E5 J Temperature Controller: Operation Manual
E5 J Temperature Controller: Operation Manual
Operation Manual
Cat. No. Z103-E3-1
Notice:
     OMRON products are manufactured for use according to proper procedures by a qualified operator
     and only for the purposes described in this manual.
     The following conventions are used to indicate and classify precautions in this manual. Always heed
     the information provided with them. Failure to heed precautions can result in injury to people or dam-
     age to the product.
            !   DANGER             Indicates information that, if not heeded, is likely to result in loss of life or serious
                                   injury.
                ! WARNING Indicates information that, if not heeded, could possibly result in loss of life or
                          serious injury.
                  ! Caution        Indicates information that, if not heeded, could result in relatively serious or mi-
                                   nor injury, damage to the product, or faulty operation.
Visual Aids
     The following headings appear in the left column of the manual to help you locate different types of
     information.
                           Note Indicates information of particular interest for efficient and convenient operation
                                of the product.
1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
 OMRON, 1998
     All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
     form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis-
     sion of OMRON.
     No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
     constantly striving to improve its high-quality products, the information contained in this manual is subject to change
     without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
     responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa-
     tion contained in this publication.
                                                                                                                                v
                                           TABLE OF CONTENTS
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                                1
  1-1   Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      2
  1-2   Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      2
  1-3   Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        4
SECTION 2
Sensor and Mode Settings . . . . . . . . . . . . . . . . . . . . . . . .                                                                           9
  2-1   Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        10
  2-2   Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       10
  2-3   Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             11
SECTION 3
Settings Before Operation . . . . . . . . . . . . . . . . . . . . . . . . .                                                                        17
  3-1   Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         18
  3-2   Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          19
  3-3   List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           20
  3-4   Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    22
  3-5   Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    23
SECTION 4
Fuzzy Self-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                                  27
  4-1   Fuzzy Self-tuning Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  28
  4-2   Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          31
  4-3   Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        32
SECTION 5
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                                      35
  5-1   Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     36
  5-2   Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   37
  5-3   Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               38
SECTION 6
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                                  41
  6-1   Error Display and Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 42
  6-2   Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          42
SECTION 7
Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                                     45
  7-1   Event Input Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             46
SECTION 8
Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . .                                                                         49
  8-1   Heater Burnout Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 50
  8-2   Heater Burnout Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  50
  8-3   Wiring the Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     51
  8-4   Heater Burnout Alarm Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   51
SECTION 9
Engineering Level Settings . . . . . . . . . . . . . . . . . . . . . . . .                                                                         55
  9-1   Engineering Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            56
  9-2   Engineering Level Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     56
  9-3   Engineering Level Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   58
                                                                                                                                                        vii
                                                 TABLE OF CONTENTS
       SECTION 10
       Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                       63
         10-1   Starting Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   64
         10-2   Conditions that Prevent Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              64
         10-3   Force-ending Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         64
         10-4   Changing Parameters during Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   64
       Appendices
         A      Dimensions/Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            65
       Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                   69
       Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                                          71
viii
About this Manual:
    This manual describes the installation and operation of the Thermac E5J Temperature Controller and
    includes the sections described below.
    Please read this manual carefully and be sure you understand the information provided before attempting
    to install and operate the Thermac E5J Temperature Controller.
    Section 1 describes the specifications and basic features of the Thermac E5J Temperature Controller.
    Section 2 describes the sensor and mode settings of the Thermac E5J Temperature Controller that are
    necessary before turning on the Thermac E5J Temperature Controller.
    Section 3 describes the settings of the Thermac E5J Temperature Controller that are necessary before
    operating the Thermac E5J Temperature Controller.
    Section 4 provides the procedures required to adjust all PID constants using fuzzy self-tuning according
    to the characteristics of the device for ideal temperature control.
    Section 5 describes the installation and wiring of the Thermac E5J Temperature Controller.
    Section 6 describes the troubleshooting of the Thermac E5J Temperature Controller.
    Section 7 describes how the event input function of the Thermac E5J Temperature Controller works.
    Section 8 describes the basic features of heater burnout detection and necessary steps that should be
    taken at the time of heater burnout, as well as the method of obtaining heater burnout alarm values.
    Section 9 describes the parameters that can be changed on the engineering level. These parameters
    should be changed only when the values set before shipping do not suit the application. After these pa-
    rameters are changed on the engineering level, record the contents of the changes for your future refer-
    ence.
    Section 10 describes how to execute auto-tuning.
    The Appendix provides the dimensions and mounting specifications for the various Thermac E5J Tem-
    perature Controller Units.
   ! WARNING Failure to read and understand the information provided in this manual may result in
             personal injury or death, damage to the product, or product failure. Please read each
             section in its entirety and be sure you understand the information provided in the section
             and related sections before attempting any of the procedures or operations given.
                                                                                                         ix
                                                                                                                                            SECTION 1
                                                                                                                                            Introduction
This section describes the specifications and basic features of the Thermac E5J Temperature Controller.
       1-1   Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   2
       1-2   Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   2
       1-3   Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     4
             1-3-1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          4
             1-3-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              6
                                                                                                                                                            1
Models                                                                                                      Section 1-2
1-1       Features
                                    The basic features of the Thermac E5J Temperature Controller are outlined
                                    below.
Fuzzy Self-tuning                   When using a conventional temperature controller for ideal temperature control,
                                    it is necessary to adjust the PID constants of the temperature controller accord-
                                    ing to the controlled device. The Thermac E5J Temperature Controller incor-
                                    porates a fuzzy self-tuning function, thus allowing ideal temperature control
                                    without any adjustment of the PID constants. The user needs only to set the
                                    E5J to the desired temperature for ideal temperature control.
Auto-tuning                         Auto-tuning is also available. It is useful when appropriate results are not
                                    obtained through fuzzy self-tuning. (Refer to Section 10 Auto-tuning.)
Event Input Function                It is possible to select a set point out of a maximum of two set values on the
                                    E5CJ-B and four set values on the E5AJ-B via their event input terminals
                                    from the PCs connected to these Temperature Controllers. The control opera-
                                    tion of the E5AJ-B via can be stopped with an event input signal.
Watertight Construction             The E5J can be used in places where water is sprayed onto the E5J, be-
                                    cause the front panel of the E5J assures IP54 when the E5J is panel-
                                    mounted (except for front panel of the E5CJ, which assures IP50). If greater wa-
                                    tertightness is required, use the Y92A-N, a dedicated watertight cover (sold
                                    separately).
Advanced PID                        The E5J incorporates an advanced PID function, which is also incorporated by
                                    the Thermac X Temperature Controller. The advanced PID function prevents
                                    temperature overshooting the moment the Temperature Controller starts oper-
                                    ating, assures a short startup time, and performs ideal temperature control by
                                    quickly responding to external disturbances.
Output Units                        The E53-R Relay Unit, E53-Q, E53-Q3, and E53-Q4 Voltage Output Units for
                                    driving SSRs, and E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output
                                    Unit can be connected to any E5J Temperature Controller (except the E5CJ)
                                    with ease according to the desired output configuration and application.
1-2       Models
                                    The thermocouples and platinum resistance thermometers listed in the follow-
                                    ing table can be connected to any Thermac E5J Temperature Controller.
2
Models                                                                                                Section 1-2
96 X 96mm
Alarm                                                  2 relay output points with heater burnout alarm (see note 1)
Event input                                            2 points (set point selection, RUN/STOP) (see note 2)
Control output                                         Replaceable Output Unit (sold separately)
Model         Communications function   ---            E5AJ-A2HB
                                        RS-232C        E5AJ-A2H01
                                        RS-422         E5AJ-A2H02
                                        RS-485         E5AJ-A2H03
              Communications Board add-on model        E5AJ-A2HM
                            Note    1. No heater burnout alarm is output if the E53-C3 Current Output Unit is used
                                       with the E5AJ.
                                    2. The event input function is not incorporated by models that have a commu-
                                       nications function.
48 X 96mm
Alarm                                                  2 relay output points with heater burnout alarm (see note 1)
Event input                                            2 points (set point selection, RUN/STOP) (see note 2)
Control output                                         Replaceable Output Unit (sold separately)
Model         Communications function   ---            E5EJ-A2HB
                                        RS-232C        E5EJ-A2H01
                                        RS-422         E5EJ-A2H02
                                        RS-485         E5EJ-A2H03
              Communications Board add-on model        E5EJ-A2HM
                            Note    1. No heater burnout alarm is output if the Linear Output Unit is used with the
                                       E5EJ.
                                    2. The event input function is not incorporated by models that have a commu-
                                       nications function.
                                                                                                                      3
Specifications                                                                                           Section 1-3
48 X 48mm
1-3        Specifications
1-3-1 Ratings
E5J
                           Item                                                   Specification
Supply voltage                                               100 to 240 VAC, 50 or 60 Hz            24 V AC/DC,
                                                                                                    50 or 60 Hz
Operating voltage range                                      85 to 110% of supply voltage
Power consumption                        E5AJ                10 VA (at 100 VAC) to                 10 VA (at 24 VAC)
                                                             14 VA (at 240 VAC)                    6 W (at 24 VDC)
                                                                                                                 C)
                                         E5EJ                10 VA (at 100 VAC) to
                                                             14 VA (at 240 VAC)
                                         E5CJ                10 VA (at 100 VAC) to
                                                             12 VA (at 240 VAC)
Input                                                        Thermocouples (K, J, T, L, U, and N) and platinum
                                                             resistance thermometers (JPt100 and Pt100)
CT input                                                     Dedicated CT (E54-CT1 or E54-CT3)
Control output      E5AJ/E5EJ                                Replaceable Output Unit (sold separately)
                    E5CJ                 Relay output        SPST-NO, 3 A at 250 VAC (resistive load)
                                         Voltage output      20 mA at 12 VDC (with short-circuit protection)
                                         Current output      4 to 20 mA DC with a load of 600 Ω max. and a
                                                             resolution of approx. 2600
Control mode                                                 ON/OFF or advanced PID with fuzzy self-tuning and
                                                             auto-tuning
Alarm output                             E5AJ/E5EJ           2 SPST-NO relay output points, 3 A at 250 VAC
                                                             (resistive load)
                                         E5CJ                2 SPST-NO relay output points (with the same common),
                                                             1 A at 250 VAC (resistive load)
Setting method                                               Digital setting with Up Key and Down Key
4
Specifications                                                                                               Section 1-3
                             Item                                                         Specification
Indication method                        E5AJ                    All digital indication (PV: Red, 15 mm; SV: Green,
                                                                 10.5 mm)
                                         E5EJ                    All digital indication (PV: Red, 14 mm; SV: Green,
                                                                 9.5 mm)
                                         E5CJ                    All digital indication (PV: Red, 12 mm, SV: Green 8.0
                                                                 mm)
Event input                                                      Contact input: ON: 1 kΩ max. OFF: 100 kΩ min.
                                                                 No-contact input: ON: residual voltage of 3 V max; OFF:
                                                                 current leakage of 1 mA max.
Other function                                                   • Key protect
                                                                 • Cooling operation/Heating operation
                                                                 • Heater burnout alarm
                                                                 Model with event input (E5J-B)
                                                                 • Set point selection (set point x 2)
                                                                 • RUN/STOP (E5AJ-B and E5EJ-B only)
Ambient operating temperature                                    –10°C to 55°C (with no condensation)
Ambient operating humidity                                       35 to 85%
Storage temperature                                              –25°C to 65°C (with no condensation)
                                                                                                                              5
Specifications                                                                                              Section 1-3
1-3-2 Characteristics
E5J
                 Item                                                      Specification
Indication accuracy                   ±0.5% or ±1°C whichever is larger ± 1 digit max.
                                      Thermocouple K, T, or N at a temperature of –100°C; thermocouple U at ± 2°C ± 1
                                      digit max.
Hysteresis (for ON/OFF control)       0.1 to 999.9°C/° F (in units of 0.1°C/°F)
Proportional band                     0.1 to 999.9°C/°F (in units of 0.1°C/°F)
Integral time                         0 to 3999 s (in units of 1 s)
Derivative time                       0 to 3999 s (in units of 1 s)
Control period                        Relay or voltage output:1 to 99 s (in units of 1 s)
Manual reset value (I = 0)            0.0 to 100.0% (in units of 0.1%)
Alarm setting range                   With K, J, L, or N input: –1999 to 9999° C/°F (in units of 1°C/°F)
                                      With JPt100, Pt100, T, or U input: –199.9 to 999.9° C/°F (in units of 0.1°C/°F)
Sampling period                       500 ms
Output refresh period                 500 ms
Display refresh period                500 ms
Insulation resistance                 20 MΩ min. at 500 VDC (measured with an Output Unit)
Dielectric strength                   2000 VAC, 50/60 Hz for 1 min. between charged terminals different from each other
                                      in polarity
Vibration               Malfunction   10 to 55 Hz, 9.8 m/s2 (1G) 10 min. in X, Y, and Z directions
resistance
   i                    Destruction   10 to 55 Hz, 19.6 m/s2 (2G) 2 hr. in X, Y, and Z directions
Shock resistance        Malfunction   196 m/s2 (20G) 3 times each in 3-axis 6 directions (98 m/s2 (10G) for the relay)
                        Destruction   294 m/s2 (30G) 3 times each in 3-axis 6 directions
Weight                  E5AJ          Approx. 360 g; mounting bracket: approx. 65 g
                        E5EJ          Approx. 280 g; mounting bracket: approx. 65 g
                        E5CJ          Approx. 170 g; adapter: approx. 10 g
Enclosure rating                      Front panel:       E5AJ/E5EJ: IEC standard IP54
                                                         E5CJ: IEC standard IP50 (see note 1)
                                      Rear case:         IEC standard IP20
                                      Terminals:      IEC standard IP00
Memory Protection                     Non-volatile memory
EMC                                   Emission Enclosure:             EN55011 Group 1 class A
                                      Emission AC Mains:              EN55011 Group 1 class A
                                      Immunity ESD:                   EN61000-4-2: 4 kV contact discharge (level 2)
                                                                                   8 kV air discharge (level 3)
                                      Immunity RF-interference:       ENV50140: 10 V/m (amplitude modulated,
                                                                                   80 MHz to 1 GHz) (level 3)
                                                                                   10 V/m (pulse modulated,
                                                                                   900 MHz)
                                      Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
                                      Immunity Burst:                 EN61000-4-4: 2 kV power-line (level 3)
                                                                                   2 kV I/O signal-line (level 4)
Approved standards                    UL1092, CSA C22.2 No. 142
                                      Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) (see note 2)
                                      Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered
                                      terminal cover is mounted.
                               Note   1. The model numbers of the exclusive watertight covers conforming to IP66,
                                         NEMA4 are as follows:
                                         For E5AJ: Y92A-96N; For E5CJ: Y92A-48N; For E5EJ: Y92A-49N
                                      2. Basic insulation is between the input and output.
6
Specifications                                                                                       Section 1-3
                       Note    1. Use the K2CU-FA-GS (with gate input terminals) for the detection of
                                  three-phase heater burnout.
                               2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and al-
                                  ways ON if the alarm is set to 50.0 A.
                               3. No heater burnout detection or heater current value measurement is pos-
                                  sible if the control output is ON for less than 190 ms.
Model with                    Refer to the E5AJ/E5EJ Communications Manual (Z102) for details.
Communications Function
                                              Item                                   Specification
                              Interface                              RS-232C, RS-422, RS-485
                              Communications method                  Half duplex
                              Synchronization method                 Start-stop synchronization
                                                                     (non-synchronization)
                              Communications speed                   1200, 2400, 4800, 9600, and 19200 bps
                              Communications        Writing to       Set point, alarm value, heater burnout alarm
                              item                  Thermac J        value, proportional band, derivative time,
                                                                     integral time, and input shift value
                                                    Reading from     Process value, set point, alarm value, heater
                                                    Thermac J        burnout alarm value, heater current value,
                                                                     proportional band, derivative time, integral
                                                                     time, output value, input shift and error code
                                                                                                                      7
                                                                                                                SECTION 2
                                                                                                    Sensor and Mode Settings
This section describes the sensor and mode settings of the Thermac E5J Temperature Controller that are necessary before
turning on the Thermac E5J Temperature Controller.
       2-1   Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    10
       2-2   Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   10
       2-3   Internal Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         11
             2-3-1 Internal Switch Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  11
             2-3-2 Input Type Selector Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    12
             2-3-3 Alarm Mode Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 13
             2-3-4 Standby Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 14
             2-3-5 Function Selector Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   14
             2-3-6 Key Protection Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       15
                                                                                                                                                           9
Output Units                                                                                  Section 2-2
2-1     Disassembly
                       Before turning on the E5J, set its sensor type and control mode with the inter-
                       nal selectors. Refer to the following illustrations for disassembling the E5J to
                       access the internal switch settings.
Hook
                       After setting the internal switches, insert the internal mechanism into the case
                       until the front panel snaps with the hook.
Bracket
Output Unit
Socket
                       After mounting the Output Unit, be sure to secure it with the mounting bracket
                       provided with the Output Unit.
                       If the E53-C3, E53-C3D, E53-V34, and E53-V35 Linear Output Unit is used for
                       control output, no heater burnout alarm is available.
                       Each Voltage Output Unit is used for driving an SSR as shown in the following
                       illustrations.
10
Internal Switch Settings                                                                                      Section 2-3
                                                                        +       +
                                                         LOAD     SSR       INPUT
                                                                        –       –
+ +
                                        PROTECT           ALL
                                        Key protection
                                        switch            OFF
                                      INPUT               SP                              FUNCTION
                                      Input type                                          Function selector
                                      selector
E5EJ
                                         ALM2
               Top view                  Alarm mode selector 2
                                        PROTECT
                                        Key protection      ALL
                                        switch
                                                            OFF
                                        ALM1
                                        Alarm mode          SP
                                        selector 1
                                        INPUT                                           FUNCTION
                                        Input type selector                             Function selector
                                                                                                                      11
Internal Switch Settings                                                                                               Section 2-3
E5CJ
                    Top view                    ALM2
                                                 Alarm mode selector 2               Bottom view
                                                ALM1                                            PROTECT
                                                 Alarm mode selector 1                          Key protection
                                                                                                switch           SP
                                                INPUT
                                                                                                                 OFF
                                                Input type selector
                                                                                                                 ALL
                                                                                     FUNCTION
                                                                                     Function selector
Note The E5CJ with no alarm does not incorporate ALM1 or ALM2.
INPUT
                                 Note The resistance of the JPt100 at a temperature of 100°C is 139.16 Ω and that of
                                      the Pt100 at a temperature of 100°C is 138.50 Ω.
                            1, 2, 3...    1. To use Fahrenheit, set function selector 4 to ON, which is usually set to OFF.
                                          2. Insert the internal mechanism into the case.
                                          3. Turn on the E5J so that d-u will be displayed on the process value display.
                                             Then press the Up Key so that f will be displayed on the set value display.
                                          4. Turn off the power in two seconds.
                                          5. Draw the internal mechanism from the case and set function selector 4 to
                                             OFF and turn on the E5J.
12
Internal Switch Settings                                                                                Section 2-3
ALM2 ALM1
                                    If the alarm mode switch is set to 1 to 7, the alarm value is set with the deviation
                                    width from the set point as shown in the following diagram.
                                                                          Alarm value
                                                                           10°C/°F
                                    If the alarm mode switch is set to 8 or 9, the alarm value is set with the absolute
                                    value from 0°C/°F as shown in the following diagram.
                                                                               Alarm value
                                                                               110°C/°F
0°C/°F
                                                                                                                    13
Internal Switch Settings                                                                                       Section 2-3
Alarm point
Alarm output
                                It is possible to change the alarm hysteresis (set to 0.2°C before shipping) on the
                                engineering level.
2-3-5 Function Selector Settings
                                All the function selector pins are factory-set to OFF.
                                                  ON
                                                  OFF
                                                                                       To set these pins to
                                                           FUNCTION                    ON, use a small flat-
                                                                                       blade screwdriver.
14
Internal Switch Settings                                                                       Section 2-3
SP OFF ALL
PROTECT
                                 Mode                                   Protection
                           SP               Prohibits all set value changes except the set point. The Level
                                            Key is not available. The Down Key and Up Key are available
                                            only for set point setting.
                           OFF              All keys are available.
                           ALL              Prohibits all set value changes. The Level Key, Down Key, and
                                            Up Key are not available.
                                                                                                              15
                                                                                                                SECTION 3
                                                                                                  Settings Before Operation
This section describes the settings of the Thermac E5J Temperature Controller that are necessary before operating the
Thermac E5J Temperature Controller.
      3-1    Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   18
      3-2    Setting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    19
      3-3    List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     20
      3-4    Parameters on Display Level 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            22
      3-5    Parameters on Display Level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            23
                                                                                                                                                         17
Nomenclature                                                                                                         Section 3-1
3-1      Nomenclature
                                       The following is the front panel of the E5AJ-A2HB. The front panels of the E5EJ
                                       and E5CJ are similar to the front panel of the E5AJ-A2HB.
                                                Process Value (PV) display
                                                Displays not only the process
                                                value but also indicates the pa-
      Stop indicator                            rameter being displayed on the
      Lit when the E5J is not operating.       SV display and error messages.            Set Value (SV) display
      The E5CJ does not incorporate this                                                  Displays the set temperature
      indicator.                                                                          and other parameters.
                              Note Refer to the E5AJ/E5EJ Communications Manual for the operation of E5J
                                   models incorporating a communications function.
18
Setting Flowchart                                                                                                           Section 3-2
Display Level 0                           Parameters that are changed frequently are ranked as display level 0 parame-
                                          ters.
Display level 1                           Parameters that are not changed frequently are ranked as display level 1 pa-
                                          rameters.
Engineering Level                         Parameters that are changed with only a few applications are ranked as engi-
                                          neering level parameters.
OFF ON
                              Level Key
                              Press for 1 s min.
       Display level 0                                 Display level 1
                              Level Key
                              Press for 1 s min.
                                                                                                                                           19
List of Parameters                                                                                  Section 3-3
                     SP-0     Set point 0         Set point lower limit   0           For models incorporating an
                                                  to set point upper                  event input function.
                                                  limit (°C/°F)
                     SP-1     Set point 1         Set point lower limit   0           For models incorporating an
                                                  to set point upper                  event input function.
                                                  limit (°C/°F)
                     SP-2     Set point 2         Set point lower limit   0           For models incorporating an
                                                  to set point upper                  event input 2 function.
                                                  limit (°C/°F)                       Displayed and can be set if
                                                                                      the default value is changed
                                                                                      on the engineering level.
                     SP-3     Set point 3         Set point lower limit   0           For models incorporating an
                                                  to set point upper                  event input 2 function.
                                                  limit (°C/°F)                       Displayed and can be set if
                                                                                      the default value is changed
                                                                                      on the engineering level.
                     in-S     Input shift value   –199.9 to 999.9 °C/°F 0.0           Displayed and can be set if
                                                                                      the default value is changed
                                                                                      on the engineering level.
20
List of Parameters                                                                                  Section 3-3
                     oFr     Manual reset value   0.0 to 100.0 %        50.0         Displayed and can be set if
                                                                                     the integral time is set to 0
                                                                                     when the E5J is in
                                                                                     advanced PID operation.
Note The value in the parentheses is the E5J--F setting before shipping.
                                                                                                                     21
Parameters on Display Level 0                                                                                Section 3-4
(Alarm 1 setting)
(Alarm 2 setting)
Set Point Setting (°C or °F)   It is possible to alter the present set point (SP0 or SP1).
al1 and al2 (°C or °F)       The alarm mode is factory-set to the upper limit alarm (deviation). It is possible to
                               change the alarm mode with the alarm mode selector. Refer to 2-3-3 Alarm
                               Mode Setting. The alarm value can be set with the deviation width or absolute
                               value according to the alarm mode.
                                           Deviation alarm                                  Absolute value alarm
                               Upper and lower limit alarm, upper limit         Absolute value upper limit alarm and
                               alarm, lower limit alarm and upper and           absolute value lower limit alarm.
                               lower limit range alarm.
                                      Set with the deviation width from           Set with the absolute value from 0°C/°F.
                                      the set point
                                                                                          Alarm value
                                                 Alarm value                               110°C/°F
                                                  10°C/°F
                                                                                       0°C/°F
                                         Set point (SP) 100°C/°F
22
Parameters on Display Level 1                                                                          Section 3-5
(Hysteresis setting)
                                                                 Displays if I is 0.
                                                             (Manual reset value
                                                             setting)
                                                                                                               23
Parameters on Display Level 1                                                                            Section 3-5
o Output Value Display       The output value is displayed within a range of 0.0% to 100.0%.
cp Control Period Setting    It is possible to set the control period within a range of 1 to 99 s. The control peri-
                             od is the period required by the E5J to turn ON and OFF its relay output or volt-
                             age output. The ON period increases in proportion to the output value. If the con-
                             trol period is short, smooth control operation will be possible although a short
                             control period shortens the life of the relay if relay output is used. Therefore, the
                             control period should not be less than 20 s if relay output is used. The following
                             are output examples with an output value of 50.0 %.
                                                      5s                             10 s
                                                 ON                            ON
OFF OFF
hys Hysteresis Setting (°C   It is possible to set the hysteresis for the E5J in ON/OFF control operation with-
or °F)                       in a range of 0.1° to 999.9°C/°F.
                                                                        Hysteresis
                                              Heating
                                              control        ON
                                              (Reverse)     OFF
                                                      Low temperature   Set point    High temperature
                                                                            Hysteresis
                                              Cooling
                                                             ON
                                              control
                                              (Normal)       OFF
                                                      Low temperature   Set point    High temperature
sp0, sp1, sp2, and sp3   It is possible to set sp-0 (set point 0), sp-1 (set point 1), sp-2 (set point 2), and sp-3
(E5J-B Only)               (set point 3) all in Celsius or Fahrenheit regardless of the set point presently se-
                             lected. To select the set point, open or short-circuit terminals EV1 and EV2. Re-
                             fer to Section 7 Event Input Function for details.
in-s Input Shift Value       It is possible to set the input shift value within a range of –199.9° to 999.9°C/°F.
                             When an input shift value is set, the process value will be the input value added
                             with the shift value.
Example                          Input                        Input shift value                        Process value
                              100°C          0 (no compensation)                                      100°C
                                             10.0 (compensation value)                                110°C
                                             –10.0 (compensation value)                               90°C
                             After the input shift value is set, the it is effective even if the input shift value dis-
                             play is turned off on the engineering level.
ct Heater Current Value      It is possible to set the heater current value within a range of 0.0 to 55.0 A. If the
Display (E5J-H Only)       current value exceeds 55.0 A, ffff will be displayed on the set value display.
                             The heater current will be processed and displayed if the control output is ON.
hb Heater Burnout Alarm      It is possible to set the heater burnout alarm value within a range of 0.0 to 50.0 A,
Value Setting (E5J-H       which will be used to detect heater burnout. If the heater burnout alarm value is
Only)                        set to 0.0 A, the heater burnout alarm output will be always OFF. If the heater
                             burnout alarm value is set to 50.0 A, the heater burnout alarm output will be al-
                             ways ON. Refer to Section 8 Heater Burnout Detection for details.
                             When the E5J is in advanced PID with fuzzy self-tuning mode, the following
                             parameters (p, i, d, ofr) will not be displayed (i.e., there is no need to set the
                             following parameters). The fuzzy self-tuning always adjusts the PID constants to
                             the most suitable values according to the characteristics of the controlled de-
                             vice.
24
Parameters on Display Level 1                                                                    Section 3-5
p Proportional Band Setting   It is possible to set the proportional band within a range of 0.1 to 999.9°C/°F.
i Integral Time Setting       It is possible to set the integral time within a range of 0 to 3999 s.
d Derivative Time Setting     It is possible to set the derivative time within a range of 0 to 3999 s.
ofr Manual Reset Value        It is possible to set the necessary output value when the E5J is in constant op-
Setting                       eration within a range of 0.0% to 100.0%. The E5J will be balanced with a devi-
                              ation between the set point and process value in P or PD control mode. This
                              deviation is called offset. The offset can be removed by changing the manual
                              reset value.
                                                                                                            25
                                                                                                                                SECTION 4
                                                                                                                            Fuzzy Self-tuning
This section provides the procedures required to adjust all PID constants using fuzzy self-tuning according to the characteris-
tics of the device for ideal temperature control.
                                                                                                                                                           27
Fuzzy Self-tuning Operation                                                                                             Section 4-1
          Set point
                             Max. tempera-                   P X 1.27
                             ture slope R
                                                                   In step response tuning, control is completely imposed step-
                                             Tuning at startup     wise to measure the maximum temperature slope (R) and
                                                                   dead time (L), and the most ideal PID constants for the de-
                                                                   vice are obtained from R and L.
                                     Dead time L
                               Note Be sure to turn on the power supply to the load either before or simultaneously
                                    with the start of Temperature Controller operation. When using the E5AJ-A2HB
                                    or E5EJ-A2HB, you can change the RUN/STOP setting to RUN via event input
                                    2 after supplying power to the load.
                                    Dead time will be measured from the time the Temperature Controller starts
                                    operating. If a load such as a heater is turned on after the Temperature Control-
                                    ler is turned on, dead time longer than the actual value will be measured and
                                    inappropriate PID constants will be obtained. If an extremely large amount of
                                    dead time is measured, the control amount will be set to 0% for a short period of
                                    time before being returned to 100%, and the constants will then be retuned.
                                    Retuning is performed only for large amounts of dead time, so be sure to follow
                                    the precaution given above when starting operation.
28
Fuzzy Self-tuning Operation                                                                                               Section 4-1
SRT Startup Condition                 SRT will be ON if the following conditions are satisfied simultaneously when the
                                      Temperature Controller is turned on or the set point is changed.
                                         At the time the Temperature Controller                  At the time set point is changed
                                                     starts operating
                                        1) The set point at the time the                      1) The new set point is different from
                                           Temperature Controller starts operating               the set point used at the time SRT
                                           is different from the set point used at               was executed last (see note).
                                           the time SRT was last executed (see                2) The set point changing range is
                                           note).                                                larger than the present
                                        2) The difference between the set point                  proportional band value (P) x 1.27
                                           and the process value at the time the                 + 4.
                                           Temperature Controller starts operating            3) The process value is in stable
                                           is larger than the present proportional               condition before the set point is
                                           band value (P) x 1.27 + 4.                            changed.
                                        3) The process value at the time the                  4) A larger set point value is set in
                                           Temperature Controller starts operating               reverse operation and a smaller
                                           is smaller than the set point in reverse              set point is set in normal operation.
                                           operation and larger than the set point
                                           in normal operation.
                             Note The last SRT-executed set point is set to 0 before shipping and when changing
                                  from advanced PID control to advanced PID control with fuzzy self-tuning.
Imposition Completion                 In order to prevent overshooting, the step controlled amount must be imposed
Condition of Step Control             continuously only while the present deviation is the same as or greater than the
Amount
                                      value obtained from the proportional band (P)1.27. The step control will not be
                                      applied when the deviation becomes smaller than this value.
PID Constant Refreshing               If the step control amount is applied before the maximum temperature slope (R)
Conditions                            is obtained, SRT will not renew any PID constant. If the proportional band ob-
                                      tained from the R and L values that were measured before the imposition had
                                      been completed is larger than the present proportional band, the PID constants
                                      will be renewed because the measured value is in the direction towards the suit-
                                      able proportional band value, and the set point at that time will be the SRT-
                                      executed set point.
DT at the Time of Operation           If there is overshooting at the time the Temperature Controller restarts operating
Start and Set Value Change            after SRT has been executed, DT adjusts the PID constants so that the set point
                                      response waveform will be as close as possible to the most ideal response wa-
                                      veform after it is deemed that there has been a characteristics change in the con-
                                      trol system.
             Set point
                                      Stability judge-
                                      ment time
                                                                                     The set point response waveform
                                                                                     at the time the Temperature Con-
                                 Measurement of                                      troller restarts operation will be
                                 set point response                                  closer to the most ideal response
                                 waveform
                                                                                     waveform.
                         PID before tuning                 PID after tuning
                                                                                                                                     29
Fuzzy Self-tuning Operation                                                                                                Section 4-1
DT at the Time of External           After the process value reaches the set point and becomes stable, if the process
Disturbance Response                 value is disturbed and the disturbance exceeds the stable range, the distur-
                                     bance is regarded as external disturbance At the time of disturbance, DT mea-
                                     sures the external disturbance waveform and adjusts the PID constants so that
                                     the external disturbance waveform will be as close as possible to the most ideal
                                     external disturbance response waveform.
                                                                                      Stable range
                                                             External disturbance     (set to 15.0°C before shipping)
                            External disturbance
       Set point
                                              Stability judge-
                                              ment time
                                                                 The external disturbance response waveform is approaching to
                                      Measurement of             the most ideal response waveform even if the same kind of
                                      external disturbance
                                      response waveform          external disturbance reoccurs. The waveform will not, however,
                                                                 change if the most ideal PID constants are already set.
Startup Conditions of DT             DT is used to monitor the control waveform if there is external disturbance or
                                     SRT does not work at the time the Temperature Controller starts operating or at
                                     the time of set point change. If the measured waveform is not an ideal waveform,
                                     DT will be ON. If either one of the following conditions is satisfied, the control
                                     waveform will be monitored.
                        1, 2, 3...    1. SRT Startup conditions 3 and 4 on page 29 are satisfied but neither 1 nor 2 is
                                         satisfied.
                                      2. There has been an external disturbance exceeding the stable range after
                                         the process value was in stable condition.
Extreme value
                                                                                              Stable range
            Set point                                                                         (set to 15.0°C before shipping)
                                              Measurement of
                                              hunting waveform
Startup Conditions of HT             HT will be ON when there is hunting with four or more maximum temperature
                                     values while SRT is not being executed.
                            Note If the periodic temperature changes of the application exceed the stable range
                                 (set to 15.0°C at the factory) due to continuous external disturbance (i.e., the
                                 temperature is affected by an external disturbance before stabilizing after a pre-
                                 vious external disturbance (refer to figure A below)), the user should change the
                                 stable range to a value greater than the temperature changing range, otherwise
30
Troubleshooting                                                                                       Section 4-2
                                 HT may change the PID constants even though the PID constants are ideal for
                                 the control system. Refer to 9-1 Engineering Level for details.
External disturbance
External disturbance
                                                                               T1<T2
                                                          T1    T2
4-2      Troubleshooting
                                 Fuzzy self-tuning may not exhibit its full capability due to the characteristics and
                                 conditions of the controlled object.
                                 Refer to the following table for troubleshooting when Unit operation is not
                                 smooth.
                                                                                                                   31
Terminology                                                                                                  Section 4-3
4-3 Terminology
                                    If the measured value continuously coincides with the set point, it can be said
                                    that the measured value is stable. The measured value will not continuously
                                    coincide perfectly with the set point if there is noise inference. It is, however, pos-
                                    sible to make the measured value stay within a permissible range called the
                                    stable range. Even if the temperature is within the stable range, the Temperature
                                    Controller may respond to external disturbance or hunting. Therefore, it cannot
                                    be said that the temperature is stable unless the temperature stays within the
                                    stage range continuously for a certain time. This time is called stability judge-
                                    ment time. Like PID constants, stability judgement time is adjusted with fuzzy
                                    self-tuning according to the characteristics of the object to be controlled. Fuzzy
32
Terminology                                                                                                             Section 4-3
                                   self-tuning will not be activated if the temperature is stable because the Temper-
                                   ature Controller deems that temperature control is smooth.
                                                                                       Stable range
         Set point
                                                                                       Stable range
Stable Stable
4-3-2 Hunting
                                   If the PID constants are not suitable to the controlled device, the measured value
                                   will fluctuate and will not coincide with the set point, this phenomenon is called
                                   hunting. Hunting is also called cycling.
Set point
4-3-5 Interference
                                   If devices, such as heaters, controlled by different temperature controllers are
                                   physically close to one another, the heaters are mutually influenced and the tem-
                                   perature of each heater are affected. This phenomenon is called interference. If
                                   there is serious interference, it will be difficult for each temperature controller to
                                   control the device, and special controlled methods taking this interference into
                                   consideration will be required.
                                                                                                                                33
Terminology                                                                       Section 4-3
4-3-6 Startup
                Startup means that the Temperature Controller starts operating. The following
                conditions are required to operate the Temperature Controller.
                    • The Temperature Controller must be turned ON.
                    • No sensor error has occurred.
                    • If a model with event input 2 is used, event input 2 must be set to RUN.
                      Event input 2 is set to RUN before shipping.
                The Temperature Controller will not start operating until all the above conditions
                are satisfied.
34
                                                                                                                         SECTION 5
                                                                                                             Installation and Wiring
This section describes the installation and wiring of the Thermac E5J Temperature Controller.
       5-1   Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     36
             5-1-1 Dimensions and Mounting Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                36
             5-1-2 Mounting Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      36
       5-2   Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   37
             5-2-1 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               37
       5-3   Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               38
                                                                                                                                                               35
Installation                                                                                    Section 5-1
5-1      Installation
                             Install the E5J in the following places.
                                                                    É
                                                                    É
                                                                             Mounting bracket
                                                                    É
                                                        Panel
                                                                    É
                                               Watertight packing   É
E5CJ                         Open a square hole in the panel to which the E5CJ is to be mounted, mount the
                             E5CJ, attach the adapter provided with the E5CJ as shown in the following il-
                             lustration to reduce the space between the E5CJ and panel, and secure the
                                                                É
                             adapter with the tightening screw.
                                                    Panel       É
                                                                É
                                                                        Adapter
                                                                É
                                                                É   Mounting screw
36
Wiring                                                                                          Section 5-2
5-2      Wiring
                                Refer to the terminal arrangements to wire the E5J. Before wiring, observe the
                                following.
                   1, 2, 3...    1. When connecting extension wires to the thermocouple, use proper compen-
                                    sating lead wires.
                                 2. When connecting extension wires to the platinum resistance thermometer,
                                    use three low-resistance wires of equal resistance.
                                 3. The power supply must not be influenced by noise. If necessary use a noise
                                    filter.
                                 4. All the wires connected to the input circuitry must be separated from the
                                    wires connected to the power supply or output circuitry.
                                 5. Use shielded wires where static inductance noise is present.
                                 6. Twist the input wires evenly and closely if there is any electromagnetic in-
                                    ductance noise.
5-2-1 Connection
With Solderless Terminals       Use solderless terminals for M3.5 screws. The terminal screws are M3.5 x 8 self-
                                up screws.
Solder-dipped Leads It is possible to connect solder-dipped leads to the terminals with ease. The
                                                            ÉÉÉ
                                length of each bare lead wire should be 6 to 8 mm.
ÉÉÉ 6 to 8
                                                                                                            37
Terminal Arrangement                                                                                                                          Section 5-3
38
Terminal Arrangement                                                                                                    Section 5-3
                                     2. Only the heater burnout alarm will be output from the alarm output 1 termi-
                                        nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
                                        output if the heater burnout alarm value is set to 0.0 A.
E5CJ Standard Model
                                                                          Control output (OUT)
                                                                              +
                                                                                   10
                                                 See note 1.               12 VDC
                                                                                        Voltage Output Unit
                                                                               –        (20 mA max.)
                                 Event input 1 (EV1) Exter-                         9
                                 nally selects the set point.                 +
                                                                                   10 Current Output Unit
                                 open
                                                                                      4 to 20 mA DC
                                                                              –
                                 short-circuit                                     9 (with a load of 600 Ω max.)
         100 to 240 VAC, 50 or 60 Hz, 12 VA
         or                                      5                                 10 Relay Output Unit
                                                                14 +                  3 A (resistive load)
         24 VAC, 50 or 60 HZ, 10 VA                                                   at 250 VAC
         24 VDC 6 W                              4                                 9
                     (Heater burnout alarm                      13 –
        See note 2. and temperature alarm)                                                  A
                                                 3                                  8
                          Alarm        (ALM1)                   12
                          output 1                                                      –   B
                                                 2                                  7
                          Alarm output 2                        11
                                                                                        +   B
                                                 1                                  6
                          1 A (resistive load)
                          at 250 VAC
                                                                                  Use the E54-CT1 with a hole
                                                                     CT           diameter of 5.8 mm or E54-CT3 with a hole
                                                                                  diameter of 12 mm (both sold separately).
                          Note       1. The event input terminals and voltage output and current output terminals
                                        are not insulated.
                                     2. Only the heater burnout alarm will be output from the alarm output 1 termi-
                                        nals if alarm mode switch 1 is set to 0. Only the temperature alarm will be
                                        output if the heater burnout alarm value is set to 0.0 A.
                                     3. A simple model with no alarm does not incorporate any event input or alarm
                                        output. A simple model with an alarm function does not incorporate any
                                        event input.
                                                                                                                                39
                                                                                                                                SECTION 6
                                                                                                                             Troubleshooting
This section describes the troubleshooting of the Thermac E5J Temperature Controller.
                                                                                                                                                        41
Troubleshooting                                                                                               Section 6-2
                            Note If the input is within the possible controlling range but exceeding the possible
                                 display range (–1999 to 9999), (((( will be displayed if the value is smaller than
                                 –1999 and )))) will be displayed if the value is larger than 9999, at which time, the
                                 control output and alarm output will work normally.
6-2        Troubleshooting
                                    Refer to the following table for troubleshooting.
42
Troubleshooting                                                                                            Section 6-2
                                                                                                                           43
                                                                                                                   SECTION 7
                                                                                                           Event Input Function
This section describes how the event input function of the Thermac E5J Temperature Controller works.
                                                                                                                                                    45
Event Input Function                                                                                            Section 7-1
EV1
Short-circuit
COM
                                                                      Set point 1
                                                                      (SP1)
           Displays the set point
           currently selected.
                                                                                  SP2 and SP3 can be displayed
                                                                      Set point 2 only when the set point selec-
                                                                      (SP2)       tion is selected with the event
                                                                                  input 2 selection (set to RUN/
                                                                                  STOP before shipping) on the
                                                                      Set point 3 engineering level. Refer to Sec-
                                                                      (SP3)       tion 9 Engineering Level Set-
                                                                                  tings for details.
                                    The set point on display level 0 and that on display level 1 are synchronized. In
                                    the above example, if the set point on display level 0 is changed from 200°C to
                                    250°C, the set point 1 value on display level 1 will also change to 250°C.
46
Event Input Function                                                                                    Section 7-1
+24 V
                                     Internal circuitry
                                                               470 Ω
                                                                          3 kΩ
                                                                                            EV* Flow current:
                                                                                                7 mA approx.
                                                          VF = 1.2               VF = 0.6
                                                                                            COM
                                     0V
                          COM                                              COM
                          ON: A resistance of 1 kΩ max.                    ON: A residual voltage of 3 V max.
                          OFF: A resistance of 100 kΩ min.                 OFF: A current leakage of 1 mA max.
                       The following table lists the event input terminal numbers for each model.
                                  Model                                E5AJ/E5EJ                       E5CJ
                       Input terminal
                       EV1                                    20                            14
                       EV2                                    19                            ---
                       COM                                    17                            13
                                                                                                                 47
                                                                                                          SECTION 8
                                                                                              Heater Burnout Detection
This section describes the basic features of heater burnout detection and necessary steps that should be taken at the time of
heater burnout, as well as the method of obtaining heater burnout alarm values.
                                                                                                                                                   49
Heater Burnout Procedures                                                                         Section 8-2
50
Heater Burnout Alarm Value                                                                              Section 8-4
                                                                                                     To heater
                                                   AC power supply
CT
                                            CT
                To the CT input terminals of the
                E5J
                              If the difference between the normal heater current value and heater burnout
                              current value is comparatively small, heater burnout detection will not be stable.
                              For stable detection, the difference must be 1.0 A minimum if the heater current
                              consumption is less than 10.0 A and it must be 2.5 A minimum if the heater cur-
                              rent consumption is 10.0 A or more.
                              The heater burnout alarm value can be set within a range of 0.0 to 50.0 A. If the
                              alarm value is set to 0.0 A or 50.0 A, no heater burnout detection is possible. The
                              alarm output is always OFF if the alarm value is set to 0.0 A and always ON if the
                              alarm value is set to 50.0 A.
                                                                                                                     51
Heater Burnout Alarm Value                                                                            Section 8-4
                              The normal heater current value should be 50.0 A max. The heater current value
                              can, however, display up to 55.0 A. If the current value exceeds 55.0 A, CT input
                              overflow will result and ffff will be displayed.
                                                                 CT input
                                                                 overflow
                                                                                                   200 VAC
                                                    Normal heater
                                                    current value
                                                                                                   CT
200 VAC
                                                      Heater burnout
                                                      current value                              CT
                                                                            Disconnect
Example 2                     In this example, 400-W, 1700-W, and 2000-W heaters at 200 VAC are con-
                              nected in parallel and the difference between the normal current value and heat-
                              er burnout current value is less than 2.5 A.
                 1, 2, 3...    1. Obtain the normal current value and heater burnout current value in ad-
                                  vance as follows:
                                  Normal current = (400 + 1700 + 2000)  200 = 20.5 A
                                  Heater burnout current = 20.5 – 400  200 = 18.5 A
                                  Normal current – heater burnout current = 20.5 – 18.5 = 2.0 A (Stable detec-
                                  tion is not possible because the value is not 2.5 A or more.)
                               2. For stable hater burnout detection, in such a case, increase the number of
                                  turns of the wire passing through the CT as if apparent current value in-
52
Heater Burnout Alarm Value                                                                   Section 8-4
Heater wire
                             3. Obtain the heater burnout alarm value using the method in example 1.
                                Apparent normal current = (400 + 1700 + 2000)  200 x 2 = 41.0 A
                                                            Normal heater
                                                            current value
                                                                                                       53
                                                                                                           SECTION 9
                                                                                              Engineering Level Settings
This section describes the parameters that can be changed on the engineering level. These parameters should be changed only
when the values set before shipping do not suit the application. After these parameters are changed on the engineering level,
record the contents of the changes for your future reference.
                                                                                                                                                      55
Engineering Level Parameter List                                                                           Section 9-2
         15.0
                ALFA    Alpha                         0.00 to 1.00               0.65
                SL-L    Set point lower limit         Set range lower limit to   –200 (–300)
                        value                         set point upper limit
                                                      value (see note 1).
                                                      (°C/°F)
56
Engineering Level Parameter List                                                            Section 9-2
                                                                                                       57
Engineering Level Parameters                                                                     Section 9-3
(°C/°F selection)
(Alpha setting)
58
Engineering Level Parameters                                                                                   Section 9-3
rdu °C/°F Selection         To change the temperature display unit from °C to °F, press the Up Key so that f
                             will be displayed in the set value display.
                                                             SV               SV
                                                                                        c: °C
                                                                                        f: °F
sbit Stop Bit                Use this parameter to change the stop bit length.
s.t-b Stable Range (°C/°F)   This parameter is used to decide conditions under which fuzzy self-tuning oper-
                             ates and can be set within a range of 0.1 to 999.9. If the absolute value of the
                             deviation (the difference between the process value and set point) is within the
                             stable range, temperature control operation is deemed smooth and fuzzy self-
                             tuning will not start.
                                                                                                                   Stable
                             Set point                                                                             range
                                                         Stable
                                                                                   Fuzzy self-tuning
alfa (α) PID Control Type    By adjusting internal parameter α of advanced PID within a range of 0.00 to 1.00,
                             PID control such as derivative preceding PID or proportional preceding PID (I-
                             PD) control will be possible.
                                                                       α = 0.00 (Derivative preceding PID)
Set point
α = 0.65
                                                                        α = 1.00
                                                                        (Proportional preceding PID)
                             To increase the set point response speed, decrease the value of parameter α. If
                             the value of parameter α is decreased, however, the overshooting value will in-
                             crease.
                                                                                                                            59
Engineering Level Parameters                                                                                  Section 9-3
ret Automatic Return of      By setting automatic return of display mode, the display will return to the normal
Display Mode (Return Time)   operation display (on level 0 displaying the process value or set point) if no key is
                             operated for the time set with this parameter. The return time can be set within a
                             range of 0 to 99 s. If the return time is set to 0 s, this function will not work. The
                             return time is set to 0 s before shipping.
rest Standby Sequence        It is possible to select the restart conditions of the standby sequence of the alarm
Reset Method                 attached with standby sequence. If this parameter is set to 0, the standby se-
                             quence will restart when the set point, alarm value, or input shift value is
                             changed or the moment the E5J starts operating including the moment the
                             E5J is turned on. If this parameter is set to 1, the standby sequence will restart
                             only the moment the E5J is turned on. The following timing chart is an example
                             of a lower limit alarm attached with standby sequence.
                                                   Alarm point
                                                                                         Set value
                                                                                         change
ins Input Shift Display     It is possible to select to display or not to display the input shift function on display
                             level 1 with this parameter.
alh1 Alarm 1 Hysteresis      It is possible to adjust alarm sensitivity with both these parameters within a range
and alh2 Alarm 2             of 0.1 to 999.9. Change the alarm sensitivity of the E5J if the alarm output chat-
Hysteresis                   ters.
                             The alarm output will be OFF when the process value is within the alarm hystere-
                             sis range when the E5J restarts (e.g., when the E5J is turned on).
sll Set Point Lower Limit   It is possible to limit the set point changeable range with both these parameters.
Value (°C/°F) and slh Set   For example, if the set point lower limit value is set to 0°C and the set point upper
Point Upper Limit Value      limit value is set to 400°C, the set point can be changed only between 0°C and
(°C/°F)
                             400°C.
60
Engineering Level Parameters                                                                     Section 9-3
eu2 Event Input 2 Type   It is possible to select the function of event input 2. If 0 (set point value selection)
Selection                 is selected, sp2 and sp3 will be displayed on display level 1 and if 1 is selected
                          RUN/STOP will be selected. When 0 is selected, the set point can be selected
                          from the following.
                                                            EV1 20
EV2 19
COM 17
                                                                                                              61
                                                                                                                                     SECTION 10
                                                                                                                                      Auto-tuning
This section describes how to execute auto-tuning.
                                                                                                                                                        63
Changing Parameters during Auto-tuning                                                                Section 10-4
                 1, 2, 3...    1. Turn ON pin 3 of the function selector switch to select the advanced PID con-
                                  trol mode (refer to Section 2-3-5).
                               2. Press the Level Key and the Display Key simultaneously for 1 s or longer to
                                  start auto-tuning.
                                                                       Auto-tuning          SP1
                                                      SP0
                                         Set point
                                                               Auto-tuning started.
                                                               Scale changes disabled here.
64
                                                  Appendix A
                                Dimensions/Mounting Holes
E5AJ
Dimensions
              96 x 96                   12             98                              91 x 91
112
Mounting Holes
                                +0.8
                           92    0
                                             92 +0.8
                                                 0
                                                                                      92 +0.8
                                                                                          0
                120 min.
                                                                                                         65
Dimensions/Mounting Holes                                                                        Appendix A
E5EJ
Dimensions
                    48                      12          98
                                                                                          44
96 112 91
Mounting Holes
                              +0.6
                         45    0
                                                                             +1
                                                        (48 x units – 2.5)    0
                                          +0.8                                            +0.8
                                     92    0
                                                                                     92    0
120 min.
E5CJ
Dimensions
                   48 x 48                  9.5        100
                                                                                  44.8 x 44.8
58
66
Dimensions/Mounting Holes                                                                          Appendix A
Mounting Holes
                                   +0.6
                              45    0                                      +1
                                                      (48 x units – 2.5)    0
                                               +0.6
                                          45    0                                    +0.6
                                                                                45    0
                    60 min.
Terminal Covers
112
58
                                                                                                           67
Dimensions/Mounting Holes                                    Appendix A
112
68
                                                          Index
          A                                                            E
                                                             engineering level
advanced PID                                                   alarm hysteresis, 60
  function, 2                                                  automatic return of display mode, 60
  setting, 14                                                  communications, 59
  setting with fuzzy self-tuning, 14                           data bit length, 59
                                                               input shift display, 60
alarm mode                                                     parameters, 19
   changing, 22                                                parameters table, 56
   setting. See settings                                       parity check, 59
   standby sequence. See settings                              PID control type, 59
                                                               selecting temperature display, 59
auto-tuning                                                    settings, 56
  force-ending, 64                                             stable range, 59
  parameters, 64                                               standby sequence reset, 60
  preventing, 64                                               stop bit, 59
  starting, 64
                                                             event input 2, 33
automatic return of display mode. See engineering level        selecting, 61
                                                             event input function, 2
                                                               parameters, 24
                                                               selecting RUN/STOP, 46
          C
                                                               selecting set point, 46
                                                               signal input method, 47
                                                             external disturbance, definition, 32
communications function, specifications, 7
          D
                                                               features, 28
                                                               function, 2
                                                                                                      69
                                                      Index
          I                                               set point
                                                             See also event input function
                                                             adjusting changeable range, 60
installation
                                                             setting type, 22
   mounting, 36
   precautions, 36                                        settings
integral time range, 25                                      advanced PID control, 14
                                                             alarm mode selection, 13
interference, definition, 33                                 functions. See functions
internal switches, sensor type and control mode, 10          fuzzy self-tuning, 14
                                                             internal switches, 11, 12
                                                             key protection switch, 15
          K-M
                                                             selecting input type, 12
                                                             selecting output unit, 10
                                                             sensor type and control mode, 10
key protection switch, setting, 15
                                                          specifications
manual reset value, 25                                      general, table, 5
models, 2                                                   operating characteristics, table, 6
 Communications Boards, 4                                   output unit, table, 6
 communications function, limitations, 3, 4
 standard, 3                                              SRT. See step response tuning
          P
                                                                    T
parameters
  engineering level, 19                                   terminal arrangement, 38
  levels, 19
  setting, 19                                             Terminal Covers, 67
  tables, 20                                              troubleshooting, 30
PID, setting constants, 32                                   controller and sensor error, 43
                                                             table, 42
proportional band range, 25
          R                                                         W
return time, 60                                           watertight cover, 2
RUN, selection, 46
                                                          wiring
                                                            current transformer, 51
                                                            precautions, 37
          S                                                 terminal arrangement, 38, 39
                                                            using solder-dipped leads, 37
self-diagnostic function, 42                                using solderless terminals, 37
70
                                          Revision History
                                         Operation Manual
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
                                                              Revision
                                                               code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version for manuals designated as E1 revisions.
                                                                                                                    71
                                         Revision History
72