AF190-30-11-14

AF190-30-11-14 250-500V 50/60Hz / DC


General Information
Extended Product Type: AF190-30-11-14 250-500V 50/60Hz / DC
Product ID: 1SFL487002R1411
EAN: 7320500480441
Catalog Description: AF190-30-11-14 Contactor
Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-
pass and Distribution application up to max 1000 V. Operated with wide control voltage
range 250-500 V, 50/60 Hz and DC

Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors

Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
EAN: 7320500480441

Dimensions
Product Net Depth: 152.0 mm
Product Net Height: 196.0 mm
Product Net Weight: 2.778 kg
Product Net Width: 105.0 mm

Container Information
Package Level 1 Width: 223 mm
Package Level 1 Length: 133 mm
Package Level 1 Height: 186 mm
Package Level 1 Gross Weight: 3.228 kg
Package Level 1 EAN: 7320500480441
Package Level 1 Units: 1 piece

Technical
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency (f): Main Circuit 50/60 Hz
Conventional Free-air Thermal acc. to IEC 60947-4-1, Open Contactors q = 40 °C 275 A
Current (Ith):
Rated Operational Current AC-1 (Ie): (690 V) 55 °C 250 A
(690 V) 40 °C 275 A
(1000 V) 40 °C 250 A
(1000 V) 55 °C 225 A
(690 V) 70 °C 200 A
(1000 V) 70 °C 185 A
Rated Operational Current AC-3 (Ie): (1000 V) 55 °C 85 A
(415 V) 55 °C 190 A
(690 V) 55 °C 135 A
(220 / 230 / 240 V) 55 °C 190 A
(440 V) 55 °C 190 A
(380 / 400 V) 55 °C 190 A
(500 V) 55 °C 135 A
Rated Operational Power AC-3 (Pe): (500 V) 90 kW
(1000 V) 110 kW
(220 / 230 / 240 V) 55 kW
(690 V) 132 kW
(380 / 400 V) 90 kW
(440 V) 110 kW
(415 V) 90 kW
Rated Breaking Capacity AC-3 acc. 8 x Ie AC-3
to IEC 60947-4-1:
Rated Making Capacity AC-3 acc. to 10 x Ie AC-3
IEC 60947-4-1:
Short-Circuit Protective Devices: gG Type Fuses 355 A
Rated Short-time Withstand Current at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
(Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Maximum Electrical Switching AC-3 300 cycles per hour
Frequency: AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Rated Operational Current DC-1 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-3 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-5 (Ie): (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Insulation Voltage (Ui): acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage Main Circuit 8 kV
(Uimp):
Mechanical Durability: 5 million
Maximum Mechanical Switching 300 cycles per hour
Frequency:
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): 60 Hz 250…500 V
50 Hz 250…500 V
DC Operation 250…500 V
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 60 Hz 185 V·A
Holding at Max. Rated Control Circuit Voltage DC 3.9 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 188 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 185 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A
Operate Time: Between Coil Energization and NO Contact Closing 25…55 ms
Between Coil De-energization and NO Contact Opening 37…47 ms
Connecting Capacity Main Circuit: Rigid Al-Cable 1x95…185 mm²
Flexible 2x50…95 mm²
Rigid Cu-Cable 1x6…150 mm²
Connecting Capacity Auxiliary Solid 2x1…4 mm²
Circuit: Flexible with Insulated Ferrule 2x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 2x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type: Main Circuit: Bars
Number of Main Contacts NO: 3

Environmental
Maximum Operating Altitude 3000 m
Permissible:
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25…+50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40…+70 °C
Close to Contactor for Storage -40…+70 °C

Technical UL/CSA
General Use Rating UL/CSA: (600 V AC) 250 A
Horsepower Rating UL/CSA: (208 V AC) Three Phase 50 Hp
(440 ... 480 V AC) Three Phase 125 Hp
(550 ... 600 V AC) Three Phase 150 Hp
(220 ... 240 V AC) Three Phase 60 Hp
(200 V AC) Three Phase 50 Hp
Maximum Operating Voltage Main Circuit 600 V
UL/CSA:

Certificates and Declarations (Document Number)


Instructions and Manuals: 1SFC100008M0201
CB Certificate: SE-71797M1
Data Sheet, Technical Information: 1SFC101070D0201
Declaration of Conformity - CE: 2CMT004613
RINA Certificate: ELE060313XG/002
RoHS Information: 1SFC101055D0202
Classifications
E-nummer: 3210135
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
UNSPSC: 39121529