1 General
1.1 Documentation
The busbar trunking system software has to be configured with a BIM
software, for example, REVIT (R) of Autodesk.
Views of the 3D busbar run layout, plan views, side views, and BOMs have to
be elaborated.
Before start of delivery, the complete execution plans must be submitted
for approval in digital form, for example as FC, IFC or PD file.
Installation may only be started according to the released diagrams.
For the busbar trunking systems used, all components must be listed in a
list of devices.
The current installation instructions must be made available to the
installer in an app suitable for devices with an up-to-date Android or iOS
operating system. This app also provides the identification and visual
documentation of the joints (bolt record) that is handed over to the
customer to document the high-quality installation.
The documentation must be submitted in printed form with 4 copies in A4
format.
The final revision must be additionally supplied on data carriers in PDF
format.
This item shall also include all costs for the measurement of fit
components on site.
2 Products
2.1 Basic description busbar trunking syst. 1100A to 5000A (AC), 1900A to
6920A (DC)
The busbar trunking systems shall be delivered and installed as design
verified low-voltage switchgear and control gear assemblies according to
IEC/EN 61439-1 and -6, ready for connection.
The following descriptions are integral parts of the calculation and the
contract. They must be considered in the descriptions of the individual
systems and operational equipment, even if they are not mentioned in detail
anymore.
The busbar trunking system must be suitable for power transmission, for
example, between transformer and low-voltage main distribution, and for
power distribution as an overall power supply both for horizontal and
vertical installation.
The busbar trunking system must consist of standardized system components
such as:
· Straight trunking units with and without tap-off points
· Feeder units for transformer, distribution board and cable infeeds
· Junction units with elbow, offset elbow, knee, offset knee, Z-units and
T-units
· Tap-off units
· Accessories
· All straight trunking units must be available ex works in lengths up to
max. 3.2m. Flexible junction units, and junction units as cable
connections are not allowed.
· Expansion compensation units and fixed points shall be configured as
required.
· The trunking units are protected against incorrect mounting (anti-
rotation feature for correct phase sequence).
· The busbar trunking systems with tap-off openings must be equipped with
tap-off units as required. The position and number of tap-off points
must be selectable.
· If necessary, it must be possible to provide the busbar trunking system
with an asbestos-free fire barrier towards the wall or ceiling opening,
certified according to EN 1366-3 and optionally conforming to the fire
resistance classes EI90 or EI120 according to EN 13501 (formerly S90 and
S120).
· If necessary, it must be possible to offer the busbar trunking system
with the functional endurance classes E60 or E90 according to DIN 4102-
12.
· The fire barrier for functional endurance must be mounted by the
installer on site. The functional endurance certificate must be enclosed
with the offer.
· The housing consists of zinc coated sheet steel.
· The individual system components must be connected by fitting a hook
into a bolt, and tightening a state-of-the-art bolt-type terminal. The
required torque for the clamping connection is 80 Nm.
· The busbars must be made of aluminum or copper, and be insulated along
their entire length.
· The aluminum busbars are nickel- or tin-plated, the copper busbars are
tin-plated. The insulation is made of highly heat-resistant insulation
coating
· The conductor cross-sections must not be below the values given in the
technical data.
· For operation with DC voltage, the product must be appropriately
qualified and clearly marked from the outside.
2.2 Conformity and test evidences
The manufacturer of the busbar trunking system has to run and furnish
evidence of a certified quality management system according to EN/ISO 9001.
Certificates or declarations of conformity must confirm the following
qualifications for the entire system:
· Design verification test IEC/EN 61439-1 a.-6 (VDE 0660-600-1 a.-6)
· Climatic resistance according to IEC 60068-2 Part -1, Part -14, Part -
30, Part -52, Part -61 and Part -78
· Fire barrier, tested in accordance with EN 1366-3
· Functional endurance, tested according to DIN 4102-12 (optional)
· Maintenance-free design
· Silicone- and halogen-free design
· Suitability for sprinklers
· Sustainability: Environmental product declaration according to ISO
14021, based on a full-scale life cycle assessment (LCA) study according
to ISO14040
Reliable proof of special, additional features (such as sprinkler test) of
system components must be available.
The manufacturer must guarantee that functional disturbances due to the
formation of whiskers are excluded by suitable measures such as air
clearances, insulation or nickel barrier layer.
2.3 General technical data of busbar trunking system
Standards and regulations: IEC/EN 61439-1 and -6
Climatic proofing:
· Cold climate, acc. to IEC 60068-2-1
· Temperature cycle, acc. to IEC 60068-2-14
· Damp heat, cyclic acc. to IEC 60068-2-30
· Saline fog, cyclic acc. to IEC 60068-2-52
· Icing, acc. to IEC 60068-2-61
· Damp heat, constant acc. to IEC 60068-2-78
Network types acc. to: IEC 60364-3
Design: Ventilated
Ambient air temperature min./max./24-h mean
· All mounting positions: -5/+40/+35 °C
· Horizontal edgewise, and vertical: -5/+40/+40 °C
Degree of protection:
O IP 31 (Ventilated, busbars flat)
X IP 34 (Ventilated, busbars edgewise)
O IP 54 (closed)
Torque for clamping connection: 80 Nm
Surface treatment of the busbars
· Insulated over the entire length
· Nickel- and tin-plated for aluminum
· Tin-plated for copper
Material of trunking unit: zinc coated sheet steel
Rated insulation voltage Ui: 1000 V AC / DC
Overvoltage category / Degree of pollution:
III / 3 acc. to EN 60 947
Rated operational voltage Ue for power transmission:
· Overvoltage category III / 3 up to 1000 V AC
· Overvoltage category IV / 3 up to 690 V AC
Rated operational voltage Ue for power distribution:
· Overvoltage category III / 3 up to 690 V AC
Rated frequency f: 50 Hz/ 60 Hz
2.4 Make stipulation
Make / type: SIEMENS / SIVACON 8PS, LD system
2.5 Conductor configuration L1_L2_L3_PEN (50%), LD-system
Design: Ventilated
Conductor configuration: L1, L2, L3, 50% PEN-conductor, Galvanic connection
between housing and PEN
Number of busbars: 7 from 2000 A (Al) 3400 A (Cu)
Network type: TN-C
2.6 Conductor configuration L1_L2_L3_PEN(100%), LD-system
Design: Ventilated
Conductor configuration: L1, L2, L3, 100% PEN- conductor, Galvanic
connection between housing and PEN
Number of busbars: 4 up to 1600 A (Al) 2600 A (Cu)
8 from 2000 A (Al) 3400 A (Cu)
Network type: TN-C
2.7 Conductor configuration L1_L2_L3_N(100%)_PE-conductor(100%), LD-
system
Design: Ventilated
Conductor configuration: L1, L2, L3, N, 100% PE- conductor Galvanic
connection between housing and PE
Number of busbars: 5 up to 1600 A (Al) 2600 A (Cu)
Network type: TN-S; TT
2.8 Conductor configuration L1_L2_L3_N(50%)_PE-Conductor(50%), LD-
system
Design: Ventilated
Conductor configuration: L1, L2, L3, 50% N, 50% PE- conductor, Galvanic
connection between housing and PE
Number of busbars: 8 from 2000 A (Al) 3400 A (Cu)
Network type: TN-S; TT
2.9 Conductor configuration L1_L2_L3_N(100%)_PE-Conductor(50%), LD-
system
Design: Ventilated
Conductor configuration: L1, L2, L3, N, 50% PE- conductor, Galvanic
connection between housing and PE
Number of busbars: 9 from 2000 A (Al) 3400 A (Cu)
Network type: TN-S; TT
2.10 Technical data of 1100 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 1100 A 900 A
Vertical: 950 A 900 A
Horizontal / flat: 700 A 700 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
40 kA
Rated peak withstand current Ipk: 121 kA
Conductor cross-section for 100% busbar: 530 mm²
Fire load without tap-off points: 7.08 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.11 Technical data of 1250 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 1250 A 1000 A
Vertical: 1100 A 1000 A
Horizontal / flat: 750 A 750 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
55 kA
Rated peak withstand current Ipk: 154 kA
Conductor cross-section for 100% busbar: 616 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.12 Technical data of 1600 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 1600 A 1200 A
Vertical: 1250 A 1200 A
Horizontal / flat: 1000 A 1000 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
58 kA
Rated peak withstand current Ipk: 176 kA
Conductor cross-section for 100% busbar: 706 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.13 Technical data of 2000 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 2000 A 1500 A
Vertical: 1700 A 1500 A
Horizontal / flat: 1200 A 1200 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
80 kA
Rated peak withstand current Ipk: 242 kA
Conductor cross-section for 100% busbar: 1060 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.14 Technical data of 2500 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 2500 A 1800 A
Vertical: 2100 A 1800 A
Horizontal / flat: 1700 A 1700 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
110 kA
Rated peak withstand current Ipk: 275 kA
Conductor cross-section for 100% busbar: 1232 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.15 Technical data of 3000 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 3000 A 2000 A
Vertical: 2300 A 2000 A
Horizontal / flat: 1800 A 1800 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 1412 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.16 Technical data of 3700 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 3700 A 2400 A
Vertical: 2800 A 2400 A
Horizontal / flat: 2200 A 2200 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 2044 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.17 Technical data of 4000 A busbar, AC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 4000 A 2700 A
Vertical: 3400 A 2700 A
Horizontal / flat: 2350 A 2350 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 2464 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.18 Technical data of 1900 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 1900 A 1550 A
Vertical: 1640 A 1550 A
Horizontal / flat: 1210 A 1210 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
40 kA
Rated peak withstand current Ipk: 121 kA
Conductor cross-section for 100% busbar DC:
1060 mm²
Fire load without tap-off points: 7.08 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.19 Technical data of 2160 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 2160 A 1730 A
Vertical: 1900 A 1730 A
Horizontal / flat: 1290 A 1290 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
55 kA
Rated peak withstand current Ipk: 154 kA
Conductor cross-section for 100% busbar DC:
1232 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.20 Technical data of 2770 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 1600 A 1200 A
Vertical: 1250 A 1200 A
Horizontal / flat: 1000 A 1000 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
58 kA
Rated peak withstand current Ipk: 176 kA
Conductor cross-section for 100% busbar DC:
1412 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.21 Technical data of 3460 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 3460 A 2590 A
Vertical: 2940 A 2590 A
Horizontal / flat: 2070 A 2070 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
80 kA
Rated peak withstand current Ipk: 242 kA
Conductor cross-section for 100% busbar DC:
2120 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.22 Technical data of 4330 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 4330 A 3110 A
Vertical: 3630 A 3110 A
Horizontal / flat: 2940 A 2940 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
110 kA
Rated peak withstand current Ipk: 275 kA
Conductor cross-section for 100% busbar DC:
2464 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.23 Technical data of 5190 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 5190 A 3460 A
Vertical: 3980 A 3460 A
Horizontal / flat: 3110 A 3110 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar DC:
2824 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.24 Technical data of 6400 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 3700 A 2400 A
Vertical: 2800 A 2400 A
Horizontal / flat: 2200 A 2200 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar DC:
4088 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.25 Technical data of 6920 A busbar, DC - Aluminum
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 6920 A 4670 A
Vertical: 5880 A 4670 A
Horizontal / flat: 4070 A 4070 A
by functional endurance _____
reduced to: _____ A
Conductor material: Aluminum
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar DC:
4928 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.26 Technical data of 2000 A busbar, AC - Copper
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 2000 A 1600 A
Vertical: 1650 A 1600 A
Horizontal / flat: 1200 A 1200 A
by functional endurance _____
reduced to: _____ A
Conductor material: Copper
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
58 kA
Rated peak withstand current Ipk: 176 kA
Conductor cross-section for 100% busbar: 706 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.27 Technical data of 2600 A busbar, AC - Copper
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 2600 A 2000 A
Vertical: 2100 A 2000 A
Horizontal / flat: 1550 A 1550 A
by functional endurance _____
reduced to: _____ A
Conductor material: Copper
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
55 kA
Rated peak withstand current Ipk: 154 kA
Conductor cross-section for 100% busbar: 706 mm²
Fire load without tap-off points: 7.09 kWh/m
Dimensions H x W: 180 mm x 180 mm
2.28 Technical data of 3400 A busbar, AC - Copper
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 3400 A 2600 A
Vertical: 2700 A 2600 A
Horizontal / flat: 2000 A 2000 A
by functional endurance _____
reduced to: _____ A
Conductor material: Copper
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 1412 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.29 Technical data of 4400 A busbar, AC - Copper
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 4400 A 3200 A
Vertical: 3500 A 3200 A
Horizontal / flat: 2600 A 2600 A
by functional endurance _____
reduced to: _____ A
Conductor material: Copper
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 2044 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.30 Technical data of 5000 A busbar, AC - Copper
Technical data
Rated current
Ventilated: closed:
Horizontal / edgewise: 5000 A 3600 A
Vertical: 4250 A 3600 A
Horizontal / flat: 3000 A 3000 A
by functional endurance _____
reduced to: _____ A
Conductor material: Copper
Insulating material: Highly heat-resistant insulation coating
Rated short-time withstand current Icw/1s, conductor:
116 kA
Rated peak withstand current Ipk: 286 kA
Conductor cross-section for 100% busbar: 2464 mm²
Fire load without tap-off points: 11.99 kWh/m
Dimensions H x W: 180 mm x 240 mm
2.31 Meter price horizontal busbar without tap-off point
Straight trunking units with current rating in A acc. to the defined
technical data, busbar as running m without tap-off points, for horizontal
routing, including end flange, busbar connection, expansion compensation
and fixing bracket.
The connection of the individual trunking units must be mechanically
protected against connection with polarity reversal.
2.32 Extra price for tap-off points AC
Extra price for running m described above. Busbar trunking system for tap-
off points up to 1250 A
The tap-off points must generally be designed with shutters guaranteeing
the prescribed minimum degree of protection IP54 in closed condition.
2.33 Extra price for vertical routing
Extra price for running m described above. Busbar trunking system for
vertical routing incl. the necessary fixing elements.
2.34 Fixing bracket, vertical
Vertical fixing bracket (alternatively to extra cost for vertical busbar
run layout) consisting of a fixing bracket for vertical busbar run layout
to the above busbar distribution system.
2.35 Extra price for 90° junction units
Extra price for running m described above. Busbar trunking system for 90
degree junction units.
2.36 Extra price for junction units unequal 90°
Extra price for running m described above. Busbar trunking system for
junction units with an angle between 85° and 175° (in steps of 5°)
2.37 Extra price busbar connection to transformer
Extra price for running m described above. Busbar trunking system for
enclosed busbar connection flange to a transformer.
The busbar connection is done
O vertically
O horizontally (left/right)
The phase sequence and the distance of the connection tags must be
selectable.
Rated power of the transformer: _________ kVA
Rated voltage of the transformer: _________ V
2.38 Extra price for flexible connectors for transformer connection
Flexible copper braid for decoupling of vibrations and for electrical
interconnection of the transformer connection tags and the transformer
connection box of the busbar trunking system, including set of bolted
joints.
Flexible length: 200 mm
Rated current according to primary current according to the maximum
transformer rating.
2.39 Extra price for distribution board feeder unit AC
Extra price for running m described above. Busbar trunking system for
distribution board feeder unit with distribution board connection flange
for switchboard
X SIVACON S8
O Non-Siemens distribution board __________
according to the rated current of the busbar trunking system.
The space required in the associated switchboard must be considered.
The dimension drawings required for connection must be enclosed.
2.40 Extra price for cable feeder unit AC
Extra price for running m described above. Busbar trunking system for cable
connection box for cable infeed according to rated current with single-core
or multi-core cable up to a maximum cross-section of 300 mm². Including
strain relief and cable glands.
2.41 Extra price for T-unit
Extra price for running m described above. Busbar trunking system for
splitting into two busbar runs through a T-unit.
2.42 Extra price for fire barrier EI90
Fire barrier for fire resistance class, tested according to EN 1366-3 for
the busbar trunking system described above, for fire barrier bushings of
walls/ceilings/floors
Fire resistance class: EI90
2.43 Extra price for fire barrier EI120
Fire barrier for fire resistance class, tested according to EN 1366-3 for
the busbar trunking system described above, for fire barrier bushings of
walls/ceilings/floors
Fire resistance class: EI120
2.44 Extra price for busbar barrier for functional endurance
Bus duct barrier for functional endurance according to DIN 4102, incl.
necessary supporting system with accessories, to be delivered and
professionally installed with PROMATECT fire-resistant plates, mineral-
bonded, non-inflammable (A1), with quality assurance according to ISO
9001:2000. Design with solid cover.
Functional endurance:
O E60
O E90
Barrier design / number of promated sides
O 4 sides
O 3 sides
O 2 sides
Duct dimensions according to planning manual "Planning with Sivacon 8PS" or
on request. An official test certificate for the system test shall be
enclosed with the offer.
2.45 Documentation
Documentation according to the preliminary remarks
2.46 Basic description of tap-off units
The tap-off points must be equipped with coding angles to prevent defective
installation. De-energized condition during installation of a tap-off unit
must be ensured by positively defined operations or by instructions to be
observed.
The current tapping of the tap-off unit must be equipped with a leading PE
or PEN connection contact.
The tap-off units are protected against incorrect mounting (anti-rotation
feature for correct phase sequence) and the degree of protection IP2X must
be ensured by a facility throughout the complete plugging process.
Tap-off units shall be available with
· Molded case circuit-breakers
· fuse switch-disconnectors
· switch-disconnector with fuse
The tap-off units can be fitted or removed when the busbar trunking system
is energized, and shall be protected against incorrect mounting.
During plugging or removing, the tap-off units must be in no-load
condition.
2.47 General technical data for tap-off units
Standards and regulations: IEC/EN 61439 Part 1 and 6
Climatic proofing: Damp heat, cyclic acc. to IEC 60068-2-30
Damp heat, constant acc. to IEC 60068-2-78
Ambient air temperature min./max./24-h mean:
–5/+40/+35 °C
Degree of protection: IP 34 / IP 54
Material of tap-off units: outside painted sheet-steel housing
Color of trunking units: RAL 7035 (light grey)
Rated insulation voltage Ui: 690 V AC
Overvoltage category: III / 3 acc. to EN 60 947
Rated operational voltage Ue:
400 V AC (partly 690 V AC)
Rated frequency f: 50 Hz/ 60 Hz
2.48 Tap-off unit with molded-case circuit-breaker (MCCB)
Tap-off unit equipped with molded-case circuit-breaker (MCCB)
· Mode of operation:
O Motor operating mechanism (on request)
O Manual operating mechanism
· Rated current Ie:
O 80 A O 100 A O 125 A O 160 A
O 200 A O 250 A O 400 A O 630 A
O 800 A O 1000 A O 1600 A
· Number of switching contacts:
O 3-pole
O 4-pole
· Rated conditional short-circuit current Icc:
O 55 kA at 415 V (MCCB with thermal-magnetic release)
O 85 kA at 415 V (MCCB with electronic release)
O 110 kA at 415 V (MCCB with electronic release)
· Overcurrent release:
O Thermal-magnetic
O Electronic
· Degree of protection:
O IP 34
O IP 54
A facility for guided safe plugging of the tap-off unit must be available
(coding angle).
Cable entry plate for
O single-core cables without cable glands
O multi-core cables without cable glands
Optional additional accessories
O Extension unit with modules for transmission of the Modbus TCP measured
values directly via the busbar trunking system with G3-PLC power line
technology, without using additional data cables or radio technologies
(available for tap-off units for MCCBs from 100 A to 1000 A)
2.49 Tap-off unit with fuse switch-disconnector
Tap-off unit equipped with fuse switch-disconnector
· Mode of operation: Manual
· Rated current Ie:
O up to 125 A
O 2 x up to 125 A
O up to 250 A
O up to 400 A
O up to 630 A
O up to 1000 A
· Number of switching contacts:
O 3-pole
O 4-pole
· Rated conditional short-circuit current with fuse Icf:
O 80 kA
O 120 kA
· Degree of protection:
O IP 20
O IP 30
O IP 54
A facility for guided safe plugging of the tap-off unit must be available
(coding angle).
Cable entry plate for
O single-core cables without cable glands
O multi-core cables with cable grommets
Optional additional accessories
Extension unit with modules for transmission of the Modbus TCP measured
values directly via the busbar trunking system with G3-PLC power line
technology, without using additional data cables or radio technologies
2.50 Tap-off unit with switch-disconnector with fuse
Tap-off unit equipped with switch-disconnector with NH fuse (low-voltage
high-rapturing capacity)
· Mode of operation: Manual
· Rated current Ie:
O up to 250A
O up to 400A
O up to 630A
· Number of switching contacts:
3-pole
· Rated conditional short-circuit current with fuse Icf: 110 kA
· Degree of protection:
O IP 34
O IP 54
A facility for guided safe plugging of the tap-off unit must be available.
Cable entry plate for
O single-core cables without cable glands
O multi-core cables with cable grommets (as of 400A)
2.51 G3-PLC power line modem for data transmission via the busbar
G3-PLC power line modem for data transmission via the busbar
Brief summary:
The G3-PLC power line modem is used for data exchange between
communication-capable low-voltage switchgear and control gear across all 3
phases of the low-voltage busbar system. It uses the Access Power line
Communication standard (Access PLC) for data transmission. In this case,
one G3-PLC modem ("client" operating mode) is installed in the power line-
capable busbar tap-off unit and another in the power distribution system
("PAN coordinator" operating mode). The devices are connected via RJ45
(Ethernet) or RJ12 (serial).
An external supply voltage is not required. The connection is parameterized
via the integrated web server of the modem.
Functions:
· "PAN coordinator" operating mode: Demodulation of the modulated power
line information and conversion to Modbus TCP or serial information
· "Client" operating mode: Modulation of the information connected to the
RJ45 (Modbus TCP) or RJ12 (serial) interface onto the power line
· Automatic configuration, no local configuration required
· Pushbutton: Reset / factory settings
· LEDs: Status display, PLC connected / data transmission, fault
indication
· Frequency range: 150 to 500 kHz
· Automatic setup of PLC network
· Dynamic routing mechanism supports mesh networking and automatic
adaptation of connection to select the optimal transmission path.
· Automatic Repeat Request (ARQ) improves error detection and reliability
of data
Technical specifications:
· Standards: G3-PLC specification (ITU-T G.9903)
· Mounting: DIN rail
· Protocols: IPv6, IPv4, IEEE 802.3
· Baud rates (gross): 240 kbps (max D8PSK)
· Modulation: Robo, DBPSK, DQPSK, D8PSK (OFDM)
· Frequency range: 150 to 490 kHz
· Output power: 100 dBμV/-9 dBm @ 50 ohms
· Device connection: RJ45 (Ethernet), RJ12 (serial), screw terminal (power
line)
· Power supply: 230 V AC three phases / one phase (internal fuse
protection with 50 kA interrupt capability)
· Dimensions (in mm): 71 (width) x 100 (45+55) (height) x 75 (depth)
· Degree of protection: IP30
· Approvals: CE class A (EU, CH, NO)
Interfaces and communication:
· Ethernet via G3-PLC
· Serial via G3-PLC
Cyber security:
· Encrypted data transfer AES 128-bit layer 2
· Password protection
· Access limitation by means of PSK (pre-shared key)
· Signed firmware
2.52 Repeater box, LD system
If the required transmission distance
· between 2 tap-off units with power line
Or
· between a tap-off unit with power line and the receiver module in the
switchboard
Is longer than the distance that can be bridged as a maximum with power
line communication, it will be necessary to install a repeater box with
integrated repeater (G3-PLC modem) each at a suitable point, in order to
ensure secure communication of the power line signals between the tap-off
units as well as between the tap-off-units and the switchboard.
The repeater boxes to be used can be mounted at the corresponding point of
the busbar like tap-off units.
The distance that can be bridged as a maximum with power line communication
depends on the power quality (e.g. harmonic content) and the topology of
the busbar trunking system (number of feeders), and can be between 200 and
1000 m.
The number and position of the repeater boxes required in the busbar run
must be determined based on the specific conditions of the project to be
implemented.
2.53 Basic description of energy units
The energy points for DC systems must be equipped with coding angles to
prevent defective installation. De-energized condition during installation
of a energy unit must be ensured by positively defined operations or by
instructions to be observed.
The current tapping of the energy unit must be equipped with a leading PE
connection contact.
The energy units are protected against incorrect mounting (anti-rotation
feature for correct phase sequence) and the degree of protection IP2X must
be ensured by a facility throughout the complete plugging process.
Energy units shall be available with
· Molded case circuit-breakers
· fuse switch-disconnectors
The energy units can be fitted or removed when the busbar trunking system
is energized, and shall be protected against incorrect mounting.
During plugging or removing, the energy units must be in no-load condition.
2.54 General technical data for energy units
Standards and regulations: IEC/EN 61439 Part 1 and 6
Climatic proofing: Damp heat, cyclic acc. to IEC 60068-2-30
Damp heat, constant acc. to IEC 60068-2-78
Ambient air temperature min./max./24-h mean:
–5/+40/+35 °C
Degree of protection: IP 30 / IP 54
Material of tap-off units: outside painted sheet-steel housing
Color of trunking units: RAL 7035 (light grey)
Rated insulation voltage Ui: 800 V DC
Overvoltage category: III / 3 acc. to EN 60 947
Rated operational voltage Ue:
440 V DC (units with fuse switch-disconnector)
750 V DC (units with Molded case circuit
breakers)
2.55 Energy unit with fuse switch-disconnector
Energy unit equipped with 3-pole fuse switch-disconnector
· Mode of operation: Manual
· Rated current Ie:
O up to 125 A DC
O 2 x up to 125 A DC
O up to 250 A DC
O up to 400 A DC
O up to 630 A DC
· Degree of protection:
O IP 30
O IP 54
A facility for guided safe plugging of the energy unit must be available
(coding angle). At this juncture it must be prevented that this box is
plugged onto a three-phase system.
Cable entry plate for
O single-core cables without cable glands
O multi-core cables with cable grommets
2.56 Energy unit with Molded-case circuit-breaker (MCCB)
Energy unit equipped with Molded-case circuit-breaker (MCCB)
· Mode of operation: rotary drive
· Rated current Ie:
O 40 A O 80 A O 100 A O 125 A
O 150 A O 200 A O 250 A O 320 A
O 400 A O 500 A O 600 A O 700 A
O 800 A
· Number of switching contacts: 3-pole
· Rated conditional short-circuit current Icc:
100 kA (MCCB with thermal-magnetic release)
· Overcurrent release: Thermal-magnetic
· Degree of protection: IP 54
A facility for guided safe plugging of the tap-off unit must be available
(coding angle). At this juncture it must be prevented that this box is
plugged onto a three-phase system.
Cable entry plate for
O single-core cables without cable glands
O multi-core cables without cable glands
3 Installation, operation and maintenance
3.1 Installation conditions to be fulfilled
· Installation height: _______________________
· Suspension length: _______________________
· Fixing options at the main body:
_______________________
· Type of fixing material:
_______________________
· Working platforms: _______________________
· Scaffoldings: _______________________
· Condition of place of installation:
_______________________
3.2 Scope of supply
The busbar trunking system has to be supplied completely according to the
project-related operation of the system, including the associated
connection material.
The indicated unit prices must include all costs for engineering,
documentation, measurement of the system components as well as preparation
of the final revision documents.
3.3 Operational installation
Complete operational installation of the busbar system.
All installation material such as brackets, struts, ropes etc., including
all hardware, is contained herein.
The fixing distances and the selection of the installation material must be
designed for equipment with an average number of tap-off units.
For the selected design and installation, the manufacturer has to provide a
declaration regarding the auxiliary installation and fixing material.
After completion of the busbar system, the insulation resistances must be
documented by a test record.
3.4 Model data (3D) for use in BIM process
In addition to the written documentation of the system, 3D data to the
planned system has to be provided in a suitable format (e.g. .RVT (Autodesk
Revit), .IFC (Industry Foundation Classes)) in order to be integrated in
the BIM (Building Information Modelling) of the building project.
Using the 3D data in the BIM process contributes to efficient and thus
sustainable planning thanks to the following factors:
More efficient planning resulting from the same level of information for
all persons involved with respect to the information that is relevant
for them
Possibility of early, efficient and precise error and weak point
analyses in the planning process
Consideration of aspects concerning the optimization of operation and
maintenance already in the planning phase
For the provision of BIM data, a software like SIMARIS project from Siemens
or a similar product shall be used.
4 BOM
No. Description Qt Price
y
2.3 Meter price horizontal busbar without tap-off point
1
2.3 Extra price for tap-off points AC
2
2.3 Extra price for vertical routing
3
2.3 Fixing bracket, vertical
4
2.3 Extra price for 90° junction units
5
2.3 Extra price for junction units unequal 90°
6
2.3 Extra price busbar connection to transformer
7
2.3 Extra price for flexible connectors for transformer
8 connection
2.3 Extra price for distribution board feeder unit AC
9
2.4 Extra price for cable feeder unit AC
0
2.4 Extra price for T-unit
1
2.4 Extra price for fire barrier EI90
2
2.4 Extra price for fire barrier EI120
3
2.4 Extra price for busbar barrier for functional endurance
4
2.4 Documentation
5
2.4 Tap-off unit with Molded-case circuit-breaker (MCCB)
8
2.4 Tap-off unit with fuse switch-disconnector
9
2.5 Tap-off unit with switch-disconnector with fuse
0
2.5 G3-PLC power line modem for data transmission via the
1 busbar
2.5 Repeater box, LD system
2
2.5 Energy unit with fuse switch-disconnector
5
2.5 Energy unit with Molded-case circuit-breaker (MCCB)
6