dedicated functionality for HVAC application: Fire mode for fan, built-in PID/Cascade operation for pump, etc.
_lv
es
riv
• Built-in category C2/C3 EMC filter as standard, catering for a variety of environments.
_d
ac
ts/
• Equipped with customized logic as standard to facilitate the free programming of up to 200 steps Unique
om
c.c
tri
• Equipped with BACnet communication protocol as standard to facilitate the productization of a variety of
ww
/w
s:/
Scan me or Click me
Dimensions (External)
W D
Power supply Standard Motor Dimensions (mm) Ingress
Inverter Model
voltage (kW) Protection
W H D
0.75 FRN0002F2E-4G 162
H
110 130
1.1 FRN0003F2E-4G 186
2.2 FRN0005F2E-4G
3 FRN0006F2E-4G 140 130 199 Low capacity
5.5 FRN0011F2E-4G W D
7.5 FRN0018F2E-4G
181.5 285 208 IP20
11 FRN0023F2E-4G
15 FRN0031F2E-4G
220 332 245
18.5 FRN0038F2E-4G
H
22 FRN0045F2E-4G
3-phase 250 400 195
30 FRN0060F2E-4G
50/60 Hz
Class 37 FRN0075F2E-4G
320 550 255
400 VAC 45 FRN0091F2E-4G Mid capacity
55 FRN0112F2E-4G 615 W D
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
10
[E2] High Performance Inverters
Overview
Inverter that produces excellent cost-performance, maintaining high performance through optimal design.
In this way, it can be applied to various machines and devices. The FRENIC-ACE is standard inverter for the next
generation and can be used in almost any type of application from fans and pumps to specialized machinery.
Whether it is simple logic functions or full-scale programming. It can be used for dedicated purposes such as wire
drawing machines, spinning machines and hoists with the appropriate programming templates.
Features
/
ce
c -a
• HHD - 150% of nominal current for 1min or 200% of nominal current for 0.5s
ac
ts/
uc
Dimensions (External)
Standard Motor
Standard Motor (kW) Dimensions (mm) Ingress Power supply Dimensions (mm) Ingress
Power supply Inverter Model (kW) Inverter Model
voltage Protection voltage Protection
HHD HND HD ND W H D HHD HND W H D
0.4 0.75 0.75 0.75 FRN0002E2 - 4GB 162 0.1 0.2 FRN0001E2 -2GB
110 85
0.75 1.1 1.1 1.5 FRN0004E2 - 4GB 186 0.2 0.4 FRN0002E2 -2GB
68 127
1.5 2.2 2.2 2.2 FRN0006E2 - 4GB 140 0.4 0.75 FRN0004E2 -2GB 100
2.2 3.0 3.0 3.0 FRN0007E2 - 4GB 140 199 0.75 1.1 FRN0006E2 -2GB 132
3.7 5.5 5.5 5.5 FRN0012E2 - 4GB 1.5 2.2 FRN0010E2 -2GB
3-phase 110
5.5 7.5 7.5 11 FRN0022E2 - 4GB 2.2 3.0 FRN0012E2 -2GB 130 143
1802 30 158 IP20 50/60 Hz
7.5 11 11 15 FRN0029E2 - 4GB 3.7 5.5 FRN0020E2 -2GB 140 IP20
Class
11 15 15 18.5 FRN0037E2 - 4GB 200 VAC 5.5 7.5 FRN0030E2S-2GB
220 270 190 180 220 158
15 18.5 18.5 22 FRN0044E2 - 4GB 7.5 11 FRN0040E2S-2GB
130
2.2 - - - FRN0011E2 - 7GB 140 143 Low capacity High capacity
For more detail, please refer to model series catalog. S : Standard / E : EMC Filter
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
11
[AR1] Inverter for HVAC Applications
Overview
Fuji Electric’s first slim type inverter dedicated for a variety of HVAC applications.
This series follows European trends and is keeping high Japanese reliability. Specific functions to manage
fan and compressor applications and new energy saving functions are installed as standard, positioning
FRENIC-HVAC as a high performance inverter on the HVAC and compressor market.
Optimized
minimum
power control
Features
c/
hva
ic-
• DCR and EMC filter built-in up to 90 kW. Built-in EMC filter for all capacities
ac
s/
ct
• Customizable Logic (mini PLC), 14 steps, manageable digital or analog signals with Real Time Clock (RTC)
du
ro
/p
om
Scan me or Click me
• 4 PID, Fire mode (forced operation), Password function
Dimensions (External)
Standard Dimensions (mm) Standard Dimensions (mm)
Power supply Ingress Power supply Ingress
Motor Inverter Model Motor Inverter Model
voltage Protection voltage D Protection
(kW) W H D (HP) W H
0.75 FRN0.75AR1 - 4A 1 FRN001AR1 - 2U
2 FRN002AR1 - 2U
1.5 FRN1.5AR1 - 4A 150 465
3 FRN003AR1 - 2U
2.2 FRN2.2AR1 - 4A 150 465 5 FRN005AR1 - 2U
262
3.7 FRN3.7AR1 - 4A 7 FRN007AR1 - 2U
FRN5.5AR1 - 4A 10 FRN010AR1 - 2U 585
5.5
3-phase 15 FRN015AR1 - 2U 203
7.5 FRN7.5AR1 - 4A 50/60 Hz 20 FRN020AR1 - 2U IP21/
Class 645 IP55
11 FRN11AR1 - 4A 262 25 FRN025AR1 - 2U
FRN15AR1 - 4A 200 VAC 30 FRN030AR1 - 2U
15 265 736 284
203 585 IP21/ 40 FRN040AR1 - 2U
18.5 FRN18.5AR1 - 4A IP55 50 FRN050AR1 - 2U
FRN22AR1 - 4A 300 885 367.9
22 60 FRN060AR1 - 2U
30 FRN30AR1 - 4A 75 FRN075AR1S - 2U
203 645 355 740 270
100 FRN100AR1S - 2U IP00
37 FRN37AR1 - 4A
125 FRN125AR1S - 2U 530 750 285
45 FRN45AR1 - 4A M : UL Type1 (IP21) / L : UL Type12 (IP55)
3-phase 265 736 284 America Model
50/60 Hz 55 FRN55AR1 - 4A
Class W D
75 FRN75AR1 - 4A
400 VAC 300 885 368
90 FRN90AR1 - 4A
110 FRN110AR1S - 4A
740 315
132 FRN132AR1S - 4A
H
530
160 FRN160AR1S - 4A
W D
200 FRN200AR1S - 4A
1000 360
220 FRN220AR1S - 4A
Low capacity
280 FRN280AR1S - 4A IP00 W D
315 FRN315AR1S - 4A 680
355 FRN355AR1S - 4A
1400 440
400 FRN400AR1S - 4A
H
630 FRN630AR1S - 4A
1000 1550 500
710 FRN710AR1S - 4A
For more detail, please refer to model series catalog. M :IP21 L :IP55
Mid capacity High capacity
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
12
[AQ1] Inverter for Special Pump Applications
Overview
The slim type inverter dedicated for a variety of applications of water supply and wastewater treatment
system from Fuji Electric. This series follows European trends keeping high Japanese reliability.
Specific functions to protect damage of pump systems and new energy saving functions are installed as
standard, positioning FRENIC-AQUA as a high performance inverter on the pumping application market.
Optimized Cascade
minimum control
power control
Features
/
ua
aq
• DCR and EMC filter built-in up to 90 kW. Built-in EMC filter for all capacities
v/
_l
es
riv
• Customizable Logic (mini PLC), 14 steps, manageable digital and analog signals with Real Time Clock (RTC)
_d
ac
s/
• 4 PID, Anti jam function, Pipe fill mode, Password function and Unit conversion function (kPa, bar, l/min, etc.)
ct
du
ro
/p
Dimensions (External)
Standard Dimensions (mm) W D
Power supply Ingress
Motor Inverter Model
voltage Protection
(kW) W H D
0.75 FRN0.75AQ1 - 4A
1.5 FRN1.5AQ1 - 4A
H
45 FRN45AQ1 - 4A
3-phase 265 736 284
50/60 Hz 55 FRN55AQ1 - 4A
Class 75 FRN75AQ1 - 4A
400 VAC 300 885 368
90 FRN90AQ1 - 4A Mid capacity
110 FRN110AQ1S - 4A W D
740 315
132 FRN132AQ1S - 4A
530
160 FRN160AQ1S - 4A
200 FRN200AQ1S - 4A
1000 360
220 FRN220AQ1S - 4A
280 FRN280AQ1S - 4A IP00
315 FRN315AQ1S - 4A 680
H
355 FRN355AQ1S - 4A
1400 440
400 FRN400AQ1S - 4A
500 FRN500AQ1S - 4A 880
630 FRN630AQ1S - 4A
1000 1550 500
710 FRN710AQ1S - 4A
For more detail, please refer to model series catalog. M :IP21 L :IP55 High capacity
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
13
[G2] High Performance Multifunctional Inverters
Overview
Inherits the excellent performance specifications and functionality of the G1 series while providing a more stylish
design. Unrelenting pursuit of performance and functionality to further enhance adaptability. The new
FRENIC-MEGA G2 series takes core capabilities, responsiveness, environmental awareness and easy
maintenance to the next level. It’s smarter, faster and resulting in significantly better efficiency.
Features
/
g2
ga
• Overload capability: 150% of rated current for 1min or 200% of rated current for 3.0s
me -
nic
/fre
• Built-in EMC filter for all capacities (compliant to EN 61800-3, category C3)
_d
/ac
cts
Scan me or Click me • Optional smart multi-function keypad TP-A2SW, enable battery backup, memory card and Bluetooth function.
Dimensions (External)
Standard Motor Dimensions (mm) Standard Motor Dimensions (mm)
Power supply Power supply
kW HP kW HP Inverter model IP kW HP kW HP Inverter model IP
voltage voltage
HHD HND W H D HHD HND W H D
0.4 1/2 - - FRN0002G2 -4G 130 0.4 1/2 - - FRN0003G2S-2G 130
110 110
0.75 1 - - FRN0003G2 -4G 0.75 1 - - FRN0005G2S-2G
1.5 2 - - FRN0004G2 -4G 1.5 2 - - FRN0008G2S-2G
260 145 260 145
2.2 3 - - FRN0006G2 -4G 150 2.2 3 - - FRN0011G2S-2G 150
3.7 5 - - FRN0009G2 -4G 3.7 5 - - FRN0018G2S-2G
IP20
5.5 7.5 7.5 10 FRN0018G2 -4G 5.5 7.5 7.5 10 FRN0032G2S-2G
7.5 10 11 15 FRN0023G2 -4G 220 7.5 10 11 15 FRN0046G2S-2G 220 IP20
3-phase
11 15 15 20 FRN0031G2 -4G 195 50/60 Hz 11 15 15 20 FRN0059G2S-2G 195
15 20 18.5 25 FRN0038G2 -4G Class 15 20 18.5 25 FRN0075G2S-2G
18.5 25 22 30 FRN0045G2 -4G 250 400 200 VAC 18.5 25 22 30 FRN0088G2S-2G 250 400
22 30 30 40 FRN0060G2 -4G 22 30 30 40 FRN0115G2S-2G
30 40 37 50 FRN0075G2 -4G 30 40 37 50 FRN0146G2S-2G 326.2 550 261.3
326.2 550 261.3
3-phase 37 50 45 60 FRN0091G2 -4G 37 50 45 60 FRN0180G2S-2G 615
50/60 Hz 45 60 55 75 FRN0112G2 -4G 615 45 60 55 75 FRN0215G2S-2G 361.2 740 276.3
Class
400 VAC 55 75 75 100 FRN0150G2 -4G 361.2 675 276.3 55 75 75 100 FRN0288G2S-2G IP00
75 100 90 125 FRN0180G2 -4G 75 100 90 125 FRN0346G2S-2G 535.8 750 291.3
90 125 110 150 FRN0216G2 -4G 740 90 125 110 150 FRN0432G2S-2G 686.4 880 366.3
535.8 321.3
110 150 132 200 FRN0260G2 -4G For more detail, please refer to model series catalog.
132 200 160 250 FRN0325G2 -4G
536.4 IP00
160 250 200 300 FRN0377G2 -4G
1000 366.3 W D
200 300 220 350 FRN0432G2 -4G
W D
220 350 280 400 FRN0520G2 -4G
686.4 W D
280 400 355 500 FRN0650G2 -4G
445.5
315 450 400 600 FRN0740G2 -4G
1400
355 500 500 700 FRN0960G2 -4G
886.4 446.3
H
H
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
14
Unit Type [VG1] High Performance Vector Control Inverter
Overview
Fuji Electric has concentrated its technologies to deliver the best-performing inverter on the market. In addition to its
basic performance, this model features the following great improvements: support for previously difficult applications
due to technical and capability limitations, easier and more user-friendly maintenance, as well as environmental
friendliness and safety. The FRENIC-VG series now proudly introduces the inverter as a unit type as well as a stack
type.
Features
/
vg
ic-
en
• Overload capability: 150% of rated current for 1min or 200% of rated current for 3.0s
/fr
_lv
es
• Strong: even though in hard environment such as sulfurizing gas, salty environments, dust, humidity, etc.
ts/
uc
d
• Flexible: IM (open and closed loop) and PMSM (open* and closed loop) control
ro
/p
mo
Dimensions (External)
Standard motor Motor Dimensions (mm)
Power supply Dimensions (mm) Ingress
(kW) Ingress Power supply (kW)
voltage Inverter Model Inverter Model Protection
Protection voltage
HD MD LD W H D HD LD W H D
3.7 - - FRN3.7VG1S-4E 0.75 - FRN0.75VG1S-4E
5.5 - - FRN5.5VG1S-4E 205 300 1.5 - FRN1.5VG1S-4E
7.5 - - FRN7.5VG1S-4E 2.2 - FRN2.2VG1S-4E
245 IP20 205 300
11 - - FRN11VG1S-4E 3.7 - FRN3.7VG1S-4E
15 - - FRN15VG1S-4E 5.5 - FRN5.5VG1S-4E
250 400
18.5 - - FRN18.5VG1S-4E 7.5 - FRN7.5VG1S-4E 245 IP20
22 - - FRN22VG1S-4E 11 - FRN11VG1S-4E
3-phase
30 - 37 FRN30VG1S-4E 50/60 Hz 15 - FRN15VG1S-4E
326.2 550 261.3 250 400
Class
37 - 45 FRN37VG1S-4E 18.5 - FRN18.5VG1S-4E
200 VAC
45 - 55 FRN45VG1S-4E 615 22 - FRN22VG1S-4E
3-phase
50/60 Hz 55 - 75 FRN55VG1S-4E 361.2 675 276.3 30 37 FRN30VG1S-4E 326.2 550 261.3
Class
75 - 90 FRN75VG1S-4E 37 45 FRN37VG1S-4E 615
400 VAC
90 110 110 FRN90VG1S-4E 740 45 55 FRN45VG1S-4E 361.2 276.3
321.3 740 IP00
110 132 132 FRN110VG1S-4E 55 75 FRN55VG1S-4E
536.4
130 160 160 FRN132VG1S-4E 75 90 FRN75VG1S-4E 535.8 750 291.3
160 200 200 FRN160VG1S-4E 90 110 FRN90VG1S-4E 686.4 800 366.3
1000 366.3 IP00
200 220 220 FRN200VG1S-4E D
W
220 - 280 FRN220VG1S-4E
686.4
280 315 355 FRN280VG1S-4E
445.5 W D
315 355 400 FRN315VG1S-4E
1400
355 400 450 FRN355VG1S-4E
886.4 446.3
H
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
15
Stack Type [SVG1] High Performance Vector Control Inverter
Overview
Fuji Electric has concentrated its technologies to deliver the best-performing inverter on the market. In addition to its
basic performance, this model features the following great improvements: support for previously difficult applications
due to technical and capability limitations, easier and more user-friendly maintenance, as well as environmental
friendliness and safety. The FRENIC-VG series now proudly introduces the inverter as a unit type as well as a stack
type.
Features
/
vg
ic-
en
• Overload capability: 150% of rated current for 1min or 200% of rated current for 3.0s
/fr
_lv
es
• Strong: even though in hard environment such as sulfurizing gas, salty environments, dust, humidity, etc.
ts/
uc
d
• Flexible: IM (open and closed loop) and PMSM (open* and closed loop) control
ro
/p
mo
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
16
PWM CONVERTER Unit Type High Performance Converter
Overview
FRENIC-eRHC, RHC & RHR series (Unit Type)
FRENIC-eRHC & RHC series acts as an Active Front End when used together with an inverter, in which the
input current is changed to a sinusoidal wave to significantly suppress the harmonic current enable meeting
IEEE 519 standard. On the other hand, the regenerated energy is returned to the power source, promotes
energy saving. The FRENIC-RHR only specify for regenerative.
IEEE 519
Features
Applied Guideline for Suppressing Harmonics
/
sia
v/a
PWM control reduces harmonics current significantly, due to sinusoidal wave at power supply side. According to
s_l
rive
"Guideline for Suppressing Harmonics by the Users Who Receive High Voltage or Special High Voltage" issued
c_d
ts/a
by the Ministry of Economy, Trade and Industry, the converter factor (Ki) can be set to "0" (meaning harmonics
duc
/pro
occurrence is 0) when combining with the inverter. Thus meeting harmonic mitigation, IEEE 519 Standard.
om
c.c
ctri
iele
Its power-factor control realizes the same phase current as the power-supply phase-voltage. The equipment,
s://
http
thus, can be operated with the power-factor of almost "1." This makes it possible to reduce the power
Scan me or Click me
transformer capacity and downsize the other devices, compared with those required without the converter.
Upgraded braking performance
Regenerated energy occurring at highly frequent accelerating and decelerating operation and elevating machine
operation is entirely returned to power supply side. Thus, energy saving during regenerative operation is
possible. As the current waveform is sinusoidal during regenerative operation, no troubles are caused to the
power supply system.
Capacity [kW]
Series Voltage
5.5 22 75
200 V series 30 to 90 kW
Harmonic Suppression &
Regenerative converter 400 V series 45 to 630 kW
Capacity [kW]
Series Voltage
5.5 22 75
Applicable inverter:
CCopyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
17
PWM CONVERTER Stack Type High Performance Converter
RHC-D Series
Converter Stack Type
RHC-D series is the active front-end of Fuji Electric in stack type configuration.
All advantages of RHC-C series but in stack type are:
• Rating available in MD and LD
• A capacity range from 132 kW to 3 MW
• Two configurations available: - Standard stack / Phase stack
• Able to work with isolated and non-isolated transformers
• SiC Technology
• 400 VAC, 690 VAC series
RHF-D Series
Filter Stack Type
RHF series is the compact solution and dedicated filter for the PWM converter (RHC-D) in stack type.
Charging circuit, harmonic filter and boosting reaction all in one.
• Rating available in MD and LD
• A capacity range from 160 kW to 1.36 MW
• Two configurations available: Standard stack / Phase stack
• 400 VAC, 690 VAC series
RHD-D series
Diode Rectifier Stack Type
• 6 pulse drive
• Harmonic mitigation: Sinusoidal - Wave Regenerative Header, 12 pluses layout, etc.
• 400 VAC, 690 VAC series
IEEE 519
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
18
(AL1M-4G5) (50Hz Type) Advance-Line Passive Harmonic Filter
Overview
ecoWAVE Advance-Line Passive Harmonic Filters represent an economical solution
to the challenge of load-applied harmonics mitigation in three-phase power systems. Achieve 5%*
It increases the reliability and service life of electric installations, help utilize electric THDi
system the key to meet power quality standards such as IEEE 519.
Guarantee result with Fuji Electric inverter.
* Achieve 5% THDi for diode rectifier without DC-link choke and thyristor rectifier.
IEEE 519 ≤ 5%
THDi
Standard Harmonic ≤ 5% THDi Improve
type mitigation at rating Power
Factor
TDJ
Module
Features
/
l1m
e-a
• Overload capability of 1.6x rated current for 1 minute, once per hour.
tio
iga
mit
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal Outside dimensions (mm)
Rated
applied motor Filter
Voltage
Frame
[kW] *** W H D
0.75 FN0.75AL1M-4G5 *
1.5 FN1.5AL1M-4G5 * 160 360 185 Size
D
2.2 FN2.2AL1M-4G5 *
3.7 FN3.7AL1M-4G5 * 180 425 206
5.5 FN5.5AL1M-4G5 *
210 483 221 W
7.5 FN7.5AL1M-4G5 *
11 FN11AL1M-4G5
15 FN15AL1M-4G5 260 560 252
18.5 FN18.5AL1M-4G5
22 FN22AL1M-4G5
50Hz 30 FN30AL1M-4G5
3-Phase H
37 FN37AL1M-4G5 290 750 319
380-415V
45 FN45AL1M-4G5
Class
55 FN55AL1M-4G5
75 FN75AL1M-4G5
353 960 386
90 FN90AL1M-4G5
D
110 FN110AL1M-4G5
132 FN132AL1M-4G5 **
462 1150 456
160 FN160AL1M-4G5 **
200 FN200AL1M-4G5 **
250 FN250AL1M-4G5 ** 550 1400 555
* Filter rating which does not require forced cooling or fan module.
** Filter rating which does not require RC damping module for rectifiers with EMI filter.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
19
(AL1M) (60Hz Type) Advance-Line Passive Harmonic Filter
Overview
ecoWAVE Advance-Line Passive Harmonic Filters represent an economical solution
to the challenge of load-applied harmonics mitigation in three-phase power systems. Achieve 5%*
It increases the reliability and service life of electric installations, help utilize electric THDi
system the key to meet power quality standards such as IEEE 519.
Guarantee result with Fuji Electric inverter.
* Achieve 5% THDi for diode rectifier without DC-link choke and thyristor rectifier.
IEEE 519 ≤ 5%
THDi
Standard Harmonic ≤ 5% THDi Improve
type mitigation at rating Power
Factor
TDJ
Module
Features
/
l1m
e-a
• Overload capability of 1.6x rated current for 1 minute, once per hour.
tio
iga
mit
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal*** Outside dimensions (mm)
Rated
applied motor Filter
Voltage
Frame
[kW] [HP] W H D
0.75 1 FN0.75AL1M-4G6 *
1.5 2 FN1.5AL1M-4G6 * 160 360 185 Size
D
2.2 3 FN2.2AL1M-4G6 *
3.7 5 FN3.7AL1M-4G6 *
180 425 206
5.5 71/2 FN5.5AL1M-4G6 *
W
7.5 10 FN7.5AL1M-4G6 *
210 483 221
11 15 FN11AL1M-4G6
15 20 FN15AL1M-4G6
18.5 25 FN18.5AL1M-4G6 260 560 252
60Hz 22 30 FN22AL1M-4G6
3-Phase
30 40 FN30AL1M-4G6
440-480V
Class 37 50 FN37AL1M-4G6 290 750 319 H
45 60 FN45AL1M-4G6
55 75 FN55AL1M-4G6
340 752 434
75 100 FN75AL1M-4G6
90 125 FN90AL1M-4G6
353 960 386 D
110 150 FN110AL1M-4G6
132 200 FN132AL1M-4G6 **
160 250 FN160AL1M-4G6 ** 462 1150 456
220 300 FN220AL1M-4G6 **
* Filter rating which does not require forced cooling or fan module.
** Filter rating which does not require RC damping module for rectifiers with EMI filter.
Motor drive input current without harmonic filter.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
20
(EL1M) (50Hz Type) Econ-Line Passive Harmonic Filter
Overview
ecoWAVE Econ-Line Passive Harmonic Filters represent an economical solution to
the challenge of load-applied harmonics mitigation in three-phase power systems.
It increases the reliability and service life of electric installations, help utilize electric
Achieve 10%*
system, the key to meet power quality standards such as IEEE 519. THDi
Guarantee result* with Fuji Electric inverter.
* Inverter must incorporate with its DC Reactor. * Achieve 10% THDi for diode rectifier with DC-link choke and thyristor rectifier.
Features
/
l1m
-e
ve
• Overload capability of 1.6x rated current for 1 minute, once per hour.
atio
itig
ic-m
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal** Outside dimensions (mm)
Rated
applied motor Filter*
Voltage
[kW] W H D
0.75 -
1.5 - - - -
2.2 - D
3.7 FN3.7EL1M-4G5 *
5.5 FN5.5EL1M-4G5 * 185 390 190
7.5 FN7.5EL1M-4G5 * W
11 FN11EL1M-4G5
15 FN15EL1M-4G5 250
455 230
50Hz 18.5 FN18.5EL1M-4G5
3-Phase
22 FN22EL1M-4G5
380-415V
Class 30 FN30EL1M-4G5
520 H
37 FN37EL1M-4G5 280
248
45 FN45EL1M-4G5
580
55 FN55EL1M-4G5
75 FN75EL1M-4G5
90 FN90EL1M-4G5
W D
110 FN110EL1M-4G5 450 700 385
132 FN132EL1M-4G5
160 FN160EL1M-4G5
* Filter to be selected by system voltage and load (motor drive) power. Note: the harmonic filter will reduce RMS input current.
Therefore, filter selection by current rating, as it is common for EMC/EMI filters, is not recommended.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
21
(EL1M) (60Hz Type) Econ-Line Passive Harmonic Filter
Overview
ecoWAVE Econ-Line Passive Harmonic Filters represent an economical solution to
the challenge of load-applied harmonics mitigation in three-phase power systems.
It increases the reliability and service life of electric installations, help utilize electric
Achieve 10%*
system, the key to meet power quality standards such as IEEE 519. THDi
Guarantee result* with Fuji Electric inverter.
* Inverter must incorporate with its DC Reactor. * Achieve 10% THDi for diode rectifier with DC-link choke and thyristor rectifier.
Features
/
l1m
e-e
• Overload capability of 1.6x rated current for 1 minute, once per hour.
tio
iga
mit
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal** Outside dimensions (mm)
Rated
applied motor Filter*
Voltage
[kW] [HP] W H D
0.75 1 -
1.5 2 - - - -
2.2 3 - D
3.7 5 FN3.7EL1M-4G6 *
5.5 71/2 FN5.5EL1M-4G6 * 185 390 190
7.5 10 FN7.5EL1M-4G6 * W
11 15 FN11EL1M-4G6
15 20 FN15EL1M-4G6 250
455 230
50Hz 18.5 25 FN18.5EL1M-4G6
3-Phase
22 30 FN22EL1M-4G6
380-480V
Class 30 40 FN30EL1M-4G6
520 H
37 50 FN37EL1M-4G6 280
248
45 60 FN45EL1M-4G6
580
55 75 FN55EL1M-4G6
75 100 FN75EL1M-4G6
90 125 FN90EL1M-4G6
W D
110 150 FN110EL1M-4G6 450 700 385
132 200 FN132EL1M-4G6
160 250 FN160EL1M-4G6
* Filter to be selected by system voltage and load (motor drive) power. Note: the harmonic filter will reduce RMS input current.
Therefore, filter selection by current rating, as it is common for EMC/EMI filters, is not recommended.
** In case of filter accurate rating, please refer to Horsepower (HP) rating.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
22
(AL1M) (Engineering Filter - 50Hz Type) Advance-Line Passive Harmonic Filter
Overview
ecoWAVE Advance-Line Passive Harmonic Filters is a skid type engineering filter
solution to challenge larger load harmonics mitigation in three-phase power systems. Achieve 5%*
It increases the reliability and service life of electric installations, help utilize electric THDi
system, the key to meet power quality standards such as IEEE 519.
Guarantee result with Fuji Electric inverter.
* Achieve 5% THDi for diode rectifier without DC-link choke and thyristor rectifier.
IEEE 519 ≤ 5%
THDi
Engineering Harmonic ≤ 5% THDi Improve
type mitigation at rating Power
Factor
TDJ
Module
Features
/
l1s
e-a
av
• Overload capability of 1.6x rated current for 1 minute, once per hour.
iga
mit
ic-
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal Outside dimensions (mm)
Rated
applied motor Filter
Voltage
[kW] *** W H D
250 FN250AL1S-4G5
890
50Hz 315 FN315AL1S-4G5 505
3-Phase 355 FN355AL1S-4G5 1060 1120
380-415V
400 FN400AL1S-4G5 890
Class 557
500 FN500AL1S-4G5 1060
*** Motor drive input current without harmonic filter.
NOTE: Enclosure ventilation fan is required for these engineering filter.
Recommended installation on top of cabinet.
DCR
W D
* consult your local Fuji Electric for more informations. Example of inverter panel integrated with the engineering filter.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
23
(AL1M) (Engineering Filter - 60Hz Type) Advance-Line Passive Harmonic Filter
Overview
ecoWAVE Advance-Line Passive Harmonic Filters is a skid type engineering filter
solution to challenge larger load harmonics mitigation in three-phase power systems. Achieve 5%*
It increases the reliability and service life of electric installations, help utilize electric THDi
system, the key to meet power quality standards such as IEEE 519.
Guarantee result with Fuji Electric inverter.
* Achieve 5% THDi for diode rectifier without DC-link choke and thyristor rectifier.
IEEE 519 ≤ 5%
THDi
Engineering Harmonic ≤ 5% THDi Improve
type mitigation at rating Power
Factor
MCCB
Features
/
l1s
e-a
av
• Overload capability of 1.6x rated current for 1 minute, once per hour.
tio
iga
mit
• Mean Time Between Failures (MTBF) 45°C/415 V (Mil-HB- 217F) at >200,000 hours
ps
htt
Dimensions (External)
Nominal Outside dimensions (mm)
Rated
applied motor Filter
Voltage
[kW] *** W H D
260/350 FN260AL1S-4G6
890
60Hz 300/400 FN300AL1S-4G6 1120 505
3-Phase
335/450 FN335AL1S-4G6 1060
380-415V
Class 370/500 FN370AL1S-4G6 890
1320 557
450/600 FN450AL1S-4G6 1060
*** Motor drive input current without harmonic filter
NOTE: Enclosure ventilation fan is required for these engineering filter.
Recommended installation on top of cabinet.
DCR
W D
* consult your local Fuji Electric for more informations. Example of inverter panel integrated with the engineering filter.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
24
IORA 3000 Active Harmonic Filter
Overview
IORA 3000 Active Harmonic Filter measures the level of current harmonics in the supply
line and eliminates it by generating counter harmonics in real time, using state of the art
Achieve Below
technology. It is available in ratings up to 600 Amps, the highest in the world. A higher 5%*
attenuation of up to 96% of individual harmonics is possible. It employs high speed THDi
IGBTs in the power circuit and offers PF compensation, both leading and lagging.
It helps in complying with IEEE 519 power quality standard.
IEEE 519 ≤ 5%
THDi
Standard Harmonic ≤ 5% THDi Improve
type mitigation at rating Power
Factor
MCCB
Circuit breaker
disconnector
Features
0/
00
a3
• Applicable Industry standard for 6-pulse rectifier & inverter and all system harmonic.
on
rm
/ha
• Deliver result actively and maintain target THDi even at partial load performance.
cts
du
pro
Scan me or Click me • Selective harmonic elimination methods. CT can be connected in load as well as in source.
• Works up to 690 VAC (Optional).
• Ethernet based Remote monitoring and 7 inch SVGA touch screen display.
• Internal CANopen communication.
• Employs high speed IGBTs in power circuit.
• Closed loop active filter with source current sensing.
• High attenuation up to 96% of individual harmonics.
• Programmable selective harmonic elimination.
• PF compensation, leading as well as lagging.
• Load balancing.
• Helps in achieving the compliance with power quality regulations like IEEE 519 standard.
• IEC/EN 62040-2 category C3.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
25
Operation Options
Optional Keypad
TP-E1
Type: 7 segment LED
Applicable inverter:
Optional keypad enable external mounting on panel, inverter body mounting is unable.
The remote control extension cable is required.
TP-E1U
Type: 7 segment LED, USB (mini-B)
Applicable inverter:
Optional keypad enables external mounting on panel, inverter body mounting is unable.
The remote control extension cable is required.
TP-E2
Type: 7 segment LED, USB (mini-B)
Applicable inverter:
TP-A1-E2C
Type: Multi-functional HMI LCD display complete with up/down/right/left cursor key.
Applicable inverter:
Optional keypad enables external mounting on panel, inverter body mounting is unable.
The remote control extension cable is required.
TP-A2SW
Type: Multi-functional HMI LCD display complete with up/down/right/left cursor key. Equipped with USB (mini-B)
Applicable inverter:
Support
Optional keypad enable inverter body mount or panel mount.
In case of panel mount, the remote control extension cable is required. Mobile Loader
CB- S
Type: RS-485 communication cable for keypad remote control extension, equipped with RJ-45 connector.
Applicable inverter:
Optional remote control extension cable for keypad external mounting on panel.
Cable come in 1m, 3m and 5m. Model: CB-1S, CB-3S and CB-5S.
CTP-A1
Type: IP55 Keypad mounting kit
Applicable Keypad:
TP-E2 TP-A1-E2C TP-A2SW
TP-A1 (FRENIC-HVAC / AQUA standard keypad)
Optional IP55 Keypad mounting kit for keypad external mounting on panel.
Consult your local Fuji Electric for more detail.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
26
Operation Options
DC Reactor
DCR4
Type: DC Reactor
Applicable inverter:
220 DCR4-220C 350 190 146 It is necessary to include the optional DC Reactor for inverter 75kW and above
rating as a standard accessory unless the inverter come with or built-in DC Reactor
250 DCR4-250C 350 190 161 (eg. FRENIC-HVAC/AQUA)
280 DCR4-280C 350 190 161
315 DCR4-315C 400 225 146
355 DCR4-355C 400 225 156
400 DCR4-400C 445 245 145
450 DCR4-450C 440 245 150
500 DCR4-500C 445 245 165
560 DCR4-560C 270 480 203
630 DCR4-630C 285 480 203
710 DCR4-710C 340 480 295
Selectable type B or type C reactor.
Input power factor of DCR2/4-□□/□□A/□□B; about 90 to 95%
Compliant with IEC/EN 61000-3-2 & IEC/EN 61000-3-12.
Input power factor of DCR2/4-□□C: about 86 to 90%
It is necessary to include the optional DC Reactor for inverter 75kW and above
rating as a standard accessory unless the inverter come with or built-in DC Reactor
(eg. FRENIC-HVAC/AQUA)
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
27
Operation Options
AC Reactor
ACR □ - □□□
Type: AC Reactor
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
28
Operation Options
Dimensions and other detail please refer to Catalog or consult Fuji Electric.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
29
Operation Options
OPC-F1-RY
Type: Relay output: Built-in 3 circuits
Applicable inverter:
OPC-RY
Type: Relay output: Built-in 2 circuits If you attach 2 interface cards, 4 relay outputs are possible.
Applicable inverter:
OPC-RY2
Type: Relay output: Up to 7 circuits
Applicable inverter:
OPC-DIO
Type: Digital Input/Output Interface Card
Applicable inverter:
Optional Digital Input/Output Interface Card enable monitor the output frequency by binary code (8bit).
General-purpose input/output terminals can be expanded.
OPC-VG1-DIO
Type: Digital Input/Output Interface Card
Applicable inverter:
Optional Digital Input/Output Interface Card enable monitor the output frequency.
Come with DI/DO=16/10 points of I/O can be added.
OPC-DI
Type: Digital Input Interface Card
Applicable inverter:
Optional Digital Input Interface Card enable general-purpose input terminal expansion.
Come with set the frequency by binary code (8, 12, 15, 16bit) and BCD code (4 digits).
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
30
Operation Options
Continue...
OPC-VG1-DI
Type: Digital Input Interface Card
Applicable inverter:
Optional Digital Input Interface Card enable input speed setting, torque command, torque current command,
torque limit, etc. in 16bit digital quantity.
OPC-DO
Type: Digital Output Interface Card
Applicable inverter:
Optional Digital Output Interface Card enable monitor frequency, output voltage, output current, etc.
by binary code (8bit). The general-purpose output terminal can be expanded.
OPC-AIO
Type: Analog Input/Output Interface Card
Applicable inverter:
Monitor output:
0 to ±10Vdc Analog voltmeter (input impedance: 10kΩ) can be connected up to 2 pieces.
4~20mADC Applicable load 500Ω or less
OPC-VG1-AIO
Type: Analog Input/Output Interface Card
Applicable inverter:
Optional Analog Input/Output Interface Card enable at most AI/AO=2/2 points of I/O can be added.
OPC-AO
Type: Analog Output Interface Card
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
31
Operation Options
Speed control (vector control with PG) 20 to 3000P/R A/B/Z phases +12Vdc±10%/120mA or less
OPC-PG Pulse train input (incremental mental) Open collector/ +15Vdc±10%/120mA or less
Complement input method
OPC-E2-PG OPC-E2-PG3
Type: Pulse Generator Feedback Card enable feedback signal of the encoder for speed and position control.
Applicable inverter:
Speed control (vector control with PG, 20 to 3000P/R A/B/Z phases +5V: 200mA max, +5V±10%
OPC-E2-PG V/f control, torque vector control with PG) (incremental mental) Open collector/
pulse train input Synchronous operation Complement
Simple positioning control Input method 5V
Speed control (vector control with PG, 20 to 3000P/R A/B/Z phases +12V: 80mA max, +12V±10%
V/f control, torque vector control with PG) (incremental mental) Open collector/ +15V: 60mA max, +15V±10%
OPC-E2-PG3
pulse train input Synchronous operation Complement
Simple positioning control Input method 12V/15V
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
32
Operation Options
Continue...
Motor speed detection A, B phase 90° phase difference 2 signals DC+5V±5%/250mA or less
Line speed detection A phase; command pulse,
Pulse detection B phase; command code
OPC-VG1-PG
Pulse command input Phase A: Forward pulse,
Phase B: Reverse pulse
5V line driver method
Motor speed detection A, B phase 90° phase difference 2 signals DC+5V±5%/250mA or less
Line speed detection A phase; command pulse,
OPC-VG1-PGo Pulse detection B phase; command code
Pulse command input Phase A: Forward pulse,
Phase B: Reverse pulse
Open collector/voltage output method
For 17-bit serial PG A/B phase signal output (FA+/-, FB+/-) DC+5V±5%/70mA or less
OPC-VG1-SPGT Synchronous motor operation 5V line driver method
(speed control)
Optional Synchronized Interface Card is used for position control with a synchro oscillator, and can convert
the synchro oscillator signal to 0 to ±10V.
Optional Encoder cable for GNF2 Motor connecting the inverter and our sensor-equipped synchronous
motor "GNF2". Straight type and right angle type. There are four types of 5m, 15m, 30m, and 50m.
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
33
Operation Options
OPC-TL
Type: T-link communication card
Applicable inverter:
OPC-VG1-TL
Type: T-link communication card
Applicable inverter:
OPC-SX
Type: SX bus communication card
Applicable inverter:
OPC-VG1-SX
Type: SX bus communication card
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
34
Operation Options
Continue...
OPC-VG1-ESX
Type: E-SX Bus Communication Card
Applicable inverter:
OPC- -PDP OPC- -DEV OPC- -COP OPC- -CCL OPC- -LNW OPC- -PNET
Type: T-link communication card
OPC-PRT
Type: Multiprotocol Ethernet interface Communication Card
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
35
Operation Options
Continue...
OPC-PRT2
Type: PROFINET IO Interface Communication Card
Applicable inverter:
OPC-PRT3
Type: PROFINET IO Interface Communication Card
Applicable inverter:
OPC-E2-RS
Type: RS-485 Communication Card
Applicable inverter:
OPC-PT
Type: Resistance Temperature Sensor Input Card (aka. PT-100 temperature sensor input card)
Applicable inverter:
OPC-VG1-UPAC
Type: User Prorgramming Card
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
36
Operation Options
Continue...
OPC-VG1-SAFE
Type: Functional Safety Card (aka. STO: Safe Torque Off)
Applicable inverter:
FRENICeHVAC:
FRN0002F2E-4G to FRN0038F2E-4G:OPC-E2-ADP1
FRN0045F2E-4G to FRN0060F2E-4G:OPC-E2-ADP2
FRN0075F2E-4G to FRN0520F2E-4G:OPC-E2-ADP3
Loader Software
The VG1 inverter needs this FRENIC Loader software to communicate via PC.
WPS-VG1-PCL
Type: Loader Software
Applicable inverter:
CB-VG1-UPAC-3S
Type: UPAC Dedicated Connection Cable between FRENIC-VG1 inverter (connector) and PC (RJ-45).
Applicable inverter:
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
37
FRENIC Series
Operation Options
各種同期モータ (参考)
Battery For Memory Backup
Battery to power inverter real time clock memory.
次世代同期ドライブシステムで省エネを。
OPK-BP
同期モータとは, 回転子(ロータ) に永久磁石
Type: Battery(Permanent
for memory backup を内蔵。
Magnet)
また, インダクションモータと違い, 永久磁石により磁束を発生し二次電流が流れないため,
Applicable inverter: 損失が大幅に低減し高効率化が実現いたします。
これからは, 同期モータ(永久磁石内蔵形) とインバータFRENIC-MEGA(G2 Series)の組合せで従来から幅広く使われているインダクション
在庫機種 e
400V級 出力5.5∼90kW・6P , 1800min -1
1 4 8, 14
Note: Wire type is 600V HIV insulated wire (75°C tolerance). Please follow above content.
高効率形 センサレス
モータ効率IE4(スーパ−プレミアム効率)と同等レベル , またインダクション
モータと取付寸法同一ながら軽量化を実現。スムーズな置き換えが可能。
在庫機種
400V級 出力75 , 90kW・6P , 1800min -1
超高効率形 センサレス
モータ効率IE4(スーパープレミアム効率)
レベルより約1.0%UP , またインダク
ションモータと同枠設計により取付寸法同一でスムーズな置き換えが可能。
本シリーズは , 全て受注生産品となります。
Copyright © 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
12 38
Inverter Migration Table (upgrade or replacement for obsolete model)
Enjoy the performance of your last Fuji Electric Inverter?
Refer to above migration guideline* for upgrade or replacement of your obsolete inverter. Data Dated 2022/Dec
Discontinuation Discontinued Substitute Model
Inverter Series Release date Remarks
date (+7 years)** (current model)
FVR-F 1980/11 (1982/07) 1989/07 FRENIC-Ace (FRN-E2)
FRENIC5000P 1981/11 (1983/02) 1990/02 FREN IC -M EGA (FRN -G1( )LD Mode) Format: RKNNP
FRENIC5000G 1981/12 (1983/02) 1990/02 FRENIC-MEGA (FRN-G1) Format: RKNNG
FVR-P 1982/07 (1983/02) 1990/02 FREN IC -M EGA (FRN -G1( )LD Mode)
FVR-G 1982/10 (1983/12) 1990/12 FRENIC-MEGA (FRN-G1)
FVR-P2 1983/02 (1984/03) 1991/03 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000G2 1983/02 (1984/03) 1991/03 FRENIC-MEGA (FRN-G1)
FRENIC5000P2 1983/02 (1984/03) 1991/03 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000H 1983/09 (1986/03) 1993/03 FRENIC-HF (FRN-H1)
FVR-G2 1983/12 (1986/01) 1993/01 FRENIC-MEGA (FRN-G1)
FVR-P3 1984/03 1985/04 1992/04 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000G3 1984/03 (1987/02) 1994/02 FRENIC-MEGA (FRN-G1)
FRENIC5000P3 1984/03 (1987/02) 1994/02 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000V2 1983/12 1995/03 2002/03 Please consult Fuji Electric
FRENIC5000M2 1986/04 1995/03 2002/03 Please consult Fuji Electric
FRENIC5000VG 1986/07 1995/03 2002/03 FRENIC-VG (FRN-VG1)
FVR-G5 1986/01 1987/12 1994/12 FRENIC-MEGA (FRN-G1)
FVR-P5 1987/02 1987/12 1994/12 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000G5 1986/09 1990/07 1997/07 FRENIC-MEGA (FRN-G1)
FRENIC5000P5 1986/09 1990/07 1997/07 FREN IC -M EGA (FRN -G1( )LD Mode)
FVR-G5E 1986/01 1993/09 2000/09 FRENIC-MEGA (FRN-G1)
FVR-G5B 1986/03 1993/09 2000/09 FRENIC-MEGA (FRN-G1)
FVR-K5 1987/08 1993/09 2000/09 FREN IC -M i n( i FRN -C 2 )
FVR-G5S 1987/12 1993/09 2000/09 FRENIC-MEGA (FRN-G1)
FVR-P5S 1987/12 1994/12 2001/12 FREN IC -M EGA (FRN -G1( )LD Mode)
FRENIC5000G6N 1989/03 1994/03 2001/03 FRENIC-MEGA (FRN-G1)
FRENIC5000G7 1989/12 1998/01 2005/01 FRENIC-MEGA (FRN-G1)
FRENIC5000P7 1989/12 1998/01 2005/01 FREN IC -M EGA (FRN -G1( )LD Mode)
FVR-G7S 1990/06 1998/01 2005/01 FRENIC-MEGA (FRN-G1)
FVR-K7S 1990/06 1998/01 2005/01 FREN IC -M ul t( i FRN -E1 )
FVR-G7N 1991/05 1998/01 2005/01 FRENIC-MEGA (FRN-G1)
FVR-E7S 1992/11 1998/01 2005/01 FRENIC-Ace (FRN-E2)
FVR-B7S 1991/05 2002/01 2009/01 FRENIC-Ace (FRN-E2)
FRENIC5000V3 1989/01 2002/03 2009/03 Please consult Fuji Electric
FRENIC5000M3 1991/06 2002/03 2009/03 Please consult Fuji Electric
FRENIC5000H2 1986/03 2007/01 2014/01 Please consult Fuji Electric
FVR-H5 1988/08 1999/11 2006/11 FRENIC-HF (FRN-H1)
FRENIC5000VG3 1990/12 1998/10 2005/10 FRENIC-VG (FRN-VG1)
FRENIC5000VG3N 1992/07 1998/10 2005/10 FRENIC-VG (FRN-VG1)
FRENIC5000G9S 1994/04 2000/05 2007/05 FRENIC-MEGA (FRN-G1)
FRENIC5000P9S 1994/04 2000/05 2007/05 FREN IC -M EGA (FRN -G1( )LD Mode)
FVR-C9S 1994/04 1999/11 2006/11 FREN IC -M i n( i FRN -C 2 )
FRENIC5000VG5S/VG5N 1995/08 2002/03 2009/03 FRENIC-VG (FRN-VG1)
FVR-E9S 1995/08 2006/05 2013/05 FRENIC-Ace (FRN-E2)
FRENIC5000MS5 1997/07 2012/06 2019/06 Please consult Fuji Electric
FVR-S11S 1998/04 2003/12 2010/12 FREN IC -M i n( i FRN -C 2 )
FVR-C11S 1998/04 2003/12 2010/12 FREN IC -M i n( i FRN -C 2 )
FRENIC5000G11S 1998/07 2010/03 2017/03 FRENIC-MEGA (FRN-G1)
FRENIC5000P11S 1998/07 2010/03 2017/03 FREN IC -M EGA (FRN -G1( )LD Mode)
FVR-E11S 1999/04 2007/11 2014/11 FRENIC-Ace (FRN-E2)
(FESPAC)
FVR-D 1999/10 2009/06 2016/06 Please consult Fuji Electric
FRENIC5000VG7S 1999/11 2013/09 2020/09 FRENIC-VG (FRN-VG1)
FRENIC5000H11S 2000/06 2010/03 2017/03 FRENIC-HF (FRN-H1)
FRENIC5000MG5 2000/11 2012/06 2019/06 Please consult Fuji Electric
FREN IC -M i n(i FRN -C 1) 2002/04 2015/12 2022/12 FREN IC -M i n( i FRN -C 2 )
FRENIC-Eco (FRN-F1) 2003/09 2019/05 (Asia) Please consult Fuji Electric Only available in Japan
FREN IC -M ul t(i FRN -E1) 2005/04 2016/09 2023/09 FRENIC-Ace (FRN-E2)
FREN IC -Li f(
t FRN -LM 1) 2006/08 Not feature in this selection guide, please consult Fuji Electric
FRENIC-MEGA (FRN-G1) 2006/10 2023/09 (FRN-G2)
FRENIC-MEGA G1 (LD) G2 (HND)
FRENIC-VG (FRN-VG1) 2011/02
FRENIC-HF (FRN-H1) 2011/03 Not feature in this selection guide, please consult Fuji Electric
FREN IC -M i n(i FRN -C 2) 2012/09
FRENIC-HVAC (FRN-AR) 2013/12
FRENIC-AQUA (FRN-AQ) 2013/12
FRENIC-Ace (FRN-E2) 2014/07
FRENIC-eF I T(FRN-EF1) 2019/05 Not feature in this selection guide, please consult Fuji Electric
FRENIC-MEGA (FRN-G2) 2021/03
* Alternative models are a guideline and may vary depending on usage conditions (functions and performance).
** 7 year parts support for discontinued model depend availability. (Terms and Conditions apply for these parts support duration, consult Fuji Electric).
39
Scan to discover !
/
ia
as
v/
_l
es
riv
_d
ac
s/
ct
du
ro
/p
m
co
c.
tri
ec
l
iej
fu
.
ww
//w
s:
tp
ht
SCAN ME OR CLICK ME
Click
Click
ME!
ME!
Copyright 2023 Fuji Electric Asia Pacific Pte Ltd. All Rights Reserved.
Information in this catalog are subject to changes without prior notice.
Fuji Electric can accept no responsibility for possible errors in catalog, brochures and other printed material.
Fuji Electric is a trademark and property of Fuji Electric Co., Ltd. its subsidiaries and affiliated companies. INV-SG-FAP-202301