3015 GHB P1
3015 GHB P1
2
Schematic of a Coal-fired Generating Station
2. REVIEW OF SINGLE-PHASE & THREE-PHASE CIRCUITS
Before we embark on a detailed study of the generators & lines, it would help to
quickly review the basic concepts of :
• 3-phase systems (as most power systems operate as 3- systems)
• Single-phase equivalent of 3- systems (since for balanced 3- systems, we can
use one phase of the star(Y)-equivalent)
• Per unit (p.u.) systems
3
Recall that all the above have been covered elsewhere (EE2005/EE3010), but
since we will be using them extensively, it is worth taking a look back in time!
First, a review of the one-phase system.
I Load represented
V Z by impedance Z
4
For = 0o (unity power factor load)
I V Z=R S=P
= VI
For lagging P.F. loads,
jX jQ
V
Z S
o
90 o
90
I R P
I R P
Z S
-jX -jQ
V
5
What are Real & Reactive Powers?
By convention,
Represents the energy exchange between source & reactor/capacitor i.e. represents
stored energy.
6
Convention for Real & Reactive Powers
1) Generators
I S = VI* = P + jQ
I S = VI* = P + jQ
7
Inductive load absorbs reactive power.
Capacitive load generates reactive power, or absorbs negative reactive power.
Review Exercises (1 & 2)
It
(1) I1 I2
o
Z2 = 5030
o
1000 V Z1 =
1010
o
2000 V
o
j10 100 F
50 Hz supply
S = 3VLINEILINEcos + j3VLINEILINEsin
= P + jQ
10
Phasor Diagram : (Vab : Reference)
Find the line currents & power dissipated in the loads (total power).
Also find Q & S.
[Y-connected system, phase seq. A-B-C]
13
' '
I1 X1 R1 X2 R 2 I'
2
V1 '
V2
which reduces to
'
I1 X R I2
'
V1 V2
14
'
I1 X I2
'
V1 V2
15
• The per-unit value of any quantity is defined as the ratio of the actual quantity to
an “arbitrarily” chosen value (base or reference) of the same dimensions.
physical quanity
Quantity in per unit =
base value
physical quantity
& Quantity in percent = 100
base value
• Percent system should be used with caution (due to mult. factor of 100)
• Per-unit system is preferred in power system calculations as it offers the
following advantages :
• Analysis is greatly simplified, e.g. all impedances of a given equivalent CKT can
be directly added without considering system voltages.
• Use of “3” is eliminated! The base values account for these easily.
• Manufacturers of electrical equipment usually specify the impedance in per unit
or percent of nameplate ratings.
16
• Electrical machines & transformers have widely varying internal impedances with
size & rating. However, it turns out that in the p.u. system, these impedances fall
within a fairly narrow range. Hence, if the actual impedance of a machine is not
known, its per unit value can be easily assigned!
• Circuit analyst is relieved of the worry of referring quantities to one side or other
side of transformer, especially in large networks containing many transformers of
different turns ratios.
Eliminates the possible cause of making serious calculation mistakes!
• P.U. values are more convenient in simulating machine systems on digital
computers.
Significant advantage : Per unit impedance of transformer is the same on both sides
of the transformer!
Per Unit (p.u.) Quantities in 3-phase Power System
There are 4 base values
1. Power base Sb, usually in MVA.
2. Impedance base Zb, usually in OHMS.
3. Current base Ib, usually in A.
4. Voltage base Vb, usually in kV.
17
In 3-phase systems, usually
S, P, Q are three-phase powers in MVA, MW & MVAr respectively
Voltages considered are line-to-line values
Currents considered are line values
Impedances considered are phase values of equivalent star (Y) configuration
(This means that all impedances in must be converted to equivalent Y
value in , before converting to its p.u. value)
The 4 base values (Sb, Zb, Ib & Vb) are related as follows :
Vb I b
Sb 3 MVA (1)
1000
where Vb is line-to-line base voltage in kV & Ib is the line current in AMPS.
Sb 1000
Ib (2)
3 Vb
(Vb / 3)
Next, Zb 1000 (3)
Ib
18
Vb
Note : is the phase voltage of the equivalent Y system.
3
Substituting (2) in (3), we get :
(Vb / 3)
Zb 1000
Sb 1000
3 V b
Vb 2
Zb (4)
Sb
• From the above, it is clear that we need to select only 2 base values, instead of all 4.
For example, if Sb & Vb are selected, then Ib & Zb can be calculated using equations
(2) & (4) respectively!
• Vb (and consequently Zb & Ib too) changes from transformer primary to secondary
as follows :
Vb (primary) No. of turns (primary)
Vb (sec ondary) No. of turns (secondary)
N1
(line to line turns ratio, a)
N2
19
• Per unit values of Z, R, X & I are the same on either side of the transformer, but the
actual values are not!
Per unit quantities can now be evaluated as :
Z() I(AMPS)
Zp.u. ; I p.u. ;
Z b () I b (AMPS)
V(kV) P(MW)
Vp.u. ; Pp.u.
Vb (kV) Sb (MVA)
If necessary, actual voltages/currents/ohms etc. can also be obtained as :
Actual value = Base value p.u. value
General Guidelines for Obtaining P.U. Values
Objective : To reduce the number of computations by selecting suitable values for
Vb & Sb.
• Base MVA (Sb) is the same for all parts of the system. Normally Sb in MVA is used.
• Base kV (Vb) is selected in one part of the system; for other parts base kV is
obtained according to the line-to-line voltage ratios of transformers.
20
• Base impedances will be different in different parts of the system.
• In general, the p.u. (or %) impedances of electrical equipment are specified in
terms of their own MVA & kV ratings. These values need to be converted to the
system bases selected in (1) & (2) above. This conversion is done using the
following formula :
Z
Zp.u. NEW ACTUAL
Zb NEW
ZACTUAL
Zp.u. OLD
Zb OLD
Manufacturer’s base (Equipment base)
where : Zb NEW = Base impedance selected in that part of the system where this
component is placed
(Vb NEW ) 2
= these are base values in that section
Sb NEW
(Vb OLD ) 2
& Zb OLD these are component bases/ratings
Sb OLD
21
Zp.u. NEW Zb OLD (Vb OLD ) 2 / Sb OLD
Zp.u. OLD Zb NEW (Vb NEW ) 2 / Sb NEW
2
V S
Zp.u. NEW Zp.u. OLD b OLD b NEW (*)
Vb NEW Sb OLD
Example 1 : A component rated for 13.2 kV, 30 MVA & with Z = 0.2 p.u. (on its
own ratings) is placed in a power system portion where Vb = 13.8 kV
& Sb = 50 MVA. What is the new p.u. Z of the component?
Here, Sb NEW = 50 Sb OLD = 30
Vb NEW = 13.8 Vb OLD = 13.2
Zp.u. OLD = 0.2 Zp.u. NEW = ?
2
13.2 50
Zp.u. NEW 0.2 0.306 p.u.
13.8 30
• If a transformer impedance is given in p.u., then this value is based on the MVA
rating of the transformer.
Use equation in (*) above to convert this given p.u. to the new p.u. on the
system base kVA, Sb.
22
• If the Sb (base MVA) is not specified (and that is usually the case), the system
component that has the largest MVA rating is chosen to give us the base MVA.
Occasionally, a nice round number such as 100 MVA is selected as the base MVA!
Example 2 : For the power system shown below,
(i) Find appropriate voltage bases by selecting Vb = 18 kV at the
generator terminals.
(ii) Find all impedances in p.u. Use Sb = 100 MVA.
TR 2
b
TR 1 400 MVA
250 MVA 345/230 kV
18 kV GEN a
X = 18% TR 3 X = 10%
250 MVA c
18/345 kV 200 MVA
X = 15% 345/138 kV
X = 10%
Solution : Given Vb, GEN = 18 kV (generator circuit)
Base voltage at point a = Vb, a
345
= Vb, GEN 345 kV 23
18
230
Base voltage at point b = Vb, b Vb, a = 230 kV
345
138
Finally, base voltage at point c = Vb, c Vb, a = 138 kV
345
Next, assuming a power base of Sb = 100 MVA, let us find all the impedances in p.u.
2
V S
ZGEN,NEW p.u. ZGEN,OLD p.u. b OLD,GEN b NEW
Vb,GEN Sb OLD,GE
2
18 100
0.18 0.072 p.u.
18 250
2
V S
ZTR1,NEW p.u. ZTR1,OLD p.u. b OLD,TR1 b NEW
Vb,GEN Sb OLD,TR1
Calculated on the primary side
2
18 100
0.15
18 250
0.06 p.u.
24
2
Vb OLD,TR2 Sb NEW
ZTR 2,NEW p.u. = ZTR2,OLD p.u.
V b,a Sb OLD,TR2
Calculated on the primary side
2
345 100
0.10
345 400
0.025 p.u.
2
V 100
ZTR3,NEW p.u. ZTR3,OLD p.u. b OLD,TR3
Vb,a 200
Calculated on the primary side
2
345 1
0.10
345 2
0.05 p.u.
25
Vb = 18 kV Vb = 345 kV Vb = 230 kV
b
X = 0.05 p.u.
Vb = 345 kV
Example 3 :
Transformer
Load
x y Feeder c 10 MVA
Supply in ZF = (0.726 + j0.847) 0.8 pf lag
per phase 11 kV
60 MVA
33/11 kV
Y/
ZT = (0.2723 + j0.726) per phase (Referred to H.V. side)
Calculate the input & output line voltages of the 3- transformer i.e. voltages at x and y.
Solution : Let base MVA = Sb = 60 MVA (constant throughout the system)`
26
Transformer H.V. side
Base kV, Vb x = 33 kV (assumed)
Vb x 2 332
Zb primary of trans. = Zb x = 18.15 Zb pri
Sb 60
ZT actual pri 0.2723 j0.726
ZT p.u. 0.015 j0.04 0.042769.44 p.u.
Zb pri 18.15
Transformer L.V. side
11
Base kV = Vb y = Vb x =11 kV
33
(Vb y ) 2 112
Zb y 2.017
Sb 60
Z () 0.726 j0.847
ZF p.u. F = 0.36 + j0.42 = 0.5532 49.4 p.u.
Zb y 2.017
Total impedance
ZTOT p.u.= ZT p.u. + ZF p.u. = 0.593550.81 p.u.
SLoad = 10 MVA, 0.8 pf lag = 1036.87o MVA
27
SLoad 1036.87
SLoad p.u. 0.166736.87 p.u.
Sb 60
VLoad 11
VLoad 11 kV VLoad p.u. 1.00o p.u.
V b c 11
Load current
SLoad p.u. 0.166736.87
*
I Load p.u. 0.166736.87 p.u.
VLoad p.u. 10
I Load p.u. = 0.1667 -36.87o p.u.
Voltage at the L.V. side of transformer
Vy p.u. = (ILoad p.u.)(ZF p.u.) + VLoad p.u.
= (0.1667-36.87)(0.553249.4) + 10 = 1.091.05 p.u.
Actual voltage Vy = Vy p.u. x Base voltage at y = 1.09 x 11 kV ~ 12 kV
Finally, voltage at H.V. side of transformer
Vx p.u. = (ZT p.u.)(ILoad p.u.) + Vy p.u.
= (0.042769.44)(0.1667-36.87) + 1.091.05 = 1.09631.24 p.u.
Actual voltage, Vx = Vx p.u. x Base voltage at x
= 1.0963 x 33 = 36.18 kV
28
Single-line Diagram (SLD) & Impedance (Reactance) Diagram
• You have already learnt the circuit models for transformers. Very soon, you will
learn circuit models for synchronous machines & transmission lines & loads.
• Often the diagram is simplified further by omitting the completed CKT thru the
neutral, and by indicating the components by standard symbols rather than by
equiv. CKTs.
29
Standard Symbols Used in SLD
30
Example of SLD :
31
Impedance & Reactance Diagrams
When the individual components of a SLD are represented by their equivalent
circuits, then the resultant drawing is called the per-phase impedance diagram.
The impedance diagram of the system shown on the previous page is as follows :
32
Note : Consistent base kVs must be specified in different sections of the system to
analyze using the p.u. system.
Example 4 : Consider the power system shown :
35
Example 5 : (Last example on p.u./reactance diagram)
T1 T2
A B ZL = (10 + j100) C
G
ZLoad = 300 (resistive)
13.2 kV
Bus 1 Bus 2
T1 : 5 MVA, 13.2 /132 Y kV, X = 10%
T2 : 10 MVA, 138 Y/69 kV, X = 8%
Assume that generator terminal voltage magnitude is 13.2 kV (L-L). (Ignore the
generator reactance).
Find actual values of : Generator current, line current, load current, load voltage &
MVA.
Solution : Assume Sb = Base MVA = 10 MVA & Vb A = 13.2 kV
Vb OLD T1 Sb NEW
2 2
X T1 p.u. NEW X T1 p.u. OLD 13.2 10
S 0.10 0.20 p.u.
V bA b T1 13.2 5
(Calculated on the primary side)
36
132
Base kV in Section B Vb B Vb A 132 kV
13.2
2
132
Zb B 1742.4
10
Z () 10 j100
ZL p.u. L = 0.00574 + j0.0574 = 0.057784.29o p.u.
Zb B 1742.4
Now,
b OLD T2 Sb NEW
2
V
X T2 p.u. NEW X T2 p.u. OLD
VbB b T2
S
(Calculated on primary side)
2
138 10
0.08 0.087438 p.u.
132 10
Next, base kV in section C
69 69
Vb C Vb B 132 66 kV
138 138
37
(Vb C ) 2 662
Zb C 435.6
Sb 10
10
I Load p.u.
j0.2 (0.00574 j0.0574) j0.0874 0.6887
10 10
1.2898 26.4 o
p.u.
0.694445 j0.3448 0.775326.404 o
38
Now,
VLoad p.u. I Load p.u. 0.68870o 0.88826 26.4 p.u.
39
ILine = Ib B ILoad p.u.
= 43.7387 1.2898 = 56.414 Amps
Sb 10 103
Ib C 87.4773 Amps
3 Vb C 3 66
40
1) Constant Power Model (e.g. Air-conditioning loads)
S S P2 Q2
S VI* I* I
V0 V V
where is load power factor angle (assumed lagging)
Here load power (S) remains constant, although load voltage (V) & current (I)
will change; e.g. air-conditioning loads.
2) Constant-impedance Model (e.g. Water heaters & light bulbs)
V V V2
Zs
I S S
V 41
P P
P I RS RS 2 2
2
I P Q2
2
V
P V2
RS 2
P Q 2
Q Q Q V2
Q I XS XS 2 2
2
2
I P Q P Q
2 2
2
V
In p.u. system : ZS p.u. = RS p.u. + jXS p.u.
For a constant-impedance load, the load impedance is kept constant but the
current & power drawn at various voltages will be different.
Note : Constant-impedance load may also be represented by R & X in parallel.
Rp (R p )( jX p )
V Zp
R p jX p
V2
Xp where R p =
P
V2
& Xp = 42
Q
REVIEW EXERCISES (5)
(5) Draw the impedance diagram for the 3-phase system shown in the following figure indicating the pu values of
impedances.
Tr 1 : (0.0083 + j0.0667) pu, Tr. line : (0.0108 + j0.0538) pu, Tr 2 : (0.0112 + j0.0784) pu
(6) The system in problem (5) delivers a load of 60 MW at bus 4 at the rated voltage of 20 kV. Indicate the load terminal
conditions in pu and calculate : (a) the voltage at bus 1, (b) phase angle of voltage at bus 1, for the following cases :
(i) 0.8 (lag), and (ii) 0.8 (lead)
o o o
(i) VL = 1.0040 pu, IL = 0.7469-36.87 pu, 38.51 kV, 5.41
o o o
(ii) VL = 1.0040 pu, IL = 0.746936.87 pu, 32.51 kV, 8.08
43
REVIEW EXERCISES (7 & 8)
(7)(a) Draw the impedance diagram for the system shown in the figure indicating the p.u. values of impedance, for the
following system data.
Tr. Lines : TL1 and TL2 : R = 16 , X = 120 .
Load : (12 + j9) MVA at 13.2 kV.
Tr 1 : 20 MVA, 11/120 kV, Z = (2 + j10)%
Tr 2 : 20 MVA, 120/13.8 kV, Z = (1 + j8)%
Represent the load by a constant series impedance and take the base values for the transmission line as 60 MVA,
and 120 kV.
(b) If the voltage at Bus 1 is maintained at rated value (11 kV), calculate the load terminal voltage.
(a) TL1 & TL2 : 0.067 + j0.50 p.u.; Load impdance : 2.928 + j2.196 p.u.;
Tr 1 : 0.06 + j0.3 p.u.; Tr 2 : 0.03 + j0.24 p.u.
(b) VL = 11.83 kV
Note : Load voltage for (b) will NOT be 13.2 kV as in (a). The load is fixed but the load voltage can vary!
(8) Consider the power system shown below.
(i) Draw the per unit reactance diagram using a 30 MVA, 13.8 kV base in the generator circuit.
(ii) If motor loads M1 and M2 draw 16 MW and 8 MW respectively at unity power factors and 12.5 kV, find the
internally generated generator voltage (i.e., voltage before the generator reactance itself).
(i) XG1 = j0.15; XT1 = j0.078; XLine = j0.166; XT2 = j0.0915; XM1 = j0.2744; XM2 = j0.549
(ii) 1.0391 p.u. (14.339 kV)
44
G1 : 30 MVA, 13.8 kV, 3- generator, XG1 = 15%
M1 : 20 MVA, 12.5 kV, 3- motor load, XM1 = 20% (synchronous motor)
M2 : 10 MVA, 12.5 kV, 3- motor load, XM2 = 20% (synchronous motor)
T1 : 35 MVA, 13.2/115 kV, Transformer, XT1 = 10%
T2 : 30 MVA, 12.5/115 kV, Transformer, XT2 = 10%
L1 : Line XL = 80
45
Basic Equations for Real/Reactive Powers (Please see Appendix A for details)
Consider transfer of power from point “A” in a power system to point “B”,
thru an impedance Z = R + jX = Z
46
VE V2
Real power P = cos( ) cos
Z Z
VE V2
Reactive power Q = sin( ) sin
Z Z
Special case : R ~ 0 Z = 0 + jX = X90o
VE V2
S (90 ) 90
X X
VE VE V2
P sin & Q = cos
X X X
Point “A” is usually
(1) Internally-generated voltage E for a synchronous generator or
(2) Sending-end voltage for a transmission line
Point “B” is usually
(1) Load voltage V for a generator connected to a load or
(2) Receiving-end voltage for a transmission line
47
Impedance Z = R + jX (or Z ~ jX) is usually
Note [for R ~ 0]
P flows from “A” to “B” for angle taking positive values; else “B” to “A”;
if = 0, P = 0 (no real power).
P depends largely on relative angle difference of voltages at “A” & “B”.
For small : Q flows from “A” to “B” if E> V; else “B” to “A”; if
E~ V, then Q ~ 0 (no reactive power).
Q depends largely on voltage magnitudes at “A” or “B”.
48