Temperature TG
Temperature TG
CSM_Temperature_TG_E_6_2
                                                                                                                          ● Temperature Sensor
                                                                                                                          The Temperature Sensor consists of an element
                                                                                                                          protected by a pipe. Locate the element, which
                                                                                                                          converts temperatures into electrical signals, in
                                                                                                                          places where temperature control is required.
                                                                                                                              Temperature
                                                                                                lizes after overshoot-
                                                                                                ing several times.
The set point is input to operate the Temperature Controller. The time
required for stable temperature control varies with the controlled
object. Attempting to shorten the response time will usually result in
overshooting or hunting the temperature. The response time must
not be shortened to reduce overshooting or hunting the temperature.
There are applications that require prompt, stable control in the                                                                                                       Time
waveform shown in (1) despite overshooting. There are other                                  2. Proper response
                                                                                                                              Temperature
applications that require the suppression of overshooting in the
waveform shown in (3) despite the long time required to stabilize the
temperature. In other words, the type of temperature control varies
with the application and purpose. The waveform shown in (2) is
usually considered to be a proper one for standard applications.
                                                                                                                                                                        Time
                                                                                             3. The response is slow
                                                                                                                              Temperature
Time
Heat capacity ······· Heat capacity, which indicates the ease of heating, varies with the capacity of the furnace.
                             Static          ······· Static characteristics, which indicate heating capability, vary with the capacity of the heater.
 Characteristics             characteristics
 of the controlled
 object                      Dynamic                 Dynamic characteristics, which indicate the startup characteristics (i.e. excessive response)
                                             ·······
                             characteristics         of heating, vary with heater and furnace capacity that can affect each other in a complex way.
                             External                     External disturbances cause temperature changes. For example, the opening or closing of a door on a
                                                ·······
                             disturbances                 constant temperature tank can cause external disturbances that generate temperature changes.
                                                                                                                                                                               1
                                                       ON/OFF Control Action                                                                                               I Action
As shown in the graph below, if the process value is lower than the                                      I action (integral control action) is used to obtain an output in
set point, the output will be turned ON and power will be supplied to                                    proportion to the time integral value of the input.
the heater. If the process value is higher than the set point, the output
                                                                                                         P action causes an offset. Therefore if proportional control action and
will be turned OFF and power to the heater will be shut off. This
                                                                                                         integral control action are used in combination, the offset will be
control method, in which the output is turned ON and OFF based on
                                                                                                         reduced over time until the control temperature eventually will
the set point in order to keep the temperature constant, is called ON/
                                                                                                         coincide with the set point and the offset will cease to exist.
OFF control action. With this action, the temperature is controlled
using two values (i.e., 0% and 100% of the set point). Therefore, the
operation is also called two-position control action.                                                                                                                                        Offset ceases to exist.
                                                                                           Hysteresis
                                Set point
                                                                                                                                                                                                       PI
                                                                                                                                                                            Offset              (proportional and
                                                                                                                                                                                             integral control) action
                                                                                                                                                                              P
                                                                                                                                                                    (proportional control)
                                                                                                                                                                         action only
                                                                                            Time
                                                                                                                                                                                                               Time
                                                                                                                        Control output
                                                                                                                                              (%)
                                 ON                                                                                                           100
                             Heater
                               OFF
                                                                                                                                                      50          A short integral time is set.
                                                                P Action
                                                                                                                                                          0
P action (or proportional control action) is used to obtain an output in                                                                                                      A long integral time is set.
                                                            ON
                             100%                                                                        proportion to the time derivative value of the input.
                                                                                                         Proportional control action corrects the control results as does
                             50%
                                                                                                         integral control action. Therefore, proportional control action and
                               0%
                                                                                                         integral control action respond slowly to temperature change. This is
                                                                                              OFF        why derivative control is required. Derivative control action corrects
                                                                                                         control results by adding the control output in proportion to the slope
                                                         90°C   Set point 100°C     110°C Temperature    of temperature change. A large control output is applied to radical
                                                                 Proportional                            external disturbances to get the temperature quickly back under
                                                                     band                                control.
Example: If a Temperature Controller with a temperature range of
                                                                                                                                                                                                     PD
         0°C to 400°C has a 5% proportional band, the width of the                                                                                                                           (proportional and
         proportional band will be converted into a temperature                                                                                                                           derivative control) action
         range of 20°C. In this case, a full output is kept turned ON                                                  Set point
         until the process value reaches 90°C, and the output is
         OFF periodically when the process value exceeds 90°C,                                                                                                             External
                                                                                                                                                                          disturbance                  P
         provided the set point is 100°C. When the process value is                                                                                                                          (proportional control)
         100°C, there will be no difference in time between the ON                                                                                                                                action only
                                                 (%)                                                                                                      (%)
                                                 100                 A wide proportional band is set.                                                     100          A long derivative time is set.
0 0
                                                                                                                                                                                                        Time
                                                                   Set point
                                                                                                                                                                      A long derivative time is set.
                                                                    A narrow proportional band is set.
                                                                                                                       Set point
                             Set point
                                                                                                                                                                      A short derivative time is set.
                                                                                               Offset
Time
Time
                                                                                                                                                                                                                        2
                            PID Control                                                                   Two PID Control
PID control is a combination of proportional, integral, and derivative   Conventional PID control uses a single control block to control the
control actions. The temperature is controlled smoothly here by          responses of the Temperature Controller to a target value and to
proportional control action without hunting, automatic offset            external disturbances. Therefore, the response to the target value
adjustment is made by integral control action, and quick response to     will oscillate due to overshooting if importance is placed on
an external disturbance is made possible by derivative control action.   responding to external disturbances with the P and I parameters set
                                                                         to small values and the D parameter set to a large value in the
                                                                         control block. On the other hand, the Temperature Controller will not
                                                                         be able to respond to external disturbances quickly if importance is
                                                                         placed on responding to the target value (i.e., the P and I parameters
                                                                         are set to large values). This makes it impossible to satisfy both the
                                                                         types of response in this case.
                                                                         Two PID control eliminates this drawback while maintaining the
                                                                         strengths of PID control. This makes it possible to improve both types
                                                                         of responses.
                                                                         PID Control
                                                                         (1)
PID control
                                                                                                                                                  3
Temperature Controller Glossary
■ Glossary of Control Terminology
Hysteresis                                                                           Control Cycle and Time-Proportioning
ON/OFF control action turns the output ON or OFF based on the set                    Control Action
point. The output frequently changes according to minute
temperature changes as a result, and this shortens the life of the                   The control output will be turned ON intermittently according to a
output relay or unfavorably affects some devices connected to the                    preset cycle if P action is used with a relay or SSR. This preset cycle
Temperature Controller. To prevent this from happening, a                            is called the control cycle and this method of control is called time-
temperature band called hysteresis is created between the ON and                     proportioning control action.
OFF operations.                                                                                                                          Actual temperature            Example:
                                                                                     Temperature                     Proportional band
                                                                                                                                                                       If the control cycle is 10 s
Hysteresis (Reverse Operation)                                                                                                                                         with an 80% control
                                                   Hysteresis                            Set                                                                           output, the ON and OFF
                     Control output
                                                                                         point
                                      ON                                                                                                                               periods will be as
                                                                                                                                                                       follows.
                                                                                                   The higher the temperature is the shorter the ON period will be.
                                                                                             ON                                                                               TON: 8 s
                                                                      OFF
                                                                                            OFF
                                                                                                                             T T T T T T T T                                  TOFF: 2 s
                                                                                                   T: Control cycle
                                                                                                                 TON                               TON: ON period
                                                                                                   MV=                  ×100(%)
                                                99.2°C      100°C      Temperature                           TON + TOFF                            TOFF: OFF period
                                                                       ON
                                                                                     derivative control (e.g., the deviation shown in the following graph)
                                                                                     that coincides with the control output in proportional control action.
                                                                                     The longer the derivative time is the stronger the derivative control
                                                                                     action will be.
                                      OFF
                                                                                     PD Action and Derivative Time
                                                                                                    Derivation
                                                                                                                                                                             P action
heater. The result is a small discrepancy between the process value
and the set point in stable operation. This error is called offset. Offset                                                                                                   D2 action
is the difference in temperature between the set point and the actual
process temperature. It may exist above or below the set point.                                                                                                              D1 action
                 Offset
                                                                                                                                                                  TD: derivative time
              Set point
                                                                                                                                 TD1
                                                                                                                                 (with a short derivative time)
                                                                                                                                              TD2
                                             Proportional                   Offset                                               (with a long derivative time)
                                                     band
              ON
             OFF
Hunting
                                                                                                                                                                                                      4
Integral Time                                                                                            Limit Cycle Method
Integral time is the period required for a step-type deviation in                                        ON/OFF control begins from start point A in this method. Then obtain
integral control (e.g., the deviation shown in the following graph) to                                   the PID constants from the hunting cycle T and oscillation D.
coincide with the control output in proportional control action. The
shorter the integral time is the stronger the integral action will be. If                                                                                             Oscillation
                                                                                                                                 Set point
the integral time is too short, however, hunting may result.                                                                                                   A
                                                  PI action
                                                  (with a long integral time)                            Readjusting PID Constants
                                                                                                         PID constants calculated in auto-tuning operation normally do not
                                                                                                         cause problems except for some particular applications. In those
                                                                                                         cases, refer to the following diagrams to readjust the constants.
             Control output
P action
                                                                                                                     Set point
                                                              T12                                                                                                                   suppress overshooting
                                                  (with a long integral time)
                                                                                                                                                                                    although a
                                                                                                                                                                                    comparatively long
Constant Value Control                                                                                                                                                              startup time and set
                                                                                                                                                                                    time will be required.
For constant value control, control is preformed at specific
temperatures.                                                                                            Nar-                                                                       The process value
                                                                                                                    Set point
                                                                                                         rower                                                                      reaches the set point
Program Control                                                                                                                                                                     within a comparatively
                                                                                                                                                                                    short time and keeps
Program control is used to control temperature for a target value that                                                                                                              the temperature stable
changes at predetermined time intervals.                                                                                                                                            although overshooting
                                                                                                                                                                                    and hunting will result
                                                        Auto-tuning                                                                                                                 until the temperature
                                                                                                                                                                                    becomes stable.
The PID constant values and combinations that are used for
temperature control depend on the characteristics of the controlled                                      Response to Change in Integral Time
object. A variety of conventional methods that are used to obtain
these PID constants have been suggested and implemented based                                            Wider                                                                      The set point takes
                                                                                                                    Set point
from a 100% step-type control output. Then obtain the PID constants                                      rower                                                                      ture reaches the set
from R and L.                                                                                                                                                                       point within a compar-
                                                                                                                                                                                    atively short time al-
                                  Set point
                                                                                                                                                                                    though overshooting,
                                                                                                                                                                                    undershooting, and
                                                  R                                                                                                                                 hunting will result.
                                                                                                                                              External disturbance
                                              L
                                                                                                                                                                                    reaches the set point
                                                                                                  Time
                                                                                                                                                                                    within a comparatively
                                                                                                                                                                                    short time with com-
Marginal Sensitivity Method                                                                                                                                                         paratively small
                                                                                                                                                                                    amounts of overshoot-
Proportional control action begins from start point A in this method.                                                                                                               ing and undershooting.
Narrow the width of the proportional band until the temperature starts                                                                                                              Fine-cycle hunting will
to oscillate. Then obtain the PID constants from the value of the                                                                                                                   result due to the
proportional band and the oscillation cycle time T at that time.                                                                                                                    change in process val-
                                                                                                                                                                                    ue.
                                                                                                         Nar-                                                                       The process value will
                  Set point
                                                                                                                                             External disturbance
                                                                                                                     Set point
                                                               A
                                                                                                         rower                                                                      take a relatively long
                                                                                TC
                                                                                                                                                                                    time to reach the set
                                                                                                                                                                                    point with heavy over-
                                                                                                                                                                                    shooting and under-
                                                                                                                                                                                    shooting.
                                                               Marginal sensitivity method
                                                                                               Time
                                                                                                                                                                                                               5
                               Fuzzy Self-tuning                                                                                Self-tuning
PID constants must be determined according to the characteristics of                         Self-tuning is supported by the E5@S. Trends in temperature
the controlled object for proper temperature control. The                                    changes are used to automatically calculate and set a suitable
conventional Temperature Controller incorporates an auto-tuning                              proportional band.
function to calculate PID constants. In that case, it is necessary to
give instructions to the Temperature Controller to trigger the auto-
tuning function. Furthermore, temperature disturbances may result if                                      Set point
the limit cycle is adopted. The Temperature Controller in fuzzy self-
tuning operation determines the start of tuning and ensures smooth
tuning without disturbing temperature control. In other words, the
fuzzy self-tuning function makes it possible to adjust PID constants
according to the characteristics of the controlled object.
                                                                                                                                                         Time
                                                                                                                       Self-tuning
Fuzzy Self-tuning in 3 Modes
• PID constants are calculated by tuning when the set point changes.
• When an external disturbance affects the process value, the PID
                                                                                             PID Control and Tuning Methods for
  constants will be adjusted and kept in a specified range.                                  Temperature Controllers
• If hunting results, the PID constants will be adjusted to suppress
  hunting.                                                                                    Model                          PID            Two PID      Two PID + Fuzzy
                                                                                                      Type of PID
Auto-tuning with a Conventional Temperature Controller                                        E5@N (See note.)                         AT, ST**
  Auto-tuning (AT) Function: A function that automatically calculates                         E5@S                    ST*
                              optimum PID constants for controlled objects.
 Features: (1) Tuning will be performed when the AT instruction is given.                     E5ZN                                     AT
             (2) The limit cycle signal is generated to oscillate the                         E5ZD                                     AT                AT
                 temperature before tuning.                                                   C200H-TC                                 AT
               Target value                                                                   C200H-TV                                 AT
                                                                                              C200H-PID                                AT
                                            Temperature           PID gain
                                AT starts    oscillated.          calculated.                 CQM1-TC                                  AT
                                                                                             ST: Fuzzy self-tuning, ST*: Self-tuning, ST**: Executed only for SP changes,
                         AT instruction
                                                                                             AT: Autotuning
                                                                                             Note: Not including the E5ZN
Self-tuning
  Self-tuning (ST) Function: A function that automatically calculates
                              optimum PID constants for controlled objects.
 Features: (1) Whether to perform tuning or not is determined by the
                  Temperature Controller.
              (2) No signal that disturbs the process value is generated.
                                                   External      External
                                                 disturbance 1 disturbance 2
            Target value
ST starts
Control Outputs
                                                                  Relay output    Contact relay output used for control methods with comparatively low switching
                                                                                  frequencies.
ON/OFF output SSR output Non-contact solid-state relay output for switching 1 A maximum.
                                                                                                                                                                            6
■ Glossary of Alarm Terminology
Alarm Operation                                                            Heater Burnout Alarm
The Temperature Controller compares the process value and the              (Three phase (E5CN, E5AN, and E5EN only) and single phase)
preset alarm value, turns the alarm signal ON, and displays the type
                                                                           Many types of heaters are used to raise the temperature of the
of alarm in the preset operation mode.
                                                                           controlled object. The CT (Current Transformer) is used by the
                                                                           Temperature Controller to detect the heater current. If the heater's
Deviation Alarm                                                            power consumption drops, the Temperature Controller will detect
                                                                           heater burnout from the CT and will output the heater burnout alarm.
The deviation alarm turns ON according to the deviation from the set
                                                                                    Current value
point in the Temperature Controller.
                                                                                                                                                             Heater burnout
Setting Example                                                                                     A                                       Heater burnout   alarm setting
It may be difficult to keep the process value outside the specified        Alarm Latch
alarm range in some cases (e.g., when starting up the Temperature
                                                                           The alarm will turn OFF if the process value falls outside alarm
Controller), and the alarm turns ON abruptly as a result. This can be
                                                                           operation range. This can be prevented if the process value enters
prevented with the standby sequential function of the Temperature
                                                                           the alarm range and an alarm is output by holding the alarm output
Controller. This function makes it possible to ignore the process
                                                                           until the power supply turns OFF.
value right after the Temperature Controller is turned ON or right
after the Temperature Controller starts temperature control. In this                                    Upper limit
case, the alarm will turn ON if the process value enters the alarm                                      alarm setting
range after the process value has been once stabilized.
                                                                                                        Set point
Example of Alarm Output with Standby Sequence Set
Temperature rise
                         Upper limit
                         alarm setting                                                                             ON
                                                                                                        Alarm setting
                                                                                                                 OFF
                         Set point
                         Lower-limit                                       LBA
                         alarm setting
                                   ON                                      (Applicable models: E5CN, E5AN, and E5EN)
                         Alarm output
                                 OFF                                       The LBA (loop break alarm) is a function that turns the alarm signal
Temperature Drop
                                                                           ON by assuming the occurrence of control loop failure if there is no
                                                                           input change with the deviation above a certain level. Therefore, this
                         Upper limit                                       function can be used to detect control loop errors.
                         alarm setting
                         Set point
                                                                           Configurable Upper and Lower Limit
                         Lower-limit
                                                                           Alarm Settings
                         alarm setting
                                                                           (Applicable models: E5@N and E5@R)
                                   ON
                         Alarm output
                                 OFF                                                                                                   L        H
                                                                                                                                                                              7
■ Glossary of Temperature Sensor Terminology
Cold Junction Compensation                                                                          Input Shift
The thermo-electromotive force of the thermocouple is generated due to
                                                                                                    A preset point is added to or subtracted from the temperature
the temperature difference between the hot and cold junctions.
                                                                                                    detected by the Temperature Sensor of the Temperature Controller to
Therefore, if the cold junction temperature fluctuates, the thermo-electromotive
                                                                                                    display the process value. The difference between the detected
force will change even if the hot junction temperature remains stable.
                                                                                                    temperature and the displayed temperature is set as an input
To negate this effect, a separate sensor is built into the Temperature Controller at
                                                                                                    compensation value.
a location with essentially the same temperature as the cold junction to monitor
any changes in the temperature. A voltage that is equivalent to the resulting
thermo-electromotive force is added to compensate for (i.e., cancel) changes that
occur in the thermo-electromotive force.
Compensation for fluctuations by adding a voltage is called cold
                                                                                                                                110°C
junction compensation.
                                                                                                                       Furnace
                                       Terminal 20°C
      Sensing point
      350°C                                VT                Temperature                                                120°C
                                                              Controller
                                                       Cold junction compensating circuit                           Input compensation value: 10°C (Displayed value is 120°C.)
                                                                                                                     (120 − 110 = 10)
In the above diagram, the           When the ambient (terminal section) temperature is
thermo-electromotive                20°C, the temperature sensor inside the Temperature
force (1) VT that is                Controller detects 20°C. If we add the voltage V(20, 0)
                                    that corresponds to 20°C in the standard electromotive
measured at the input               force table to the right side, we get the following:
terminal of the
Temperature Controller is                    V(350, 20)         +         V(20, 0)
Compensating conductor
An actual application may have a sensing point that is located far
away from the Temperature Controller.
If normal copper wires are used because the wiring length is limited
for a sensor that uses thermocouple wires or because conductors
are too expensive, a large error will occur in the temperature.
Compensating conductors are used instead of plain wires to extend
the thermocouple wires.
If compensating conductors are used within a limit temperature
range (often near room temperature), a thermo-electromotive force
that is essentially the same as the original thermocouple is
generated, so they are used to extend the thermocouple wires.
However, if compensating conductors that are suitable for the type of
thermocouple are not used, the measured temperature will not be correct.
                               Connection
                                terminal Compensating Terminal
                                           conductor
20°C
                                                                                                                                                                                 8
■ Glossary of Output Terminology
Reverse Operation (Heating)                                                                                                             Rate of Change Limit
The Temperature Controller in reverse operation will increase control
                                                                                                                                        The rate of change limit for the MV sets the amount of change that
output if the process value is lower than the set point (i.e., if the
                                                                                                                                        occurs per second in the MV. If the MV calculated by the
Temperature Controller has a negative deviation).
                                                                                                                                        Temperature Controller changes significantly, the actual output
                                                                                                                                        follows the rate of change limiter setting for MV until it approaches
                                 Control output (%)
                                                                                                                                                     Output (%)
                                                                                                                                                                  100
                                                                                                                                                                                                                          Rate of
                                                       0
                                                                                                                                                                                                                          change
                                                                                                                                                                                                                     1s   limit setting
                                                             Low                 Set point                  High
                                                                                                                                                                   0
Direct Operation (Cooling)                                                                                                                                                                                            Time
                                                                                                                                                                        Change point
The Temperature Controller in normal operation will increase control
output if the process value is higher than the set point (i.e., if the
Temperature Controller has a positive deviation).
                                                                                                                                        Dead Band
                                                                                                                                        The overlap band and dead band are set for the cooling output. A
                                  Control output (%)
                                                100                                                                                     negative value here produces an overlap band and a positive value
                                                                                                                                        produces a dead band.
                      Temperature                                                  Heating
                      Controller in                                                                       Controlled
                      heating and                                                  Cooling                object
                      cooling                                                                                                                                               Heating                            Cooling
                      control
                                                                                                                                                                            output                             output
                                                                                                                                                                                                                             PV
Heating and Cooling Outputs                                                                                                                                        0
                                                                                                                                                                                           Target value
    Output                                                                              Output
                                                                                                                                        Cooling Coefficient
                                                                                                                                        When adequate control characteristics cannot be obtained using the
          Heating                                                        Cooling              Heating                    Cooling        same PID constants, such as when the heating and cooling
          output                                                         output
                                                                                    PV
                                                                                              output                     output
                                                                                                                                   PV
                                                                                                                                        characteristics of the controlled object vary significantly, adjust the
      0                                                                                   0
                    Target value                                                                        Target value                    proportional band on the cooling side (cooling side P) using the
                                                                                                                                        cooling coefficient until heating and cooling side control are
MV (Manipulated Variable) Limiter                                                                                                       balanced. P on the heating and cooling control sides is calculated
                                                                                                                                        from the following formula.
The upper and lower limits for the MV limiter are set by the upper MV
and lower MV settings. When the MV calculated by the Temperature                                                                        Heating side P = P
Controller falls outside the MV limiter range, the actual output will be
                                                                                                                                        Cooling side P = Heating side P x cooling coefficient
either the upper or lower MV limit.
                                                                                                                                        For cooling side P control when heating side characteristics are
                    Output (%)
                                                                                                        Lower MV limit
                                             0
                                                                                                                                                                                                                    Heating side
                                                                                                 PV                                                                                                                   P × 1.0
With heating and cooling control, the cooling MV is treated as a
negative value. Generally speaking then, the upper limit (positive                                                                                                                   Heating              Cooling
                                                                                                                                                                                      side P               side P
value) is set to the heating output and the lower limit (negative value)                                                                                                         0
                                                                                                                                                                                                                     PV
is set to the cooling output as shown in the following diagram.
                                                                                                                                        Heating Side P × 1.5
                                                           Output (%)
Output
                                 Lower MV limit
                                                                                                                                                                                     Heating              Cooling
                                                                              Heating                      Cooling                                                                    side P
                                                                               output                      output                                                                                          side P
                                                                                                                                                                                 0
                                                                          0                                   PV                                                                                                     PV
                                                                                         Target value
                                                                                                                                                                                                                                          9
Positioning-Proportioning Control                                              Transfer Output
This is also called ON/OFF servo control. When a Control Motor or              A Temperature
Modutrol Motor with a valve is used in this control system, a                  Controller with current
                                                                                                                         Temperature
potentiometer for open/close control reads the degree of opening               output independent                       Controller with
(position) of the control valve, outputs an open and close signal, and         from control output is                   transfer output
transmits the control output to Temperature Controller. The                    available. The process
Temperature Controller outputs two signals: an open and close                  value or set point
signal. OMRON uses floating control. This means that the                       within the available
potentiometer does not feed back the control valve position and                temperature range of                                                                    Recorder
temperature can be controlled with or without a potentiometer.                 the Temperature
                                                                               Controller is                      Temperature Sensor
                                                                               converted into 4- to
                                                                               20-mA linear output                     20 mA
                                                                                                              output
               Controller in                                                   recorders to keep the                   12 mA
                                                               Controlled
                 position-                    M                  object        results of temperature
               proportioning
                  control
                                                                               control on record.
                                 Close
                                                                                                                       4 mA
                                                                                                                                                          Time
Two or more set points independent from each other can be set in                                                  Change point
the Temperature Controller in control operation.
                                                                               Remote Set Point (SP) Input
Setting Memory Banks
                                                                               For a remote set point input, the Temperature Controller uses an
The Temperature Controller stores a maximum of eight groups of                 external input ranging from 4- to 20-mA for the target temperature.
data (e.g., set value and PID constant data) in built-in memory banks          When the remote SP function is enabled, the 4- to 20-mA input
for temperature control. The Temperature Controller selects one of             becomes the remote set point.
these banks in actual control operation.
            Memory Bank 00                                                     Event Input
              Set value              Bank 1
              P constant                                                       An event input is an external signal that can be used to control
              I constant                            Bank 7
                                                                               various actions, such as target value switching, equipment or
              D constant
                                                                               process RUN/STOP, and pattern selection.
0.63 A
                                                                                                  (Time                                                    Time
                                                                                                 constant)
                                                                                             Input digital filter
                                                                                                                                                                                       10
Precautions for Correct Use of Temperature Controllers
For the precautions for individual products, refer to the Safety Precautions for that product.
Waterproofing
Models for which the degree of protection is not specified and models
with IP@0 degree of protection do not have waterproof specifications.
EN/IEC Standards
If the Temperature Controller is to conform to EN/IEC standards, it is
recommended to install the following fuse in the power supply
terminal section.
Recommended fuse: T2A, 250-VAC, time-lag fuse with low breaking
capacity
In the interest of product improvement, specifications are subject to change without notice.
11