E70-905 WP/APR 2002

File: EQUIPMENT MANUAL


Replaces: NOTHING (New Information)

Liquid Injection Oil Cooling


of Frick® Screw Compressors

By: J. W. Pillis
Director of Frick Engineering
YORK Refrigeration

Presented: Frick® Factor Sales Meeting


2002 Annual Meeting
March 14, 2002

Liquid Injection Oil Cooling of Frick Screw Compressors

J.W. Pillis, Director Frick Engineering

One of the primary advantages of screw compressors over reciprocating compressors is


the inherently low discharge temperatures achieved with screws due to oil injection into
the gas stream during compression. This allows screws to run at high compression
ratios without approaching temperatures which could shorten the life of the oil or
materials of construction of the compressor.

The use of oil injection does however shift a portion of the heat of compression from the
discharge gas to the oil circuit, requiring that oil cooling of some type be used to reject
the heat.

Water or glycol cooled oil cooling is used to cool the compressor oil in a heat exchanger
through contact with water or glycol circulating to a cooling tower. Thermosyphon
cooling systems reject the oil heat through a heat exchanger that is evaporating liquid
refrigerant and rejecting the generated vapor to the system condenser.

Liquid refrigerant injection systems cool the oil in the compressor package through
direct contact of liquid refrigerant with the hot oil and gas being compressed in the
screw compressor. In effect, the compressor is treated like an evaporator, with liquid
sprayed directly into a trapped pocket in the compressor, part way through
compression. The direct contact of the liquid droplets with the hot oil or gas will change
the state of the refrigerant from liquid to vapor, absorbing the latent heat of vaporization

Page 1 of 10
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 2 of 10

of the liquid in the process. Because heat transfer is not instant, much of the injected
liquid will travel down the discharge line while being mixed with the oil and discharge
gas, giving time to vaporize the liquid refrigerant. The oil separator will come to an
equilibrium temperature set by the temperature setting of the liquid expansion control
device where the discharge gas, the oil, and the vapor from the expansion of the liquid
are all in equilibrium at the desired discharge temperature. Any reasonable discharge
temperature is achievable by the injection of a larger or smaller quantity of liquid. In
general, the discharge temperature is chosen by the desired oil temperature needed for
injection of oil to the compressor.

Sporlan thermal expansion valves have been used as the expansion device for liquid
injection systems for many years. They are simple, durable and low in cost. They do
however bring with them some inherent weaknesses that must be understood in order
to have systems that function acceptably.

Cross Section of Sporlan TXV

Conventional expansion valves utilize a refrigerant liquid filled bulb attached to a


capillary tube in order to sense the temperature after the evaporator. These systems are
generally used to control the amount of expanded liquid based on maintaining a fixed
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 3 of 10

superheat at the evaporator outlet. Screw compressor liquid injection systems are a bit
different in that a fixed discharge temperature is normally desired, not a fixed superheat
at the measuring point. For this reason the TXV’s used for liquid injection generally use
an external equalizing line that is set with a pressure regulator to establish a fixed
“balance pressure” below the TX valve head, instead of the equalizing pressure being
tied to the evaporator pressure as on conventional evaporator TXV’s. Adjustment of the
desired screw compressor discharge temperature is achieved through the setting of the
pressure in the TXV equalizer line.

A particular charge of refrigerant in the capillary bulb will vaporize at the temperature
outside the bulb, and establish the saturation pressure of the fluid used inside the bulb,
and above the TXV head where it is connected. Sporlan offers a variety of different
refrigerant charges in their standard TXV lines. The relationship between the equalizer
pressure that is set and the temperature where the valve controls is quite different with
the different charges. See figure A.

Control Fig. A
Temp. F Sporlan valves
210
1199
190
170 1200
150 1201
130 1202
110 764
90 830
70
0 50 100
Regulator psig

The valves fall into two basic families based on the refrigerant charge in the TXV bulb.
The conventional valves used for many years for liquid injection oil cooling used either
the 764 or 830 charge. With a nominal 75 psig pressure set at the equalizer line the
control temperature of these valves is in the 110° to 120° degree F range. Because the
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 4 of 10

Sporlan pressure regulator normally used to establish the equalizer pressure has a
maximum adjustment pressure of 80 psig, it is normally impossible to adjust the control
temperature on these valves much above 130°F. If a different, (non-Sporlan), regulator
is used it is possible to adjust these valves somewhat higher in pressure. However,
even at 100 psig the control temperature is only about 140°F and still too low to be
optimum on the HFC gases or some NH3 applications.

Switching the charge in the bulb to the other family, (1199-1202 charge), makes it
possible to adjust the control temperature much higher. For example, looking at the
1200 charge curve, we see that at 75 psig equalizer pressure the control temperature is
about 200° F. This unfortunately is too high to be optimum for most screw compressor
applications. To establish a control temperature of approximately 165° F, which we
consider optimum for HFC applications, the control pressure needs to be set at
approximately 30 psig. For reference NH3 Liquid Injection Systems are normally run
from 140° F to 165° F discharge temperature. This lower control pressure is ideal for
booster screw packages where now the hot gas source can be taken directly off of the
booster discharge pressure without the necessity to run high stage discharge pressure
to the TXV just to get 75 psig, for the equalizer line. Most boosters will operate below 75
psig discharge. With the lower pressure requirements of these valves a regulator
pressure down to 10 psig is still suitable to adjust the control temperature to about 140°
F. Elimination of a small hot gas line in the engine room just to the TXV equalizer line
allows elimination of a potential leak source, sometimes running hundreds of feet from
wherever the closest high-pressure source is found.

These higher temperature valves cannot be used in all cases. In systems where the
suction pressure is higher than 30 psig, (15° F on NH3), the control temperature cannot
be adjusted down below about 170° F because there is no lower pressure in the system
to allow adjustment of the equalizer pressure. For higher evaporating temperatures the
low temperature charges must be used in the TX valves.

Some people have questioned why compressors were run at nominally 120° F liquid
injection temperatures for so many years but now they can be run higher. In fact the
main consideration in setting the discharge temperature, (and the oil temperature) is the
oil viscosity coming back to the compressor bearings. Because Frick screw
compressors use all anti-friction bearings, the oil viscosity requirements are generally
lower than sleeve bearing compressors that our industry grew up with. Operating on
NH3, or any of the common HFC's and R22, we can achieve more than adequate
operating viscosity at a 165° F control temperature using 68 ISO oils, even with the
effects of dilution. It is possible to operate Frick screws up to 240° F oil temperature, as
long as an oil is chosen with adequate operating viscosity at the higher temperature.
Consult the factory for additional information on this issue.
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 5 of 10

Performance penalties

One of the greatest drawbacks to the use of liquid injection oil cooling is the fact that it
can severely impact the overall efficiency of the compressor. Injection of liquid
refrigerant into a screw compressor impacts performance in several ways. First, as the
liquid comes through the expansion valve, a percentage of the liquid will be changed
immediately into vapor. Injection of more vapor into the screw compressor takes more
power to compress from the injection point to discharge. In addition, the liquid that is
injected will mix with the oil injected into the screw threads. A portion of this liquid will
leak from higher-pressure threads to lower pressure threads as it is carried through the
compression process. This leakage occurs around the rotor tips, over the end faces of
the threads, and through the blowhole between the rotors back into the open suction
cavity. Any time liquid leaks from high pressure to low, a portion of the liquid will flash to
vapor. If the flash vapor is into a lower pressure trapped thread, power will again be
required to compress the vapor from the early threads back to the discharge from the
machine. If the flash vapor is generated in the suction cavity, it will take up space that
could have been filled by suction charge from the evaporators. This decreases the
suction capacity of the compressor, but not the power, as the screw threads are still
being filled with the same amount of vapor, just not from the evaporator.

Performance Penalty Factors


Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 6 of 10

Recognizing the source of the power and capacity penalty gives some possibilities to
reduce the penalties. The first principal to reduce the performance penalties is to put the
liquid into the compression as late as possible. If it comes in late, it has further to leak to
suction, and the vapor is generated in later threads, where it does not have to be
compressed as far to get to discharge.

The second principal to save power is to inject less liquid. Raising the liquid injection
temperature can significantly reduce the quantity of injected liquid. When compressing
dense gases with low heat of compression, a 170° F liquid injection temperature can
totally avoid a liquid injection penalty at full load. In the case of R-507, R-404a or R-
134a at higher suction temperatures, a 170° F injection temperature can avoid a liquid
injection penalty down to very low slide valve percentage, as no injection is needed to
maintain the desired discharge temperature. On ammonia applications a higher injection
temperature will in some cases reduce the performance penalty by 0.5 to 1.0%.

Port pressure

The liquid used for injection generally comes from the high-pressure receiver. A
pressure difference is needed to drive liquid into the compressor. In order to minimize
power, the liquid should be injected as late as possible, but in order for a Sporlan TXV
to work it needs a minimum of about 55 psi pressure difference across it. The liquid
injection ports are located in the compressor at fixed positions, which means the
pressure measured at any port is a fixed function of suction pressure, see Figure "B" for
the standard low vi port, (SL-1 Port).

Fig. B
Port Pressures

200.0
Port Press (psia)

150.0

100.0 Low Vi

50.0

0.0
0 20 40 60 80 100
Suct. Press (psia)
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 7 of 10

In order for Frick to apply liquid injection in any application, we consider the highest
suction and lowest liquid source pressure to be sure there is 55 psi of pressure
difference available across the TXV. For example; at a suction pressure of 40 psia, the
SL-1 port pressure is 90 psia, plus the 55 psi needed for the TXV gives a minimum
liquid pressure needed of 145 psia; approximately 77° F minimum condensing
temperature. If the head pressure on the job falls below 77° F condensing the liquid
injection will stop feeding, and the compressor will get too hot. If this job is specified to
have a 65° F minimum condensing temperature, (103 psig), the low vi injection port will
not work all the time.

For the above reason all Frick compressors are equipped with four different ports, at
varying pressures, that can be used for liquid injection. In the above case with a 103
psig minimum condensing temperature, we need 103 minus 55 psig, or 48 psig port
pressure maximum to allow liquid to feed. Looking at figure "C" it is evident that even
piping the liquid to the economizer port will not give a low enough port pressure to allow
successful operation. Piping the liquid to the closed thread port however will allow
successful operation even at the 65° F condensing temperature.

Fig. C
Liquid Inj. Port Pressure
300

250

200 closed thd


Port
Psia econo
150
lo vi
100 hi vi

50

0
0 50 100 150 200 250
Suct Psia
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 8 of 10

Fig D - Minimum allowable Head Pressure


giving 55psia delta P across TXV

190

170

150 closed thd


Cond. Psia

130 econo
lo vi
110
hi vi
90

70

50
0 20 40 60 80 100
Suct Psia

Figure “D” shows minimum allowable head pressure when injecting to any of the
available ports using a Sporlan Valve.

Dual Automatic Liquid Injection

The earlier that liquid is injected into the compressor the more performance penalty will
be recognized. Using the closed thread port will allow the system to operate at the high
suction and low condensing condition; however, if the head pressure returns to normal
levels most of the time, say 95° F condensing (181 psig), the higher pressure low Vi
injection port will work and minimize the power penalty.
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 9 of 10

It would waste excessive power to permanently pipe the liquid to the closed thread port
just so the system would work at the low head condition, which might only occur a few
days of the year. Eliminating the excessive power penalty, while still allowing the low
head operation is the purpose of Frick's patented dual port liquid injection system.

Frick installs dual liquid injection on applications with varying conditions, where energy
can be saved by using a lower port pressure when needed, but switching back to a
higher port pressure when it will start to feed again. Frick is the only manufacturer to
offer a system like this. At the time of the order entry the conditions are reviewed and if
energy can be saved with dual port liquid injection we use it as our standard system.
Our competitors only pipe to a low port pressure, and the customer pays the excessive
power penalty every day of the year that the head pressure is at the higher level.

With dual liquid injection operating, the liquid will be expanded normally through the
TXV, but after the TXV enters a full ported spool valve that will divert the liquid to the
most efficient liquid injection port that has adequate differential pressure to allow proper
feed. The changeover signal is generated in the micro panel based on the volume ratio
the compressor is running at any time. This system is saving thousands of horsepower
today in plants around the world.

Jordan liquid injection valves are sometimes applied instead of Sporlan TX valves.
These are primarily used on very large systems where the valve capacity exceeds the
normal Sporlan sizing. They are also sometimes applied in systems where the 55psi
differential requirement cannot be met, even with the lowest available compressor port
location. The Jordan valve only requires about 20 psi differential pressure instead of 55
psi, and will sometimes allow liquid injection to be successfully applied on applications
with very low operating differential pressures.

Easy CoolTM

Frick's latest innovation in liquid injection systems is the new Easy CoolTM liquid injection
system. This system replaces the Sporlan TXV and the Jordan valves with a motorized
expansion valve, controlled directly out of the Quantum panel. Easy CoolTM eliminates
the need for different bulb changes in the TX valves, setting of regulators for
temperature setting, and changing of the valve size and discharge tubes in the TX
valves for relatively small changes in design load. With Easy CoolTM liquid injection,
adjustment is completely controlled in the Quantum panel. You can set the control
temperature as easily as setting suction temperature. Because the valves have much
better regulation than the Sporlan valves, they are usable down to 20-psi differential
pressure instead of the 55-psi limit. More information on this new innovation will be
forthcoming in the near future, but it is available for delivery now. After reading this
Liquid Injection Oil Cooling of Frick Screw Compressors
J.W. Pillis
March 14, 2002
Page 10 of 10

paper and understanding some of the complexity of applying liquid injection systems it
is clear that it is time for Easy CoolTM.

Easy Cool TM

Liquid Injection System

File: Liquid Injection Oil Cooling 2002.doc