Chapter 9 - Technical data
9.1 General
9.1.1 Ordering information
Device designation UNITROL 1000-15, V5
Order number BASIC 3BHE014557 R0003
PF / VAR regulation
MODBUS (Remote Access)
Voltage Droop Compensation (VDC)
FULL 3BHE014557 R0006
BASIC options
Synchronization (SYNC)
Rotating Diode Monitoring (RDM)
Double Channel Software (DCH)
9.1.2 Mechanical data
Weight 5 kg
Protection class IP20
Dimensions (HxWxD) 245x190x142 mm
9.1.3 Climatic stability
Temperature range for operation 0 to 60 °C
Temperature range for storage -20 to +75 °C
Vibration 2 mm f<15 Hz, 0.7 g f>15 Hz
Shock 5 g, 11 ms pulse
9.1.4 Electrical data
Auxiliary supply UAUX: Maximum power consumption 25 W
AC Input voltage, 3-ph min/max 9 to 250 VAC
AC Input voltage, 1-ph min/max 50 to 250 VAC
DC Input voltage min/max 18 to 300 VDC
Test voltage 2 kV
Power electronics supply UPWR: Frequency range DC, 40 to 600
AC Input voltage, 3-ph min/max 0 to 250 VAC
AC Input voltage, 1-ph min/max 0 to 250 VAC
Test voltage 2 kV
Excitation output Ie: Continuous current at 50 °C 15 A
Continuous current at 55 °C 10 A
UNITROL 1000 User Manual 3BHS262681 E80 Rev.A 9-1
Chapter 9 - Technical data
Continuous current at 60 °C 5A
Overload (maximum 10 s) 30 A DC
Overload (maximum 4 min) 20 A DC
10 to 100 Hz
Frequency range of measuring values UM and Maximum overcurrent 3A
Machine current IM2: Voltage regulation <0.1%
Accuracy:
Test voltage:
Power electronics supply UPWR against case and auxiliary supply UAUX 2830 V DC, 2 s
Auxiliary supply UAUX against case and power electronics supply UPWR 2830 V DC, 2 s
Voltage measurement inputs UM, UNET: High impedance voltage input without galvanic separation
According to (USA, Canada) UL specification:
The screw-type terminals for inputs and outputs are approved for maximum voltage 150 V
9.1.5 Relevant standards, CE conformity
EMC directive: 89/336/EEC
Generic emission standard IEC/EN 61000-6-4
Generic immunity standard IEC/EN-61000-6-2
9.1.6 Ordering information connection cable
Connection Cable PC to UNITROL 1000:
Serial RS232 cable (terminals 2 and 3 crossed) DB9 f/f/ 3 m
9.1.7 Reliability
MTBF (MIL-HDBK-217F) GB(40°C) 4100 FIT / 27.6 years
9.2 Settings record for UNITROL 1000
Name and Address of Customer:
Plant:
Order No.:
Plant Schematic No.:
Device Identification:
Type Plate:
Delivery Date:
Software Revision: Control:
Panel:
CMT 1000:
Remarks:
9-2 3BHS262681 E80 Rev.A UNITROL 1000 User Manual