NEMSA Regulations
NEMSA Regulations
        In exercise of powers conferred on me by section 4 of the Electricity Act and all other
 powers enabling me in their behalf; I the Minister of Power and Steel with the prior consent of
 the Head of State, Commander-in-Chief of the Armed Forces, Federal Republic of Nigeria,
 hereby make the following regulations:
 1. Short title
      These regulations may be cited as the Regulations for Electrical Installations, 1994, Section 4
 of the Electricity Act, cap 106 LFN 1990.
 2. Interpretation
      In these Regulations the undermentioned expressions shall have the meanings respectively
 assigned thereto. Otherwise the definitions contained in Nigerian Industrial Standards (Glossary
 of Term) shall apply.
“accessory” means any device, other than a fitting, associated with the wiring, fittings and
consuming devices: for example, a small switch, cut-out, plug, socket, or similar device.
“adaptor, socket-outlet” means an accessory for insertion into a socket-outlet and containing
metal contacts, to which may be fitted one or more plugs for the purpose of connecting to the
supply, portable light fittings or current-using appliances.
 “apparatus” means machines, equipment and fittings associated with generation, transmission,
 distribution and utilization of electrical energy.
 “appliance” means any device which utilizes electricity for a particular purpose, excluding a light
 fitting or an independent motor.
 “authorised inspector” means an inspector employed by the Licensee concerned, save that in
 any case where the licensee is also the consumer. “Authorised Inspector” shall mean a person
 appointed for the purpose by the Director of Electrical Inspectorate Services.
 “authorised person” means -
          (i)     the owner or occupier of any premises; or
          (ii)    a contractor for the time being under contract with the owner, occupier; or
          (iii)   a person employed, appointed, or selected, by the owner, occupier, or contractor
                  as afore-said to carry out certain duties incidental to the generation,
                  transformation, distribution, or use of electrical energy; such owner, occupier,
                  contractor, or person being a person who is competent for the purposes of the
                  regulation in which the term is used.
 “balanced” means a three-wire system of generation or supply is said to be “balanced” when –
                                            Page 1 of 173
       (i)       in the case of direct current or single phase alternating current systems of
                 generation or supply, loads connected between the middle and each of the outer
                 conductors are equal;
        (ii)     in the case of three phase systems of generation or supply, the load carried by
                 any combination of two conductors is equal to the load carried by any other
                 combination of two conductors;
        (iii)    in case of three phase four-wire system of generation or supply in addition to
                 condition in (ii) above, the loads connected between the neutral and each of the
                 “phase” conductors are also equal.
“bonded” means the electrical interconnection of metallic parts order to maintain them at the
same potential and to achieve a desired distribution of currents within an earthing system.
“cable” means a length of single insulated conductor (solid or stranded) or two or more of such
conductors each provided with its insulation which are laid up together. The insulated conductor
or conductors may or may not be provided with an overall mechanical protective covering.
“cable, armoured” means an armoured cable is one provided with a metallic covering of wires or
tapes as a protection against mechanical injury.
“cable, bunched” means cables are said to be bunched when more than one is contained within
a single duct, conduit or trunking, or when unenclosed, cables are not separated from each
other.
“cable coupler” means a means enabling the connection, at will, of two flexible cables. It
consists of a conductor a plug.
“cable ducting” means an enclosure of metal or insulating material, other than conduit or cable
trunking, intended for the protection of cables which are drawn-in after erection of the ducting,
but which is not specifically intended to form part of a building structure.
“cable, flexible” means a flexible cable is one in which the conductor (or conductors) comprise a
number of wires, the diameter of the wires and the material of the dielectric being such as to
ensure flexibility.
“circuit” means an assembly of electrical equipment supplied from the same origin and
protected against over-current by the same protective device(s).
“circuit-breaker” means a mechanical switching device capable of making, carrying and breaking
current under normal circuit conditions and also of making, carrying for a specified time, and
breaking currents under abnormal circuit conditions such as those of short circuit.
“circuit conductor” means a current conductor forming part of a circuit or final sub-circuit, but
excluding the earth-continuity conductor.
“conductor (or a core or cable)” means the conducting portion, consisting of a single wire or of a
group of wire of a group of wires in contact with other. For earthed concentric wiring, the term
may also denote the metal sheath of a cable.
“conduit” means an approved pipe or tube of standard dimensions and material for electrical
use.
“consumer” means any person supplied with electrical energy by the licensee.
                                          Page 2 of 173
“consumer installation” mean consumer’s wiring together with any apparatus upon the
premises connected to or intended to be connected thereto and situate upon the consumer’s
side of the Licensee’s supply terminals.
“consumer’s terminals” mans the point in the consumer’s installation at which the incoming
supply of energy is delivered to that installation.
“cable, flexible” means a flexible cable is one which the conductor (or conductors) does not
exceed 4mm2 in cross-section and comprises a number of wires, the diameter of wires and the
material of the dielectric being such as to ensure flexibility.
“core (of a cable)” means the conductor with its insulation or dielectric, but does not include the
mechanical covering. Two, three or more cores may be laid up together to form a twin, three-
core, or multi-core cable.
“cut-out” comprises all the separate parts-e.g., fuse-element, fuse carrier, fuse-contacts, fuse-
extension, and circuit contacts-which together with their mountings and base, form the
complete protecting device.
“damp-and dust-proof” applied to apparatus and accessories to denote that the live and other
component parts are protected by an enclosure or enclosures being so protected and/or fitted
as to prevent the ready ingress of dust and or moisture.
“damp situation” means a situation in which moisture is either permanently present, or
intermittently present to such an extent as to be likely to impair the effectiveness of an
installation conforming to the requirements for ordinary situations
“dead or de-energised” means free from any electrical connection to a source of potential
difference and from electric charge, or not having a potential different from that of the earth.
“dielectric” means that portion of a core cable which is relied upon to insulate conductor.
“Director of Electrical Inspectorate Services” means the Registered Engineer for the time being
holding that office under the government of the Federal Republic of Nigeria.
“distribution board” means an accessory containing fuses or circuit-breaker arranges for the
distribution to, and protect and control of sub-circuits or final sub-circuit.
“double insulation” a conductor is said to have double insulation when it is provided with
insulating material between the conductor and its surrounding envelope or immediate support,
as well as between such envelope or support and earth.
“earthed” means connection to the general mass of earth in such a manner as well ensure at all
times an immediate discharge of electrical energy without electrical hazards.
“earth electrode” means a metal rod or rods, a system of underground metal pipes or other
conducting object, providing an effective connection with the general mass of the earth.
Note: The use of pipes of public gas or water supply undertakings as a sole earth electrode is not
permitted in these Regulations.
“earthing-lead” means the conductor connecting the earthing-system to the metal sheathing or
apparatus required to be earthed.
“electrical energy” means electrical energy when generated transmission of a message.
“electrical hazard” means danger to life or property from electrical energy.
“electrical supply authority or supply authority” Same as Licensee
                                          Page 3 of 173
“electrode boiler (or electrode water heater)” means apparatus for the electrical heating of
water by the passage of an electric current between electrodes immersed in the water.
“final-sub-circuit” A final sub-circuit is that portion of the wiring system extending beyond the
final set of fuses and intended to supply electrical energy to current using apparatus, either
directly or through an outlet or fused spur boxes.
“flame-proof” is applied to apparatus to denote that the containing case or other enclosure will
withstand without injury any explosion of prescribed flammable gas that may occur within it
under practical conditions of operation within the rating of the apparatus (and recognized
overloads, if any, associated herewith) and will prevent the transmission of the flame such as will
ignite any prescribed flammable gas that may be present in the surrounding atmosphere.
“fuse-element” means a fuse element is the actual wire or strip of metal in a cut-out which is
designed the moving part of which carries one or more fuses.
“fuse- switch” means a switch the moving part of which carries one or more fuses.
“hazardous location” means any premises including buildings erected thereon, whether
enclosed or not, in which explosive, highly inflammable or corrosive substances are produced,
manufactured, refined or stored or packed, and in the case of highly inflammable substances are
offered for sale, or where the same results in the presence of an explosive highly inflammable or
corrosive liquid or gas, and shall be deemed to include electrically operated equipment for the
delivery of petrol and paraffin oil, and rooms used for the storage of cinematograph films made
of celluloid.
“heating point” means a socket-outlet to which a portable heater is plugged.
“h.o.f.r. sheath (or cable)” means heat-resisting, and flame retardant sheath.
“indirect contact” means contact of person or live stock with exposed conductive parts made
alive by a fault and which may result in electric shock.
“installation” means an assembly of associated electrical equipment to fulfill a specific purpose
and having certain co-ordinated characteristics.
“insulation” means suitable non-conducting materials enclosing, surrounding or supporting a
conductor.
“intrinsic safety” means –
(i)          Applied to a circuit, denotes that any electrical sparking that may occur in normal
working, under the conditions specified by the certifying authority, and with the prescribed
components, is incapable of causing an ignition of the prescribed flammable gas or vapour.
(ii)         Applied to apparatus, denote that it is so constructed that when installed and
operated under the conditions specified by the Certifying Authority, any electrical sparking that
may occur in normal working, either in the apparatus or in the circuit associated therewith is
incapable of causing an ignition of the prescribed flammable gas or vapour.
         Note 1: The use of the term “In normal working” is intended to cover sparking that may,
         in normal use, be produced by breaking line current, or a short circuit across the lines in
         the circuit that is required to be intrinsically safe. It is also intended to cover sparking
         that may be produced under any condition of fault which in the opinion of the Certify
         Authority, might arise in practice.
                                           Page 4 of 173
         Note 2: For applications other than coal mining, where part of the certified equipment is
         to be mounted outside the hazardous area or in a flame-proof enclosure the assessment
         of intrinsic safety may be restricted to cover only such electrical sparking as may occur
         within the hazardous area or outside the flame-proof enclosure. Any certificate of
         intrinsic safety issued by the appropriate authority will then define the circumstances to
         which it applies.
“lighting fitting/luminaire” means equipment which distributes, filters, or transforms the light
from one or more lamps, and which includes parts necessary for supporting, fixing and
protecting the lamps, but not the lamps themselves, and where necessary circuit auxiliaries
together with the means for connecting them to the supply.
         Note: For the purposes of this Regulations a batten lamp holder, or a lamp holder
         suspended by a flexible cord is a luminaire.
“licensee” means any Local Authority, Company, Body, person or persons authorized by the
issue of a licence by the Minister, to use, work or operate in accordance with these Regulations,
any plant, apparatus or work designed for the supply or use of electrical energy or to supply such
energy to or for the use of any other Local Authority, Company, Body, person or persons from
any such plant, apparatus or works.
“live (alive)” means an object is said to be alive when a difference of potential exists between it
and earth, except in the case of multi-earthed neutral system, all metal connected to the neutral
conductor of the supply system, shall be deemed to be alive for the purpose of these
regulations.
“machine (electrical)” means a device for converting electrical energy into mechanical energy or
vice versa, or for converting one form of electrical energy into another.
“machine, drip-proof” means one which has a frame provided with opening for ventilation, so
protected as to exclude falling water or dirt.
“machine, enclosed, ventilated” means one in which the ventilation openings in frame are
protected with wire screen, expended metal, or other suitable perforated covers having
apertures.
“machine, flame-proof” means one in which the enclosing case can withstand, without injury,
any explosion of gas that may occur in practice within it under the conditions of operations and
prevent the transmission of sparks or flames capable of igniting any inflammable gas or particles,
such a coal-dust, or flour or textile flyings, which may be present in surrounding atmosphere.
“machine, protected” means one in which the internal rotating parts and live parts are
protected mechanically from accidental or careless contact, whilst ventilation is not materially
obstructed.
“machine, totally enclosed” means one so enclosed as to prevent circulation of air between the
inside and outside of the case, but not so such an extent as to make the machine air-tight.
“mains feed” means that portion of the wiring between the main switchboard and the electric
service line from which supply is obtained.
“the minister” means a Minister charged with responsibility for matters relating to electricity.
“multiple-earthed neutral (m.e.n.)” means the neutral conductor of any low or medium voltage
alternating-current-system is said to be multiple-earthed when it is earthed at the point of
                                          Page 5 of 173
supply (that is, generating station, sub-station, or transformer) and at one or more other point
along the distribution or service line and at each consumer’s premises.
“plug” means a device intended for connection to a flexible cord or flexible cable which can be
engaged manually with a socket-outlet or connector or adaptor and which has current-carrying
contact pins which may be exposed when not engaged.
“point (in wiring)” means a termination of the fixed wiring intended for the connection of
current-using equipment.
“regulation for electricity supply” means regulations made under the Electricity Act, as from
time to time amended.
“service fuse” means the device installed by Electricity Supply Authority for automatically
disconnecting the installation of a consumer’s premises from service line.
“socket-outlet” means a device with protected current-carrying contacts intended to be
mounted in a fixed position and permanently connected to the fixed wiring of the installation, to
enable the connection to it of a flexible cord or flexible cable by means of a plug.
“space factor” means the ratio (expressed as a percentage) of the sum of the overall cross-
sectional area of cables (including installation and any sheath) to the internal cross-sectional
area of the conduit or other cable enclosure in which they are installed. The effective overall
cross-sectional area of a non-circular cable is taken as that of a circle of a diameter equal to the
major axis of the cable.
                                                  PART I
                                         Division One – general
1.       Application; enforcement and exemptions from regulations
  These regulation apply to all Electrical installations connected to any of electrical energy
operated under the authority of a licence granted under Electricity Act (and to whe3ther granted
before or after the coming into force of these regulations), and to all electrical installations for
the installing of which such a licence is required (and whether granted before or after the
coming into force of these regulations), but save as provided in the Electricity Supply Regulations
nothing herein shall apply to any generating plant which is subject to these regulations.
2.       (1) It shall be a condition of every licence granted under the Electricity. Act (and whether
granted before or after the coming into force of these regulations) by which any supply
Electricity Supply Authority is empowered to supply electricity energy to any consumer that such
Supply Authority shall not connect with such line any new installation on the consumer’s
premises unless and until such installation has been inspected, tested, and certified pursuant to
these regulations.
         (2) It shall also be a condition of every such licence that the Electricity Supply Authority
shall not continue to supply electrical energy to any installation connected with the Supply
Authority’s electric lines, or to supply electrical energy to any other existing installation or any
part thereof is not reasonably free from electrical hazard, and such work in accordance with
these regulation as such Electricity Supply Authority directs is not done to render such
installation or such part reasonably free: provided that it shall not be necessary for the Supply
Authority to require strict compliance with these regulations in the doing of any such work if it is
satisfied that such compliance would involve unreasonable expenditure and that the installation
can otherwise be rendered reasonably free from electrical hazard.
         (3)It shall not be necessary until six months after the commencement of these
regulations for the Supply Authority to insist on the use of any material necessary to make any
installation comply with the requirement of these regulations if such materials are not in general
use or are not readily procurable in Nigeria.
3.       In any case where the Electricity Supply Authority is also a consumer of the electrical
energy supplied by it, the conditions imposed by the last preceding regulation shall apply to it in
its capacity as Supply Authority as if it were supplying electricity to some other consumer than
itself, but in such case the Director of Electrical Inspectorate Services or some person appointed
                                           Page 7 of 173
by him in writing in that behalf shall have and may exercise the power mentioned in Regulation
2(1) to inspect, test and certify.
4.       Where a Supply Authority changes over from one voltage or system to another the
Director of Electrical Inspectorate Services may, be by notice published in the Gazette, make
such modification as may be specified in such notice of these regulations in their application to
the reconditioning of installations for the purposes of such change-over.
5.       The Director of Electrical Inspectorate Services may from time to time, by notice in the
Gazette, approve methods or types of construction or materials not specially provided for in
these regulations, and impose such conditions as he deems necessary with respect to the use
thereof.
6.       (1) In any case where the Director of Electrical Inspectorate services upon application
being made to him in writing by any person proposing to make any new installation, is satisfied
that strict compliance with these regulations would involve expenditure out of proportion to the
degree of freedom from electrical hazard to be secured by compliance, he may modify any such
requirements if satisfied that reasonable freedom from electrical hazard can be otherwise
secured.
   (2) Every such application shall be accompanied by a full statement the reasons why
modification is desired and of the nature thereof, and by a certificate by the Supply Authority’s
engineer that the application is a reasonable one and that in his opinion such modification will
not lead to serious increase in the electrical hazard.
   (3) In granting any such modification the Director of Electrical Inspectorate Services shall
specify what special work (if any) he requires to be done to render the installation reasonably
free from electrical hazard.
                                                  PART II
                                     Permits for electrical installation
7. Save as provided in Regulations 9 and 10 hereof, no electrical installation shall be
commenced until a written permit thereafter has been obtained from the Electricity Supply
Authority.
8.     (1) A Supply Authority may grant permits for temporary installations-
             i. no permit for temporary installation shall be granted for longer period than one
                  month after the date on which such installation is connected the source of
                  supply.
       (2) On the expiration of the period for which a permit for temporary installation is granted
a further such permit may be granted for a period not exceeding one month. But the total period
during which temporary installation may be connected to the source of supply under the
authority of successive permits shall not exceed six months from the date on which it was first
connected.
9.       In any case of emergency due to a breakdown or other accident any authorised person
may, without obtaining a permit as required by these regulations, begin any work necessary to
repair the installation, but application for such permit must be made to the Supply Authority
within twenty-four hours after such work is began.
                                          Page 8 of 173
10.     In any case where an Electricity Supply Authority is also the consumer of the electrical
energy supplied by it, or is the contractor for any electrical installation work, the Director of
Electrical Inspectorate Services or any person authorized by him in writing in that behalf shall
exercise and perform the powers, functions, and duties conferred or imposed on the Electricity
Supply Authority as such by the foregoing provisions of this part of these installations.
                                               PART III
                                       Requirements for safety
11.       Testing
On completion of an installation or an extension or major alteration of an installation, tests
should be made with suitable instruments to verify as far as practicable that the requirements of
regulations 12 – 18 have been met; that the installation of all conductors and apparatus is
satisfactory, and that the earthing arrangements are such that in the event of an earth fault
circuit or sub-circuit or apparatus is automatically disconnected from the supply so as to prevent
danger.
12.       Conductors and apparatus
   (1) (i) All electrical conductors shall be of sufficient size and current rating for the purposes for
which they are to be used.
       (ii) All apparatus shall be suitable for the maximum power demanded by the             apparatus
when it is in use, and shall be otherwise so constructed, installed, and protected as to prevent
danger as far as is reasonable practicable,
      (iii) All circuit conductors, including conductors forming part of apparatus, shall be either-
              (a) so insulted, and where necessary further effectively protected; or
              (b) so placed and safeguarded, as to prevent danger so far as is reasonably
                   practicable,
      (iv) every electrical joint and connection shall be of proper construction as regards
conductance, insulation, mechanical strength, and protection. Conductors and apparatus
operating at voltages between conductors or to earth exceeding 250 volts shall either-
        i.    be completely enclosed in earthed metal which is electrically continuous and
              adequately protected as to prevent danger as far as is necessary practicable.
       ii.    be so constructed, installed and protected as to prevent danger as far as is
              reasonably practicable.
13.       Protection
   (1) Every electrical circuit and sub-circuit shall be protected against excess current by fuses,
circuit breakers, or other similar devices which –
        i.    will operate automatically at current values which are suitably related to the safe
              current, ratings of the circuit, and
       ii.    are of adequate making and breaking capacity, and
      iii.    are suitable located and of such construction as to prevent danger from over-
              heating, arcing or the scattering of hot metal when they come into operation
      iv.     and as to permit ready renewal of fuse-elements without danger.
                                             Page 9 of 173
   (2) Where the earth-fault-leakage current from a circuit due to a fault of negligible impedance
from a live conductor to earthed metal is sufficient to operate the fuses or circuit-breakers or
other similar devices provided so as to comply. With Regulation 13(1), the current shall be
protected against the persistence of earth-leakage currents liable to cause danger by an earth-
leakage circuit-breaker or equivalent device.
   (3) No fuse, or circuit-breaker other than a linked circuit breaker, shall be inserted in a
conductor connected with earth, and any linked circuit-breaker inserted n a conductor
connected with earth shall be arranged to break also all the live conductors.
   (4) Every single-pole switch shall be inserted in the live conductor only, and any switch
connected in the conductor connected with earth shall be linked switch and shall be arranged to
break also all the live conductors.
14.       Precaution
   (1) Where metal work, other than current-carrying conductors, is liable to become charged
with electricity in such a manner as to create a danger if the insulation of a conductor should
become defective or if a defect should occur in any apparatus-
        i.    the metalwork shall be earthed in such a manner as will ensure immediate electrical
              discharge without danger, or
       ii.    other adequate precautions shall be taken to prevent danger.
15.       Isolation
   Effective means, suitable placed for ready operation, shall e provided so that all voltage may
be cut off from every circuit and sub-circuit and from all apparatus, as may be necessary to
prevent danger.
16.       Apparatus installation
   (1) Every piece of apparatus which requires operation, in normal use shall be so installed that
adequate means of access and working space are afforded for such operation or attention.
   (2) Every electric motor shall be controlled by an efficient switch for starting and stopping
such switch should be readily accessible and easily operated and so placed as to prevent danger.
17.       Abnormal conditions
   (1)All apparatus and conductors exposed to whether, corrosive atmosphere, or other adverse
conditions, shall be so constructed or protected as may be necessary to prevent danger arising
from such exposure.
   (2) Where a conductor or apparatus is, or is likely to be, exposed to flammable surroundings
or, an explosive atmosphere it shall be protected by a flame-proof enclosure or be otherwise do
designed and constructed as to prevent danger.
    (3) In situation which may normally be wet or damp, where electrical apparatus is present
and might give rise to danger and where there are substantial exposed metal parts of other
services (such as gas and water pipes, sinks and baths) the earth-continuity conductor of the
electrical installation shall be effectively connected electrically and mechanically to all such
metal parts and to exposed metalwork of the electrical apparatus which is required by
Regulation 3.8 to be earthed.
18.       Additional to installations
                                         Page 10 of 173
   No addition, temporary or permanent, shall be made to the authorized load of an existing
installation, unless it has been ascertained that the current rating and condition of any existing
conductors and apparatus (including those of the supply undertaking) which will have to carry
the additional load are adequate for the increased loading, and that the earthing arrangements
are also adequate.
                                          Page 11 of 173
   (4) Suitable means shall be provided for controlling the current with which battery is being
charged. Such means shall comprise, as a minimum, an automatic cut-in and cut-out, or
alternatively, a circuit-breaker with overload and reverse-current trips.
   (5) The room in which batteries are placed shall be thoroughly ventilated.
22.      Static transformers and choke coils
   (1) Transformers and choke-coils shall be either amply ventilated or else oil-immersed. But in
situations where inflammable or explosive gases, dust or flying particles are liable to be present
the transformers shall be oil-immerses.
   (2) Transformers shall be in accordance with Nigerian Standard Specifications
   (3) Auto-transformers, resistances shall not be used to reduce the voltage to low or extra-low
voltage.
         (a) to supply general wiring in building; or
         (b) for any other purpose where the low or extra-low voltage circuit or apparatus has
               exposed live metal with which it is possible for any person to make contact.
                                                  PART V
                    Temporary installations and installations on construction sites
23.      General
    Temporary installations and installations on construction sites shall comply in all respects
with the requirements of these regulations for permanent installations and in addition with the
requirements of the Regulations 24 and 25.
24.      Responsibility for installation
   Every installation on a construction site, and every temporary installation other than an
installation in a private dwelling, shall be in charge of a competent person, who shall accept full
responsibility for the safety of the installation, for its use, and for any alternation or extension
thereto. The name and designation of such person shall be prominently displayed close to the
main switch or circuit-breaker of the installation.
25.      Testing
   Every installation for which this section applies shall be inspected and tested in accordance
with the requirement of Part XII- Testing, at intervals of three months or at such shorter periods
as the particular nature of the installation necessitates.
                                                 PART VI
                              Controls of supply to consumers’ installation
26.      Supply control
    (1) Every consumer installation shall be adequately controlled by switch-gear readily
accessible to the consumer which shall incorporate-
             i.   means of isolation, and
            ii.   means of excess-current protection, and
           iii.   means of earth-leakage protection
    (2) All such installation shall be easily accessible to the consumer and as near as possible to
             i.   the point or points of entry of the service main in the case of a public supply; or
            ii.   the generator in the case of private plant.
                                           Page 12 of 173
    (3) In the case of a private plant where the building containing the generator is isolated from
the building in which the electricity is consumed, a main switch shall be installed at a point at
which the main cables enter the latter building. Where more than one building is supplied from a
common man, switches shall also be installed at each building.
    (4) The means of isolation required by Regulation 26(1) shall comprise a linked switch
suitable for operation on load or a linked circuit-breaker arranged to disconnect all having an
excess-current release fitted in each live conductor of the supply.
27.       A. Protection
      (1) The means of excess-current protection required by Regulation 26(1) shall comprise
either a fuse in each live conductor of supply or circuit-breaker having an excess-current release
fitted in each live conductor of the supply.
      (2) Every means of excess-current protection shall be suitable for the maximum short-circuit
current attainable.
      (3) The characteristics and settings of excess-current protective gear, including fuses and
arrangement of the installation, shall be such that discrimination in the operation of the excess-
current protection gear is ensured.
      (4) Throughout a 2-wire installation connected to a source of supply having one pole
connected with earth, all fuses and single-pole control devices, e.g. switch or circuit-breakers,
thermostats and the like, shall be connected in the live conductor only. This does not preclude
the use of double-pole linked devices controlling both conductors of the supply.
      (5) Throughout a 2-wire installation connected to a source of a supply having neither pole
connected with earth, every switch or circuit-breaker shall be of the double-pole linked type, and
fuses (where installed) shall be fitted in both poles.
      (6) Every conductor in the installation shall be protected against excess current by a fuse or
circuit-breaker fitted at the origin of the circuit of which the conductor forms part. The current
rating of every fuse use for this purpose shall not exceed that of the lowest-rated conductor in
the circuit protected, account being taken of the class of excess-current protection afforded by
the fuse. Every circuit-breaker used for this purpose shall operate when the circuit protected is
subjected to a sustained excess current of 1.5 times the rating (appropriate to this form of
protection) of the lowest-rated conductor in the circuit. Sizes of fuse elements for semi-enclosed
fuses are given in Table 1 in Schedule 1.
        B. Cut-out
    (1) For low and medium voltage cut-out shall comply with Regulation 27
     (2) It shall be provided with a suitable incombustible and insulating carrier for the fuse of
such shape as to protect a person handing it from shock and burns; and contacts shall be
provided on the carrier to which the ends of the fuse can be readily attached.
    (3) The base shall be provided with fixed circuit contacts of such shape as to retain the carrier
in position in the presence of vibration.
     (4) The bus-bars, fixed contacts, removable contacts, and fuses shall be so shielded as to
protect a person against contact with live metal when the fuse-carrier is being inserted or
removed.
28.       Switchboard
                                           Page 13 of 173
    (1) Switchboards shall be constructed wholly of durable, non-ignitable, non-absorbent
materials, and all insulation shall be of permanently high strength and insulation resistance.
    (2) All switchboards with metallic frames shall be provided with suitable terminals, to which
the earthing lead shall be attached.
    (3) The various exposed live parts of switchboards shall be so arranged by suitable spacing or
shielding with non-ignitable insulating materials that an arc cannot be maintained between any
such parts or between such parts and earth. For voltage not exceeding 250 volts the minimum
clearance between the live metal parts of fuses of opposite polarity or phase, or between any
live metal and any earthed metal shall be 50mm. For medium voltage the clearance shall not be
less than 100mm. Fuses which on blowing expel the gas parallel to the axis of the fuse, and
which are of opposite polarity or phase, may be mounted one above the other if an insulating
shield is fixed between them.
    (4) The arrangements of all parts shall be such that the connections to all instruments and
apparatus can be readily traced.
    (5) All parts, including connections, shall be readily accessible; and no fuse, circuit-breaker, or
switch other than an isolating switch shall be fixed on the back of the switchboard panel if it is
necessary to operate the same from behind.
     (6) All nuts or parts carrying over twenty-five amperes, shall be effectively locked so that they
cannot become loose.
    (7) All bus-bars and connections on switchboards shall be in accordance with relevant
Nigerian Standard Specifications.
    (8) Where a scheme of colouring is employed to distinguish switchboard bus-bars and
connections to individual poles or phases, such scheme of colouring shall be in accordance with
relevant Nigerian Standard Specifications.
    (9) The arrangement of bus-bars carrying alternating currents shall be in accordance with
relevant Nigerian Standard Specifications.
   (10) Conductors must be symmetrically placed and spaced apart, and so arranged that the
course of every conductor may be readily traced.
   (11) All circuits, instruments, and important apparatus shall be clearly and indelibly labeled for
identification.
    (12) Switches shall be so arranged that their blades or moving parts are disconnected from
the supply in the off position. They shall be so mounted that the top of the handle is at a height
not exceeding 2.3m above floor level.
    (13) In every case in which the switches and fuses are fitted on the same pole or phase these
switches shall preferably be so arranged that the fuses are disconnected from the supply when
their respective switches are in the “off” position.
     (14) Where meters, service fuses or other apparatus belonging to the Supply Authority are to
be mounted on a switchboard, loops shall be left in the leads of sufficient length to allow the
ends of the conductors to be properly connected by the Supply Authority.
     (15) Each distribution board shall have fitted in or on its case or cover, or in an adjacent
conspicuous position, an indication of the circuit protected by each fuse or circuit-breaker
contained therein and of the appropriate current rating for the circuit so protected.
                                           Page 14 of 173
   (16) More than one phase supply shall not be brought into a multi-gang switch box.
    (17) Where service meters are not mounted on the main switchboard they be mounted on a
substantial base.
   (18) Where instrument transformers are used, and are easily accessible, all live metal shall be
effectively insulated.
29.      Final sub-circuits
    (1) The number of points which may be supplied by a final sub-circuit of rating not exceeding
15 amperes is limited by their aggregate demand as determined from Table 2 in schedule 1;
there shall be no other allowance for diversity in the final sub-circuit and the current rating of
the cable must not be exceeded.
    (2) All socket outlets in any one room shall be connected to the same phase (or pole of a 3
wire system).
   (3) Where an installation comprises more than one final sub-circuit, each shall be connected
to a separate way in a distribution board.
   (4) The wiring of each final sub-circuit shall be electrically separated from that of every other
final sub-circuit. To facilitate disconnection of each sub-circuit for testing, the neutral conductors
shall be connected at the distribution board in the same order as that in which the live
conductors are connected to the fuses or circuit-breakers.
   (5) A final sub-circuit having a rating exceeding 15 amperes shall not supply more than one
point. For the purpose of this regulation the following items may each be regarded as one point
–
             i.  a cooker control unit incorporating socket outlet;
            ii.  a light fitting track system provided that individual light fittings are suitably
                 protected against excess current.
    (6) To determine the rating of a final sub-circuit supplying stationary cookers in domestic
premises, the current demand of each cooker shall be assessed not less than 30A. The minimum
size of cable should be 6mm2.
    (7) Every stationary cooking appliance in domestic premises shall be controlled by a switch
separate from the appliance and installed within 2m of the appliance.
30.      Diversity
    (1) Diversity shall not be allowed for when calculating the size of circuit conductors and
switch-gear and circuits other than final sub-circuits, other to the extent specifically permitted by
Regulations for final sub-circuits, for cooking appliances.
   (2) Diversity may be allowed for when calculating the size of circuit conductors and switch-
gear and circuits other than final sub-circuits provided this is justified by known or anticipated
conditions.
         Note: Allowance for diversity is a matter calling for special knowledge and experience
                 and the application of diversity should be decided by the engineer responsible for
                 designing each particular installation.
31.      Ring and radial circuit
    (1) In domestic installations either radial or ring final sub-circuit conforming with Table 3 may
be installed to serve socket outlets complying with relevant Nigerian Standard Organisation’s
                                           Page 15 of 173
Specification and Stationary appliances of rating not exceeding 13 amperes provided that the
general requirements of Regulations and in case of ring sub-circuits, the special requirements of
Regulations 31(5) to 31(11) are met.
     (2) Each socket outlet of a twin or multiple socket outlet unit shall be counted as one socket
 for the purposes of Regulation 31(1) and Table 3.
     (3) A stationary appliance connected permanently (i.e. not through a plug and socket outlet)
 to a radial or ring final sub-circuit conforming with Regulation 31(1) shall be locally protected by
 a fuse of rating not exceeding 13 amperes and controlled by a switch or protected by a circuit-
 breaker of rating not exceeding 15 amperes.
     (4) The conductor sizes tabulated in Table 3 in schedule 1 are minimum and shall be
 increased if necessary where circuits are installed in groups or in conditions of high ambient
 temperature, taking account of the class of excess-current protection provided. In such
 circumstances it must be ensured that –
                 i.   for radial final sub-circuits, the current rating of the conductors is not less
                      than that of the fuse or circuit-breaker protecting the final sub-circuit, and
                ii.   for ring final sub-circuits, the current rating of the conductors forming the
                      ring is not less than 0.67 times the rating of the fuse or circuit-breaker
                      protecting the final sub-circuit.
    (5) Each circuit conductor of a ring final sub-circuit shall be run in the form of a ring,
commencing from a way in a distribution board (or its equivalent), looping into the terminals of
socket outlets and joint boxes (if any) connected in the ring and returning to same way of the
distribution board.
    (6) Except where a ring final sub-circuit is run throughout in metallic conduit, ducts or
trunking, or in metal-sheathed cable, the earth-continuity conductor shall also be run in form of
a ring having both ends connected to earth at the distribution board (or its equivalent).
     (7) Each ring final sub-circuit conductor shall be looped into every socket-outlet or joint box
which forms parts of the ring and shall either remain unbroken throughout its length or,
alternatively, if the conductor is cut, is electrical continuity shall be ensured by joints complying
with the Regulations 50 to 52.
    (8) For ring final sub-circuits complying with Regulations 31(1) to 31(4) the total number of
spurs shall not exceed the total number of socket-outlets and stationary appliances-connected
directly in the ring.
    (9) For ring final sub-circuits complying with Regulations 31(1) to 31(4) the total number of
spurs shall be connected through fused spur boxes. The rating of the fuse shall not exceed that
of the cable forming the spur and in any event shall not exceed 13 amperes. The total current
demand of points served by a fused spur shall not exceed 13 amperes.
    (10) For ring final sub-circuits complying with Regulations 31(1) to 31(4) non-fused spurs shall
be connected to the ring at the terminals of socket-outlets or at joint boxes or at the origin of
the ring in the distribution board. Non-fused spurs shall have a current rating not less than that
of the conductors forming the ring. Not more than two socket-outlets, or one twin socket-outlet,
or one stationary appliance, shall be fed from each non-fused spur.
                                           Page 16 of 173
     (11) In domestic premises, a ring final sub-circuit may serve an unlimited number of points
but shall not serve an area of more than 100m2. Where two or more ring final sub-circuits are
installed, the socket-outlets and stationary appliance to be served shall be reasonably
distributed among the separate ring final sub-circuits.
      (12) For industrial, commercial and other non-domestic installations radial and ring final sub-
circuits otherwise conforming with the requirements of Regulations 31(1) to 31(10) may be
installed where, owing to diversity, the maximum demand of apparatus to be connected is
estimated not to exceed the corresponding fuse or circuit-breaker ratings set out in Table 3 in
schedule 1.
     (13) Provision shall be made so that every portable appliance and portable light fitting can be
fed from an adjacent, conveniently accessible socket outlet.
         Note 1: Industrial and commercial premises it may be desirable to provide pilot       lamps
                   to indicate when portable non-luminous heating appliances such as smoothing
                   irons and soldering irons, are in operation.
         Note 2: For hand-held appliances which are likely to be used out of doors or in damp
                   situations, attention is drawn to the added safety which can be obtained by the
                   use of a double-wound transformer having a reduced secondary voltage or
                   alternatively by the use of monitored earthing-continuity circuits.
31B. Control of socket and appliances
     (1) Where the supply is direct current, each socket-outlet shall be controlled by a switch
immediately adjacent thereto or combined therewith. Where the supply is alternating current
and plug is readily withdrawable, such a switch need not be provided.
     (2) An appliance or light fitting connection to an installation other than by means of a plug
and socket outlet shall be controlled by a switch or switches which shall be arranged to
disconnect all live supply conductors. For an appliance fitted with heating elements which can be
touched or into which more than one phase of the supply is introduced, the switch shall be
linked switch arranged to break all the circuit conductors.
     (3) The switch required by Regulation 31B(2) shall be separate from the appliance or light
fitting in a readily accessible position subject to the provisions Regulations 31B (4), 31B(5) or 31B
(6) where applicable.
      (4) The switch required by Regulation 31B (2) may be mounted on the appliance or light
fittings provided the connections are so arranged that the appliance or light fitting can be
dismantled for maintenance without thereby exposing any parts which remain live shall be as
short as possible, separated from any other conductors or cables by screens of earthed metal or
suitable barriers of insulating material and so installed that they are not adversely affected by
any heat from the applicable or light fitting.
     (5) Where Regulation 168 requires a switch to be situated so as to be normally inaccessible to
a person who is using a bath or shower, it is admissible for the switch to be placed in a suitable
position outside and immediately adjacent to the normal access door of the room, or to be of
the type operated by an insulating cord.
                                           Page 17 of 173
     (6) The switch or switches providing control of comprehensive space cooling, or light
installations, comprising more than one appliance or light fitting may be installed in a separate
room.
32.       Motor circuits
     (1) Every electric motor shall be provided with means for starting and stopping, the latter so
placed as to be easily operated by the person in charge of the motor.
     (2) Every electric motor shall be provided with the control apparatus specified in items (i) –
(iii) below:
                  (i)     means to prevent automatic restarting after a stoppage due to a drop in
                          voltage or failure of supply, where unexpected restarting of the motor
                          might cause danger.
                  (ii)    where more than one method of manually stopping a motor is provided
                          and danger might be caused by the unexpected restarting of the motor,
                          or of a machine being driven by the motor, means to prevent restarting
                          until every stopping device has been reset.
                  (iii)   means of isolation suitably placed and so connected that all voltage may
                          thereby be cut off from the motor and all apparatus including any
                          automatic circuit-breaker, used therewith. If this means of isolation is
                          remote from a motor, an additional means of isolation adjacent to the
                          motor shall be installed, or alternatively, provisions shall be made for the
                          primary means of isolation to be locked in the “off” position.
     (3) Every electric motor having a rating exceeding 0.37kW shall be provided with control
apparatus incorporating a suitable device affording protection against excess current in the
motor or in the cables between the device and the motor. The Supply Authority shall be
consulted regarding starting arrangements for motors requiring heavy starting current.
     (4) Cables carrying the starting, accelerating and load current of a motor shall be of rating at
least equal to the full-load current rating of the motor when rated in accordance with the
relevant Nigerian Standard Specifications.
     (5) A final sub-circuit supplying a motor shall be protected in accordance with the
requirements of Regulation 27A (60 unless Regulation 32 (6) applies.
     (6) Where a starter is provided which affords protection against excess current in a motor
and in the cables between the starter and the motor, the rating of the fuse or circuit-breaker
protecting the final sub-circuit which supplies the motor may be up to twice that of the cable
between the fuse or circuit-breaker and the starter.
     (7) The sizes of the cables for motor circuits of slip-ring or commutator induction motors shall
be suitable for the starting and load conditions.
                                                    PART VII
                                             Conductor and cables
33.       Materials and type cable
     (1) All conductors for internal wiring other than the outer conductors of earthed concentric
systems shall be of annealed copper, and shall conform to Nigerian Standard Specifications.
                                           Page 18 of 173
     (2) Every non-flexible cable for use as fixed wiring operating at low and medium voltages shall
be selected from one of the following types and shall comply with the appropriate Nigerian
Standard Specifications so far as this is applicable. In cables of every type, conductors of cross-
sectional area 10mm2 or less shall be of copper or copper-clad aluminum. Any of the types of
cable sheathed with p.v.c. or lead, or having a h.o.f.r. sheath, if intended for aerial suspension,
may incorporate a catenary wire.
          (i)        Non-armoured p.v.c. insulated cables,
          (ii)       Armoured p.v.c. insulated ,
          (iii)      Split-concentric copper-conductor p.v.c. insulated cables,
          (iv)       Rubber insulated cables,
          (v)        Impregnated-paper-insulated, lead-sheathed or aluminum sheath,
          (vi)       Mineral-insulated metal-sheathed cables
     (3) Bus-bars and bus-bar connections on switch boards shall comply with Nigerian Standard
Specifications. The requirement does not apply to bus-bar trunking system.
     (4) Every conductor for use as an overhead line shall be selected from one of the following
types and shall comply with the appropriate Nigerian Standard Specifications:
          (i)        Hard-drawn copper or cadmium-copper conductors,
          (ii)       Hard-drawn aluminum and steel-cored aluminum conductors,
          (iii)      Aluminum-alloy conductors,
          (iv)       Insulated conductors for overhead power lines.
     (5) Every flexible cable and flexible cord for use at low and medium voltages shall be selected
from one of the following types and shall comply with the appropriate Nigerian Standard
Specifications so far as this is applicable.
This regulation does not apply to a flexible cord forming part of a portable appliance or light
fitting where the appliance or light fitting as a whole is the subject of and complies with Nigerian
Standard Specifications, or to special flexible cables and flexible cords for combined power and
telecommunication wiring –
               (i)      insulated flexible cords,
               (ii)     rubber insulated flexible cables,
               (iii)    P.V.C. insulated flexible cables (non-Armoured),
               (iv)     Braided traveling cable for lifts,
               (v)      Rubber-insulated flexible trailing cables for quarries and miscellaneous mines.
                        Such rubber insulated flexible cables and flexible cords, may incorporate a
                        flexible armour of galvanized steel or phosphor-bronze, or a screen of tinned
                        copper-wire braid.
     (6) All cables, including flexible cables and flexible cords, for use at extra-low voltage shall
have adequate insulation, and further protection if necessary, to ensure that they do not cause
risk of fire.
34.       Choice of type installation
    (1) The type of installation and protective covering if any, of every cable for fixed wiring shall
be selected so as to allow compliance with the requirements of this Section as to precaution
against mechanical damage by heat fire or explosion, and damp and corrosion.
                                           Page 19 of 173
    (2) Cables insulated and/or sheathed with general-purpose p.v.c. shall not be installed in
refrigerated spaces or other situations where the temperature is considered consistently below
0oC.
    (3) Single-core cables armoured with steel wire or tape shall not be used for a.c.
    (4) Every flexible cable and flexible cord shall be selected from one of the following types –
                 (i)      braided circular,
                 (ii)     un-kinkable,
                 (iii)    circular sheathed,
                 (iv)     flat-twin sheathed,
                 (v)      braided circular twin and three-core, insulated with glass fiber; provided
                          that these types shall be used only in dry situations for light fitting or for
                          other applications where the cord is not subject to abrasion or undue
                          flexing.
    (5) Flexible cables and flexible cords, where they are exposed to risk of mechanical damage,
shall as a minimum be of a type sheathed with rubber or p.v.c. and where necessary shall also be
armoured.
    (6) Flexible cables and flexible cords which in normal use are exposed to risk of contact with
water shall be of a type sheathed with rubber or p.v.c.
    (7) Where flexible cables or flexible cords are exposed risk of contact with oil or petrol, or
where cable which will not support combustion is required, use shall be made of cables or cords
having a p.v.c., h.o.f.r. or oil resisting and flame retardant sheath.
35.      Voltage rating and conductor sizes
     The voltage rating of every cable shall be not less the decleared or nominal voltage of the
circuit.
36.      (1) The size of every bare conductor or cable conductor shall be such that its current
rating as stated in Table 15-33 and or the Preface thereto, after the application of any factors
appropriate to the type of cable, the conditions of installation, and the class of excess-current
protection provided it is not less than the maximum sustained current which will normally flow
through it. This regulation does not apply to certain conductors on switchboards.
    (2) No cable having a conductor of nominal sectional area less than 1mm 2 and no flexible
cord having a conductor of nominal section area less than 0.75mm2 shall be used
    (3) Service mains shall be stranded, and shall have a carrying capacity not less than the
maximum demand of the installation, but in no case shall they be smaller than 6mm2.
37.      (1) Where the maximum demand is not readily ascertainable it shall be assessed as
follows –
Lighting                                    Two-thirds of connected load.
Heating (including cooking
   and cooling)                    Three-quarter of connected load.
Power:
         One motor                          Total connected load.
         Two motors                         Three-quarters of connected load.
         Exceeding two and not
                                            Page 20 of 173
         exceeding five motors              Two-thirds of connected load.
         Exceeding five motors One-half of connected load.
    (2) Where electrical energy is used for more than one purpose the maximum demand shall be
assessed by adding together the figures obtained from the above calculations.
    (3) The earthing-lead shall be stranded cable or flat copper, the latter not less than 19mm
wide by 3mm. No conductor of a cross-sectional area less than 6mm2 shall be used as an
earthing lead.
38.      (1) Every conductor used as earth continuity conductors shall have cross-sectional area
of not less than the cross-sectional area of the largest live conductor but in any case not less
than 1.5mm2
    (2) Cables connected in parallel shall be of the same type, size and length, to ensure proper
division of the current.
    (3) The size of every bare conductor or cable conductor shall be such that the drop in voltage
from the consumer’s terminals to any point in the installation does not exceed 2.5 % of the
declared or nominal voltage when the conductors are carrying the full load current, but
disregarding starting conditions. This requirement shall not apply to wiring fed from an extra-low
voltage secondary of a transformer.
    (4) Where allowance is made for diversity, it may be taken into account in calculating voltage
drop.
                                                  General installation
39.      Protection against damages
    (1) All conductors and cables shall be adequately protected against any risk of mechanical
damage to which they may be liable in normal conditions of service.
    (2) Where cables pass through holes in metalwork, precautions shall be taken to prevent
abrasion of the cables on any sharp edges.
    (3) Non-sheathed cables shall be protected by enclosure in conduit, duct or trunking.
    (4) Cables shall not be run in a lift (or hoist) shaft unless they form a part of the lift
installation. Cables of lift installations, other than traveling cables, in such a shaft shall be:
         (i) armoured, or
         (ii) mineral-insulated, metal-sheathed, or
         (iii) of a type having a h.o.f.r. or oil-resisting and flame-retardant shaft, or
         (iv) enclosed in metal conduit, duct or trunking, high impact rigid p.v.c. conduit, or
         otherwise effectively protected against mechanical damage.
40.      Bending and supports
     The internal radius of every bend in a cable shall be not less than the appropriate value
stated in Table 4.
41.      Every cable installed in or on a building shall be supported by one of the methods
described below and supports shall be so arranged that there is no appropriate mechanical
strain on any cable termination.
                  i.   for non-sheathed cable, installation in conduit without further fixing of the
                       cables, provided, that precautions are taken against undue compression of
                       the installation at the top of any vertical runs exceeding 5m in length,
                                          Page 21 of 173
              ii.    for non-sheathed cables, installation in trunking without further fixing of the
                     cables provided, that vertical runs shall not exceed 5m in length without
                     intermediate support,
               iii.  for sheathed and/or armoured cables installed in accessible positions,
                     supported by clips at appropriate spacings,
                iv.  for cables of any type, resting without fixing in horizontal runs of ducts or
                     trunking,
                 v.  for sheathed and/or armoured cables installed in horizontal runs which are
                     inaccessible and unlikely to be disturbed, resting without fixing on part of a
                     building provided that the surface is dry and reasonably smooth,
                vi.  for sheathed-and-armoured cables in vertical runs which are inaccessible and
                     unlikely to be disturbed, support at the top of the run by a clip and a round
                     support of a radius not less than the appropriate valued stated in Table 4,
               vii.  for sheathed cables without armour in vertical runs which are inaccessible
                     and unlikely to be disturbed, support by the method described in item (vi)
                     above; provided that the length of run without intermediate support shall
                     not exceed 2m for a lead/sheathed cable or 5m for a rubber or p.v.c.
                     sheathed cable,
              viii.  for rubber or p.v.c. sheathed cables, installation in conduit without further
                     fixing of the cables, provided that any vertical shall be in conduit of suitable
                     size and shall not exceed 5m in length;
                ix.  for rubber or p.v.c. sheathed cables installed as surface wiring, clips shall be
                     spaced at intervals not exceeding 200mm,
                 x.  support by a catenary wire incorporated in the cable during manufacture,
                     provided that the spacings between supports shall not exceed those stated
                     by the manufacturer,
                xi.  for flexible cords used as pendants, attachment to a ceiling rose similar
                     accessory by the cord-grip or other method of strain relief provided in the
                     accessory,
               xii.  for cables of the types described in items (i) and (iii) of Regulation 39(4) in lift
                     shafts, support by clip at spacings not exceeding 1m.
42.      Protection against heat
    Every cable shall be so selected and installed as to be suitable for operation under such
ambient temperatures of its surroundings as are likely to occur, which shall not exceed the
appropriate value stated by the manufacturer, account being taken of any transfer of heat from
any accessory, appliance (e.g. immersion heater or other appliance) or lighting fitting to which
cable or flexible cord is connected.
43.      Flammable and explosive locations
    If it is necessary to install cables in a situation where flammable and/or explosive, dust,
flammable volatile liquid or vapour or gas is likely to be present, or where explosive materials
are handled or stored, one or more of the following types of wiring systems shall be used. This
                                            Page 22 of 173
regulation does not apply to cables of intrinsically-safe circuits; nor does it normally apply to
adequately ventilated battery rooms or garages –
                 i.       cables in solid-drawn or seam-welded conduit,
                ii.       lead-sheathed, steel-armoured cable,
               iii.       mineral insulated cable or copper-sheathed cable,
               iv.        armoured p.v.c. insulated cable having an overall extruded covering of
                          p.v.c. provided that this type shall not be buried direct in ground which
                          may be contaminated by flammable volatile liquid.
44.      Where cables, conduits, ducts or trunking pass through floors, walls, partitions or
ceilings, the surrounding hole shall be made good with cement or similar fire-resisting material
to the full thickness of the floor, wall, etc. and space through which fire or smoke might spread
shall not be left around the cable, conduit, duct or trunking. In addition, where cables, conduits
or conductors are installed in channels, ducts, trunking, or shafts which pass through floors,
walls, partitions or ceilings, suitable internal fire-resisting barriers shall be provided to prevent
the spread of fire.
45.      Damp and corrosive situations
   (1) Every cable shall be installed where it will not be exposed to rain, dripping water,
condensed water, accumulations of water or oil, or corrosive substance; or shall be of a type
designed to withstand such explosive.
   (2) In damp situations and wherever they are exposed to the weather all metal sheaths and
armour of cables, metal conduit, duct, or trunking, and clips and their fixings, shall be of
corrosion-resisting material or finish and shall not be placed in contact with other metals with
which they are liable to set up electrolytic action; conduit, if of steel shall be galvanized heavy-
gauge. This regulation does not normally apply to conduit buried in plaster.
46.      (1) Armoured p.v.c. insulated cables and mineral-insulated metal-sheathed cables
installed in damp situations or in concrete ducts or wherever exposed to the weather or other
risk of corrosion, shall be of a type having an overall extruded covering of p.v.c.
    (2) Aluminum-sheathed cables installed in underground pipes or in concrete ducts shall be
provided with a corrosion-resistant finish.
47.      Segregation of circuits
Where an installation comprises extra low-voltage or telecommunication or fire-alarm circuits,
as well as circuits operating at low voltage and connected directly to a mains supply system,
precautions shall be taken, to prevent electrical contact between the cables of the various types
of circuit.
48.      (1) Types of circuit described in these Regulations are divided into categories as follows:
         (a) Category I circuits: circuits (other than fire alarm circuits) operating at low voltage
             and supplied directly from a mains supply system.
         (b) Category II circuits: with the exception of fire-alarm circuits, all extra low-voltage
             circuits; and telecommunication circuits (e.g. radio, telephone, sound-distribution,
             burglar-alarm, bell and call circuits) which are not supplied directly from a mains
             supply system.
         (c) Category III circuits: fire-alarm circuits.
                                           Page 23 of 173
   (2) Cables of Category I circuits shall not be drawn into the same conduit or duct as cables of
Category II circuits, unless the latter cables are insulated in accordance with the requirements of
these Regulations for the highest voltage present in the Category I circuits.
    (3) Cables of Category I circuits shall not in any circumstance be drawn into the same conduit
or duct as cables of Category III circuits.
49.      A. (1) where a common channel or trunking is used to contain cables of Category I
circuits, and Category II circuits, all cables connected to Category I circuits, shall be effectually
partitioned from the cables of the Category II circuits, or alternatively the latter cables shall be
insulated in accordance with the requirements of these Regulations for the highest voltage
present in the Category I circuits. Where a common channel or trunking is used to contain cables
of Category I and Category III circuits, the two Categories of circuits shall be separated by
continuous partitions of fire-resisting material; provided that this requirement shall not apply
where the Category III circuits are wired in mineral-insulated metal-sheathed cable.
    (2) In conduit, duct, or trunking systems, where controls or outlets for Category I and
Category II circuits are mounted in or on common boxes, switch-plates or blocks, the cables and
connections and the two Categories of circuits shall be partitioned by means of rigid fixed
screens or barriers. At any common outlets in a trunking system for Category I and Category III
circuits, the two categories of circuits shall be separated by continuous partitions of fire resisting
material.
    (3) Where cores of Category I and Category II circuits are contained in a common multi-core
cable, flexible cable or flexible cord, the cores of the Category II circuits shall be insulated
individually or collectively as a group, in accordance with the requirements of these Regulations,
for the highest voltage present in the Category I circuits, or alternatively shall be separated from
the cores of the Category I circuits by an earthed metal braid of equivalent current-carrying
capacity to that of the cores of the Category I circuits. Where terminations of the two categories
of circuits are mounted in or on common boxes, switch-plates or blocks, they shall be partitioned
in accordance with Regulations or alternatively be mounted on separated and distinct terminal
blocks adequately marked to indicate their functions
    (4) Cores of Category I and Category III circuits shall not in any circumstances be contained in
a common multi-core cable, flexible cable or flexible cord.
     (5) Metal sheaths and armour of all cables operating at low voltage, and metal conduits,
ducts and trunking and bare earth-continuity conductors associated with such cables; which
might otherwise come into fortuitous contact with other fixed metalwork shall be either
effectually segregated therefrom, or effectually bonded thereto so as to prevent appreciable
voltage differences at such possible points of contact. Electrical services shall not be installed in
the same conduit or trunking as pipes or tubes of non-electrical services e.g. air, gas, oil or water.
        B. Identification of conductors
     (1) Every non-flexible single-core and every core of a win or multi-core cable for use as fixed
wiring shall be identifiable at its terminations and preferably throughout its length, by the
appropriate method described in items (i) to (v) below
This regulation does not apply to special cables designed for heating –
                                           Page 24 of 173
         (a) for rubber and p.v.c. insulated cables, the use of core colours in accordance with the
             requirements of Table 5A of the Schedule 1 or the application at termination of
             sleeves or discs of the appropriate colours prescribed in the Table.
         (b) for armoured p.v.c. insulated cables as an alternative to the method described in
             items (a) above, the use of numbered cores; provided that the numbers 1, 2 and 3
             shall signify live conductors, the number 0 the neutral conductor, and the number 4
             the fifth (special-purpose) core, if any;
         (c) for paper-insulated cables, the use of numbered cores, provided that the numbers 1,
             2 and 3 shall signify live conductors, the number 0 the neutral conductor, and the
             number 4 the fifth (special-purpose) core, if any
         (d) for mineral-insulated cables, the application at terminations of sleeves or discs of the
             appropriate colours prescribed in Table 5A Schedule 1.
   (2) Bare conductors shall be made identifiable where necessary by the application of sleeves
or discs of the appropriate colours prescribed in Table 5A Schedule 1 or by painting with those
colours.
   (3) Any scheme of colouring used in a consumer’s installation to identify switchboard bus-bars
or poles shall comply with the requirements of Table 5A so far as these are applicable.
   (4) The cores of every flexible cable including a flexible cord, shall be coloured throughout in
accordance with the requirements of Table 5B Schedule 1. The colour combination, green and
yellow is reserved exclusively for identification of earthing conductors and shall not be used for
any other purpose. This regulation does not apply to p.v.c. installed parallel-twin non-sheathed
flexible cords.
   (5) Flexible cables or flexible cords having the following core colours shall not be used; green
alone; yellow allow alone; or any bicolour other than the colour combination green-and-yellow
mentioned in Regulation 49(4).
50.      Terminations
    (1) All terminations of cable conductors and bare conductors shall be mechanically and
electrically sound.
   (2) Every connection at a cable termination shall be made by means of a terminal, soldering
socket, or compression-type socket; shall securely contain and anchor all the wires of the
conductor, and shall not impose any appreciable mechanical strain on the terminal or socket.
   (3) An aluminum conductor shall not be placed in contact with a terminal of brass or other
metal having a high copper content, unless the terminal is suitably plated or other suitable
precautions are taken to prevent corrosion.
   (4) At every cable termination, the insulation shall be removed no further than is necessary
for compliance with Regulation 50(2).
   (5) At every cable termination, any braid, tape, sheath, or amour over the insulation shall be
cut back from the end of the insulation, as may be necessary to prevent undue leakage from live
parts of the braid, tape, sheath, or armour. This regulation does not apply to mineral-insulated
cables.
   (6) In any situation, the exposed conductor and insulation of cables insulated with
impregnated paper shall be protected from ingress of moisture by being suitably sealed.
                                           Page 25 of 173
    (7) The ends of mineral-insulated metal-sheathed cables shall be protected from moisture by
being suitably sealed and the insulation shall be thoroughly dry before the sealing material
applied. Such sealing material, and any material used to insulate the conductors where they
emerge from the insulation, shall have adequate insulating and moisture proofing properties,
and shall retain these properties through the range of temperatures to which the cable is
subjected in service.
    (8) Soldering fluxes which remain acidic or corrosive at the completion of the soldering
operation shall not be used.
51. (1) Where a non-metallic outlet box of thermoplastic material (e.g. p.v.c) is used for the
suspension of, or is in contact with, a light fitting, care shall be taken to ensure that the
temperature of the box does not exceed 600C. The mass suspended from the box shall not
exceed 3 kg.
      (2) The termination of cables in a situation where flammable and/or explosive dust,
flammable volatile liquid vapour or gas is likely to be present, or where explosive materials are
handled or stored, shall be avoided wherever possible Otherwise, terminations shall be enclosed
in a flame-proof fitting or alternatively, where methods are employed for avoiding the explosion
hazard other than by the use of flame-proof equipment the terminations shall be enclosed in a
box suitable for such use.
     (3) Cable glands shall securely retain the outer sheath or armour of the cables without
damage to these, and where necessary shall incorporate adequate means of maintaining earth
continuity between the sheath or armour and the threaded fixing component of the glad.
52. Cable joints
    (1) Where joints in cable conducts and bare conductors are necessary they shall be
mechanically and electrically sound. Joints in non-flexible cables shall be accessible for
inspection provided that this requirement shall not apply to joints in cables buried underground,
or joints buried or enclosed in non-combustible building material so that no danger can arise.
Joints in non-flexible cables shall be made by soldering, brazing, welding, or mechanical clamps,
or be of the compression type; provided that mechanical clamps shall not be used for,
inaccessible joints buried or enclosed in the building structure. All mechanical clamps and
compression-type sockets shall securely retain all the wires of the conductors.
    (2) Every joint in a cable shall be provided with insulation not less effective than that of the
cable cores and shall be protected against moisture and against mechanical damage. Soldering
flues which remain acidic or corrosive at completion of soldering operation shall not be used.
    (3) For joints in paper-insulated metal-sheathed cables, a wiped metal sleeve or joints box,
filled with insulating compound, shall be provided.
                                            Wiring systems
53. (1) Bare or lightly-insulated conductors may be insulted in building for the following
purposes only-
                i.  earth continuity conductors, earthing leads;
               ii.  the external conductors of earthed concentric wiring systems;
              iii.  conductors extra-low voltage systems;
              iv.   protected rising-main and bus-bar systems;
                                          Page 26 of 173
              v.    collector wires for travelling cranes or trolleys or for similar purposes.
      (2) Bare or lightly-insulated conductors of extra-low voltage systems shall have adequate
insulators, and further protection where necessary, to ensure that they do not cause risk of fire.
54. (1) Where bare conductors are used for rising-main and bus-bar systems operating at low
voltage, they shall
         (a) be so installed that they are inaccessible to un-authoried persons and either be
             totally enclosed in earthed metal or fixed in a channel, trunking, or shaft specially
             provided for the purpose; and
         (b) be of adequate strength to withstand the electro-mechanical forces that may be set
             up by prospective short-circuit current; and
         (c) be free to expand and contract, as the temperature changes, without detriment to
             themselves or to any other part of the installation; and
         (d) Where they pass through floors, walls, partitions, or ceilings, they shall pass through
             directly and be protected by enclosure in non-absorbent, non-combustible insulating
             material, unless earth metal trunking is used.
       (2) Bare collector wires of the type described in item (v) of Regulation 53(1) which are
necessarily exposed in normal service shall be efficiently protected accidental contact by screens
or barriers or by adequate clearance. At each strain position for such wires, suitable straining
gear fitted with double insulators shall be provided.
55. Metal sheathed and armoured cables
 All metal sheaths and armour of cables and associated accessories shall be earthed in
accordance with these Regulations. Where non-metal joints boxes are used with metal-sheath
and, or armoured cables, the continuity shall be maintained by a metal bonding strip or similar
means having a resistance not higher than that of an equivalent length of metal cable sheath or,
(for armoured non-mental sheathed cables), the armour of the largest cable entering the box.
56. Paper insulated cables
Paper insulated cables shall be of a non-draining type which will comply with appropriate
Nigerian standard, where migration of the impregnating compound would otherwise be liable to
occur.
57. Conduits systems
   (1) The conduits for each shall be completely erected before any cable is drawn in. This
requirement does not apply to prefabricated flexible conduit systems which are not wired in-
situ.
   (2) Conduits shall be securely fixed, and where they are liable to mechanical damage they
shall be adequately protected.
   (3) Inspection type conduit fittings such as inspection boxes, draw boxes, bends, elbows, and
toes, shall be so installed that they can remain accessible for such purposes as the withdrawal of
existing cables or the installing of additional cables.
58.      The number of single core rubber insulated, braided and compounded cable, of p.v.c.
insulated non-sheathed cables run in one conduit shall be such as to permit of easy drawing in.
The number of cables drawn in shall not be greater than the appropriate number given in Table
6 or Table 7 of schedule I as applicable. For types of cables having large overall diameters than
                                          Page 27 of 173
 those shown in the Table, appropriate reduction shall be made in the number of cable drawn in.
 For groups of cables other than those provided in Table 6 and 7, the number and sizes of the
 cables installed shall be such that a space factor of 40% is not exceeded. The numbers stated in
 the tables; and the space factor of 40% relate to conduit runs incorporating not more than two
 900 bends or radius not less than that specified for normal bends or for runs having more bends
 than this or having opposing adjacent bends for runs containing additional sets or other
 restrictions, appropriate reduction shall be made in the number of cables installed.
 59. (1) The use of solid (non-inspection) conduit, elbows or tees shall be restricted to –
              (a) locations at the ends of conduits immediately behind a light fitting outlet box or
                  accessory of the inspection type; or
              (b) one solid elbow located at a position not more than 500mm from a readily
                  accessible outlet point provided that all other bends in the conduit run are not
                  more than the equivalent of one right angle.
     (2) Ends of lengths of conduits shall be so reamed and where they terminate at boxes,
 trunking and accessories not fitted with spout entries, shall be so bushed, as to obviate abrasion
 of cables.
     (3) Substantial boxes of ample capacity shall be provided at every junction involving a cable
 connection in a conduit system. Where non-metallic conduits used, and where metal conduits
 are terminated, boxes may be of non-absorbent, non-flammable material other than metal. All
 unused conduit entries shall be blanked off, and all removable covers firmly secured to provide
 complete enclosure.
     (4) Conduit systems not intended to be gas-tight shall be self-ventilating, and drainage outlets
 shall be provided at any points in the installation where condensed moisture might otherwise
 collect.
60. Metal conduit: special requirement
     (1) Metal conduits and fittings for use in wiring systems shall comply with Nigerian Standard
 Specifications for rigid steel conduits and fittings; for flexible steel conduits and adaptors and for
 aluminum or zinc-base-alloy conduits and fittings as appropriate. Where steel pipes are used as
 conduits, they shall comply with appropriate Nigerian Standard Specifications and shall have a
 corrosion-resistant finish inside and outside.
     (2) Metal conduits systems shall be earthed. All join shall be made mechanically and
 electrically continuous by screwing or by substantial mechanical clamps, or by inserts but plain
 slip or pin-grip sockets shall not be used.
     (3) For the purposes of these Regulations flexible steel conduits having an outer sheath of
 insulation material (e.g., p. v. c.) shall be deemed to be metal conduits.
     (4) Cables of a. c. circuit installed in steel conduit shall always be so bunched that the cable of
 all phases and the neutral conductor (if any) are contained in the same conduit.
 61. Non-metal conduit: special requirement
     (1) Rigid non-metallic conductors and fittings for use there-with shall comply with relevant
 Nigerian Standard Specifications as appropriate.
                                            Page 28 of 173
   (2) Non-metallic systems shall be used only where it is ensured that they are suitable for the
extremes of ambient temperatures to which they are likely to be subject in service, and where
used, earth continuity conductor shall be installed throughout the system.
   (3)The method of support for rigid p. v. c. conduit shall allow for the longitudinal expansion
and contraction of the conduits which may occur with variation of temperature under normal
operating conditions.
   (4) For the purposes of these Regulations, conduits comprising metal parts having an inner
and outer covering of insulating materials are deemed to be non-metallic conduits, provided that
effective precautions are taken to prevent the metal parts of the conduits at their ends from
coming into contact with any other metal parts.
62.      (1) Flexible metal conduit and fittings shall comply in all respects with relevant Nigerian
Standard Specifications. Flexible non-metallic conduit shall comply with relevant Nigerian
Standard Specifications and fittings for use therewith shall also comply with the relevant
Nigerian Standard Specifications.
   (2) (a) Flexible metal conduit shall not be used as the sole means of providing earth-
continuity, and earth-continuity conductor complying with the requirements of Nigerian
Standard Specifications shall be provided for every part of a system formed by such conduit.
       (b) Where necessary, flexible conduit shall be adequately supported.
63. Pre-fabricated, duct and trunking systems
    (1) In the prefabrication of conduit systems which are not to be wired in-situ, adequate
allowance shall be made for variations in building dimensions so that the conduits or cables are
not subjected to tension or other strain during installation. Adequate precautions shall also be
taken against damage so such systems during installation and any subsequent building
operations, especially against deformation of the conduits and damage to any exposed cable
ends.
    (2) Ducts of metal or insulating material, and trunking, shall be securely fixed, and where
they are liable to mechanical damage they shall be adequately protected.
    (3) Trunking shall be constructed of metal or non-combustible insulating material.
    (4) Cables of a.c. circuits installed in steel ducts or trunking shall always be so bunched that
the cables of all phases and the neutral conductor (if any) are contained in the same duct or
trunking.
    (5) Every entry to finished ducts or trunking shall be so placed as to prevent the ingress of
water, or be protected against such ingress. All removable covers shall be securely fixed after
wiring is completed.
    (6) Every outlet for cables from a duct system, every joint in such a system, and every joint
between such a system and another type of duct or conduit, shall be so formed that the joints
are mechanically sound and that the cables drawn in are not liable to suffer abrasion.
    (7) Every bend formed in a concrete duct (whether or not formed by channels or formers
retained in position after the concrete has set) shall be of an inner radius not less than four times
the diameter of the completed duct.
    (8) Ducts cast in situ in concrete, by means of a suitable form laid before the concrete is
poured, into which cables are to be drawn (whether or not former are retained in position after
                                           Page 29 of 173
the concrete has set) shall be so formed that the radial thickness of concrete or screed
surrounding the cross-section of the completed duct is not less than 15mm at every point.
Where all or any part of the completed duct is formed by the concrete or the screed rubber-
insulated, braided and compound cables, non-sheathed p.v.c.-insulated cables are installed in
this type of duct and there is a risk that the duct may become damp, the cable shall be of a type
having overall extruded covering of p.v.c.
     (9) The number of cables to be installed in ducts shall as will permit easy drawing-in without
damage to the cables and shall be such that a space factor of 35% is not exceeded. This space
factor relates to runs of ducts incorporating not more than two 90o bends or the equivalent; for
runs having more bends than this, appropriate reduction shall be made in the number of cables
installed.
     (10) The number of cables to be installed in trunking or channels shall such that a space
factor of 45% is not exceeded.
64. Flexible cords and cables: special requirements
    (1) Flexible cables or flexible cords shall be used for all connections to movable apparatus.
For the purposes of this regulation, an electric cooker of rated input exceeding 3kW is deemed
not to be movable.
    (2) Where armoured flexible cables and flexible cords are used, the armouring shall not be
used as the sole means of providing earth continuity conductor shall be provided.
    (3) Flexible cables and flexible cords shall not be used as fixed wiring unless contained in
earthed metal or other non-combustible and mechanically strong enclosure; provided that this
requirement shall not apply to short lengths of sheathed flexible cable or flexible cord used for
final connections to fixed apparatus or of connection of control of gear of fluorescent lamps or
discharge lamps. Non-sheathed flexible cables and flexible cords shall not be drawn into conduits
or ducts.
65.      (1) Exposed lengths of flexible cables cord used for final connections to fixed apparatus
shall be as short as possible and connected to the fixed wiring by one of the following means–
                  i. a plug and socket-outlet; or
                 ii. a fused spur-box having suitable provision for the entry of the flexible cable
                     or flexible cord; or
                iii. a switch forming the means of local control of the apparatus; or
                iv. a suitable joint box
         (2)     Where a twin flexible cord supports, or partly supports, a light fitting, the
maximum mass supported by the cord shall not exceed the appropriate value indicated below–
                Nominal cross-sectional area of conductor (mm)2   Maximum mass (kg)
                                     0.75                                 3
                                     1.0                                  5
        (3)     No flexible extension shall be taken more than 2m across a ceiling to a drop-light.
Such flexible extensions shall be supported by an insulated hook fixed to the ceiling.
66. Earthed concentric wiring
   (1) Earthed concentric wiring may be used only after approval has been given by-
                                             Page 30 of 173
          (a) The Electricity Supply Authority where the supply is obtained from an electric power
              Board or other public body.
          (b) The Director of Electrical Inspectorate services in any other case.
    (2) The use of earthed concentric wiring shall in all cases be subject to the following
conditions-
        i. When the supply is derived from the supply Authority’s main it shall be taken from the
            secondary side of the transformers or converter so arranged that the public supply
            system is electrically insulated therefrom.
       ii. Every earthed concentric installation shall be so arranged that the internal conductor is
            protected by a single –pole circuit-breaker or switch and fuse placed in a position easily
            accessible to the consumer and situated as near as possible to–
            (a) The point or points of entry of the service main or to the secondary of the
                transformer, in case of a public supply; or
            (b) The generator in any case.
67. Earthed concentric installations
    (1) When the supply is direct current the external conductor shall always be the one nearest
to earth potential and shall, where possible be negative to the inner conductor; and the
difference of potential between ant two points in the external conductor shall not exceed.
    (a) Seven volts if the internal conductor is connected to the positive pole of the system; or
    (b) One and a half volts if the internal conductor is connected to the negative pole of the
          system.
    (2) From the position or positions at which the installation is earthed, concentric wiring shall
be employed throughout up to all fixed positions for fittings or accessories. At all positions
where the external conductor ceases to surround the internal conductor the latter shall be
separated from the surface upon which the fitting or accessory is mounted by an in-corrodible
metal plate or terminal box to which the external conductor is electrically connected. This
requirement does not preclude the interposition of wooden block between the metal plate and
the fitting or accessory mounted thereon, provided that this metal plate covers the principal
recessed in the wooden block.
    (3) Where the sheathing of a cable is used as one conductor, the resistance of the sheathing
shall not be greater than that of the inner conductor when measured at a temperature of 200C.
    (4) Joints in the external conductor, however made, shall be of such a nature that the
conductivity of the conductor is not reduced.
    (5) All circuits, lamps, and appliances shall be controlled and protected by single-pole circuit-
breakers, or switches and fuses, which shall be inserted in the internal conductor if the circuit.
No circuit-breaker, switch, or fuse, shall be included in the external conductor.
    (6) Ordinary accessories may be used, but if lamp-holders having central contacts are
employed, such central contacts shall be connected to the internal conductor.
    (7) Lamp fittings, may be wired with two separated wires, one being insulated and
connected to the internal conductor and the other to the metal work of the fitting.
                                           Page 31 of 173
    (8) Twin flexible cords may be used between fixed points and portable or pendant fittings. If
such flexible cords terminate in plug-and-socket connections, these connections shall be of
either the concentric or the two-pin polarized type.
68. Consumers wiring between buildings
    (1) Consumer’s wiring intended for operation at low voltage and installed underground for
distribution between a building and point of utilization not attached thereto (e.g. another
building), shall be in the form of one or more of the following systems, using the types of cable
indicated-
                                                   In ducts
       (i)        metal-sheathed and served cable or
       (ii)       general-insulated, metal-sheathed cable having an overall extruded covering of
                  p.v.c or
       (iii)      armoured p.v.c insulated cable having an overall extrude covering of p.v.c or
       (iv)       p.v.c. insulated, p.v.c. sheathed cable or rubber-insulated cable having an oil-
                  resisting and flame-retardant or h.o.f.r. sheath.
                                             In conduits or pipes
    (2) (a) p.v.c. insulated, p.v.c sheathed cable, or rubber-insulated cable having an oil-
             resisting and flame-retardant or h.o.f.r. sheath in adequately protected heavy-gauge
             steel conduit or galvanized steel pipe, provided that the conduit or pipe shall not be
             used as an earth-continuity conductor, or
             (b) p.v.c. insulated sheathed cable or rubber-insulated cable having an oil-resisting
                  and flame-retardant or h.o.f.r. sheath in non metallic conduit.
                                          Laid Direct In the Ground
    (3) (a) metal-sheathed, armoured and served underground cable, or
              (b) armoured p.v.c. insulated cable having overall extruded covering of p.v.c., or
              (c) metal-sheathed and served underground cable, or mineral insulated copper-
sheathed cable having an overall extruded covering of p.v.c. with mechanical protection by cable
cover except where installed under a permanent surface.
69. Consumer’s wiring intended for operation at low voltage and installed on exterior surface
walls, boundary walls and the like for distribution between a building and a point of utilization
not attached thereto (e.g. another building), shall be in the form of one or more of the following
systems. Such wiring shall not be installed on fences.
    (i)         Heavy-gauge hot-dipped galvanized steel conduit (see Appendix 2) or steel pipe
                systems complying with Regulations 60(1) – (4),
    (ii)        Mineral-insulated, metal-sheathed cable, preferably having an overall covering of
                p.v.c preferably black in colour.
    (iii)       Armoured and served cables or preferably, armoured cables having an overall
                covering of p.v.c. or an oil-resisting and flame-retardant or h.o.f.r. sheathed overall
                preferably black in colour.
    (iv)        Lead-sheathed cables;
    (v)         insulating cables having a p.v.c. sheath preferably black in colour, or high impact rigid
                p.v.c. conduit, preferably black in colour
                                            Page 32 of 173
70. Consumer’s overhead wiring intended for operation at low voltage and for distribution
between a building and a point of utilization not attached thereto (e.g. another building), shall
be in the form of one or more of the following systems using the types of cable or conductor
indicated. Lengths of span shall not exceed, and heights above ground shall be not less than, the
appropriate values indicated in Table 8 Schedule 1–
                (i) p.c.v. insulated, p.v.c. sheathed cable, or rubber-insulated cable having an
                      oil-resisting and flame-retardant or h.o.f.r. sheath referable black in colour,
                      without intermediate support; provided that the terminal supports shall be
                      so arranged that no undue strain is placed upon the conductors or insulation
                      of the cable, and provided that adequate precautions are taken against any
                      risk of chafing of the cable sheath,
                (ii) P.v.c. insulated, p.v.c. sheathed cable, or rubber-insulated cable having an oil-
                      resisting and flame-retardant or h.o.f.r. sheath, installed in heavy-gauge hot-
                      dipped galvanized steel conduit without intermediate support: provided that
                      the conduit shall be earthed in accordance with part XI and shall be securely
                      fixed at the ends of the span, shall not be jointed in its span
                (iii) P.v.c covered overhead line conductors of hard-drawn copper, hard-drawn
                      cadmium copper, hard-aluminum, steel cored aluminum, aluminum alloy,
                      installed on insulators without intermediate support: provided that no part of
                      the span shall be accessible to any person from any building or other place
                      without the use of a ladder or other special device,
                (iv) Cables having a sheath of p.v.c. or lead, or an oil-resisting and flame-
                      retardant or h.o.f.r. sheathed preferably supported by a catenary wire,
                (v) Special aerial cable incorporating a catenary wire,
                (vi) Bare or p.v.c. covered overhead lines having conductors of hard-drawn
                      copper, hard-drawn cadmium copper, hard-aluminum or steel-cored
                      aluminum or aluminum alloy.
71. A. Collector and trolley cables
   (1) Bare conductors may be used as collector or trolley wires for travelling         cranes   and
similar appliances and for battery connections.
   (2) They shall be supported upon insulators, and so spaced that risk of accidental contact
between the conductors themselves or between conductors and walls or any other conducting
structure is reduced to a minimum.
   (3) The circuit supplying current to such bare conductors shall, except in the case of the
regulating cells of batteries, be protected either by a suitable circuit-breaker or by a suitable
switch and fuse.
   (4) Bare conductors extended to positions liable to lightening-discharge shall be fitted with
lightening-arrestors on each pole or phase.
   (5) Wall rosettes or brackets used as supports for span-wires shall not be fixed within 300mm
of any gas-pipe.
                                           Page 33 of 173
   (6) Except as herein before specified, bare conductors shall be used only in positions not
ordinarily accessible to unauthorized persons and in such circumstances as my be sanctioned by
the authorized inspector.
71B. Cables which are used in connection with the electric bells telephone and signaling
apparatus, etc., in a building shall be kept away from and not be installed in the same casing or
conduit as the cables used for distribution of the electrical supply throughout the building.
72. Bell and signaling circuits (except telephone circuits) may be operated from the electric
lighting, heating, or power supply mains, provided that they are connected to the secondary side
of double-wound transformers, having a secondary voltage twelve volts, and further provided
that-
        (i) Each transformer is mounted on the main switch-board,
        (ii) Each transformer is protected on the primary side by a single-pole switch and fuse,
              and one side of the secondary winding is earthed,
        (iii) The conductors when un-enclosed are secured individually by means of insulated
              stapes, and where subject to mechanical injury the conductors are adequately
              protected,
        (iv) Joints in the conductors are, as far as practicable, avoided, but where they are
              unavoidable they are staggered, soldered and efficiently insulated,
        (v) The conductors are insulated with vulcanized rubber/p.v.c. save that ordinary bell-
              wire may be used if the transformers are of a capacity not exceeding fifty watts and
              so designed that on sustained short circuit their impedance is such as to limit the
              current to such a value as will not burn out the transformer.
73. The control-circuit wiring and accessories in wiring systems having extra-low voltage
control shall comply with the following requirements–
                   (i) Remote controlled switches shall have their live parts enclosed in non-
                         combustible and non-absorbent cases. They shall be fixed in full view in
                         readily accessible positions. The insulation resistance between the supply
                         terminals and the control terminals of the switch shall be not less than 100
                         Mega ohms;
                   (ii) All control wiring shall be run entirely apart from the supply wiring;
                   (iii) The voltage of the control circuit shall not exceed twelve volts. Transformers
                         shall be double-wound with one side of the secondary earthed and shall be
                         mounted on the switch or distribution board, and be controlled by a switch
                         and fuse on the primary side;
                   (iv) where subject to mechanical injury conductors shall be protected. When un-
                         enclosed they shall be secured with clips having rounded edges or insulated
                         staples. But two or more conductors shall not be secured under the same
                         staple,
                   (v) Between roof and ceiling, conductors may be fastened to the sides of joists
                         or battens-without further protection. Where buried in plaster or concrete
                         they shall be enclosed in an approved metallic sheathing. All joints shall be
                         accessible, and be efficiently soldered and insulated,
                                           Page 34 of 173
                  (vi) bushes shall be of substantial mechanical construction. The conductors shall
                       terminal in suitable terminals and be secured by a metal thread screw.
                       Heating circuits shall not be controlled by this system unless fitted with an
                       indicating device.
74. Hazardous locations
    (1) Electric wires, fittings, consuming devices and associated equipment installed in
hazardous locations in which explosive or highly inflammable substances are produced,
manufactured, refined, stored or packed shall be installed and maintained to comply with the
following additional requirement–
                 (i) All electrical conductors shall be enclosed in an efficiently earthed metallic
                       envelope so constructed that in the event of the ignition of an inflammable
                       or explosive material within the metallic envelope, there will be no
                       transmission of flame to the atmosphere surrounding it,
                 (ii) Each consuming device shall be provided with automatic protective
                       equipment to cut off the electricity in the event of overload or an electrical
                       fault developing, in addition to means for normally cutting off all power to,
                       or, in the immediate vicinity of the device in the event of danger: provided
                       that this paragraph shall not apply to single lights which form part of a group
                       of lights installed and maintained in conformity with this regulation.
                 (iii) All current consuming devices including lighting fixtures shall be housed in
                       metallic enclosures certified as flame-proof and the enclosures maintained
                       in such a condition that the validity of the flame- proof certificate is not
                       impaired,
                 (iv) The attachment of all metallic envelopes enclosing cables to consuming
                       devices shall be such as not to invalidate any flame-proof certificate.
                 (v) Before effecting maintenance or repairs involving the opening of a flame-
                       proof enclosure, all conductors within the flame-proof enclosure to be
                       worked on shall be made dead and earthed, and on completion of
                       maintenance or repair, the apparatus not made until all openings have been
                       closed restoring flame-proofness.
(2) The provision of this regulation shall not apply solely because of the presence of stationery
electrical storage batteries of the electro-chemical type or because of the recharging of portable
electric batteries.
75. In this regulation “certified as flame-proof” means so certified by the Director of Electrical
Inspectorate Services, and equipment shall be deemed to be so certified if it bears a label
consisting of the letters FLP enclosed in a crown in out-line together with the relevant number of
the certificate. The Director of Electrical Inspectorate Services may be notice in writing in any
particular case approve an alternative certification as being an adequate substitute for the
requirements of this paragraph.
76. (1) In rooms containing stationary electric storage batteries of the lead-acid or alkaline
types, or where corrosive gases or liquids which are not explosive or highly inflammable are
present–
                                           Page 35 of 173
          (i) The system of wiring employed shall be such that all electrical conductors including
                earthing connections are enveloped in a corrosion-proof non-metallic sheath;
          (ii) Where metallic enclosures are necessary used for motors, switch-gear or other
                accessories, including conductors which are liable to mechanical damage, all exposed
                metallic surfaces shall be effectively painted or otherwise coated to resisted
                corrosion;
          (iii) All cables entries to requirement or accessible or accessories shall be such that the
                non-corrosion sheath of conductors enters the terminal chamber of the equipment
                accessory and the entry hole or holes are fitted with an accessory to exclude the
                corrosive liquid or gas present,
          (iv) All unused entry holes shall be effectively sealed.
      (2) (i) Distribution boards shall not be fixed in freezing or cooling chambers–
           (ii) Switches shall not be fixed in freezing or cooling chambers,
           (iii) No conductors other than those required for the supply and use of current therein
shall be installed in freezing chambers and cool stores.
      (3) (i) Cable insulated with rubber shall not be used in situations where the temperature of
the conductor would exceed 600C for short periods, or 500C for long periods
           (ii) Cable insulated with paper or fibre shall not be used in situations where the
temperature of the conductor would exceed 800C;
          (iii) Where higher temperatures are liable to be experienced, the wiring shall be in
accordance with the requirements of the             authorized inspector.
77. All cables shall be installed in such a manner as will not damage or weaken the building
unnecessarily and with the least possible cutting-away of any structural work.
                                                  PART VIII
                                     Equipment fittings and accessories
78. Construction of fittings
    Fittings shall be so designed and constructed that the passages for the insulated conductors
are of ample size, and are from rough projections and sharp angle, or bends. All outlets shall
have-rounded edges or be bushed.
79. Fittings shall be so designed, and the insulated conductors so installed that no stress can
be applied by the conductors to any terminal to which they may be connected.
80. Fittings shall be so designed and fixed that neither dust not moisture can readily
accumulate on live parts.
81. Where a hanging fitting exceeds 5kg in weight it shall be supported by a metal chain, tube,
or rod, or by several flexible cords in such a manner that the maximum weight to which any cord
is subjected shall not be greater than that specified in regulation 67(2).
82. Open-type fittings shall be furnished with inflammable shades unless such shades are kept
free from contact with the lamps by suitable guards or supports.
83. Enclosed type fittings shall be provided with a removable glass receptacle arranged to
enclose the lamp completely, and of such size or construction as to prevent undue heating of the
lamp; and if the position of the fitting be such that the glass receptacle is liable to mechanical
damage, the glass shall be protected by a suitable wire guard.
                                           Page 36 of 173
84. Fittings whether fixed or portable, shall, whenever exposed to rain, drip or externally
condensed moisture, be of the weather-proof type.
85. Fittings for lamp shall be so designed as to provide for adequate dissipation of heat from
such lamps.
86. Enclosed fittings shall be used–
         i.   In places where inflammable or explosive dust or gas is liable to be present or where
              inflammable goods are stored, and they shall be of strong construction, having air-
              tight external globes of thick glass provided with substantial guards.
        ii.   In positions in which the lamp is either near to or can swing in contact with readily
              combustible materials.
87. The handle of every hand-lamp (not being a hand-lamp made entirely of metal specified in
the last preceding regulation) shall be made treated hard-wood, or of some suitable non-
ignitable composite insulating material capable of withstanding round usage in service.
88. Where portable fittings, appliance, or accessories are likely to be used, the voltage
between any two points in one room or compartment shall not exceed 250 volts, unless the
fittings, appliances or accessories between which there may be a higher voltage are so situated
that they cannot be brought with 2 meters of each other, or, alternatively, unless the metal
frames and sheathing of all such portable appliances and accessories are earthed.
89. Flexible conductors of portable fittings or apparatus shall be connected through wall plugs.
90. Fittings shall be mounted on a base-block.
91. Accessories other than fuses shall be mounted a base-block unless they are completely
enclosed in metallic casing, and where the surface of which it is mounted is liable to become
damp the base-block shall be rendered impervious to moisture.
92. Ceiling roses
    (1) A ceiling rose shall not be installed in any circuit operating a voltage normally exceeding
250 volts.
    (2) A ceiling rose shall be connected to the fixed wiring in such a manner that one of its
terminal remains alive when the associated switch is off unless that terminal cannot be touched
when the ceiling rose is dismantled to the extent necessary for the replacement of the
associated flexible cord.
    (3) A ceiling rose shall not be used for the attachment of more than one outgoing flexible
cord, unless it is specially designed for multiple pendants.
    (4) The earthing terminal of every ceiling rose shall be connected to the earth-continuity
conductor of the final sub-circuit.
93. Lamp-holders
    Lamp-holders for filament lamps shall normally be used only in circuits operating at a voltage
not exceeding 250 volts.
94. Every lamp-holder for a bayonet-cap lamp in any damp situation or in any situation in
which it can readily be touched by a person in contact with or standing on earthed metal shall
be–
         i. Earthed, or
                                          Page 37 of 173
       ii. Constructed of, or shrouded in, insulating material and for moulded insulated bayonet,
            fitted with a protective shield.
95. Where centre-contact bayonet or Edison-type screw lam-holders are connected to a
source of supply having an earthed neutral conductor, the outer or screwed contact shall be
connected to that conductor. Where such lamp-holders are used in circuits having neither pole
connected with earth, or in any damp situation in which they can readily be touched by a person
in contact with or standing on earthed metal, they shall be provided with a protective shield of
insulating material or shall be place or safe guarded, so that neither the lamp cap nor the outer
or screwed contact of the lamp-holder can be inadvertently touched when the lamp cap is
engaged with that contact.
96. Where arc lamps are used in positions where danger might otherwise arise, they shall be
protected either by a metal reflector rigidly fixed beneath the arch or by a globe or lantern.
Wherever noxious fumes are likely to be emitted from such a lamp, suitable ventilation shall be
provided.
97. Application of transformers
     Where a step-up transformer forms part of a consumer’s insulation, a linked switch shall be
provided for isolating the transformer from all circuit conductors of the supply.
98. An auto-transformer having an output in the extra-low-voltage range shall not be used to
supply–
             i.    any socket-outer, or
            ii.    any portable appliance, unless the auto-transformer is contained therein, or
           iii.    earthed concentric wiring, or
           iv.     any extra-low-voltage circuit which is outside scope of these Regulations, e.g. an
                   electric bell circuit operating at a voltage not exceeding 15 volts.
99. A step-up auto-transformer shall not be connected to an installation obtaining its supply
from a system in which none of the poles of the supply is connected to earth.
100. The common terminal of every auto-transformer winding shall be connected to the neutral
conductor.
101. Capacitor
     Every capacitor, unless incorporated for the sole purpose of radio interference suppression
or directly connected across a motor winding, shall be provided with a means, such as a high-
resistance leak, for its prompt automatic discharge immediately the supply is disconnected. This
requirement shall not apply to small capacitors where no risk of shock can arise.
102. Plugs, socket-outlets and adaptors
     Every plug and socket-outlet shall as a minimum comply with requirements set out in items
(i) and (ii) below, and in addition comply with the appropriate requirements of Regulations 103
to 106 and Table 9–
             i.    It shall not be possible for any pin of the plug to be engaged with any live contact
                   of its associated socket-outlet while any other pin of the plug is completely
                   exposed; provided that this requirement shall not apply to socket-out-lets and
                   plugs for extra-low voltage circuits, and
                                           Page 38 of 173
          ii.     It shall not be possible for any pin of the plug to be engaged with any live contact
                  of any socket-outlet within the same installation other than the type of socket-
                  outlet for which it is designed.
103. In circuits in which one pole is earthed at the source of supply, every socket-outlet and
plug shall be of the non-reversible type, with provisions for earthing.
104. Plug and socket-outlets may be used in two-wire circuits operating at a voltage not
exceeding 250 volts for the connection of electric clocks, provided that the plug and socket-
outlets are designed specifically for that purpose and that each plug incorporates a fuse of rating
not exceeding 3 amperes.
105. Every plug containing a fuse shall be non-reversible and so designed and arranged that no
fuse can be connected in an earthed conductor.
106. For two-pole-and-earth circuits, the connection of plugs, socket-outlets and connectors
shall be in accordance with Table 10 Schedule 1.
107. Where outlets from a socket adaptor have a lower current rating than that of the input,
appropriate fusing shall be provided for each outlet of lower rating. Every socket-outlet adaptor
used at a voltage exceeding extra-low voltage shall be non-reversible and shall be so designed
that the output contacts are arranged in the same phase or polarity as those of the
corresponding socket-outlet adaptors intended for use with electric shaves shall incorporate a
fuse of rating not exceeding 3 amperes and shall be marked “FOR SHAVES ONLY”
108. Weather-proof plugs and sockets shall be used whenever exposed to rain drip, or
externally condensed moisture.
109. Such accessories shall be of specially robust construction, and be provided with efficient
means to keep the sockets weatherproof when the plug is removed therefrom. When a loose
cover is employed for this purpose it shall be anchored to the socket by means of a chain.
110. When the plug is inserted in its sockets, the combine fitting and its interlocking switch (if
any), shall also be weatherproof.
111. In places where petrol-diver conveyances are stored or repaired, plugs and sockets shall be
placed not less than 2 meters above the floor level unless an interlocked plug and gas-tight
switch is used.
112. (1) Adaptors for use in lampholders shall be constructed of tough, non-ignitable, non-
conducting, non-hygroscopic material other than hardwood.
   (2) Adaptors for use in screw holders shall be of one of the following types–
                i. Combine adaptor with pull-out plug,
               ii. Adaptor with a loose screw to prevent twisting of the flexible conductor.
113A. Cable couplers and connectors
     Cable couplers and conductors shall be mechanically and electrically sound and grounded
either in metal which can be earthed or in non combustible insulating material. Where the
apparatus to be connected requires earthing, every cable coupler and connector shall have
adequate provision for maintaining earth continuity.
114A. Electric signs
    Every electric sign shall comply with the following requirements–
      (a) It shall be readily accessible for inspection and attention;
                                           Page 39 of 173
        (b) It shall be fire-proof, or alternatively the wiring shall be independent, and shall be
            controlled by a fuse and switch on each live conductor. When more than switch is
            required the switched shall be linked;
        (c) Where elaborate switching and flashing apparatus is installed, a special non-ignitable
            enclosure shall be provided;
        (d) If fixed in the open air.
                   i. It shall be weather-proof and lamp-holders shall be weather proof;
                  ii. Only non-ignitable material shall be used in its construction, except for letters
                      and designs, for which hardwood is permissible.
                                                  PART IX
                                                Appliances
113B. heating and cooking appliances
      (a) All heating and cooking appliances shall be so constructed and mounted that their
supports and those parts which have necessarily to be handle in their operation cannot become
heated to a temperature exceeding 55 degrees centigrade. The heating elements shall be of
materials durable at the highest temperature to which they attain during use, and be so
arranged that they can be readily replaced.
     (b) The support and frame of every fixed appliance shall be provided with a suitable terminal
to which the earthing lead in this case.
114B. (i) The connection between heating elements shall be effected either by parts of the
elements themselves or by material having heat-resisting properties similar to those of the
elements;
    (ii) the junction between elements and switches or external connecting leads shall be
effected without solder by connectors which shall be so placed that the temperature of no part
of the switch or terminal connections can rise above 800C.
115. All connection between elements or between elements and main terminal shall, unless
self-supporting or rigidly fixed in posited, be continuously insulated with suitable non-ignitable
material.
116. The hot-plates of all electric cookers shall be iron-clad, and the oven elements shall be so
guarded that the cooking utensils cannot be made into contact with them, and so that accidental
personal contact cannot be made.
117. (1) Each element shall be protected and controlled by a switch and fuse on the live side.
       (2) When a plug-socket is fitted to the appliance it shall have a switch and fuse on the live
side, and be so mounted as to secure freedom from electrical hazard. This plug shall have a
separate contact connected to earth and any portable apparatus used from this plug shall be
earthed in accordance with the requirement of these Regulations.
118. Control
     (1) Appliances shall be protected by a fuse on each live conductor
     (2) Appliance shall be controlled as a whole by a switch on each live conductor and such
switch shall be mounted on the wall adjacent to and within easy reach of such appliance. If more
than one switch is so used for any one appliance, all such switches shall be linked.
                                           Page 40 of 173
    (3) The wiring to fixed appliances shall be in screwed conduit connected mechanically and
electrically to the metal frame of the appliance provided than flexible metallic conduit may be
used between the wall and the appliance is connected mechanically to the screwed conduit and
the metal frame of the appliance.
    (4) For the purpose of this regulation a fixed appliance is one which is obviously intended by
size, weight, and construction to be secured in a fixed position.
     (5) Heating and cooking appliances shall not be fixed near combustible materials unless the
latter are suitably protected.
119. Portable appliances
    Portable appliances shall be of such shape or be so weighted that they cannot be easily
overturned.
120. Heating points
   (1) Heat-points shall each be rated at not less than 1,000 watts, and shall be controlled by a
switch of not less than eight amperes capacity. For appliances over 1,800 watts, the heating
points shall, except in the case of a multi-earthed neutral system, be controlled by a double-pole
switch.
   (2) The minimum size of conductor for any heating point shall be 2.5mm2
   (3) Switches for heating points shall be at a distance not less than 300mm from any switch
controlling lighting.
121. Boilers and water heaters-general
     Electrode boilers and electrode water-heaters shall be connected to a.c. systems only, and
shall be installed in accordance with the general requirements of Regulations 122 to 125 and,
according to the type of equipment connected, with the particular requirements of Regulations
127 and 128.
122. The supply to the heater or boiler shall be controlled by a circuit-maker which shall be–
             i. Of the multiple linked type arranged to disconnected the supply from all electrode
                simultaneously, and
            ii. So placed with excess-current protective devices in each conductor feeding an
                electrode, and
           iii. so placed that it may easily be operated by the person in charge, and where it is
                not adjacent to he electrode boiler there shall be a means at hand at the boiler to
                open the circuit-breaker instantaneously.
 123. Adequate means, such as an isolator adjacent to the heater or boiler, or a locking device
      on the circuit-breaker, shall be provided to prevent the apparatus being made while
      persons are working thereon.
124. Where the circuit-breaker is remote from the heater or boiler, indicating lamps shall be
provided adjacent to or mounted on the boiler, to indicate whether the circuit-breaker is in the
“on” or “off” position.
125. The earthing of the heater or boiler shall comply with the requirements for earthing, in
addition, the shell of the heater or boiler shall be bonded to the metallic sheath and armour, if
any, of the incoming supply cable. The rating of the earthing lead, which shall be connected to
the shell of the heater or boiler, shall be not less than that of the largest phase conductor
                                          Page 41 of 173
connected to the apparatus, or, where an earth-leakage protective device is provided, not less
than the operating current of than device, subject to a minimum conductor size 2.5mm2
126. Where an electrode water-heater or electrode boiler is directly connected to a supply at a
voltage exceeding low voltage, the installation shall, in addition to complying with the general
requirements of Regulations 121-125 include a differential earth-leakage protective device
arranged to disconnect the supply from the electrodes on the occurrence of a sustained earth-
leakage current in excess of 10% of rated current of the heater or boiler under normal conditions
of operation, except that if in any instance a higher value is essential to ensure stability of
operation of the heater or boiler, the value may be increased to a maximum of 15%. A time
delay may be incorporated in the device to prevent unnecessary operation in the event of
unbalance of short duration.
127. Three-phase boilers and water heaters
Where an electrode water-heater or electrode boiler is connected to a three-phase supply, in
addition to complying with the general requirements of Regulations 123 to 125, the shell of the
heater or boiler shall be connected to the neutral of the supply as well as to the earthing lead.
The current rating of the neutral conductor shall be not less than of the largest phase conductor
connected to the apparatus.
128. Single-phase boilers and water heaters
Where the supply to an electrode water-heater or electrode boiler is single-phase supply and
one electrode is connected to a neutral conductor earthed by the supply authority, in addition to
compliance with the general requirements of Regulations 121 to 125, the shell of the water-
heater or boiler shall be connected to the neutral of the supply as well as to the earthed lead.
129. Every water heater or boiler having un-insulated heating element immersed in the water
shall comply with the requirements of Regulations 130 to 135.
130. The parts of the heater or boiler intended to be connected to the incoming water supply
and to the outlet pipe for the heated water, shall be of metal so as to afford the means of
earthling required by these Regulations.
131. The heater or boiler when in use shall have an insulation resistance between the element
and the metal parts referred to in Regulation 130 above of not less than 0.25 megaohm with
water flowing.
132. The heater or boiler shall incorporate an automatic device to prevent a dangerous rise in
temperature.
133. All metal parts of the heater or boiler which are in contact with the water (other than
current-carrying parts) shall be solidly and metallically connected to a metal water-pipe through
which the water supply to the heater or boiler is provided, and the said water-pipe shall be in
effective electrical connection with earth by a means independent of the earth-continuity
conductor.
134. The heater or boiler shall be provided with an earthling terminal which is in effective
electrical connection with all exposed metal parts of the heater or boiler, and this terminal via
the earth-continuity conductor of the final sub circuit supplying the heater or boiler.
135. The heater or boiler shall be permanently connected to the electricity supply through a
double-pole linked switch which is separate from and within easy reach of the heater or boiler,
                                         Page 42 of 173
and the wiring from the heater or boiler shall be directly connected to that switch without the
use of a plug and socket-outlet; and, where the heater or boiler is installed in a room containing
a fixed bath, the switch shall in addition be placed outside the room.
                                                PART X
                                     Motors, control gears and lifts
 136. Motors shall conform in all respect with Nigerian Standards Specifications
 137. Terminals of motors shall be so guarded that they cannot be accidentally touched or short-
      circuited.
 138. Position and safety precautions
     Motors shall, whenever possible, be placed in a well ventilated space in which inflammable
gases cannot accumulate. Where that is not practicable, the motors shall be of the flame-proof
or pipe ventilated type, with inlet and outlet connected to the outside air.
139. Motors shall, wherever possible, be placed in positions in which they are not exposed to
risk of mechanical injury or damage from water, steam, oil. Motors necessarily exposed to such
conditions shall have suitable types of enclosing frames selected from the standard “specified in
Nigerian Standard Specifications”.
140. Pipe-ventilated forced-drought, and induced-draught motors shall be supplied with air as
cool as possible, and the air-intakes shall be guarded against the admission of dirt or moisture.
141. No unprotected woodwork or other combustible material shall be within a distance of
300mm (measured horizontally) from or within one (1) meter (measured vertically) above any
motor, unless such motor be of the totally enclosed, flame-proof, or pipe-ventilated type with
inlet and outlet connected to the outer air. A metal plate or tray extending 300mm beyond the
base of the machine shall be placed under every open-type machine which is mounted on or
over a floor consisting of wood or other combustible materials.
142. Where conductors are run in conduit, or where metal-sheathed cables are used, the
conduit or metal sheath, as the case may be, shall terminate in and be properly secured to the
motor terminal box; provided that flexible metallic may be used between screwed conduit and
the motor terminal box.
143. Trailing cables used in connection with portable motors shall have their protective
sheathing terminating in and properly secured to the motor terminal box.
144. Resistances and machine-control gears
       (1) The general construction of all resistances and machine-control gear shall be
accordance with the appropriate Nigerian Standards Specifications.
       (2) All these parts shall be so guarded as to prevent accidental contact therewith.
145. The frame of every resistance and control gear shall be provided with a suitable terminal to
which the earthing lead can be connected.
146. Resistances shall be so proportioned and placed that they do not rise to such a
temperature as to impair their durability, and they shall be so disposed within their cases that no
accessible part of such cases shall rise to a temperature higher than 800C.
147. Internal connections, the temperature rise of which may exceed 300C shall not be
soldered, and all such connections, unless self-supporting or rigidly fixed in position, shall be
continuously insulated with non-ignitable material or beads.
                                          Page 43 of 173
148. Suitable terminals with cable sockets shall be provided for the attachment of external
leads, and shall be so situated that such leads enter the case below the resistance, and are not
exposed at any point to a high temperature.
149. Location of control gears.
    (1) All resistance control gear shall, as far as possible, be placed–
    (a) In positions in which they will not be exposed to risk of mechanical injury or to damage
         from water, steam, or oil;
    (b) In well-ventilated spaces in which inflammable or explosive gases or dust cannot
         accumulate.
    (2) Where necessarily exposed to such conditions as aforesaid, resistance and control gear
shall be completely enclosed; and if liable to be exposed to inflammable or explosive gases or
duct, control gear shall be flame-proof.
150. All woodwork or other combustible material which is within distance of 600mm (measured
vertically below), or 150mm (measured in any other direction) from the frames or cases
containing resistance shall be protected with non-ignitable material.
151. Electric lifts
Every electrically-operated lift shall be operated from a circuit which is independent of the
lighting installation.
152. The trailing-cable shall be multi-core, and shall comprise the requisite number of
conductors to keep the wiring of the control and each set of safety-devices entirely separate.
153. All cables in the lift or hoist shaft, except trailing-cables, shall be enclosed in screwed metal
conduits, the control and motor leads being in separate conduits.
                                                PART XI
                                                Earthing
154. Prevention of danger from earth leakage current
    Every item of apparatus and every live conductor shall be effectively prevented, by one of the
methods described in items (i) to (iv) below, from giving rise to danger from earth-leakage
currents–
         (i) enclosure in insulation which is durable and substantially continues, i.e., “all-
         insulated” construction;
         (ii) double insulation;
         (iii) earthing of exposed metal parts in accordance with the requirements of this section;
         (iv) isolation of metal in such a way that is not liable to come into contact with live parts
         or with earthed-metal.
155. General provisions
    In every installation operating at any voltage, a consumer’s earthing terminal shall be
provided adjacent to the consumer’s terminals. Shall be provided and connected to the
consumer’s earthing terminal.
156. All metal work of wiring system (other than current-carrying parts), including cable
sheathes and armour, conduit, ducts, trunking, boxes, and catenary wires, shall be connected to
the appropriate earth-continuity conductors.
                                           Page 44 of 173
157. Exposed metalwork of all apparatus shall be connected to the appropriate earth-continuity
conductors.
158. The earthing terminal of every socket-outlet shall be connected to the earth-continuity
conductor of the final sub-circuit. Where the earth-continuity conductor is formed by conduit,
trunking, duct, or the metal sheath and/or armour of cables, the earthing terminal of each
socket-outlet shall be connected by an appropriate conductor to an earthing terminal
incorporated in the associated box or other enclosure. For the purpose of this regulation,
physical connection of adjacent sections of ducts or trunking is necessary to ensure earth-
continuity.
159. At every lighting point with metal fitting, an earthing terminal shall be provided and
connected to the earth=continuity conductor of the final sub-circuit.
160. An earthing terminal connected to the earth-continuity conductor of the final sub-circuit
shall be provided at every metal lighting switch position unless this takes the form of an earthed
metal box having a means of fitting the switch-plane in reliable electrical contact with the box.
161. Metalwork (other than current-carrying parts) and one point of the secondary winding
shall be connected to the appropriate earth-continuity conductor, provided that this regulation
shall not apply to–
    (i) a transformer in which the windings are mounted on separate limbs of an earthed core
          or are separated by an earthed metallic screen; or
    (ii) a double-insulated transformer; or
    (iii) the secondary winding of a “high-reactance’ transformer serving solely to energise a
          tesla coil or the heating element of an electric discharge lamp;
    (iv) the secondary winding of a transformer in a shaver supply unit; or
    (v) a transformer which is an integral part of an item of apparatus, where the apparatus as a
          whole is the subject of and complies with Nigerian Standards Specification; or
    (vi) a transformer used in are welding installations designed in accordance with Nigerian
          Standards Specification.
162. Isolated metal
   (1) Where isolation of metal is adopted for the prevention of dangerous earth-leakage
currents, it shall be confined to the following items-
          (i) short isolated lengths of metal used for the mechanical protection of cables having a
                non-metallic sheath, other than over-head spans of conduit between buildings or
                conduit used for protection of cables in circuits operating at voltages exceeding low
                voltage in discharge-lighting installations.
          (ii) Metal clips used for fixing cables,
          (iii) Metal lamp caps,
          (iv) small metal parts such as screws or name-plates isolated by insulating material,
          (v) metal chains for the suspension of lighting fittings,
          (vi) metal lighting fitting using filament lamps installed above a non-conducting floor and
                so mounted, or so screened in non-conducting material, that they cannot readily be
                touch by a person standing on or within reach of earthed metal.
          (vii) catenary wires where insulated hangers are used
                                           Page 45 of 173
163. Bonding
     (1) The consumer’s earthing terminal shall be bonded to the metalwork of any public gas
services and any water services on the consumer’s premises in addition to the connection to the
general mass of the earth.
     (2) It shall be noted that before the consumer’s earthing terminal is bounded to the
metalwork of any gas or water service, connection of the earthing terminal to an effective means
of earthing should be completed.
164. The bonding connections to any gas or water service shall be made as near as practicable
to the point of those services into the premises; provided that where there is an insulating
section or insert at that point, the connection shall be made to the metalwork on the consumer’s
side of that section or insert and, in the case of a gas service on the consumer’s side of the gas
meter.
165. Copper bonding leads used for compliance with Regulation 163 shall be of cross-sectional
area not less than the appropriate value shown in Table 12 subject to a minimum size of 6mm 2.
For the purposes of this regulation, the associated circuit conductor shall be the largest
conductor connected into the input side of the consumer’s switch-gear. Conductors of material
other than copper shall have a resistance not exceeding that of the prescribed copper conductor.
Connections to the pipes of other services shall be made by means of clamps.
166. The exposed metalwork of all apparatus which is required by these Regulations to be
earthed, which might otherwise come into fortuitous contact with extraneous fixed metalwork
shall be either effectually segregated therefrom, or effectually bonded thereto so as to prevent
appreciable voltage differences at such possible points of contact. Copper bonding leads shall be
of cross sectional area not less than the appropriate value shown in Table 1.2, subject to a
minimum of 1.5mm2 where the bonding lead is un-enclosed. Conductors of material, other than
copper shall have resistance not exceeding that of the prescribed copper conductor.
167. Bathrooms
    In a room containing a fixed bath or shower cubicle, parts of a lamp-holder within a distance
of 2.5m from the bath or shower cubicle shall be constructed of, or shrouded in, insulating
material. Bayonet-type lamp-holders shall be fitted with a protective shield. As an alternative,
totally enclosed light fittings may be used.
168. Every switch or other means of electrical control or adjustment shall be located outside the
inner walls of a fixed bathroom normally inaccessible to a person using a fixed bath or shower.
This requirement does not apply to insulating cords or cord-operated switches. No stationary
appliance having elements which can be touched shall be installed within reach of a person using
the bath or shower.
169. In a room containing a fixed bath or shower, there shall be no sock-outlets and there shall
be no provision for connecting a portable appliance except for shavers supply unit.
170. In a room containing a fixed bath or shower, electric shavers shall be connected only by
means of shaver supply unit where the secondary circuit supplying the output sockets shall be
isolated both from the supply mains and from earths.
171. Protection against earth leakage
                                         Page 46 of 173
The earthing of the consumer’s installation shall be effected in such a manner that no fault of
negligible impedance to earthed metal shall be so sustained as to cause danger and shall be in
accordance with the appropriate requirements of these Regulations
172. Protection by fuse or circuit breakers
    Earth-leakage protection may be afforded by means of fuses or, excess-current available to
operate that the earth fault current available to operate the protective devise and so make the
family circuit dead exceeds–
     (i) 3 times the current rating of any semi-enclosed fuse having a fusing factor exceeding 1.5,
           used to protect the circuit (see Table 11). or
     (ii) 2.4 times the rating of any cartridge fuse having a fusing factor not exceeding 1.5, used
           to protect the circuit, or.
     (iii) 1.5 times the tripping current of any excess-current circuit-breaker used to protect the
           circuit.
173. Where the requirement of Regulation 172 cannot be satisfied, earth-leakage protection
shall be provided by one or more earth-leakage circuit-breaker for all parts of an installation to
which the requirement of earthing applies, installation of the earth-leakage circuit-breakers shall
satisfy the test requirements of these Regulations.
174. A current-operated earth-leakage circuit-breaker shall be used only where the product of
its operating current in amperes and the earth-loop impedance in ohms does not exceed 40.
Where such a circuit-breaker is used the consumer’s earthing terminal shall be connected to a
suitable electrode.
175. Every voltage-operated earth-leakage circuit-breaker shall be arranged to have its
operating coil connected between the consumer’s earthing terminal (which may serve the whole
or part of an installation) and an earth electrode, the connecting lead shall be insulated.
176. The earth electrode used with any voltage-operated earth-leakage circuit-breaker shall be
placed outside the resistance area of any parallel earth which may exist, for example where a
water heater is installed. If by subdivision of the earthing system, discrimination in operation
between a number of voltage-operated earth-leakage circuit-breakers is to be afforded, the
resistance areas of the associated earth electrodes shall not overlap.
 177. Every conductor used as an earth-continuity conductor shall satisfied the appropriate
      requirements stated below–
               (i) Where the conductor forms part of the same cable as the associated circuit
                     conductors, other than a flexible cable or flexible cord, conductor shall comply
                     with the relevant requirements for the cable.
               (ii) Where the conductor is contained in a flexible cord, it shall have a cross-sectional
                     area not less than that of the largest associated current-carrying conductor,
               (iii) Every cable sheath and/or armouring used as an earth-continuity conductor shall
                     satisfy the relevant requirements of standards mentioned in these Regulations;
               (iv) Conductors of copper other than those mentioned in item (i) to (iii) above, shall
                     have a cross-sectional area not less than the appropriate value shown in Table
                     12, subject to a minimum of 1.5mm2 where the conductor is unenclosed.
                                            Page 47 of 173
                 Conductor of material other than copper shall have a resistance not exceeding
                 that of the prescribed copper conductor.
178. Installation
    The installation of every earth-continuity conductor and earthing lead shall satisfy the
appropriate requirement stated below–
        i.  Every earth –continuity of cross-sectional area 1.5mm2 up to and including 6mm2,
            other than copper strip , shall be protected throughout by installing at least
            equivalent to that provided for a single-core, non-sheathed cable of appropriate size.
       ii.  Where the sheet of hearth-continuity conductors is removed adjacent to joints and
            terminations, earth-continuity conductors of cross-sectional area up to and including
            6mm shall be protected by installing slaving.
      iii.  Bare earth-continuity shall be protected, where necessary, against mechanical
            damage and corrosion, particularly at terminations.
      iv.   Every bare earth-continuity of the types other than copper strip shall be identified at
            terminations as appropriate.
       v.   All joints in earth-continuity conductors shall be mechanically sound, electrically
            continuous and protected, where necessary, against corrosion,
      vi.   Connections to cable sheaths and/or armoring, and to pipes, shall be soundly made
            by soldered joints or by clamps. Every clamp shall be so installed as to provide
            reliable connection without damage to the associated cable or pipe.
     vii.   Copper clad aluminum conductors shall not be used for bonding connections to
            water pipes likely to be frequently subjected to condensations in normal use, or in
            other situations where the terminations of the conductors are likely to be exposed to
            sustained wet conditions. This requirement does not apply to terminations which
            may be only initially damp during building construction.
179. Earthing leads
    Pipe such as gas or water, or members of structural metalwork, shall not by themselves
constitute an earth-continuity conductor where this is necessary.
180. The cross-sectional area of every copper conductor used as an earthing lead shall be not
less than that shown in Table 12 except that for connection of an earth-leakage circuit-breaker
to an earth electrode a cross-sectional area of 2.5mm need not be exceeded. A maximum size of
copper conductor of 70mm2 cross-sectional area need not normally be exceeded except for the
earthing of a transformer neutral or electrode boiler. For the purpose of this regulation, the
associated circuit conductor shall be the largest conductor connected into the input side of the
consumer’s switch-gear. Every conductor of material other than copper shall have a resistance
not exceeding that of the prescribed copper conductor. Copper-clad aluminum conductors shall
not be used for final connections to earth electrodes.
181. Every connection of an earthing lead to an earth electrode or other means of earthing shall
be readily accessible and soundly made by use of soldered joints or clamps: a permanent label
indelibly marked with the words “Safety Electrical Earth – DO NOT REMOVE”, in a legible type
not less than 4.75mm high, shall be permanently fixed at the point of this connection.
                                          Page 48 of 173
182. Where protection against dangerous earth-leakage currents by fuses or excess –current
circuit breakers is admissible, one of the following methods of earthing shall be employed–
            i.   where the supply undertaking provides an earthing point which affords a metallic
                 return path to the means of earthing of the supply system, the earthing lead shall
                 connect the consumer’s earthing terminal to this point;
           ii.   where a means of earthing has not been provided by the supply undertaking, the
                 consumer’s earthing terminal shall be connected by the earthing lead to an
                 effective earth electrode or electrodes, such as copper strip or rod, which shall be
                 buried in the ground at a position as near as practicable to the consumers
                 earthing terminal and shall satisfy the tests specified in Appendix 3.
          iii.   where Protective Multiple Earthing (P.M.E) is provide by the supply undertaking,
                 and with the concurrence of the Post Office, the earthing lead shall be connected
                 to the consumer’s earthing terminal and, together with the neutral conduction of
                 consumers installation, shall be so arranged that connection to the neutral
                 Conductor of the incoming supply can be carried out by the supply undertaking.
183. The metalwork of public gas services and water services shall not be used as the sole earth
electrode of the installation.
184. If more than one plate or tubular earth electrode is employed for one earthing system they
shall be efficiently connected together.
185. Every fixed heating and cooking appliance shall for the purpose of earthing. Be provided
with a suitable terminal to which the earthing lead shall be connected.
186. In the case of fixed heating and cooking appliances and of motors of over 3.75kW an
earthing lead other than the conduit shall be taken direct from the appliance or motor to the
nearest earth.
187. (1) Where the multiple-earthed neutral system is used, the earthing lead shall be taken
from the neutral bar or stud, and the conduit shall (in addition to being itself earthed) be
connected to this earthing lead.
   (2) Save as provided in the last preceding paragraph the neutral wire of any system shall not
be used as an earthing lead.
188. Precautions in earthing
   Pipes conveying gas, hot water, or an inflammable liquid shall not be used as an earthing
system.
                                           Page 49 of 173
                                             Division Three – Testing
                                                     PART XII
                                         Tests, inspections and certificate
189. General
     The contractor carrying out any installation shall notify the electricity supply authority or a licensee in
writing of the competition thereof, and except as provided in Regulation 206 hereof, shall not allow the
current to be switched on from the source of supply until the installation has been duly inspected and he has
been notified that a certificate has been issued pursuant to regulation 201 hereof.
190. Supply authority as the contractor
     Where an Electricity supply authority itself contracts to carry out any installation for a consumer, the
following special provision shall apply
    i.   the notice required by Regulation 188 hereof need not be given,
   ii.   the certificate to be issued pursuant to regulation 211 hereof shall be a certificate by the supply
         authority to the Director of Electrical Inspectorate Services.
191. Inspection on behalf of the Director Inspectorate Services
    Any person authorized writing in that behalf by the Director of Electrical Inspectorate services may at any
time, between the hours of 9 a.m. and 6 p.m. on any day of the week other than Sunday, demand admission
to the premises of any consumer for the purpose of ascertaining whether the requirements of these
Regulations have been complied with.
192. If any consumer refuses to admit such person during such hours, the Electric Supply Authority shall on
demand in writing by the Direction Electrical Inspectorate Services disconnect the consumer’s installation
from source of supply.
193. Tests
    The testing and inspection are to be carried out in the sequence–
    i.   Verification of polarity.
   ii.   Test of effectiveness of earthing.
  iii.   Insulation resistance tests.
  iv.    Test of ring-circuit continuity.
194. Basic Requirement General
     Every installation and every major alteration to an existing installation shall, on completion, be inspected
and tested in accordance with requirements of this section to verify, as far as practicable that the
requirement of these Regulations have been met. In case of a major alteration, both new work and that part
of the existing installation related thereto shall be inspected and tested.
195. Polarity Test
     A verification of polarity shall be made and it shall be insured all fuses and single pole control devices, are
connected in the live conductor only, that centre contact bayonet and Edison-type screw lampholders in
circuits having an earthed neutral conductor have their author or screwed or connected to that conductor,
and that writing has been correctly connected plugs and socket-outlets.
196. Earth continuity test
A separate test of every earth-continuity conductor shall be made by the contractor and another person
responsible for the work, before an installation or major alteration to an installation is put into commission.
                                                  Page 50 of 173
Where earth-leakage protection relies on the operation of fuses or excess-current circuit-breakers, the
impedance or resistance between the consumer’s earthing terminal and remote end of every earth-
continuity conductor shall not exceed the appropriate value prescribed.
197. Earth effectiveness test
Where earth-leakage protection relies on the operation of excess-current circuit-breakers, the contractor and
other person responsibilities the work shall test the effectiveness of the earthing of each completed install or
major alteration by means an earth-loop-impedance test.
198. Where earth-leakage circuit-breaker, relies on the operation earth-leakage circuit breaker, its
effectiveness shall be tested as specified Appendix 3.
199. The insulation resistance tests shall be made before a common installation or major alteration is
permanent connected to the supply. For these tests large installations may be divided into groups of outlets,
each containing not less than 50 outlets. A d.c. voltage not less than twice the normal voltage of the supply
(r.m.s. value of a.c. supply) shall be applied for the measurement of insulation resistance, provided that for
tests on low-voltage circuits, the test voltage need not exceed 500V d.c.
200. When measured with all fuse links in place, all switches (including, if practicable, the main switch)
closed and, except where earthed concentric wiring is installed, all pole or phases of the wiring electrically
connected together, the insulation resistance to earth shall be not less than 1 mega ohm.
201. When measured between all the conductors connected to any one pole or phase of the supply and, in
turn, all conductors connected to each other pole or phase of the supply, the insulation resistance shall be
not less than 1 mega ohm. Wherever practicable, so that all parts of the wiring may be tested, all lamps shall
be removed and all current-using apparatus shall be disconnected and all local switches controlling lamps or
apparatus shall be closed; where the removal of lamps and/or the disconnection of current-using apparatus is
impracticable, the local switches controlling such lamps and/or apparatus shall be open. This test is not
applicable to earthed concentric wiring systems.
202. When apparatus is disconnected for the tests under Regulation 200 and 201, the insulation resistance
between the case or framework and all live parts of each item of fixed apparatus shall be not less than 1.0
mega ohm.
203. A test shall be made to verify the continuity of all conductors (including the earth-continuity
\conductor) of every ring circuit.
204. Certification
   Following the inspection and testing required by this section for a completed installation, or major
alteration to an existing installation, a completion certificate shall be given by the conductor or other person
responsible, or by an authorized person acting on his behalf, to the person ordering the work. The certificate
shall be signed by a registered electrical engineer and shall be in the form set out in these Regulations. Any
defects or omissions revealed by inspection or test shall be made good before a completion certificate is
issued.
205. For a major alteration to an existing installation the person ordering the work shall be notified of any
repairs required to that part of the existing installation which is required to be inspected and tested, but
completion certificate shall apply only to the new work.
206. Every re-inspection of an installation should be reported upon by means of an Inspection certificate
which should be submitted to the consumer and be signed by a competent person who should be a
registered electrical engineer.
                                                Page 51 of 173
207. Notwithstanding anything to the contrary in the foregoing provisions of this part of these Regulation,
the supply authority may, in case of urgency on the recommendation of the authorized inspector, permit an
installation to be temporarily connected with the source of supply notwithstanding that any one or more of
the hereinbefore prescribed insulator resistance tests have not been satisfied; provided that no such permit
shall be granted unless the installation otherwise generally complies with the requirements of these
Regulations, and is certified by the authorized inspector to be reasonably free from electrical hazard; or for a
longer period than one month; provided further than the Director of Electrical Inspectorate Services of the
recommendation of the supply authority, may extend such period beyond one month.
208. On the expiration of the period or extended period as aforesaid for which temporary connection has
been so permitted, the installation shall be disconnected from the source of supply unless before such
expiration the authorized inspector has issued his certificate pursuant to the last preceding regulation.
209. Periodic inspections and tests
    The results of a periodic inspection and test of an installation, or any part thereof, shall be recorded on an
inspection certificate and given by the contractor or by an authorized person acting on his behalf, to the
person ordering the inspection. The certificate shall be in the form set out in these Regulations.
210. A notice of such durable material as to be likely to remain easily legible throughout the life of the
installation shall be fixed in a prominent position at or near the main distribution board of every installation
upon completion of the work. The notice shall be inscribed in indelible characters no smaller than those here
illustrated and shall read as follows–
         “IMPORTANT” –This installation should be periodically inspected and tested and a report on its
         condition obtained, as prescribed in the Regulations for Electrical Installations.
211. Periodic inspection and tests of electrical installation shall be carried out and recorded on an
inspection certificate at intervals of not more than three years.
212. (1) After having inspected and tested an installation the authorized inspector, if satisfied that the
work has been done in a workmanlike manner in accordance with the requirements of these Regulations and
if the test made as required by the foregoing provisions of this Part of these Regulation have been satisfied,
shall certify in writng to the electricity supply authority that the installation has been duly inspected and
tested and may be safely connected with the source of supply.
     (2) Nothing in any such certificate shall relieve the owner or occupier of any premises from the obligation
to bring any installation into conformity with these Regulations if on any subsequent inspection any defects
are discovered which render such installation electrically hazardous.
                                                 Page 52 of 173
                                      Division four – Special application
                                                   PART XII
                                   Agricultural and horticultural installation
213. General
    All installation in agricultural and horticultural holdings, except dwellings, shall comply with the
requirements of this Part and generally with the Regulations for the Electrical Installations.
214. Switch-gear
Main switch-gear shall not be installed –
        i.   Within reach of livestock; or
       ii.   In any position where access to it may be impeded by livestock, account being taken of the
             conditions likely to arise in the event of panic by the livestock.
 215. Control of building
    Where an installation serves more than one building, a switch shall be installed in or adjacent to each
building for the control and isolation of all those parts of the installation contained in that building. For the
purposes of this regulation a glass-house is deemed to be a building and where glass-house are combined in a
block, separate means of control shall be provided for each house within the block.
216. For isolated items of apparatus, e.g. pumps, remote from the main installation, a separate means of
control adjacent to the apparatus and readily accessible to the person in charge of the apparatus, shall be
provided.
217. Presence of different voltage
    Means of access to all live parts of switch-gear and other fixed live parts where different nominal voltages
exist shall be marked to indicate the voltages present.
218. Control of points
    Every point, including every socket-outlet, shall be controlled by a switch or switches, which shall be
readily accessible at all times. For motors driving machinery, the switches shall be clearly marked to show the
on and off position.
219. Selection of types of cables
    Cables sheathed with general-purpose rubber shall be used only for dry, clean situations indoors and for
clean situations outdoors.
220. Non-served metal-sheathed paper-insulated cables shall be used only for dry, clean situations indoors
and for clean situations outdoors.
221. Bright-wire armoured cables shall not be used out of doors.
222. Non-sheathed twisted-twin flexible cords and non-sheathed parallel-twin flexible cords shall not be
used.
223. Cable installation
All cables shall be place out of reach of livestock and clear of all vehicles.
224. Cables having a sheath of p.v.c. or an oil-resisting and flame retardant or h.o.f.r. sheath shall not be
placed where they would be liable to contact with liquid creosole.
225. Where additional protection against mechanical damage to cable is required, it shall wherever possible
be provided by the use of non-metallic materials, e.g. non-metallic conduit or hardwood, and in any event
metal conduit shall not be used.
                                                 Page 53 of 173
226. Where long runs of cable must be placed along the sides of building, they shall wherever practicable be
placed on the outside of the building, and as high as practicable.
227. Wiring between buildings
    Cables buried underground shall be place at a sufficient depth to avoid any risk of damage by implements
used for purposes of cultivation of drainage. In any case not less than 600mm, and where considerations of
drainage arise a depth of I’m may be necessary.
228. Where conductors or cables are carried overhead, supported buildings or by pole, the minimum heights
above ground and maximum length of span specified in Regulation 70 are applicable, provided for this
purpose the any position on any horticultural or agricultural holding is deemed to be accessible to vehicular
traffic.
229. Steel conduit or pipe shall not be used for spanning gaps between buildings.
230. Exposure to flammable dust
   Where apparatus may be exposed to a concentration of flammable dust, such as in situations used for
grain milling and mixing, grain drying, some intensive rearing houses, and the like, the apparatus shall satisfy
the test requirements of Regulation 74.
231. Garages
    Where vehicles are housed, stored or repaired in buildings or other enclosed spaces, every fixed item of
apparatus shall be mounted at a sufficient height or in such a position as to be clear of all vehicles.
232. Lamp-holders
All Edison-type screw lamp-holders shall be of the drip-proof type and shall be provided with a protective
shield. The requirements of Regulation 93 and 94 for the use of such lamp-holders in damp situations shall
apply to all situations in agricultural or horticultural installations.
233. Couplers
   Cable couplers shall not be used.
234. Earth leakage
In situations accessible to livestock in and around agricultural buildings, the installation shall so far as is
practicable be of “all-insulated” construction.
235. An earthing terminal, connected to the earth-continuity conductor, shall be provided at every outlet
point the installation.
236. In situations accessible to livestock, a metal pipe or conduit shall not be used as a sole earth-continuity
conductor, though it may be used to supplement a separate earth-continuity conductor.
237. The earthing lead of an agricultural installation shall be adequately protected against disturbance or
damage by live stock or by passing mechanical implements. Where the earthing lead is not enclosed in
conduit or equivalent mechanical protection, it shall be of the armoured type.
238. Protection against earth-leakage currents by isolation of metal-work, as provided for in items (i), (v) and
(vi) of Regulation 162, is not recognized for agricultural and horticultural installations, unless the metalwork is
out of reach of livestock and is not liable to accidental contact with passing machinery, implements or
vehicles.
239. Wash troughs
    Every switch or other means of control or adjustment not forming an integral part of other apparatus shall
be so situated as to be out of reach of a person in contact with wash troughs, sterilizing equipment and the
                                                  Page 54 of 173
like. Where apparatus having exposed metalwork and incorporating a switch or other means of control of
adjustment is adjacent to extraneous fixed metalwork, effectual bonding shall be carried out as that
regulation requires; the alternative of effectual segregation is not recognized for agricultural and horticultural
installations.
240. Electric fence controllers
     Every mains-operated electric fence controller shall be so installed that, so far as is reasonably practicable,
it is free from risk of mechanical damage or unauthorized interference.
241. A mains-operated electric fence controller shall not be fixed to any pole of an overhead power or
telecommunication line; provided that, where a low voltage supply to an electric fence controller is carried by
insulated overhead line from a distribution board, the controller may be fixed to the pole carrying the supply.
242. Any earth electrode connected to the earth terminal of an electric fence controller shall be separate
from the earthing system of any other circuit and shall be situated outside the resistance area of any
electrode used for protective earthing.
243. Not more than one controller shall be connected to any electric fence or similar system of conductors.
244. Every electric fence or similar system of conductors and the associated controller shall be so installed
that it is not liable to come into contact with any power or telecommunication apparatus or wiring, including
an overhead power line, telephone or telegraph wires or an aerial, or with all earth-continuity conductor.
                                                  Page 55 of 173
                                                    PART XIV
                                          Places of public amusement
245. General
     (1) The regulations in this part shall apply to theatres, music-halls, motion-picture theatres, and public
halls, and embody special requirements in addition to any other requirements of these Regulations.
     (2) In case of any dispute as to whether a place is a public hall, the matter shall be submitted to the
Director of Electrical Inspectorate Services whose decision shall be final.
246. All fixed wiring shall be enclosed in screwed galvanized conduits.
247. (1) The state-switchboard shall be either of the dead-front type or the accessories shall be of totally
enclosed type.
    (2) The switch-board shall be fixed in a convenient position preferably overlooking the stage, and
inaccessible to all but the switchboard operator.
     (3) A platform with proper means of access shall be provided for the switchboard operator. The platform
shall be of fire-resisting material, with a hardwood or other insulating floor. The hand-rail of the platform, if
of metal, shall not be connected directly or indirectly to earth.
    (4) Switchboards and fuse boards shall be fixed in accessible positions where they will not obstruct
passage or exit-ways.
248. (1) Resistance shall be mounted on incombustible bases, and shall be so protected and placed at such a
distance from any combustible material that no part of the resistance, if broken, can fall on such material, or
vice versa.
    (2) The resistances shall be provided with adequate ventilation.
249. Stage-lighting, including footlights, border-lights and proscenium side-lights shall be so wired that the
maximum current on each circuit shall not exceed ten amperes.
250. Cables to battens and floats shall be suspended in such a manner that no stress can be applied by the
conductors to any terminal to which they may be connected and shall be either–
     (a) Flexible cables covered with tough-rubber compound; or
     (b) Vulcanized rubber-insulated cables containing not less than seven strands for each conductor and
         enclosed in canvass hose; or
     (c) Flexible cables covered with a slow-burning braiding approved by the Director of Electrical
         Inspectorate Services; or
     (d) Flexible cables, covered with asbestos, or fire-resisting braiding approved; or
     (e) Flexible cables covered with cord braiding.
251. (1)Lamps on battens, footlights, etc., shall be protected by stiff wire guards so arranged that no scenery
or other inflammable material can come in contact with the lamps, and shall be properly protected from
every liable to cause short-circuit.
   (2) No readily combustible material shall be used in connection with any lamps in such a manner that it
might come in contact with the lamps or conductors.
252. Every electrical fitting or apparatus of any description shall be so fixed or arranged that in no
circumstances can it interfere with the proper working of the safety-curtain.
253. Portable lamps for the orchestra or similar lighting shall be connected to a sub-circuit or sub-circuits to
which no other lighting is connected.
                                                 Page 56 of 173
                                  Special requirements for motion picture theatres
254. Lighting and electrical installation
     The provisions of this part shall apply to every cinematograph theatre, projection or re-winding room and
file store-room.
255. Control of lighting
    Where the general lighting of the premises can be controlled from within, the projection or re-winding
room, there shall also be separate and independent means of control outside of and away from the
projection or re-winding room.
256. Electrical installation
     Where electrical energy is used for lighting or other purposes within the building the following provisions
shall be observed–
     (a) except as otherwise provided in Cinematograph Regulations, the installation generally shall be in
         accordance with these Regulations;
     (b) The main supply fuses and switches shall not be accessible to the public. They shall be located where
         there is ample space and head room and where there is no risk of fire resulting therefrom. In no
         circumstances shall they be place in a projection room, re-winding room, or film store;
     (c) a separate circuit shall be taken from the source of supply for the projector circuit so that no accident
         to this circuit can affect the general lighting;
     (d) each of the main circuits shall be separately protected by an efficient linked switch and by a fuse on
         each phase;
     (e) the general wiring of the building shall be in accordance with these Regulations, except as regards any
         necessary flexible conductors such as may be required for pendant lamps or movable fittings;
     (f) conductors from the switchboard in the projection room to the cinematograph machine shall be
         enclosed in screwed conduit, and r=terminate in a terminal-box approved by the authorized
         inspectors from such box to lamp shall be covered with fire-resisting material;
     (g) the conductor for cinematograph machines and accessories shall be taken as a separate circuit from
         the source of supply or from the supply side of the main fuses in the general lighting-circuit; and
         there shall be efficient switches and fuses inserted at the point where the supply is taken, and in
         addition an efficient double-pole switch shall be fitted in the conductors within the projection room;
     (h) the maximum potential difference across the carbons of the lamp or between any part of the arc-
         circuit on the cinematograph machine and earth shall not exceed 100volts in any circumstances;
     (i) resistances for cinematograph machines shall not be placed inside the projection room.
257. The general wiring shall be carried out in accordance with the following system–
   (1) Copper cables installed in screwed galvanized conduit: Provided that–
     (a) the conduits shall be mechanically and electrically continuous throughout and shall be efficiently
         earthed in the manner specified in these Regulations;
     (b) the electrical resistance of the conduit in a complete installation, and of the earth connection, shall
         not exceed the maximum values specified in these Regulations;
     (c) where the galvanizing of the conduit or fittings has been damaged by the use of tools or by screwing
         or threading, the exposed metal shall be painted with an aluminium paint after erection;
     (d) metal conduit shall not be buried in the ground. Where it is necessary to bury cables, armoured
         cables shall be used.
                                                 Page 57 of 173
   (2) A suitable fire-resisting mineral, insulated and metal sheathed system: Provided that–
     (a) The system shall be in accordance with the appropriate Nigerian Standards Specifications
     (b) the system shall be installed and tested in accordance with the General Regulations for Electrical
         Regulations.
258. Projection and rewinding room and film store
     All wiring contained in the projection and rewinding rooms and film store shall be carried out in a mineral
insulated metal sheathed, fire-resisting system, approved by the Director of Electrical Inspectorate Services.
All slack cables shall be heavily covered with fire-proof material.
259. An efficient double-pole main switch shall be fixed within the projection room whereby all current may
be cut off from the projector circuit, or circuits within the projection room and an additional double-pole or
triple-pole switch shall be fixed for each arc lamp so that the current may be cut off whilst recarboning is
taking place.
260. Where two or more projectors are installed and a change-over switch is required, it shall, unless it be a
double-pole switch having a secure “off” position, be in addition to and not in substitution for the main
switch.
261. All live parts of apparatus within one and a half metre of the projector shall be shielded so that they
cannot be accidentally touched. The covers of enclosed switches shall be of metal and, shall be so
constructed that the switch handle does not work through an open slot.
262. The lamp or lamps for lighting the projection and re-winding room and film store shall not be
connected to the safety lighting and shall be of the bulkhead type.
263. All metal work liable to become accidentally charge, including the projecting apparatus, shall be
efficiently earthed. The size of the earth wires shall be in accordance with the requirements of these
Regulations.
264. The arc lamp adjusting handles shall be made of insulating material and shall be so constructed and
arranged that the hand cannot inadvertently touch live metal.
265. Resistances, in which more than two kilowatts are dissipated, shall be placed in a room or place other
than the projector or re-winding room and accessible only by the technical staff. If such room or place is
within the theatre, the room or place shall not communicate directly with the auditorium. It shall be well
ventilated by ample inlets and outlines connecting directly with the outer air. Switches suitably placed shall
be provided whereby the pressure may be cut off from the resistance.
266. Motor generators or electrical generating plant and the main switch-gear shall be in a room or rooms
constructed of fire resisting materials. Such room or rooms may also contain resistance and the main supply
fuses and switches and shall be well ventilated and shall not communicate directly with the auditorium or any
part of the building to which the public is admitted. Such room or rooms shall not be used as a projection
room, rewinding room, and film-store.
267. Safety lighting.
     Safety lighting, shall be provided in every cinematograph theatre and shall be maintained in good working
order and so kept in use that it is adequate to enable the public to see the way out of the premise.
268. Electrical conductors forming part of the safety lighting system shall not be contained in the same
conduit or incorporated in the same cable as electrical conductors used for any other purpose.
269. Batteries for safety lighting.
                                                Page 58 of 173
Where the safety lighting is derived from a battery of accumulators, the battery shall be of such capacity and
so maintained as to be capable of supplying at normal voltage the full load which will be connected thereto
while the public is upon the premises.
270. All electric conductors shall be of adequate size for the current which they have to carry and shall be
efficiently covered with insulating material and shall be either placed out of reach of persons in the
auditorium and where they are not liable to damage, or protected against injury by suitable casings.
                                                       PART XV
                              Electric discharge and fluorescent light circuits and signs
271. Switches
    Every switch not specifically designed to break an inductive load of its full rated capacity shall, if used to
control filament lighting and discharge lighting, have a current rating of not less than twice the total steady
current which is required to carry out or, if used to control filament lighting and discharge lighting, have a
current rating of not less than the sum of the current flowing in the filament lamps, and twice the total
steady current flowing in the electric discharge lamps.
272. Circuit loading
     Circuits shall be capable of carrying the total steady current viz that of the lamp(s) and any associated
gear and also their harmonic currents. Where more exact information is not available, the demand in volt-
amperes may be taken for the purpose of this regulation as the rated lamp watts multiplied by not less than
1.8. The neutral conductor in every discharge-lighting circuit shall have a cross-sectional area not less than
that of the phase conductor(s).
         Note: The multiplier referred to in regulation 272 is based on the assumption that a circuit is corrected
         to a power factor of not less than 0.85 lagging, and takes into account control-gear losses and
         harmonic currents.
273. Transformer and inductors
     Every inductor and high-reactance transformer shall be installed as near as is practicable to its associated
electric discharge lamp.
274. Screening
     All live parts, including all apparatus and conductors but excluding the lamps except in the neighborhood
of their terminal, shall, be provided with effective screens of earthed metal or insulating material, of
mechanical strength adequate to withstand the conditions of normal service or alternatively for installations
on the exterior of a building, such live parts may be so situated as to be accessible only to authorized
persons. Screens of insulating materials used for this purpose shall be non-hygroscopic anti-tracking, and
substantially non- combustible.
275. Motor-generators and converters
     Every circuit which is energized by a motor generator or double wound converter shall be permanently
earthed at a terminal of the motor-generator converter.
276. Maximum permissible voltage
     No circuit sha1l use a voltage exceeding 5 kilovolts r.m.s, to earth, measured in open circuit.
277. Transformers of input exceeding 500W
     Every circuit at a voltage exceeding low voltage supplied from a transformer having a rated input
exceeding 500 watts shall be provided with means for the automatic disconnection of the supply in the event
of a short a circuit on an earth-leakage current which exceeds 20% of the normal steady current in the circuit.
                                                 Page 59 of 173
278. Ancillary requirement
    Ancillary equipment for installations at voltages exceeding low voltages, including inductors, capacitors,
resistors, and transformers shall be either totally enclosed in a substantial, earthed, metal container which
may form part of lighting fitting, or alternatively shall be placed in a suitably ventilated enclosure of
noncombustible material or of fire-resisting construction which is reserved for this equipment. A notice,
“DANGER - HIGH VOLTAGE”, shall be placed and maintained on every such container or enclosure that is
accessible to unauthorized persons and otherwise, where necessary. The word "DANGER” shall be in block
letters not less than 10mm high and the words "HIGH VOLTAGE" in letters not less than 5mm high. The
letters shall be in red on a white background and the size of each notice shall be not less than 65mm by
50mm overall
279. Segregation of circuits
    No conductor which is in metallic connection with a discharge lamp operating at a voltage exceeding low
voltage shall be in connection with any conductor or the mains supply other than by means of any connection
with earth complying with these Regulations; provided that auto-transformer delivering, voltage not
exceeding 1.5 kilovolts r.m.s. measured on open circuit may be used on a.c 2-wire circuit in which one pole of
the supply is connected with earth, subject to the provision of means of isolation of both poles of the supply.
280. Isolation of circuits
    One of the following means shall be provided inside the building for the isolation from all poles of the
supply of every self-contained light fitting or alternatively of every-circuit supplying discharge lamps
operating at a voltage exceeding low voltage, except that means need not be provided for isolation from the
neutral conductor of a 3-phase 4-wire installation–
            i.    an interlock on the self-contained light titling, so arranged that before access can be had to
                  live parts, the supply is automatically disconnected, such means being provided in addition to
                  the switch normally used for controlling the circuit, or
           ii.    effective local means for the isolation of the circuit from that supply, e.g. an adjacent plug and
                  socket-outlet conveniently placed such means being provided in addition to the switch
                  normally used for controlling the circuit, or
          iii.    a switch having a removable handle or a switch which can be locked, or a distribution board
                  which can be locked, arrangements being made to prevent the restoration of the supply by
                  unauthorized persons. Where an installation comprises more than one such switch or
                  distribution board, all keys and removable handles shall be non-interchangeable
281. Fireman’s switch
    A fireman's emergency switch shall be provided for the following installations operating at a voltage
exceeding medium voltage -
            i.    Exterior installations.
           ii.    Interior installations which run unattended (e.g. for window lighting or display purposes).
              EXEMPTION – For the purpose of regulation 282 a portable discharge-lighting fitting or sign of
              rating not exceeding 100 watts and fed from socket-outlet which provides the local means of
              isolation required by Regulation 282(ii), need not be regarded as forming part of an interior
              installation operating at a voltage exceeding medium voltage.
282. Every fireman's emergency switch shall -
                                                  Page 60 of 173
 i.      be arranged to isolate the installation from all poles of the supply, except that it need not isolate the
         installation from the neutral conductor or a 3phase 4-wire supply, and
  ii.    be colored red and have fixed near it a nameplate marked with the words, ("FIREMAN'S SWITCH”) the
         plate being of minimum size 150mm by 100mm with lettering that shall he easily legible from a
         distance appropriate to the site conditions but not less than 13mm high, and
                NOTE to item (ii) –it is desirable that the name of place should also be marked with the name of
                the company which installed or (if different) which maintains the installation.
iii.     have its ON and OFF positions clearly indicated by lettering legible to a person standing on the ground,
         and the OFF position shall be at the top, and
                NOTE to item (iii) – it is desirable that the fireman, switch be provided with a lock or catch so
                designed as to prevent the switch being inadvertently or accidentally returned to the ON position.
 iv.     be fixed in conspicuous position, reasonably accessible to -firemen, and except in the case of an
         agreement to the contrary with the-local fire-brigade authority, at not more than 2.75m from the
         ground, and
  v.     for exterior installations, be outside the building and adjacent to the electric discharge lamp(s), or
         alternatively a notice indicating the position of the switch shall be placed adjacent to the electric
         discharge lamp(s) and a nameplate shall be fixed near the switch so as to render it clearly
         distinguishable, and
 vi.     for interior installations, be in the main entrance to the building or alternatively in a position to be
         agreed with the local fire brigade authority, and
                NOTE to items (v) (vi) - It is desirable that, whenever practicable all exterior installations on any
                one building should be controlled by a single fireman's switch similarly, all 'internal installations in
                anyone building should be controlled by a single fireman's switch independent of the switch or
                any external installation.
vii.     where more than one such switch installed on anyone building be clearly market to indicate the
         installation or section of the installation which it controls, and the local fire-brigade authority shall be
         notified accordingly.
  283. A fireman's switch may be us to open one or more contactors or circuit-breakers for the total
  isolation of an installation from the supply, provided that every such contactor or circuit-breaker is arranged
  to open automatically on failure of the supply to its holding coil circuit.
  284. Types of cables
      Connections in circuit at a voltage exceeding medium voltage shall be made by cable complying with
  Nigerian Standard Specifications, except as provided in Regulations 285, 286, 293, and 294. Metal-sheathed,
  or armored, or metal-sheathed and armored, cable shall be used, except that cable having a non-metallic
  sheath may be used–
                (a) in exterior installations for inter-lamp series connections not exceeding 3m in length which
                    are not likely to suffer mechanical damage, or which are installed in box signs constructed
                    substantially of non-combustible material, and
                (b) in interior installations, in self-contained light fitting.
  285. Bare or lightly insulated conductors
                                                    Page 61 of 173
     Bare or lightly-insulated conductors of copper or nickel having a cross-sectional area of not less than 0.4
mm2 (170.7Imm), may be used for series connections in circuits operating at a voltage exceeding low voltage,
e.g. for window signs provided that either –
              1. the conductor does not exceed 1 m length is supported at intervals not greater than 500mm,
                  is-not exposed to the likelihood of mechanical damage, and is completely protected by non-
                  combustible, no hygroscopic insulating material which if in the form of glass tubing has a wall
                  thickness not less than 1 mm an overall diameter not less than 5mm and is so arranged as to
                  be reasonably secured against any displacement which would expose any part of the live
                  metal, or.
              2. The conductor is in an enclosure to the interior of which only authorized persons can have
                  access.
286. For shop-front fascia installations bare or lightly insulated conductors shall be used only for
connections housed within an earthed metal enclosure or for connections between the terminals of
electrode housings. For all other connections behind or through fascia panels, including series connections,
armored or metal-sheathed or metal-braided cable shall be used.
287. Cables and conductors in circuits operating at a voltage exceeding low voltage shall be supported at
intervals not exceeding the appropriate value stated in Table 13 in Schedule 1. Supports for insulated and
braided cables and for bare conductors shall be of non-combustible, non-hygroscopic insulating material, e.g.
glass or glazed porcelain.
288. Creepagos and clearances
     The length in mm measured along the centre line of every support which serves to separate bare mental
or cable operating at a voltage exceeding medium voltage the cable being neither metal sheathed nor
armored, from earthed metalwork, woodcraft, or surfaces likely to became damp, shall be not less than the
value obtained by multiplying the voltage to earth of transformer secondary in kilovolts (r.m.s.) measured on
open circuit, by 10.
289. In circuit operating at a voltage, exceeding low voltage the air gap in mm from metal or cables which
are neither metal-sheathed not armored, to earthed metal woodwork, or surfaces likely to become damp,
shall be not less than the value obtained by multiplying the voltage to earth of the transformer secondary in
kilovolts (r.m.s.) measured on open circuit, by 4.
290. Cable installation
     In a circuit operating at a voltage exceeding medium voltage, every cable shall be supported close to each
terminal connection and in no instance at a distance greater than 150mm, or 300mm if a glazed porcelain
electrode-receptacle forming an adequate support for the cable is used.
291. Where a connection is made to a cable in a circuit operating at a voltage exceeding medium voltage,
the insulation exposed by removing the metal sheath or braid shall be suitably protected from the effect of
ozone.
292. Where likely to suffer mechanical damage, every cable in a circuit operating at a voltage exceeding
low voltage shall be armoured or otherwise suitably protected. Non-armoured cable shall not be drawn into
metal tubing except where they pass through walls or floor where they may be installed in short lengths of
metal conduit which shall be earthed.
293. Where not otherwise readily identifiable, cables in a circuit operating at a voltage exceeding low
voltage or their protective covering shall be distinguished by tabs or labels marked "DANGER" securely
                                                 Page 62 of 173
attached at intervals not greater than 1.5m. The letters shall be in red on a white background, and shall be
not less than 10mm high.
294. Earthed return conductors
   The return cable from an electrode to a transformer terminal which is earthed may be a low voltage cable
provided that the cross-sectional area of the conductor is not less than 2.5mm2
295. The metalwork at a rotating device (e.g. the hands or a clock) may be used as a return conductor
provided that adjacent un-insulated metalwork -is permanently and effectively earthed
296. Regulation L.N 25 of 1958
The Electric Wiring Regulations Cap. 106 L.F.N of 1990 is here by repealed.
                                               Page 63 of 173
                                                 SCHEDULE 1
                                                   TABLE 1
Sizes of fuse elements composed of plain or tinned copper wire, for use in semi-enclosed fuse
                                 Current rate of fuse              Nominal diameter of wire
                                          A                                   mm
                                          3                                   0.15
                                          5                                   0.20
                                         10                                   0.35
                                         15                                   0.50
                                         20                                   0.60
                                         25                                   0.75
                                         30                                   0.85
                                         45                                   1.25
                                         60                                   1.53
                                         80                                   1.80
                                         100                                  2.00
                                                  TABLE 2
                             Assumed current demand of points and other apparatus
                        Point or other apparatus                         Current demand to be assumed
                (a)   15-ampere socket-outlet                   15 amperes
                (b)   13-ampere socket-outlet                   13 amperes
                (c)   5-ampere socket-outlet                    5 amperes
                (d)   Lighting-outlet                           Current value equivalent to the connected load,
                                                                with a minimum of 100 watts per lamp-holder
                                                                May be neglected
                (e) Electric clock, electric shaver supply
                    unit, shaver socket outlet, bell
                    transformer,       and      current-using
                    apparatus of a rating not greater than
                    15 volt-amperes                             Normal current
                (f) All other stationary appliances
       Note 1: In the interest of good planning it is undesirable that whole of the fixed lighting of an
       installation should be supplied from one final sub-circuit.
       Note 2: In the interest of providing the consumer with an adequate installation it is recommended
       that use should be made of ring final sub-circuit where applicable.
                                                        Page 64 of 173
                                                             TABLE 3
                                                 Radial and ring final sub-circuits
Description and special             Minimum copper      Minimum           Minimum copper      Rating of fuse   Maximum number of
condition if any                    conductor size or   copper clad       conductor size of   or circuit-      socket –outlets and
                                    rubber or p.v.c.    aluminum          mineral insulated   breaker          stationary appliance of
                                    insulated cable     conductor size    cable used          protecting       rating not exceeding
                                    used throughout.    of p.v.c.         throughout          final sub-       13 amperes.
                                                        insulated cable   (alternative to     circuits.
                                                        used              Col.2)
                                                        throughout
                1                          2                  3                  4                  5                    6
                                          mm2                mm2                mm2                 A
(a)     Radial final sub circuit                                                                               Provided that no fixed
        serving one room only                                                                                  water heating
        of less than 30m2 floor                                                                                appliance shall be
        area which is not a                                                                                    connected to any of
        kitchen………………..                                                                                        these points.
        Radial final sub circuit,          2.5          4                 1.5                 20
(b)     serving rooms other                                                                                    2
        than in (a) above………..             2.5          4                 1.5                 20
        Ring final sub circuit,                                                                                6
        with spurs if                      4.0          6                 2.5                 30               See regulation 31 (8) –
(c)     any………………….                                                                                            (12)
                                           2.5          4                 1.5                 30
                                                            Page 65 of 173
                                                   TABLE 4
                          Minimum internal radius of bends in cables for fixing wiring.
          Insulation                    Finish                 Overall diameter         Factor to be applied to
                                                                                     overall diameter of cable to
                                                                                     determine minimum internal
                                                                                            radius of bend
Rubber or p.v.c.(circular     Non-armored                  Not exceeding 10mm                     3
copper or circular standard                                Exceeding 10mm but not
aluminum conductors)                                       exceeding 35mm…                        4
                                                           Exceeding 25mm……….                     6
                              Armored                      Any ………………………….                        6
p.v.c.(solid aluminum or      Armored or non-armored       Any …………………………                         8
shaped copper conductors)
Impregnated paper             Lead or corrugated           Any ………………………….                       12
                              aluminium sheath with or
                              without armour
                              Smooth aluminium sheath      Not exceeding 30mm                    12
                              with or without armour       Exceeding 30mm but not
                                                           50mm……………….                           15
                              Copper or aluminium sheath   Exceeding 50mm……….                    18
Mineral                       with or without p.v.c        Any ………………………….                        6
                              covering
 *The factors are applied to the diameter over the aluminum sheath.
                                                  Page 66 of 173
                                                TABLE 5A
       Colour identification of cores of non-flexible cables and bare conductors for fixed wiring.
        Function                                             Colour identification of cores of rubber –or p.v.c.
                                                             insulated non-flexible cable or of sleeve or disc to
                                                             be applied to be conductors or cable core.
        Earthing                                             green-and -yellow
                                                  Page 67 of 173
                                                        TABLE 5B
                               Colour identification of cores of cables and flexible cords.
                 Number of cores                       Function of core           Colour(s)of core
                         1                    Live…………………………………………                Brown (a)
                                              Neutral……………………………………               Blue
                                              Earthing …………………………………              Green and yellow
                         2                    Live ………………………………………..              Brown
                                              Neutral …………………………………..             Blue (b)
                         3                    Live …………………………………………               Brown (c)
                                              Neutral …………………………………..             Blue (b)
                                              Earthing………………………………….              Green and yellow
                      4 or 5                  Live ………………………………………..              Brown or black (d) (c)
                                              Neutral……………………………………               Blue (b)
                                              Earthing………………………………….              Green and yellow
                                                  TABLE 6
                                        Capacities of steel conduits
 Maximum capacities of steel conduits, for the simultaneous drawing-in of single-core p.v.c. cables or rubber
                                                   cables.
                          Cable size                                              Conduit size and gauge
Nomina       Number and          Nomin
    l      diameter of wire         al
conduc         No/mm2            overall
                                            16mm or 5/8 in       20 mm or ¾ in         25 mm or 1in        32 mm or 1 ¼ in
tor size                         diame
 mm2                               ter
                                   mm
   1              2                 3        4         5          6         7        8           9          10       11
             P.V.C cables                  Metric    Metric     Metric    Metric  Metric       Metric      Metric   Metric
                                           Light     Light      Light     Light    Light       Light       Light    Light
                                                                      Maximum number of cables
  1.0          1/1.13             2.9        8         7         13        12       22          19          38        35
  1.5          1/1.38             3.1        7         6         12        10       19          17          33        31
  1.5          7/0.50             3.3        6         5         11        10       18          16          31        28
  2.5          7/1.78             3.5        5         4          9         8       15          13          26        24
  2.5          7/0.67             3.8        4         4          8         7       13          11          22        20
   4           7/0.85             4.3        3         3          6         5       10           9          17        16
   6           7/1.04             4.9        3         2          5         4        7           7          13        12
  10           7/1.35             6.2        -         -          3         2        4           4          8          7
  16           7/1.70             7.1        -         -          2         -        3           3          6          5
  25           7/1.24             9.0        -         -          -         -        2           2          4          4
  35          19/1.53             10.1       -         -          -         -        -           -          3          2
  50          19/1.78             12.0       -         -          -         -        -           -          2          2
            Rubber cables
  1.0          1/1.13              3.4       6         5          10        8          16            14     28        25
  1.5          1.1.38              3.6       5         4          9         8          14            13     27        23
                                                      Page 68 of 173
  2.5            1/1.78         4.0      4          3           7      6         11        10         20         18
   4             7/0.85         5.2      2          2           4      3          7        6          12         11
   6             7/1.04         6.0      2          -           3      2          5        4          9           8
  10             7/1.35         7.3      -          -           2      -          3        3          6           5
  16             7/1.70         8.4      -          -           -      -          2        2          4           4
  25             7/2.14         10.1     -          -           -      -          -         -         3           2
  35             19/1.53        11.7     -          -           -      -          -         -         2           2
NOTE. – The maximum numbers of cables in the table relate to conduit ruins incorporating not more than
two 900 bends or the equivalent. Where runs include additional bends, sets or other restrictions, the numbers
must be appropriately reduced. This applies particularly where solid conductor cables are to be drawn in.
                                                  Table 7
                                        Capacities of p.v.c. conduits
 Maximum capacities of steel conduits, for the simultaneous drawing-in of single-core p.v.c. cables or rubber
                                                   cables.
                              Cable size                                         Conduit size and gauge
Nominal            Number and            Nominal
                                                         16mm or                                       12mm or 1 ¼
conductor size     diameter of wire      overall                     20mm or ¾ in     25mm or 1 in
                                                          5/8 in                                           in
mm2                No/mm2                diameter mm
      1                     2                   3          4              5                6                7
                                                         Metric A    Metric A or B    Metric A or B    Metric A or B
                       P.V.C Cables                       or B
                                                                        Maximum number of cables
        1.0              1/1.12              2.9            7            12            20                   34
        1.5              1/1.38              3.1            6            11            18                   30
        1.5              7/0.50              3.3            6            10            16                   28
        2.5              1/1.78              3.5            5             8            14                   20
        2.5              7/0.67              3.8            4             7            12                   20
         4               7/0.85              4.3            3             5             9                   15
         6               7/1.04              4.9            2             4             7                   12
        10               7/1.35              6.2            -             2             4                    7
        16               7/1.70              7.3            -             2             3                    5
        25               7/2.4               9.0            -             -             2                    3
        35              19/1.53              10.3           -             -             2                    3
        50              19/1.78              12.0           -             -             -                    2
                      Rubber cables
        1.0              1/1.13              3.4            5              9               15               25
        1.5              1/1.38              3.6            5              8               13               22
        2.5              1/1.78              4.0            4              6               10               18
         4               7/0.85              5.2            2              4                6               10
         6               7/1.04              6.0            -              3                4                8
        10               7/1.35              7.3            -              2                3                5
        16               7/1.70              8.4            -              -                2                4
        25               7/2.14              10.1           -              -                -                2
        35              19/1.53              11.7           -              -                -                2
                                                    Page 69 of 173
NOTE. – The maximum numbers of cables in the table relate to conduit ruins incorporating not more than
two 900 bends or the equivalent. Where runs include additional bends, sets or other restrictions, the numbers
must be appropriately reduced. This applies particularly where solid conductor cables are to be drawn in.
                                              TABLE 8
   Minimum lengths of span and minimum heights above ground for consumer’s overhead wiring between
                                           buildings etc.
                                                                               Minimum height of span above ground
                                           Maximum length
 Types of system, and relevant item of                                                   In position accessible
                                               of span                                                              In positions
           Regulation 7.112                                                                to vehicular traffic
                                                                    At road crossing                              inaccessible to
                                                                                            other than road
                                                                                                                 vehicular traffic
                                                                                                crossings
                  1                                 2                      3                        4                    5
                                                    m                      m                       m                     m
 Cables sheathed with p.v.c. or having
an oil-resisting and flame-retardant or
 h.o.f.r. sheath, without intermediate
             support (item (i))                     3                                                                   3.5
 Cables sheathed with p.v.c or having
an oil-resisting and flame-retardant or
  h.o.f.r sheath, in heavy-gauge steel
            conducts (item(ii))                     3                                                                    3
p.v.c. covered overhead line conductors
    insulators without intermediate
            support (item(iii))                     30              5.8 (for all types)        5.2 (for all types)      3.5
 Cables sheathed with p.v.c .or having
an oil-resisting and flame retardant or
     h.o.f.r.shearth supported by a
        centenary wire (item(iv))              No limit                                                                 3.5
Aerial cable incorporating a centenary    No limit subject to
                                                                                                                        3.5
               wire (item(v))              regulation 7.3(x)
  Bare or p.v.c covered overhead lines
 installed in accordance with the over
    head line Regulations (item(vi))             No limit                                                               5.2
                                                        TABLE 9
                                     Plugs and socket-outlets for low-voltage circuits
                   Type of plug and socket-outlet                                         Rating (amperes)
     Fused plugs and shuttered socket-outlets, 2-pole and
     earth for a.c                                                                13a (with fuses rated at 3 and 13)
     Plugs (fused or non-fused) and socket-outlets, 2-pole and
     earth                                                                                   2, 5, 15, 30
     Plugs (fused or non-fused) and socket-outlets, protected
     type, 2-pole with earthing contacts                                                      5, 15, 30
     Plugs and socket-outlets (theatre type)                                                      15
     Plugs and socket-outlets(industrial type)                                             16, 32, 63, 125
                                                            Page 70 of 173
                                                 TABLE 10
                            Connection of plugs, socket-outlets and connectors
                                                                    Corresponding conductor
       Terminal marking                For circuits having an earthed neutral      For circuits in which neither pole of the
                                                       conductor                               supply is earthed
                L                                   Live conductor
               N                                  Neutral conductor                             Live conductors
             I or E                          Earth-continuity conductor                  Earth-continuity conductor
                                             TABLE 11
Maximum earth-loop impedances for earth-leakage protection by semi-enclosed fuses or cartridge fuses
         rating a fusing factor exceeding 1.5 (system operating at 230-250 volts to earth)
                           Current rating of fuse:                       Impedance:
                                 amperes                                   ohms
                                     5                                       16
                                    10                                        8
                                    15                                      5.3
                                    20                                        4
                                    30                                      2.7
                                    45                                      1.8
                                    60                                      1.35
                                    100                                     0.8
                                              TABLE 12
Minimum sizes of copper earthing leads, copper bonding leads and copper earthing continuity conductors
               not forming part of the same cable as the associated circuit conductors.
    Nominal cross sectional        Nominal cross               Nominal cross               Nominal cross
    area of largest associated     sectional area of           sectional area of           sectional area of
    copper circuit conductor       earthing lead               earthing lead               bonding lead
                                   conductor                   conductor                   conductor
                  1                           2                           3                           4
                                                     Page 71 of 173
mm2   mm2                mm2   mm2
1.0     6                1.0   1.0
1.5     6                1.0   1.0
2.5     6                1.0   1.0
  4     6                2.5   1.0
  6     6                2.5   1.0
 10     6                  6   2.5
 16     6                  6   2.5
 25    16                 16    6
 35    16                 16    6
 50    16                 16    6
 70    50                 50    16
 95    50                 50    16
120    50                 50    16
150    50                 50    16
185    70                 70    50
240    70                 70    50
300    70                 70    50
400    70                 70    50
500    70                 70    50
630    70                 70    50
        Page 72 of 173
                                                    TABLE 13
          Support for cables and conductors in circuit operating at voltage exceeding medium voltage.
                                                                                       Spacing of supports
                   Types of cable or conductor
                                                                          Horizontal                            Vertical
                                                                            mm                                   mm
     Bare conductors                                                         500                                  500
     Insulated and braided cables                                            500                                  800
     Metal-sheathed non-armoured cable                                       800                                 1250
     Armoured or metal-sheathed armoured cable                              1000                                 1500
                                                TABLE 14
                                         Allowance for diversity
 Estimation of the maximum current which will normally flow in an installation. For use in calculating the size
                          of cables and switch-gear except for final sub-circuits.
 Purpose of final sub-circuits fed from the                                     Types of installation
     wiring to which diversity applies         Individual domestic         Block of          Hotel, boarding           Shops, etc e.g.
                                                   installation        residential flats     houses, lodging             offices and
                                                     including                                  houses, etc          business premises,
                                                Individual flats of                                                      other than
                                                      a block                                                             Factories
1.                  Lighting                            66%                  50%                   75%                       90%
2.   Heating and power appliances (but        100% fl up to 10        100% fl of the       100% fl of the           100% fl of the
     see 3-8 below)                           amperes                 largest appliance    largest appliance        largest appliance
                                              +50% of any load in     +50% fl of 2nd       +80% fl of 2nd           +75% fl of
                                              excess of 10            largest appliance    largest appliance        remaining
                                              amperes                                                               appliance
                                              appliance               +33% fl of 3rd       +60% fl of
                                                                      largest appliance    remaining
                                                                                           appliances
                                                                      +20% of
                                                                      remaining
                                                                      appliance
3.   Cooking appliances permanently           10 amperes              100% fl of largest   100% fl of largest       100% fl of largest
     connected                                                        appliance            appliance                appliance
                                              30% fl of connected     +50% fl of 2nd       +80% fl of 2nd           +80% fl of 2nd
                                              cooking appliances      largest appliance    largest appliance        largest appliance
                                              in excess of 10
                                              amperes
                                              +5 ampere if socket-    +33% fl of 3rd       +80% fl of 2nd           +80% fl of 2nd
                                              outlet incorporated     largest appliance    largest appliance        largest appliance
                                              in unit
                                                                      +25% fl of 4th
                                                                      largest appliance
                                                                      +20% of
                                                                      remaining
                                                                      appliances
4.   Motors other than Kft motors which                                                    100% fl of the           100% fl of the
                                                      NO DIVERSITY ALLOWED
     are subject to special conditions                                                     largest motor            largest motor
                                                                                           +50% fl of               80% fl of 2nd largest
                                                           Page 73 of 173
                                                                                         remaining motors      motors
5.   Water heaters (instantaneous type)    100% fl of the largest appliance              To be assessed by a competent person
                                               150% fl of 2nd largest appliance          To be assessed by a competent person
                                               +25% of remaining appliances              To be assessed by a competent person
6.   Water heaters (thermostatically
                                                              NO DIVERSITY ALLOWED **
     controlled)
7.   Socket-outlets and stationery         100% largest fuse      100% largest fuse      100% largest fuse      100% largest fuse
     appliances in accordance with Table   or circuit-breaker     or circuit-breaker     or circuit-breaker     or circuit-breaker
                                           rating of individual   rating of individual   rating of individual   rating of individual
                                           circuits               circuits               circuits               circuits
                                           +40% sum of fuse       +40% sum of fuse       +50% sum of fuse       +40% sum of fuse
                                           or circuit-breaker     or circuit-breaker     or circuit-breaker     or circuit-breaker
                                           rating of other        rating of other        rating of other        rating of other
                                           circuits               circuits               circuits               circuits
8.   Socket-outlet and stationery          100% fl of largest     100% fl of largest     100% fl of largest     100% fl of largest
     appliances other than those listed    point                  point                  point                  point
     above
                                           40% fl of other        40% fl of other        75% fl of points in    75% fl of other
                                           points                 points                 main rooms (dining     points
                                                                                         room, etc)
                                                                                         40% fl of remaining
                                                                                         points
*For the purpose of this Table, an instantaneous water-heater is deemed to be water-heater of any loading
which heats water only while the tap is turned on and therefore uses electricity intermittently.
**It is important to ensure that the distribution boards are of sufficient rating to take the total load
connected to them without the application of any diversity.
                                                SCHEDULE II
                                                 APPENDIX I
                                                Completion Certificate
(Prescribed for Electrical Installations of Buildings)
Completion Certificate to be given by the contractor or other person responsible for the construction of the
installations, or major alteration thereto, or by an authorized person acting on his behalf.
I certify that the electrical installation at …………………………………………………………………………………………
……………………………………………………………………………………………………………………………………………………..
has been inspected and tested, in accordance with the requirements of Federation of Nigeria, Electricity Act
and Regulations for Electrical Installations and that, to the best of my knowledge and belief, the installation
summarized complies, at the time of my test, with those Regulations current at the date of contract for the
work, except as stated.
I recommend that this installation be further inspected and tested after an interval of not more than
……………………………………………………………………………… months.
                                                       Page 74 of 173
For and on behalf of: ………………..........................................................................................................
Address…………………………………………………………………………………………………………………………………………
                                                                Page 75 of 173
                                          INSPECTION CERTIFICATE
                                                    APPENDIX 2
 Notes on precautions against corrosion of metal sheaths of cables and mental conduit ducts and trunking and
                                                     their fixings
In damp situations, precautions are desirable against corrosion of metal cable sheaths and amour of cables,
metal conduit and conduit fittings, metal duct and trucking systems, and associated metal fixings, where
these are likely to come into contact with any of the following materials:
           i.    Materials containing magnesium chloride which are used in the construction of floors and
                 dadoes,
          ii.    Plaster undercoats contaminated with corrosive salts,
         iii.    Lime, cement and plaster (e.g. on unpainted walls).
         iv.     Oak and other acidic woods,
          v.     Dissimilar metals liable to set up electrolytic action.
Application of bitumen or bituminized paint before erection - or prevention of contact by separation with
bitumen felt, is recognized as effectual precautions against corrosion.
Special care is required in the choice of materials for clips and other fittings, for bare aluminum-sheathed
cables and for aluminum conduit, to avoid risk of local corrosion n damp situations. Suitable materials for this
purpose are the following -
Porcelain,
Aluminum,
Corrosion-resistant aluminum alloys,
Zinc alloys
Iron or steer protected-against rust by galvanizing,
Sherardizing, etc.
Contact between bare aluminum sheaths or aluminum conduits and any parts made of brass pr other metal
having a high copper content, should be especially avoided in damp situations, unless the parts .are suitably
plated. If such contact is unavoidable, the joint should be completed protected against ingress of moisture
wiped joints in aluminum-sheathed cables should always be protected against moisture by a suitable paint,
by an impervious tape, or by embedding in bitumen.
                                                  APPENDIX 3
                                       Earthing tests and measurements
     The following methods shall be used to carry out that test called for in these Regulations –
                                                  Page 77 of 173
(1) Test of earth-continuity conductors:
      The resistance of earth-continuity conductors referred below are subject also to the requirements for
earth loop impedance. Lower values than those stated may be necessary in order to meet the requirements
for the total earth loop impedance (see Regulation 173).
         (a) A.C. Test:
            Tests of earth-continuity conductors shall preferably be made with alternating current at the
frequency of the supply and of magnitude approaching 1.5 times the rating of the final sub-circuit under test,
except that the current need not exceed 25 amperes. The test shall be made when the normal supply is
disconnected from the final sub-circuit under test. One end of the earth-continuity conductor shall be
connected to a cable of known resistance, which may be one of the tables of that final sub-circuit. An a.c.
voltage not exceeding 40 volts shall then be applied between other end of the earth-continuity conductor
and the other end of the cable. Subject to the requirements for total earth loop impedance, it is satisfactory if
in this instance the ratio voltage/current, less the resistance of the return conductor does not exceed 1 ohm.
         (b) Reduced A.C. test
            If it is preferred, e.g. owing to the need to use hand testers, not to apply a test at full current as
described above, a lower value of alternating current at approximately frequency of the supply may be used
for the testing of an a.c. installation, following in other respects the same procedure.
          Subject to the requirements for total earth loop impedance, it is satisfactory if after allowance has
been made for the return conductor, a value not exceeding 0.5 ohm for the ratio voltage/current is obtained
where steel conduit or pipe forms part or whole of the earth-continuity conductor, or a value of 1 ohm where
the earth continuity conductor is composed entirely of copper, copper-alloy or aluminum. it is often more
convenient if a hand-generator or other portable device can he used rather than a transformer fed from the
supply, as in this- event the live conductors of the various sub circuits, while disconnected from the supply,
may be connected for purpose of test to the consumer's earthling terminal and a test can then be carried out
between line and earthling conductor at each individual point, such as a socket outlet.
         (c) D.C. test of A.C. installation
          If it is not convenient to use a.c. for the testing of an a.c. installation, d.c. may be applied instead
provided it has been ensured by inspection throughout the whole length of the earth-continuity conductor
that no inductor is incorporated. In these circumstances and subject to the requirements tor total earth loop
impedance, it is satisfactory, where steel conduit or pipe forms part or the whole of the earth-continuity
conductor, if a value of resistance not exceeding 0.5 ohm is obtained, or where the earth continuity
conductor is composed entirely of copper, copper-alloy aluminum, a value of resistance not exceeding 1ohm.
         (d) D.C. test of D.C. installation
          Where a test of an earth-continuity conductor in a d.c. installation is required, this shall preferably
be made by means of a current (which may be obtained from a secondary battery and rheostat) of
magnitude approaching 1.5 times the rating of the sub-circuit under test, subject to a maximum of 25
amperes. If it ·is preferred 'not to apply a test at full current, a hand-tester may he used. In other respects the
procedure set out in (a) above applies and, subject to the requirement for total earth loop impedance, it is
satisfactory if the resistance obtained in the test does not exceed 1 ohm.
(2) Earth-loop impedance test:
         These tests should be made with the cross bonds required by these Regulations in place. The earth-
fault-loop path (line-earth loop) comprises the following parts, starting and ending at the point of fault (see
                                                  Page 78 of 173
also Figure 1) – the earth-continuity conductor, the consumer's earthing terminal and the earthing lead, the
metallic return path where available, which may consist of the metallic cable sheath or the continuous earth
wire or an overhead line or, in the case of protective multiple earthing (P.M.E.) the neutral conductor or,
where no metallic return path is available the earth return path and the path through the earthed neutral
point of the transformer and the transformer winding and the live conductor.
        The method used may show the loop impedance in ohm alternatively it may give a direct indication of
the maximum permissible fuse rating or setting of a circuit-breaker, or an indicator where a fuse or circuit-
breaker of a given rating will operate satisfactorily under fault conditions.
         (a) Tests in line-earth loop:
          These tests may be achieved by an instrument which determines the current flowing when a known
resistance is connected between the live conductor and consumer's earthing terminal using such an
instrument, care should be taken that no ill effects can arise if the earthing circuit is defective
         (b) Tests in neutral-earth loop:
          Except when the system is earthed by protective multiple earthing (P.M.E.), it is permissible to test
the neutral-earth loop instead of the line-earth loop. This may be achieved by a method which injects current
into the neutral-earth Loop, preferably by means of a transformer fed from the mains, or alternatively from
a.d.c. source the polarity of which is rapidly and continually reversed. The instrument employed must he so
designed, or used, that its indications are not affected by neutral currents flowing in the system. In using such
an instrument, care should be taken to ensure that no ill effect can arise if the circuit tested is defective.
Measurements on systems fed from small transformers may require compensation to include an allowance
for the impedance of the winding of transformers, balancers, etc. If a test with rapidly-reversed d.c. is made
on an a.c installation it should be ensured, by inspection, that no inductor is incorporated in the earth-
continuity conductor.
          When a measurement on an a.c system is made with less man 10 amperes a.c. or with rapidly-
reversed D.C. and the earth-continuity conductor is wholly or mainly of steel conduit or pipe, the effective
value shall be taken as twice the measured value less the value measured at the consumer's earthing
terminal. In all other cases the' effective value shall be the measured value subject to any necessary
adjustment for impedance of supply transformers, balances, etc., as mentioned above.
(3) Test of earth-leakage circuit-breakers:
      For the purpose of this test a voltage not exceeding 45 volts, obtained from a double-wound
transformer connected to the mains supply Shall applied across the neutral and earth terminals (or neutral
and frame terminal of a voltage operated earth leakage circuit breaker) and /the circuit-breaker shall trip
instantaneously. The transformer shall preferably have a short-time rating of not, less than 750 V A. (see
Figures 2 and 3).
      When, in accordance with the requirements of these Regulations, across-bonding to other services is
carried out in an installation where a voltage-operated earth-leakage circuit-breaker is provided, this may
result in a direct earth connection of low impedance being introduced in parallel with the path through the
earth-leakage circuit-breaker. Thus an increased value of earth-leakage current would need to flow before
the circuit-breaker came into operation, and in some instances the cross-bonding may well remedy the
deficiency which originally gave rise to the need for the earth-leakage circuit breaker. These effect are not
harmful it is common practice to use the best solid earth available (e.g. suitably spaced earth electrodes) in
                                                 Page 79 of 173
parallel with an earth-leakage circuit-breaker. The circuit-breaker would still be effective in preventing the
exposed metal work of the installation from rising to a dangerous voltage.
(4) Measurement of consumer's earth-electrode resistance:
       The following procedure shall be adopted where it is desired measure the resistance of the earth
electrode, e.g.-where the installation fails to satisfy the earth-loop impedance test or where desired to check
the continuity effect) through an earth electrode. (See also Figure 4).
        An alternating current of a steady value shall be passes between the earth electrode X and an auxiliary
earth electrode Y placed at such a distance from X that the resistance areas of the two electrodes do not
overlap. A second auxiliary earth electrode Z, which may be metal like driven into the ground shall be
inserted half-way between X and Y and the voltage drop between X and Z shall be measured. The resistance
of the earth electrodes is then the voltage between X and Z divided by the current flowing between X and Y
provided that there is no overlap the resistance areas. To check that resistance of the earth electrodes is a
true value two further readings shall be taken with the second auxiliary electrode Z moved further from and
6m further to X respectively. If the three results are substantially agreement, the mean of the three readings
shall be taken as the resistance of the earth electrode X. if there is no such agreement the tests shall be
repeated with the distance between X and Y increased.
       The test shall be made either with current at power frequency, in which case the resistance of the
voltmeter used must be high (of the other of 200 ohms per volt), or with alternating current from an earth
tester comprising a hand-driven generator, a rectifier (where necessary), and a direct-reading ohmmeter.
       If the tests are made at power frequency the source of the current used for the test shall be isolated
from the power mains (e.g. by a double-wounded transformer), and in any event the earth electrode X under
test shall be disconnected from all sources of supply other than that used for testing.
                             Preface to the tables of current rating and voltage drop
1. Basis of current ratings and values of voltage drop
      The current ratings and values of voltage drop for cables and 'bare conductors set out in Tables 15 to 33
with the associated rating factors and notes.
      The current ratings and values of voltage drop for cables are applicable only to cables of voltage rating
not exceeding 600/1000V (or of voltage rating 600V or 1000V, for mineral-insulated cables).
      The voltage drop for any particular cable run must be such that the total voltage drop in the circuit of
which the cable forms a part does not exceed the limit prescribed in these Regulations i.e. the total voltage
drop between the' consumer's terminals and the other end of the circuit must not exceed 2.5 % of the
declared or nominal voltage (for example, 5.75 volts for a phase voltage of 230 volts) when the circuit is
carrying the designed full load current. The tabulated current ratings may be used only where the associated
values of voltage drop, adjusted in proportion to the actual length of run, do not cause that limit to be
exceeded.
       Values of voltage drop are tabulated for a current of one ampere for all 1m run, i.e. for a distance of
1m along the route taken by the cables, and represent the result of the voltage drops in all the circuit
conductors. For balanced three-phase a.c. circuits the values relate to the line voltage.
       For any given run the values need to be multiplied by the length of the run in meters and by the
current the cables are to carry. Where the actual current to be carried differs greatly from the current rating
tabulated, the result obtained by multiplying the tabulated voltage, drop values in this way are approximate
                                                Page 80 of 173
only; for a more accurate assessment allowance should be made for, the change in conductor resistance with
operating temperature.
       The values of voltage drop tabulated (except those in Tables 24 - 25 and 32 -33) relate the worst
conditions, viz where the phase angle of the cable circuit is equal to that of the load. For cables up to and
including 120mm2 they apply with sufficient accuracy where the power factor of the load lies between 0.6
lagging and 1.0 and for larger cables where the power factor of load does not exceed 0.8 lagging. In all other
causes the value may be unduly conservative and more exact calculation is necessary
       As explained below, the rating is to be modified where applicable by rating factors in respect of–
         Ambient temperature,
         Class of excess-current protection,
         Grouping,
         Disposition,
         Type of sheath.
       If the conditions of installation of cables depart in more than one respect from those provided for in
the appropriate table, it is necessary to apply a separate factor for each special circumstance. In every
instance the appropriate factors are to be applied to the current ratings as multipliers.
2. Application of rating factors
                  (a) For ambient temperature
       The current ratings given in the Tables for cables and hare conductors are based on an ambient air
temperature of 30oC. Where the ambient air temperature exceeds this figure, the appropriate rating factor
referred to below the Table must be applied: on the other hand if it can be established that the ambient
temperature will not exceed 25°C, use may be made of the rating factor appropriate to this temperature.
       The ambient air temperature may be determined by thermometers placed in free air as close as
practicable to the position at which the cables are installed or are to be installed, subject to the provision that
the measurements must not be influenced by the heat arising from the cables; thus if the measurements are
made while the cables are loaded, the thermometers must be placed about O.5m from the cables, depending
on their size, in the horizontal plane, Or 150mm below the lowest of the cables.
                  (b) Class of excess-current protection
       Cables insulated with some thermoplastic materials (e.g., p. v. c.) may sustain serious damage when
subject even for relatively short periods, to ·temperature which are appreciably higher than those
permissible for continuous operation. Also at such excess temperatures, if sustained, the elastic properties of
the smaller sizes of cables having synthetic rubber installation may show a tendency to deteriorate.
Therefore the current ratings of cables insulated with p. v. c or synthetic rubbers are determined not only by
the maximum conductor temperature admissible for continuous running, but also by the temperature likely
to be attained under conditions of excess-current.
       In the tables relating to those types cable, therefore, the tabulated ratings are related to the class of
excess-current protection afforded for the cables. For the purposes of the Regulations the following classes of
excess-current protection are defined–
                                           Close excess-current protection
       Excess-current protection which will operate within four hours at 1.5 times the designed load current
of the circuit which it protects. Devices affording close excess-current protection include–
                i.    Fuses fitted with fuse-links of fusing factor not exceeding 1.5:
                                                  Page 81 of 173
              ii.   Miniature, and moulded-case circuit breakers;
             iii.   circuit-breakers set to operate at an overload not exceeding 1.5 times the designed load
                    current of the circuit.
                                                 Page 82 of 173
       (1) Two or three single-core cables are installed one above the other, fixed to the vertical surface at a
wall or open cable trench as follows, the distance between the wall and the surface of the cable being at least
20mm in each instance. Cables in which the conductor cross-sectional area exceeds 185mm2 are installed at a
distance between centres of about 90mm.
       The ratings for two cables may be applied with safety in instances where such cables are installed in
horizontal formation on brackets fixed to a wall, either spaced as indicated above, or touching throughout.
      (2)Three single-core cables are installed in trefoil formation, fixed to the vertical surface of a wall or
open cable trench, the cables touching throughout and the distance between the wall and the surface of the
nearest cable being at least 20mm; or, alternatively, three single-core cables are installed in trefoil 1
formation and laid on a non-metallic floor, the cables touching each other and the floor throughout.
       The ratings given apply provided that the sheaths of single-core metal-sheathed cables are electrically
bonded at each end of the run. The cables are assumed to be remote from iron steel, or ferro-concrete, other
than the cable supports.
                (b) Multicore cables
        Cables of all types other than single-core cables are installed singly, fixed to the vertical surface of a
wall, open cable trench, the distance between the surface of the cable and the wall being at least 20mm in
every instance.
       For cables spaced by distances less than those described above, the current ratings in the columns
headed “Clipped direct to a surfaced ....” should be applied.
4. Types of cable and conditions of installation not provided for in the tables
         To reduce the number of tables of current rating that would otherwise need to be included in the
Regulations, ratings are not tabulated for types of cable and/or conditions of installation in less common use.
Thus ratings for the following types and conditions have been omitted–
                     i.   rubber insulation non-flexible multi core cables,
                    ii.   Cables insulated with varnished fabric (Terylene) or with varnished cambric and heat-
                          resisting fiber
                  iii.    p.v.c. insulated and p.v.c. sheathed circular Cables of conductor size up to and
                          including 16mm2
                   iv.    Paper insulated cabIes.
                    v.    p.v.c. insulated cables, non-armoured, copper-clad conductors; circular twin and multi
                          core type, and single core cables of conductor’s size above 35mm2,
                   vi.    Cables in underground pipes and ducts
                  vii.    Cables buried direct in the ground,
                 viii.    Overhead line conductors,
                   ix.    400 Hz ratings
                    x.    Cables insulated with heat-resisting P. V.C compound.
                                                 Page 83 of 173
                                                    SCHEDULE 3
                                                      TABLE 15
                          P.V.C non-armoured single-core (1.0 mm2 to 35mm2) (Copper)
  Single-circuit current ratings and associated bolt drops for single-core p.v.c-insulated cables,non-armoured
                                               with or without sheath
                                      (Copper conductors) 1.0 mm2 to 35 mm2
 The ratings tabulated apply where the cable is provided with coarse excess-current protection (see item 2(b)
                                                   of the preface)
                             For the close excess-current protection, see ratings below
            Conductors                     Bunched and enclosed in conduit or        Clipped directed to surface or on a cable tray,
                                                     trunking**                                 bunched and unenclosed
Nominal       No. and dia (mm)     2 cables, single-phase    3 or 4 cables three-    2 cables, single –       3 or 4 cables, three-
cross-        or wires (nominal)   a.c or d.c                phase a.c               phase a.c or d.c         phase a.c
sectional
area
                                   Current          Volt      Current     Drop per    Current     Volt drop    Current     Volt drop
                                    rating         drop*       rating     ampere       rating        per        rating        per
                                                    per                     per                    ampere                   ampere
                                                  ampere                   metre                     per                      per
                                                    per                                             metre                    metre
                                                  metre*
    1                    2             3             4           5              6        7            8           9           10
        2
   mm                                 A             mV          A            mV          A           mV          A            mV
   1.0             1/1.13             11            40           9           35          13          40          12           35
   1.5             1/1.38             13            27          11           23           -          27           -           23
     -             7/0.50              -            30           -           26          16          30          15           26
   2.5             1/1.78              -             -           -            -           -           -           -            -
     -             7/0.67             18            16          16           14          23          16          20           14
     4             7/0.67             24            10          22           8.8         30          10          27           8.8
     6             7/1.04             31            6.8         28           5.9         38          6.8         34           5.9
    10             7/1.35             42            4.0         39           3.5         51          4.0         46           3.5
    16             7/1.70             56            2.6         50           2.2         63          2.6         61           2.2
    25             7/2.14             73            1.6         66           1.4         89          1.6         80           1.4
    35             19/1.53            90            1.2         80           1.0        109          1.2         98           1.0
   *Total volt drop between the consumer’s terminals and any other points in the installation must not
exceed 2.5%of the nominal voltage.
   **The range ratings in columns 3 and 5 relate to cables in metal or non-metallic conduit and trunking. For
cables in underground pipes and ducts see item 4(vi) of the preface to the Tables.
                                                            Page 84 of 173
                                               Rating factors
                                       For class of current protection
    The rating tabulated may be multiplied by 1.11 where close excess-current protection can be assured
                                          For ambient temperature
Ambient temperature                                            250C     350C    400C           450C     500C    550C       600C         650C
Rating factor for cables having coarse excess-current
protection………………………                                            1.02     0.97        0.94       0.91     0.88     0.77          0.63     0.44
Rating factor for cables having close excess-current
protection………………………                                            1.06     0.94        0.87       0.79     0.71     0.61          0.5      0.35
                                                     For groups
 For groups of circuits unenclosed the single circuits rating apply provided that
    (1) The horizontal clearance between circuits is
             (a) Not less than 6 times the overall diameter of an individual cables and
             (b) Not less than overall width of an individual circuits except that the horizontal clearance need
                 not in any case exceed 150mm,and
    (2) The vertical clearance between circuits is not less than 150mm,and
    (3) If the number of circuits exceeds 4.they are installed in a horizontal plane.
  In all other cases unless a more precise evaluation of current ratings has been made based on
experimental work or calculated data ,the following factors are applicable–
No. of circuits (pairs of cables single –phase a.c or d.c
                                                          Page 85 of 173
                                                                           TABLE 16
                                               P.V.C. non-armoured single core (50mm2 to 630mm2) (Copper)
            Single-circuit current ratings and associated volt drops for single core p.v.c insulated cables non-armoured with or without sheath.
                                                          (Copper conductors) (50mm2 to 630mm2)
                                    The rating tabulated apply only where the cables has close excess current protection,
                                                                (see item 2 (b) of the preface)
                                     For coarse excess-current protection, the rating factors given below must be applied
nominal      Bunched and enclosed in conduit of trunking**       Clipped direct to a surface or on a cable, tray                      Defined conditions                      Conduc
  cross-                                                                    bunched and unenclosed                                                                              tor
sectional    2 cables single-phase a.c or     3 or 4 cable      2 cables single-phase a.c or      1 cable three-     Volt drop per ampere per metre*       Trefoil (3 cable
 area of                  d.c               three-phase d.c                  d.c                     phase d.c                                              three-phase)
 conduct      current       Volt drop per   curren     Volt    current       Volt drop per       curren      Volt   curren   Single      d.c     Three     curr       Volt
    or         rating          ampere          t       drop     rating        ampere per            t       drop       t        -                  -        ent      drop
                               metre*       rating      per                      metre*          rating      per    rating   phase               phase     ratin      per
                                                      amper                                                amper                                             g      amper
                                                       e per                                                e per                                                    e per
                                                      metre                                                metre                                                    metre*
                                                         *                                                     *
   1             2           3        4       5          6         7          8          9         10         11     12       13         14        15       16       17        18
       2
  mm             A          mV       mV       A        mV         A         mV         mV         A        mV         A       mV        mV        mV        A        mV        mm2
   50           145        0.97     0.91     100      0.82      175        0.93       0.91        10       0.82      195     0.95      0.91       0.85     170      0.10        50
   70           185        0.71     0.63     160      0.62      220        0.65       0.63       200       0.59      240     0.68      0.63       0.62     210      0.59        70
   95           230        0.56     0.45     195      0.48      270        0.48       0.45       240       0.45      300     0.52      0.45       0.49     260      0.42        95
  120           260        0.48     0.36     220      0.42      310        0.40       0.36       280       0.38      350     0.44      0.36       0.43     300      0.34       120
  150            -           -        -       -         -       335        0.34       0.29       320       0.34      410     0.39      0.29      0.39      350      0.29       150
  185            -           -        -       -         -       405        0.29       0.24       365       0.30      470     0.35      0.24      0.36      400      0.25       185
  240            -           -        -       -         -       450        0.24       0.18       430       0.27      560     0.36      0.18      0.38      480      0.22       240
  300            -           -        -       -         -       500        0.22       0.14       500       0.25      660     0.33      0.14      0.35      570      0.19       300
  400            -           -        -       -         -       680        0.20       0.12       610       0.24      800     0.30      0.12      0.33      660      0.17       400
  500            -           -        -       -         -       800        0.18       0.86       710       0.23      910     0.24      0.086     0.31      770      0.16       500
  630            -           -        -       -         -       910        0.17       0.068      820       0.22     1040     0.26      0.068     0.30      880      0.15       630
*Total volt drop between the consumer’s terminals and any other points in the installation must not exceed 2.5%of the nominal voltage.
                                                                                 Page 86 of 173
      ** The range ratings in columns 2 and 5 relate to cables in metal or on -metal conduit and trunking. For cables in underground pipes and ducts
see Item 4(vi) of the preface to the Tables.
                                                                  Page 87 of 173
                                                 Rating factors
                                    For class of excess-current protection
       Where coarse excess-current protection is afforded the tabulated ratings must be multiplied by 0.75
                                For Ambient temperature
Ambient temperature                           25oc    35oc      40oc          45oc     50oc          55oc      60oc             65oc
                                                      For groups
For groups of circuits unenclosed, the single-current ratings apply provided that–
    (1) The horizontal clearance between circuits is–
             (a) not less than six times the overall diameter of an individual cable; and
             (b) not less than the overall width of an individual circuit except that the horizontal clearance
                 need not in any case exceed 150mm; and
    (2) the vertical clearance between circuits is not less than 150mm; and
    (3) if the number of circuits exceeds four they are installed in a horizontal plane.
In all cases, unless a more precise evaluation of current rating has been made on experimental work or
calculated data, the following factors are applicable–
                               No. of circuits (pairs of cables single-phase a.c or d.c)
                                                        Page 88 of 173
                                                                         TABLE 17
                                               P.V.C. non-armoured single core (1.0mm2 to 35mm2) (Copper)
                   Single-circuit current rating and associated volt drops for twin and multicore p.v.c. insulated and sheathed cables
              The ratings tabulated apply where the cable is provided with coarse excess-current protection (see item 2(b) of the preface)
                                            For coarse excess-current protection, the rating factor given below
     Conductor            Enclosed in conduit or trunking        Clipped direct to a surface or on a cable              Defined conditions
                                                                          tray, and unenclosed
                      One twin cable,     One      three-core   One twin cable, One              three-core   One twin cable,     One      three-core
                      with or without     cable, with or        with or without cable, with or                with or without     cable, with or
                      earth-continuity    without       earth   earth-continuity       without        earth   earth-continuity    without       earth
                      conductor single-   continuity or one     conductor single- continuity or one           conductor single-   continuity or one
Nomina     No. and    phase a.c or d.c    four-core    cable,   phase a.c or d.c       four-core     cable,   phase a.c or d.c    four-core    cable,
                                                                                                                                                         Conductor
l cross-   dia(mm)                        three-phase                                  three-phase                                three-phase
section    of wires   Current   Volt      Current Volt          Current Volt           Current Volt           Current   Volt      Current     Volt
al area    nominal    rating    drop      rating     drop       rating     drop        rating      drop       rating    drop      rating      drop
                                per                  per                   per                     per                  per                   per
                                ampere               ampere                ampere                  ampere               amper                 amper
                                per                  per                   per                     per                  e per                 e per
                                metre                metre                 metre                   metre                metre                 metre
   1          2          3          4         5          6          7          8           9          10         11       12          13         14            15
 mm2                    A         mV          A        mV           A         mV           A         mV          A        mV          A         mV            mm2
 1.0        1/1.13      11         40         9         35         12         40          10          35          -        -           -          -     1.0
 1.5        1/1.36      13         27        12         23         15         27          13          23          -        -           -          -     1.5
                                                                                                                                                               Flat
 2.5        1/1.78      18         16        16         14         21         16          18          14          -        -           -          -     2.5    cables
   4        7/0.85      24         10        22        8.8         27         10          24          8.8         -        -           -          -     4      only
   6        7/1.04      30        6.8        27        5.9         35         6.8         30          5.9         -        -           -          -     6
  10        7/1.35      40        4.0        37        3.5         48         4.0         41          3.5         -        -           -          -     10
  16        7/1.70      63        2.6        47        2.2         64         2.6         54          2.2         -        -           -          -     16
  25        7/2.14      60        1.7        53        1.5         71         1.7         62          1.5        86       1.7         72        1.5     25   Circul
  35        19/1.53     74        1.2*       65        1.0         87         1.2         72          1.0       105       1.2         92        1.0     35   ar
                                                                                                                                                             cable
    *Total volt drop between the consumer’s terminals and any other point in the installation must not exceed 2.5% of nominal                           voltage.
                                                                                                                                                             s
                                                                   Rating factors
                                                      For class of excess-current protection
The ratings tabulated may be multiplied by 1.33 where close excess-current protection can be assured
                                                            For ambient temperature
                                                                  Page 89 of 173
             Ambient temperature                                                    250C      350C     400C      450C       500C          550C          600C      650C
             Rating factor for cables having coarse excess-current protection
             …………………                                                                  1.02      0.97     0.94      0.91       0.88          0.77          0.63      0.44
             Rating factor for cables having close excess-current protection        1.06      0.94     0.87      0.79       0.71          0.61          0.5       0.35
                                                                        For groups
For groups of circuit unenclosed, the single-current ratings apply provided that–
        (1) The horizontal clearance between circuits is not less than six times the overall diameter of an individual cable; and
        (2) The vertical clearance between circuits is not less than 150mm; and
        (3) If the number of circuits exceeds four they are installed in a horizontal plane.
        In all other cases, unless a more precise evaluation of current rating has been made based on experimental work or calculated data, the
following factors are applicable–
                                                                                    Page 90 of 173
                                                     TABLE 18
                                        P.V.C. armoured (1.5mm2 to 35mm2)
            Single-circuit rating associated volt drops for twin and multicore p.v.c.-insulated cables
                                      (copper conductors) (1.5mm2 to 35mm2)
         The ratings tabulated apply where the cable is provided with coarse excess-current protection
                               For close excess-current protection, see rating below
 Nominal        Clipped direct to a surface or on a cable tray                        Defined conditions                      conductor
   cross-                 bunched and unenclosed
 sectional   One twin cable, single-     One three or four-core      One twin cable, single-        One three or four-core
  area of        phase a.c or d.c           cable, three-phase           phase a.c or d.c             cable, three-phase
conductor     Current      Volt drop      Current       Volt drop     Current      Volt drop        Current       Volt drop
               rating         per          rating          per         rating         per            rating          per
                            ampere                       ampere                     ampere                         ampere
                              per                      per metre                  per metre                      per metre
                            metre*
    1             2             3             4             5           6               7               8             9          10
  mm2            A            mV              A           mV            A              mV              A             mV         mm2
  1.5            14            28            13            24            -              -               -             -         1.5
  2.5            20            17            17            15            -              -               -             -         2.5
    4            26            11            22            9.1           -              -               -             -           4
    6            32            7.0           28            6.0          38             7.0             32            6.0          6
   10            45            4.1           38            3.6          52             4.1             44            3.6         10
   16            58            2.6           50            2.2          68             2.6             58            2.2         16
   25            76            17            66            1.5          91             1.7             77            1.5         25
   35            92            1.2           80            1.0         112             1.2             94            1.0         35
       * Total volt drop between the consumer’s terminals and any other point in the installation must not
exceed 2.5% of the nominal voltage
                                                   For groups
For groups of cables unenclosed, the single-circuit ratings apply provided–
    (1) The horizontal clearance between cables is not less than six times the overall diameter of an
individual cable except that the horizontal clearance need not in any case exceed 150mm; and
    (2) The vertical clearance between cables is not less than 150mm; and
                                                 Page 91 of 173
   (3) If the number of cables exceeds four they are installed in a horizontal plane.
   In all other cases, unless a more precise evaluation of current rating has been made based on
experimental work or calculated data, the following factors are applicable–
    No. cables             2        3        4        5       6       8         10         12       14       16        18         20
    Rating factor………        0.80     0.70     0.65     0.62    0.57    0.52      0.48       0.45     0.43     0.41      0.39       0.38
                                                     TABLE 19
                                   P.V.C. armoured (50mm2 to 400mm2) (Copper)
     Single-circuit current ratings and associated volt drops for twin and multicore armoured p.v.c-insulated
                                                     cables
                                                (50mm2 to 400mm2)
           The ratings tabulated apply where the cable is provided with close excess-current protection
                     For coarse excess-current protection, rating factor below must be applied
 Nominal       Clipped direct to a surface or on a cable, tray                       Defined conditions                        conductor
   cross-                bunched and or trunking
 sectional     One twin cable, single-       One three-or four-    One twin cable, single-          One three-or four-
  area of          phase a.c or d.c          core cable, three-       phase a.c or d.c              core cable, three-
conductor                                           phase                                                  phase
             Curren     Volt drop per       Current       Volt    Curren      Volt drop per        Current       Volt
                t         ampere per         rating    drop per      t         ampere per           rating     drop per
             rating         metre*                      ampere    rating         metre*                        ampere
                                                          per                                                     per
                                                        metre*                                                  metre*
                         a.c.       d.c.                                      a.c.       d.c.
     1         2          3          4          5           6       7          8          9          10          11               12
   mm2         A         mV         mV          A         mV        A         mV         mV          A          mV               mm2
    50        150       0.92        0.92       123        0.81     180        0.92       0.92       155         0.81              50
    70        180       0.65        0.64       155        0.57     220        0.65       0.64       190         0.57              70
    95        225       0.46        0.46       190        0.42     270        0.48       0.46       230         0.42              95
   120        260       0.40        0.36       220        0.34     310        0.40       0.36       270         0.34             120
   150        290       0.32        0.25       250        0.39     355        0.32       0.25       310         0.29             150
   185        340       0.29        0.23       290        0.24     410        0.29       0.23       350         0.24             185
   240        400       0.25        0.18       350        0.20     485        0.25       0.18       420         0.20             240
   300        460       0.23        0.14      4000        0.18     550        0.23       0.14       475         0.18             300
   400        520       0.22        0.11       460        0.17     620        0.22       0.11       550         0.17             400
*Total volt drop between the consumer’s terminals and any other point in the installation must not exceed
2.5% of the nominal voltage.
                                                   For groups
For groups of cables unenclosed, the single-circuit ratings apply provided that–
    (1) The horizontal clearance between cables is not less than six times the overall diameter of an
individual cable except that the horizontal clearance need not in any case exceed 150mm; and
    (2) The vertical clearance between cables is not less than 150mm; and
    (3) If the number of cables exceeds four they are installed in a horizontal plane. In all other cases, unless
a more precise evaluation of current rating has been made based on experimental work or calculated data,
the following factors are applicable–
                                                        Page 92 of 173
No. cables         2       3       4       5       6       8       10      12      14      16      18      20
Rating factor………    0.80    0.70    0.65    0.60    0.57    0.52    0.48    0.45    0.43    0.41    0.39    0.38
                                               Page 93 of 173
                                                                            TABLE 20
                                                         Paper, single-core, lend-sheathed (Copper)
         Single-circuit current ratings and associated volt drops for single-core cables insulated with impregnated paper, lead-sheathed, with p.v.c
                                                       oversheath, non-armoured (copper conductors)
                          The ratings tabulated apply whatever may be the class of excess-current protection provided for the cables
 Nominal         Clipped direct to a surface or on a cable tray, bunched and or                                          Defined conditions                                    Conductor
   cross-                                   trunking
 sectional     2 cable single-phase a.c or d.c        3 or 4 cabled three-phase a.c        2 cable, flat or vertical,      3 or 4 cables, flat or      3 cables, in trefoil,
  area of                                                                                      single-phase a.c         vertical, three-phase a.c        three-phase a.c
conductor     Current     Volt drop per ampere      Current rating    Volt drop per     Current       Volt drop per     Current      Volt drop per   Current      Volt drop
               rating          per metre*                              ampere per        rating        ampere per        rating       ampere per      rating     per ampere
                                                                         metre                            metre                         metre*                   per metre*
                              a.c         d.c                                                         a.c         d.c
    1             2            3           4              5                6                7          8           9       10            11             12           13            14
  mm2             A          mV          mV               A               mV                A         mV         mV        A            mV              A           mV           mm2
    50           190         0.93        0.93            180              0.82            230        0.94        0.93     220           0.84           205          0.81           50
    70           240         0.64        0.64            230              0.61            290        0.68        0.64     280           0.61           255          0.58           70
    95           300         0.48        0.47            285              0.48            355        0.58        0.47     345           0.47           315          0.43           95
   120           350         0.40        0.37            340              0.39            415        0.48        0.37     405           0.41           370          0.35          120
   150           405         0.33        0.30            390              0.35            470        0.42        0.30     460           0.38           420          0.30          150
   185           470         0.29        0.24            450              0.31            550        0.36        0.24     535           0.35           485          0.26          185
   240           580         0.25        0.18            575              0.28            675        0.38        0.18     670           0.38           580          0.22          240
   300           670         0.22        0.14            660              0.26            770        0.36        0.14     760           0.32           670          0.20          300
   400           775         0.20        0.11            765              0.23            890        0.31        0.11     870           0.30           775          0.18          400
   500           895         0.18        0.09            870              0.21            1000       0.29        0.09     975           0.28           885          0.17          500
   630          1030         0.17        0.07            990              0.18            1150       0.27        0.07    1100           0.26          1020          0.16          630
   800          1160         0.16        0.05           1100              0.17            1290       0.26        0.05    1220           0.24          1150          0.15          800
  1000          1280         0.16        0.04           1190              0.15            1420       0.25        0.04    1330           0.22          1270          0.15         1000
                                                                                      Page 94 of 173
*Total volt drop between the consumer’s terminals and any other point in the installation must not exceed
2.5% of the nominal voltage.
                                            Rating factors
                                       For ambient temperature
   Ambient temperature             25oC       35oC     40oC      45oC         50oC          55oC        60oC     60oC       70oC        75oC
   Rating factor                   1.05       0.95     0.89      0.82         0.75          0.68        0.61     0.53       0.43        0.3
                                           For groups
For groups of cables unenclosed, the single-circuit ratings apply provided that -
    (1) The horizontal clearance between cables is -
        (a) not less than six times the overall diameter of an individual cable except that the horizontal
             clearance need not in any case exceed 150mm; and
        (b) not less than the overall width of an individual circuit, except that the horizontal clearance need
             not in any case exceed 150mm; and
    (2) The vertical clearance between cables is not less than 150mm; and
    (3) If the number of cables exceeds four they are installed in a horizontal plane.
    In all other cases, unless more precise evaluation of current rating has been made based on experimental
work or calculated data, the following factors are applicable–
                                                               Page 95 of 173
                                                    TABLE 21
                       Paper, twin and multicore, lend-sheathed or aluminium-sheathed
  Single-circuit current and associated volt drops for twin and multicore cables insulated with impregnated
 paper, lead-sheathed or aluminum-sheathed, armoured, or non-armoured with or without serving (copper
                                                  conductors)
 The ratings tabulated apply whatever may be the class of excess-current protection provided for the cables
  Nominal       Clipped direct to a surface or on a cable tray, and      Defined conditions see item 3 of preface to tables          conduc
    cross-                          unenclosed                                                                                         tor
  sectional       One twin cable, single-       One three-or four-      One twin cable, single-phase            One three or four
   area of            phase a.c or d.c           core cable, three-              a.c or d.c                     core cable, three-
 conductor                                             phase                                                          phase
                Current      Volt drop per     Current Volt drop        Current        Volt drop per          Current Volt drop
                 rating       ampere per        rating        per        rating         ampere per             rating        per
                                metre*                     ampere                         metre*                          ampere
                                                              per                                                            per
                                                            metre*                                                        metre*
                            a.c.3       d.c
     1              2                    4         5           6           7           8            9           10          11         12
   mm2              A        mV        mV          A          mV           A          mV           mV           A          mV         mm2
    50            165       0.95       0.95       145         0.82        200         0.95         0.95        170         0.82        50
    70            205       0.66       0.66       180         0.58        250         0.66         0.66        215         0.58        70
    95            255       0.49       0.47       225         0.43        305         0.49         0.47        265         0.43        95
   120            295       0.40       0.36       260         0.35        355         0.40         0.36        305         0.35       120
   150            335       0.33       0.30       300         0.28        405         0.33         0.30        350         0.28       150
   185            390       0.28       0.24       345         0.24        465         0.28         0.24        405         0.24       185
   240            460       0.24       0.19       410         0.20        555         0.24         0.19        480         0.20       240
   300            525       0.21       0.15       470         0.18        635         0.21         0.15        550         0.18       300
   400            610       0.20       0.12       545         0.17        735         0.20         0.12        640         0.17       400
       *Total volt drop between the consumer’s terminals and any other point in the installation must not
exceed 2.5% of the nominal voltage.
       **Stranded or solid conductors
                                                Rating factors
                                          For ambient temperature
Ambient temperature               25oC       35oC     40oC       45oC          50oC        55oC        60oC       60oC      70oC      75oC
Rating factor                     1.05       0.95     0.89       0.82          0.75        0.68        0.61       0.53      0.43      0.3
                                                   For groups
For groups of cables unenclosed, the single-circuit ratings apply provided that–
    (1) The horizontal clearance between cables is not less than six times the overall diameter of an
individual cable except that the horizontal clearance need not in any case exceed 150mm; and
    (2) The vertical clearance between cables is not less than 150mm; and
    (3) If the number of cables exceeds four they are installed in a horizontal
    In all other cases, unless a more precise evaluation of current rating has been made based on
    experimental work or calculated data, the following factors are applicable–
   No. cables                 2          3     4        5        6         8          10          12      14         16     18       20
                                                            Page 96 of 173
Rating factor………….   0.80   0.70   0.65   0.60   0.57   0.52   0.48   0.45   0.43   0.41   0.39   0.38
                                           Page 97 of 173
                                                                         TABLE 22
                                           Light duty mineral, exposed to touch or p.v.c covered (Copper)
   Current ratings and associated volt drops for light-duty mineral insulated cables (copper conductors and sheath) exposed to touch or having an
                                                               overall covering of p.v.c.
                     The ratings tabulated apply whenever may be the class of excess-current protection provided for the cables
 Nominal     Two single-core cables,     Three or four single-   One twin cable, single-   One three-core cable,    One four core cable,   One seven-core cable, all cores fully
   cross-    single-phase a.c or d.c      core cables, three-       phase a.c or d.c         three-phase a.c          three-phase a.c                   loaded
 sectional                                    phase a.c
  area of     Current     Volt drop    Current      Volt drop    Current     Volt drop     Current    Volt drop    Current     Volt drop   Current      Volt drop per ampere
conductor      rating        per       rating       per          rating      per           rating     per          rating      per         rating       per metre*
                           ampere                   ampere                   ampere                   ampere                   ampere                    1-phase      3-phase
                             per                    per                      per                      per                      per                      a.c or d.c      a.c
                           metre*                   metre*                   metre*                   metre*                   metre*
    1           2             3             4             5         6             7            8           9          10           11         12           13            14
  mm2           A           mV              A            mV         A            mV           A           mV          A            mV         A            mV            mV
   10           22           42            18            36         17           42           14          36          15           36         10           42            36
  1.5           27           28            23            24         22           28           18          24          19           24         13           28            24
  2.5           36           17            31            14         29           17           24          14          25           14         17           17            14
    4           46           10            41            9.0        38           10           32          9.0         33           9.0         -            -             -
    6           59           6.9           52            6.0        49           6.9           -           -           -            -          -            -             -
   10           80           4.2           70            3.6         -            -            -           -           -            -          -            -             -
*Total volt drop between the consumer’s terminals and any other point in the installation must not exceed 2.5% of the nominal voltage.
                                                                                Page 98 of 173
                                                            Rating factors
                                                       For ambient temperature
        Ambient temperature                                                              25oC       30oC    40oC        50oC      60oC
        Rating factor for cables exposed to touch………                                     1.06       1.0     0.85        0.68      0.31
        Rating factor for cables having overall p.v.c covering                           1.16       1.1     0.91        0.75      0.51
                                                                 Page 99 of 173
                                                                          Table 23
                                              Heavy duty mineral, exposed to touch or p.v.c covered (Copper)
  Current ratings and associated volt drops for heavy duty mineral-insulated cables (copper conductors and sheath) exposed to touch or having an overall
                                                                      covering of p.v.c
                        The ratings tabulated apply whatever may be the class of excess-current protection provided for the cables
Nominal      Two single-core cables,   Three or four single-     One twin cable, single-   One three-core cable,    One four core cable,     One seven-core cable, all cores fully
cross-       single-phase a.c or d.c   core cables, three-       phase a.c or d.c          three-phase a.c          three-phase a.c          loaded
sectional                              phase a.c
area of      Current      Volt drop    Current       Volt drop   Current      Volt drop    Current      Volt drop   Current      Volt drop   Current       Volt drop per ampere
conductor    rating       per          rating        per         rating       per          rating       per         rating       per         rating        per metre*
                          ampere                     ampere                   ampere                    ampere                   ampere                    1-phase      3-phase
                          per                        per                      per                       per                      per                       a.c or d.c   a.c
                          metre*                     metre*                   metre*                    metre*                   metre*
     1           2             3             4            5          6             7           8             9          10           11          12           13            14
       2
   mm            A            mV            A            mV          A            mV           A            mV          A            mV          A            mV            mV
   1.0           23           42            20           36          19           42           16           36          16           36          11           42            36
   1.5           29           28            26           24          24           28           20           24          20           24          14           28            24
   2.5           39           17            34           14          32           17           26           14          27           14          19           17            14
     4           50           10            44           9.0         41           10           34           9.0         35           9.0         24           10            9.0
     6           63           6.9           56           6.0         53           6.9          44           6.0         45           6.0          -            -             -
    10           85           4.2           75           3.6         71           4.2          59           3.6         61           3.6          -            -             -
    16          110           2.6           99           2.3         94           2.6          78           2.3         81           2.3          -            -             -
    25          150           1.7          130           1.4        124           1.7         105           1.4        110           1.4          -            -             -
    35          180           1.2          160           1.0          -            -            -            -           -            -           -            -             -
    50          225          0.83          200          0.72          -            -            -            -           -            -           -            -             -
    70          275          0.59          240          0.51          -            -            -            -           -            -           -            -             -
    95          330          0.44          290          0.38          -            -            -            -           -            -           -            -             -
   120          380          0.35          335          0.30          -            -            -            -           -            -           -            -             -
   150          440          0.28          385          0.24          -            -            -            -           -            -           -            -             -
*Total volt drop between the consumer’s terminals and any other point in the installation must not exceed 2.5% of the nominal voltage.
*Total volt drop between consumer’s terminals and any other point in the installation must not exceed 2.5%
of the nominal voltage.
  NOTE–the tabulated ratings are not applicable to flexible cables wound on drums. The current rating of a
cable on a drum depends upon the type of drum and may be less than one half of the corresponding rating
stated in the table.
                                                    Rating factors
                                               For ambient temperature
              Ambient temperature               250C         350C         400C         450C         500C         550C
              Rating factor                     1.04         0.91         0.82         0.71         0.57         0.41
TABLE 27
*Total volt drop between consumer’s terminals and any other point in the installation must not exceed 2.5%
of the nominal voltage.
                                                    Rating factors
                                                0
                                             60 C rubber and p.v.c. cords
                                              For ambient temperature
        Ambient temperature                                      350C           400C      450C         500C         550C
        Rating factor                                            0.96           0.92      0.87         0.71         0.50
                                                                        For groups
For groups of cables unenclosed, the single-circuit ratings apply, provided that–
     1. The horizontal clearance between cables is–
        (a) Not less than six times the overall diameter of an individual cable, and
        (b) Not less than the overall width of an individual circuit, except that the horizontal clearance need not in any case exceed 150mm, and
The vertical clearance between cables is not less than 150mm; and
If the number of cables exceeds four they are installed in a horizontal plane. In all other cases, unless a more precise evaluation of current rating
has been made based on experimental work or calculated data the following factors are applicable–
    No. of circuits (pairs of cables, single phase a.c or d.c 3 cables per    2            3    4      5          6    8     10          12      14     16**     18**     20**
    circuit or 4 where one is the neutral, 3 phase a.c)
    Rating factor                                                            0.80      0.69    0.62   0.59    0.55    0.51   0.48        0.43    0.41   0.39     0.38     0.36
                                                        TABLE 31
                    Paper, twin and multicore, lead-sheathed or aluminium-sheathed (aluminium)
         Single-circuit current ratings and associated volt drops for twin and multicore cables insulated with
       impregnated paper, lead-sheathed or aluminium-sheathed, armoured or non-armoured, with or without
                                            serving (aluminium conductors)
      The ratings tabulated apply whatever may be the class of excess-current protection provided for the cables
Nominal         Clipped direct to a surface or on a cable tray, bunched     Defined conditions                                        Conductor
cross-          and or trunking
sectional       One twin cable, single-phase       One three-or four-       One twin cable, single-       One three-or four-
area of         a.c or d.c                         core cable three-        phase a.c or d.c              core cable three-
conductor                                          phase                                                  phase
                Current     Volt drop per          Current Volt drop        Current     Volt drop per     Current Volt drop
                rating      ampere per             rating     per           rating      ampere per        rating     per
                            metre*                            ampere                    metre*                       ampere
                            a.c.       d.c.                   per                       a.c.     d.c.                per
                                                              metre*                                                 metre*
     1              2           3         4            5           6           7         8          9        10          11               12
   mm2              A         mV         mV           A           mV           A        mV         mV         A          mV              mm2
    50             125        1.6        1.6         115          1.3         145       1.6        1.6      130          1.3              50
    70             165        1.1        1.1         140         0.95         195       1.1        1.1      160         0.95              70
    95             205       0.81        0.79        170         0.70         240       0.81       0.79     200         0.70              95
   120             235       0.64        0.63        200         0.55         275       0.64       0.63     230         0.55             120
                                                               Page 110 of 173
150          265          0.53     0.53        225           0.46        315          0.53      0.51           265            0.46          150
185          310          0.44     0.41        245           0.38        365          0.44      0.41           305            0.38          185
240          370          0.36     0.31        290           0.31        435          0.36      0.31           365            0.31          240
300          425          0.30     0.25        335           0.26        500          0.30      0.25           420            0.26          300
400          495          0.26     0.19        435           0.22        585          0.26      0.19           510            0.22          400
*Total voltage drop between the consumer’s terminals and any other point in the installation must not
exceed 2.5% of the nominal voltage.
                                                  Rating factors
                                             For ambient temperature
                                      0
   Ambient temperature             25 C     350C 400C 450C 500C 550C 600C 650C 700C 750C
   Rating factor                   1.05     0.95 0.89 0.82 0.75 0.68 0.61 0.53 0.43 0.30
                                                    For groups
For groups of cables unenclosed, the single-circuit ratings apply, provided that–
    (1) The horizontal clearance between cables is not less than six times the overall diameter of an
         individual cable, except that the horizontal clearance need not in any case exceed 150mm; and
    (2) The vertical clearance between cables is not less than 150mm; and
    (3) If the number of cables exceeds four they are installed in a horizontal plane.
In all other cases, unless a more precise evaluation of current rating has been made based on experimental
work or calculated data, the following factors are applicable–
  No. of cables                    2        3         4       5        6        8        10          12        14       16         18     20
  Rating factor                   0.80     0.70      0.65    0.60     0.57     0.52     0.48        0.45      0.43     0.41       0.39   0.38
                                                    TABLE 32
                                  Bare circular aluminium conductors (risers)
    Single-circuit current ratings and associated volt drops for bare or lightly-insulated solid aluminium
conductors or circular cross-section installed in vertical trunking with a spacing of 75mm between conductors
                NOTE. – Table 32 does not apply to busbars and connections of switchboards
Conductor                        2 conductors d.c            2 conductors, single-phase a.c                3 or 4 conductors, three-phase a.c.
Diameter      Approximate        Current       Voltage       Current       Voltage drop per ampere         Current       Voltage drop per ampere
              cross-sectional    rating        drop per      rating        per metre*                      rating        per metre*
              area                             ampere                      p.f.=1.0      p.f.=0.7                        p.f.=1.0      p.f.=0.7
                                               per
                                               metre*
     1                2               3             4            5             6               7               8             9            10
   mm               mm2               A            mV            A           mV              mV                A           mV            mV
    10               79              205          0.98          205          0.98            0.96             205          0.84          0.85
   12.5             120              275          0.63          275          0.63            0.70             275          0.55          0.63
    16              200              385          0.38          385          0.38            0.58             385          0.33          0.46
    20              315              520          0.24          520          0.25            0.40             520          0.22          0.36
    25              490              710          0.16          700          0.16            0.32             700          0.14          0.30
  *Total volt drop between the consumer’s terminals and any other point in the installation must not
exceed 2.5% of the nominal voltage.
                                               Rating factors
  For conductors connected to rubber- or p.v.c.-insulated cables–
       (a) Current rating factor: 0.9
       (b) Volt drop rating factor–
                                                            Page 111 of 173
 I.   0.97 for d.c conductors and a.c. conductors with p.f. = 1.0
II.   0.98 for a.c conductors with p.f. = 0.7 (mean value)
                                                       TABLE 35
                                    Rating factor for cables in enclosed trenches
                                                  PART 1
    Regulations describing the conditions on which licenses may be issued and the fees payable thereon
    3. System of supply
    4. Standard types of supply
    5. Voltage supply
    6. Location o0f power and communications overhead lines
    7. Conditions of supply
                                                   PART II
                          Regulations governing licensee who is a supply authority
    8. Application before commencing work
    9. Minister’s approval
    10. Notice of completion
    11. Obligation to supply
    12. Continuity o0f supply
    13. Record to be kept
    14. Extension and alteration
    15. Maintenance
    16. Safety precaution
    17. Subsequent inspection
    18. Standards of materials, design and construction
    19. Fees
    20. Assignment
    21. Decision of Minister
                                                   PART III
                Regulations prescribing the issue of private license and governing a licensee
    22. Application
    23. Application for licence
    24. Minister may require additional information
    25. Term of licence
    26. Amendment of licence
                                               PART IV
                            Regulations appertaining to electrical apparatus
  36. Minister’s approval.
  37. Standard of design.
  38. Safety.
  39. Maintenance.
  40. Repo0rt of accidents, interruptions and breakages.
  41. License fees.
                                                  PART V
Safety Regulations for supplies and uses of electrical energy and equipment as affecting new installations
  42. Conditions of direct -current supply with earth return.
  43. System earthing.
  44. Star-connected systems with earthed neutral.
  Delta-connected systems or star-connected systems with isolated neutrals
                                                PART VI
    Regulations appertaining to overhead lines and restriction to placing electric lines above ground
  45. Overhead lines.
  46. Support.
  47. Load on support.
  48. Foundation.
  49. Materials.
  50. Minimum size.
  51. Insulation.
  52. Factors of Safety.
  53. Temperature and pressure.
  54. Wind pressure.
  55. Spacing of electric lines.
  56. Dual voltage construction.
  57. Parallel spacing of electric lines.
  58. Mid-span crossing of electric lines.
  59. Clearance of electric lines to buildings.
  60. Alternate provision.
                                           PART VIII
               Regulation appertaining to sub-stations and switching stations
104.   Substations
105.   Automatic protection and isolation of circuit
106.   General conditions as to transformation and control
107.   Further constructional detail in certain cases
108.   Precautions against risk of fire
109.   Provision for faults between transformer windings
                                            PART IX
                Regulation appertaining to sub-stations and switching stations
110.   Switchboards.
111.   Connection with earth.
112.   Power station.
113.   Clearances to bare conductors in open spaces.
114.   Horizontal clearance in passage ways.
115.   Clearance to bare metal in screened spaces.
116.   Power houses and substations enclosures.
117.   Notice on electric shock treatment.
118.   Electric lines and apparatus for high voltage completion and control.
119.   Insulation resistance test.
120.   Electric lines to be metal-sheathed: precaution against excess leakage.
121.   Connection with earth of high voltage systems.
                                            PART X
           Electric lines and apparatus generally other than consumer installations
122.   Standard of construction of electric lines.
123.   Precaution against excess energy.
124.   Precaution against shock and fire.
125.   Protection from lightening.
126.   Precaution against metal work becoming electrically charged.
127.   Overhead lines
128.   Bituminous, etc insulation or protection
129.   Receptacles for electric lines and apparatus
130.   Underground shaft, etc
131.   Precautions against failure of supply.
132.   Precaution against for telegraph lines.
                                                     PART XI
                                  Supply to premises of consumers installations
    136.        Service lines into consumer, s premises.
    137.        Identification of conductors of service lines.
    138.        Protection of consumer’s installation against excess energy.
    139.        Licensee’s lines, etc on consumer’s premises.
    140.        Inspection and test of consumer’s installation prior to connection: license to appoint
        installation inspectors.
    141.        General conditions as to supply to consumers.
    142.        Supply at low voltage from more than one pairs of conductors of system at medium voltage.
    143.        Supply at medium voltages.
    144.        Supply at high voltage.
   146. Supply for luminous tube sign on outside of premises.
   147. Disconnection of supply in certain circumstances.
   148. Notices by licensee to consumers where connection is declined or it is intended to disconnect
supply.
                                                 PART XII
                                                 Meters
     149. Meters to be tested for accuracy.
     150. Testing station to be established.
     151. Appointment of competent person to have a charge of meter testing station.
     152. Records to be kept by competent person.
     153. Meters to be subject to periodical testing.
     154. Meters to be marked with date of testing.
     155. Inaccurate meters.
     156. Precautions in transporting meters.
                                                  PART XIII
                                  Prescribed tests and accuracy of meters
     157. Prescribed tests and accuracy meters
     158. High voltage tests.
                                                PART IV
           Conditions of supply to consumers where distribution mains of adequate capacity exist
     159. Person entitled to demand a supply
     160. Where no distribution mains exist.
                                            PART XVI
                        Penalties for breaches of licenses and regulations
 164. Penalties.
 165. Revocation.
                                           SCHEDULES
                                            SECHEDULE 1
         Application for Electricity Private License under Electricity Act Cap.E7, Part 111
                                          SECHEDULE 2
                                Application for Electricity License
                                                   PART I
     Regulations describing the conditions on which licenses may be issued and the fees payable thereon
3.   Systems of supply
     The following system standards shall apply–
          i.   frequency – The frequency of alternating current systems shall be 50 hertz
     (2) Standard A.C. voltages – shall be 230 volts between phase conductor and neutral conductor and
400; 3,300; 6,600; 11,000; 33,000, 66,000; 132,000 and 333,000, 750,000 volts between any two-phase
conductors of three-phase system.
4.   Standard types of supply
     (1) Two-wire system (whether direct current or single-phase alternating) at a normal voltage not
exceeding 230 volts at the consumer’s main switchboard subject to regulation 4(6).
                                                       PART II
                             Regulations governing licensee who is a supply authority
8. Application before commencing work
    (1) Before commencing any works–
             (a) application shall be made in writing to the Minister;
             (b) application shall be accompanied by plans showing the location of the lines to a scale not less
                 than 1.250,000. All locality plans shall have the north point marked thereon.
    (2) In showing the voltage of the electric lines the following colours shall be used on all plans–
             (a) Blue to indicate 330,000 volts;
             (b) Black to indicate 132,000 volts;
             (c) Green to indicate 33,00 volts
             (d) Red to indicate 11,00 volts;
             (e) Yellow to indicate 415 volts.
9. Minister’s approval
    (1) Approval must be given in writing by the Minister prior to the commencement of any new works,
other than service lines.
    (2) If the Minister’s decision is not advised to the applicant within thirty days he may appeal direct to the
Minister.
    (3) This approval will in no way relieve the applicant of these responsibilities to any local authority or
other authority affected.
10. Notice of completion
    (1) The licensee shall give at least fifty days’ notice to the Director, Electrical Inspectorate Services, of the
intention of commencing supply within a new area of supply or of the bringing into use any new works and
to request for an inspection of same.
                                                     PART III
               Regulations prescribing the issue of a private license and governing a licensee
22. Application for license
    (1) These regulations shall apply throughout the Federation of Nigeria and shall govern the grant or
assignment or extension or suspension or revocation of a license issued under the provisions of subsection
(a) of Section 4 of the Electricity Act or any Act in substitution thereof.
                                                       [Cap. E7.]
    (2) The provisions of these Regulations shall also apply to any works or installations owned and used by
the Federal Government or a State Government for the generation, supply or use of electrical energy.
23. Application for license
    (1) Every application for a license, whether for sole source of Supply or emergency supply, shall be in
writing and in the form set out in the First Schedule hereto, and shall be accompanied by the fee prescribed
by section 41 (1) of this Electricity Supply Regulation as amended from time to time and together with a
prepared plan.
                                                   [First Schedule]
    (2) In Second Schedule, the supply authority in the area concerned shall be consulted to say whether they
can undertake the functions of the said application either at all or within a reasonable time in the case of
sole source of supply whether they have any objection in the case of generating plant installed for
emergency purposes only.
                                                 [Second Schedule]
     (3) Where the application involves the placing of any works or electric lines on or across under or over,
any public place, the applicant shall furnish evidence at the time of his application that -
         (a) notice in writing shall be served on the following -
         (b) the local authority concerned; and
         (c) the Local Water Supply Authority;
         (d) the Director of Telecommunications; and
         (e) the owner of any other electrical line interested in the proposed works;
         (f) that the proposed works are not objected to or are approved subject to certain conditions being
             observed.
For the purposes of Regulation 23 (3), it shall be sufficient evidence if certified copies of any notice served
and of any counter notice received by the applicant are attached to the application.
24. Minister may require additional information
    (1) Before considering any application for a license the Minister or any officer duly authorized by him in
that behalf may by notice in writing require the applicant to furnish such additional information as he may
require.
    (2) Where an applicant fails to furnish such additional information within sixty days of service of any
written notice, the application shall be deemed to have lapsed and any fee paid shall be forfeited.
25.      Terms of license
     Licenses shall be in the form prescribed in Schedule I hereto and may be granted for a term not exceeding
twenty-five (25) years or such shorter term as the Minister may decide.
26. Amendment of licenses
                                                 PART IV
                              Regulations appertaining to electr1cal apparatus
36. Minister’s approval
Before commencing any works the approval of the Minister shall first be obtained in accordance with
regulation 9.
37. Standards of design
        (a) factors of safety shall not be less than those quoted in these Regulations;
        (b) Materials shall be suitable for the purposes and conditions for which they are to be used.
        (c) Electrical clearances shall be such as to eliminate all hazards and shall not be less than those
            quoted in these Regulations.
38. Safety
   (1) All apparatus shall be protected electrically and mechanically so as to eliminate danger to life and
property.
   (2) Apparatus shall be situated and protected in such a manner as not to constitute a hazard
   (3) Precautions shall be taken to ensure that apparatus is protected against over voltage, over current and
earth leakage conditions.
                                                     PART V
  Safety regulations for supplies and uses of electrical energy; and equipment as affecting new installations
                                                     PART VI
        Regulations appertaining to overhead lines and restriction to placing electric lines above ground
46. Overhead lines
    (1) Except under and in accordance with the terms of a written authority granted by the Minister, no
electric lines (other than service lines) shall be placed above ground and no support carrying electric lines
shall be erected unless such line or support complies with the provisions of these Regulations.
   (a) Where double circuit construction is employed all clearance shall refer to the circuit of the high
       voltage;
    Lower Circuit (Voltage between phases)               Upper Circuit (Voltage between phases)
                     Earth
                                400      3,300   6,600    11,000      33,000       66,000         132,000   330,000
                     wire
      Earth wire        30       20         30   30          30         120          60            120       240
        400V            20      120        120   120        120         120         150            180       270
       3,300V           30       ––         ––   120        120         120         150            180       270
       6,600V           30       ––         ––   120        120         120         150            180       270
       11,000V          30       ––         ––    ––        120         ––          150            180       270
       33,000V          30       ––         ––    ––         ––         ––          150            180       270
       66,000V          60       ––         ––    ––         ––         ––          150            210       300
     (d) where the circuit of the higher voltage is fully insulated the minimum clearance calculated in
          accordance with 59 (c) above may be reduced by 50%.
60. Clearance of electric lines to buildings
A line may be erected over or adjacent to a building provided that-
     (a) the radial distance in metres from the point of attachment of the suspension insulator (or conductor
          if attached to a fixed insulator) of the lower conductor, to any part of the building is not less than-
                   conductor sag at maximum design temperature plus length of suspension insulator string plus
                   A, where A is a constant dependent on the voltage between phases of the conductors of the
                   line-
                   400 volts to 11,000 volts ………………………… 2.4 metres
                   33,000 volts ……………………………………………. 3.0 metres
                   132,000 volts ................................................ 4.0 metres
                   330,000 volts ................................................ 6.0 metres
                   Over 330,000 volts ........................................ 8.0 metres
     (b) where the conductors of the circuit are fully insulated the constant "A" may be reduced by 50%.
61. Alternative provision
     (1)Where the condition of regulation 60 (a) cannot be met, the line shall be erected so that the minimum
horizontal distance in metre of the nearest conductor in still air is not less than-
          (Conductor sag at maximum design temperature plus length of suspension insulator sting) plus B,
          where "B" is a constant dependent on the voltage between phases of the conductors of the line-
                   400 volts - 11,000 volts.............................. 2.4 metres
                   33,000 volts ................................................. 3.0 metres
                   132,000 volts ……………………………………….. 4.0 metres
                   330,000 volts ………………………………………... 6.0 metres
                   Over 330,000 volts ....................................... 9.0 metres
     (2) Where the conductors of the circuit are fully insulated the constant "B" may be reduced by 50%.
     (3) In the case of specially designed fully insulated serial cables clearance to buildings may be reduced at
the discretion of the Minister.
     (4) No building or other structure shall be erected under or adjacent to an electric line without adhering
to the provisions of these Regulations.
62. Electric line clearance to ground
    (1) The height above ground of any electric line under the most adverse operating conditions shall not,
except with the written authority of the Minister, be less than the height appropriate to the system voltage
and situations tabulated below-
        System voltage between    Over streets and roads        Along streets and roads   In positions inaccessible to
        phases                    and public open spaces        and other places          vehicular traffic not
                                  and other places of           accessible to traffic     streets or roads
                                  vehicular traffic
    (2) Fully insulated service lines operating at a voltage not exceeding 400 volts may be terminated on
buildings at a height of not less than 2.7 metres from ground level provided that the street clearance at any
point of its span is not less than 5.8 metres.
63. Electric lines crossing waterways
    (1)The height of an electric line under the most adverse conditions, above the highest recorded water
level, over harbours, rivers and waterways, shall not be less than that required by the appropriate authorities
for physical safety clearance plus a minimum electrical safety clearance of 3 metres of I metre per 78 kV or
phase to neutral voltage of the electric line, whichever the greater.
    (2) The licensee shall at least thirty days and not more than ninety days prior to the
placing of such work serve written notice on the appropriate authorities specifying the
intended use of the works, the voltage of operation and such other information that the
authorities may require him to supply.
    (3) Every notice served in conformity with regulation 63 (2) shall be accompanied by
a plan of suitable scale indicating the site of the crossing, the location of all supports,
stays, struts, switches, transformers and other apparatus intended to be used.
    (4) The authorities may within 21 days of the receipt of such a notice of intention
served under regulation 63 (2) serve a counter notice on the licensee -–
         (a) objecting to the siting of the works specifying the reason in the counter notice; and
         (b) requiring protective features to be fitted, such features to be specified in the
             counter notice.
64. Minister's decision is final
    Where mutual agreement is not reached the matter shall be referred to the Minister whose decision shall
be final.
65. Proximity to railway lines
The provision of regulations 63 (2) to 64 shall apply where the licensee intends to place an electric line, other
than a service line, in the proximity of, over or under a railway line.
66. Proximity to post and telegraphs lines
    (1) The provision of regulation 63 (2) to 64 shall apply where the licensee intends to
place an electric line, other than a service line, in the proximity of, over or under Posts
and Telegraphs line.
    (2) Other than in the case of a fully insulated services line all electric lines, except
with the written authority of the Minister, shall cross over Post and Telegraphs lines with a minimum
clearance, under the most adverse operating conditions at the point of crossing of –
    (3) So far as may be practicable the licensee shall leave one side of each street free for telegraph line and
where the street is continuous the licensee's line shall be kept to the
same side of the street for the whole distance.
    (4) Except with the permission of the Posts and Telegraphs Authorities all overhead lines shall be placed
on the opposite side of the street to that on which any telegraph lines are erected, and where the erection or
operation of the electric lines necessitates an alteration of an existing telegraph line, and such alteration is
approved by the Posts and Telegraphs Authorities, the expense of the alteration shall be borne by the
licensee; provided that where existing telegraph lines of the Posts and Telegraphs Authorities occupy both
sides-of the street that Authority shall bear the cost of putting all telegraph lines on the one side of the street
or if agreeable to the licensee, consent to an arrangement for the joint use of poles on both sides of the
street.
    (5) Where electric lines are on one side of the street and telegraph lines on the other, and service is
required to be given from either side to the other, the licensee and the Posts and Telegraphs Authorities shall
give to each other reasonable facilities as far as possible to effect supply. Where possible electric service
lines, unless fully insulated, shall pass over telegraph lines and telegraph service lines shall pass under electric
lines.
67. Proximity to airfield
The provision of regulations 63 (2) to 64 shall apply where the licensee intends to place an electric line in the
proximity of an airfield.
68. Proximity to radio or television aerial
The provision of regulations 63 (2) to 64 shall apply where the licensee intends to place an electric line, other
than a service line, in the proximity of a radio or television aerial.
69. Approval in specific instances
Notwithstanding the foregoing, where the regulation clearance are so attainable the Minister may, in specific
instances, authorize the use of reduced clearances subject to such additional safety precautions in the form
of warning notices, warning lights or crash bars, as he may deem necessary.
70. Location of electric lines
    (1) The provisions of regulation 63 (2) shall apply where the licensee proposes to erect any electric line
above or below ground and he shall serve written notice on the Town Planning Authorities, town councils and
any other Government Department, company, body or persons concerned.
    (2) The provisions of regulations 63 (2) to 64 shall apply in respect of location of electric lines in relation to
waterways.
    (3) The provisions of regulations 63 (2) to 64 and 77 shall apply in respect of the location of electric lines in
relation to railway lines.
    (4) The provisions of regulation 67 shall apply in respect of the location of electric lines in relation to Posts
and Telegraphs lines.
                                                  PART VII
                        Regulations appertaining to substations and switching stations
102. Provisions
    (1) Where energy at high voltage is transformed, converted, regulated or otherwise controlled in
substations or switch stations, the following provisions shall have effect–
     (a) outdoor substations and outdoor switch stations (unless the apparatus is completely enclosed in a
         metal casing connected with earth, the said apparatus also being connected with the system by
         suitable electric cables) shall be efficiently protected by fencing not less than 2.5 metres in height or
         other means so as to prevent access to the electric lines and apparatus therein by any unauthorized
         person. The said fencing, if of metal shall be earthed separately from the sub- station earth. All
         metallic gates shall be effectively bonded to the fencing;
     (b) the works of the licensee shall be labeled with an appropriate danger notice, with the name of the
         licensee and with the address, and telephone number, of their local office at which an officer or
         servant of the licensee will be in attendance:
     (c) any metal work accessible from the ground level which normally has to be handled when the line is
         alive, (i.e. a switch operating handle), shall be connected to an earth mat, so situated as to include
         within its area the whole of the ground on which the operator would normally stand;
     (d) suitable provision shall be made, either by connecting with earth a point of the system at the lower
         voltage or otherwise, to guard against danger by reason of the said system becoming accidentally
         charged above its normal voltage by leakage from or contact with the system at the higher voltage.
103. Substations situated inside building
    (2)
         (a) Where a substation or switch station is situated in any building so that a fire in the substation or
             switch station might involve risk to the said building and the said sub- station or switch station
             contains oil-immersed transformers or switches involving the use of oil in a tank receptacle or
             chamber, provision shall be made for the draining away or removal of any oil which may leak or
             escape from the tanks, receptacles or chambers containing the same; special precautions shall be
             taken to prevent the spread of any fire resulting from the ignition of the oil from any cause; and
             adequate provision shall be made for the extinguishing of any fire which may occur.
         (b) Spare oil shall not be stored in any such substation or switch station.
104. Protection
All transformers shall be protected by primary fuses or overload circuit-breakers fitted adjacent to the
transformers.
                                                 PART VIII
                             Transformation and control of energy at high voltage
105. Substations
   Substations to be supplied at high voltage shall be established in suitable places and shall be in the sole
occupation and control of the licensee. In the case of any substation established on the premises of a
consumer, arrangements shall be made in conformity with the proviso to regulation 107 for that particular
                                                      PART X
                     Electric lines and apparatus generally other than consumer installation
123. Standard of construction of electric lines
    The standard of construction of electric line of the license shall unless otherwise allowed by the director
of electrical inspectorate services, be at least that prescribed in the appropriate Nigeria industrial standard
current at the time of their manufacture.
124. Protection against excess energy
    Every circuit of the licensee (other service line from distribution mains) shall be protected against excess
energy by a suitable fusible cut-out or automatic circuit breaker of adequate breaking capacity, fusible cut-
outs or automatic circuit breakers shall not be inserted in any conductors permanently connected with earth.
125. Precautions against shock and fire
                                                     PART XI
                                   Supply to premises of consumers installations
137. Service lines into consumer’s premises
     Any service line of the licensee which is taken into the premises of a consumer at a point below the level
of the ground shall be taken into the premises in such manner as to prevent as far as reasonably possible any
influx of gas at the point of entry.
141. Inspection and test of consumer’s installation prior to connection; licensee to appoint installation
   inspectors
   (1) Licensee shall appoint in writing one or more competent persons to inspect consumers installations.
    (2) The licensee shall not permanently connect a consumers installation supplied at low or medium
voltage with their electric lines unless and until the said installation has been inspected and duly tested as
aforesaid to determine compliance with the provisions for the Regulation for Electrical Installations.
[S.I. 5 of 1996.]
    (4) The provisions of this regulation shall not apply to consumers installation coming within the provisions
of the Minerals and Mining Act (cap. 226), or the National Film and Video Censors Board Act, or where the
installation to be supplied is another undertaking, instead the licensee shall make happy themselves that the
installation complied with the appropriate writing regulations if any or that the installation has been
approved by an inspector duly appointed to administer the appropriate wiring regulations applicable to the
particular installation, before commencing to give a supply.
                                                    PART XII
                                                     Meters
149. Meters to be tested for accuracy
     (1) Every meter intended to be used by the licensee for the purpose of ascertaining charge for electrical
energy supplied by him to a consumer shall prior to its installation be tested to determine compliance with
the provisions of regulations 157 and 158.
     (2) Any meter failing to comply with the requirements of regulations 156(2) (iii) hereof shall be used until
it shall have been adjusted and found by retesting to register within the prescribed limits.
150. Testing stations to be established
     (1) For the purpose of determining the accuracy of meters in compliance with regulation 149, the licensee
shall establish either a central area or both central and area meter testing stations.
      (2) Every testing station established in compliance with this regulation shall be provided with
standardized precision measuring instruments for the purpose of determining the following measurements-
     (a) potential as volts;
     (b) current as amperes;
     (c) power as watts;
     (d) frequency of supply in hertz;
     (e) time in tenths of a second;
     (f) any other measurements which the director of electrical inspectorate services may deem to be
         essential.
    (3) Precision instruments shall have been standardized by comparison with standard instruments at either
standardizing institution in the country of manufacture or by comparison with some other standard
instruments known accuracy approved by the Director of Electrical Inspectorate Services. Every sub-standard
instrument shall have a dated certificate of calibration covering its entire scale range and except a timing
device, its accuracy shall be within the limits of error prescribed by the I.E.C. where current or potential
transformers are used with an instrument they shall be class AL and their ratio and phase angle errors shall
not exceed the values prescribed by the appropriate I.E.C. standard or other Nigeria Standard.
    (4) Terminal markings of meters and associated transformers shall be marked to correspond with actual
connections made at the time of calibration and certification. Certificates of calibration shall be valid for a
period of five years from the data of issue. No sub-standard meter shall be used at a testing station within a
valid certificate of calibration.
    (5) Every such testing station shall be approved by the director electrical inspectorate service in writing
under his hand. Any approval so given may be revoked at the sole discretion of the director of electrical
inspectorate service if he has reason to believe that the station is no longer capable of performing the
functions for which it was established.
151. Appointment of competent person to have charge of meter testing station
      The licensee shall appoint a competent person having the qualifications prescribed by order of the
     minister on the advice of the director of electrical inspectorate services. Where no such qualifications
     have been prescribed the director of electrical inspectorate services shall be satisfied that the person so
     appointed is competent to have charge of the meter testing station.
152. Records to be kept by competent person
    (a) meter installed at the prescribed date; until seven years following the prescribed date; and
    (b) meter installed subsequent to the prescribed date.
155. Inaccuracy of meters
    (1) If any consumer disputes the accuracy of any meter or meters used for the purpose of determining
the charge of energy supplied to him, he may by written notice served on the licensee (accompanied by a
deposit of #5) required the licensee to cause the meter to be tested and certified as to its accuracy. On
receipt of such notice from a consumer the licensee shall forthwith cause a meter having known errors to be
connected in series with the suspect meter to determine whether the latter’s accuracy is within the prescribe
limits and shall supply the consumer with copy of the test results not later than 28 days from the date of the
termination of the testing period.
   (2) In the event of the test disclosing that the registration of the meter is not within the prescribed limits.
The licensee shall immediately refund the deposit paid by the consumer and adjust his account for the period
of charge immediately preceding the date of the notice given by the consumer under the provisions
regulation 154(1) hereof and in addition make adjustment in respect of the registration of the meter
between the last meter reading thereof at the date of removal from the consumer’s premises for
certification.
   (3) Where the registration of the meter or meters is found to be within the prescribed limits, except as
provided for in regulation 154(4) the consumer shall have no further claim against the licensee and the
deposit paid to the licensee shall be forfeited.
   (4) In the event of a consumer being dissatisfied with the licensee’s test of his meter he may by written
notice require the Director of Electrical Inspectorate Services to investigate the matter and give his ruling.
The Director of Electrical Inspectorate Services’ ruling shall be final and binding on both parties. The cost of
any additional test made by or on the instructions of the director of electrical inspectorate service shall be
borne by the consumer or licensee or both as may be directed by the Director of Electrical Inspectorate
Services.
   (5) Written or printed extracts of this regulation shall be kept at every office of the licensee at which
monies due for electricity supplied are receivable and on complaint by a consumer regarding the alleged
inaccuracy of a meter a copy thereof shall be handed to the complainant. If the complainant cannot read or
PART XIII
                                                            TABLE 2
                                                  Limits of percentage error
                             Single phase 2-wire prepayment
                                                                                    Power factor        Error limit per cent %
                      Value of current as percentage of basic current
               5%                                                                       1.0                  +-2.5 – 3.5
               10%                                                                      1.0                  +-2.0 – 2.5
               From 20% up to and including rated maximum current                       1.0                      +-2
               30%                                                                  0.5 lagging              +-2.0 – 2.5
               From 40% up to and including rated maximum current                   0.5 lagging                  +-2
                                                             TABLE 3
                                                          Limits of errors
                                     Polyphase or 4-wire 3-phase
                                            Conditions of test
                  Current expressed as a fraction of marked current       Power factor            Limit of percentage error
                  5% to 125%                                                  1.0                            +2.0
                  10%                                                       0.5 lag                          +2.0
                  20% to 125%                                               0.5 lag                          +2.0
                                                         TABLE 4
                          Limits of error for meters fitted with maximum demand indicators
                              Whole current or transformer operated type
                                          Conditions of test
   (4) for the purpose of determining that the energy register fitted is of the correct type and appropriate to
the meter to which it is fitted, meters shall be tested by the application of a load, not exceeding rated full
load, for such a periods as will cause the register to advance by not less than ten complete revolutions of the
lowest reading dial.
   (5) Insulation resistance – meters and instrument transformer if used, shall have an insulation resistance
not less than the values prescribed by the relevant I.E.C. or Nigerian Standard. The insulation resistance shall
be measured immediately prior to issue of the meter and accessories from the testing station.
(6) Thermal type maximum demand indicators – registration of meter shall not –
    (a) exceed 85% of the load actually applied prior to the expiry of 50% of the demand integration period;
        or
    (b) at the expiration of the demand integration period, the recorded demand shall not vary by more than
        plus or minus three per centum of the applied load, when tested in the following manner – a steady
        current equivalent to one quarter of the name plate rating shall be applied for a period of the time
        equal to the demand integration period, the registration being noted after the expiry of half the
        demand integration period and again at the end of said period. Immediately following the expiration
        of the demand integration period with a current equivalent to one quarter load, the current passing
        shall be increased to the equivalent of one half and at the end of the demand integration period.
        Thereafter without pause similar tests shall be made at three quarters and at marked plate rating of
        the indicator.
   (7) Any terms and expressions in regulations 157 and 158 not specifically defined by regulation 2 of these
Regulations shall be deemed to have the same meaning as is assigned to them in the relevant Nigerian
standards.
                                                     PART XIV
             Conditions of supply to consumers where distributing mains of adequate capacity exist
159. Persons entitled to demand and supply
    (1) Licensee shall upon being required to do so by the owner or occupier of any premises not previously
supplied with electrical energy situate within 90 meters from any distributing mains of the licensee used for
general supply, give and continue to give a supply of electricity to such premises subject to the following
conditions-
    (a) every owner or occupier of premises requiring a supply of electricity shall serve a written notice on
        the licensee specifying the premises for which the supply is required, the nature and the extent of the
        electrical installation and appliances to be utilized and the day on which the supply is required; which
        date shall not be earlier than 14 days after the date of the notice; and shall enter into a written
        contract; of which a copy shall be furnished to the owner or occupier, as the case may be; to pay for
        such supply of electricity at the appropriate published rate of charge for the time being charged to
        ordinary consumers in the area and if required by the licensee to deposit such sum of money by way
        of security for payment to them of all meters which may from time to time become due to them by
        the consumer in respect of electric lines to be erected under the provisions of subparagraph(c) or (d)
        of this paragraph or current to be supplied;
    (b) the electrical installation provided within the premises to be supplied complies with the requirements
        of the appropriate regulation, then in force covering electrical installations on consumers’ premises
        and has been inspected and tested and so certified by an inspecting engineer duly authorized for this
        purpose;
    (c) the cost of so much of the overhead service line exceeding 50 meters as may be laid on the private
        property of such owner or occupier shall if the licensee so required be defrayed by such owner or
        occupier;
   (2) Where the premises to be supplied have previously received a supply of energy the provisions of
regulations 155(1) shall apply and in addition the following conditions –
         if required by the licensee the owner or occupier of the premises to be supplied shall pay the
         published tariff connection fee. Where the nature and extent of the installation is substantially the
         same as when previously supplied, provided that the service line has not been dismantled the
         licensee shall be bound to give a supply within 14 days of the date of receipt of the application
         subject to there being compliance with all other conditions set out herein;
          where the nature and extent of the installation is such as to require the provision of additional
         service lines or to increase the capacity thereof, the provisions of subparagraph (c) or (d) of paragraph
         (1) shall apply.
160. Where no distribution mains exist
     (1) Requisition of supply – where in any street or part of a street, no distribution mains for the purpose of
general supply have been provided by the licensee or where the general supply distribution system is more
than one hundred meters distant, two or more owners or occupier of premises or the local authority may
serve a requisition in writing on the licensee specifying the premises for which the supply is required, the
nature and extent of supply required, requiring them to provided mains for the purpose of general supply
throughout any street or part of a street. Every such requisition served on the licensee shall be signed by the
persons making it or by the chairman of the local authority as the case may be.
    (2) The licensee may as soon as possible after the service of such requisition serve a notice on the person
by whom such requisition was submitted stating that they decline to be bound by such requisition unless
such persons or some of them will guarantee-
     (a) to reimburse the licensee the entire cost of providing the general supply mains and any other
         necessary works to give a supply or a proportion thereof at the sole discretion of the licensee; or
     (b) to reimburse the licensee, by an annual service charge in addition to any charge payable at published
         tariff rates. The said annual charge to be based on the entire cost of providing the supply or such
         proportion thereof as the licensee may determine together with interest charge thereon at a rate not
         exceeding current bank loan rate and depreciation charges not exceeding five per centum per annum.
         The said annual service charge to be payable for a term not exceeding twenty years; or
     (c) to reimburse the licensee a proportion or the entire cost of providing the general supply mains and
         ancillary works the balance or such proportion thereof as the licensee may determine in the manner
         provided for in subparagraph (b) of this paragraph.
    (3) Where a notice as provided for in paragraph (1) of this regulation has been served the requisition
served in conformity with paragraph (2) of this regulation shall not be binding on the licensee unless within
twenty eight (28) days after the service of such notice on all the persons signing the requisition or in the
                                                    PART XV
                                                    General
161. Saving in respect of amenity undertaking
    (1) where the licensee are operating an undertaking declared by notice in the official Gazette to be an
“amenity undertaking” and where compliance with regulation 159 (1) (f) or regulation 160 (5) would involve
over loading of the electric lines or plant to the detriment of other consumers already supplied with
electricity and further makes it difficult or impossible to maintain supply within the limits of voltage and
frequency prescribed by regulation 160 (2), the licensee may make representations in writing to the minister
that they are unable to comply with the requirements of regulations 159, 160 and this regulation unless the
mains or the plant or both mains and plant are enlarged.
    (2) If the minister is satisfied that the representations are just and proper he may by notice in the Official
Gazette relieve the licensee of compliance with the said parts of regulation 159 and 160 for such period as in
his absolute discretion he considers just and reasonable.
    (3) provided that any relief given o a licensee under the provisions of this regulation be for a term not
exceeding twelve months from the date of the publication of the notice in the Gazette, however on written
application by the licensee, relief for further terms not exceeding twelve months may be given to the licensee
by the minister in his absolute discretion by further notice or notices in the Official Gazette.
162. Declared type of current, frequency and voltage at supply terminals
    (1) Before commencing to given a supply of energy to consumer, the licensee shall declare to that
consumer –
     (a) the type of current, whether direct or alternating which they propose to supply;
     (b) in the case of alternating current, the number of phases and also the constant frequency at which
         they propose to deliver the energy to the supply terminals; and
     (c) the constant voltage at which they propose to deliver the energy to the supply terminals
    (2) The type of current, the number of phase and the frequency in the case of alternating current and the
voltage declare as aforesaid shall be constantly maintained subject to a permissible variation as regards
voltage not exceeding six per centum above or below the declared voltage and as regards frequency to a
variation not exceeding one and half per cent above or below the declared frequency provided that the
permissible variation in frequency is such that the variation in time recorded by a standard synchronous
electric clock to be maintained in proper working order at each and every electric generating station at which