POLYCAB Elastomeric Insulated Cable Confirming to BS EN 50525-2-21.

Polycab offers a comprehensive range of Rubber flexible cable conforming to BS EN 50525-2-21 for various
application.

The highly flexible and robust Polycab Rubber cable makes its use in portable electrical equipment and
devices. The mechanical force involved in moving apparatus requires cables to withstand high degree of
wear and tear, extreme weather condition, oil/grease prone area and high heat zone. These flexible
rubber cables are also suitable for wide range of application in lighting, appliances or equipment including
heavy industrial equipment requires flexible connection to power supply.

Conductor: High conductivity bunched tinned copper conductor produced in-house from state-of-the art
Machine.

Insulation: In-house developed cross linked elastomeric compound ethylene propylene rubber (EPR) or
Ethylene vinyl acetate (EVA).

Sheath: In-house developed cross linked elastomeric sheathing polychloroprene (PCP) or


chlorosulphonated polyethylene (CSP) or ethylene vinyl acetate (EVA) or thermoplastic polyurethane
(TMPU) compound.

The construction based on the application and requirement of the user against BS EN 50525-2-21

POLYCAB H05GG-F/H05GGH2-F BS EN 50525-2-21 POLYCAB H07RN-F BS EN 50525-2-21 MC - Rubber


MC - Rubber Cable, 300/500 V AC Cable, 450/750 V AC

POLYCAB H07RN8-F BS EN 50525-2-21 MC - Rubber POLYCAB H07BN4-F BS EN 50525-2-21 MC - Rubber


Cable, 450/750 V AC Cable, 450/750 V AC
POLYCAB H07BB-F BS EN 50525-2-21 MC - Rubber POLYCAB H05RR-F BS EN 50525-2-21 MC - 300/500
Cable, 450/750 V AC V Rubber Cable, 300/500 V AC

POLYCAB H07BQ-F BS EN 50525-2-21 MC - Rubber POLYCAB H05BQ-F BS EN 50525-2-21 MC - Rubber


Cable, 450/750 V AC Cable, 300/500 V AC

POLYCAB H05BN4-F BS EN 50525-2-21 MC - POLYCAB H05BB-F BS EN 50525-2-21 MC - Rubber


300/500 V Rubber Cable, 300/500 V AC Cable, 300/500 V AC

POLYCAB H05RN-F BS EN 50525-2-21 MC - Rubber


Cable, 300/500 V AC
POLYCAB H05BB-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Application
POLYCAB H05BB-F EPR insulated and cross linked elastomeric sheathed heavy-duty cable are intended to use
in appliances or equipment, heavy industrial equipment, where a flexible connection is required for power
supply.

Voltage Rating
Standard and References
300/500 V
IEC 60228
BS EN 50363-1
Operation Temperature
BS EN 50363-2-1
Fixed: -40˚C to 90˚C
BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 6 (EPR) to EN 50363-1 Compliance
• Sheathed with cross linked elastomeric compound Conductor Resistance test - IEC 60228
Type EM 6 (EPR) to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
2 core Blue and Brown Flame retardant properties as per IEC 60332-1-2
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Blue, Black, Grey Approval
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05BB-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
mm² Gland Size
mm kg/km
RCBS04TRUARE002C.75S 2 x 0.75 6.23 53 DBW - 01SS (UN)
RCBS04TRUARE002C001S 2x1 6.78 65 DBW - 01SS (UN)
RCBS04TRUARE002C1.5S 2 x 1.5 8.32 97 DBW - 01SS (UN)
RCBS04TRUARE002C2.5S 2 x 2.5 9.83 141 DBW - 01SS (UN)
RCBS04TRUARE003C.75S 3 x 0.75 6.80 67 DBW - 01SS (UN)
RCBS04TRUARE003C001S 3x1 7.18 78 DBW - 01SS (UN)
RCBS04TRUARE003C1.5S 3 x 1.5 8.83 116 DBW - 01SS (UN)
RCBS04TRUARE003C2.5S 3 x 2.5 10.44 171 DBW - 01SS (UN)
RCBS04TRUARE003C004S 3x4 12.25 248 DBW - 01SS (UN)
RCBS04TRUARE003C006S 3x6 13.89 338 DBW - 01S (UN)
RCBS04TRUARE004C.75S 4 x 0.75 7.41 81 DBW - 01SS (UN)
RCBS04TRUARE004C001S 4x1 7.83 95 DBW - 01SS (UN)
RCBS04TRUARE004C1.5S 4 x 1.5 9.85 147 DBW - 01SS (UN)
RCBS04TRUARE004C2.5S 4 x 2.5 11.63 217 DBW - 01SS (UN)
RCBS04TRUARE004C004S 4x4 13.63 315 DBW - 01S (UN)
RCBS04TRUARE004C006S 4x6 15.43 430 DBW - 01A (UN)
RCBS04TRUARE005C.75S 5 x 0.75 8.26 87 DBW - 01SS (UN)
RCBS04TRUARE005C001S 5x1 8.72 103 DBW - 01SS (UN)
RCBS04TRUARE005C1.5S 5 x 1.5 10.73 152 DBW - 01SS (UN)
RCBS04TRUARE005C2.5S 5 x 2.5 12.90 232 DBW - 01S (UN)
• DBW – Weatherproof series

Electrical characteristics
Current carrying capacity.
Current-carrying capacity Max. DC conductor
Nominal cross
resistance at 20˚C
sectional area Single-phase a.c. Three-phase a.c.
mm² Amp. Amp. Ω/km
0.75 6 6 26.7
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21
4 32 25 5.09
6 - - 3.39
Ambient temperature: 30˚C, Conductor operating temperature: 90˚C
The above table is in accordance with Table 4F3A of BS 7671:2018

De-Rating Factor
De-rating factor for 90°C thermosetting insulated cable.
Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H05BN4-F BS EN 50525-2-21 MC
300/500
Rubber VCable, 300/500 V AC

Application
POLYCAB H05BN4-F multicore Flexible cable insulated and sheathed with cross-linked elastomeric compound.
This cable fulfils the requirement as per EN 50525-2-21, cables are intended for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Standard and References


300/500 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to 90˚ C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 7 (EPR) to EN 50363-1. Compliance
• Sheathed with cross linked elastomeric compound Conductor Resistance test - IEC 60228
Type EM 7 (CSP) to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
3 core Green/Yellow, Blue, Brown Flame retardant properties as per IEC 60332-1-2
4 core Green/Yellow, Brown, Black, Grey
Approval
Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05BN4-F BS EN 50525-2-21 MC
300/500
Rubber VCable, 300/500 V AC

No. of Overall Weight


Construction POLYCAB/DOWEL
Product Code strands/strand Diameter (Approx.)
n x mm² Gland Size
dia. mm kg/km

RCBS04TRUARC003C.75S 3 x 0.75 24/0.2 6.80 72 DBW-01SS(UN)


RCBS04TRUARC003C001S 3x1 32/0.2 7.18 84 DBW-01SS(UN)
RCBS04TRUARC003C1.5S 3 x 1.5 30/0.25 8.83 125 DBW-01SS(UN)
RCBS04TRUARC003C2.5S 3 x 2.5 50/0.25 10.44 184 DBW-01SS(UN)
RCBS04TRUARC004C.75S 4 x 0.75 24/0.2 6.91 72 DBW-01SS(UN)
RCBS04TRUARC004C001S 4x1 32/0.2 7.83 102 DBW-01SS(UN)
RCBS04TRUARC004C1.5S 4 x 1.5 30/0.25 9.85 158 DBW-01SS(UN)
RCBS04TRUARC004C2.5S 4 x 2.5 50/0.25 11.63 232 DBW-01SS(UN)
• DBW – Weather proof series

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance.

Current-carrying capacity
Nominal cross Single- Three-phase Max. DC conductor
sectional area phase a.c. a.c. resistance at 20˚C

mm² Amp Amp Ω/km


0.75 6 6 26.7
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21
The ambient temperature is 30⁰C.
Conductor operating temperature 90⁰C.
The above table is in accordance with Table 4F3A of BS 7671:2018

De-Rating Factor

De-rating factor for 90˚C thermosetting insulated cable.

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H05BQ-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Application
POLYCAB H05BQ-F heavy-duty cable insulated with cross-linked elastomeric compound and sheathed with TPU.
This cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications
where appliances or equipment, including heavy industrial equipment, require a flexible connection to the
power supply.

Voltage Rating Standard and References


300/500 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-10-2
Fixed: -40˚C to + 90˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 6 (EPR) to EN 50363-1. Compliance
• Sheathed with thermoplastic polyurethane (TMPU) Conductor Resistance test - IEC 60228
to EN 50363-10-2 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
2 core Blue, Brown Flame retardant properties as per IEC 60332-1-2
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey Approval
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05BQ-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Gland Size
mm kg/km
RCBS04TRUAM1002C.75S 2 x 0.75 6.23 53 DBW - 01SS (UN)
RCBS04TRUAM1002C001S 2x1 6.78 65 DBW - 01SS (UN)
RCBS04TRUAM1003C.75S 3 x 0.75 6.80 67 DBW - 01SS (UN)
RCBS04TRUAM1003C001S 3x1 7.18 78 DBW - 01SS (UN)
RCBS04TRUAM1004C.75S 4 x 0.75 7.41 81 DBW - 01SS (UN)
RCBS04TRUAM1004C001S 4x1 7.83 95 DBW - 01SS (UN)
RCBS04TRUAM1005C.75S 5 x 0.75 8.26 87 DBW - 01SS (UN)
RCBS04TRUAM1005C001S 5x1 8.72 103 DBW - 01SS (UN)
• DBW – Weatherproof series

Electrical characteristics
Current carrying capacity and maximum DC conductor resistance.

Current-carrying capacity Max. DC


Nominal cross conductor
sectional area Single-phase Three-phase resistance
a.c. a.c. at 20˚C
mm² Amp. Amp. Ω/km
0.75 6 6 26.7
1 10 10 20
Ambient temperature: 30˚C
Conductor operating temperature: 90˚C
The above table is in accordance with Table 4F3A of BS 7671:2018

De-Rating Factor
De-rating factor for 90°C thermosetting insulated cable.

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H05GG-F/H05GGH2-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Application
POLYCAB H05GG-F & H05GGH2-F heavy-duty cable insulated and sheathed with cross-linked elastomeric
compound. This cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of
applications where appliances or equipment, including heavy industrial equipment, require a flexible
connection to the power supply.

Voltage Rating Standard and References


300/500 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to + 110˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as Test Voltage
per IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric
compound Type EI 3 (EVA rubber) to EN 50363-1. Compliance
• Sheathed with cross linked elastomeric Conductor Resistance test - IEC 60228
compound Type EM 4 (EVA) to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
2 core Blue, Brown Flame retardant properties as per IEC 60332-1-2
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey Approval
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05GG-F/H05GGH2-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Dimension table of H05GG-F

Nominal cross Overall Weight


POLYCAB/DOWEL
Product Code sectional area Diameter (Approx.)
Gland Size
mm² mm kg/km
RCBS04TEUAEV002C.75S 2 x 0.75 6.23 53 DBW - 01SS (UN)
RCBS04TEUAEV002C001S 2x1 6.78 64 DBW - 01SS (UN)
RCBS04TEUAEV002C1.5S 2 x 1.5 8.32 95 DBW - 01SS (UN)
RCBS04TEUAEV002C2.5S 2 x 2.5 9.83 140 DBW - 01SS (UN)
RCBS04TEUAEV003C.75S 3 x 0.75 6.80 65 DBW - 01SS (UN)
RCBS04TEUAEV003C001S 3x1 7.18 77 DBW - 01SS (UN)
RCBS04TEUAEV003C1.5S 3 x 1.5 8.83 115 DBW - 01SS (UN)
RCBS04TEUAEV003C2.5S 3 x 2.5 10.44 170 DBW - 01SS (UN)
RCBS04TEUAEV003C004S 3x4 12.25 240 DBW - 01SS (UN)
RCBS04TEUAEV003C006S 3x6 13.89 320 DBW - 01S (UN)
RCBS04TEUAEV004C.75S 4 x 0.75 7.41 80 DBW - 01SS (UN)
RCBS04TEUAEV004C001S 4x1 7.83 95 DBW - 01SS (UN)
RCBS04TEUAEV004C1.5S 4 x 1.5 9.85 145 DBW - 01SS (UN)
RCBS04TEUAEV004C2.5S 4 x 2.5 11.63 210 DBW - 01SS (UN)
RCBS04TEUAEV004C004S 4x4 13.63 300 DBW - 01S (UN)
RCBS04TEUAEV004C006S 4x6 15.43 405 DBW - 01A (UN)
RCBS04TEUAEV005C.75S 5 x 0.75 8.26 100 DBW - 01SS (UN)
RCBS04TEUAEV005C001S 5x1 8.72 115 DBW - 01SS (UN)
RCBS04TEUAEV005C1.5S 5 x 1.5 10.73 170 DBW - 01SS (UN)
RCBS04TEUAEV005C2.5S 5 x 2.5 12.90 255 DBW - 01S (UN)
• DBW – Weatherproof series

Dimensions table of H05GGH2-F

Weight
Construction Overall Dimension
Product Code (Approx.)
mm² mm
kg/km
RCBS04TEUAEV002C.75S 2 x 0.75 3.92 x 6.23 44
POLYCAB H05GG-F/H05GGH2-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Electrical characteristics
Current carrying capacity and maximum DC conductor resistance

Conductor cross- Current carrying Maximum DC conductor


sectional area capacity resistance at 20°C
mm² Amp. Ω/km
0.75 12 26.7
1 14 20
1.5 19 13.7
2.5 26 8.21
4 34 5.09
6 44 3.39
Ambient temperature: 30°C
Conductor maximum operating temperature: 110°C

De-Rating Factor
De-rating factor for 110°C thermosetting or thermoplastic insulated cable

Air Temperature 35°C to 80°C 85°C 90°C 95°C 100°C 105°C


Correction Factor 1.0 0.96 0.85 0.74 0.60 0.42
POLYCAB H05RN-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

68

Application
POLYCAB H05RN-F heavy-duty cable insulated and sheathed with cross-linked elastomeric compound. This
cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Standard and References


300/500 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to + 60˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed tinned bunched copper conductor as per Test Voltage
IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 4 (EPR) to EN 50363-1. Compliance
• Sheathed with cross-linked elastomeric compound Conductor Resistance test - IEC 60228
Type EM 2 (PCP) to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
2 core Blue, Brown Flame retardant properties as per IEC 60332-1-2
3 core Green/Yellow, Brown, Black
4 core Green/Yellow, Brown, Black, Grey Approval

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05RN-F BS EN 50525-2-21 MC
Rubber Cable, 300/500 V AC

Stranding Overall Weight


Construction No. of POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² strand/strand Gland Size
mm kg/km
dia.
RCBS04TRUARP002C.75S 2 x 0.75 24/0.2 6.23 53 DBW - 01SS (UN)
RCBS04TRUARP002C001S 2x1 32/0.2 6.78 65 DBW - 01SS (UN)
RCBS04TRUARP003C.75S 3 x 0.75 24/0.2 6.80 67 DBW - 01SS (UN)
RCBS04TRUARP003C001S 3x1 32/0.2 7.18 78 DBW - 01SS (UN)
RCBS04TRUARP004C.75S 4 x 0.75 24/0.2 7.41 81 DBW - 01SS (UN)
RCBS04TRUARP004C001S 4x1 32/0.2 7.83 95 DBW - 01SS (UN)
• DBW – Weather proof series

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance.

Current-carrying capacity Max. DC


Nominal cross
Single-phase Three-phase conductor
sectional area
a.c. a.c. resistance at 20˚C
mm²
Amp. Amp. Ω/km
0.75 6 6 26.7
1 10 10 20
The ambient temperature is 30⁰C.
Conductor operating temperature 60⁰C.
The above table is in accordance with Table 4F3A of BS 7671:2018

De-Rating Factor

De-rating factor for 60˚C thermosetting or thermoplastic insulated cable

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C


De-Rating Factor 0.91 0.82 0.71 0.58 0.41
POLYCAB H05RR-F BS EN 50525-2-21 MC
300/500 Cable,
Rubber V 300/500 V AC

Application
POLYCAB H05RR-F Multicore Flexible cable insulated and sheathed with cross-linked elastomeric compound.
This cable fulfils the requirement as per EN 50525-2-21, cables are intended for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Standard and References


300/500 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15°C to +60˚ C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2000V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 4(EPR) to EN 50363-1. Compliance
• Sheathed with cross linked elastomeric compound Conductor Resistance test - IEC 60228
Type EM 3 (EPR) to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
2 core Blue, Brown Flame retardant properties as per IEC-60332-1-2
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey Approval

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H05RR-F BS EN 50525-2-21 MC
300/500 Cable,
Rubber V 300/500 V AC

Overall
Weight
Construction Stranding Diameter POLYCAB/DOWEL
Product Code (Approx.)
mm² mm (Approx.) Gland Size
kg/km
mm
RCBS04TRUARE002C.75S 2 x 0.75 24/0.2 6.23 59 DBW-01SS(UN)
RCBS04TRUARE002C001S 2x1 32/0.2 6.78 71 DBW-01SS(UN)
RCBS04TRUARE002C1.5S 2 x 1.5 30/0.25 8.32 106 DBW-01SS(UN)
RCBS04TRUARE002C2.5S 2 x 2.5 50/0.25 9.83 153 DBW-01SS(UN)
RCBS04TRUARE003C.75S 3 x 0.75 24/0.2 6.80 72 DBW-01SS(UN)
RCBS04TRUARE003C001S 3x1 32/0.2 7.18 84 DBW-01SS(UN)
RCBS04TRUARE003C1.5S 3 x 1.5 30/0.25 8.83 125 DBW-01SS(UN)
RCBS04TRUARE003C2.5S 3 x 2.5 50/0.25 10.44 184 DBW-01SS(UN)
RCBS04TRUARE004C.75S 4 x 0.75 16/0.2 6.91 72 DBW-01SS(UN)
RCBS04TRUARE004C001S 4x1 32/0.2 7.83 102 DBW-01SS(UN)
RCBS04TRUARE004C1.5S 4 x 1.5 30/0.25 9.65 153 DBW-01SS(UN)
RCBS04TRUARE004C2.5S 4 x 2.5 50/0.25 11.43 226 DBW-01SS(UN)
• DBW – Weather proof series

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance.

Current-carrying capacity Max. DC


Nominal cross Single-phase Three-phase conductor
sectional area a.c. a.c. resistance at 20˚C

mm² Amp Amp Ω/km


0.75 6 6 26.7
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21
The ambient temperature is 30⁰C.
Conductor operating temperature 60⁰C.
The above table is in accordance with Table 4F3A of BS 7671:2018

De-Rating Factor

De-rating factor for 60˚C thermosetting or thermoplastic insulated cable

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C


De-Rating Factor 0.91 0.82 0.71 0.58 0.41
POLYCAB H07BB-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Application
POLYCAB H07BB-F heavy-duty cable insulated and sheathed with cross-linked elastomeric compound. This
cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Standard and References


450/750 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to 90˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
Test Voltage
• Annealed bunched tinned copper conductor as
2500V AC at (20±5) °C
per IEC 60228, class 5
• Insulated with cross-linked elastomeric
compound Type EI 6 (EPR) to EN 50363-1. Compliance
Conductor Resistance test - IEC 60228
• Sheath either in a single layer, cross linked
Insulation Resistance test - EN 50525-2-21
elastomeric compound Type EM 6 (EPR) to EN
Test under fire condition - EN 60332-1-2
50363-2-1 or in two layers, with both layers made
of cross linked elastomeric compound of Type EM
Flame retardant properties as per IEC 60332-1-2
6 (EPR) to EN 50363-2-1
Approval
Core Identification
2 core Blue, Brown
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H07BB-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
POLYCAB/DOWEL
Product Code Construction Diameter (Approx.)
Gland Size
n x mm² mm kg/km
RCBS06TRUARE001C1.5S 1 x 1.5 5.96 49 -
RCBS06TRUARE001C2.5S 1 x 2.5 6.62 65 DBW - 01SS (UN)
RCBS06TRUARE001C004S 1x4 7.56 91 DBW - 01SS (UN)
RCBS06TRUARE001C006S 1x6 8.33 118 DBW - 01SS (UN)
RCBS06TRUARE001C010S 1 x 10 10.08 183 DBW - 01SS (UN)
RCBS06TRUARE001C016S 1 x 16 11.32 254 DBW - 01SS (UN)
RCBS06TRUARE001C025S 1 x 25 13.18 367 DBW - 01S (UN)
RCBS06TRUARE001C035S 1 x 35 14.78 488 DBW - 01A (UN)
RCBS06TRUARE001C050S 1 x 50 17.07 677 DBW - 01A (UN)
RCBS06TRUARE001C070S 1 x 70 19.15 905 DBW - 02 (UN)
RCBS06TRUARE001C095S 1 x 95 21.74 1202 DBW - 02 (UN)
RCBS06TRUARE001C120S 1 x 120 23.68 1477 DBW - 04A (UN)
RCBS06TRUARE001C150S 1 x 150 26.01 1802 DBW - 05A (UN)
RCBS06TRUARE001C185S 1 x 185 28.69 2235 DBW - 05A (UN)
RCBS06TRUARE001C240S 1 x 240 31.63 2808 DBW - 06 SP (UN)
RCBS06TRUARE001C300S 1 x 300 34.67 3478 DBW - 07 SP (UN)
RCBS06TRUARE001C400S 1 x 400 38.92 4542 DBW - 08 (UN)
RCBS06TRUARE001C500S 1 x 500 42.74 5600 DBW - 09 (UN)
RCBS06TRUARE001C630S 1 x 630 46.46 6906 DBW - 010A (UN)
RCBS06TRUARE002C001S 2x1 8.38 91 DBW - 01SS (UN)
RCBS06TRUARE002C1.5S 2 x 1.5 9.32 116 DBW - 01SS (UN)
RCBS06TRUARE002C2.5S 2 x 2.5 11.03 168 DBW - 01SS (UN)
RCBS06TRUARE002C004S 2x4 12.72 234 DBW - 01S (UN)
RCBS06TRUARE002C006S 2x6 14.27 308 DBW - 01A (UN)
RCBS06TRUARE002C010S 2 x 10 19.16 547 DBW - 02 (UN)
RCBS06TRUARE002C016S 2 x 16 21.64 742 DBW - 02 (UN)
RCBS06TRUARE002C025S 2 x 25 25.57 1072 DBW - 05A (UN)
RCBS06TRUARE003C001S 3x1 9.04 111 DBW - 01SS (UN)
RCBS06TRUARE003C1.5S 3 x 1.5 10.03 141 DBW - 01SS (UN)
RCBS06TRUARE003C2.5S 3 x 2.5 11.84 206 DBW - 01SS (UN)
RCBS06TRUARE003C004S 3x4 13.65 288 DBW - 01S (UN)
RCBS06TRUARE003C006S 3x6 15.29 383 DBW - 01A (UN)
RCBS06TRUARE003C010S 3 x 10 20.59 681 DBW - 02 (UN)
RCBS06TRUARE003C016S 3 x 16 23.24 934 DBW - 04A (UN)
RCBS06TRUARE003C025S 3 x 25 27.44 1356 DBW - 05A (UN)
RCBS06TRUARE003C035S 3 x 35 30.61 1777 DBW - 06 SP (UN)
RCBS06TRUARE003C050S 3 x 50 35.51 2458 DBW - 08 (UN)
RCBS06TRUARE003C070S 3 x 70 39.74 3245 DBW - 08 (UN)
RCBS06TRUARE003C095S 3 x 95 45.46 4323 DBW - 010A (UN)
POLYCAB H07BB-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Gland Size
mm kg/km
RCBS06TRUARE003C120S 3 x 120 49.38 5269 DBW - 010A (UN)
RCBS06TRUARE003C150S 3 x 150 54.36 6430 DBW - 011 SP (UN)
RCBS06TRUARE003C185S 3 x 185 60.09 7966 DBW - 012 (UN)
RCBS06TRUARE003C240S 3 x 240 67.40 10128 DBW - 013 (UN)
RCBS06TRUARE003C300S 3 x 300 74.74 12624 DBW - 014 (UN)
RCBS06TRUARE004C001S 4x1 9.99 137 DBW - 01SS (UN)
RCBS06TRUARE004C1.5S 4 x 1.5 11.05 175 DBW - 01SS (UN)
RCBS06TRUARE004C2.5S 4 x 2.5 13.03 255 DBW - 01S (UN)
RCBS06TRUARE004C004S 4x4 15.03 360 DBW - 01A (UN)
RCBS06TRUARE004C006S 4x6 17.03 487 DBW - 01A (UN)
RCBS06TRUARE004C010S 4 x 10 22.48 841 DBW - 04A (UN)
RCBS06TRUARE004C016S 4 x 16 25.39 1161 DBW - 05A (UN)
RCBS06TRUARE004C025S 4 x 25 30.43 1722 DBW - 06 SP (UN)
RCBS06TRUARE004C035S 4 x 35 33.91 2259 DBW - 07 SP (UN)
RCBS06TRUARE004C050S 4 x 50 39.30 3126 DBW - 08 (UN)
RCBS06TRUARE004C070S 4 x 70 44.17 4155 DBW - 010A (UN)
RCBS06TRUARE004C095S 4 x 95 50.86 5577 DBW - 010A (UN)
RCBS06TRUARE004C120S 4 x 120 54.78 6748 DBW - 011 SP (UN)
RCBS06TRUARE004C150S 4 x 150 60.46 8258 DBW - 012 (UN)
RCBS06TRUARE004C185S 4 x 185 66.98 10259 DBW - 013 (UN)
RCBS06TRUARE004C240S 4 x 240 75.00 13028 DBW - 014 (UN)
RCBS06TRUARE004C300S 4 x 300 83.29 16265 DBW - 015 (UN)
RCBS06TRUARE005C001S 5x1 11.00 146 DBW - 01SS (UN)
RCBS06TRUARE005C1.5S 5 x 1.5 12.13 188 DBW - 01SS (UN)
RCBS06TRUARE005C2.5S 5 x 2.5 14.30 274 DBW - 01A (UN)
RCBS06TRUARE005C004S 5x4 16.71 393 DBW - 01A (UN)
RCBS06TRUARE005C006S 5x6 18.86 535 DBW - 02 (UN)
RCBS06TRUARE005C010S 5 x 10 24.69 921 DBW - 04A (UN)
RCBS06TRUARE005C016S 5 x 16 28.10 1290 DBW - 05A (UN)
RCBS06TRUARE005C025S 5 x 25 33.60 1908 DBW - 07 SP (UN)
RCBS06TRUARE005C035S 5 x 35 37.21 2493 DBW - 08 (UN)
RCBS06TRUARE005C050S 5 x 50 43.54 3487 DBW - 010A (UN)
RCBS06TRUARE005C070S 5 x 70 49.08 4667 DBW - 010A (UN)
RCBS06TRUARE005C095S 5 x 95 56.18 6227 DBW - 011 SP (UN)
RCBS06TRUARE005C120S 5 x 120 60.33 7521 DBW - 012 (UN)
RCBS06TRUARE005C150S 5 x 150 66.55 9194 DBW - 013 (UN)
RCBS06TRUARE005C185S 5 x 185 73.92 11449 DBW - 014 (UN)
RCBS06TRUARE005C240S 5 x 240 82.69 14535 DBW - 015 (UN)
RCBS06TRUARE005C300S 5 x 300 91.78 18147 DBW - 015 (UN)
• DBW – Weatherproof series
POLYCAB H07BB-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Electrical characteristics
Current carrying capacity H07BB-F (1 mm² to 2.5 mm²)

Current-carrying capacity Max. DC


Nominal cross conductor
Single-phase Three-phase
sectional area resistance at 20˚C
a.c. a.c.
mm² Amp. Amp. Ω/km
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21

Current carrying capacity H07BB-F (4 mm² to 630 mm²)

Single-phase a.c. or Three-phase Single-phase Max. DC


d.c. a.c. a.c. or d.c. conductor
Nominal cross
1 two-core cable, resistance at
sectional area 1 three-core, four- 2 single-core
with or without 20˚C
core or five-core cables, touching
protective conductor
mm² Amp. Amp. Amp. Ω/km
4 42 37 – 5.09
6 55 49 – 3.39
10 76 66 – 1.95
16 103 89 – 1.24
25 136 119 – 0.795
35 – 146 200 0.565
50 – 177 250 0.393
70 – 225 310 0.277
95 – 273 369 0.21
120 – 316 432 0.164
150 – 363 497 0.132
185 – 414 567 0.108
240 – 487 673 0.0817
300 – 560 773 0.0654
400 – – 924 0.0495
500 – – 1,062 0.0391
630 – – 1,242 0.0292
Ambient temperature: 30°C
Maximum conductor operating temperature: 90°C
The above table in accordance with Table 4F3A & 4F2A of BS 7671

De-Rating Factor
De-Rating factor of 90°C thermosetting insulated cable

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H07BN4-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Application
POLYCAB H07BN4-F heavy-duty cable insulated and sheathed with cross-linked elastomeric compound. This
cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Standard and References


450/750 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to 90˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as Test Voltage
per IEC 60228, class 5 2500V AC at (20±5) °C
• Insulated with cross-linked elastomeric
compound Type EI 7 (EPR) to EN 50363-1. Compliance
• Sheathing either in a single layer, cross-linked Conductor Resistance test - IEC 60228
elastomeric compound Type EM 7 (CSP) to EN Insulation Resistance test - EN 50525-2-21
50363-2-1 or in two layers, with the inner layer Test under fire condition - EN 60332-1-2
made of one of the cross-linked elastomeric
compounds type EM 7 or EM 6 to EN 50363-2-1 Flame retardant properties as per IEC 60332-1-2
and the outer layer of cross-linked elastomeric
compound type EM 7 to EN 50363-2-1 Approval

Core Identification
2 core Blue, Brown
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H07BN4-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

No. of Overall Weight


Construction POLYCAB/DOWEL
Product Code strands/strand Diameter (Approx.)
n x mm² Gland Size
dia. mm kg/km
RCBS06TRUARC001C004S 1x4 56/0.3 7.56 99 DBW-01SS(UN)
RCBS06TRUARC001C006S 1x6 84/0.3 8.33 128 DBW-01SS(UN)
RCBS06TRUARC001C010S 1 x 10 80/0.4 10.08 197 DBW-01SS(UN)
RCBS06TRUARC001C016S 1 x 16 126/0.4 11.32 270 DBW-01SS(UN)
RCBS06TRUARC001C025S 1 x 25 196/0.4 13.18 388 DBW-01S(UN)
RCBS06TRUARC001C035S 1 x 35 276/0.4 14.78 514 DBW-01A(UN)
RCBS06TRUARC001C050S 1 x 50 396/0.4 17.07 710 DBW-02(UN)
RCBS06TRUARC001C070S 1 x 70 360/0.5 19.21 953 DBW-03 SP(UN)
RCBS06TRUARC001C095S 1 x 95 484/0.5 21.74 1252 DBW-03 SP(UN)
RCBS06TRUARC001C120S 1 x 120 608/0.5 23.65 1531 DBW-04 A(UN)
RCBS06TRUARC001C150S 1 x 150 750/0.5 26.01 1871 DBW-05A(UN)
RCBS06TRUARC001C185S 1 x 185 925/0.5 28.54 2281 DBW-05A(UN)
RCBS06TRUARC001C240S 1 x 240 1210/0.5 31.63 2902 DBW-06SP(UN)
RCBS06TRUARC001C300S 1 x 300 1527/0.5 34.67 3587 DBW-07SP(UN)
RCBS06TRUARC001C400S 1 x 400 2036/0.5 38.92 4672 DBW-08(UN)
RCBS06TRUARC001C500S 1 x 500 2530/0.5 42.67 6559 DBW-010A(UN)
RCBS06TRUARC001C630S 1 x 630 3180/0.5 46.34 7988 DBW-010A(UN)
RCBS06TRUARC002C004S 2x4 56/0.3 12.72 257 DBW-01S(UN)
RCBS06TRUARC002C006S 2x6 84/0.3 14.27 337 DBW-01A(UN)
RCBS06TRUARC002C010S 2 x 10 80/0.4 19.16 601 DBW-03SP(UN)
RCBS06TRUARC002C016S 2 x 16 126/0.4 21.64 809 DBW-03SP(UN)
RCBS06TRUARC002C025S 2 x 25 196/0.4 25.57 1164 DBW-05A(UN)
RCBS06TRUARC003C004S 3x4 56/0.3 13.65 312 DBW-01S(UN)
RCBS06TRUARC003C006S 3x6 84/0.3 15.29 413 DBW-01A(UN)
RCBS06TRUARC003C010S 3 x 10 80/0.4 20.59 738 DBW-03SP(UN)
RCBS06TRUARC003C016S 3 x 16 126/0.4 23.24 1004 DBW-04A(UN)
RCBS06TRUARC003C025S 3 x 25 196/0.4 27.44 1451 DBW-05A(UN)
RCBS06TRUARC003C035S 3 x 35 276/0.4 30.61 1894 DBW-06SP(UN)
RCBS06TRUARC003C050S 3 x 50 396/0.4 35.51 2612 DBW-08(UN)
RCBS06TRUARC003C070S 3 x 70 360/0.5 39.87 3463 DBW-08(UN)
RCBS06TRUARC003C095S 3 x 95 484/0.5 45.46 4568 DBW-010A(UN)
RCBS06TRUARC003C120S 3 x 120 608/0.5 49.33 5540 DBW-010A(UN)
RCBS06TRUARC003C150S 3 x 150 750/0.5 54.36 6772 DBW-011SP(UN)
RCBS06TRUARC003C185S 3 x 185 925/0.5 59.75 8258 DBW-012(UN)
RCBS06TRUARC003C240S 3 x 240 1210/0.5 67.40 10646 DBW-013(UN)
RCBS06TRUARC003C300S 3 x 300 1527/0.5 74.74 13255 DBW-014(UN)
POLYCAB H07BN4-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

No. of Overall Weight


Construction POLYCAB/DOWEL
Product Code strands/strand Diameter (Approx.)
n x mm² Gland Size
dia. mm kg/km
RCBS06TRUARC004C004S 4x4 56/0.3 15.03 387 DBW-01A(UN)
RCBS06TRUARC004C006S 4x6 84/0.3 17.03 522 DBW-01A(UN)
RCBS06TRUARC004C010S 4 x 10 80/0.4 22.48 905 DBW-04A(UN)
RCBS06TRUARC004C016S 4 x 16 126/0.4 25.39 1241 DBW-05A(UN)
RCBS06TRUARC004C025S 4 x 25 196/0.4 30.43 1834 DBW-06SP(UN)
RCBS06TRUARC004C035S 4 x 35 276/0.4 33.91 2396 DBW-07SP(UN)
RCBS06TRUARC004C050S 4 x 50 396/0.4 39.30 3305 DBW-08(UN)
RCBS06TRUARC004C070S 4 x 70 360/0.5 44.32 4416 DBW-010A(UN)
RCBS06TRUARC004C095S 4 x 95 484/0.5 50.86 5871 DBW-010A(UN)
RCBS06TRUARC004C120S 4 x 120 608/0.5 54.72 7062 DBW-011SP(UN)
RCBS06TRUARC004C150S 4 x 150 750/0.5 60.46 8661 DBW-012(UN)
RCBS06TRUARC004C185S 4 x 185 925/0.5 66.60 10590 DBW-013(UN)
RCBS06TRUARC004C240S 4 x 240 1210/0.5 75.00 13636 DBW-014(UN)
RCBS06TRUARC004C300S 4 x 300 1527/0.5 83.29 17010 DBW-015(UN)
RCBS06TRUARC005C004S 5x4 56/0.3 16.71 418 DBW-01A(UN)
RCBS06TRUARC005C006S 5x6 84/0.3 18.86 566 DBW-02(UN)
RCBS06TRUARC005C010S 5 x 10 80/0.4 24.69 979 DBW-04A(UN)
RCBS06TRUARC005C016S 5 x 16 126/0.4 28.10 1362 DBW-05A(UN)
RCBS06TRUARC005C025S 5 x 25 196/0.4 33.60 2006 DBW-07SP(UN)
• DBW – Weather proof Series
POLYCAB H07BN4-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance.

Single-phase a.c. or d.c. Three-phase a.c. Max. DC


Nominal cross 1 two-core cable, conductor
2 single-core 1 three-core, four
sectional area with or without resistance at 20˚C
cables, touching core or five core
protective conductor Ω/km
mm² Amp Amp Amp Ω/km
4 42 – 37 5.09
6 55 – 49 3.39
10 76 – 66 1.95
16 103 – 89 1.24
25 136 – 119 0.795
35 – 200 146 0.565
50 – 250 177 0.393
70 – 310 225 0.277
95 – 369 273 0.21
120 – 432 316 0.164
150 – 497 363 0.132
185 – 567 414 0.108
240 – 673 487 0.0817
300 – 773 560 0.0654
400 – 924 – 0.0495
500 – 1,062 – 0.0391
630 – 1,242 – 0.0292
The ambient temperature is 30⁰C.
Conductor operating temperature 90⁰C.
The above table is in accordance with Table 4F2A of BS 7671:2018

De-Rating Factor

De-rating factor for 90˚C thermosetting insulated cable

Air temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H07BQ-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Application
POLYCAB H07BQ-F heavy-duty cable insulated with cross-linked elastomeric compound and sheathed with TPU.
This cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications
where appliances or equipment, including heavy industrial equipment, require a flexible connection to the
power supply.

Voltage Rating Standard and References


450/750 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-10-2
Fixed: -40˚C to 90˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2500V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 6 (EPR) to EN 50363-1. Compliance
• Sheathed with thermoplastic polyurethane (TMPU) Conductor Resistance test - IEC 60228
to EN 50363-10-2 Insulation Resistance test - EN 50525-2-21
Test under fire condition - EN 60332-1-2
Core Identification
Flame retardant properties as per IEC 60332-1-2
2 core Blue, Brown
3 core Green/Yellow, Blue, Brown
Approval
4 core Green/Yellow, Brown, Black, Grey
5 core Green/Yellow, Blue, Brown, Black, Grey

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H07BQ-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Gland Size
mm kg/km
RCBS06TRUAM1002C001S 2x1 7.58 74 DBW - 01SS (UN)
RCBS06TRUAM1002C1.5S 2 x 1.5 8.32 93 DBW - 01SS (UN)
RCBS06TRUAM1002C2.5S 2 x 2.5 9.83 136 DBW - 01SS (UN)
RCBS06TRUAM1002C001S 2x4 11.52 195 DBW - 01SS (UN)
RCBS06TRUAM1002C006S 2x6 12.87 259 DBW - 01S (UN)
RCBS06TRUAM1002C010S 2 x 10 16.96 445 DBW - 01A (UN)
RCBS06TRUAM1002C016S 2 x 16 19.24 616 DBW - 02 (UN)
RCBS06TRUAM1003C001S 3x1 8.04 89 DBW - 01SS (UN)
RCBS06TRUAM1003C1.5S 3 x 1.5 8.83 113 DBW - 01SS (UN)
RCBS06TRUAM1003C2.5S 3 x 2.5 10.44 167 DBW - 01SS (UN)
RCBS06TRUAM1003C004S 3x4 12.25 242 DBW - 01SS (UN)
RCBS06TRUAM1003C006S 3x6 13.89 330 DBW - 01S (UN)
RCBS06TRUAM1003C010S 3 x 10 18.19 564 DBW - 02 (UN)
RCBS06TRUAM1003C016S 3 x 16 20.84 798 DBW - 02 (UN)
RCBS06TRUAM1004C001S 4x1 8.99 113 DBW - 01SS (UN)
RCBS06TRUAM1004C1.5S 4 x 1.5 9.85 143 DBW - 01SS (UN)
RCBS06TRUAM1004C2.5S 4 x 2.5 11.63 212 DBW - 01SS (UN)
RCBS06TRUAM1004C004S 4x4 13.63 308 DBW - 01S (UN)
RCBS06TRUAM1004C006S 4x6 15.43 420 DBW - 01A (UN)
RCBS06TRUAM1004C010S 4 x 10 20.08 712 DBW - 02 (UN)
RCBS06TRUAM1004C016S 4 x 16 22.79 1003 DBW - 04A (UN)
RCBS06TRUAM1005C001S 5x1 10.00 120 DBW - 01SS (UN)
RCBS06TRUAM1005C1.5S 5 x 1.5 10.73 149 DBW - 01SS (UN)
RCBS06TRUAM1005C2.5S 5 x 2.5 12.90 227 DBW - 01S (UN)
RCBS06TRUAM1005C004S 5x4 15.11 332 DBW - 01A (UN)
RCBS06TRUAM1005C006S 5x6 17.06 456 DBW - 01A (UN)
RCBS06TRUAM1005C010S 5 x 10 22.09 774 DBW - 02 (UN)
RCBS06TRUAM1005C016S 5 x 16 25.30 1109 DBW - 05A (UN)
• DBW – Weatherproof series
POLYCAB H07BQ-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Electrical characteristics
Current carrying capacity (1 mm² to 2.5 mm²) and maximum DC conductor resistance.

Current-carrying capacity
Nominal cross Max. DC conductor
sectional area Single-phase Three-phase resistance at 20˚C
a.c. a.c.
mm² Amp. Amp. Ω/km
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21

Current carrying capacity (4 mm² to 16 mm²) and maximum DC conductor resistance.

Single-phase a.c. or Three-phase Single-phase


Max. DC
d.c. a.c. a.c. or d.c.
Nominal cross conductor
1 two-core cable, 1 three-core, 2 single-core
sectional area resistance at
with or without four-core or cables,
20˚C
protective conductor five-core touching
mm² Amp. Amp. Amp. Ω/km
4 42 37 – 5.09
6 55 49 – 3.39
10 76 66 – 1.95
16 103 89 – 1.24
Ambient temperature: 30°C
Maximum conductor operating temperature: 90°C
The above table in accordance with the 4F3A & 4F2A of BS 7671

De-Rating Factor
De-rating factor for 90°C thermosetting insulated cable.

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C 60˚C 65˚C 70˚C 75˚C 80˚C 85˚C
De-Rating Factor 0.95 0.91 0.86 0.82 0.76 0.7 0.64 0.57 0.5 0.4 0.28
POLYCAB H07RN8-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Application
POLYCAB H07RN8-F heavy-duty water-resistant cable insulated and sheathed with cross-linked elastomeric
compound. This cable fulfils the requirement as per EN 50525-2-21, for installation in dry, damp or wet
environments, in workshops with explosive atmospheres, it can be immersed in fresh water up to 10m depth
and it could be used as energy supply cable for submersed pumps. Not advisable for under waterpower
transmission or installation in a water way or where mechanical damage may occur a cause hazard

Voltage Rating Standard and References


450/750 V IEC 60228
BS EN 50363-1
Operation Temperature BS EN 50363-2-1
Fixed: -15˚C to 60˚C BS EN 50525-2-21
IEC 60332-1-2
Construction
• Annealed bunched tinned copper conductor as per Test Voltage
IEC 60228, class 5 2500V AC at (20±5) °C
• Insulated with cross-linked elastomeric compound
Type EI 4 (EPR) to EN 50363-1. Compliance
• Sheath either in a single layer, cross-linked Conductor Resistance test - IEC 60228
elastomeric compound Type EM 2 (PCP) to EN Insulation Resistance test - EN 50525-2-21
50363-2-1 or in two layers, with the inner layer Test under fire condition - EN 60332-1-2
made of one of the cross-linked elastomeric
compounds type EM 2 or EM 3 to EN 50363-2-1 and Flame retardant properties as per IEC 60332-1-2
the outer layer of cross linked elastomeric
compound type EM 2 to EN 50363-2-1 Approval

Core Identification
2 core Blue, Brown
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey
5 core Green/Yellow, Blue, Brown, Black, Grey
6 core & above Green/Yellow, Black with white
numbering

Bending Radius
Fixed installation – 8 x Overall diameter
POLYCAB H07RN8-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Gland Size
mm kg/km
RCBS06TRUARP001C1.5S 1 x 1.5 5.96 49 -
RCBS06TRUARP001C2.5S 1 x 2.5 6.62 65 DBW - 01SS (UN)
RCBS06TRUARP001C004S 1x4 7.56 91 DBW - 01SS (UN)
RCBS06TRUARP001C006S 1x6 8.33 118 DBW - 01SS (UN)
RCBS06TRUARP001C010S 1 x 10 10.08 183 DBW - 01SS (UN)
RCBS06TRUARP001C016S 1 x 16 11.32 254 DBW - 01SS (UN)
RCBS06TRUARP001C025S 1 x 25 13.18 367 DBW - 01S (UN)
RCBS06TRUARP001C035S 1 x 35 14.78 488 DBW - 01A (UN)
RCBS06TRUARP001C050S 1 x 50 17.07 677 DBW - 01A (UN)
RCBS06TRUARP001C070S 1 x 70 19.15 905 DBW - 02 (UN)
RCBS06TRUARP001C095S 1 x 95 21.74 1202 DBW - 02 (UN)
RCBS06TRUARP001C120S 1 x 120 23.68 1477 DBW - 04A (UN)
RCBS06TRUARP001C150S 1 x 150 26.01 1802 DBW - 05A (UN)
RCBS06TRUARP001C185S 1 x 185 28.69 2235 DBW - 05A (UN)
RCBS06TRUARP001C240S 1 x 240 31.63 2808 DBW - 06 SP (UN)
RCBS06TRUARP001C300S 1 x 300 34.67 3478 DBW - 07 SP (UN)
RCBS06TRUARP001C400S 1 x 400 38.92 4542 DBW - 08 (UN)
RCBS06TRUARP001C500S 1 x 500 42.74 5600 DBW - 09 (UN)
RCBS06TRUARP001C630S 1 x 630 46.46 6906 DBW - 010A (UN)
RCBS06TRUARP002C001S 2x1 8.38 91 DBW - 01SS (UN)
RCBS06TRUARP002C1.5S 2 x 1.5 9.32 116 DBW - 01SS (UN)
RCBS06TRUARP002C2.5S 2 x 2.5 11.03 168 DBW - 01SS (UN)
RCBS06TRUARP002C004S 2x4 12.72 234 DBW - 01S (UN)
RCBS06TRUARP002C006S 2x6 14.27 308 DBW - 01A (UN)
RCBS06TRUARP002C010S 2 x 10 19.16 547 DBW - 02 (UN)
RCBS06TRUARP002C016S 2 x 16 21.64 742 DBW - 02 (UN)
RCBS06TRUARP002C025S 2 x 25 25.57 1072 DBW - 05A (UN)
RCBS06TRUARP003C001S 3x1 9.04 111 DBW - 01SS (UN)
RCBS06TRUARP003C1.5S 3 x 1.5 10.03 141 DBW - 01SS (UN)
RCBS06TRUARP003C2.5S 3 x 2.5 11.84 206 DBW - 01SS (UN)
RCBS06TRUARP003C004S 3x4 13.65 288 DBW - 01S (UN)
RCBS06TRUARP003C006S 3x6 15.29 383 DBW - 01A (UN)
RCBS06TRUARP003C010S 3 x 10 20.59 681 DBW - 02 (UN)
RCBS06TRUARP003C016S 3 x 16 23.24 934 DBW - 04A (UN)
RCBS06TRUARP003C025S 3 x 25 27.44 1356 DBW - 05A (UN)
RCBS06TRUARP003C035S 3 x 35 30.61 1777 DBW - 06 SP (UN)
RCBS06TRUARP003C050S 3 x 50 35.51 2458 DBW - 08 (UN)
RCBS06TRUARP003C070S 3 x 70 39.74 3245 DBW - 08 (UN)
RCBS06TRUARP003C095S 3 x 95 45.46 4323 DBW - 010A (UN)
RCBS06TRUARP003C120S 3 x 120 49.38 5269 DBW - 010A (UN)
RCBS06TRUARP003C150S 3 x 150 54.36 6430 DBW - 011 SP (UN)
RCBS06TRUARP003C185S 3 x 185 60.09 7966 DBW - 012 (UN)
RCBS06TRUARP003C240S 3 x 240 67.40 10128 DBW - 013 (UN)
POLYCAB H07RN8-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Gland Size
mm kg/km
RCBS06TRUARP003C300S 3 x 300 74.74 12624 DBW - 014 (UN)
RCBS06TRUARP004C001S 4x1 9.99 137 DBW - 01SS (UN)
RCBS06TRUARP004C1.5S 4 x 1.5 11.05 175 DBW - 01SS (UN)
RCBS06TRUARP004C2.5S 4 x 2.5 13.03 255 DBW - 01S (UN)
RCBS06TRUARP004C004S 4x4 15.03 360 DBW - 01A (UN)
RCBS06TRUARP004C006S 4x6 17.03 487 DBW - 01A (UN)
RCBS06TRUARP004C010S 4 x 10 22.48 841 DBW - 04A (UN)
RCBS06TRUARP004C016S 4 x 16 25.39 1161 DBW - 05A (UN)
RCBS06TRUARP004C025S 4 x 25 30.43 1722 DBW - 06 SP (UN)
RCBS06TRUARP004C035S 4 x 35 33.91 2259 DBW - 07 SP (UN)
RCBS06TRUARP004C050S 4 x 50 39.30 3126 DBW - 08 (UN)
RCBS06TRUARP004C070S 4 x 70 44.17 4155 DBW - 010A (UN)
RCBS06TRUARP004C095S 4 x 95 50.86 5577 DBW - 010A (UN)
RCBS06TRUARP004C120S 4 x 120 54.78 6748 DBW - 011 SP (UN)
RCBS06TRUARP004C150S 4 x 150 60.46 8258 DBW - 012 (UN)
RCBS06TRUARP004C185S 4 x 185 66.98 10259 DBW - 013 (UN)
RCBS06TRUARP004C240S 4 x 240 75.00 13028 DBW - 014 (UN)
RCBS06TRUARP004C300S 4 x 300 83.29 16265 DBW - 015 (UN)
RCBS06TRUARP005C001S 5x1 11.00 146 DBW - 01SS (UN)
RCBS06TRUARP005C1.5S 5 x 1.5 12.13 188 DBW - 01SS (UN)
RCBS06TRUARP005C2.5S 5 x 2.5 14.30 274 DBW - 01A (UN)
RCBS06TRUARP005C004S 5x4 16.71 393 DBW - 01A (UN)
RCBS06TRUARP005C006S 5x6 18.86 535 DBW - 02 (UN)
RCBS06TRUARP005C010S 5 x 10 24.69 921 DBW - 04A (UN)
RCBS06TRUARP005C016S 5 x 16 28.10 1290 DBW - 05A (UN)
RCBS06TRUARP005C025S 5 x 25 33.60 1908 DBW - 07 SP (UN)
RCBS06TRUARP006C1.5S 6 x 1.5 14.48 259 DBW - 01A (UN)
RCBS06TRUARP006C2.5S 6 x 2.5 16.85 367 DBW - 01A (UN)
RCBS06TRUARP006C004S 6x4 19.48 515 DBW - 02 (UN)
RCBS06TRUARP007C1.5S 7 x 1.5 14.68 287 DBW - 01A (UN)
RCBS06TRUARP007C2.5S 7 x 2.5 17.05 407 DBW - 01A (UN)
RCBS06TRUARP007C004S 7x4 19.88 583 DBW - 02 (UN)
RCBS06TRUARP012C1.5S 12 x 1.5 18.95 459 DBW - 02 (UN)
RCBS06TRUARP012C2.5S 12 x 2.5 22.07 656 DBW - 02 (UN)
RCBS06TRUARP012C004S 12 x 4 25.97 953 DBW - 05A (UN)
RCBS06TRUARP018C1.5S 18 x 1.5 22.21 648 DBW - 04A (UN)
RCBS06TRUARP018C2.5S 18 x 2.5 26.08 943 DBW - 05A (UN)
RCBS06TRUARP018C004S 18 x 4 30.60 1369 DBW - 06 SP (UN)
RCBS06TRUARP024C1.5S 24 x 1.5 25.97 854 DBW - 05A (UN)
RCBS06TRUARP024C2.5S 24 x 2.5 30.69 1254 DBW - 06 SP (UN)
RCBS06TRUARP036C1.5S 36 x 1.5 29.73 1195 DBW - 06 SP (UN)
RCBS06TRUARP036C2.5S 36 x 2.5 35.31 1777 DBW - 08 (UN)
• DBW – Weather proof series
POLYCAB H07RN8-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance. (1 mm² to 2.5 mm²)

Current-carrying capacity
Nominal cross Max. DC conductor
sectional area Single-phase Three-phase resistance at 20˚C
mm² a.c. a.c. Ω/km
Amp Amp
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21

Current carrying capacity and max. DC conductor resistance. (4 mm² and above)

Single-phase a.c. or d.c. Three-phase a.c. Max. DC


Nominal
1 two-core cable, 1 three-core, conductor
cross 2 single-
with or without four-core or resistance at
sectional are core cable
protective conductor five-core 20˚C
mm2 Amp Amp Amp Ω/km
4 30 – 26 5.09
6 39 – 34 3.39
10 51 – 47 1.95
16 73 – 63 1.24
25 97 – 83 0.795
35 – 140 102 0.565
50 – 175 124 0.393
70 – 216 158 0.277
95 – 258 192 0.21
120 – 302 222 0.164
150 – 347 255 0.132
185 – 394 291 0.108
240 – 471 343 0.0817
300 – 541 394 0.0654
400 – 644 – 0.0495
500 – 738 – 0.0391
630 – 861 – 0.0292
The ambient temperature is 30⁰C.
Conductor operating temperature 60⁰C.
The above table is in accordance with Table 4F3 A & 4F1A of BS 7671:2018
De-Rating Factor

De-rating factor for 60˚C thermosetting or thermoplastic insulated cable

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C


De-Rating Factor 0.91 0.82 0.71 0.58 0.41
POLYCAB H07RN-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Application
POLYCAB H07RN-F heavy-duty cable insulated and sheathed with cross-linked elastomeric compound. This
cable fulfils the requirement as per EN 50525-2-21, cables are intended to use for a variety of applications where
appliances or equipment, including heavy industrial equipment, require a flexible connection to the power
supply.

Voltage Rating Bending Radius


450/750 V Fixed installation – 8 x Overall diameter

Operation Temperature
Standard and References
Fixed: -15˚C to 60˚C
IEC 60228
BS EN 50363-1
Construction BS EN 50363-2-1
• Annealed bunched tinned copper conductor as BS EN 50525-2-21
per IEC 60228, class 5 IEC 60332-1-2
• Insulated with cross-linked elastomeric
compound Type EI 7 (EPR) to EN 50363-1. Test Voltage
• Sheathing either in a single layer, cross-linked 2500V AC at (20±5) °C
elastomeric compound Type EM 7 (CSP) to EN
50363-2-1 or in two layers, with the inner layer Compliance
made of one of the cross-linked elastomeric Conductor Resistance test - IEC 60228
compounds type EM 7 or EM 6 to EN 50363-2-1 Insulation Resistance test - EN 50525-2-21
and the outer layer of cross linked elastomeric Test under fire condition - EN 60332-1-2
compound type EM 7 to EN 50363-2-1
Flame retardant properties as per IEC 60332-1-2
Core Identification
2 core Blue, Brown Approval
3 core Green/Yellow, Blue, Brown
4 core Green/Yellow, Brown, Black, Grey
5 core Green/Yellow, Blue, Brown, Black, Grey
POLYCAB H07RN-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction Class of POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Conductor Gland Size
mm kg/km
RCBS06TRUARC001C1.5S 1 x 1.5 30/0.2 5.85 44 -
RCBS06TRUARC001C2.5S 1 x 2.5 50/0.2 6.41 72 DBW-01SS(UN)
RCBS06TRUARC001C004S 1x4 56/0.3 7.56 99 DBW-01SS(UN)
RCBS06TRUARC001C006S 1x6 84/0.3 8.33 128 DBW-01SS(UN)
RCBS06TRUARC001C010S 1 x 10 80/0.4 10.08 197 DBW-01SS(UN)
RCBS06TRUARC001C016S 1 x 16 126/0.4 11.32 270 DBW-01SS(UN)
RCBS06TRUARC001C025S 1 x 25 196/0.4 13.18 388 DBW-01S(UN)
RCBS06TRUARC001C035S 1 x 35 276/0.4 14.78 514 DBW-01A(UN)
RCBS06TRUARC001C050S 1 x 50 396/0.4 17.07 710 DBW-02(UN)
RCBS06TRUARC001C070S 1 x 70 360/0.5 19.21 953 DBW-03 SP(UN)
RCBS06TRUARC001C095S 1 x 95 484/0.5 21.74 1252 DBW-03 SP(UN)
RCBS06TRUARC001C120S 1 x 120 608/0.5 23.65 1531 DBW-04 A(UN)
RCBS06TRUARC001C150S 1 x 150 750/0.5 26.01 1871 DBW-05A(UN)
RCBS06TRUARC001C185S 1 x 185 925/0.5 28.54 2281 DBW-05A(UN)
RCBS06TRUARC001C240S 1 x 240 1210/0.5 31.63 2902 DBW-06SP(UN)
RCBS06TRUARC001C300S 1 x 300 1527/0.5 34.67 3587 DBW-07SP(UN)
RCBS06TRUARC001C400S 1 x 400 2036/0.5 38.92 4672 DBW-08(UN)
RCBS06TRUARC001C500S 1 x 500 2530/0.5 42.67 6559 DBW-010A(UN)
RCBS06TRUARC001C630S 1 x 630 3180/0.5 46.34 7988 DBW-010A(UN)
RCBS06TRUARC002C001S 2x1 32/0.2 8.38 101 DBW-01SS(UN)
RCBS06TRUARC002C1.5S 2 x 1.5 30/0.2 8.70 108 DBW-01SS(UN)
RCBS06TRUARC002C2.5S 2 x 2.5 50/0.2 10.22 152 DBW-01SS(UN)
RCBS06TRUARC002C004S 2x4 56/0.3 12.72 257 DBW-01S(UN)
RCBS06TRUARC002C006S 2x6 84/0.3 14.27 337 DBW-01A(UN)
RCBS06TRUARC002C010S 2 x 10 80/0.4 19.16 601 DBW-03SP(UN)
RCBS06TRUARC002C016S 2 x 16 126/0.4 21.64 809 DBW-03SP(UN)
RCBS06TRUARC002C025S 2 x 25 196/0.4 25.57 1164 DBW-05A(UN)
RCBS06TRUARC003C001S 3x1 32/0.2 9.04 121 DBW-01SS(UN)
RCBS06TRUARC003C1.5S 3 x 1.5 30/0.2 9.35 128 DBW-01SS(UN)
RCBS06TRUARC003C2.5S 3 x 2.5 50/0.2 10.97 181 DBW-01SS(UN)
RCBS06TRUARC003C004S 3x4 56/0.3 13.65 312 DBW-01S(UN)
RCBS06TRUARC003C006S 3x6 84/0.3 15.29 413 DBW-01A(UN)
RCBS06TRUARC003C010S 3 x 10 80/0.4 20.59 738 DBW-03SP(UN)
RCBS06TRUARC003C016S 3 x 16 126/0.4 23.24 1004 DBW-04A(UN)
RCBS06TRUARC003C025S 3 x 25 196/0.4 27.44 1451 DBW-05A(UN)
RCBS06TRUARC003C035S 3 x 35 276/0.4 30.61 1894 DBW-06SP(UN)
RCBS06TRUARC003C050S 3 x 50 396/0.4 35.51 2612 DBW-08(UN)
RCBS06TRUARC003C070S 3 x 70 360/0.5 39.87 3463 DBW-08(UN)
RCBS06TRUARC003C095S 3 x 95 484/0.5 45.46 4568 DBW-010A(UN)
POLYCAB H07RN-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Overall Weight
Construction Class of POLYCAB/DOWEL
Product Code Diameter (Approx.)
n x mm² Conductor Gland Size
mm kg/km
RCBS06TRUARC003C120S 3 x 120 608/0.5 49.33 5540 DBW-010A(UN)
RCBS06TRUARC003C150S 3 x 150 750/0.5 54.36 6772 DBW-011SP(UN)
RCBS06TRUARC003C185S 3 x 185 925/0.5 59.75 8258 DBW-012(UN)
RCBS06TRUARC003C240S 3 x 240 1210/0.5 67.40 10646 DBW-013(UN)
RCBS06TRUARC003C300S 3 x 300 1527/0.5 74.74 13255 DBW-014(UN)
RCBS06TRUARC004C001S 4x1 32/0.2 9.99 150 DBW-01SS(UN)
RCBS06TRUARC004C1.5S 4 x 1.5 30/0.2 10.29 156 DBW-01SS(UN)
RCBS06TRUARC004C2.5S 4 x 2.5 50/0.2 12.06 222 DBW-01SS(UN)
RCBS06TRUARC004C004S 4x4 56/0.3 15.03 387 DBW-01A(UN)
RCBS06TRUARC004C006S 4x6 84/0.3 17.03 522 DBW-01A(UN)
RCBS06TRUARC004C010S 4 x 10 80/0.4 22.48 905 DBW-04A(UN)
RCBS06TRUARC004C016S 4 x 16 126/0.4 25.39 1241 DBW-05A(UN)
RCBS06TRUARC004C025S 4 x 25 196/0.4 30.43 1834 DBW-06SP(UN)
RCBS06TRUARC004C035S 4 x 35 276/0.4 33.91 2396 DBW-07SP(UN)
RCBS06TRUARC004C050S 4 x 50 396/0.4 39.30 3305 DBW-08(UN)
RCBS06TRUARC004C070S 4 x 70 360/0.5 44.32 4416 DBW-010A(UN)
RCBS06TRUARC004C095S 4 x 95 484/0.5 50.86 5871 DBW-010A(UN)
RCBS06TRUARC004C120S 4 x 120 608/0.5 54.72 7062 DBW-011SP(UN)
RCBS06TRUARC004C150S 4 x 150 750/0.5 60.46 8661 DBW-012(UN)
RCBS06TRUARC004C185S 4 x 185 925/0.5 66.60 10590 DBW-013(UN)
RCBS06TRUARC004C240S 4 x 240 1210/0.5 75.00 13636 DBW-014(UN)
RCBS06TRUARC004C300S 4 x 300 1527/0.5 83.29 17010 DBW-015(UN)
RCBS06TRUARC005C1.5S 5 x 1.5 30/0.2 11.29 165 DBW-01SS(UN)
RCBS06TRUARC005C2.5S 5 x 2.5 50/0.2 13.41 241 DBW-01S(UN)
RCBS06TRUARC005C004S 5x4 56/0.3 16.71 418 DBW-01A(UN)
RCBS06TRUARC005C006S 5x6 84/0.3 18.86 566 DBW-02(UN)
RCBS06TRUARC005C010S 5 x 10 80/0.4 24.69 979 DBW-04A(UN)
RCBS06TRUARC005C016S 5 x 16 126/0.4 28.10 1362 DBW-05A(UN)
RCBS06TRUARC005C025S 5 x 25 196/0.4 33.60 2006 DBW-07SP(UN)
RCBS06TRUARC007C1.5S 7 x 1.5 30/0.2 14.75 294 DBW-01A(UN)
RCBS06TRUARC007C2.5S 7 x 2.5 50/0.2 17.24 407 DBW-02(UN)
RCBS06TRUARC012C1.5S 12 x 1.5 30/0.2 17.65 405 DBW-02(UN)
RCBS06TRUARC012C2.5S 12 x 2.5 50/0.2 21.43 601 DBW-03SP(UN)
RCBS06TRUARC019C1.5S 19 x 1.5 30/0.2 22.44 664 DBW-04A(UN)
• DBW – Weather proof Series
POLYCAB H07RN-F BS EN 50525-2-21 MC
Rubber Cable, 450/750 V AC

Electrical Characteristics
Current carrying capacity and max. DC conductor resistance. (1 mm² to 2.5 mm²)

Current-carrying capacity Max. DC


Nominal cross conductor
sectional area Single-phase Three-phase resistance at
mm² a.c. a.c. 20˚C
Amp Amp Ω/km
1 10 10 20
1.5 16 16 13.7
2.5 25 20 8.21

Current carrying capacity and max. DC conductor resistance. (4 mm² and above)

Three-phase
Single-phase a.c. or d.c. Max. DC
a.c.
Nominal cross conductor
1 two-core cable, 1 three-core,
sectional are 2 single-core resistance
with or without four-core or
cable at 20˚C
protective conductor five-core
mm2 Amp Amp Amp Ω/km
4 30 – 26 5.09
6 39 – 34 3.39
10 51 – 47 1.95
16 73 – 63 1.24
25 97 – 83 0.795
35 – 140 102 0.565
50 – 175 124 0.393
70 – 216 158 0.277
95 – 258 192 0.21
120 – 302 222 0.164
150 – 347 255 0.132
185 – 394 291 0.108
240 – 471 343 0.0817
300 – 541 394 0.0654
400 – 644 – 0.0495
500 – 738 – 0.0391
630 – 861 – 0.0292
The ambient temperature is 30⁰C.
Conductor operating temperature 60⁰C.
The above table is in accordance with Table 4F3 A & 4F1A of BS 7671:2018

De-Rating Factor

De-rating factor for 60˚C thermosetting or thermoplastic insulated cable.

Air Temperature 35˚C 40˚C 45˚C 50˚C 55˚C


De-Rating Factor 0.91 0.82 0.71 0.58 0.41