TURCK-GDP-IS-Excom-IO System
TURCK-GDP-IS-Excom-IO System
excom
I/O System for
Ex and Non-Ex Areas
Turck's excom offers a universal remote I/O system that can be The excom systems can be optimally adapted to the number of
installed in Zone 1/21, Zone 2/22 and C1D2 or in the non-Ex area. signals to be connected and the space requirements on site thanks
The field circuits are approved for Zone 0 and C1D1. You benefit to the module racks available for 8, 16 and 24 I/O modules. The
not only in terms of components optimized for the particular zone, redundancy concept – each module rack can be run if needed with
but also from the standard configuration and parameterization two power supply units and two gateways – gives you optimum
concept for the periphery and field instrumentation. availability guaranteed. The gateways act as masters to the internal
data bus and as slaves to the higher-level fieldbuses PROFIBUS-DP
Whether via an Ethernet or fieldbus connection: The excom system as well as Profinet, EtherNet/IP and Modbus TCP.
is transparent for the full functionality of the DCS systems of Rock-
well, Emerson, Honeywell, Siemens, ABB, Yokogawa, Schneider, or The I/O density of up to 960 signals on five module racks in a
Supcon. Integration in the DCS/PLC is made easy and error-free standard control cabinet is the only one of its kind worldwide. The
thanks to the detailed integration manuals and worldwide support signal isolation from the Ex area is already integrated in the I/O
provided. system. This therefore completely eliminates the need for con-
trol cabinets for safety barriers, as well as I/O cards in the control
system. This space benefit can be a critical factor, particularly in
retrofit projects. Up to 192 binary or 96 analog signals can be con-
nected via excom using a single IP address.
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
System module benefit Availability benefit Approval benefit
■ A single system for all areas (non-Ex, ■ High availability through extensive
Zone 1/21, Zone 2/22, C1D2) redundancy concepts for PNO, line and
■ Application optimized system structure system redundancy for all distributed
through modular concept control systems
■ High packing density through module ■ Full redundancy for power supplies and
racks for 8, 16 and 24 modules gateways
■ Up to 192 binary or 96 analog signals via ■ Exchange and expansion of all com-
one bus address ponents by inserting and removing all
modules during operation (Hot Swap)
■ Standard configuration and setting of all Simple connection to all standard process
parameters during operation (configura- control systems of
tion in run) ■ ABB
■ Online configuration and setting of all ■ Emerson
parameters during operation (configura- ■ Honeywell
tion in run) ■ Siemens
■ DTM-based commissioning of the periph- ■ Yokogawa
ery and field instrumentation without ■ Schneider Electric
control technology ■ SUPCON
■ HART transparency from the process ■…
control system to the field device
2021 | 05 2 |3
excom – System Configuration
Connection to the Ether- Redundancy possible Local diagnostics through Different I/O module
net network through two gateways LED indication types
Connection to the Connection of the high- Labeling options Connection of the Ex-i field
power supply (on Ex-e er-level Profibus-DP fieldbus devices via removable screw
terminals under the terminals or cage clamp
end cap) terminals
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Application range: non-intrinsically safe
MT08 MT16
MT24
Application range: intrinsically safe circuits and installation in the non-Ex area and in Zone 2 or C1D2
MT08 MT16
MT24
Application range: intrinsically safe circuits and installation in Zone 1 or C1D2
MT08 MT16
2021 | 05 4 |5
excom – Connecting to the Industrial Internet of Things
predictive maintenance.
Enterprise
Resource Planing
Manufacturing
s s
ce
safe
Execution Level
Ac
ta
Da
Field Level
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Connection Ethernet multiprotocol Maximum availability
In addition to the exchange of process One gateway, three protocols: excom supports Profinet S2 redundancy
data with the control system, excom also ■ Turck's multiprotocol I/O devices detect and ring topologies. Even for Ethernet pro-
features a second channel that provides the master after startup and adjust them- tocols that do not have a native redundan-
the parallel data stream to any system. It is selves automatically to the protocol cy specification, excom establishes with its
ideal for analyzing data firstly in an edge ■ PROFINET, Modbus TCP or EtherNet/IP own specification either system redundan-
device and sending only these results to ■ Fully developed web server enables cy, gateway redundancy or combinations
the cloud. device configuration, I/O parameteriza- of both options. This makes it possible to
tion and diagnostics via a PC or mobile achieve maximum availability with all sys-
Turck also offers here alternative routes in terminal devices tems – irrespective of whether the control
addition to its proprietary cloud solution ■ Integrated Ethernet switch also enables systems support the redundancy concept
with industry specific data visualization line and ring topologies or not.
and the encrypted Kolibri cloud protocol Turck's multiprotocol Ethernet technology
for the most demanding security require- has become a proven solution in several Besides network and protocol redundancy,
ments. The Turck cloud hardware also products and market segments. The system excom also supports hot swapping, i.e. the
enables data to be transferred to one of the can be used straightaway with all control ability to exchange all components during
large cloud systems via MQTT or OPC UA. systems supporting Profinet, EtherNet/IP or operation. This considerably simplifies
Modbus TCP, including for example: maintenance work.
Flexible network topology ■ Siemens
■ Honeywell
The gateways are provided with an ■ Rockwell
integrated 2-port switch and can thus be ■ Yokogawa
installed in line structures like conventional ■ Emerson
fieldbuses. Other standard Ethernet topolo- ■ Supcon
gies like star, tree or ring structures are also ■ ABB
supported. ■ ...
2021 | 05 6 |7
Network Topology
I/O devices with an integrated switch en- All stations are connected via a switch. If The line topology is extended into a ring
able networks to be created easily without one connection is broken, the remaining topology by using a redundancy protocol.
any external switches. If a connection is stations can still be reached. All stations must support the redundancy
broken, however, the downstream stations protocol (MRP or DLR).
can no longer be reached.
901 901
78
78
2 3
2 3
4 56 4 56
MRP
901 901
DLR 901 901
78
78
78
78
2 3
2 3
2 3
2 3
4 56 4 56 4 56 4 56
78
78
78
2 3
2 3
2 3
2 3
4 56 4 56 4 56 4 56
78
78
78
78
78
78
78
2 3
2 3
2 3
2 3
2 3
2 3
2 3
2 3
4 56 4 56 4 56 4 56 4 56 4 56 4 56 4 56
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
System Redundancy
■ Profinet = S2 ■ Turck‘s own solution for all systems Each gateway only communicates with one
possible master
S2 describes physical redundancy at the ■ Turck‘s own solution for all systems
control level and logical redundancy at the Simple and cost-effective redundancy con- possible
field device/gateway level through com- cept for increasing availability at the con-
munication relationships to the primary nection level between the control level and The highest availability is ensured if both
control and backup control. If the primary gateways. Both gateways have a communi- the master and the gateway are operated
control fails, the physical twin automatical- cation relationship with the control system redundantly. In this case, the gateway
ly takes over. and thus ensure that communication via communicates with only one master. The
the second gateway is maintained in the two masters negotiate internally who is the
event of a gateway failure or line break. master and who is the backup master. With
the intelligent excom solution, permanent
system availability can be implemented.
901 901
901 901
78
78
2 3
2 3
78
78
2 3
2 3
4 56 4 56
4 56 4 56 901 901
78
78
2 3
2 3
4 56 4 56
2021 | 05 8 |9
excom – Installation Overview with Ethernet
MQTT
OPC UA
Kolibri
Asset
DCS Management
DCS
optional
Ring redundancy
optional
Double ring
Line redundancy Ring redundancy
redundancy
Non-Ex Area
78
2 3
2 3
78
78
2 3
2 3
901 901 4 56 4 56 4 56 4 56
78
78
2 3
2 3
4 56 4 56
78
78
78
2 3
2 3
2 3
2 3
78
78
2 3
2 3
4 56 4 56 4 56 4 56
4 56 4 56
Zone 2
C1D2
Zone 0/1
C1D1
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
excom – Installation Overview with Profibus-DP
Asset
Management DCS System redundancy and line redundancy possible
DCS
alternatively
OC11Ex/3G.2
OC11Ex/3G.2
FO
coupler
FO
Non-Ex Area
alternatively
OC11Ex/2G.2 OC11Ex/2G.2
Segment FO FO
coupler coupler coupler
FO
Zone 2
C1D2
RS485-IS
OC11Ex/2G.2
OC11Ex/2G.2
FO
coupler
Zone 1
C1D2
Zone 0
C1D1
2021 | 05 10 | 11
excom – Control System Integration and
Asset Management
Redundancy
Function blocks
HCIR
Asset Management
Hon
son ey
er Exp e we
ll
Em
r io n
V ,C
lt a 20
De 0,
C
l a te DS
mp B
Te 30
0
S ch
dy
n e id e
S FD
ce, Symphony, Melo
M
AM
Foxboro EVO
r Electric/Iv
FDT- sed
-b ase d
Template
Template
ABB
excom
ba
FDT
PD
n
PR M M
a
e
e l
n
Fre
s ysy
rd a Fo
nd
VP
PC r
sta S7
um t PNO
Cen …
S7
a S, C S ie
w m
ga Ce n t u me
o
Yok ns
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
DTM for excom®
The excom DTM makes it possible to easily The module-specific settings for each The simulation view of the DTM simplifies
commission the periphery and the field excom module are mapped for each the commissioning of excom together with
instrumentation via the Profibus network channel. The entry of incorrect parameters the periphery. Input data can be overwrit-
even without a higher-level Class 1 master is prevented by a plausibility check which ten, in order, for example, to simulate key
of the distributed control system. The inte- is carried out immediately for the entry values for field instrumentation. Actuators
grated system scan function enables fast concerned. can be switched to the simulation state via
and fault-free commissioning. the output data.
2021 | 05 12 | 13
excom – Individual and Standard System Solutions
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Turck Mechatec (Germany) and
TEPS (USA)
Turck Mechatec and TEPS (Turck Engi-
neered Packaged Systems) offers complete
electrical system solutions to customer
specifications for all areas of industrial
automation. The Turck subsidiary can also
assemble excom control cabinets – either
in a standard configuration or individually
to customer specifications.
2021 | 05 14 | 15
Standard Housing Sizes
for Zone 2
■ 128 digital I/O
■ 64 analog I/O
■ 46 cm housing width
■ maximum channel density
for Zone 2
■ 196 digital I/O
■ 96 analog I/O
■ 80 cm housing width
■ customer-specific compo-
nents fitted
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Type Code for System Enclosures
EG - VA 65 55 26 / 1 1 1 - 02 0 0 / 2GD 60 . …
Width
46 Housing width (cm)
65 Housing width (cm)
80 Housing width (cm)
2021 | 05 16 | 17
excom for Intrinsically Safe Circuits
Module rack
For
taking MT08-2G MT16-2G MT08-3G MT16-3G MT24-3G MT-PPS
Power supply units 1 x PSD24Ex 2 x PSD24Ex 2 x PSM24-3G 2 x PSM24-3G 2 x PSM24-3G 2 x PPSA…/Ex
Gateways 1 2 2 2 2 -
I/O modules 8 16 8 16 24 -
Mounting in Zone 1/2, Non-Ex, Zone 1/2, Non-Ex, Zone 2, Non-Ex, Zone 2, Non-Ex, Zone 2, Non-Ex, Zone 1/2, Non-Ex,
C1D2 C1D2 C1D2* C1D2* C1D2* C1D2*
I/O modules DM80Ex DI401Ex DO401Ex AI43Ex AIH401Ex AOH401Ex TI40EX TI41EX DF20EX
Channels 8 4 4 4 4 4 4 4 2
Function DI/DO DI DO Poti AI with HART AO with HART RTD / TC RTD Frequency/
DI: Namur, Namur, < 50 mA Counter
mechanical mechanical
contact contact
DO: < 4 mA
Hans Turck GmbH & Co. KG | 45466 Mülheim an der Ruhr, Germany | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
excom for Non-Intrinsically Safe Circuits
Module rack
For
taking MT08-N MT16-N MT24-N
Power supply units 2 x PSM24-N 2 x PSM24-N 2 x PSM24-N
Gateways 2 2 2
I/O modules 8 16 24
Installation in the non-Ex area
I/O modules DM80-N DI40-N DI80-N DO40-N DO80-N DO60R-N AI43-N AIH401-N AOH401-N TI40-N TI41-N DF20-N
Channels 8 4 8 4 8 6 4 4 4 4 4 2
Function DI/DO DI DI DO DO Relays Poti AI with AO with RTD/TC RTD Frequen-
DI: Namur, Namur, 3-wire < 50 mA < 500 mA HART HART cy/Counter
mechanical mechanical (NPN/
contact contact, PNP)
DO: < 4 mA 3-wire
(NPN/PNP)
2021 | 05 18 | 19