INTERNATIONAL ISO
STANDARD 16358-1
First edition
2013-04-15
AMENDMENT 1
2019-04
Air-cooled air conditioners and air-
to-air heat pumps — Testing and
calculating methods for seasonal
performance factors —
Part 1:
Cooling seasonal performance factor
iTeh STANDARD PREVIEW
AMENDMENT 1
(standards.iteh.ai)
Climatiseurs
ISO à condenseur
16358-1:2013/Amd 1:2019 à air et pompes à chaleur air/air — Essais
et méthodes de calcul des coefficients de performance saisonniers —
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Partie 1: Coefficient de performance saisonnier de refroidissement
115a9293d850/iso-16358-1-2013-amd-1-2019
(COPSR)
AMENDEMENT 1
Reference number
ISO 16358-1:2013/Amd.1:2019(E)
© ISO 2019
ISO 16358-1:2013/Amd.1:2019(E)
iTeh STANDARD PREVIEW
(standards.iteh.ai)
ISO 16358-1:2013/Amd 1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
115a9293d850/iso-16358-1-2013-amd-1-2019
COPYRIGHT PROTECTED DOCUMENT
© ISO 2019
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting
on the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address
below or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Fax: +41 22 749 09 47
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii © ISO 2019 – All rights reserved
ISO 16358-1:2013/Amd.1:2019(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to the
iTeh STANDARD PREVIEW
World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT) see www.iso
.org/iso/foreword.html. (standards.iteh.ai)
This document was prepared by Technical Committee ISO/TC 86, Refrigeration and air-conditioning,
Subcommittee SC 6, Testing and rating ISO of air-conditioners
16358-1:2013/Amd and heat pumps.
1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Any feedback or questions on115a9293d850/iso-16358-1-2013-amd-1-2019
this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
© ISO 2019 – All rights reserved iii
iTeh STANDARD PREVIEW
(standards.iteh.ai)
ISO 16358-1:2013/Amd 1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
115a9293d850/iso-16358-1-2013-amd-1-2019
ISO 16358-1:2013/Amd.1:2019(E)
Air-cooled air conditioners and air-to-air heat pumps —
Testing and calculating methods for seasonal performance
factors —
Part 1:
Cooling seasonal performance factor
AMENDMENT 1
Page 1, 1.2
Add “ and T3” after the words “the rating conditions are those specified under T1”.
Page 3, 3.13
iTeh STANDARD PREVIEW
Add “ or T3” after the words “cooling capacity at T1”.
(standards.iteh.ai)
Page 3, 3.14 ISO 16358-1:2013/Amd 1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Add “ or T3” after the words “electric power input at T1”.
115a9293d850/iso-16358-1-2013-amd-1-2019
Page 3, 3.15
Add “ or T3” after the words “capacity which is 50 % of cooling full capacity at T1”.
Page 3, 3.16
Add “ or T3” after the words “electric power input when operated at 50 % of cooling full capacity at T1”.
Page 3, 3.17
Add “ or T3” after the words “capacity at T1”.
Page 3, 3.18
Add “ or T3” electric power input at T1”.
Page 3, after 3.22
Add 3.23 and 3.24
© ISO 2019 – All rights reserved 1
ISO 16358-1:2013/Amd.1:2019(E)
3.23
T1 climate
standardized range of climate conditions for a moderate climate
3.24
T3 climate
standardized range of climate conditions for a hot climate
Page, 3, Clause 4 Symbols
Add the following row after CCSE row
CD degradation coefficient
Add the following row after Pful(t j) row
Pful(46) cooling full power input at T3 temperature condition W
Add the following row after Phaf(t j) row
Phaf(46) cooling half power input at T3 temperature condition W
Add the following row after Pmin(tj) row
Pmin(46) cooling minimum power input at T1 temperature condition W
iTeh STANDARD PREVIEW
Add the following row after ϕful(tj) row
(standards.iteh.ai)
ϕful(46) cooling full capacity at T3 temperature condition W
ISO 16358-1:2013/Amd 1:2019
ϕhaf(tj) row
Add the following row afterhttps://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
115a9293d850/iso-16358-1-2013-amd-1-2019
ϕhaf(46) cooling half capacity at T3 temperature condition W
Add the following row after ϕmin(tj) row
ϕmin(46) cooling minimum capacity at T3 temperature condition W
Page 5, 5.2 Test conditions
Add
“for units rated for T1 climate and Table F.1 in Annex F for units rated for T3 climate”
after
“for calculation shall be as specified in Table 1”
Page 6, 5.3.2 Low temperature cooling capacity tests
Add
“for T1 climate or Table F.1 for T3 climate”
after
“default values as given in Table 1”
2 © ISO 2019 – All rights reserved
ISO 16358-1:2013/Amd.1:2019(E)
Page 7, 5.3.3 Low humidity cooling test and cyclic cooling test
Add
“for T1 climate or Table F.1 for T3 climate”
after
“default values as given in Table 1”
Page 7, Clause 6 Calculations
Add the following sentences and Table after the first sentence:
For units rated for T1 climate, calculations shall be made according to Clause 6 and for units rated for
T3 climate, calculations shall be made according to F.2.
NOTE A calculation tool (spreadsheet) is available to perform all the calculations of Clause 6, given the
individual test input. It is available at https://standards.iso.org/iso/16358/-1/ed-1/en/amd/1. The issuer is
permitted to use the calculation tool in its original format without any modifications for the purpose specified in
this document.
Table 2 shows the formulae used for T1 climate and T3 climate in order to read this document more easily.
Table 2 — Formulae used to calculate CSPF and FCSP for T1 climate and T3 climate
iTeh STANDARD PREVIEW
T1 climate T3 climate
(standards.iteh.ai)
CSPF, FCSP (1) and Annex B (1) and Annex B
Cooling load Lc(t j) (2) with t0 = 20 °C and t100 = 35 °C (2) with t0 = 20 °C and t100 = 46 °C
ISO 16358-1:2013/Amd 1:2019
ϕful(t j) (3) (F.1), (F.2)
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Pful(t j) (4)
115a9293d850/iso-16358-1-2013-amd-1-2019 (F.3), (F.4)
Fixed
(CSTL), LCST (5) (5)
(CSEC), CCSE (6), (7), (8) (6), (7), (8)
ϕful(t j) (3) (F.1), (F.2)
ϕmin(t j) (9) (F.5), (F.6)
Pful(t j) (4) (F.3), (F.4)
Two-stage
Pmin(t j) (10) (F.7), (F.8)
(CSTL), LCST (5) (5)
(CSEC), CCSE (11), (7), (12), (13), (4) (11), (7), (12), (13), (4)
ϕful(t j) (3) (F.1), (F.2)
Φhaf(t j) (14) (F.9), (F.10)
ϕmin(t j) (9) (F.5), (F.6)
Pful(t j) (4) (F.3), (F.4)
P haf(t j) (15) (F.11), (F.12)
Pmin(t j) (10) (F.7), (F.8)
Multi-stage
(CSTL), LCST (5) (5)
(CSEC), CCSE when (16), (7), (17), (18), (19), (20), (4) (16), (7), (17), (18), (19), (20), (4)
minimum capaci- (Annex E) (Annex E)
ty available
(CSEC), CCSE when (21), (7), (19), (20), (4) (21), (7), (19), (20), (4)
minimum capaci-
(Annex E) (Annex E)
ty not available
© ISO 2019 – All rights reserved 3
ISO 16358-1:2013/Amd.1:2019(E)
Table 2 (continued)
T1 climate T3 climate
ϕful(t j) (3) (F.1), (F.2)
Φhaf(t j) (14) (F.9), (F.10)
ϕmin(t j) (9) (F.5), (F.6)
Pful(t j) (4) (F.3), (F.4)
P haf(t j) (15) (F.11), (F.12)
Pmin(t j) (10) (F.7), (F.8)
Variable (CSTL), LCST (5) (5)
(16), (7), (22), (23), (24), (25), (16), (7), (22), (23), (24), (25),
(CSEC), CCSE when (26),(27),(4) (26),(27),(4)
minimum capaci-
ty available (Annex E) (F.13), (F.14), (F.15), (F.16),
(F.17), (F.18)
(CSEC), CCSE when (21), (7), (24), (25), (26),(27),(4) (21), (7), (24), (25), (26),(27),(4)
minimum capaci-
(Annex E) (F.15), (F.16), (F.17), (F.18)
ty is not available
Page 7, 6.2
Replace “Table 2 — Defined cooling load”
with
“Table 3 — Defined cooling load”
iTeh STANDARD PREVIEW
(standards.iteh.ai)
Page 7, 6.3 ISO 16358-1:2013/Amd 1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Replace 115a9293d850/iso-16358-1-2013-amd-1-2019
“Table 3 — Reference outdoor temperature bin distribution for T1 climate”
with “Table 4 — Reference outdoor temperature bin distribution for T1 climate”
Page 13, Clause 7 Test report
Add the following sentence at the end of the last sentence of the Clause.
“It shall be specified whether the CSPF is for T1 climate, T3 climate or a location specific temperature
bin distribution.”
Annex A
Replace Figure A.1 — Cooling capacity, power input and cooling load for fixed capacity units, by the
following figure:
4 © ISO 2019 – All rights reserved
ISO 16358-1:2013/Amd.1:2019(E)
iTeh STANDARD PREVIEW
(standards.iteh.ai)
ISO 16358-1:2013/Amd 1:2019
Key https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
X outdoor temperature 115a9293d850/iso-16358-1-2013-amd-1-2019
Y1 capacity or load
Y2 power input
Figure A.1 — Cooling capacity, power input and cooling load for fixed capacity units
Replace Figure A.2 — Cooling capacity, power input and cooling load for two-stage capacity units, by
the following figure:
© ISO 2019 – All rights reserved 5
ISO 16358-1:2013/Amd.1:2019(E)
iTeh STANDARD PREVIEW
(standards.iteh.ai)
ISO 16358-1:2013/Amd 1:2019
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
115a9293d850/iso-16358-1-2013-amd-1-2019
Key
X outdoor temperature
Y1 capacity or load
Y2 power input
Figure A.2 — Cooling capacity, power input and cooling load for two-stage capacity units
Replace Figure A.3 — Cooling capacity, power input and cooling load for multi-stage capacity units, by
the following figure:
6 © ISO 2019 – All rights reserved
ISO 16358-1:2013/Amd.1:2019(E)
iTeh STANDARD PREVIEW
(standards.iteh.ai)
Key
ISO 16358-1:2013/Amd 1:2019
X outdoor temperature
https://standards.iteh.ai/catalog/standards/sist/bc4add86-e96b-4f27-b5c0-
Y1 capacity or load 115a9293d850/iso-16358-1-2013-amd-1-2019
Y2 power input
Figure A.3 — Cooling capacity, power input and cooling load for multi-stage capacity units
Replace Figure A.4 — Cooling capacity, power input and cooling load and EER for variable capacity
units, by the following figure:
© ISO 2019 – All rights reserved 7