Siemens Cientifico 2
Siemens Cientifico 2
com/energy/hvdc
High Voltage
Direct Current Transmission –
Proven Technology for Power Exchange
3 Converter Theory 8
4         Principle Arrangement
          of an HVDC Transmission Project      11
5 Main Components 14
5.6.2 DC Cable 32
7 Project Management 46
                                                     3
    1 Why High Voltage
    Direct Current?
    1.1 Highlights from the High Voltage Direct                 In 1941, the first contract for a commercial HVDC
    Current (HVDC) History                                     system was signed in Germany: 60 MW were to be
                                                                supplied to the city of Berlin via an underground
    The transmission and distribution of electrical energy      cable of 115 km length. The system with ±200 kV
    started with direct current. In 1882, a 50-km-long          and 150 A was ready for energizing in 1945. It was
    2-kV DC transmission line was built between Miesbach        never put into operation.
    and Munich in Germany. At that time, conversion
    between reasonable consumer voltages and higher             Since then, several large HVDC systems have been
    DC transmission voltages could only be realized by          realized with mercury arc valves.
    means of rotating DC machines.                              The replacement of mercury arc valves by thyristor
                                                                valves was the next major development. The first
    In an AC system, voltage conversion is simple.              thyristor valves were put into operation in the late
    An AC transformer allows high power levels and              nineteen-seventies.
    high insulation levels within one unit, and has             The outdoor valves for Cahora Bassa were designed
    low losses. It is a relatively simple device, which         with oil-immersed thyristors with parallel/series
    requires little maintenance. Further, a three-phase         connection of thyristors and an electromagnetic
    synchronous generator is superior to a DC generator         firing system.
    in every respect. For these reasons, AC technology          Further development went via air-insulated air-
    was introduced at a very early stage in the develop-        cooled valves to the air- insulated water-cooled
    ment of electrical power systems. It was soon               design, which is still state of the art in HVDC valve
    accepted as the only feasible technology for genera-        design.
    tion, transmission and distribution of electrical           The development of thyristors with higher current
    energy.                                                     and voltage ratings has eliminated the need for
                                                                parallel connection and reduced the number of
    However, high-voltage AC transmission links have            series-connected thyristors per valve. The develop-
    disadvantages, which may compel a change to                 ment of light-triggered thyristors has further reduced
    DC technology:                                              the overall number of components and thus contrib-
    ■■ Inductive and capacitive elements of overhead lines      uted to increased reliability.
       and cables put limits to the transmission capacity       Innovations in almost every other area of HVDC have
       and the transmission distance of AC transmission         been constantly adding to the reliability of this tech-
       links.                                                   nology with economic benefits for users throughout
    ■■ This limitation is of particular significance for        the world.
       cables. Depending on the required transmission
       capacity, the system frequency and the loss evalua-      Self-Commutated Voltage Sourced Converters
       tion, the achievable transmission distance for           Voltage sourced converters require semiconductor
       an AC cable will be in the range of 40 to 100 km.        devices with turn-off capability. The development
       It will mainly be limited by the charging current.       of Insulated Gate Bipolar Transistors (IGBT) with high
    ■■ Direct connection between two AC systems with            voltage ratings have accelerated the development
       different frequencies is not possible.                   of voltage sourced converters for HVDC applications
    ■■ Direct connection between two AC systems with            in the lower power range.
       the same frequency or a new connection within a          The main characteristics of the voltage sourced
       meshed grid may be impossible because of system          converters are a compact design, four-quadrant
       instability, too high short-circuit levels or undesir-   operation capability and high losses.
       able power flow scenarios.                               Siemens is offering voltage sourced converters for
                                                                HVDC applications with ratings up to 250 MW under
    Engineers were therefore engaged over generations           the trade name HVDCplus Power Link Universal
    in the development of a technology for DC transmis-         Systems.
    sions as a supplement to the AC transmissions.              This paper focuses upon HVDC transmission systems
                                                                with high ratings, i.e. with line-commutated current
    Line-Commutated Current Sourced Converters                  sourced converters.
    The invention of mercury arc rectifiers in the nine-
    teen-thirties made the design of line-commutated             HVDC   =   high voltage direct current
    current sourced converters possible.                         DC     =   direct current
                                                                 AC     =   alternating current
4                                                                IGBT   =   insulated gate bipolar transistor
        1.2 Technical Merits of HVDC                                    1.4 Environmental Issues
        The advantages of a DC link over an AC link are:                An HVDC transmission system is basically environment-
        ■■ A DC link allows power transmission between                  friendly because improved energy transmission possi-
           AC networks with different frequencies or networks,          bilities contribute to a more efficient utilization of
           which can not be synchronized, for other reasons.            existing power plants.
        ■■ Inductive and capacitive parameters do not limit             The land coverage and the associated right-of-way
           the transmission capacity or the maximum length              cost for an HVDC overhead transmission line is not
           of a DC overhead line or cable. The conductor cross          as high as that of an AC line. This reduces the visual
           section is fully utilized because there is no skin effect.   impact and saves land compensation for new projects.
                                                                        It is also possible to increase the power transmission
        For a long cable connection, e.g. beyond 40 km,                 capacity for existing rights of way. A comparison
        HVDC will in most cases offer the only technical                between a DC and an AC overhead line is shown
        solution because of the high charging current of                in Fig. 1-2.
        an AC cable. This is of particular interest for trans-
        mission across open sea or into large cities where
        a DC cable may provide the only possible solution.
        ■■ A digital control system provides accurate and
           fast control of the active power flow.
        ■■ Fast modulation of DC transmission power can be
           used to damp power oscillations in an AC grid and
           thus improve the system stability.
DC Line
                             AC Line
                                                 DC Terminals
AC Terminals
                     Break-Even         Transmission
                      Distance            Distance
                                                                                                                                    5
    2 Main Types of HVDC Schemes
    2.1 DC Circuit
    The main types of HVDC converters are distinguished
    by their DC circuit arrange-ments. The following
    equivalent circuit is a simplified representation of
    the DC circuit of an HVDC pole.
Ud
Ud1 Ud2
                                                                                                                                      AC System 2
                                                                            AC System 1
HVDC
AC System 2
                                                                                                      HVDC
                                                                            AC System 1
AC System 2
6
2.4 Bipolar Long-Distance Transmissions
A bipole is a combination of two poles in such a way
                                                                                              HVDC
that a common low voltage return path, if available,
                                                                                            Cable/OHL
will only carry a small unbalance current during normal
AC System 1
                                                                                                                     AC System 2
                                                                                            Electrodes
operation.
This configuration is used if the required transmission
capacity exceeds that of a single pole. It is also used
                                                                                              HVDC
if requirement to higher energy availability or lower                                       Cable/OHL
load rejection power makes it necessary to split the
capacity on two poles.
During maintenance or outages of one pole, it is still           Fig. 2-8: in monopolar metallic return
possible to transmit part of the power. More than 50 %           operation (converter pole outage)
of the transmission capacity can be utilized, limited
by the actual overload capacity of the remaining pole.           2.4.2 Bipole with Dedicated Metallic Return Path
The advantages of a bipolar solution over a solution             for Monopolar Operation
with two monopoles are reduced cost due to one                   If there are restrictions even to temporary use of
common or no return path and lower losses. The main              electrodes, or if the transmission distance is relatively
disadvantage is that unavailability of the return path           short, a dedicated LVDC metallic return conductor
with adjacent components will affect both poles.                 can be considered as an alternative to a ground
                                                                 return path with electrodes.
2.4.1 Bipole with Ground Return Path
This is a commonly used configuration for a bipolar
transmission system. The solution provides a high                                             HVDC
degree of flexibility with respect to operation with                                        Cable/OHL
                                                                         AC System 1
                                                                                                                     AC System 2
reduced capacity during contingencies or maintenance.
                                                                                              LVDC
                                                                                            Cable/OHL
                                                                                              HVDC
                             HVDC                                                           Cable/OHL
                           Cable/OHL
        AC System 1
AC System 2
                           Electrodes
                                                                 Fig. 2-9: in bipolar balanced operation (normal)
AC System 2
                             HVDC                                                             HVDC
                           Cable/OHL                                                        Cable/OHL
        AC System 1
AC System 2
Electrodes
    3.1 Bridge Circuit Function                               The angle between the time at which the valve voltage
    Current flows through the valves when the voltage         becomes positive and the firing time (start of commu-
    between the anode and cathode is positive. For the        tation) is referred to as the firing delay. Fig. 3-2 shows
    valve to commutate the current, there must be a           that for a firing delay of 90°, the average voltage equals
    positive potential (voltage), and the thyristor must      zero. i.e. the positive and negative areas of the curve –
    have firing pulses. In the reverse direction, i.e. when   voltage against time – cancel each other out. No active
    the potential between anode and cathode is negative,      power flows through the converter. When the firing
    a firing pulse has no effect. The flow of current in      delay is greater than 90°, the negative voltage/time
    a valve ends when the voltage between anode and           areas dominate, and the polarity of the average direct
    cathode becomes negative. The instant when current        voltage changes. Due to physical reasons, the direction
    begins to flow through a valve, or to commutate           of the current does not change. (The thyristor valves
    from one valve to another, can be delayed by post-        conduct current only in one direction.) When the direc-
    poning the firing. This method permits the average        tion of energy flow is reversed, the delivery changes
    value of the outgoing voltage of the rectifier to be      to the supply side. The rectifier becomes an inverter
    changed. The firing pulses are generated by synchro-      which delivers energy to the AC network.
    nizing the network using an elec-tronic control device.
    These pulses can be displaced from their ”natural         The average value of the direct voltage as a function
    firing“ point, which is the point where the two phase     of the firing delay is given by:
    voltages intersect. The method of firing-pulse dis-       Udiα = 1.35 * UL * cos α
    placement is called phase control.                        UL     = secondary side line voltage
                                                              α      = firing angle
                                                              γ      = extinction angle
                  DC current in each valve and phase
                         1      3    5     1
                         L1    L2    L3
                               60°                                                0°
                             0° 120°           Ud                           Udi
                         6   2    4        6   2                                                      ωt
            ld                                                                                             = 0°
                                                                                  0°
            i1
            i2
            i3
            i4                                                                                        ωt
                                                                                                           = 60°
                                                                                       60°
            i5
            i6
                                                                                                      ωt   = 90°
            iL                                                                          90 °
              1                                                                                            = 90°
            iL
              2
            iL
              3
                                                                                             150°     ωt   = 150°
                                                       ld                                                  = 30°
                                  1    3       5
L1
                    L2                                 Ud                                      180°
                                                                                                      ωt   = 180°
                    L3                                                                                     = 0°
4 6 2
Fig. 3-1: Six-pulse converter bridge Fig. 3-2: DC voltage of bridge converter as a function of α
8
      3.2 12-Pulse Group and Converter Transformer                       3.3 Reactive Power as a Function of Load
      HVDC converters are usually built as 12-pulse circuits.            The curve of reactive power demand of an
      This is a serial connection of two fully controlled                HVDC station with changing active power P
      6-pulse converter bridges and requires two 3-phase                 can be calculated from equation:
      systems which are spaced apart from each other by
      30 electrical degrees. The phase difference effected               Q = P * tan [ arc cos ( cos α - dx)]
      to cancel out the 6-pulse harmonics on the AC and
      DC side.                                                           In Fig. 3-5, the reactive power demand of a converter
                                                                         is presented under three different control methods.
= 60°
                                                                                           Q/PN
Udi                                                                                 1.2
                                                                                                             3
                                                                                    1.0
ωt 0.8
                                                                                    0.6
                              Secondary Voltage
                              of the Transformer                                    0.4                 2
                                                                                    0.2                          1
                                             Basic AC Current
                                                                                                                             P/PN
0.5 1.0
Fig. 3-4:Current displacement with angle control Fig. 3-5:Reactive power demand of an HVDC converter
                                                                                                                                     9
                                                                                                                                            3.4 Reactive Power Control
                                                                                                                                            The possibility of electronic reactive power control
420 kV 50 Hz                                                                                                     420 kV 50 Hz               as demonstrated in the preceding section is used
                                                                                                                                            only to a very limited degree in HVDC technology.
                                                                                                                                            This is due to economic reasons. Both control reac-
                                                                                                                                            tive power and commutation reactive power are
                                                                                                                                            increased by the reduction of the DC voltage and
                                                                                                                                            the corresponding increase of current. However,
                                                                                                                                            load losses increase with the square of the current.
                                                                                                                                            For this reason, application is limited to the light
                                                                                                                                            loads where the necessary filter circuits produce
                                                                                                                                            a considerable overcompensation for the reactive
                                                                                                                                            power required by the converter.
                              Q = 103 Mvar                                                  Q = 103 Mvar
                                                                                                                                            Fig. 3-6 depicts the reactive power control of the
                                                                                                                                            Dürnrohr HVDC link. In this system, a compensation
                                                                                                                                            to ± 60 Mvar was specified. Compliance with the
                              Q = 103 Mvar                                                  Q = 103 Mvar
                                                                                                                                            Q limit is achieved by load-dependent switching of
                                                                                                                                            a capacitor bank and one of the two high-pass filters.
                              Q = 103 Mvar                                                  Q = 103 Mvar
                                                                                                                                            Electronic reactive power is used only in the light
                                                                                                                                            load range. Normally, there is a difference between
                                                                                                                                            the connect and disconnect points of the reactive
                                                                                                                                            power elements. This provides a ”switching hysteresis”
                                                    Fig. 3-6: Reactive-power compensation and control                                       which prevents too many switching operations or
                                                    of an HVDC back-to-back link                                                            even a ”pumping”.
 Q (Mvar)
 100
  80
                                                                                                     Over load
       Reduced minimum load
                              Normal minimum load
Normal load
60
40
20
–40
–60
                                                    Electronic                           Capacitor
                                                    reactive                                bank
                                                    power
                                                    regulation                 High–pass filter 2
–80
                                                                               High–pass filter 1
–100
                                                     Reactive-Power Balance
                                                     UAC in p.u. (AC bus voltage)
                                                     – cap.                                 reactive-power                      reactive-power         reactive-power        reactive-power
                                                     + ind                                  converter                           AC filters             reactors              capacitors
                                                     QNetwork =                  +         QConv                        –     QFK*UAC2          +   QL*UAC2          –   QC*UAC2
  10
              4 Principle Arrangement of
              an HVDC Transmission Project
                                                                               The Principle Arrangement of an HVDC Transmission
                                                                               Project is reflected on the Moyle Interconnector
                                                                               project. The HVDC stations between Northern Ireland
                                                                               and Scotland are operating with the following
                                                                               highlights:
                                                                               ■■ Direct light triggered thyristor valves for the
                                                                                  complete HVDC system, with 1872 thyristors
                                                                                  in total, with 20 % better reliability and all valve
                                                                                  components free from oil.
                                                                               ■■ Triple tuned AC filter in both stations.
                                                                               ■■ Unmanned stations, fully automatic remote
                                                                                  operation and automatic load schedule operation.
                                                                               ■■ Hybrid optical ohmic shunt for DC current
                                                                                  measuring unit.
                                                                               ■■ Low noise station design for:
                                                                                  – AC filter capacitor and reactors
                                                                                  – Converter transformer
                                                                                  – Converter valve water cooling system
                                                                                  – DC hall with smoothing reactor
                                                                               ■■ Station design for DC see/land cable with
                                                                                  integrated return conductor and fibre optic
                                                                                  cable for control and communication.
                                                                               System Data
                                                                               Transmission capacity                           2 x 250 MW
                                                                               System voltages                                 250 kV DC
                                                                                                                               275 kV AC
                                                                               Rated current                                   1000 A
                                                                               Transmission distance                           63.5 km
                                            Moyle Interconnector
                      Ballycronan
                         More                                               Auchencrosh                              Coylton
Overhead Line
                                             Undersea Cables
                      Existing 275-kV                                                                     Existing 275-kV
                      Transmission System                                                                 Transmission System
                                                                                                                                            11
250 DC Power Cable.         HVDC Station Auchencrosh                                                         L   L
63.5 km to HVDC Station                                                                                   HA
                                                                                                     DC
Ballycronan More
Northern Ireland                                                                                                 L
                                                                                                              VA
            Smoothing Reactor                                                                           L
                                                       AC-Filter                                       O G
                                                                                 DC                  R
   Pole 1, 250 MW
                                                                            kV                     NT DIN
                                                       AC-Filter                                 O
                                                                                                C UIL
                Thyristor
                 Valves                                            2   50                         B
                                                       C-Shunt
                Thyristor
                 Valves
                                                       AC-Filter                1
                                                                                                              S
                                                                                                          AN
   Pole 2, 250 MW
                                                                                                       TR
                                                       AC-Filter
                                                                                            2
                                                                                                  ER
            Smoothing Reactor                                                                                 16
                                                                            3
                                                                                                  RT
                                                       AC-Filter
                                                                                      14
                                                                                              N VE
                                                                                           CO
                                             AC Bus
                                                                                                              SH
                                                                                                          6
                                                                                                              14
     12
            L   L
         HA
    E                14
 LV
                    4
                EA
          AR
     ER
     M
OR
SF
NK
                                                                   11
                     BA
                   R
                TO
            CI
          PA
     CA
 NT
                                                                                 9
                                                                                     8 10
HU
                                                                                                 15
                                                                         27
                                                                        SWI 5 kV AC
     5                      15                                             TCH
                                                                               YAR                    5    6
                                                                                   D                            7   5   6   5   6
                                 10
                                       8      9
                                                               9
                                                                   10                10                                             275 kV
                                                                        8                 9 12        13                                     OHL
14
                                                                                                                                        13
     5 Main Components
12-pulse group
14
5.1.2 Valve Design
The modular concept of the Siemens thyristor
valves permits different mechanical setups to best
suit each application: single, double, quadruple
valves or complete six-pulse bridges – either
free – standing or suspended from the building
structure.
                                                        15
     5.1.3 Thyristor Development                                         system faults without any limitations. In case of elec-
     Thyristors are used as switches and thus the valve                  trically triggered thyristors (ETT), this is only possible
     becomes controllable. The thyristors are made of                    if enough firing energy is stored long enough on the
     highly pure mono-crystalline silicon. The high speed                thyristor electronics.
     of innovation in power electronics technology is
     directly reflected in the development of the thyristor.             Direct light-triggered thyristors with integrated over-
                                                                         voltage protection (LTT) is now a proven technology
                                                                         and the Siemens standard. It was implemented success-
                     Thyristor Current         Thyristor Blocking
                     (IdN)                        Voltage (UDRM)         fully for the first time in 1997 (Celilo Converter Station
                                              LTT                 8      of the Pacific Intertie). It shows excellent performance
                                                                         and no thyristor failures or malfunction of the gating
            kA                                                      kV
                                                                         system have been recorded. BPA has emphasized its
                               Thyristor Blocking                        confidence in this technology in 2001 by awarding
                6                         Voltage                   6    Siemens the contract to replace all mercury arc valves
                                                                         with direct-light-triggered thyristor valves. Further-
                                                                         more, this valve technology is used for the Moyle
                4                                                   4    Interconnector (2 x 250 MW), which went into
                                                                         service in 2001 and is on contract for the 3000-MW,
                                     Thyristor Current for
                              Long-Distance Transmission                 ± 500-kV Guizhou-Guangdong system.
                2                                                   2
                                                                         Monitoring of the thyristor performance is achieved
                                                                         by a simple voltage divider circuit made from standard
                                                                         off-the-shelf resistors and capacitors; monitoring
                                                                         signals are transmitted to ground potential through
                     1970     1980        1990          2000 2003
                                                                         a dedicated set of fibre optic cables as for the ETT.
                                                                         However, all electronic circuits needed for the evalu-
     Fig. 5.1-3: Thyristor development                                   ation of performance are now located at ground
                                                                         potential in a protected environment, further simpli-
     The high performance thyristors installed in HVDC                   fying the system. The extent of monitoring is the
     plants today are characterized by silicon wafer                     same as for the ETT.
     diameters of up to 5’’ (125 mm), blocking voltages
     up to 8 kV and current carrying capacities up to                    It can be expected that this technology will become
     4 kA DC. Thus no parallel thyristors need to be                     the industry standard in HVDC thyristor valves of the
     installed in today’s HVDC systems for handling                      21st century, paving the way towards maintenance-
     the DC current. The required DC system voltages                     free thyristor valves.
     are achieved by a series connection of a sufficient
     number of thyristors.
                                                                                                                    Light Pipe
      Cu    =       Copper
      Si    =       Silicon
      Mo    =       Molybdenum
      LTT   =       Light-triggered thyristors
      ETT   =       Electrically triggered thyristors
                                                                         Fig. 5.1-5: Valve module with direct-light-triggered thyristor
16
                                                                5.1.6 Flame Resistance
                                                                A lot of effort has been invested by Siemens
                                                                to minimize the fire risk:
                                                                ■■ All oil has been eliminated from the valve and
                                                                   its components. Snubber capacitors and grading
                                                                   capacitors use SF6 as a replacement for
                                                                   impregnating oil.
                                                                ■■ Only flame-retardant and self-extinguishing
                                                                   plastic materials are used.
                                                                ■■ A wide separation between the modular units
                                                                   ensures that any local overheating will not affect
                                                                   neighbouring components.
                                                                ■■ Careful design of the electrical connections avoids
Fig. 5.1-6: Silicon wafer and housing                              loose contacts.
of a direct-light-triggered thyristor
b a c
                      a                 c
              b
                                                                                                                         17
     5.2 Converter Transformer
Transformer Rating
  Three-phase – two-winding transformer          2.2      The high harmonics content of the operating current
                                                          results from the virtually quadratic current blocks of the
  Three-phase – three-winding transformer 3.6             power converter. The odd-numbered harmonics with
                                                          the ordinal numbers of 5, 7, 11, 13, 17 … cause addi-
                                                          tional losses in the windings and other structural parts.
The transport dimension and the weight of the
converter transformer depends on the limitations
for street, railway and shipping, especially in the
case of bridges, subways and tunnels.
                                                                                                                       19
     5.2.4 Main Components                                    of the thyristor valve towers. This frequently leads
     of the Converter Transformer                             to very high connection heights and the need to
                                                              mount the oil expansion tank at a significant height.
     Core                                                     In close cooperation with the equipment design
     HVDC transformers are normally single-phase              department, the engineering specialists at the
     transformers, whereby the valve windings for             Nuremberg Transformer Plant have always been
     the star and delta connection are configured             able to find a design suited to every customer
     either for one core with at least two main limbs         requirement.
     or separately for two cores with at least one main
     limb, depending on the rated power and the               Bushings
     system voltage. Appropriately sized return limbs         Compared to porcelain, composite bushings provide
     ensure good decoupling for a combined arrange-           better protection against dust and debris. A 15%
     ment of windings.                                        higher DC voltage testing level compared to the
                                                              windings underscores the particular safety aspect
     The quality of the core sheets, the lamination of        of these components.
     the sheets, and the nominal induction must all
     conform to special requirements covering losses,         Special Tests for HVDC Transformers
     noise level, over-excitation, etc. Special attention     Special tests for verifying operating functionality
     must be paid to the DC premagnetization of the           are required for HVDC transformers. The applicable
     core due to small asymmetries during operation           international standards are subject to constant
     and stray DC currents from the AC voltage network.       further development. Separate tests with DC voltage,
     The effects of DC premagnetization must be compen-       switching and lightning impulse voltages cover the
     sated by appropriate design and manufacturing            range of different voltage loads. The 2-MV DC volt-
     efforts (e.g. additional core cooling ducts, avoidance   age generator in the Nuremberg Transformer Plant
     of flux pinching in the core sheet).                     is well-suited for all required DC voltage and reverse
                                                              poling tests. The most important criterion is partial
     Windings                                                 discharge. A maximum of 10 discharges over 2000 pC
     The large number of parameters concerning                during the last 10 minutes of the test is permitted.
     transport limitations, rated power, transformer
     ratio, short-circuit voltage, and guaranteed losses      5.3 Smoothing Reactor
     require significant flexibility in the design of
     windings.                                                5.3.1 Functions of the Smoothing Reactor
                                                              ■■ Prevention of intermittent current
     In concentric winding arrangements, star or delta        ■■ Limitation of the DC fault currents
     valve windings lying directly on the core have           ■■ Prevention of resonance in the DC circuit
     proven optimal in many cases. The line winding,          ■■ Reducing harmonic currents including
     normally with a tapped winding, is then mounted             limitation of telephone interference
     radial outside this core configuration.
                                                              Prevention of intermittent current
     The valve windings with high insulation levels and       The intermittent current due to the current ripple
     a large portion of current harmonics make particular     can cause high over-volt-ages in the transformer and
     demands on the design and the quality of the wind-       the smoothing reactor. The smoothing reactor is used
     ing manufacturing. Together with its pressboard          to prevent the current interruption at minimum load.
     barriers, each limb set, including a valve, an over
     voltage and a tapped winding, forms a compact            Limitation of the DC fault current
     unit, which is able to cope with the demand made         The smoothing reactor can reduce the fault current
     by voltage stress, loss dissipation, and short-circuit   and its rate of rise for commutation failures and
     withstand capability.                                    DC line faults.
                                                              This is of primary importance if a long DC cable is
     Tank                                                     used for the transmission. For an overhead line trans-
     The unconventional tank design in HVDC transformers      mission, the current stress in valves is lower than the
     result from the following requirements:                  stress which will occur during valve short circuit.
     ■■ The valve-side bushing should extend
        into the valve hall                                   Prevention of resonance in the DC circuit
     ■■ The cooling system is mounted on the opposite         The smoothing reactor is selected to avoid resonance
        side to facilitate rapid transformer exchange         in the DC circuit at low order harmonic frequencies like
                                                              100 or 150 Hz. This is important to avoid the amplifi-
     For HVDC transformers with delta and star valve          cation effect for harmonics originally from the AC
     winding in one tank, the valve bushing must be           system, like negative sequence and transformer
     arranged so that their ends conform to the geometry      saturation.
20
Reducing harmonic currents including limitation            The wall bushing in composite design is the
of telephone interference                                  state-of-the-art technology which provides
Limitation of interference coming from the DC over-        superior insulation performance.
head line is an essential function of the DC filter
circuits. However, the smoothing reactor also plays
an important role to reduce harmonic currents acting
as a series impedance.
                                                                                                           21
                                                                                   5.4 Harmonic Filters
                                                                                   The filter arrangements on the AC side of an
                                                                                   HVDC converter station have two main duties:
                                                                                   ■■ to absorb harmonic currents generated
                                                                                      by the HVDC converter and thus to reduce
                                                                                      the impact of the harmonics on the connected
                                                                                      AC systems, like AC voltage distortion and
                                                                                      telephone interference
                                                                                   ■■ to supply reactive power for compensating
                                                                                      the demand of the converterstation
                                           600
                                                                                   performance is given in figure 5.4.1-3. The most
                                                                                   commonly used criteria for harmonic performance
                                           400
                                                                                   are related to the harmonic voltage on the converter
                                           200                                     station busbar. The purpose of the filter circuit is to
                                             0                                     provide sufficiently low impedances for the relevant
                                                 0   10     20    30   40   50
                                                                                   harmonic components in order to reduce the harmonic
                                                                                   voltages to an acceptable level.
               Fig. 5.4.1-1: Different harmonic filter types
    22
                                                                 There are basically two methods to include the
                                                                 network impedance in the filter calculations:
                                                                 ■■ to calculate impedance vectors for all relevant
                                                                    harmonics and grid conditions,
               Ih             ZF           Uh               ZN   ■■ to assume locus area for the impedance vectors.
                                                                                                                         23
     Fig. 5.4.2-1 DC filter of Guangzhou/China
                                                                                                                  25
     5.4.3 Active Harmonic Filter                               400 kV AC busbars of the station. This has the advan-
                                                                tage that the harmonic control requires just one
     Active filters can be a supplement to passive filters      measurement point, compared to a current measuring
     due to their superior performance. They can be             scheme, which would require to measure the current
     installed on the DC side or on the AC side of the          at several points and combining the measured signals.
     converter. The connection to the high-voltage system       The other advantage is that the active filter works
     is achieved by means of a passive filter, forming a        just like a passive filter ideally should do, i.e. elimi-
     so-called hybrid filter. This arrangement limits the       nating the voltage in the bus, thus representing no
     voltage level and the transient stresses on the active     change in philosophy.
     part, so that comparatively low equipment ratings
     can be used. Appropriate design allows the exploita-
     tion of the positive characteristics of both passive
     and active filters. Additionally, the passive part
     can be used as a conventional passive filter if the
     active part is by-passed for maintenance purposes.
Main Components
No. Component
1 IGBT converter
4 Transformer
      5       Low-pass filter
                                                                Fig. 5.4.3-1: Active DC filter on site (Tian Guang HVDC project)
      6       Vacuum switch
                                                                The active filter is fully assembled in a transportable
      7       ZnO arrester                                      container and is tested at the factory as a complete
                                                                system before shipping. Fig. 5.4.3-5 shows the
      8       Isolators and grounding switches                  installed active AC filter (in the container) at the
      9       LC branch for deviating the                       Tjele substation.
              50-Hz current component
                                                                                                                                              400 kV Bus
     The Siemens active filters use voltage-sourced
     IGBT converters with a high switching frequency                                                                                         Existing
                                                                       Capacitive
     to produce an output voltage up to approximately                  Potential                  Optical                                     Passive
     700 Vpeak, containing harmonics up to the 50th                    Transformer
                                                                                                 Interface
                                                                                                                 From the                       Filter
                                                                                                                 Other Phases                    ZF2
     as required. A powerful high-speed control and
     protection system processes the currents and/or                                                                                    Underground
                                                                                 Active AC Filter                                              Cable
     voltages measured at the network by appropriate                                                                                     To/From Main
     sensors and produces the control pulses for the                              Common                             Simadyn D           Components
                                                                                                                     cubicle             of the Other
     IGBT’s.                                                                      Control and Auxiliary              (control and
                                                                                                                                         Phases (in
                                                                                  Equipment                          protection)
                                                                                                                                         the Container)
26
One harmonic controller is dedicated to each harmonic
selected for elimination by the action of the active
filter. In these harmonic controllers, the particular
                                                                               Voltage on the                                                To the IGBT
harmonic is isolated and expressed by a complex                                400-kV Busbar                                                 Converter
signal in the frequency domain.
             Harmonic voltages at the 400-kV bus                              … with active filter control (23th, 25th, 35th,
             (L1) without and …                                               47th and 49th harmonics)
Fig. 5.4.3-4: Plots from measurement: left without, right with active filter control
Fig. 5.4.3-5: Installation of the active AC filter, 400-kV substation Tjele (Denmark)
                                                                                                                                                     27
                      5.5 Surge Arrester                                                   ■■ Low   resistance during surges so that overvoltages
                                                                                              are limited
                      Siemens surge arresters are designed optimally                       ■■ High resistance during normal operation in order
                      to the following requirements:                                          to avoid negative effects on the power system and
                      ■■ Excellent pollution performance for coastal and                   ■■ Sufficient energy absorption capability for stable
                         desert regions or in areas with extreme industrial                   operation
                         air pollution.
                      ■■ High mechanical stability, e.g. for use in seismic zones.         MO (Metal Oxide) arresters are used in medium-,
                      ■■ Extremely reliable pressure relief behaviour                      high- and extra-high-voltage power systems.
                         for use in areas requiring special protection.
                                                                                           Here, the very low protection level and the
                      What is more, all Siemens surge arresters are                        high energy absorption capability provided
                      sized for decades and the material used provides                     during switching surges are especially important.
                      a contribution towards the protection of the                         For high voltage levels, the simple construction
                      environment.                                                         of MO arresters is always an advantage.
                      The main task of an arrester is to protect the equip-                Arresters with Polymer Housings
                      ment from the effects of overvoltages. During                        Fig. 5.5-2 shows two Siemens MO arresters
                      normal operation, it should have no negative effect                  with different types of housing. In addition
                      on the power system. Moreover, the arrester must                     to what has been usual up to now – the porcelain
                      be able to withstand typical surges without incurring                housing – Siemens offers also the latest generation
                      any damage. Non-linear resistors with the following                  of high-voltage surge arresters with polymer
                      properties fulfil these requirements:                                housing.
  1
 20 °C
115 °C
150 °C
  0
              10-4   10-3   10-2     10-1     1       10       102     103     104
                                                         Current through Arrester Ia [A]
         28
                                                                   Flange with Gas Diverter Nozzle
                                                                   Seal
Fig. 5.5-3 shows the sectional view of such an           The polymer-housed high-voltage arrester design
arrester. The housing consists of a fibre-glass-         chosen by Siemens and the high-quality materials
reinforced plastic tube with insulating sheds            used by Siemens provide a whole series of advan-
made of silicon rubber. The advantages of this           tages including long life and suitability for outdoor
design which has the same pressure relief device         use, high mechanical stability and ease of disposal.
as an arrester with porcelain housing are absolutely
safe and reliable pressure relief characteristic,        For terminal voltage lower than the permissible
high mechanical strength even after pressure             maximum operating voltage (MCOV), the arrester
relief and excellent pollution-resistant properties.     is capacitive and carries only few milli-amps. Due
The very good mechanical features mean that              to its extreme non-linear characteristics, the arrester
Siemens arresters with polymer housing (type             behaves at higher voltages as low-ohmic resistor
3EQ/R) can serve as post insulators as well.             and is able to discharge high current surges.
The pollution-resistant properties are the result        Through parallel combination of two or more
of the water-repellent effect (hydrophobicity            matched arrester columns, higher energy absorption
of the silicon rubber).                                  capability of the ZnO arrester can be achieved.
                                                                                                                   29
                              AC Filter Bank                                       9                10    DC      to DC line            10
                                                                                                                                             DC
                  1
             Aa
                                   AC                          V                                D                      D
                          2       Filter                                                                                                    11
                                              4 AC Bus   5
                                                 A             V
                                                                                                          DC                                12
                          3                              7                    C                          Filter
                                                               V
                                                                                                                                                      Fdc2
          Fac1                         Fac2              6
                                                 A             V                                                           Fdc1
                                                                                       8       Neutral
     AC filter bus              The ZnO arrester will be installed                         Protect the AC filters busbar
     arrester ‘Aa’              at the busbar of the AC filter banks                       against lightning surges
     Valve-arrester ‘V’         3-pulse commutation group                                  The main events to be considered with respect
                                                                                           to arrester discharge currents and energies are:
                                                                                           a) Switching surges from the AC system
                                                                                              through converter transformer
                                                                                           b) Ground fault between valve and HV bushing
                                                                                              of converter transformer during rectifier 		
                                                                                              operation
     DC bus arrester ‘D’        At the HV smoothing reactor                                They will protect the smoothing reactor and
                                and at the DC lines                                        the converter station (e.g. DC switchyard)
                                                                                           against overvoltages coming from the DC side
     Neutral DC bus             Neutral DC bus                                             The neutral bus arresters protect the LV
     arrester ‘E’                                                                          terminal of the12-pulse group and the neutral
                                                                                           bus equipment
     AC filter arrester         AC filter                                                  The operating voltage for the AC filter arresters
     ‘Fac‘                                                                                 consists of low fundamental frequency and
                                                                                           harmonic voltages. Overvoltages can occur
                                                                                           transiently during faults
     DC filter arrester         DC filter                                                  The operating voltage for the DC filter arresters
     ‘Fdc‘                                                                                 consists of low DC component and harmonic
                                                                                           voltages. Overstresses may occur transiently
                                                                                           during DC bus fault to ground
30
5.6 DC Transmission Circuit
5.6.1.1 Towers
Such DC transmission lines are mechanically
designed as it is practice for normal AC
transmission lines; the main differences are:
■■ The conductor configuration
■■ The electric field requirements
■■ The insulation design
5.6.1.2 Insulation
The most critical aspect is the insulation design and
therefore this topic is described more detailed below:
For DC transmission lines, the correct insulation design
is the most essential subject for an undisturbed oper-
ation during the lifetime of the DC plant.                  Fig. 5.6.1-1: DC transmission line (bipolar tower 300-kV link)
                                                                                                                             31
     Long-Rod Porcelain Type                                        Composite Long-Rod Type
     Positive Aspects:                                              Positive Aspects:
     ■■ Long-term experience/track record                           ■■ Small number of insulators in one string
     ■■ Good mechanical strength                                    ■■ Up to 400 kV per unit possible
     ■■ Puncture-proof                                              ■■ Good mechanical strength, no chipping
     ■■ Good self-cleaning ability                                     of sheds possible
     ■■ Less intermediate metal parts                               ■■ Very light – easy handling during construction
     ■■ Due to caps on both insulator ends                             and maintenance, logistical advantages in areas
        not subjected to pin corrosion because                         with poor access
        of low track current density                                ■■ Puncture-proof
     ■■ Moderate price                                              ■■ Good self-cleaning behaviour – hydrophobicity
                                                                       of surface which offers advantages of less
     Negative Aspects:                                                 creepage distance up to pollution class II
     ■■ Heavy strings                                               ■■ Very good RIV and corona behaviour
     ■■ String not very flexible                                    ■■ Good resistance against vandalism
     ■■ Under extreme vandalism failure of string                   ■■ Shorter insulator string length
        possible                                                    ■■ Very competitive price
                                                                    Negative Aspects:
                                                                    ■■ Relatively short track record in DC application
                                                                       (since 1985 first major application in the USA)
                                                                    ■■ Less tracking resistance against flash-over
                                                                       (can be improved by means of corona rings)
32
The conductor is built of stranding copper layers of    1) XLPE
segments around a central circular rod. The conductor   To overcome the disadvantages of the above men-
is covered by oil and resin-impregnated papers. The     tioned cable types, extensive R&D was conducted
inner layers are of carbon-loaded papers whereas        by the cable suppliers. The result is the XLPE cable.
the outer layer consists of copper-woven fabrics.       XLPE means ‘cross-linked polyethylene‘ and forms the
The fully impregnated cable is then lead-sheathed       insulation material. The conductor is the segmented
to keep the outside environment away from the           copper conductor insulated by extruded XLPE layers.
insulation. The next layer is the anti-corrosion        The insulation material is suitable for a conductor
protection which consists of extruded polyethylene.     temperature of 90 °C and a short-circuit temperature
Around the polyethylene layer galvanized steel          of 250 °C. Although the main application for XLPE
tapes are applied to prevent the cable from perma-      cables is the land installation and the offshore industry,
nent deformation during cable loading. Over the steel   XLPE with extruded insulation material for HVDC
tapes a polypropylene string is applied followed        systems of lower transmission capacities are under
by galvanized steel wire armour.                        development.
The technology is available for voltages up to 500 kV
and a transmission capacity of up to 800 MW in one      2) Lapped Thin Film Insulation
cable with installation depths of up to 1000 m under    As insulating material a lapped non-impregnated thin
sea level and nearly unlimited transmission lengths.    PP film is used instead of the impregnated materials.
The capacity of mass-impregnated cables is limited      The tests for the cable itself are completed. Now the
by the conductor temperature which results in low       tests for the accessories such as joints are under
overload capabilities.                                  process.
                                                        This type of cable can sustain up to 60 % higher
2) Oil-Filled Cable                                     electrical stresses in operation, making it suitable
In comparison to mass-impregnated cables,               for very long and deep submarine cables.
the conductor is insulated by paper impregnated         Another area of development are the cable arrange-
with a low-viscosity oil and incorporates a longi-      ments. For monopolar transmission systems, either
tudinal duct to permit oil flow along the cable.        the return path was the ground (’ground return‘)
Oil-filled cables are suitable for both AC and DC       or a second cable. The first solution always provokes
voltages with DC voltages up to 600 kV DC and           environmental concerns whereas the second one
great sea depths. Due to the required oil flow          has excessive impact on the costs for the overall
along the cable, the transmission line lengths          transmission scheme.
are however limited to <100 km and the risk             Therefore, a new cable was developed with an inte-
of oil leakage into the environment is always           grated return conductor. The cable core is the tradi-
subject to discussions.                                 tional design for a mass-impregnated cable and the
                                                        return conductor is wound outside the lead sheath.
5.6.2.3 Future Developments for HVDC Cables             The conductor forms also part of the balanced armour,
Most of the research and development activities         together with the flat steel wire layer on the outside
for new cable types are done with the insulation        of the return conductor insulation.
material. These include:                                This cable type was installed between Scotland and
                                                        Northern Ireland for 250 kV and 250 MW. R&D is on-
                                                        going to increase the voltage as well as the capacity
                                                        of the cable with integrated return conductor.
                                                                                                                     33
     5.6.3 High Speed DC Switches
     5.6.3.1 General
     Like in AC substations, switching devices are also
     needed in the DC yard of HVDC stations. One group
     of such devices can be characterized as switches
     with direct current commutation capabilities,
     commonly called ”high-speed DC switches”.
                                  HVDC                                                             HVDC
                              Overhead Line                                                    Overhead Line
             AC System 1
AC System 2
AC System 1
                                                                                                                 AC System 2
                                Electrodes                                                       Electrodes
                                  HVDC                                                             HVDC
                              Overhead Line                                                    Overhead Line
                                  HVDC
                              Overhead Line
             AC System 1
AC System 2
Electrodes
                                  HVDC
                              Overhead Line
Type Duties
      HSNBS                                     The HSNBS must commutate some direct current into the ground
      (High-Speed Neutral Bus Switch)           electrode path in case of faults to ground at the station neutral.
      HSGS                                      The HSGS is needed to connect the station neutral to the station
      (High-Speed Ground Switch)                ground grid if the ground electrode path becomes isolated.
      GRTS                                      The GRTS is needed for the retransfer from metallic return to bipolar
      (Ground Return Transfer Switch)           operation via ground return, also without interruption of power flow.
34
5.6.3.3 Design Considerations
                                      Rm         Lm                                                   t0              t1         t
                    l4
                                                                                                           tc
                                                                                                 Uabsorber
                          GRTS
                                 l3   Re         Le
          l0                                                                                            Uarc
                                                                                                                           l3
                          MRTB
                                                                                                                                              35
     5.6.4 Earth Electrode                                             As shown in figure 5.6.4-1, the electrode conductor
                                                                       itself, which is generally made of iron, is laid horizon-
     5.6.4.1 Function of the Earth Electrode                           tally at a depth of approximately 2 m. It is embedded
     in the HVDC System                                                in coke which fills a trench having a cross section of
     Earth electrodes are an essential component of                    approximately 0.5 x 0.5 m2.
     the monopolar HVDC transmission system, since
     they carry the operating current on a continuous                  The advantage of this design becomes apparent in
     basis. They contribute decisively to the profitability            anodic operation. The passage of the current from
     of low-power HVDC systems, since the costs for a                  the electrode conductor into the coke bed is carried
     second conductor (with half the nominal voltage)                  primarily by electrons, and is thus not associated
     are significantly higher, even for transmission over              with loss of the material.
     short distances, than the costs for the earth electrodes.
                                                                       Several typical patterns of horizontal land electrodes
     Earth electrodes are also found in all bipolar HVDC               are illustrated in figure 5.6.4-2
     systems and in HVDC multi-point systems. As in any
     high-voltage system, the power circuit of the HVDC
     system requires a reference point for the definition                                    a)                     b)
     of the system voltage as the basis for the insulation
     coordination and overvoltage protection. In a bipolar
                                                                                        c)        d)           e)           f)
     HVDC system, it would conceivably be possible to
     connect the station neutral point to the ground mat                           a) Line Electrode
                                                                                   b) Multi-Line Electrode
     of the HVDC station to which the line-side star points
                                                                                   c) Ring-Shaped Electrode
     of the converter transformers are also connected. But                         d) Ring-Shaped Electrode with second ring
     since the direct currents in the two poles of the HVDC                        e) Star-Shaped Electrode
     are never absolutely equal, in spite of current balanc-                       f) Forked Star Electrode
     ing control, a differential current flows continuously
                                                                       Fig. 5.6.4-2: Plan view of a typical design of
     from the station neutral point to ground. It is com-              horizontal land electrodes
     mon practice to locate the grounding of the station
     neutral point at some distance (10 to 50 kilometres)
                                                                       5.6.4.2.2 Vertical Land Electrode
     from the HVDC station by means of special earth
                                                                       If the ground strata near the surface have a high
     electrodes.
                                                                       specific resistance, but underneath, there is a con-
                                                                       ductive and sufficiently thick stratum at a depth
     5.6.4.2 Design of Earth Electrodes
                                                                       of several tens of meters, the vertical deep electrode
     Earth electrodes for HVDC systems may be land, coastal
                                                                       is one possible solution.
     or submarine electrodes. In monopolar HVDC systems,
     which exist almost exclusively in the form of sub-
                                                                       Figure 5.6.4-3 shows, as an example, one of the
     marine cable transmission systems, there are funda-
                                                                       four deep electrodes at Apollo, the southern station
     mental differences between the design of anode
                                                                       of the Cahora Bassa HVDC system.
     and cathode electrodes.
                                                                                                                         Graphite Rod
                                            Fill                                                                         Crushed
                                                                                                                         Stone
            1.5 – 2.5m                                                                                                   Borehole ø:
                                                                         10
                                                                         m
                                                                                                                         Conductive
                                            Coke Bed
                                                                                                                         Layer
                                            (5 x 0.5m2)
     Fig. 5.6.4-1: Cross section through a horizontal land electrode   Fig. 5.6.4-3: Vertical electrode at Apollo, the Southern
                                                                       Cahora Bassa HVDC station
36
                                                                                                            Electrode
                                                                                                            Module
                                                                                                            Feed
                                                                                                            Cable
0.5 – 1 m Cable
                                                                          2–5m
                  0.5 – 1 m
                                                                                                                             37
                     5.7 Control & Protection
                     5.7.1 General
                     The WIN-TDC Control and Protection System plays an                                     All WIN-TDC components from the Human Machine
                     important role in the successful implementation of HVDC                                Interface (HMI) workstations, the control and
                     transmission systems. High reliability is guaranteed                                   protection systems down to the state of the art
                     with a redundant and fault tolerant design. Flexibility                                measuring equipment for DC current and voltage
                     (through choice of optional control centres) and high                                  quantities have been upgraded to take advantage
                     dynamic performance were the prerequisites for the                                     of the latest software and hardware developments.
                     development of our control and protection system.                                      These control and protection systems are based
                     Knowledge gained from over 30 years of operational                                     on standard products with a product life cycle for
                     experience and parallel use of similar technology                                      the next 25 years.
                     in related fields has been built into the sophisticated
                     technology we can offer today.                                                         The control is divided into the following
                                                                                                            hierarchical levels:
                     Main objectives for the implementation of the HVDC                                     ■■ Operator control level (WIN CC)
                     control system are reliable energy transmission                                        ■■ Control and protection level (Simatic TDC)
                     which operates highly efficient and flexible energy                                    ■■ Field level (I/Os, time tagging, interlocking)
                     flow that responds to sudden changes in demand
                     thus contributing to network stability.
Dispatch Centres
                                                                                                                                                                                                                            Opposite Converter
        System 1   System 2
                                                                                                                                                                                          Telecommunication
                                                                                                Telecommunication Equipment
Equipment
                                                                                                                                                                                                                                 Station
                                                                                                            Remote Control            Remote Control
                                                                                   Router   Router            Interface                 Interface           Router       Router
                                                                                                              System 1                  System 2
LAN 1
LAN 2
Field Level
I I I I I I
O O O O O O
Fig. 5.7.1-1: HVDC control hierarchy, one station (bipolar HVDC transmission scheme)
         38
                                                  Internet
In the following section, functions, tasks and               5.7.1.4 Best Support – Remote Access
components are described to provide an overview.            As an optional feature, the control system can be
                                                             accessed remotely via point-to-point telephone
5.7.1.1 High Availability                                    connection or via Internet. This allows remote plant
The main design criteria for Siemens HVDC systems            monitoring and fault detection including diagnostics.
is to achieve maximum energy availability. This applies      To ensure the data security, a VPN (Virtual Private
to the design of the control and protection systems          Network) encrypted connection is used. Furthermore,
as well. A single fault of any piece of equipment in         a password protected access ensures that only autho-
the control and protection systems may not lead to           rized personnel have access.
a loss of power. Therefore, the primary control and
protection components are configured as redundant            With the use of a standard web browser, main
systems.                                                     diagnosis data can be monitored. Expert access
                                                             to the control components is also possible. This
5.7.1.2 Self-Testing Features                                remote access feature provides flexible support
All control and protection systems are equipped              for the commissioning and maintenance personnel
with self-diagnostic features that allow the                 by our design engineers.
operator to quickly identify and replace the
defective part to recover redundancy as soon                 5.7.1.5 Modular Design
as possible.                                                 The control and protection systems use multiprocessor
                                                             hardware. This means that the computing capacity
5.7.1.3 Low Maintenance                                      can be scaled according to the requirements.
With today’s digital systems there is no requirement
for routine maintenance. However, should it be               Therefore, the most economic solution can be found
necessary to replace single modules, the design              at the start. Additional computing capacity can be
is such that there is no operational impact on the           added at any time later, if required.
HVDC system. This is achieved by designing all
primary components as redundant systems, where               5.7.1.6 Communication Interfaces
one system can be switched off without impact                The control and protection systems as well as the
on the other system.                                         operator control system communicate via Ethernet
                                                             or Profibus. For remote control interfacing, a number
                                                             of standard protocols are available. Custom protocols
                                                             can be implemented as an option.
                                                                                                                     39
                                                                 5.7.2 Control Components
40
■■ Analysisof operating mode based on user-
   defined and archived data (trend system)
■■ Generation of process data reports
Measuring
DC values are measured by means of the hybrid optical
DC measuring system. This system measures the
voltage drop over a shunt or a voltage divider,
converts this voltage into a telegram and transfers
it to the measurement cubicle via fibre optics.
Shunt
                Id                                                                       Optical
                                 Electrical Energy
                                                                       Power fibre       Energy                        Power
                                                                                                          Electrical   supply
                                               Optical Energy                                             Energy
Sensor Head
                                                                                                                                       41
                     Control of Power Transmission                                           The HVDC-related protection functions are referred
                     The pole control system is responsible for firing                       to as DC protection. These include converter protection,
                     the thyristor valves so that the requested power is                     DC busbar protection, DC filter protection, electrode
                     transmitted. The pole controls on each side of the                      line protection and DC line protection.
                     transmission link therefore have to fulfill different                   The AC protection scheme consists mainly of the
                     tasks. The pole control system on the rectifier side                    AC busbar, the AC line and the AC grid transformer
                     controls the current so that the requested power                        protection as well as the AC filter protection and
                     is achieved. The pole control system on the inverter                    converter transformer protection.
                     side controls the DC voltage so that rated DC voltage                   The task of the protective equipment is to prevent
                     is achieved.                                                            damage of individual components caused by faults
                                                                                             or overstresses.
                     The pole control is implemented redundantly.
                     A failure in one system thus has no impact on                           Each protection zone is covered by at least two inde-
                     power transmission.                                                     pendent protective units – the primary protective
                                                                                             unit and the secondary (or back-up) protective unit.
                     This system can be repaired while the other system
                     remains in operation. In bipolar schemes a redundant                    Comprehensive system monitoring and measurement
                     pole control system is assigned to each pole. Failures                  plausibility functions are implemented in the protection
                     in one pole will not have any impact on the remaining                   systems. This serves to prevent false trips due to
                     pole.                                                                   singular equipment failure.
System 2
System 2
                                                                                                                2
           Valve Base                               Valve Base
           Electronic                               Electronic                                                                                                   9
7 6
Fibre Optic 8
                                                                                                            4
                                                                                                                          5
                                                                                                     1
                          12-Pulse Group
                     Fig. 5.7.1-7: Redundant pole control system            Fig. 5.7.1-8: Protection zones, one pole/one station
                     structure (for one 12-pulse group)
     42
Fig. 5.7.1-9: Real-time simulator
All protective equipment in the HVDC converter             5.7.4 Testing and Quality Assurance
station is implemented either with digital multi-          The design process has a number of defined review
microprocessor systems or with digital Siemens             steps. These allow verification of the control and
standard protective relays. ”The DC protection is          protection system functionality and performance
designed to be fully redundant. Additionally both          before delivery to site (see figure 5.7.1-10).
protection systems incorporate main and back-up
protection functions using different principles.           Already along with the tender, the use of accurate
The AC protection con-sists of a main and back-up          simulation tools allows to answer specific perfor-
system using different principles. Each protective         mance issues that are vital to the customer’s grid.
system is assigned its own measuring devices as
well as power supplies.”                                   5.7.4.1 Offline Simulation EMTDC
                                                           Siemens uses a simulation model that includes
5.7.3 Control Aspects                                      all details of control and protection functionality
                                                           in detail. Thus forecast of real system behaviour
5.7.3.1 Redundancy                                         is reliable. Therefore it is possible to optimize
All control and protection systems that contribute         the application to find the best economic solution
to the energy availability are configured redundantly.     while providing the optimum performance.
This covers any single faults in the control and pro-
tection equipment without loss of power.                   5.7.4.2 Dynamic Performance Test
                                                           The offline simulation with EMTDC is already an
5.7.3.2 Operator Training                                  extremely accurate forecast of the real system
For Siemens HVDC application, an operator training         behaviour. To verify the findings and optimize
simulator is optionally available. The simulator allows    the controller settings, the control and protection
the operator to train with the same hardware and           systems are additionally tested during the dynamic
software as in the real process. This simulator consists   performance test with a real-time simulator. During
of the original operator workstation and a simulation      that phase, the customer may witness these perfor-
PC. The simulation PC runs the HVDC process and            mance tests of the final control and protection
feeds the relevant data to the workstation.                software.
                                                                                                                 43
                                                                                         5.7.4.4 On-Site Tests
                                                                                         On-site tests are basically divided into test steps
                                                                                         regarding the related station (station A, station B)
                                                                                         and into the test steps related to the whole HVDC
                                                                                         system.
     Fig. 5.7.1-10: The main steps for the HVDC control and protection versus the time starting from the contract award
     up to commercial operation
44
6 System Studies, Digital Models,
Design Specifications
6.1 System Studies                                          6.2 Digital Models
During the planning stage of a HVDC project, prelimi-       Digital models of HVDC system can be developed
nary studies are carried out in order to establish the      according to the specified requirements. Typically
basic design of the whole HVDC transmission project.        a digital model of dc system is needed for a specific
This includes the co-ordination of all relevant technical   load flow and stability simulation program, while
parts of the transmission system like HVDC converters,      another digital model is required for simulation in
AC and DC overhead lines as well as the submarine           a typical electromagnetic transients program such
cable, if applicable. All specified requirements will be    as EMTDC. The functionality and settings of HVDC
taken into account and are the basis for the preliminary    control and protection system will be represented
design of the HVDC transmission link. In addition,          in a proper manner in such models, which allow
special attention is paid to improving the stability of     suitable simulation of steady state and transient
both connected AC systems. Several additional control       behavior of HVDC system in the corresponding digi-
functions like power modulation, frequency control          tal programs. Digital models consistent with the
and AC voltage limiter can be included in order to          actual dc control and protection system are benefi-
provide excellent dynamic behaviour and to assist           cial both for the operation of the HVDC scheme and
the AC systems if the studies show it necessary. Sub-       for the network studies including DC link. Typically
synchronous oscillation will be avoided by special          such models can be developed on request in the
control functions, if required. All the AC system con-      detailed project design stage when all major design
ditions and the environmental conditions as given           works of control and protection functions are
in the relevant documents will be considered in the         completed.
design calculations. The final design of the HVDC
transmission system, including the operation charac-        6.3 Control and Protection Design Specifications
teristics, will be defined during the detailed system       Design Specifications are written for the control,
studies. All necessary studies are carried out to           protection and communication hardware and soft-
confirm the appropriate performance requirements            ware. The control panels are then designed, manu-
and ratings of all the equipment. Due consideration         factured inspected and tested in accordance to the
is given to the interaction with the AC systems on          design specification. The software for the control
both sides, the generation of reactive power, system        and protection is also written in accordance to the
frequency variations, overvoltages, short circuit           design specification. It is tested using real time
levels and system inertia during all system                 simulators in the dynamic performance test and
configurations.                                             functional performance test.
Typically the following studies are carried out:            Specifications for the topics below are typically
a) Main Circuit Parameters                                  written:
b) Power Circuit Arrangements                               a) General Control and Protection
c) Thermal Rating of Key Equipment                          b) Interface Systems
d) Reactive Power Management                                c) Station Control
e) Temporary Overvoltages                                   d) Diagnosis Systems
   and Ferro-Resonance Overvoltages                         e) Pole Control
f) Overvoltage Protection                                   f) HVDC Protection
   and Insulation Coordination                              g) AC Protection
g) Transient Current Requirements                           h) Metering and Measuring
h) AC Filter Performance and Rating                         i) Operator Control
i) DC Filter Performance and Rating                         j) Communication
j) AC Breaker and DC High-Speed
   Switch Requirements
k) Electromagnetic Interference
l) Reliability and Availability calculations
m) Loss Calculation
n) Subsynchronous Resonance
o) Load Flow, Stability and Interaction
   between different HVDC Systems
p) Audible Noise
                                                                                                                    45
     7 Project Management
                                                                     Transient Network
                                                                         Analyser
                                          Civil Engineering                                     Commercial
                                                                        Functional
                       Main                                          Performance Test
                                          Civil Construction
                    Components
                                                                      Commissioning
                                             Installation
                                                                      Communication
                                                                         Systems                 Financing
46
7.1.5 Scheduling                                       Deadlines for project decisions – especially those of
The hierarchically structured bar-chart schedule       the critical path – can easily be identified enabling the
is a high-level control tool in project management.    project manager to make up-to date pre-estimates
The clear structure of sequential processes and        and initiate suitable measures in due time.
parallel activities is crucial for execution of a 24
to 36 month duration, according to the project
requirements.
Activity Time
Award of Contract
 Engineering/System
 Studies
Manufacturing
Transportation
 Erection &
 Precommissioning
Station Tests
System Tests
 Commercial
 Operation
Fig.7-2: Structured bar-chart timeschedule
                                                                                                                   47
Published by and copyright © 2011:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens AG
Energy Sector
Power Transmission Division
Power Transmission Solutions
Freyeslebenstrasse 1
91058 Erlangen, Germany
www.siemens.com/energy/hvdc
Printed on elementary chlorine-free bleached paper.     Subject to change without prior notice.
                                                        The information in this document contains general
All rights reserved.
                                                        descriptions of the technical options available, which
Trademarks mentioned in this document
                                                        may not apply in all cases. The required technical
are the property of Siemens AG, its affiliates,
                                                        options should therefore be specified in the contract.
or their respective owners.