0% found this document useful (0 votes)
214 views396 pages

Wiegand Volume 02

Uploaded by

moin shafiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
214 views396 pages

Wiegand Volume 02

Uploaded by

moin shafiq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 396

3]

CD
W I E G A N D ro
WIEGAND
File1 Files
1 Operating Instructions Evaporation 20 Maintenance Instructions
Plant for Foxboro Instruments
2 Erection Drawings No.
763/764/765/766-303-0
3 Flow-sheet No.
513/515-302-0 File 4
4 Maintenance Instructions SIHI 21 Maintenance Instructions
Vacuum pump Bran + Lubbe pump
5 Maintenance Instructions Hilge 22 Conductivity Controller
Centrifugle pumps Condensate tank SPIRAX
6 Maintenance Instructions 23 Hicon Conductivity Controller
Mono pump Nezch Rosemount
7 Maintenance Instructions GEA 24 pH Controller Wiegand Evap
Ahlborn heat exchangers Endress&Hauser Mypex
8 Maintenance Instructions 25 Pressure Transmitter 2088G
Schiele Fan Rosemount
9 Maintenance Instructions 26
Alfa Laval LKM Valves
27
File 2
28
11 Installation, Assembly &
commisioning of controls 29
12 Parts list of control
systems
13 Drawings of control
systems
14 Taylol

15 Keystone

16 Valmet

17 Samson

18 Fisher Gravitrol

19 Berthold
11
Erection, installation and
Commissioning of the Control
Karlsruhe GmbH System
0-7505 Ettlfngen

The erection, installation and commissioning of the control


system is only part of the WIEGAND supply if this was "explicit-
ly mentioned in the confirmation of order. The same applies
for all electric instruments as well as for the pump motors.
If this was not especially agreed upon, it will belong to
the customer's supply in any case.

general (Control Elements)


The control elements (control valves acd control flaps)
are mostly mounted together with the evaporating plant.
In doing so, the following will have to be checked and
observed:
a) correct installation, according to the flow direction
marked on the outside,
b) nominal widths of flow of the pipings are mostly
larger than those of the control elenents
c) the control elements have to remain free from inside
contamination
d) the piping will have to be supported such that the
control elements can be installed and removed without
problems
e) note the input section on the erection drawing if
indicated by us

B) PRECISION CONTROL INSTRUMENTS


i The installation of precisioit control instruments, such
as transmitters, sensors, and pontrollsrs should only be
started after completion of . all construction, painting
and rough locksmith works in the, evapcarator room and
after removal of all scaffolds ,' in order to avoid damages,

I- Transmitters (measuring transducer^ Sensors


In this connection, please note the indications on our
drawings. The instruments will have to be installed
free from vibrations close by the measuring section.
The connection between measuring point and transmitter
is called pulse line.
Important;
1. provide a syphon for the steam pressure transmitter
2, do not provide a syphon for the vacuum transmitter,
install it lo cm above the measisring point (pulse
line being a copper tube of 12 Em length) . Lay this
tube with an inclination to the measuring point.
For both a.m. transmitters a shut-off cock will have
to be mounted in the pulse line. Do not brace measuring
point and transmitter with the pulss line. Leave sorre.
space for a later insulation.

Datum: 27th Nov, , 1975 Bearbeitung: Hl/Fe/Cr/iMa JBsehen:


P tC.!! UK Q
page 2

Erection, Installation and


Karlsruhe GmbH Commissioning of the Control
D-7505 EtUtngen System

3. Install the temperature transmitters, sensors


in reverse current and dip thera into the liquid flow
in their total length.
4. Screw in the electric resistance thermometers
with special care.
5. The flowmeter will have to be absolutely mounted
with the fixings provided for and in accordance
with our erection drawing. In any case, it has to
be avoided that pre- or subsequently arranged
tube sections are fixed at the flowmeter. If necessary,
these tube sections have to be fixed separately.
There must be the possibility to install and remove
the flowmeters quickly and without problems, without
impairing pre- or subsequently arranged tube
sections.
6. Screw in and tighten the conductivity measuring cells
in the tube bend as indicated.
Attention: Do not turn the electric connecting head
of the measuring point- (danger of damaging
it) . Only use existing hexagon.
7. Density measuring instrument
It is of particular importance that no vibrations
are transmitted by the pump which ,is normally pre-
arranged. If this is not possible, flexible
connections will have to be provided for. Density-
meters will have to be fixed to a firm foundation.
Compensators of oscillation are not allowed.
»

All places of installation/of transmitters have to be


checked on that
a) no impairment of the instruments can take place by
dripping and splashing'liquids or steam,
b) they are mounted outside areas which are frequented
by public or the opiating personal.

Datum: 27th Nov., 1975 Bearbeltung: Hl/Fe/Cr/Ma sesohen:

F 26/4.75/3000 .B.
page 3

Erection, Installation and


Karlsruhe GmbH Commissioning of the Control
0-750S Ettllngen System

II. Control Panel

1. The control panel v;ill have to be mounted on


the foundation prepared by the customer.
The control panel is to a large extent pre-
assembled, pneumatically tubed and electrically
wired.

2. The WIEGAND supply contains the following


control instruments which, for reasons of
transportation can only be mounted into the
control panel on site:
- compact indicator
- compact controller
- six-colour point printer
- three-line recorder
3. These instruments will have to be inserted and
clamped in t>E control panel with the aid of
the control panel drawing. Make the connections
between the indicators, controllers, six-colour-
point printers and line recorders and the lines
pre-assembled in the panel from the pneumatic
and electric connecting block to the controllers.
Use our drawings for this purpose.

C) AIR SUPPLY (Pneumatics)


1. Connect ion, compre ssor with supply a ir reduc ing
station and filter station.
A suitable, accessible 'space outside the control
panel has to be chosen for the air reducing station.
Please note that air will have to be conveyed
directly from the supply air reducing station into
the control panel and into the plant. The connection,
compressor with supply air reducing station will
have to be laid by t^e customer using a metal tube
of 1/2

2. Connection, air reducing station with the control


panel will have to be carried out by the customer,
using a metal tube of 1/2" or a plastic hose which
is resistant to compression (10 atue).

3. Connections, air reducing station with air


distributor for transmitters, change-over valves
and positioner controllers at the controlling units
have to be made as described under paira: 2.
4» Connections of the pneumatic connecting block
in the control panel with the control valves and
transmitters as well as change-over valves

Datum: 2 7 t h Nov., 1975 Bearbeitung: m / p e / C r / M a gesehen;

F 26/4.75/3000 .B.
age 4

Erection; installation and


Karlsruhe GmbH Commissioning of the Control
D-7505 Ettllngen System

a) with small plants concerned, individual lines


will have to be laid, see pneumatic diagram
b) with bigger plants concerned, the pneumatic
multi-strand collective cable from the control
panel to the individual air distributors in the
plant will have to be used.

Note ; We recommend to lay the spare circuits at the


same time.
- supply air distributors (see para 3) and signal
air distributors will have to be mounted on
a protected spot in the plant and must be
easily accessible.
- they should, be arranged close by each other
- when chosing their location, one should
take care that the connecting lines with the
transmitters, change-over valves and control
elements are as short as possible.

5. The connecting lines between supply air distributors


(feed air for the transmitters) will have to be
inserted, consisting of a plastic hose, 1/4" and
6 mm, of blue colour. At the same time, the signal
lines between the transmitters and the signal air
distributor will have to be inserted, consisting
of a plastic hose, 1/4 " and 6 mm, of black colour.

6. Make the connections ^tween signal air distributor


and control elements (control valves, control flaps),
change-over valves by means of a plastic hose of 1/4"
and 6 mm, of red colour.
At the same time, the ;feed air supply lines for the
positioner controllers at the control elements will
have to be laid. Here too, a plastic hose of 1/4"
and 6 mm, of blue colour, will be used.
a) If there is no sCipply air distributor for the
positioner controllers in the plant, the air
is directly taken from the air reducing station,
see the pneumatic diagram for this purpose.
b) If there are several positioner controllers,
a separate supply air distribution is provided
for (in addition to the two distributors
mentioned under para 3 and 4b) .

Datum: 27th NOV., 1975 Bearbeitung: Hl/Fe/Cr/Wa gesehen:


F 26/4.75/3000 .B.
page 5

Erection, Installation and


Karlsruhe GmbH Commissioning of the Control
D-7505 Ettlingen System

D) E^RECTIQN OF THE ELECTRO PART


If not especially agreed upon, these works do not form
part of our scope of supply

In particular, the following will have to be installed


(according to the electric and pneumatic WIEGAND diagrams) ;

I. General
1. Connecting lines between the electric panel part
(contactor panel) and the p\amp motors of the
evaporating plant•
2» The connecting line between the electric panel part
(contactor panel) and the. fan motor of the cooling
tower, particularities of installation of the stator
heating of the motor will have to be observed.
3. The connecting line from the electric panel part
(contactor panel) to the cooling tower heating
(for this purpose, please see our electric wiring
diagram) •

4. The connecting line from the electric panel part


(contactor panel) to the bowl heating thermostat of
the cooling tower and to the fan motor thermostat.
The former will be fixed in the cooling tower' bowl
and prevents the cooling water from freezing, the
latter should be fixed to an outside wall of the
cooling tower building* The stator heating will be
brought into action at an outside temperature of
- 15
5. The control lines from the WIEGAND control panel
to the electric panel part (contactor panel) for the
pump motors.
6. The connecting line t^tween water-flo\>? detector after
the sealing water tanTc and the control panel.

7. Connecting lines between control panel and damp proof


distributor cap within the evaporating plant,
connecting lines between distributor cap and
illuminating hoods for the separator illumination.
8. The electric measuring lines of the resistance
thermometers to the control panel. For this a copper
wire, twined, 2 x 1,5 mm^, will be required. The
lines will have to be equalized (in this connection
please see the operating instructions of the
electric temperature recorder).

Datum: 27th NOV., 1975 Bearbeitung: Hl/pe/Cr/Ma gesehen:


F 7fi/!«VVl W R
page 6

Erection, Installation and


Karlsruhe GmbH Commissioning of the Control
0-7505 Ettllngen System

!!• If provision is made for an electric control system

1. Lay the connections, transmitter with control


panel by^means of twined copper wire of 2 x
1,5 mm^.
2. If pneumatic valves with electric positioner
controllers are applied, twined copper wire,
2 X 1,5 mm^, will have to be laid for each
positioner controller from the connecting block
in the control panel to the individual positioner
controllers at the pneumatic valves.

3. care has to be taken that the signal lines


from the transmitters to the connecting block
in the control panel and from the connecting
block in the control panel to the valves are
laid in steel-armoured conduit and that no
power circuits are nearby which might cause
inductive voltages.

4. If electric control valves are used a four-strand


line will have to be laid in addition from the
control panel to the control valves. This is a
power circuit, the cross section of which will
have to be selected according to the respective
drive.

Datum: 27th Nov. , 1975 Bearbeitung: Hl/Fe/Cr/Ma gesehen:


Erection, Installation, and
Karlsruhe GmbH commissioning of the Control
D-7505 EtUingen System

page 7
COMMISSIONING
As soon as the erection of the measuring and control in-
struments as well as the supply air reducing station and
the individual air distributors is completed and all con-
nections are made, the commissioning will be started.
The following sequence shall be kept tO:

I. Checking of the Air Supply

1. The connections between the air reducing station and


the control panel will be loosened at the air dis-
tributor in the control panel. The same is done with
the individual connections at the air distributors
in the plant.

2. Start the compressor and let the air blow for about
3 hours, so that the supply air piping will get clean.
Attention; Avoid that oil containing air gets into
the control instruments when you start the
system. This would make necessary consider-
able repairing works.

3. Tighten the loosened unions again.

II. Adjustment of the Air Supply (Supply Air at the Air


Reducing Station) »
«

The individual instruments'have to be supplied as des-


cribed below:

1. Positioners at the control valves with 2.5 atm.g.


2. Change-over and spray cleaning valves with 4 atm.g.
3. Pressure, absolute pi'essure, and temperature trans-
mitters, density me^uring instrument, flowmeter, and
controllers with 1.35 - 1.4 atm.g.

Attention: These values must individually be checked


at the input of the respective instruments
by means of a hand manometer (loosen the
supply air line at the individual instru-
ments) .

III. Preparation of the Control System (Positioners, Trans-


mitters, and Controllers) for the Start-up
1. Adjust all controllers to manual operation. Remove
the transport safety devices in the controllers, trans
mitters, densitymeter, and flowmeters as described in
the attached operating instructions.

Datum: 2 7 - 1 1 - 1 9 7 5 Bearbeitung: Hl/J'e/Cr/Schm gesehen: p.t.O.


page 8

Erection, Installation, eind


Karlsruhe GmbH Commissioning of the Control
D-750S Ettllngen System

2. By means of the manual controllers of the individual


auto-manual stations at the controllers the respective
valves are passed in the whole range. That means, a valve
for steam has to be closed when the control capacity is
O %, it has to be open by 50 % when tlie control capacity
is 50 %. The control capacity is adjusted at the manual
controller of the auto-manual station.

3. When the control elements are. equipped with positioners


the positioners must be checked according to the operating
instructions attached and, if necessary, they must be re-
adjusted. It has to be taken care, that the closing and
opening velocities of the control elenents with positioners
are the same. This can be regulated at the spring tension
for the control element.

4. When the controUers are adjusted to "manijal", the valves must


be checked as follows:
a) Manual controllers at the controllers to 50 %. The valve
must be opened by 50 %.

b) Repetition at O % and lOO With O the valve must be


closed and at 100 % it has to be completely open. This
applies to the steam valve only. As far as the other valves
are concerned, you will have to look at our drawings for
the control technique where we stated the required safety
positions of the valves; i.e. whether the valve has to be
closed without pressure or opened without pressure.
»

5. If the values stated under item 3 cannot be repeated, please


check:
/

a) the control capacity output'of the controller - this out-


put must be measured directly before the valve.
b) If a) is correct, check th^ control element.

Datum: 27th NOV. , 1975 Bearbellung: H l / t ' e / C r / S c h m sesehen: p.t.O.


F 26/4.75/3000 .B.
page 9

Erection, Installation, and


Karisruhe GmbH Coiranissioning :bfr the Control
D-750S Ettllngen System

Start-up of the Plant


Now everything is ready to start the measuring and control
system of the plant.

When you start up the plant, you have to take care that the
rectifiers of the indicating instruments and the motors of
the recorders are supplied with electricity and that all the
controllers are switched on manual operation. Now the plant
can be started on water.(see general operating instructions
for the evaporator) .

I With the manual controllers at the individual controllers


the valves will be adjusted in such, a way that the
required values for steam, pressure, temperature, and
feed are obtained. As soon as those; values are obtained,
and after' a time of about 10 minutes, the set-point de-
vices will be adjusted in such a way that the output
signal of the controller equals the output signal of the
manual controller.is giving to the valves. Those figures
will be indicated at the controller. •

II. Criteria for the adjustment of the controllers

steam pressure control loop - proportional range = 80 %,


reset time: 0.2 min.
vacuum control loop - proportional range = lOO %,
reset time: 0.5 min.
temperature control loop - proportional range = 80 %,
reset time: 1.5 min.
feed control loop - proportional range = 100 %,
/ reset time_^ 0.3 min.
level control loop - proportional range = 50 %,
reset time: 1.0 min.
concentration control loop - proportional range = 400 %,
reset time: 6.0 min.

Datum: 27 th NOV., 1975 Bearbeitung: Hl/Fe/Cr/Schm gesehen: p. t.O


F 2E/4.7S/;a» w a
page 10

Erection, Installation, and


Karlsruhe GmbH Commissioning of the Control
D-7505 EMIngen System

III After the adjustment of the approximate control para-


meters stated under II, the manual-automatic switches
at the individual auto-manual stations will be manually
switched over to automatic.
Attention; When it is switched over from manual to auto-
matic, the actual values^ and the set-points
must correspond; if they do not correspond,
the direction of the action has to be changed,
as described in the instructions for the spe-
. cific instrument. If there are still differen-
ces between actual values and set-points with
correct direction of the action, the zero points
at the controllers must be changed as per oper
operating instructions for the controllers.

IV When this has been done and when the temperatures in the
plant have reached the values specified, the product
feed can be opened and the plant is now run on product.

V The zero points for concentration end viscosity at the


respective transmitters (measuring transducers) can only
be adjusted during operation with product according to
measurements in the laboratory. That means for instance
for the concentration: a certain content of % TS will be
determined with the help of a pocket refractometer, If this
/ value corresponds to the vplue given by the indicator at
i the controller, it is moment;arily ijot necessary to correct
anything. If the controller-indication, however, differs
from the refractometer indication, it will be necessary
to correct the zero point at the transmitter (measuring
transducer) according to tHe instructions for the parti-
cular instrument.
Example: by means of the steam pressure the plant will
be run in such a way that an outlet concentration of
45 % TS which had been indicated on the refractometer
is obtained. After a period of aboat lO minutes, the dry
substance content in the product outlet shown on the in-
dication is still 45 The indication at the controller
itself, however, does only show 3 0 % TS. Now, it is ne-
cessary to correct the concentration with the zero-point
screw at the transmitter (measuring transducer) as des-
cribed in the instructions for the instrument, so that
the indication at the controller dees also state 45 % TS.
This can only be done, when the coatroller is switched
on manual operation.

The above-described correction can be repeated later,


i.e. it can be improved by comparisons with laboratory
measurements.

Datum: 27th NOV. # 75 Bearbeitung: Hl/t*e/Gr/Schra gesehen:

F 26/4.75/3000 .B.
page 11

Erection, Installation, and.


Karlsruhe GmbH Commissioning of the Control
D-7505 EUSngen System

VI It is a precondition for a correct operation of the


control system, that the optimum controller adjustments
are found and realized during the first operation,
(see enclosure) .

VII Optimum Controller Adjustment

1. For the adjustment of the controller to the control


section it is necessary that the preparations des-
cribed in the instructions "Erection, Installation,
and Commissioning of the Control System" are completed.

2. All the control instruments will be checked and cali-


brated by the different companies before they are supp-
lied. The calibration is an optimum 95 % calibration.
In most cases this is the best calibration possible,
because the calibration is done on a production line.
The calibration may afterwards be changed due to trans-
port and weather conditions. The basic calibration is
mostly sufficient, because the controller adjustment;
methods of today only give approximate values. As far
as control sections for which the normal basic calibra-
tion is not sufficient are concerned,- these may be
4th class.control secti6ns.-, it is necessary to carry
out a second optimum cali,bration. This has to be done
as described in the operating instructions for the res-
pective instrument.

3. Adjustment of the contfoiler to the control section


We know different methods of adjusting a controller to
the control section, toe of the most simple methods
which is mostly used is the method found by Ziegler
and Nichols. In the most cases, this method brings abou^
the success required. All the methods known give appro-
ximate values only, guaranteeing an optimum 90 - lOO %
adjustment, it may only be necessary to an unimportant
correction not requiring any considerable adjustment.
It is not possible to determine a 100 % adjustment of
the controller.
When the class of the control section shall be deter-
mined, one has often to rely on assumptions, so that
in practice there are only approximate reference points
for the adjustment available. Even, if the data for si-
milar sections are available, it may be necessary due
to differences which cannot be seen from the outside
' to have different adjustments of control sections which
are equal for the rest. The methods known up to
to adjust a controller to the control section have been

Datum: 27th Uovember, Tfeearbehung: Hl/Fe/Cr/Schm gesehen: p . t . O .

F Jfi/vinn vj n
page 12

Erection, InstaUaticsi, and


Karlsruhe GmbH Commissioning of the Control
D-7505 Ettlingen System

either been determined by calculaticQ or by tests with


certain control systems.

4. Method of Adjusting the Controller


The controller must function as a pire P-controller.
For that purpose, the Tn-throttle (integral action) has
to be closed and the Tv-throttle (derivative action) has to
be opened. If the derivative action is not existing, it
is not necessary to open the Tv-throttle. Subsequently
you adjust a larger P-range (proportional) of approximate-
ly 500 With this position of the controller, you
now have to cause a sudden disturbance by changing the
set-point. As a result of this action, the control value
(actual value) which has to be seen on the recorder,will
change. Shown in a sketch, this will presumably look
like.figure "a".

a)

Zeii t

b)

Zeii t

Then, the proportional b^nd will be changed in a down-


ward direction and a disturbance is repeatedly caused by
changing the set-point until the recorder fig. IVb" shows
the control value. Now, the criticciE P-range Xpk is reach-
ed- This critical P-range can be read at the P-range ad-
justment of the controller. The valce resulting will be
multiplied by two and , thus, the P-range to be adjusted
is determined.

The whole time for the curve Tk as shown on fig. "b"


will be multiplied by 0.85, thus, determining the reset
time Tn. To find out the D-action (derivative time) , Tk
will be multiplied by 0.5.

The above-described method should lead to a good adjust


ment of the controllers.

Datum: 27th NOV., 75 Bearbeitung: Hl/te/Cr/Schm 5>sehen: p.t .O


F 26/4.75/3000 V/.B.
Assembly, Installation, and
Karisruhe GmbH Coininissioning of the Control
D-7505 Ettlingen System

H) ASSEMBLY AND ADJUSTMENT OF POSITIONER CONTROLLERS


The positioner controller is a proportional follow-up
controller. The output signal of the process controller
is the input signal of the positioner and thus it can
at the same time be considered the nominal value for the
follow-up control loop - in our case the positioner con-
troller.

The positioner controller shall be installed as described


in the assembly instructions attached. The assembly in-
structions always refer to a certain make. When the
positioner controller is installed at .the correcting ele-
ment, it will have to be adjusted. Please follow the
below stated sequence.

1. Open the supply air valve and check the air pressure.
The correct supply air pressure can be taken from
the type plate of the respective instrument. If the
pressure is not stated, choose a pressure of 4 bar g.

2. The action type of the positioner controller depends


on the required safety position of the correcting ele-
ment .

3) The input signal for the positioner can either be an


electric or a pneumatic signal - depending on the con-
troller make installed. By means of the range and zero
point devices the positioner must be adjusted such that
the correcting element is closed or opened — depending
on the action chosen - by*25 % when the input signal
is 25 With an input sigr^al of 50 %, the correcting
element must be opened by 50 %. With an input signal of
75 %, the correcting element must either be opened or
closed by 75 % - depending on the type of action chosen
When the instrument is adjusted, check all fastening
elements once again and control the correcting range.
(For a better understanding, please see the explanation
to the diagram.;H = lifi: of the correcting element,
y = input value for the positioner. H + y indicated in
percent)

\
mu
M <n /
SchlieHventil
Bn \
\
Offnungsvcntil
closing valve 70 / opening valve
fiO \ /
50 \/
/ \
Antriebskennlinien
(Crundform I to
30 / \
characteristic curves
20 / \
\
of drive
( basic form) 10 /
/ \
Y inVo

Datum:19th Febr. , 76 Bearbeitung: Hl/wa/Schm gesehen:

F 26/4.75/3000 W
Assembly, Installation, and
Karlsruhe GmbH Commissioning of the Control
D-7505 EttOngen System

G) ASSEMBLY OF SHUT-OFF AND CONTROL FLAPS

General
Flaps will be installed between the tube flanges. As the
flap disc is centrically located, the flaps can be in-
stalled independently from the throughput direction. To-
tal solids containing media form exceptions.For those
media we recommend to install the flap with horizontal
shaft with the lower half of the flap opening in the through-
put direction.
If the seat ring of the flap is provided with a sealing lip,
which is simultaneously forming a flange joint, it is not
permitted to use additional flange gaskets.

Installation
The flap will be shifted inbetween the flanges? at this time
the flap is almost closed (30^) . The flanges should be
drawn asunder so that the flap can easily be installed with
clearance. Afterwards, the. flange screws will be inserted
and the flap centered as well as adjusted. After a test
switching the screws will be tightened. .At new plants the
screws will have -to be tightened by hand and the flange
pinchwelded. The flap will then be dismantled again and
the flange weld completed. Only after the flange has cooled
down, will the flap be assembled again between the flanges.
Before the flange screv/s are equally tightened, a test
switching shall guarantee that the flap disc can move in the
connection flange. Orientatibn means are key surfaces and
the feather nut of the flap sh'aft resp., they must always
lie in parallel to the flap disc.
X ' .

Einbaudar s t e d u n g view of I n s t a l l a t i o n
Kloppe 30® gebffnef flop opened

Datum: 19th Febr. , 76 Bearbeftung: Hl/Wa/Schm Sdsehcn:

F 26/4.75/3000 W.B.
/
12
Benennung: wiisGj-Aisri^
description: Karlsruhe GmbH D-7005 Eitlmcen
Mef3-_und Regelstuckliste Kom. 2 5 9 0 - 7 5 - 8 3 . 0 1 ,, ^
Job No. 520-83-83.01
|| ^iece l i s t for measuring and control equipment
Blatt: « voni
poge: ' . of:

Proj. I n q . Bearbeiter Datum: Zeich. Nr.


Engeinardt responsible: Hellmutl date 7/11/84 drwg. no. . 157-393-4

Schrankausfuhrung: L^Wieqcnd Lager , . . o


B'bestellt [r^oex unter Bemerkung •
execution of the poneh
Steuerspannung- FlieBbild: Z e i c h n u n g Nf; .-ioj^-rfTL
control voitnae: mimic dioarom: drawing no.: ^^^^..jiecr U
Betriebsspannunq; Elektr. B e d i e n u n q s e l e m e n t e :
operation voltage: electn switches and Buttons:
Zuluft: Besonderheiten:
inlet oir- porticularities-
Anderung Datum Kommission Bearbeiter Blott
alteration dote Job No. responsible page

pos, Stuck Benennung Blatt Zeichnung Lieferung 1


item quty description page drcwinq supply j

PIC 1 main.steam control


FIC 2 feed control

TIC 3 temperature control

1
TIC 4 temperature control

PIC 5 vacuum control

Die 6 concentration control

Lie 7 level control '^ecsuj^

float balance tank

TR 8 temperature recording

{!
Bc-nenr.ung
descripfion Knrlr.fu^3 GmbH D-7:.0"r
M e n . und R eg e I si uc kl isfe Kom. 2 5 9 0 - 7 5 - 8 3 . 01
Job No. 520-83-8 3.01 Maelor
.piece list for measuring and control equipmenf
Blaft
pnge
Proj. Ing. Bearbeiler Dafum Zeichn. Nr.
-Sngjelhaxdt- L^EE^jieJJjnuJ^ij^^ no. 157-393-4
Pos. Siuck Benennung Blatt Zeichnung
item quty .lererung

CISA 9 condensate supervision

HS 10 contro.l (gating) .

LSA 11 level supervision


A
w

TIA 12 temperature supervision

XIAS 12 vibration control-


(fan)

LS 13 supervision of service
>
water
t
t

PIC 1 J steam control

(sealing steam/fan) ^ '

/
FIC 15 feed control

TIC 16 temperature control

PIC 17 vacuum control

Die 18 control of the concentrati:n

(high-concentrator) 1
1
1

t
f
Benafinung
description Koi-lsruhe GmbH 0-7505 Ettlingen
M e n . und R g q g Istiickiisf-e Kom 2590-75-83.01
Job No. 520-83-83.01 Maelor
piece list for meosuring end control equipment
Blatt
poge
Proj. Ing. Bearbeiter Datum. Zeichn. Nr.*
Engelhardt responsible Hellmuth dote 7/1 1/84 drwQ- no. 157-393-4
Pos. Benennung Blatt Z e i c:hh n u n g "fUeterung
item quty description page dfov,'''ing [ supply

Lie 19 level control HlCO J


(float balance tank)

Lie 20 level control

L i e 21 level control

TR 22 temperature recording

CISA 23 condensate supervision

HS 24 Control

-J

26 - supply air reducing station

list of materials for assembly

LI 28 - level control
float balance tank

29 - control oanel

U..
Donennung
cjGsc;rip}ic.i
McH-und Regelstuckiisi-e Kom. 2590-75-83.01
jk piece list for nieasuring ond control equipment Job No. 520-83-83.01
1 Blatt
page 4
Proj. I n g . .Bearbeiter | Datum Zeichn Nr i
En_gelhardt rGspohsible Hellmith date 7/11/84 rifv;o no " 157-393-4
Pos jSiuckj Benei'inung Fabrikat Type iBemorkurci
item quty 1 description moke type 1 refnarks "j
PIC 1 main steam-control

- • — — {

1.01 1 meas. transducer for pressure Foxboro


meas. range: 0 - 1 0 bar
- output: 4 - 2 0 mA-

1i type: 821GM-IK1NM2

connection: R 1/2"
<

1 .04 1 I/P transformer Foxboro


input: 4 - 20 mA
\
output: 0,2 - 1., O.bar 1
i
aux. energy: 1,4 bar

type:' E69R-J2/CS-E/FN-A .

w 1 .05 1 diaphragm control valve DN 80, Samson 241



FN 16

Kvs

1.06 1 positioner Samson 765


input: 0,2 - 1 bar j
• supply air: 4 bar
1
at input 0,2 bar: valve closed i
I
1
f
1f
c

I1
• _.
>

•I
Bcnonnung
dsscripfion
MeB-und Regelsi-ucl<[!si'e Kom. 2590-75-83.01
^^^ piece lisi" for measuring ond control equipment Job K'o. 520-83-83.01
BIQH
page
Pro), icig. Bearbeiter | Datum Zeichn Nr
EngeJ. hard t^ responsihk Hellimith doi^ 7/1 1 /84 dnvQ no 1 57-393-4
'Pos~'~jsTCick Benennung Fabrikat Type i Benfiork urv?-
i ieni ^quty description moke type I remarKs
FIC 2 feed control

2.01 flow pick-up DN 50, PN Foxboro


raeas. range: 0 - 4 0 mVhr

aux. energy: 110 V, 50 cycles

model: 2802-SAZD-TSF-G

2.02 meas. transducer Foxboro


meas. range: 0 - 4 0 m^/hr

aux. energy: 110 V, 50 cycles


-L—
model: 896-SA-AE/ with pulse

output . 1 nulse '/ 100 1

2.03 10m signal cable

2.04 I/P transformer Foxboro


input: 4 - 20 mA

output: 0 , 2 - 1 bar

aux. energy: 1 ,-4 bar

type: identical to item 1.04


BonGnnung'
cjcscripfiai
M e n- u n d R e g e I s t u c k j i s i' e' Kom. 2590-75^83.01 .j^^^OP^
piecc list formaosuring and c o n t r o l equipfnent Job No. 520-83-83.01 ^^^^^^^
Blatt
page
Proj. I n g . Bearbeiter Daium Zeichn Nr •
Engelhardt rosponsibIg H e l l m u t h doi e 7/11/84 drwti no 157-393-4
Benennung FabrikQt Type [Semerk urr
ilem iQuty 1 description m a K' G type

2.05 1 control flap DN 65, PN 16 Keystone fig.


9-18
coating: EPDM

drive: 790-018

• with•mechanical closing limitatici

2.06 positioner. Keystone


input: 0 , 2 - 1 bar

flap opened at input 1 bar

aux. energy: 4 bar

order no. 43-101-002


j
L.
item 2.06 mounted to item 2.05
BonGnnung
ciescripficn
M eO- Lind R e g e I s fu c k I i s f e Kom. 2590-75-83.01 ^^
jk • piece tist for moDSuring and control equipfnent Job K'c. 520-83-83.01
1 Blaff
page ^
Proj. Irig. Bearbeiter | Datum Zeichn Nr
rosponsibio Hellnrath doi G 7/11/84 drwg no " 157-393-4
Pos isTuc Benennung Fabri k a i 1 T ype B emork uric^
item {Quty description make | f-ype reniarKs "j

TIC 3 - temperature control

3.01 1 resistance thermometer Degussa PT 100


connection. R 1/2"' I
1
_ J
1
i 1 3.02 1 R/I transformer Foxboro
measuring range: 0 - 40 ®C
aux. energy: 110 V, 50 cycles

output: 4 - 20 mA
type: E94G64B
-
1I
3.04 1 I/P transformer Foxboro

inputs 4 - 20 mA .

output: 0 , 2 - 1 bar

i aux. energy: 1,4 bar

type: icSentical to item 1.04

3.05 1 diaphragm control valve DN 32, Samson 241


PN 16
1
Kvs

3.06 1 positioner Samson 1


765
input: 0 , 2 - 1 f
bar f
«1 -supply air: 4 bar
r
i

t
at input 0,2 bar: valve opened
Boncnnunp
description
M c f3- un d R e g G I s f 0 c k I i s i- G
Kom 2590-75-83.01 ^ ^ i
piece llsf for measuring and conf rol equipment Job No. 520-83-83.01 ^^^OP;
•^ Blatt
page 8
Proj. \ng. Bearbeiter Datum Zeichn Nr
Engelh rcsnonsiblG H e l l n i i t l dniG 7/11/84 157-3 9 3-4

Pos j3iuclJ Benennung Fabrikai Type (Bemerkurc-


item (quty j desr.ripJion tn a I; G type

TIC 4 temperature control

4.01 resistance thermometer Degussa PT 100

connection•R 1/2"

4.02 R/I transformer Foxboro

meas. range:.0 - 100 ®C

aux. energy: 110 V, 50 cycles

output: 4 - 2 0 mA

type: identical to item 3.02


„j

4.04 I/P transformer Foxboro


input: 4 - 20 mA

output: 0 , 2 - 1 bar

aux. energy: 1,4 bar


—f
type: identical to item 1.04

4.05 diaphragm control valve DN Samson 241

PN

Kvs

4.06 positioner Samson 765

input: 0 , 2 - 1 bar
su|5ply air: 4 bar

at input 0,2 bar: valve closed


Bennnnung'
tiescripfian
MGH- und Regel stuckjisi-e" K om. 2590-75-83.01
• piece list for measuring and conirol equipment Job No. 5 2 0 - 8 3 - 8 3 . 01
Blaft
page
Proj. I n g . Bearbeiter Daium Zeichn Nr •
^Engelhard^ roj^ponsiblG Ilellimith doi e 7/11/84 rlrw'o no 1.57-393-4
Pos Benennung Fabrikat Type }B?merkun.7;
ifem iQufy 1 description rrioke type ( remarKs '

PIC 5 vacuum control

5.01 abs. pressure meas. transducer Foxboro


•meas. range: 0 - 300 mbar

output: 4 - 2 0 mA"

connection: R 1/2"
type: 821ALIK1NM2

5.04 I/P transformer Foxboro


input: 4 - 20 mA

output: 0 , 2 - 1 bar

aux. energy: 1,4 bar

type: identical to item 1.04

5.05 control flap DN 150, FN 10 Keystone fig.9-18


drive: 790-036

coating: EPDM

5.06 positioner Keystone 43101002


input: 0,2 - 0,6 bar

aux. energy: 4. bar


at input 0,6 bar: flap closed.

^5.07 like item 5.05 . DN 50

drive:. 790-012

T ' : ' input 0,6 - 1',0ar


t
like Item 5.06 output at 1,0 bar
Bencnhung
descripficn
MeH-und Regelsf-Licklisie Kom. 2590-75-83.01
piece l i s t for measuring and control equipinc-nt J o b No. 520-83-83.01 ^^^^^^
BlaH
page
Proj. Ing. Bearbeifer Datum Zeichn Nr
Enqelhardt responsible H e U m u t l i d c f o 7/1 1/84 rirwo no ' 157-393-4
Pes !3iLic!d Benennung i pabrikai Type jBerriGrk uni
item iquty j descriplion j make' type 1 reniarKs

Die 6 - control of the

concentration

6.01 densitymeter Fisher

type: Gravitrol Mark V

meas. range: 1,05 - 1,2 kg/1

aux. energy: 1,4 bar

output: 0,2 - 1 bar

process connection: flange 1"

L..
6.02 P/I transformer Foxboro
.input: 0,2 - 1,0 bar

outpat: 4 - 20 mA

aux. energy: 110 V, 50 cycles

type: E92-RFN 61

«
f
t
Boriennung
dcscfip'ion
M G n~ un d R G gG I sf u c 1i s i- e
Kom 2590-75-83.01
1 • picce lisf for measuring and c o n t r o l equipmenf Job No. 520-83-83.01 ^^^^^OR,
1 B\Q\i
page —
Proj. Bearbeiter j Datum Zeichn Nr
Engelhardt responsible H e l l m i t h r i o l e 7/11/84 drwo no 1 57-393-4
Pos |::>iuckj Benennung i pabrikai
Type fBemorkunr'-
ifern qufy j description j fjiai^e lype remarKs

Lie 7 level control

float balance tank

7.01 1 level transmitter Valmet-


raeas. range: 0 - 2,5 m WG

1 1 supply air: 1,4 bar

output signal: 0,2 - 1 bar

DN 80, PN 16,

7.02 1 P/I transformer Foxboro <


?
— ... _ J
input: 0,2 - 1,0 bar ' ;
i
output: 4 - 20-mA
aux. energy: 110 v, 50 cycles •

type: identical to item 6.02


^
1 1

7.04 1 I/P transformer Foxboro


input: 4 - 20 mA

output: 0,2 - 1 bar


aux. energy: 1,4 bar

type: identical to item 1.04 •

7.05 1 control flap (condensate) Keystone fig.9-18 i

DN 65; PN 10 1
[

1 drive: 790-018 !>

coating: EPDM \
— .
- . 1-

I
Bonennung'
descfipficn
MeH-und Regelsfuckjisfe" Kom 2590-75-83.01 ^
k piece l i s t for measuring ond c o n t r o l equiprnenf Job Ro. 520-83-83.01
Blatt 1
page ^^
Proj. I n g . Bearbeiter Datum Zeichn Nr • [
^Jngelhardt rosponsiblo H e l l m u t i ) d o t e 7/11/84 drwg no 157-393-4 |
Pos i51ud<j Benennung Fo.brikai Type
iiem iQufy |
Bemerlcurr'^
- —

7.06 1 positioner Keystone

input: 0,2 - 0,6 bar


. —
aux. energy: 4 bar
1
at input 0,6 bar: flap closed
{

1 I/P transformer Poxboro


input: 4 - 20 mA 1
output: 0 , 2 - 1 bar 1
<

aux. energy: 1,4 bar.


\
type: identical to item 1.04 I
tJ
f
i
.7.08. 1 .control flap (product) Keystone fig.9-18 j

DN 6 5, PN 10 i
1
- drive: 790-018

# lining : EPDM

7.09 1 positioner Keystone 43101002

input: 0,6 - 1,0 bar


aux. energy: 4 bar
I
at input 1,0 bar: flap closed 1

^
-k
# !
I
c
-
- .*
i
t
i \
Benonnung
descrip'ion
MeB-und RegGlsi'ucklis^e Korn. 2590-75-83.01 ^
pfcce lisf for moQsurlng and conf rol equipment Job No. 520-83-83.01 ^^^^^
Blatt 13
page
Proj. Irig. Bearb&iter Datum Zeichn Nr
E ng ej. ha r d ^ r^ponsj^blc HellmLith doig 7/11/84 drv/o no " 157-393-4
Pos jStuckj Benennung Fabrikat Type
item {Quty I Berriorkurx=!
descripJion make fype j remorKs
TR 8 - temperature recording

8.01- resistance thermometers Degussa


8.08 PT 100

8.09 resistance thermometer Degussa


PT 100

8.10 R/J transducer for rack mounting Foxboro


model E94G 64B

0 - 100

output: 4 - 20 mA

8.11 like item 8.10


8.12

8.13

8.14

8.15

8.16

8.17

8. 18 1.
Benennung
CiGscripfion
M G n - u n d R e g e I s i" u c i< I i s i- G Kom. 2590-75-83.01 MAELOR-
piece lisf for measuring ar^d c o n f r o l equipment Job l,'o. 520-83-83 . 01
Blatf
page
14
P:oj. Ing. Bearbeiter Datum Zeichn Nr
En ^gJl h a r d t responsible H e l l n i u t h d n l g 7/11/84 (!r\/.3 no 157-393-4
Pos jSiuckj Benennung PabrikQf
Hern {^uty I descrlplion
Type Ber!-jorkurv>i
moke lypo re marks

CISA 9 condensate supervision

9.01 conductivity measuring cell Foxboro


temperature: 1 0 - 8 0 ®C

model: 871CC-A2

9.02 conductivity meas. trandsducer Foxboro

measuring range: 0' - 100 \iS

aux. energy: 110 V, 50 cycles

output: 4 - 20 mA

type: 870CC-10-P

9.03 4-way solenoid valve Burkert 420G


gating: 24 V DC
with mounting plate

9.05 •1 on/off flap

gating air/air

DN 50

with acknowledgement at position

open and closed

approximation initiators Turk

type:- BJ-5-S18-AP-6-X .
with 6 m connecting cable
Bononnung
dcscripHoa
MgG- und R e g e l s i u ck.lisi" g' Korn 2590-75-83.01 MAELOr
• pJGce lisf for measuring and control equipment Job Ho.- 520-83-83 .01
Blatt
page 15
Proj. I n g . Bearbeifer j Daium Zeichn Nr
^ncfe_lhardt_ Responsible H e l l m a t h d d i e 7/11/84 drwo no 157-393-4
[""Tos rsTOckj Benenr^ung Fabrikat
descriptian Type Bemcrkurv:
il'om moke t-ype romarKs

9.06 on/off flap

gating air/air

DN 50

with acknowledgement at position

open and closed

approximation initiators Turk

type: BJ-5~S18-AP-6-X

with 6 m'connecting cable

9 .07 on/off flap

gating air/air -

DN 50

with acknowledgement at position

open and closed

approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Banennung ZtG-i-J:":, iXHOt
cJRScripfion
Men- und Reg el s f u ck I isi- p Kom 2590-75-83.01 MAELOF
• ptoce lisf- for measuring and confrol equipment Job No. 520-83-83 .01
Blatt
16
page
Proj. Ing. Bearbeiter j Datum Zeichn Nr
L^)^ ng^el hardly rospons^bJ^G Hell^rnutll dale 7/11/84 drwi] no " 157-393-4
f^OHi [Stuck Benennung ^ Fabrikat Type OBemcrkurv"
item iQuty description' iTi 0 k e type ^ ^remorKs

9.08 on/off flap

gating air/air

DN 25

with acknowledgement at

position open and closed


approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable

J
Bcnennung
dcscftpficn

Mefir und R ege I stuck Iis f e Kom. 2590-75-83.01


piGCG llsf formeosuring ond c o n t r o l equipnient Job t^c. 520-83-83.01
Blati
page 17
Proj. I i i g . Bearbeiter Datum Zeichn Nr
Enge-lharclt rosDonsiblc H e l l m i t J dofe 7/11/84 ' cirwn no 157-393-4
Pos jSti-ic}^ Benennung Fabrikai Type Bemerkurv"--
ifem (Qtify ! descripJio.'i make type ^ remarks

HS 10 - Control

10.01 inclined seat valve Biirkert


casing VA,.DN 3/4"

spring: opening

10.01.2 4-way solenoid valve Burkert 420G


gating: 24 V DC

with mounting plate

.!
10.02 inclined seat valve r
Biirkert
casing VA, DN R 3/4"

spring: opening

0.02.2 4-way solenoid valve Burkert 420 G


gating: 24 V DC

with mounting plate

10.03 1. inclined seat valve Burkert


casing VA, DN R 1/2"

spring: opening

10.03.2 4-way solenoid valve Burkert 420 G


gating: 24 V DC

with mounting plate


Bcnonnung
descriplion
M G R- u n d R G g e I s t u c k .1 i s i- e'
Kom. 2590-75-83 .01
• pjoce list for measuring and control equipment Job N'o. 520-83-83.01
B(att
page
18
Prcj. Ing. Bearbeiter Datum Zeichn Nr

Pos "jSiOcV- Benennung Fabrikai Type -jBemcrkur^-


item iquty descriplion make type 1 remc-rks

10.04.2 1 4-way solenoid valve Biirkert 420G i


1
gating: 24-V DC 1
1
with mounting plate 1
f
1
• 10.04 1 oji/off flap
t

gating: air/air

DN 4 0

with' acknowledgement at
!
position open and closed /
f
approximation initiators Turk
1
type: BJ-5-S18-AP-6-X I
I
x
, with 6 m connecting cable

f
!
«C

[i c
i

— .*

!
t
I
r Benennung-
d'escriptiOiT
Men-- und R e g e I s fu c k I i s i" g
Kom. 2590-75-83 .01
• piece l i s t for measuring and control" equipment J o b No. 520-83-83.01
Blalt 19
page
p r o j . |r-»g. Bearbeiter Datum Zeichn Nr •
^^En geJJi a rd ^ rosDonsiblo HelLmith dote ^rinvp no • 157-393-4
Pos |5iucl Benennung Fabrikaf Type jBen^rkurr-i
item (Quty description moke type I remarKs

10.05.2 4-way solenoid valve Biirkert 420 G


gating: 24 V DC

with mounting plate

10.05 on/off flap

gating: air/air
DN 40

with acknowledgement at

position open and closed

approximation initiators Turk

type: BJ-5-S18-AP-6-X
with .6 m connecting cable

L.
Bonennung
descrip'ion
MoR-und Regelsiucklisi-e Kom. 2590-75-83.01 j , ™ ^
- piece lisf for measuring and c o n t r o l equipment- Job No. 520-83-83.01
Blatt 20
poge
Proj. I n g . Bearbeiter | Datum Zeichn Nr
Enge-lhardt responsibjo H e l l i m t h d o t e 7/11 /84 drv/n no 1 57-393-4

Pos jSTijcf: Ben&nnung Fabrikaf Type Bemorkurv:^


item Quty description m a In e type remarKs
I.

10.06.2 4-way solenoid valve Biirkert 420 G

gating: 24 V DC

with mounting plate

'10.06 on/off flap

gating air/air

DN 40

with acknowledgement- at

position open and closed


L.
approximation initiators Turk
•type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Donc'finung
cic-scriplion
M G il- u n d R G g e I s 1- ij c k I i s i- e |( o m 2 5 9 0 - 7 5 - 8 3 .01 '^
piccc list for fnoQsuring ond c o n t r o l GcjuipmGnt Job Uo. 520-83-83.01 ^^^^^^^^
Blatt 2 1.
page-
Proj,l?tg. Dearbeiter Datum Zeichn Nr
Enqelhardt Qjg tJrwQ no 157-393-4
Pos {SiucU Benenriung I Fc.brlkai
J tern tqufy j dc'Scriptian
Type jBerTicrkurr^
I m a Ic G type t romarivs "I

10.08.2 4-way solenoid valve Burkert 420 G


gating: 24 V DC

with mounting plate

1^.08 on/off flap

gating air/air

DN 40

with acknowledgement, at

position open and closed

approximation initiators Turk

•type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Bcnermung
descriplion
M G n- u n d R e g e I s f Li c k 1 i s i- ti Kom 2590-75-83,01
• pictc lisf for measuring and confrol equipment Job N'o. 520-83-83.01
Blatt 22
page
Proj. I n g . Bearbeiter Datum Zeichn Nr
^JE n ge 1 h a r d t r£sp^onsJ_^bl^Henjriith dais • 7/11 /84
drwo no ' 1 57-393-4
Pos jSiC'ckj Benennung I FabrikoJ
item {^uty | Type Bemcrkufx--
desr.ripMon I m o Ic e type renicrkf. " i

10.09.2 . 4-v7ay solenoid valve Biirkert 420 G


gating: 24 V DC

with'mounting plate

10.09 on/off -flap -

gating air/air

DN 40

with acknowledgement at

position open and closed


J
approximation initiators Turk
•type: BJ-5-S1B-AP-6-X

with 6 m connecting cable


r'-
Dcnofinung
c)cscrip'io.-i
M G f3- u n d R e g e [ s i- u c k I i s i- (3
Kom 2590-75-83.01 ^ :
^ • pjccc lis.f for mL'OSuring ofid control Dqyipfncnt Job No. 520-83-83.01
"Blatt : 1
pro']. I fig. poge J
Bc^arbeiter j Datum Zeichn Nr
157-393-4
Pos jSiucH Benei'i n u ng 'F a b r i k a t Type Bsmcrlcurx-:-
ifem »quly j riescripliI on mo e type [ rC'marKf. "s'

10.10.2 4-way solenoid valve Burkert 420 G

gating: 24 V DC

with mounting plate

10 on/off flap

gating air/air

DN 40

with acknowledgement at

positions open and closed


• L.
approximation initiators Turk

•type: BJ-5-S18-AP-6-X

with m connecting cable


r
Denennung-
dcscrip'ion
MeB- und Re g e I s fii c k j i s i" e Kom 2590-75-83.01 ' i
picce l i s t for measuring and control equipment Job K'o. 520-83-83.01 ^^SLOPv
Blalt
page
24
Prcj. Ing. Oearbeiter Datum Zeichn Nr
Engelhardt y i 1 dnv-.-) no 1 5 7 - 3 9 3-4.
Pos j3iucld B e n e i m u nvg
Jtem^ jquty I
Fabrikat Type Bsmorkurv-;
descripJton moke lyp2 rfimGr)(s "I

10.11.2 4 way solenoid valve Biirkert 420 G

gating: 24 V DC

with mounting plate

10.11 on/off angle valve Alfa


Laval
gating: opening by air

DN 40

with acknowledgement at positions

open and closed

approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6m connecting cable


Y
Boneanung'
cicscriplion
M g H - und R e g g I Si-ii c k I i s I- G Kom. 2590-75-83.01
pfoce l i s t for moQsuring and c o n t r o l equipineni Job No. 520-83-83.01
Blatt 25
page
Proj. I tig. Bearbeiier [Datum Zeichn Nr •
^E n g e 1 h a r d ^ l^spofisiblG 7/11/84 rirwrj no ' 157-393-4
Pes jSluckj Ben en n u ng — ™ FabrTkoT Type [BemcrUuixi
item fQuty i

Alfa
10.12 1 on/off angle valve Laval
gating: ^penina by air

DN 40

with acknowledgement at

i positions on and off

approximation initiators Turk


typ: BJ-5-S18-AP-6X

with 6 m connecting cable

f
P

-
!

• • " 1

i
1
(

t
»

- - .
>
f
Denennung-
descripficn wzii!
MeH-und Regelsfiickiisfe
Kom. 2590-75-83.01
• piece Itsf for measuring and c o n t r o l equiprnenf Job Mo. 520-83-83.01 ^^^^^^'i
"Bialt 26 ^
page
ProJ. I n g . Bearbeiter Datum Zeichn Nr
Enge-lh a r dt _ rosDonsiblo Hellmuth dafG 7/11/84 drv/t^ no 157-393-4
Pos iluck! Benennung Fabrikat
item {Quiy I
Type fBem
description make type I remarKs

10.13 on/off angle valve Alfa


Laval
gating: openina by air
DN 40

with acknowledgement at

positions on and off

approximation initiators Turk

typ: BJ-5-S18-AP-6-X•

with 6 m connecting cable


_ I
Bencnnung
descfip'ion
MeH-und Regelsfucklisfe Kom. 2590-75-83.01
• piGcc l i s t for measuring and c o n t r o l equipment Job Uo. 520-83-83 .01 ^^^^^
Blatf 27
poge
Proj. Ing. Bearbeiter Datum Zeichn Nr
_En_gelhardt responsible I l e l l i n a t h d a f e 7/11/84 drv/fj no 1 57-393-4
Pos Siucki Benennung Fabrikaf Type 'Berr.orkurv?^
Item quty I dcscriplion m a l\ e type remarks

10.14.2 4-way solenoid valve Burkerf 420 G


gating: 24 V D.C.

with mounting plate

0.14 on/off angle valve Alfa


Laval
gating: onenincy b'v air

DN 40

with acknowledgement at
positions on and off

approximation initiators Turk


type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Banonnung
clcscripJion
MoR-und Regelsf-ucklisi-e Kom^ 2590-75-83.oT
piece l i s f for measuring ond c o n t r o l equipmenf Jot) No. 5 2 0 - 8 3 - 8 3 .01
Blatt
28
page
Proj. Ing. Be-arbeiter [Datum Zeichn Nr
"^Sl? V11/84 drw^ no ' 1 57-393-4
Poii j5lucl;j "Benennung Fabrikat
^ ^ Item jqufy 1 description'
Type Bemcrkurv"'
make type remorhs

10.15.2 4-way solenoid valve Biirkert 420 G

gating; 24 V D.C.

with mounting plate

0.15 on/off flap

gating: air/air
DN 25

with acknowledgement at

positions on and off


,
approximation initiators Turk
type: BJ-5-S18-AP-6-X .

with 6-m connecting cable


Benc-nr;LV:g
A—,
MeR-und Regelsfucklisfe 2590-75-83.OT
Kom
520-83-83.01
tneosuring control p i c c e list
Blatt von
page 28a
of
Proj. Ing. Bearbs'iler Datum Zeichn Mr
Engelhardt
F^os jstuc iu Bc^nennung {Fabrikaf Type [Bem^rkuri
ifcrr. tP'^ce description • - j n^Q^^ h'Pe 1 nntc
10.20.2 1 4-way solenoid valve Biirkert 420 G
gating: 24 V D.C.

with mounting plate

II10.20 1 on/off (inclined seat) valve Biirkert


VA DN R 1 "

opening by air

1
\\
{
1


!
*

t.

• • -i
{
1

\
\
f
( i 1 1
Bonennung
descfipMon
M e f3- u n d R e g e I s f u c k j i s i- e Kom. 2590-75-83.01
pjcce list for measuring and c o n t r o l equipmenf Job No. 520-83-83.01 ^^^^OF
Blatt 29
page
Proj. Ing. Bearbeiter ( Datum Zeichn Nr
^^ngelhardt rnsponsiblc H e l l m u t h d a i e 7/11/84 drwo no 157-393-4 ;
Pos si Cickj Ben en n u ng Fabrikat
item quty I descriplion
Type jBemcrk urc
m a Ic e type i remcrKs

10.21.2 1 . 4-way solenoid valve


Bvirkert 420 G
gating: 24 V D.C.

with mounting plate

(
1
1 f1 0 . 2 1
1 on/off flap
gating: air/air
DN 50 c

with acknowledgement at
i
positions on and off
r ~ i
approximation initiators 1
Turk i
f
type: BJ-5-S18-AP-6-X
i
i
with 6. m connecting cable i
f

1
1 P1

f
1


!
1

i
i9
c
I
1
1
^
t
Bonennung •
descripfion
MeH- und R e g e I s fii c k 1 i s i" g Kom. 2590-75-83.01
• piecc l i s f for measuring ond confrol equipmenf J o b No. 520-83-83.01
~Blaff 30
page
Proj. I n g . Bearbeiter Datum Zeichn Nr •
rcsponsiblo Hellnrjtl" dnJff 7/1 1/84 drv;.3 no " 1 57-393-4
Pos ISiucl'J Benennung Fabrlkat Type fBemerkuixi
item I'quty ! description' m a l\ G type remurKs

10.22.2 4-way solenoid valve Biirkert 420 G


gating: 24 V D.C.

with mounting plate"

0.22 on/off flap

gating: air/air

DN 40

with acknowledgement at

positions on and off


1
approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable.

f
Bcnennung
descrip'ion
Vv m;
MeR-und Regelstucklisfe K om 2590-75-83.01
piece l i s t for measuring and ccnfrot equipment Job No. 520-83-83.01 ^^^^^^^
B l a t t 3T
page
P r o j . If-jg. Bear belter Datum Zeichn Nr
E^e-lhardt rnsponsiblc Hellmatl^ d o l e 7/1 1/84 ' drwQ no 1 57-393-4
Pos |3tuck{ Fa brikat Type Bemork urv:=;
dcscriplion m Q K' e fype roniorks 'i

10.23.2 4-way solenoid valve Burkert 420 G


gating: 24 V D.C.

with mounting plate

ino.23 on/off valve (inclined seat valve) Biirkert

VA DN R 1"

ooening by air

.1.
BofiGnnung
.descrip'ion
M gR- unci Rg g e [ s f u c k j i s i- e Kom. 2590-75-83,01
• piece l i s t for mGOSuring and conl rol equipmenf Job N'o. 520-83-83,01
Blatt
page 32

proj. Ing. Bearbeiter | Datum Zeichn Nr


_ JEn^elJ} a r d t ^ responsible H e l l i T i a t l j d a i e 7/11/84 drv/.j no 1 57-393-4
Pos Stuck! Benennung Fabrlkaf Type Bemerkun-i

"J— — — — - •...

10.24.2 1 4-way solenoid valve Biirkert 420 G

gating: 24 V D.C.

with•mounting plate

P
<

1
P

i
k
-

ft [
P r
i

- i
Denonnung'
descrip'ion
MeH- und Regelsfucklisi'e Kom. 2590-75-83.01 MAELOP;
{•
• piece lisf for measuring and confrol equipmenf- •Job No. 5 2 0 - 8 3 - 8 3 . 01
~Blat{ 33
page
Proj. Ifig. Bearbeiter { Datum Zeichn Mr
Engelhard^ r G s p on s i h 10 H e l l m u t i i d ai Q ^ ^jJrwg no • 157-393-4

Pos jSTucld Benenr^ung Fabrikat Type jBen-iorkun.:^!


item ^quty IJ descriplion' m G l\ e type I remarks 'j

10.24 on/off valve Samson 241

DN 50, PN 16, Kvs max

casing: grey cast


drive: 240 cm^

closing by spring towards 10 bar

I
Bcnonnung
(Joscripiicn
McB-und Regelsfucklisi-e Kom. 2 5 9 0 - 7 5 - 8 3 . 0 1 !
piece l i s t for meosuring and control equipmenf Job No. 5 2 0 - 8 3 - 8 3 . 0 1

1
Proj. Itig. Bearb9iier ( Datum
'Blatf
page
Zeichn Nr
__En^elhs]:dt _ ^ 7/11/84 dnvg no 157-393-4
Pos jSfLickj Benennung Fabrikat
item jquty
Type [ B e m o r k urv:^
dosf.rip'ion moke type remarks ";
.1

10.25 hand flap with acknowledgement

at position, closed

anproxirr.ation initiator
type: BJ - 5 - si 8 - AP-6-x -Turk

with 6 m connectina cable


BenRfinung
dGscrip'ion
MeO-und Regplstucklisi-e
Kom. 2 5 9 0 - 7 5 - 8 3 . 0 1
jk • piece list for measuring and control equipment Job No. 5 2 0 - 8 3 - 8 3 . 0 1 ^ ^ ^ ^ ^
1 Biatt
page
Proj. Ing. Bearbeiler Datum Zeichn Nr
n^e 1 h a r d t rGsponsibfe Helliruth dole 7/11/84 drv;Q no ' 157-39 3-4
Pos jSiiickj
item (quty \ ^ e ^ s ^ r l n - ' J o n - " P V p e |Ben-rerkur.^
ot^snrip.ion make tvDo 1 ri^mnrh^ '
LSA 11 Level Control

11.01 1 Level switch "Alt a


Laval
• • '
t
- t

ii

1
1

J
t
f

^
iw

!
(

\
I
• \
i I
c
j
- . . - - .

t
t •
1

i
Bonennung'
descripfion
Mef3- und R e g e I s fu c k [ i s f e Kom. 2590-75-83.01 _
k • piece hsf for measuring and confrol equipmsnf Job No. 5 2 0 - 8 3 - 8 3 . 0 1 ^^^^^^^
Blalt 3g
page
PrOj. Ing Bearbeiter j Datum Zeichn Nr •
ardjt responsible Hellmutl^Df g 7/11/84 dn/g no 1 57-39 3 - 4 ;
Pos jSiuc H Benennung | Fabrikat Type Bemcrkurri
ifem Jqufy { descriplion | jrioike iypo . remarks
TIA 12 Temperature Supervision

. XIAS 12 V i b r a t i o n Control

(Fan)

(
12.01 1 resistance thermometer Deaussa

f
4 identical to' item 8.01

12.02 1 R/J t r a n s d u c e r identical to Foxboro

item 8.10
\
12.03 1 resistance thermometer Deaussa \1
identical to item f.01 i?

12.04 1 R/J transducer Foxboro


identical to item 8,10

12.05 1 vibration control delivery


Schenk
bv fan
supplier

relay k:-}206 shut-off

1
1
$

>

• 1
»

.tI
1
e
- .
j

f(
Donennung A.'. .
..s ^
descrip'ion .J'.-. - V^^b- ;

MGH- und R e g e l s I'U c K.L i s I'G" Kom. 2590-75-83 .01


• pfece llsf for measuring and c o n t r o l equipment Job He. 520-83 -83 Q^ MAELOI^
Blatt 37
page
Pi oj. Iiig. Bearbeiter Datum Zeichn Nr
Engelhar dt j;csponsib(e Hellmutrh daie 7/11/84 drwQ no 1 57-393-4
Pos jSiuckj Benennung Fabrikat
item iQufy | Type (Bemcrkunc^
descripJion make type remcrKs

LS 13 Supervision of the

Service Water

13.01 electrode RUF HR-61111


connection: R 1/2"

13.02 electrode relay EXNER 3R3a5kOHW


auxiliary energy: 24 V/A.C.

output: relay

.I
13.03 identical to item 13.01

13.04 identical to item 13.02

'13.05 identical to item 13.01

13.06 identical to item 13.02

13.07 identical to item 15.01

13.08 1. identical to item.13.02

3.02.1 tension supply unit


Ocnnnnung
dcscrip'ion
M e n - u n d R e g e I s f ii c 1 i s i" e Kom. 2590-75-83.01
• pieco l i s t for measuring ond confrol equipmenf Job Nc. 520-83-83.01
Bloti
page 38
Prbj. Ifig. Bc?arbeiter Datum Zeichn Nr
^^^ 1/84 dnvo no " 1 57-393-4
Pos jStuc'rtj Benennung Fabrikat Type jBemorkurr^
iforn jctuty | descripfinn' m• h0 type I rc'tncrKf; i
PIC 14 Steam Control

{Sealing Steam/Fan)

14.01 measuring .transducer for FOXBORO

pressure
meas. range: 0 - 1 0 bar

output: 4 - 20 mA

type: 821GM-IK1NM2

connection: R 1/2"

14.04 I/P transformer FOXBORO


input: 4 - 20 mA

outputs 0.2 - 1.0 bar


auxiliary energy: 1.4 bar

type:.identical to item 1.04

14i05 1 diaphragm control valve DN 25, SAMSON 241


PN 16, Kvs

14.06 positioner SAMSON 765


input: 0 . 2 - 1 bar

supply air: 4 bar

at an.input of 0,2 bar the

valve is closed
n
Benennung
dcscripftcn
MeR- und Regelsi-ucklisi-G Kom 2590-75-83.01
• p/cce list- for measuring and c o n f r o l equipment Job lie. 520-83-83 .01
Blatf 39
page
proj. ing. Bearbeiter | Daium Zeichn Nr "
Enqe-lhardt 7/11/84 drv/g no 157-393-4
II • I Ct 11 • P f

Pos jslucl'^ Benennung


Hem ^quty dcsrripfion I Fabrikat Type? iBemcrkurr:
typo j remGrKs
1 moke
FIC 15 Feed Control

15.01 flow receiver DN 25; PN 10 FOXBORO


meas. range: 0 - 8 m^/hr

aux. energy: 110 V, 50 cycles

model: 2801'-SAZD-TSF-G

15.02 meas. transducer FOXBORO


meas. range 0 - 8 m^/hr
aux. energy : 110 V, 50 cycles
I
model: 896-SA-AE

15.03 10m signal cable

15.04 I/P transformer FOXBORO


input: 4 - 20 mA

aux. energy: 1.4 bar

output: 0.2.- 1 bar

type: identical -to. Item. 1^04

15.05 1 . diaphragm control valve DN 40 Max v.Rohr


PN 16

Kvs sanitary
Benennung
description
H e n - un d R e g e I s f u c k .1 i s f e' Kom. 2590-75-83.01
• piece llsf- for measuring ond c o n t r o l equiprnenf Job No. 520-83-83,01
Blatt
page 40

Proj. Ing. Bearbeiter Datum Zeichn Nr


J^ngelha rd t rosponsiblG J t e l l m u t h d n i e 7/11/84 dnvQ no 157-393-4

Benenr^ung Fabrikai Type Berrserkua'-5


item descr jpfion fno ke type remarKs i

15.06 positioner

input: 0.2 - 1 bar

supply air^ 4 bar

at an input of 0.2 bar the valve

is open

J L
Bc-nennung
cicscripdon
MeH-und Regelsl-ucklisi-e Kom. 2590-75-83.01 ^
• ptece l i s t for measuring and c o n t r o l cquipmenf J o b No. 520-83-83.01
Blaff
page 41
Proj. l ! i g . Bearbeiter Datum Zeichn Nr
^J^^^JL ha r d ^ rosponsibl^Iellrnath dnis 7/11/8 4 drw.j no ' 157-393-4
Pos iSTucH
item Iquty 1
Benennung
doscripiinn"
Fabrikat Type [Bemcrkuroi
fTJo ke typo I remarks "i

TIC 16 Temperature Control

16.01 resistance thermometer Degussa PT 100


connection•R 1/2"

16.02 R/I transformer FOXBORO

meas. range: 0 - 50 °C
aux. energy: 110 V, 50 cycles

output: 4 - 20 mA

type: identical to item 8.10

16.0 4 I/P transformer FOXBORO

input? 4 - 20 mA

output: 0.2 - 1 bar

aux. energy: 1.4 bar


type: identical to item 1.04

16.05 control flap DN 125, PN 16 Keystone Fig.9-18


lining : EPDM

drive: 790 - 018

with mechanical closing limita-

tion
BDnermung"
dcscripfion
Men- und RegoIstuck(isfe Kom. 2590-75-83.01 ^
• piece l i s t for mDosuring and confrol equipment Job No. 520-83-83.01
Blatt 42
page
Proj. I n g . Bearbeiter j Datum Zeichn Nr -
_Enge-lhardt res pons i b j j ^ H e l l i n a t h d n i e 7/11/84 drv/o no 157-393-4
~ Pos'""j5T0cir
item iQ'jfy
BDnennunf)
dcscripfion
Men- und Regel stuckjisi-e' Kom 2590-75-83.01
MAELOJ
^ • pioco l i s i for measuring ond conlrol equipcienf Job No. 520-83-83.01
Blaft 43
page
Proj. Ing. Becirbelter j Datum Zeichn Nr
_Engelh a ^ r^sporisihIg Hellmutl] dnje 7/11/84 rfp.,;,^ 157-393-4
Pos sTuci; Benennung Kabrikat
^ ifem quty description
Type Cb emerk urr-'i
iTioke fype remarks
t — . • -

PIC 17 Vacuum Control

17.01 abs. pressure meas. transducer Foxboro


meas. range: 0 - 300 mbar

output: 4 - 2 0 mA-

connection: R 1/2"

type: 821AL-IK1NM2

17.04 I/P transformer Foxboro


input: 4 - 2 0 mA

output: 0 . 2 - 1 bar

aux. energy: 1.4 bar

type: identical to item 1.04

17.05 control flap DN 100, FN 10 Ceystone . Fig.9-18


drive: 79 0 - 018

lining : EPDM

17.06 positioner keystone 43101002


input: 0.2 - 0.6 bar

aux. energy: 4 bar

at an input of 0.6 bar the "flap

is closed
BonennunQ
(Joscriplian
Mef3- und R e g G I s i u c k [ i s i" e
Kom. 2590-75-83.01 ,, _ _
Job Nc. 520-83-83.01
i • piece lisf for mc-QSuring and confrol equipment
Blatt
page 44
Proj. Ing. Bearbeiter j Datum Zeichn Nr
^^^igelhardt rcsponsihin Hellitutl^dnio 7/11/84 dnvq no ' 157-393-4
Pos jSTuc M Benennung Fabrikat Type jBemorkumi
item (Quty 1 description' m Q I\ e lype 1 remarKs

1
17. 07 1 • control flap DN 80, PN 10 Keystone Fig.9-U

drive: 79 0 - 018

lining ; EPDM

i 'l7.08 1 positioner Keystone 43101002

input: 0.6 - 1 bar


1
aux. energy: 4 bar

a t an i n p u t o f 1.0 bar. the flap is


1
closed

i
I
*

i

s
-

€k
f c
• . - - .
i
{
f
Bcnonnung
V i. ^ .cl.
tlGscfip'im
MeB-und Regelsi-ucklisi-e Kom. 2590-75-83.01
• piece l i s t for measuring and coiifrol equipmenf Job Ho. 520-83-83 .01
"Blatt ~
page 45
Pr'oj.Jng. Bearbeiter j Datum Zeichn Nr •
riispon^l^H^lriTiith daie 7/11 /84 drv/g no 1 57-393-4
Pos iSiuck Benenfiung Fabrikat Type {Bemorkurr^
ifem (Quty dnscripiion make type { rGmcrh?;

Die 18 Concentrate Control

(High-Concentrator)

18.01 isotope measuring section DN 65 Berthold • LB379

18.02 meas. amplifier 110 V, 50 cycles Berthold LB 3 79


meas. range: 50 - 90 % TS, whey

output: 4 - 20 mA

with temperature compensation

and linearization
.L.

1.8.04 . I/P transformer


Foxboro
input:. 4 - 20 mA

output: 0.2 - 1 bar

aux. energy: 1.4 bar

type identical to 1.04


18.05 diaphragm control valve DN 241
Samson
PN Kvs

18.06 positioner, input: 0.2 - 1 bar Samson 765


supply air: 4 bar

at an input of 0.2 bar the valve-


is closed "1
Beneanung
descripHcn
M e n - und R e g e I s f u c k j i s i-e
Kom. 2590-75-83.01
piece (isr for measuring and confrol equipntenf Job No. 520-83-83 .01
Blatf 46
page
Proj. If-jg. Bearbeiter | Datum Zeichn Nr
^ n g e l h ardt_ P*"',^' ^ 7/11 /84 dnvQ no 1 57-393-4
Pos jsTuck Benennung FabrikQi Type |Bemorkun.:i
item {Qufy description rri 01\ e type I remorKs

Lie 19 Level Control

Float Balance Tank

19.01 level transmitter Valmet


meas. range: 0 - 2.5 m WG
supply air: 1.4 bar

output signal: 0.2 - 1 bar


DN 80, PN 16

19.02 P/I transformer Foxboro


input: 0 . 2 - 1 bar

output: 4 - 20 mA
aux. energy: 110 volts, 50 cycles
type: icientical to item 6.02

19.04 I/P transformer Foxboro


input: 4 - 20 mA

output: 0.2'- 1 bar

aux. energy: 1 . 4' bar'

type: identical to item 1.04


r"
Den ennung'
descfiplion
M e n - und R e g e[ si'u c k 11 s i" e
Kom. 2590-75-83.01
piece list formoQsuring and confrot cquipmenf Job No. 520-83-83 .01
Blatt
47
page
Pr oj. ifig. Bearbeiter j Daium Zeichn Nr •
rcsponsiblrj Kellmath doie 7/11/84 drwo no • 1 57-393-4
Pos iSlQckj
[SiCickj Bene-nnung Fabrikaf Typi
item description' make Bemcrkurr5
type remorks
CGW ''"Sb.-.iys^'Xhr.rc^ .

19.05 control flap DN 40, P N M 6 Keystone Fig. 9-1g


lining EPDM
drive: 79t]^018

19.06 positioner Keystone


input: 0.2 - 0.6 bar
at an input of 0. 15 bar, the flap

is closed

aux. energy: 4 bar


-L.
serial no. 43-101-002

item 19.06 is attached to item

19.05

19.07 I/P transformer Foxboro.


input: 4 - 20 mA

output: 0.2 - 1 bar


aux. .energy: 1.4 bar

(
.f
Bonennung
(Jescripiicn
MeR- und R e g el s f u ck I i s ^ e
Kom 2590-75-83.01
• piece l i s t for measuring and c o n t r o l equipment Job No. 520-83-83.01
Blatt
page 48
Proj. Ifjg. Bearbeiter | Datum Zeichn Nr
Enge-lh a r ^ ^ responsible Hellmith doie 7/11/84 drv/Q no 1 57-393-4
Pos iSiLick Benen r^ung Fabrikat
item {Quty description
Type iBemcrkurv:'
moke type I remarks

19.08 control flap DN 40, PN 16 ' <eystone Fig.9-18


lining EPDM
drive: 790-018

with mechanical closing limitation

19.09 positioner Keystone


input: 0.6 - 1.0 bar

at an input of 1 bar the flap

is closed

aux. energy: 4 bar

serial no. 43-101-002

item 19.09 attached to item 19.08


BGnenn'jng
(Joscripfion -.,1 . . . ' " o - . -
M E N - und R e g G I sf u c k.l isi* e
Kom. 2590-75-83.01
• piece list for measuring oncJ control equipment Job No. 520-83-83.01
Blatf
page 49
Pr'oj. Ing. Bearbeiter Datum Zeichn Nr
157-393-4
. " p o s " " 5iuckj B&nennung
Fabrikat Type Bemcrkurr
item quty { descriplion
make type remcrks

Lie 20 Level Control

20.01 1 measuring transducer for differen- Taylor


tial pressure
i
^ 1
with attached pressure transmitter i
DN 80
•. capillary length between meas.

transducer and pressure transmitte

3 m each

diaphragm of the transmitter


i
meas. range: 0 - 300 mm WG 1
I
aux. energy: 4 - 20 mA f

output: 4 - 20 mA 1
t
i
type: 3423TD10 763-01-10-146-DC702

>

-
f
A
V- [
i
»
• \
— .*
\
1
i
Bcnunnung
ciGS(;rip{ion
MeH-und Regelsf-ucklisi-G Kom. 2590-75-83.01
jk • piece lisf for nioosuring and conirol equiptnenf Job (>'o. 520-83-83 .01 ^^^^^^^
i Blatt
page ^^
Prbj-lrtc]- Bearbeiter j Datum Zeichn Nr
Engelhardt rosponsiblo Hellmuth dniG • 7/11/84 rirwg no • 1 57-393-4
Pos jSiuckl Benennung Fabrikai Type BemGrkurc"
item fQufy 1 descriplinn' m 0 Ix e lype remcrKs '
Lie 21 Level Control \ 1
- z

21.01 1 meas. transducer for differential Taylor


pressure
-
with attached pressure transmitter t

i 1 DN 80

capillary length between measuring

transducer and pressure transmitter


t
i
3 m each t
(
1
diaphragm of the pressure trans-

mitter i. — \
(
i

meas. range: 0 - 300 mm WG


aux. energy: 24 V, D.C.

output: 4 - 20 mA
i 1 type: 34230^010763-01-10-14 6-00.702


1

1
¥ r

. . . - .
]
f
•f
«
BGnennung'
descripfion
MeH-und Regelsiuclvlisi-G Kom. 2590-75-83.01 MAELOP.
• piece lisf for moQsuring ond conlrol cquiprr.enf • Job No! 520-83^83 .01
Blatt
page
51
Proj. I n g . Bearbeiter Datum Zeichn Nr '
Engelhar d t rosponsiblc Hellmutl" dnfe 7/1 1/84 rirv/i] no 1 57-393-4
Pos {Stuck Benennung Fabrikat
item jqiify Type [Bemerkunr
descripiion m a l\ e iype I remarks
TR 22 Temperature Registration

22.01-

22. 05 resistance thermometers Degussa


PT 100

22.06 R/I transformer for rack mounting FoxDoro


model E94G6413
0 - 100 ®C

output: 4 - 20 mA

22.07- identical to item 22.06 Foxboro

22.08

22.09

22.10
Bonnnnung
dcscripfion
M G R- un d R e g e I s f u c k j i s i- e' Kom 2 5 9 0 - 7 5 - 8 3 . 0 1 MAELOPo
• (HGce l i s t for moasuring and c o n t r o l equipment Jot* No. 5 2 0 - 8 3 - 8 3 .01
'Blatt 52
page
Prbj. Ifig. Bearbeiler | Datum Zeichn Nr
hardt re sp on si hie H^lmuth dnte 7/11/84 rirv/g no 1 57-393-4
Pos iyOdJ Benennung Fabrikat Type
item iquty j dnscripJion moke cype
-Bemerkufx-
CISA 23 Condensate Supervision

23.01 conductivity measuring cell Foxboro


temperature: 10 - 80 "C

model: 871CC-A2

23.02 conductivity measuring transformer Foxboro

meas. range: 0 - 100 iiS


—I
aux. energy: 110 volts', 50 cycles

output: 4 - 20 mA
L.
model: 870CC-10-P

23.03 4-v;ay solenoid valve Burkert


gating: 24 volts, D.C

with mounting plate

23.05 on/off flap

gating: air/air

DN 32
with acknowledgement at

positions on and off

approximation initiators" Turk

type: BJ-5-S18-AP-6-X
with 6 m connecting cable
Boncnnunf]
descrip'icM v v iris
MgH- und Reg el si-Lick [isi-G
Kom. 2590-75-83.01
H - [M'ece lisf- for measuring and control equipmenf Jcb t-!o. 520-83-83.01
i •
Blatt
page
Proj. Ifig. Byarbeiter | Datum Zeichn Nr
Enqelhardt rosponsiblo. Hellmithj dai o 7/1 1/84 rirv/o no ' 157-393-4
Pos Stuc W Benennung Fabrikaf Type {Bemer'kunc:
Hem [ dGScripJ.on' jrtoUe Jype 1 remarks
- Sill

23.06 1 on/off flap

gating: air/air

DN 32
!
-
with acknowledgement at t

i9 positions on and off

approximation initiators. Turk

type: BJ-5-S18-AP-6-X t

with 6 m connecting cable


1
\
t
23.07 1 on/off flap i
k
i
gating: air/air

DN 32

with acknowledgement at positions

i1 on and off'

approximation initiators Turk


type: BJ-5-S18-AP-6-X

with 6 m connecting cable

i
-

t
1
¥ C
• — . 1
t
OGnofmunc)
descriplicn
•• » • ^ , • , • » ••>»v J

MGH- und Reg e I sfu c k I isi-G Kom. 2590-75-83.01


k • piece Irsf for measuring and control equiprient Job No. 520-83-83.01
Blaff 54 1
page
Proj. Ing. Bearbeiter Datum Zeichn Nr " i
^Engelhardt rosponsihlo Hellrniath d o l e 7/1 1/84 drwg no 157-393-4 j

Po^ ofuc^d Benennung Fabrikat Type "fB-merkC'r;


.^em ^ qufyJL ^dcscr.pf.on 1 '

23. 08 1 ' on/off flap

gating: air/air

DN 32

with acknowledgement at positions

on and off

approximation initiators Turk


type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Dcnonnung
clcscripfion
M GH- unci Reg e [ sfu c k j isi- e K om. 2590-75-83.01
• ptece l i s t for measuring and control equipment Job Uo. 5 2 0 - 8 3 - 8 3 . 01
"Blatt
page
55
Proj. Ing. Bearbeiter Datum Zeichn Nr
_^En 1 ha rd t ^ ffrwQ no 157-393-4
Pos jSiuck Benenriung Fabrikat
item jquty , descripJion Type Bemerkuix":
moke type remarks

HS , 24 Control

24.01 inclined seat valve Burkert


casing VA, DN R 1/2"

opening by spring

24.01.2 4-way solenoid valve Biirkert 420 G

gating: 24 volts, D.C

with mounting plate

24.02- 4-way solenoid valve Burkert 420 G


gating: 24 volts, D.C
.with mounting plate

24.02 on/off flap

gating: air/air

DN.25

with acknowledgement•at

positions on and off

approximation initiators
Turk
type: BJ-5-S18-AP-6-X

with 6 m connecting cable


Bencnnijng
dcscripJicn Ktxmfjrte GmtiH D-rbOS i-i'.
Men-und RegelsfucklistG 2590-75-83.01^ ,
jneosuring confrol p i c c e list
Bialt von •
56
of
Proj. Ing Bearbt-iter I Datum { Zeichn Nr
Engelh
^rdt. respcnsibleHellmutI}cJ.p,f^ 7/11/84 ^^ .
Pos 51 i k i j B nGn n u n g Fabrikat
" iion psce dcscripfion • Type jBemc-rkLir
moke h'po i nnfe
24.03 1 on/off flap-

gating: air/air

DN 2 5
with acknowledgement at positions

on and off
II
approximation initiators Turk
type: BJ-5-S18-AP-6-X
with 6 m connecting cable

24.03. 1 4-way Solenoid valve ill Biirkert 420 G


gating: 24 V D.C., with mountij|^^

24 .04 1 on/off flap 7

•gating: air/air; DN 25

with acknowledgement at positions


k on and off

approximation initiators Turk


type: BJ-5-S18-AP-6-X

with 6 m connecting cable

24:04.2 1 4-way sole'npid valve Burkert 420 G


gating 24 V D.C. •

with mounting plate

[
• _
J
]
I
(
1
1 \
r Bcne.'in'jng
ucsr.ripfiai
M e n - und . R e g G I si"ii c k j i si" G
Koin. 2590-75-83."01
\ • pic.te tisi- for measuring and cont rol equiprnenf :Iob No. 5 2 0 - 8 3 - 8 3 .01
Blaff
poge 57
Proj. \ng. Bearbeiter j Datum Zeichn Nr
^ ej^h a rd t drv/.;) no 1 57-393-4
Pos iStucid Benennung
item quiy | FabrikQ( Type Ben'jcrk ur
descripiion mo ke type ^ ^ rRrnarks
24.05 1 on/off flap

gating: air/air; DN 25

with acknov/ledgement at positions

on and off

approximation initiators Turk


typec BJ-5-S18-AP-6-X ^

with 6 m connecting cable

24.05.2 4-way solenoid valve • Burkert


gating: 24 V D.C.

V7ith mounting plate

24.06 on/off 'flap

gating: air/air; DN 25

with acknowledgement at positions

on and off
approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable

24.06.2 V 4-way solenoid valve Burkert


gating: 24 V D.C.

with mounting plate


\—
DoneMRung
dosf.fipllcn
M G Hr u n d R g g e [ s 1* ij cl< j i s i' e' Kom 2590-75-83.01
^ • f'ince list for measuring qhcj confrol equiptnenf Job Ho. 520-83-83 .01
BlaU 57 a
ppge
Proj. Ing. Bearbeiier Datum Zeichn Nr
_EncfeJ.il a r dt responsihI aj^e 7/11/84 f|r\./Q no 157-393-4
PCS SiuST Benennung »-abril<ai
item Type • jBemorkun-
qufy I description fno Ice typo ^ r&mcrKs

24.07 on/off angle valve Alfa Lavc1


gating: openina bv
a1 r
DN 4 0
with acknowledgement at positions

on and off

approximation initiators Turk


type: BJ-5-S18-AP-6-X
with 6 m connecting cable

24.07. 4-way solenoid valve Biirkert 420 G


gating.: 24V DC

with mounting plate

actuation Item 24.07 / 24.08 /

24,09 / 24.10 / 24.11

I'

i
Boncnnuny
descripn'jn
M G R- u n d R e g e [ s i" u c k I i s i' G
Kom. 2590-75-83.01
piece l i s t for measuring end c o n t r o l equipment Job No. 520-83-83.01
Blatt
page 58
Prbj. l!ig. Bearbeiter j Dalum Zeichn Nr
Engelhardt J^elliirath doi e
££sp3nsiblc 7/11/84 rirv/9 no 157-39 3-4
Pos jsiud^r Benennung Fabrikai Type |Bemorkunr5
item (Quty 1 doscriniton make type remarKs ';

24.08 on/off angle valve Alfa


Laval
gating : Qpgj^j^j^g by air-

DN 40

with acknowledgement at

positions on and off

approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable

L.
24.09 on/off angle valve Alf
£a v a l
gating: openiriq by air
DN 40

with acknowledgement at

positions on and off

approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable

24. 10 on/off angle valve


aval
gating: opening by air-

DN 40

with acknowledgement at- positions

on and off

approximation initiators Turk


type: •BJ-S-S18-AP-6-X"
with 6 m connecting c a b l e
DonGnnuna
descripfio.-s

M e n- und R e g e I s f ii c k j i s l* e Kom. 2590-75-83.01


ptece l i s t for measuring and control equipment Job No. 520-83-83,01
Blatt
page 59
Proj. Ing. Bearb&iter Datum Zeichn Nr •
Engelha r d ^ ^espon^bJ^G^elliiTLi^ 7/11 /84 drv/g no 157-393-4
' 'pos "TsTo^ Benennung Fabrikat Tvpe? Bemorkurv';
item jquty description
fti a U e t/pe remorKs '

24. n : . on/off flap

gating: air/air

DN 40

w i t h acknowledgement at positions

on and off

approximation initiators Turk

—t
type: BJ-5-S18-AP-6-X

with 6 m connecting cable

24.12 on/off flap

gating: air/air

DN 150

with acknowledgement at

positions on and off

approximation initiators Turk

type: BJ-5-S18-AP-6-X

with 6 m connecting cable

24.12.2 4-way solenoid valve Burkert 420 Q


gating: 24 V D.C.

with mounting plate.


Deneruiung
clGScripfion
MoH-und Regelsi-ucklisi-e Kom. 2590-75-83.01 J
piece lisf for measuring onri confrol equipment
Job No. 520-83-83.01

page
Proj. Ing. Bearb&iter j Datum Zeichn Nr
r_cspoi^bjG Hellroutli dale 7/1 1 /84 cirw.j no • 1 57-393-4
F^s iSTucl^ Bene-nnung Fabrikai "^ype ^Bemorkurr^-
item U'JU' { dnscriplinn' moke 'fypo
- ' remarks

24. 13.'2 4-way solenoid valve Bii r k e r t 420 G

gating: 24 v o l t s D.C.

with mounting plate

^24. 13 on/off valve Samson 241

DN 32,PN 16, Kvs max.

casing in grey cast

with soft seat

drive: 240 cm.'

closing by s p r i n g towards 10 bar

24. 14.2 4-way'solenoid valve Biirker t 420 G

gating: 24 Volts D.C

with mounting plate

24.14 on/off flap

gating: air/air

DN 250

with acknowledgement at.

positions on and off

approximation initiators Turk

type:- BJ-5-S18-AP-6-X

with 6 m connecting cable

•r
k :
Beneanung, j
descripiiun
M G R- u n d R G g e I s f ij c i? [ i s i" G Kom. 2590-75-83.01
k piece lisf for meGSuring and control Gquipmonf Job t,'o. 520-83-83.01
BlaH 1
page 61 j
Prbj. Icig. BearbGiter \ Datum Zeichn Nr j
_^Engel.hardt rospcnsihle Helinuith riofe 7/11/84 drwg no 1 57-393-4 j
Pos jStuckj Benennung t-abrikoT^rype .""^B^^'C^rkua-i
^ jfem |C}ufy j dpscripiion rri a i; g jype^ J^romarKs |
24. 15.2 A-way solenoid valve Btirke r t 420 G

;ating: 24 v o l t s D.C.

with mounting plate

24.15 on/off valve 241


larason •
DN 25, PN 16, Kvs max.

casing in grey cast

with soft seat

drive: 240 cm^

closing by s p r i n g towards 10 bar


BGDCfmuag" S" / ''"^-"..r^ --
descfipficm
V i, ,4.14 I • .V
Men- und R G g e [ s j - u c k j i s i " e'
Kom 2590-75.-83.01
• fMCce l i s t for measuring and control equipmenf Job No. 5 2 0 - 8 3 - 8 3 .01
Blatf
page 62
Proj. Ir-.g. Bearbeiier Datum Zeichn Nr •
-^S^J: h a r If „Hel}mit}) dofo 7/11/84 drv/Q no 1 57-393-4
Pos jStuckl Benennung Type jBemorkuf%--
Hcm^ jqu^y dnscripJion * Fabrlkai
mo e type [remarKs
26 Supply Air Reducing

Station

Wilker-
26.01 water separator son

26.02 micro filter Wilker- M21-C3


son FOO

26.03 pressure reducer for 1.4 bar Wilker R10-C3-


son 00
with pressure gauge 0 - 4 bar

J
Wilker R10-C3-
26.04 pressure reducer for 6 bar
son 00
With pressure gauge 0 - 1 9 bar

mounting plate with the instru- L e r ch

ments of items 26.01 to 26.04


Bpncfi nung:
dCSCripfion: Moniagcmai'fcirial Lisfe KcMrri.:f)vr Gntin» D-7':-C'r:
lis! of fcr ihc tTcciion Kofn.
Job r-Jo.
Pos. Oai"um: BIQU von;
>i icin. 27 6-3 of:
date: poge :

AnHhf Benennung HersioWfsr Bem.?ikung


qunnI i i y desf.riniion "nTieniTca-
frinnufacturcr ri» m a r k s supply
10 l-lano.'nt' (prunsch lu H v e r s c h r a u b u n q C
pressure gauge connecting fitting R 1 /2 " auf 12 mm
Mono r.i c-i 0 r hri hno (A )
pressure gauge cocks R 1 /2
Kupf er r 0hr ( B)
12- mm jcr o u s s e n
outside dia.
Kufistsiof fsch IGUC h schworz ( ! sfv/.)
100 m 6 • X /, 0
synthetic hose black(actual value)
2000 m Kunststoffsch I ouc h rot Stcuerdruck
s y n t h e t i c h o s e red ( c o n t r o l pressure
Kunststof fschi 0 uch b I ou ( u { uf fr)
500 m s y n t h e t i c hose blue (suppTy a i r ) " 6 X ^ ^
E i n s c h r o u b v e r b indc?r
100 HPT 1/8
screw-in connector
EI n s c h r 0 u i) V e r b i n d o r
loo NPT 1
screw-in connector
Schlnuchverb i nd e r
20 hose connector f. 6 mm Schlauch
f o r 6 mm h o s e
T-Verbindcr
20 T-connector f. 6 mm S c h I ciuch
for 6 mm h o s e
Sfiifz holscn
50 4 mm 0
supporting sleeves
PVC-Gevcbesch i a u c h
DN 25 innen-
Schlcuchschc11 en
ON 25 inne.'i
PVC-Ggv.'cbo&chtQi.rh
loo m PVC f i b r e , hose R 1/2 '
S c h l a u c h tu lion
hose nozz1es R 1/2
Sch I n u c h s c h c d e n
12 hose clamps R 1n
f^ehrfochschlQuchkabe I
x6x 1
BGnennung
cjGScrjpfion
MeB-und Regelsfucklisi-e Kom. 2590-75-83.01 MAELOR
piece l i s t for measuring and confrol equipment Job Ho. 520-83-83 .01
Blatf
page 64
p?oj. Ing. Bearbeiter j Datum Zeichn Nr
Engelhardt responsiblG Hellmuth dnto 7/11/84 drv/g no 1 57-393-4
Pos iStuck. Ben en n u ng Fabrikat Type Bemorkurc
item jquty desert pJ ion moke type remarks

LI 28 Level Control

(Float Balance Tank)

!
28.01 1 level transmitter VaIme t I
i
meas. range: 0 - 2.5 m WG {
{
4
t
supply air: 1.4 bar i
t
output signal: 0.2 - 1 bar (
DN 80; PN 16
!tt
(

f
t
1
1 i
I
1
|28.02 1 P/I transformer Fox bor0
i
I
input: 0.2 - 1 bar
i
1 output: 4 - 20 mA i
i
aux. energy: 110 v o l t s , 50 cycles I
J
type: identical to item 6.02 (
h
t
i
t
1

i
t
(
t
- 1
t
i

I
t
— —_ J %
}
i

f
4
1

• - .

1
Bononnung•
cjcsccipficn
Men- und Regel sfucklisi-e
Kom. 2590-75.-83.01
, • piece lisf for measuring oncJ c o n t r o l equiprnenf Joh No. 5 2 0 - 8 3 - 8 3 . 0 1 ^^^^^^^

B\qU •
page 1
Proj.lfig. Bearbeiier j Datum Zeichn Nr • j
rosponsibiG Hellmuth riale 7/11/84 drwQ no 157-393-4 . 1
Pos jSiurJu Benennung Fabrikat Type i Bemork urv'-
description" •moke
i fem l-ype 1 remcrKs

29 Control Panel

29.01 1 control panel

construction: panel casing."in VA

- designed for being fixed to the t

i
# wall
1
protection type: IP 65 !
!
f
1t
i
i;
1
i
f
1.
{

W f
c

• -1
13
c e o

Quality Assurance Department

The following image quality is


poor due to original page quality

www.cleardata.co.uk
tel: 01670 356 734 fax: 01670 356 439
"- a c - .
.-. ., o- " - ^
. J ? ' vl c

•z . » ; 3

Regelung Steuerung
und UberwQchung

requlai-ion cont-roliinc
and supervision
page 1 to 67
PumpGnsteuerung
pump control
Evaporafer page 60.1to 73.4
High Concentr. page 74 to 80

1-1 f
^ CO ro
••r> OQ ^

>0 11 12 13 lb
SoC <U
C
C31
c
3 =3 Dctum Name Henennuna
a <u 28.3~8U
Georu'; 2590-75-83,01
Gesef^^en
a Maelor
Voiifie 13
oa
u
5j«>
S
5 =
H —Dc<nu
C a
in
O£ • N O
ii-e
go o£
I
D.O o a"
M "•30 n"b s
-t; _- 5 « = <u
S55 —• cn
ffe H -- sz > CQ ^
a
Ia ^ 14 9 a C
Mn
•305
O
ov® e .fi ? u
o^ m
m.cr> ai
^4< z P 5 £ > CO CaL
. at
>3 cn
N CI.
« -aj
a
CD Q.
m r?
o MO
O O
<U
-J cn u>
> CO a
No
CN
o
m m
<u
Scn m
P cn a
=j Q-
fvi m o CN
g 6 o o
O O Q
z: Q.
Netzversorgung 110 V
Karlsruhe GmbH D - 7 5 0 5 EiMingen J
Zeichng. Nr. Index 1
2590-75-83.01 157-393-4 1
BiaH ') *] von
Welvte Rostort 43-0556 A bx AA
5
4A

m
^• pI uIf^
a. 1,
7> p CL "
c

5•
H
ill
•^c a1 -
^ ^

i- c o» - £ ^ 4 - 2 0 mA U - 20mA
« c
7=5
oo oo
m
S 1, «

a. B 3
Z
-. «c
-J

Q Q ^
X2
20psig

1.04

J ii
6 0 psig

Li L

1-06 n

E >
105

electr. lines
pneum. lines

sfeofT) pressure control loop

Ootum Name Benennung


PICA J
20.3.84 Kartspjrie Gir.ri i D-7?C5 E: I - g e
Gezeichn
Gepruft Kom /{eic.hng Nr tnce*
Gesehen 2590 -75- 83.01 , 157 - 393 - 4
rBlo>t
i«<oivw Poiion
2 f,
»a
c
?. K
Z
• c^

3 V a~
CC s

^ *r «_
«. c ecu
f I ! I'
-—- -TLTU C- 20 mA
- = ?A £^
c.- 5 c
o
i 3 t- cr ' ? Q O o o
r7u& c e i t
P.i hii 110V/50Hz
iizo-£S>ry
von BL.1.1
X2 16 air dist^lbu^or A
X5 i i i SBS 20 psig
10 n 12 A2

Qir distributor B
J LI LJ J Lj l-J ll 6 0 psig
-.82

J Lj L|
£
* • ~y' TJ
C
o
C
2.02 cJ
u^

CL
o.
2.06 3
2.03
7
i §

Power
' e

C
I O 2.05
SC screen
ISC mner screen tnduktiv
OSC outer 2.0

-e electr. lines

-74- pneum. I ines

Datum N'cmc Benenrur.c


Gezeichn
C 7 Kcrts'u'he GmbH 0 - 7 5 0 5 Eltimgen

GRD''uf! Kom Zeichng Nr incJd*'

Gesehen - 75-83. 01 157-393- 4


Blolt 3
!
A
o *
fa
o
Sis
oil
i:)
X. a
Hh
HI * o * a, C
4-20mA 4 - 20mA
£ £

Sf 3a » ?
^
OQ O O
%••£ c?
Si 5'{5 o-
i? o o 00
•Ir distributor A
areao 20 DSIG
A3

3.04

air distributor B
6 0 psig
B3

Z1

T3
C
4j UJ LJ a
cn

r 3.06

' / ] 3.01
• £
o
' z J
V

,£ 3.05

-£: electr lines

' c
pneum.lines
D

Datum Bcne'inuog ^
Nome •v.mizGJsjm:^
Geze'Chn 21. 3 . 8 4 IC 3
Konsmne GmoH
Gepruft Ze-cnng Nr
Kom iriuoi
Gesehen 2590-75-83.01 157-393 -A a iI
I
I o
c 3icn f«7iii.i'ii'.»',ijri» I ij m.miii i m/i
"I'o'vi* OftiMn .j-O^M t>
4-20mA
oo

6 6
29 air distribufor A
20 psig

Qir distributor B
taxu 6 0 psig

4
z

J Lj Lj

r
/ 1 4.06

/ I 4.01
I \/
J -t>kh
4.05

electr. lines

-A- pneum. lines

Dalum Name tsenennunc


Cezeicnr. 2). 3 . 0 4 ' TIC4 •'ar»sruh'? GmCH 0-7i)06 EMm'^en
Gepcuf; 2en;nrvg Nr moe'
Gese^en 2590-75- 83.01 157-393 -A
Blati 5
Rjitiir . 1 « -TN™™™
air disi•^lbu^or A
eaasmB aaasa 20psig
••AS

5.0 ff

Qir distribufor B
60 psig
LSBwwra:'IT •••.•i.'^k.i.hj i
4-B6

TC3
a
C71
CJ

CL
5.08 5.06 O.

o
5 07 5 OS
, o

-B- electr. lines

-A pnem. lines

Datum Nome B^nennuna


Gezeichn 22.3.81* PIC 5 K c ris.-'jhe GfT- bH D - 7 5Q5 C3 e
Gepruft Kom Zeichno Nr Ince.'
f
Gesenon 2590-75-83.01 "157 -393 - 4

A K
t f f
c s•

4•20mA 4-20fnA
O O • 0 0 -

'. •: < r
o o
37 38

c
c
n
<v
cn
"co
_

- £ o

<U ^ CJ c
O Si
> clO^

6.01

air supply
min. 1Q00 mn
20 p si g
verticoity up ward
i

min 1000 mm
sfraighf tube

-e- electr. lines

-A- pneum. lines

. .-Itur".
22.3.
Die 6

2590-75- 83. 01 157-393


Eiut; 7
TK"
^ K
•x -
f. c.

4 - 20mA
Q Q Q Q QQ. Q Q O O O O QO CO 00

X2 n d 66 cScS 6 6 66 6 6.66 66 66

I ji J1 li Ji li ji Jl II I
8.01 8.02 8.03 8.04 6.05 8.06 8.07 ft.OB TIAS
8.09

elecfr. lines

femperarure r ec o r d i n g
C'riiuTi Benennunt; ^p g WISGAM'in)
29. 3. e'u ^
'Qf 'jt-.-'v C TzZ^:' E'ti
jeyi o'l Kom ZdChric -'r
Gebe^fri
2590 - 75 83.01 157 - 393 - 4
Dia:: 9 1
AK
-s
1/

r
«o••

U
J?
^t
^ Vs£»i
»•a'£^S
" - r• £ -f
?=l
1- s
^ i'c »• t
? r??
-til/i
o

5 5 If
a i e

O 24V=
ooo 0 00
X7 12
6 X7 H3 0 0
X2 73 74 75
0 0 00
air distributor ^ X2 76 77 73
Lj- 60 psig .-A 10

9.03

Xz
C I
< : < : o .'

23 2/t
a z

cr
c
cu

CL
CL
3

9.06

11 12 13 U 15
condencote super vi sicn

Nofr.e CISA9
Ge/e'CiT^ iMojju^
Gppr.jtt
inrte I
Gesenen 2590-75-83 01 157-393- 4 e "f
B.nr! 11 .or
A'jrx** ®os''ir . ; OWh
ir

HI
11 > a

ub Vo

7t B

ill
t^i K> 5
< - c c» s
rk- ' ^
O O
0 0 0 0 0 0

X7 14 X7 15 6 0 0 6 6 6
6 air distributor 6 X2 79 80 81 X2 82 83 04

60 pstg --All

9.03
CK

X
c
a
Z ZL
o^ !

25 26

-A- t-o page 13


-A-

TT
c
o^
o
a-

V Q.
CV
D

Z/1

9 07

10 n 13 u 15

condenccte supefvisico

Oeze-c r5.11 '.'8U


^n "O'li^urif- Cmo- Crti-noef"
Cecuf /?.fnnq Sr inae •
Gesenvf 2590-75-83 01 157-393-^ e f j
[filer; -12 -c-
"^TfT—
< ?J
:5

" ?f'
• ^t.t •
(H f U
i i - f* .i < *
•.•1

O Q O 0 0 0

6 6 0 66 6
X2 85 86 87 X2 88 89 90

from page 12

TT.

9.08

5 10 12 13 15

condensate super vi si on
f •OtljtTV No'^^e Cpienp.ijng Q j g
Oe/eu 5.11. jfmOijj^ oris-'
jif- OiT'S)- D -- SOS £tf '>
KQTI ir<cie •
— ... —«
2590-75-83 01 157-393- ^ e f
6ion '13 '0'
c
1. ^"<
5
Ci
T3 — O £
F O o. _
3
i
- t -3 V O
- 1o « = g
• >- o
S 4, C
^if
0 t: -c o
= 5S !5 c
u
c r.2 2t ;J 33

III 5i
o o o o

110V 5 0 H z
von Bl. 1.1
rV-,^ a i r distributor X2T91 ^'92
X 5 ?16?17?18

13.02.1 13.02

X3 9-4

yi 13.01

il

10.01

10 11 12 13 U • 15

sealing water
Dotum Name Benennong
H S-control Karlsruhe GmbH D-75:OS Etilrr-oen
Gezetchn 26. U.BU
Gepfuit Kom Zeichnn rir _ _ index
! f !
Gesehon 2590-75-83.0; 157-393-^
cicrt 14- •'ori

wonrie Pcsi;r: i3-0SS&


N K

f
» O"
£ u 5- •
3J
C r

» — — tf
_ a, ? Cr
5?=
? k; = 2 S S
cc
•J .S 'ovA• o
c
o5 £ 5 i
o Q O

X7 018 X7 V-Q Qir disfributor


^

• -A13 60 psig

c
c
10.0 24V CL

29 30

13.03

C'
(b

cv
3

10.02

I C
10 12 13 U 15

SpcerwQsser pump Item H.I

! 'm
)
Cereichn
Ootum

26.
'>10016 Benennung
H S-control KorJsruhe C-T-.tH D-VSH? Ertfrg^r.
i Gepi-uft t:. Zeicnng Nf Infle*
X Gesehen 2590-75-83.01 157-393- 4,
X3
i _c
Bictl 15

Ai
o- s~
U
.s» o>

-J *i
C t5

5-3

fc
V LS c
O 0 O

6 V7To'i distributor
X7 20 A/ ^ I A
--AU 60psig

OJ
tl a
a
• 10.03.2
13.06 a.

Sil

31 32 9 O
X3 47 48

13.05

a
cr

o.
ci
z>

10.03

8 10 12 13 U 15

service water pump item H.2

Dctum Name Benennung


Ge^eichn 26.
H S-control Karlsruhe Grr.bH C - 7 5 0 5 £:;:>ncen

Geof-ufi K'om Zeir.hng Nf


Gesehen 2590-7S-83.01

Wo»>rte Soslctt 43-0556


'0 n 12 • 13 u
selection for item 10
uoforri Ni.f-.t Be'ip'.no'^c
5.11..'84 ^lodoJJM ' HS- control
je&ruft
/e'C.'ing "-tt ir.ce,
Gi?senert 2590-75-83 01 157-393- U 0 • f '
slfiM 1 7
*for><it «Jovi.)r .3 OSife Ai
5
c : > a
~ V
t2
St U i

- 3=
«'5
*- ;
1i i f
o o
000 Q O O

X7
6 Qir distributor
X7 I 25
V X2
01030XY.0105 O O 6
X2 106 107
60 pstg .-A 16

R ^10.05.2
A

C. i
ic ••

35 36
a z

•co
o
C7>

a.
CL
z>

TO

10.05 .

5 6 9 ' 10 n 12 13 U 15

selection for item 10


Ben^ir-orin
HS-conlrol
toce<
2590:75-83 01 1S7-393-4 e ' f
Biafi 18
"21
t (
u
I ••

is 2
" f- r .
t
ir & »
IV
ikf
t c ^
fl
5 -1ei«?»^t
/I •
o o
ooo
X7 26 X7 27
999
O Qlr distributor 0 X2 109110 111
60psig --A17

R 10.06.2
A a
c
>

X z
a

<

37 38

\ZJZ

"O
c
a
C7^
Oi
V >-
CL
a.
3

TO

10.06

2 5 10 ''7 13 U 15

selection f o r item 10
DOIOTI Norrie
Gf/e-c''"'! 5.11..ac
HS-control
• C "SOS fl'ingf-n
Oepfjt' Kom /e-ct^nq Nf inrte •
— .
-
Gese'^en 2S90-75-83 01 157-393-4 e • f '

Biof ,0'
*or<''» S s i U j r . 1
i V
I z
X ^ ft

I u
J
mi
_ Q t- e

f r s.'
l!f
t' i JI-
Cf; o S r -
r 1 a- - ?
fI ? X
»• 1 c •i
*r ?
o o
ooo

X7
o
28 X7
6
29 9 0 0 9 99
air distributor X2 115116 117 X2 118119 120
60 psig --A 18
^10.08 2

X
39

10 n 12 13 U • 15

to the float balance tank

Onium Name Be....... HS-control


Geze'cr^o 5.11 ."84 i&Miu.
Oeprut! Kcm t'eiCf'og Nr
Gesenpn 2590-75-83.01 157- 393-^
e "f

Qiot! 20
J Ui.
BEOE'T'U'^G

G#2e<fv> 6.11 'bL HS - conlrol "ONS'-UHE Gn-.DH O - V S C : RMLMGFT', 1


C>ec»'uf>
/E'C^N^ NF
Oesehen 2590-75-83 01 1S7 - 393-4 e ' f ' f

21 -V - F
tc
- i

Iii
o O
O O O

X7 32 X7 33 6 6 6
0 air distributor 0 X2 127 128129
60psig •.a20
tJ t.;
« ''10.10.2

43 itA

10.10

ro fhe concentrate fanU


Be^o'^'ong
Ge/e'C'v 6.11' HS-control Kansru^e GmbH £tfbr»gen

GfeO'v;"
Geiehen 2590-75-83.01 157- 393-4
BinP 22
ooo

999
X2 1 3 3 1 3 5

10.25

10 n 12 13 U 15

to the concentrate tonk

C'j!UfT> Nnme jjen^onuog


/ e'C nr.
6.11. 8A
HS-conlrol K o n s f u n i * O'T'bH Fttlmgen

Gecu^t K OTi
2590-75-83.01 157- 393-4
H
9 s» Va
tr o
H

« s Vi i !

HI » » C 2/>V =
-- £•
r: A Z
'
o 0 00
'' 5 o oo
o-
*?s 0 9P Q Q 0
6 0
X7 36 X7 37 X2 391W41 X 2 y»2 143 144

air distributor

60psig -I-A22
p 10.11.2

X Z

47 48

to page 25

•o
c
a
ai
. e
ioz
Q.
! E cx
• 3 wt

: c 10 12 13 U 15

I < spray c i eoning

Ge20<cfv> KQrtsAy>0 GmbH Ettiinoer,


1 I Geporfl Zeichrtg f4r '.nds
157-393-4
stGft 24 ^
Oati/m ^^afT>•
Gfizeichn 6.n 8^1
Geon;"
i Os^ichdo 2590 -75-83.01
Datum
1 Gszoicho 6.11 ^ ^jifhtMA.
R Geoa;*t
1 G?9C!>en

'j 1
!
f
&

Ji s

ife i R?
Si-
tt
li f!
Htii
« « •
sti
m
m
?=
tfc -
fc - o 0
0 00 ooo
i ^ C £.
V»-J r?f 6 o 6
V 00
O •£ 6 6 X2 nsvnsfe
X7 38 X7 39 X 2 Tl60n6in62

Qir distributor IJ
A
60psig + A23
P 10.T4.2

X z
<u
>
c
o

50

•o
c
o
CT>
i i
; z
O-
cx
rj
' £

;C o

c
10.K o -J

10 ti 12 13 U 15

spray cIeaning

.icaoast?- .
c e o

Quality Assurance Department

The following image quality is


poor due to original page quality

www.clearclata.co.uk
tel: 01670 356 734 fax: 01670 356 439
" ^ R -

o O
ooo

X7 40
6
X7 41 999 999
air distributor 6 X2 163 164165 X2 166 167168
60ps!g .-A 24
10 .IS.2

51 52
Z E

TD
C
o
s>.
ci
ci

10.15

5 10 n 12 13 U 15

spray cleaning
DotuT! f^Of^-P
Of? 7 e'Cm6 .11 "34 HS-control « 0'•l^'•<J^e O-'^'JO'. trtlm^pn y
jOpt-JIJ om /eic^og Sr incei a
Oescnen 2590-75-83 01 157- 393-^ e" f "1
-••- - —•- — • Dic^t 2 8 '<>'•
i....

< c

SS
»2
o>. "i
a
"« 5
» 15
ac"-

fii
y HI
^ ^- <
® C _ «•,•,.
«6 e ^ T c
soJ» fu f5 t V
cc 3 » • -
sV ' ° ^
o o oo oo

0 XI6U3 Qir distributor 9 P


X2 3/.S 349
0 9
X7 U? 39D 351
•A 25 60 psig
10.20.2

53

"CD
o
cn ]
o;

o.
Q. 1
r) !

10-20

' : c
I : = 10 H 12 13 U 15

Datum Nome Benennorig


H S-control
Gezeichr. 26." VSV Kortsfuhe Gm&H D - 7 5 0 5 Cttungen

Oeoru^t Kom Z»icnng Nr


157-393-U
Qo^ehen 2590-75-63.01
Bioti 2 9
iJ
•f*
< , :5
If SI
>• i

L f
dA c

c ti
r " .' 7V
? i U T'
£ if ?: >
s i/ 5;
- <• •• 0 o 24V,:
ooo ooo

X7U4 X7 A5 6 6 O 6 6 6
X2 T7S176177 X2 178 179180
^ air disiributof 6
A
60psig |A26
® P 10.21.2
A

Xz
r <.

55 56
Z E

X3
C

o
C
Cf
b^

Ci.
CL
ZJ

10.21

to 13 U 15

Spray cleaning
Na«T.e
HS- control Kar(sruh# Gr^.DH 0 7Sf!'5 EtIlinQpn
Oere'C^n ^J^ciauu
Oep'fjft /e'Cfing ^^f tn-iv
G^jse'ien 2590-75-83 01 157- 393- e •f
faian 30 ^or
O
O O O ooo

X7 X7 U7
O X2
000 O 9 0
X2 184185
6 Qlr distributor iai 182 183

60 psig --A27

10.22.2

57 58
2 E

XcJ
07>
C
01

Q.
Q.

10.22

to tl 12 13 U 15

Spray cleaning

No^e HS-coniro!
6 .71 .8U auu ''0''«S'ur>e O^ibH 0 'SCI r;tlingt>r
inoe I
Qp^on^rt 2590-75-83 01 157-393-4 e f
Biott 'O'
j't ••eweweeaDfawiBW
O V

M
f- 'I
V•;

C {• < .
t »=a '
.J ~ 1
»?S ^ j
0 0 Q O 0 0

X7U8 X7
^ 0 Q| r distnbufor
X2
0 6353 6 6355
A 352 3SU
• A28 60 psig
10.23.2-
a> <
CI

<

59 60

f
I
i
•CD
on
c
jC
c.
c.,
Z)

10.23

10 11 12 13 U 15

Speerwasser/ Sealing wafer .


i^'jtor. Nome Beoenr-vj.'^g
H S-confrol
ri'v 26. 4.84 Kcrisru^>e GmOH D-^bOl f Mir-i^n
JvO'ij'" Zeichng .'if inje
Oo^phen 2590-75-83.01 157-393-
Blati 32
NV

O
0 0 o o

XI 50 X7 I 51
QP 00
O O Q1 r distribufor
X 2 356 357 B58T359
• Ai9 60 psig
10.24.2
OJ

I Q.

61 62

"O
c
a
C
OT
i"
1
d
V
T -I Ci.
ZD

\
•10.2A

10 11 12 13 R 15

SpeerwQsser
u'-Jt^m Ren<>nr- u n g
26. 4.8A
Name H S-control Koflsruhe Gmt)HO-7SO^ Ef-Si'^qe'''
Ze'Cfing Nf inac-
2590-75-83.01 157-393-U
e."f
Bian 33
"TT"
S «—
Ml—

d• o&
fs
B> •
=S s
" ^

giE o
V (, c
££ a
C A 3 111
S O osss
O 41 c E
o
o
L.
_
o
c
o

o o

2 W DC
O 9 9 cf O)
X7 S2 X2 187 188 XI 53 Q.
L-

K 11. 02 Ol
L.

2WDC OJ
g
o

-o o-
A A

11.01

3709

8 10 11 12 13 U 15

circuit breaker alarm and fan / level supervision


Dol'jm Name Benennung L S ']']
Gezeichn 3.5.84 A Karlsruhe GmbH D - 7 5 0 5 Eiilingen ^ ^^^ j
GeprCift Kom. Zeichng, Nr. Index ^

Gesehen 2590-75-83.01 157 393 4


Blatt 3 4 von
UL
3jL

<

2U\f =
o2
r3
c l-

iliil;

3 c *• v,
v.

isaC-c b
2"o
iZ<z r.? £

4 ' 2 0 mA
O Q

X3?49 ?50?51

T3
<Z
a
cn

Q.
o.
3)
r

/
I
I
rI
12.01

10 11 12 13 U 15

temperature supervision
Datum Name Benennung ,^ ^ ^^.Ql f QH

4.5.84 Korlsruhe GmbH D - 7 5 0 5 Ettlmgen ;


Goze'chn
Zeichng. Nr. i Index
Gepruft Kom
Gesehen
2590-75-83.01 157-393 - 4 ai f
Blart 35
il m o
OS ? 2AV =
?I r >.3A
T= 1
s
cr III
JH i
•5 O ^

trJ: c '
5 ^ P V£
4=o £i i
z — s r

4-20fnA
O 0

Q Q G
X3T52 153154

"O
c
o
C
O7)I
y.
Q.
P-

O /
/

_J
12.03

10 11 12 13 U 15

temperature supervision

Daium No-Tie Senennung y , ^^ ^^ 02 f QO
Gezeichn U.'i.QU Karlsruhe GmbH D-7505 £tfiirjgen J
Gepru^t Kom Zeichng, Nr ind'- K 1
Gesehen 157-393 - k C[ f j
2590- 75-83.01
Blatt 36
•MCftViIiSlVSSHV
(uooj 10J4UOO ]dUDd Jd4JdAU0D
4UD id
m
oo
•o vO
o
o
3
a.
CN
-o
LO
o- CM
X
a
>
-J-
CM
CM
o
CM
o JC
o -o o sz CT«
ro c
c
r>
o- CN
CVI ^
X 3 £
J
c.
O-
l/>
f Qj
E
JZ
A oi a.
O
c D
T— M o; 6 O
< T-^ 3 C
f LTL
o
^ y r^j
UJ
cn o
c
§ . > 0 1 '
O C
'6 6- CM" O => c
>« cn o
Q. E o c
CL o o o
=3
X t a t/) I -
JZ J—
D
>
Schwm gungsuberwachung
vibroncn supervision
Datum
Name
U.S.31*
Cezeichn Korlsruhe GmLiH D-^50') EUiing^n
Geoojft Kom ZeiChna Nr
mds*
Gesehen 2590-75-83.01 15^7-393 -4 e'r ;
I s/off 37 ^o^T •ENJ
3 Z .

o=

U- 20mA U-20mA
o o o o

X2 2061207
I

Li L,
6 0 psig

LJ

'C

A
U.06 n

1401
>
N ''
S

c
ex.
1W5

-E- electr. lines


-A- pneum.lines

sfenm pressure control loop

Dcf'jm Nome Bonennung


PIC K
Oe 2 eic 20.3. Karlsruhe GmbH D cJti.naen
Geai'u't Kom 2eiCf%ng Nr
Indy »
Gesehen 2590-75-83.01 157 - 393 ' 4
"7f"
3 8
s Ill 1.11.1 I. Ill
5 0 psig

electr. lines

pneum. I i nes

N'fjrvifj Benennunq
FIC 15
Oc" 2 eic.*' 21.3.8^ Knrls'u'^e GmOH D - V S O ' ; j.'

tP'CMng Nr
2590 - 75-83. 01 157-393- 4 e • f
Bicrt 3 9 ^on
N V

U ' 20mA 4-20mA


0o
O O

20ps>g

6 0 psiQ

J Lj U

r
/ "I A
16.06

/ 16.01 J
( _ J
16.05

electr lines

-rH- pneum lines

•-VK.'T ST'T j5ene''>A.>ng


'n i.bu T I C 16 •onsrune OmoH D •." '•Cje:
.ooe»
2590-75- 8 3 - 0 1 1 5 7 - 3 9 3 -A ' e T
sioft 40 'O*"'
JI
r

§ v:
j m

I* - 20 mA 4-20mA
o o o o

X2 6 6
Qir distributor A
20psi5
A 33

17.04 4-
Lj L,
Qir distributor B
60 psiQ
B13 ^ ••B13 --B14

69 71
2 z

Lj Lj

17.06 17.08

F" /

17.01
N/

17.0 5 17 C7

-E- electr. lines


-74- pnem. (ines

JfltuTI oeno.-.n jna


22.3.84 PIC 17 Kofisfune GmnH f
Ze-chng Nr ' Mi—m I'l
•o'f
2590-75-83.01 157 - 3 9 3 -4
Biati 1 von
1

4 - 20 mA 4-20fnA

oo oo
110V50H2 X2 226 22?
von BL 1.1 06
X5 U Ij
025o26o27 air distrtbutorA
22h 23- 32 3130
20ps.g fTYz.
18.02 1804
10
L2 12
LI air distributorB
13 lacccassz
60psig •i^iBtl'
0

3 2 1
ij li t] «-»

f .72 73

118.03

•cn
a
18.06
CT>
cu

18.01
0 > Q.
CL
3
N/
[XI
18.05

Oichleregelkreis density control loop


Datum (Vcme ionennung D l C 18
975'
uesei-z'n Karisfuhe GmtjH i
jQpnjrt KOT. Zeicring Nr
2590-75-83.01 157-393 - 4 e. f
Ci?
Berthold
A-ZOmA 4-20mA 4-20mA
O O
oo oo

X2 230 231 0 0233 O 0


235
232 X2 air distributor A
Hj dj U ij Ij I] 20 psjg
A35 X A.36

19.02
•A
19.04 19.07 -4 f
Qir distributor B
A 33 60psig
r-B16 B16 317
1
lU75 76 77 78 79
2 Z a / 7

A
1906 19 09
V
/
/ ^ A

19.05 19.08
19.01

electr. lines

pneum. lines

.w Doturr. New? BeMD'uiunq j_ | C 19


22'3754 Karlsr-jne GmoH f; ''-.•J •. ' j'••
- e-n Zeichng Nr
; - • - 2 5 9 0 - 75- 83.01 157-393-k
43 'or^ ^ ' ^ '1
N Y

< ,

S?c >
Is ra o
11
c • a r
CT-S = £ ¥
UJ - V ' f
J* • i i J;
oi 3 5 r
?n A> :
% Z -
' oo SS*. ^. » ?
c «- S
r n " 4-20mA - 20 m A
J- * C
!< z ^ i
oo 6o

X2 236 237 X 2 238 239


6 O 6 6

Q.
e
3
Q.
<LI
Variable speed drive
XI

"C
CT
a
cn
OJ

2 0.01 a.
CL
3
c
o o _

! ?
10 11 12 13 U 15

Datum Name Benennung [_ | Q 20


Gezeicnn 9. 5.8(» KorlsruKe GmbH 0-7505 Ettli'^gen
Georuft Kom Zeichng Nr
2590-75-83.01 157- 3 9 3 - 4 f J j
Geseh^n
Biott Zf/f von
i* - 20mA - 20 m A

O O O O

X2 X2 2i»2'243
0 Q O O

Q,
E
rj
CL
Variable speed drive

"O
ac»n

21 .01 CL
Q.
ZD

10 11 12 13 U 15

Ootufn Kome Benennung Lie 21 W l K G A l ^ O


•jezeic.'^n 9. S.^U Kcrisruhe GmoH D-7505 ErMi-ngen
jopru'i Kom Zerchng Nr !nao>
2590-75-83.01 157- 3 9 3 - 4
Gosehec
BiQtt/j.5 von
N r

i%

i lA
^^; f-.
tlA'"e-: • V•• • ?
oI* ?t
9. i t
o O 20 mA
9 9 9 O CO
oo
from page 1.1
X7 55 X7 56 0 0 0 6 6 6 110 V 0 O
6 Qif distributor 6 X2 25fe! 256 y.225725S 259 X2 26C 261
X 5128129'30
60psiq -AB?
23.03
23.02

Z
z:
i: <:
23.01
80 81

c <:

•co
o
4/

\/
O-
O.

23.05

3 4 5 6 to ti u 15

c onder t Q?e sucf-' vi s: o^

5 .11. 84 CISA 23

• t '"^q SR tndoB
» I Oeveno^ 2590-75-83 01 157- 3 9 3 - 4 e' f •
J
47
O
o oo
6 6 6
Ti
X7 57 X7 5 9 99
O
oir cfistributor
6 X2 2G?263 26if
X 2 265 266 2 67
60 psig -A 38
ft P 23.03
A

X Z]

82 83

o
cr

Ci.
cx
3

12 n U 15

condensate super vi si on
Name Senennung ^ j ^ ^ 23
Gf/P'Cfvi 6J1 .84 /[GJCUJ^-^
jeor-J* Koni
Ge&eTytn 2590-75-83 01 157- 393 - 4 e' f ' 1
r Bto't 48 [
o o 24V-
O O O o oo
. ___
X7 59 X7 160 0 9 9 6 6 6
6 o X2 268269 270 X2 271 272 273
oir distributor

60pS!g 4-A39
R 23.03-

Xz
JX

QU85

if- to page 50

N/

ir.

23.07

10 n 12 13 u IS

condensate supervision
Cotun^ Bene'ino'^g Q j 5 ^ 23
6.11.84 GfioM 0-7'j05 Ertliogp'
KOfTi fr>a&»
2590-75-83 01 157- 3 9 3 - I
Bioft 49
000 G O O

p o o 66 6
X2 Zli^ 275 276 X2 277 278 279

a
c
<
S.
Or

c!

"cO
0
01

IT. Ci.
Q.
3

23.08

5 10 n 12 13 U 15

c on den sat e supcrvi slon


r or-in-.
• jeD'jf
6 .n. QU
Some

Zt-iOng Hr 'nopt J
2 5 9 0 - 7 5 - 8 3 01 157-393-^ e"f' 1
Biatt 50 'O"
«• W T
<3 < Z.
J O J,

o o o

XI 61 X7 I 6? X 2 280 .281
6 V oir distributor
A
0 0
• •AUO 6 0 p s i g
24.01.2

X 1613

24 V
13.08

86 87
X3 %

13.07

•CJ
cz
a
c
<vn

c
O
24.01

10 12 13 U 15

Speerwasser
ucMjm Nume 3ener.nung
H S - control
Gezoicrn 26. 4.84 Korlsruhe GmbH D-75C5 Eittmgen
OfrDruK Koni ZeiChng Nr
Gesehen 157-393-U e.. f
2590-75-83.01
BiCff 5T
r

5 ?

ii7

O
o oo o oo
X7 63 X7 tU 9 99 O O O
6 Q«r distributor 6 X2
282 283 284 X 2 285 286 2

60psig --A 41
^ ^lum.i
A

88 89
eiz

•co
a
cr-
o.-

d
CL

24.02

11 1? 13 U 1S

HS-control WSHCS-i^^D
G^ze-cnr 6.11 .84 Ofnt)H 0 i .'tlif-Qtfn
q 'If V.oo «
2590-75-83 01 157- 393 - 4 e 'f '
Blaft 5 2
T T ™
f^ • •

o o 2UM-
O O O
o oo
X7 65 X7 66 9 9 9 6 6 6
6 Qir distributor O X2 288 28^290 X 2 291 292 293

60ps»g --A42

Oi
\ a
C 1

Z o.

90 91

02

XJ
c
o
a<

cs.
rv
••A

£ 1
Q.

12 13 U 15

to float balance tank

TT HS-control
6.11 "O'lsru^e G-^DH D 7'jOS ttt:<r>ceri
•4
IjhmM^
'lOSP*'©' 2590-75-83 01 157- 393 - ^
J. f

.
? J '•'J.
. ~ V
1 :

o O
000 0 oo
X7 67 X7 U 8 6 6 6 p 0
O oir distnbufor 9 X2 2% 295 296 X2 owm 299
60psig 4 A
R
A

Xz
92 93

t <

TC3
a
cr

A
a.
Q.
3

3 i 5 6 10 " 12 13 U 15

to the drain
Nome Benerir.ung
6,n .04 HS-coniroI
Ijm^
"•eofij*:
(^•tf^'rig Sf inde*
« f C>^»se^(^^' 2 5 9 0 - 7 5 - 8 3 01 157- 3 9 3 - 4
3lOtt 54
- ^ V
i _ c
? ¥ t

TD
C
o
CT»
Of

Ci.
c.
3

•2 U 15

• • concentrate tank
Dofun>
6.11. HS-control w n K G A r s M O 1
Ue/e-c^in . /ifiauAA •orisruhe C "^Sl'S Efiimqon J
^ecuf /eic^ftq Nf
- -
2590-75-83 01
Gesonen 157- 393-4
I
1flifjTi 5 5
f
SI

£
V 'J

I• -^

I
J' . ^ C V 4
£V i s ' '
r « r » i

O O
ooo o oo
X7 71 X7 1^72 0 9 o
6 X2 3D6 30/ 308
999
•ir distributor ^ X 2 309 ?.0 311
60psig ••A45
R '' 24.06.2
rs I
c
o
z d.
Ci
OJ
>
c

% 97
eiz

-co
0
C7>

01

a.
a.
n

24.06

5 12 13 U 15
to ihe cleaning

f7' - "afts'une G'^DH D L" rliingo.-. |


OT. 7eif.nng Sf inoft. C
2 5 9 0 - 7 5 - 8 3 01 157-393-U 1
Bion 5 6 ?
w

o O OO ...O 0 0
c—s

0 6 0 00 X2
Q.0 0
teT3107
X?T73 X7 74 X 2 131213131314

^ orr distributor 1. J
A

to pag e 58

x>
c
a

OJ

a.
ex.
3
V TT.

J"!

24.07

10 12 13 U 15

Kcrtsruha CynBH D-750b Et'bno!?f> ^


iMjL^_jju-iiUL-mJ-"WJ»"M miwimiiwjli " n i i < i ~ ~
Hr —K'^.'l j
2590 -75-83.01 157-393-^ n
57
o oo 0 Q O

00Q Q 99
X 2 32ft 325 326 X 2 327 328 329

from to
page 58 page 60

X3
C
o
CJ

O.
O.

24.09

10 12 13 U 15

Korlinjhe GT^OH O-ViOS ir-'.-nm


j Zo«chng ti!

1 157- 3 9 3 - ^
1 Bhjtt 5 9 von
ceo
Quality Assurance Department

The following image quality is


poor due to original page quality

www.cleardata.co.uk
tel: 01670 356 734 fax: 01670 356 439
t

5-
55
n
Vl
» .m
r?? Hi
* ? ^
s- £ «
O OO
Hi
f® ' 0 O O

o 5 .••. 0 66
X 2 33C 331 3 3 2
066
X 2 333 33i*335
CS

from
page 59

c

QJ

a.
C
3k

10 11 12 13 U 15

Ootum Nome B«nennuog


G#2«chn 6.11. 84
HS-control
&(j(UJiU
Ge»nyt j Zoifhrig Kr Indox l!
2590 -75-83.01 157-393- G jf 5
1 BJcit 60 9
i
g
- i

, e
V
?I
* :
?• ••

Pi J - r-,
* ®: y • •

Hr
.ta > ^ < •
0 0 0 0 0 0

0 9 0 6 6 6
X2 336 337 338 X 2 3393W3y

CJ
c
o
d

c
from
page 57.

100101

TJ
c
o
O)
/\
C5.
D

24.11

1 2 3 8 9 10 t1 12 13 U 15

Dotom Nnrne gf nenr-u'^g


Ge^e^c'ir* 6.11 .a; HS-control Gi^D^ D tttlmgen
Gep'ijtf If, tie,
Oe^enen 2 5 9 0 - 7 5 - 8 3 01 157- 393 - 4
Osorf 51 •o'"
E.

<r
i
Oi

-Tf >-3
_ e ' z
Si
£ S S c «.
e. •• •
i* *S O 0 O O O
f
- ^* - i !
P °5» ^c r - 5
f5 ^^
lil I ?i'ti
tr
X7 077 X7 678
V»uJ;- 00 0Q
•.Si .:• i ?
X2 360 361 1352 363

Qir disfributor ij
A
60psig +A£»8
p 2A.13.2

X
lOA 105

r* n
^ I

!I N/ 1
1o t h

• 0,
• c 10 11 12 13 U 15
i5
STEAM
Oolurn Nome Benennunq
G^zeicnn HS-confrol Kofisojhe GmoH 0-750S Etttmgen. I
Gtfpruft Kom 2e»crvi9 Nr lnde>-
weierier. 2590 -75-83.01 157- 393-
atoft
t
s
%
&
t
» ?
f
9 &y
X

o•t
X«9 • >
*

«1
%k
!
Co
?1V
••
>.
- f.
?^
V J E
» u JIf-'f *
«6 - 5r - •
.

'J iifi *

e X •
3JI / » .»
o
O
O OO

T
X7
6
79 X7 80 999 0 0 V
•ir distributor
6 X2 3i»8345 350 X2 351 352 353
A «B5=3=pK=a
60 psjg
« P 24.1^^2

z
A

< <

106 107

/
^ j

•cz
o
C3
cr> 1
<i> 1
3:
C
l.
CL
V

c
a
CL
24.14

4 5 8 9 '0 t1 12 13 U 15

Nafne HS-control
6.11 .8U- Mojum
Oec'u**
2590-75-83 01 157-393-U e "f '
3io" 54
J
N K

o o o o oo

X 7 6 81 X7 682
P0 00
X 3 36i 365 366 367

Qif distributor
A
60psig •fASO
P 2V15.2

loe IDS

•o
c
o
1 CT-
<1>
.s

Q.
CI.
3

24.15

10 12 13 U 15

Dotui^ Ber>enr»ur>q
26
HS -control •^alsnjhe GmOH 0 7^0*2 £tl|in<;.?n
OepruM Z^fChng Nf
Oeserier. 2 5 9 0 -75-83, 01 157- 393- 4
Btatt ^ 5 von
I-—- .^IFI. Illl.*
o5

Ol
c
a
CL

<u
>
c
o

jsippiycir 85-115 psig


oil and wnterfree

I. Diese Reriuzierstafion wird in der Niihe vom Regelschrank monliert


c This Qir sfaHon has to be mounted near the control panel

V
I ! Kundenlleferung
customer supply

pneum. Rsgelung pneum. control


Datum Name Benennung Zuluttreduzisr StotiOH
Oez&r.hn K. 5.84 Gir reducing station Korls.-vihe GmbH D-7505 ET'- '
Gspmft /*. om Zeichng Nr h.ce.-
Gesehen 2590-75-83.01 157 • 3 9 3 - 4
I -i TE
Biatf
A K
- 20 mA
Q Q

X2 355
U Ij

28.02

no 111
/

28.01

-e electr. lines

pneum. lines

hp' ^'"v'"'.' L I 28 W I K G A I ^ X J
22.3.81* -.Ofisfjne GrTibr- C '"rO'i : "K-.^e-
J'' >icnfi.5 Nf
"levp-'^er 2590- 75- 83.01 1 5 7 - 3 9 3 - I*
Bicn 6 7 V
c»f'
WMIIW
L1.1

2F2
i r -r
t I-^ —-
i i
\k

2K1 \ 2K1

X3 X3
f- r

Auto

2\ JC CJ
c
c o
2 SI -A C3 a.
w e
.C
1 AutomoHk cn c
2 STOP CC t_f
3 0
U START

10 11 12 13 U IS

; WISSGANXJ.
1U.2 Vocuumpump Koftsrui-e Gmb»- D-7S05
fCom Inde"
2590 - 75 ^83.01 1 5 7 - 393 -4
62 J
Diott
1L1
U2
113
N

3F1
i'

Jl 3 S
3K1 VA-^ 3K2 3K3VA-A

BFZ [ c d E in sl

XI

7.5 KW

?
2 10 11 12 t3 u 15

Doti^ Noma
K. 3 Feed pump KrrHo^ GmbH D-7505
0«7«K:hn 27.9.84
Kom Z»icihrtc f* tnMx
Gepnjft
2 5 9 0 - 7 5 - 83.01 157- 393 - 4
u I G»s»hen
Bkjtt 6 r r WW
! 1

Kt

s '2

6 J

5'I

5C " -
V ^ = I

s.'^a: 4 ?

3S1
1 Autom.
2 STOP
3 0
<. START X2 Xh
I X3
X3

1 2 3
A
y
1 Autom.
2 0
3 Hond

3 K3 3Kr2\

IKK . 3 K2 7 JC
c
o

C Q-
] s O O C P 0
3K2 3K ^ 3K 1 3K 1.2 3K 3 3H 15
in

6401
L AL A f
63116405
6if09 6i;i3 6312
6307 6W35 6413
6313
6308 6303
6309 6 301V
6 305
o
c
>
e
c 10 11 12 13 U 15

• Datum Nome
279 84 14.3 Feed pump Korisru^« GmbH D-7505 i;trTr.Qfn
Ocprjft
2590 - 7 5 - 83. 01 157-'393 U
GesXien
filott
Dahjfn f^ome 1 Bertennxjng W I E G A K T O
GeTe<.hn
279. QU ''r" Oil illU . 5 { Pump ex- woy 2 Konsnir>e oTitjH D-7S0S sftt^nen
OeprxJt Kom Zucf^ng Nt inaer
1 2 5 9 0 - 75 - 83. 01 157-393 -4
1 BfQ» 66»'1 yo.t
.6F2
l |
o; .
rsi I-

6K1 \ 6K1

X3
f

Auto

I 23 t
6 SI J - X ^ V - H-i-—]
1 Automolik
2 STOP
3 0
4 START

10 11 12 13 U. 15

1C.6 Pump ex - way 3 Korisnjhe Gmoh 0-7505 E??»r:gen

K OTJ Zeicnng Nr tndtx


^ 5 9 0 - 7 5 - 8 3 . 01 157 - 3 9 3 -U
! 6 lA
L1.1
.. c.
^ \ •>
s~5 111 —
w0 i
^ tc k -J 112 —
4. •»
t t. EJ 113 —
C
P£ - 7F2
1J c
•TL -TL I I
vt t
t g £
«. ~

' CA;

^ "s i ^ t
tiiin <~> —•
7 F I
r
fj 7 K1 \ 7 K1 \
: -- £ c t i
ifot r r 5C t/i
—O
•S.-S ? i J 3r
X3 XI X3
r
XA

1 3 5
7 K1
7 U
l2 3 \
^ 1
7S1
1 AutomoHk
A ^O oo .
W o
7 F2 C c t 2 STOP a> c
3 0 S s
I* START

XA X2
i .
X3 X1
.^
1 Autom.
2 0
3 Hand
7H1
o
JC
3.0 KW c
a

rt> •s 2
1/1 o
c o.
—Of
6801
68C6 I/)
6811

10 11 12 13 U IS-

f^'ne
279.
I Cere<hn H.7 Pump ex - way Kor?sruh« GmbH D-7505 Err^ngcn
l&ecyuC j Zeichng Nr
2 5 9 0 - 7 5 - 83. 01 1S7 - 393 -4
1 Bian 6 S-'? J
L1.1

' - (

r^
« »
-c

C » -a r r-7 10? 1
c a- ? • t-Df 3
»^ ^: -tO Q,(/•
n
—O ^
3

M 3 S
10 K1 V-
2 4 6

10F2 n e t

XI . ^

4>
E
o

E is
3
o
Q

c*
I
•s
c 1 10 11 12 13 U IS

Datum
Benennur*g
Cezetchn27 9 fiia^iu K.10 Pump by fnnk Ktfrisrune GmoH 0-7S05
OopojJT Kom Zeicfing N'
Oesef^en 2 5 9 0 - 7 5 - 83. 01 157-393 -4
71
•rr
N !

» >

c?
«
c .

?? ; 4i- ^ :
; V i.

•^ c £ > i
N 1 2 'ii J
11 ST
1 Autom.
2 STOP
3 0
i. START

X3

0
11H 15

L A
7305 7301 7311 721"? 7305
7309 7313 7 212
7207 7305 7313
7213
7208 7203
7 2 09 720!t
7205

10 11 12 13 U 15

Dotxjm Name Benennung


14.11 Condensate pump KortsVuhe D-750S ETw-^pn
Ge/enc/vi 279 84
iGcen^ Kom Z9'Chr>g Nr
2 5 9 0 ^ 75- 83: 01 157- 3 9 3 - 4
js^off 73
2 J
r. *I

'I N

U. 2

13F1
V i • 5iJ
» p - -• V
=4 ? i •• •- 2 i-

1 3 5 ,3
13K1 VA-A
2 <> 6
•A-V
? t6

13F2 C C C
Einsl

X1

w1

15 KW

8 10 11 12 13 U 15

Ootum Nome 8«oefWjr>g


•27.9. U.13 Cooling wafer pump Kortsoihe GmbM 0-7505 Erir-qen
Opojft • . Kckti Z»ichr\g Nf
2 5 9 0 - 7 5 - 83. 01 157- 3 9 3 - 4
Bwtt 74 voo

I . 13F2 -TL-

1 Dotum Name Ben^nnung


ICe^ffc/wi 27.9 84 U . 13 Cooling Korisruhc D - 7 5 0 5 tttt-^gen

KofTt ZeiChrtg Nr mac*


\OeprJft .
2590 157- 3 9 3
"JGese^ten
ISlaft IS
Dohjm Nomt B^n^nnung 1 WIEG-A^^TO
\GeTe<hn 27.9. H.15 Feed pump | Korlirune G^^DM D - r S O S Etrtr>^en 1
''C'lflll-L
- Horn ZeKhng Nr mde* j
2 5 9 0 - 75 - 8 3 . 0 1 157 - 3 9 3 i 1
1 Biott 7 7 von J|
1L1
W -« t C® U2
t- •^ 1L3
»J
Pi
« «

I
r - » <
c-i:
I
-—-
i i 5
t t ir-= ;
16F1
< (i a> i
i' k "C
O t/-
3
rti

§!

1 3 5
16K1 V-V"^

16 F2 C Z C

.^

Oi
c
c

Ootxjm

I 279 ei* 14.16 Product pump ex 3 Kortsnj^e G t i d h D - 7 5 0 5 tryr>g*'

Gef^nJ! 2^'Chng Nr —? r*
2 5 9 0 - 7 5 - 8 3 . 01 157 - 393 - 4
&>ofi 7 8 von
L1.1

O1
t^ 5» r_ \
El
5 ». i~t :. .
- ~
J i =£ ?i

" t ^ } I; =
I- i t • c
i • i. ; •
6 i " ?2r — ••
C « I Z ~
Pi'i
5- * : 18r 1
•OC fZ;
3
c/>
fS
— o
?
3

1 3 5
18K1.V-V-A

18F2 d c d

>
T3
Ita>

10 11 12 13 H 15

Oofum N<yne Benennung


27 9
Oezttchn ''rrL:^ 1A.18 Product pump ex 1A Kon5'•u^e GmoH 0-75C5 Etv-qen
Oeprjf Kom ZeiChng Nr
Gese/^n 2 5 9 0 - 7 5 - 8 3 . 01 1 5 7 - 3 9 3 -4.- 1 1
e'crr ft n voo
14
MAINTENANCE tB-12B956
Diff^^ent^ai Pressure Transmitters Issue 1
with Remote Seal Elements Oct 1981
3423T, 3424T, 3473T, 3474T, 3478T, 3479T, 3481T, 3482T M o d e l B

Refer to the Table of Contents in one of the' following publications for a list of all
sections applicable to these transmitters.

3^1237, 3424T: IB-12B229


3473T, 3474T, 3478T, 3479T: IB-12B230
3481T, 3482T: 16-120231

T A B L E OF C O N T E N T S

Para Page Para Page


1 INTRODUCTION 2.8 Adjusting Overrange Stop 11
1.1 Removing Transrr»ltter from Service 3
1.2 Test Equipment and Tools 3 3 TROUBLESHOOTING
1.3 Repair-By-Exchange Program 4 3.1 General 12
3.2 Troubleshooting Electronics Assembly 13
2 CALIBRATION 3.3 Troubleshooting Optional Surge Protector ..17
2.1 Span and Zero Adjustments 6
2.1.1 General 6 4 REPAIR
2.1.2 Zero Jumper 6 4.1 Replacing Electronics As.senibly 20
2.2 Test Setup 6 4.1.1 General 20
2.3 Zero Based Calibration 7 4.1.2 Removing Old Electronics 21
2.4 Elevated Zero Calibration (Negative Upper 4.1.3 Installing New Electronics 22
Range Value) 8 4.2 Replacing Measuring Element 23
2.5 Elevated Zero Calibration (Positive Upper 4.2.1 Removing Old Measuring Element 23
Range Value) 9 4.2.2 Installing New Measuring Element 23
2.6 Suppressed Zero Calibration 9 4.3 Replacing Electronic Components 26
2.7 Center Zero Calibration 10

ILLUSTRATIONS

Rg. Page Rg. Page


9 Example of Span and Range Values for an
1 Bectronlcs Assembly 5
2 Location of Zero Jumper 6 Elevated Zero Calibration with Positive
3 Calibration Circuit 7 Upper Range Value 9
4 Example of Span and Range Values for a 10 Example of Span and Range Values for a
Zero Based Calibration 7 Suppressed Zero Calibration 9
Test Hookup for Zero Based and 11 Example of Span and Range Values for a
Suppressed Zero Calibrations 7 Center Zero Calibration 10
Span and Zero Adjustments 8 12 Adjusting Overrange Stop H
Example of Span and Range Values for an 13 Component Locations for Electronics
Elevated Zero Calibration with Negative Assembly
Upper Range Value 8 14 Troubleshooting Flow Chart for Transmitter
Test Hookup for Elevated Zero and Center Electronics '•S
Zero Calibrations 8

S Y B R O N TaylOf
IB-123956 . . . , . .

^ B L E OF CONTENTS

I L L U S T R A T I O N S (Cont'd)

Fig. Page - Fig Page


15 Troubleshooting Flow Chart for Optional 20 Replactng Electronics on Transmitter with
Surge Protector •...18 Threaded Cover " 21
16 Removing Surge Protector ...19 21 Replacing Measuring Element on Transmitter
17 Test Circuit for Surge Protector . ..19 with Bolted Cover 24
18 Surge Protector Circuit Board ...19 22 Replacing Measuring Element on Transmitter
19 Replacing Electronics on Transmitter with with Threaded Cover • 25
Bolted Cover ...20

TABLES

^pie - • Page Table Page


1 Test Equipment 3 3 Input Values for Adjusting Overrange Stop.... 11
2 Tools 4 4 Troubleshooting Chart 12

<

Use of D A N G E R , W A R N I N G , C A U T I O N and NOTE

This publication includes D A N G E R , W A R N I N G , C A U T J O N and NOTE infornialion where


appropriate to point out safety related or other important information.

DANGER — Hazards which will result in severe persona! injury or death.

WARNING — Hazards which could result in personal injury.

CAUTION — Hazards which.could result in equipment or property damage.

NOTE . — Alerts user to pertinent facts and conditions.

Although D A N G E R and W A R N I N G hazards are related to personal injury, and C A U T I O N


hazards are associated with equipment or property damage, it should be understood that opera-
tion of damaged equipment could, under certain operational conditions, result in degraded
process system performance leading to personal injury or death. Therefore, comply fully with all
D A N G E R , W A R N I N G and C A U T I O N notices.
llJf

-vr-r-wryr
•"I'f-rrrfi-
DIFFERENTIAL P R E S S U R E T R A N S M I T T E R IB-12B956{AS)
with Remote Seal Elements Issue 1
3423T. 3424T. 3473T, 3474T, D e c 1381
3478T, 3479T, 3481T. 34S2T
Model B
A D D E N D A SHEET
Use only with Instruction 18-123956, Issue 1

Substitute the following for the corresponding instructions on pages 22 and 23.

4.1.3 Installing N e w Electronics 8. Adjust output with strain gage in its free posi-
tion. Proceed as follows:
CAUTION
Do not bend bellows which connects stud a. Turn S P A N adjustment fully clockwise
to strain gage. If bellows becomes bent, (22-turn potentiometer).
the electronics may have to he replaced.
b. Remove strain gage from mounting bracket
1. Assemble nut L on stud of new strain gage. Turn and hold strain gage in same orientation as
nut until it is flush with end of threads nearest its mounted position with nothing touching
strain gage. stud.

2. Insert strain gage stud into hole in yoke and tem- Turn ZERO adjustment until output is
porarily fasten strain gage to bracket with one 1.263V dc ±0.005. Clockwise rotation in-
nut T, Rgure 19 or 20. (Strain gage will be re- creases output.
moved again in Step 8 for a zero adjustment.) •
Turn S P A N adjustment counterclockwise
3. Assemble potentiometers as follows: until output is IV dc ±0.002.

a. Bolted Cover — Insert each potentiometer Turn'ZERO adjustment clockwise until out-
shaft into hole in base. Figure 19, and slowly put is 0.709V dc ±0.002.
turn plastic adjustment cap until driving rib
on cap engages slot on end of shaft. Retain Allow strain gage to hang over side of base
potentiometers with screws B. and proceed to Step 9.

b. Threaded Cover — Assemble poten- 9. Be sure both sides of measuring element are
tiometers in base and retain with screw E, vented.
Rgure 20.
10. Insert strain gage mounting posts into holes in
4. Mount circuit board as follows: mounting bracket •

a. Bolted Cover — Mount board in base and 11. Lubricate the threads of three strain gage mount-
retain with two screws A. Be sure wires are ing posts, Rgure 19 or 20, with Dow Corning
- not pinched in board mounting grooves. Molykote 505' (or equivalent). Be sure shoulders
of posts are free of lubricant.
fa. Threaded Cover — Assemble board on cir-
cuit board bracket with four screws C, then CAUTION
mount bracket in base and retain with The raised shoulder of three nuts T must
screws D. face the strain gage. Incorrect positioning
of the nuts can interfere with transmitter
5. Connect black and gray wires to terminal block performance.
TBI on circuit board. Black wire connects to -i-
(plus) terminal and gray wire connects to - Finger-tighten strain gage to bracket with three
(minus) terminal. nuts T. The raised shoulder of nuts T must face
strain gage,
6. Connea calibration circuit, Figure 3.
12. Align the strain gage so stud is centered in hole
7. .Place ZERO jumper in NORM position. Figure 2. in yoke; then lighten three nuts T to a torque of 8
inch-lbs (0.9 Nm).
'T.M. of Dow Comrng Co.

SYBRON Taylor
IB-'r2B956{AS)

13. Finger-tighten nut K on stud of strain gags.


NOTE
Be sure to replace "and securely fasten
14. Adjust nuts K and L until output is IV dc ±0.04,
cover as soon as maintenance is com- '
then tighten nuts. Do not ovenighten. Output pleted.
must be IV dc ±0.04 after tightening.
15. Calibrate transmitter. Refer to 2 Calibration.

Substitute the following for the corresponding instructions on pages 23 and 26.

4.2.2 Installing New Measuring Element 8. Asse.mbie potentiometers in base as follows:

CAUTION
a. Bolted Cover - Insert each potentiometer
Do not bend bellows which connects stud
shaft. Figure 19, into hole in base and slowly
to strain gage. If bellows becomes bent, turn plastic adjustment cap until driving rib
the electronics may have to be replaced. on cap engages slot on end of shaft. Retain
potentiometers with screws 8.
Remove force beam protector from new measur-
ing element.
b. Threaded Cover - Assemble poten-
2. Continue assembly as follows: tiometers in base and retain with screw E.
Figure 20.
a. Bolted Cover - Assemble base on measur-
9. Mount circuit board as follows:
ing element, i=jgura 21. Position base so that
terminal box faces Kl side of measuring ele-
ment. Retain base with two spring washers a. Bolted Cover - Mount board in base and
and screws P. retain with screws A. Be sure wires are not
pinched in board mounting grooves.
b. Threaded Cover — Assemble mounting
plate and retsin with four screws N Fiaure b. Threaded Cover - Mount circuit board
22. bracket in base and retain with screws D.

3. Assemble yoke to end of force beam. Orient 10. Connect black and gray wires to terminal blocks
yoke as shown in Figure 21 or 22 and retain with TBI on circuit board. Black wire connects to -f
screw R. Tighten screw R to a torque of 20 inch- (plus) terminal and gray wire connects to -
lbs (2.2 Mm). (minus) terminal.

11. Connect calibration circuit. Rgure 3.


Lubricate threads and underside of screw heads
of two screws M with Dow Corning Molykote
12. Place ZERO jumper in N O R M position. Hgure 2.
505, or equivalent.
13. Adjust output with strain gage in its free posi-
5. Assemble strain gage bracket and retain with tion. Proceed as foilov/s:
two screws M. Tighten screws alternately to a
torque of 10 inch-!bs {1.1 Nm); then tighten to a
a. Turn S P A N adjustment fully clockwise
torque of 50 inch-lbs {5.7 Nm). (22-turn potentiometer).
6. Adjust nut L on strain gage stud until it is flush
with end of threads nearest strain gage. b. Remove strain gage from mounting bracket
and hold strain gage in same orientation as
its mounted position with nothing touchina .
Insert strain gage center stud into hole in yoke stud. ^
and temporarily fasten strain gage to bracket
with one nut T, Figure 19 or 20. (Strain gage will
c. Turn ZERO adjustment until output is
be removed again in Step 13b for a zero adjust-
1.263V dc ±0.005. Clockwise rotation in-
ment.) creases output.
w
IB-12B956(AS)

d. Turn S P A N adjustment counterclockwise Finger-tighten strain gage to bracket with three


until output is IV dc ±0.002. nuts T. The raised shoulder of nuts T must face
the strain gage.
e. Turn ZERO adjustment clockwise until out-
put is 0.709V dc ± 0.002. 17. Align the strain gage so center stud is centered ih
hole in yoke; then tighten three nuts T to a
f. Allow strain gage to hang over side of base , torque of 8 inch-lbs (0.9 Nm).
and proceed to Step 14.
18. Finger-tighten nut K on center" stud of strain
14. Be sure both sides of measuring element are gage.
vented.
19. Adjust nuts K and L until output is 1V dc ±0.04,
15. Insen strain gage mounting posts into holes in then tighten nuts. Do not overtighten. Output
mounting bracket, must be IV dc ±0.04 after tightening.

16. Lubricate the threads of three strain gage mount- NOTE


ing posts. Rgure 19 or 20, "with Dow Corning Be sure to replace and securely fasten
Molykote 505 (or equivalent). Be sure shoulders cover as soon as maintenance is com-
of posts are free of lubricant. Be sure no lubri- pleted.
cant is cn bracket.
20. Calibrate transmitter. Refer to 2 Calibration.
CAUTION
The raised shoulder of three nuts T must
face the strain gage. Incorrect positioning
of the nuts can interfere with transmitter
performance.

Printed in U.S.A. TP-10096


iB02B956

INTRODUCTION

IIMTRODUCTION

1.1 REMOVING TRANSMITTER FROM from damage during handling. If a seal diaphragm is
SERVICE damaged, the transmitter must be returned to Taylor
for factory repair.
WARNING
Process pressure and material retained 1.2
by T E S T E Q U I P M E N T A N D T O O L S
the sea! elements can cause injury andThe test equipment required to calibrate and trouble-
damage equipment. Standard plant safe- shoot the transmitter is shown in Table 1.
ty procedures must be followed when
removing the instrument from service. The tools required to disassemble and reassemble
the transmitter are shown in Table 2.
Turn off power to transmitter and disconnect wiring.
Do not loosen or remove bolts' and nuts in the WARNING
measuring element body. Do not use a soldering iron in an area
classed as hazardous by the electrical
When removing the seal elements from service, do code. Explosion or fire may result, thus
not allow the seal diaphragm to be bumped or causing injury or property damage.
scraped. After removing a sea! element, immediately Remove instrument from service for
attach a cover over the seal diaphragm to protect It repair in a workshop.

Table 1. Test Equipment

MINIMUM
^.DESCRIPTION CHARACTERISTICS QUANTITY

Power Supply 24V dc ± 1 0 % 1

Voltmeter 0 to 25V dc 1
± 1 mV accuracy at 1.25V

Ohmmeter Oto 5k 1

Jumper Wire A inches 1

62.5 Ohm Precision


Resistor 0.1% 1

Manometer or Gage As required for trans- 1


mitter range. Accurate
to 0.25% of transmitter
range

Air Supply - 1

Pressure Regulator - 1

Shutoff Valves -

Tubing £f Fittings - As req.

1211-145
IB-12B956

TRODUCTION

« Table 2. Tools

TOOL SIZE QTV USE

3/32-inch T B I Screws & Scrcw B


Screwdrivers
3/16-inch Screws A, C. 0 . E & N
Open End Wrench 1/4-inch 2 Nuts K & L

3/32-inch 1 Screw R
Hex Wrenches
&/32 by 4-inch long Screws M & P
with T-Handle

100 in. ib 112 Nni) 1 Screw M


capacity with 5/32-inch
hex driver

50 in. lb (5 Nm) 1 Screw R


capacity with 3/32-inch
hex driver

Torque Wrcnches 25 in. lb (2.5 Nm) 1 Nuts T


capacity with 1/4-inch
socket

Capacity and socket 1 Flange nuts on measuring


as required. Refer to element
Replacing Diaphragm
Capsule.

Soldering Iron 40W 1 Replocing Electronic Components

E-12I1-146A

1.3 R E P A I R - B Y - E X C H A N G E P R O G R A M pensated as a matched pair. Individual replacement


If It Is necessary to replace ihe transmitter electronics strain gages or circuit boards are not available.
assembly. Figure 1, the used assembly can be re-
turned for credit against the purchase of arnew elec- NOTE
tronics assembly. Contact Taylor for detailed infor- The hermetically sealed strain gage is not
mation about this program. field repairable. Any attempt to repair the
strain gage will void the instrument war-
The strain gage force unit and circuit board In the ranty and make the electronics assembly
electronics assembly are factory temperature com- ineligible for credit under the Repair-By-
Exchange Program.
IB-12B956

INTRODUCTION

Circuit Board

>Z«ro JumpiH

Figure 1. Electronics Assembly


IB-12B956

IRTION

CALIBRATION

NORM y
i M Position 07
« I « .a .
»I IS I • { u>NORM


RS
oi\
£l
EL/SUPR
Position

YYFtDRRRCSYGGGA
125P!857-CVI 125S1857-
O O

Figure 2. Location of Zero Jumper

2.1 S P A N A N D ZERO A D J U S T M E N T S Is lowered below 48.5 Inches of water (11.63 kPa),


the output will remain essentially constant at approx-
2.1.1 General imately 0.233V dc.
The design of the transmitter circuit minimizes the in-
teraction between the span and zero adjustments to 2.1.2 Zero J u m p e r
simplify the calibration procedure. Because of this A zero jumper is located on the clrcuifboard. Figure

« iture, the transmitter output will not respond


early to changes in input which are below the
lower range value by more than 0.5% of cpan. Also,
2. The N O R M position is for zero based calibration
and increases the sensitivity of the external ZERO
adjustment. The jumper must be moved to the
there will be essentially no output changes in EL/SUPR position for some elevated, suppressed,
response to input changes which are below the lower and center zero calibrations. Refer to 1.4 Specifica-
range value by more than 1.5% of span. tions, for ranges available in both the N O R M and
EL/SUPR positions. Adjustments to trim an existing
For example, assume that a transmitter has been calibration can be made using the S P A N and ZERO
calibrated for a span of 100 inches of water (25 kPa) adjustments located on the outside of the housing.
with a lower range value of 50 (12) and an upper
range value of 150 inches of water {37 kPa). When 2.2 T E S T S E T U P
the input is 50 Inches of water (12 kPa) the output The transmitter is part of a two-wire system. Thus, It
measured across the 62.5 ohm resistor. Figure 3, will does not contain an internal power supply. The test
be 0.25V dc (4 mA). If the input Is lowered by 0.5% equipment required to calibrate the transmitter is
of span to 49.5 inches (11.88 kPa), the o4tput will shown in Table 1. Calibrate the transmitter using the
decrease linearly by 0.5% to 0.245V dc. If the input is circuit shown In Figure 3. The voltage drop across
further lowered to 48.5 Inches of water (11.63 kPa), the 62.5 ohm precision resistor will be 0.25 to 1.25V
the output response will not be linear; and if the input dc for a 4 to 20 mA dc output change.

T^r^yr.-r^r. I'T'TT'
IB-12B956

IRTION

Output

Figure 3. Calibration Circuit

If the transmitter catalog number has electrical con- 2.3 Z E R O B A S E D C A L I B R A T I O N


nection suffix 02, 03, 04, 05, or 08, the terminal box An example of a zero based calibration Is shown in
on the transmitter contains a 2.5 ohm, 0.1% preci- Figure 4.
sion calibration resistor. This resistor may be used in
place of the 62.5 ohm resistor shown in Figure 10. 1. Connect output to calibration circuit as shown in
The voltage drop across the 2.5 ohm resistor will be Figure 3; and connect input to test hookup as
10 to 50 mV dc for a 4 to 20 mA dc output change. shown In Figure 5.

If the transmitter catalog number has electrical con- Be sure that both seal elements are at the same
nection suffix 03, an output test jack is connected elevation, so that the head pressures In the
across the 2.5 ohm precision resistor. The test jack measuring element are equalized.
accepts a standard miniature phone plug, Taylor Part
No. 113S290. Other acceptable plugs are G.E. Elec-
tronics numbers 33-660, 662, 664. 666, 668, or 670.

If the transmitter catalog number has electrical con-


nection suffix 08, an output current meter jack which
accepts a miniature phone plug Is connected across a
shunting diode. Refer to the schematic diagram in
the back of this Instruction Manual. Wafar type seal e l e m e n t s Installed
back-to-back between 3" A N S I
blind f l a n g e s . ( F l a n g e s ' t a p p e d for
Use the test hookup shown In either Figure 5 or input c o n n e c t i o n . )
Figure 8 for applying calibration inputs. To determine Input
the type of calibration required for a specific applica- M a n o m e t e r or G a g e
A c c u r a t e to 0 . 2 5 % of
tion, refer to the Process installation Section. Transmitter Renge

Pressure
Regulator
Lower Range Upper Range -Air Supply
Value Value
0" + 120"
{0 kPa) (+30 kPa) -Bleed

N o t e ; A calibrating fixture, Taylor P a r i N o . 153S7,


Span = 120" c o n be u s e d to c e l i b r s t e t r a n s m i t t e r s w i t h
(30 kPa) C I 2 0 9 I6C(I| w a f e r t y p e or c h e m i c a l too type seal element.

Figure 4. Example of Span and Range Values for Figure 5. Test Hookup for Zero Based and
a Zero Based Calibration Suppressed Zero Calibration
IB-12B956

RTION

k --)
' ' IT"-' 1 K'.LJi» Jiiiii !
TAYLOn » r Zoro
Span Adjustment
Adjustmant- ft " c u t>H r^i*''
ago €>T| 1
H-O SPA* Span
Adjustment

BOLTED COVER THREADED COVER

Figure 6. Span and Zero Adjustments

2. Place ZERO jumper in N O R M position. Figure 2. 2.4 ELEVATED ZERO CALIBRATION


(Negative Upper R a n g e Value)
^ ^ Adjust input to lower range value. An example of an elevated zero calibration with
negative upper range value is shown in Figure 7.
Examples
U.S. Units: 0 inches of v^ater for a 0 to 1. Connect output to calibration circuit as shown in
Figure 3, and connect input to test hookup as
+120 inch range.
shown in Figure 8.
SI Units: 0 kPa for a 0 to +30 kPa range.
Be sure that both seal elements are at the sama
4. Turn ZERO adjustment, Figure 6, until output is elevation, so that head pressures in the measur-
0.25V dc ±0.001. Clockwise rotation increases ing element are equalized.
output.
2. Place ZERO jumper in N O R M position. Figure 2.
5. Adjust input to upper range value.

Examples
U.S. Units: 120 inches of water for a 0 to
+120 inch range.

^ SI Units: 30 kPa for a 0 to +30 kPa range.

6. Output should be 1.25V dc ±0.0025. If it is not, W a f e r type seal e l e m e n t s Installed


turn S P A N adjustment to obtain 1.25V dc. bsck-to-back between 3" A N S I
blind f l a n g e s . (Flenges t a p p e d for
Clockwise rotation increases output and de- input c o n n e c t i o n . )

creases span. Input

M a n o m e t e r or G a g e
7. Repeat Steps 3 through 6 for required accuracy. A c c u r a t e to 0 . 2 5 % of
Vented Transmitter R e n g o

Pressure
Regulator
Lower R a n j e Upper Range
Value Value -cJa ^ Air S u p p l y
—134" -44" 0"
( - 3 4 k Pa) ( - 1 1 kPa) (0 kPa)
-tSj- -Bleed

/ ^ Span = 90" N o t e : A calibrating fixture. Taylor Part N o . 1&3S7,


c a n be u s e d to celibrato transmitters w i t h
I (23 kPa) w a f e r t y p o or c h e m i c o l tee type seal elemtfnt.
M i n u s indicates positive pressure
applied to L O side E-I209-I6r|ll
Figure 8. Test Hookup for Elevated Zero and
Figure 7. Example of Span and Range Values for an Center Zero Calibrations
Elevated Zero Calibration with Negative
^^ Upper Range Value
IB-12B956

IRTION

3. Adjust input to lower range value. at the same elevation, so that the head pressures
In the measuring element are equalized.
Examples
U.S. Units: 134 inches of water for a 2. Place ZERO jumper In N O R M position. Figure 2.
- 1 3 4 to - 4 4 inch range.
3. With input connected to LO side, adjust input to
SI Units: 34 kPa for a - 3 4 to - 1 1 kPa lower range value.
range.
Examples
4. Turn ZERO adjustment. Figure 6, until output is U.S. Unrts: 37 inches of water for a - 3 7
0.25V do ±0.001. Clockwise rotation Increases to + 5 inch range.
output. If output of 0.25V dc ±0.001 is not
possible, refer to 2.1.2 Zero-Jumper; then SI Units: 9 kPa for a - 9 to + 1 kPa range.
repeat Steps 3 and 4.
4. Turn ZERO adjustment. Figure 6, until output is
5. Adjust input to upper range value. 0.25V dc ±0.001. Clockwise rotation increases
output. If output of 0.25V dc ±0.001 is not
Examples possible, refer to 2.1.2 Zero Jumper; then
U.S. Units: 44 Inches of water for a - 1 3 4 repeat Steps 3 and 4.
to —44 inch range.
5. Connect Input to HI side; and adjust input to up-
SI Units: 11 kPa for a - 3 4 to - 1 1 kPa per range value.
range.
Examples
6. Output should be 1.25V dc ± 0.0025. If it is not. U.S. Units: 5 inches of water for a —37 to
turn S P A N adjustment to obtain 1.25V dc. + 5 Inch range.
Clockwise rotation increases output and de-
creases span. SI Units: 1 kPa for a - 9 to + 1 kPa range.

7. Repeat Steps 3 through 6 for required accuracy. 6. Output should be 1.25V dc ±0.0025. If it is not,
turn S P A N adjustment to obtain 1.25V dc.
Clockwise rotation increases output and de-
Lower Range Upper Range creases span.
Value Value
-37" 0" 4 5"
1 - 9 kPa) ( O k P a l ( + 1 kPa) 7. Repeat Steps 3 through 6 for required accuracy.

•Span = 4 2 " -
dOkPa) Lower R a n g e Upper R a n g e
M i n u s indicates positive pressure Value Value
0" • 12" + 122"
appljed to L O side e-I209-U<|l> (0 kPa) («3kPa) l + 30kPa)

Figure 9. Example of Span and Range Values for an


Elevated Zero Calibration with Positive •Span a 120"
(Z7kPa)
Upper Range Value C-1ZB-16K2ia(1)

Figure 10. Example of Span and Range Values for a


Suppressed Zero Calibration
2.5 ELEVATED ZERO CALIBRATION
(Positive Upper R a n g e Value)
An example of an elevated zero calibration with 2.6 S U P P R E S S E D Z E R O C A L I B R A T I O N
positive upper range value is shown in Figure 9. An example of a suppressed zero calibration is
shown in Figure 10.
1. Connect output to calibration circuit as shown in
Figure 3; and connect input to test hookup as 1. Connect output to calibration circuit as shown In
shown in Figure 8. Arrange input line so that It Figure 3; and connect input to test hookup as
can bs switched from the LO side to the HI side shown in Figure 5.
connection. Be sure that both seal elements are
iB-128956

lLIBRATION

Be sure that both seal elements are at the same 2.7 C E N T E R Z E R O C A L I B R A T I O N


elevation, so that the head pressures in the An example of a center zero calibration is shown in
measuring element are equalized. Figure 11.

2. Place ZERO jumper in N O R M position. Figure 2. 1. Connect output to calibration circuit. Figure 3,
and connect input to test hookup. Figure 8. Ar-
3. Adjust input to lower range value. range input line so that it can be switched from
LO side to HI side connection.
Examples
U.S. Units: 12 inches of water for a + 12 Be sure that both seal elements are at the same
to + 132 inch range. elevation, so that the head pressures In the
measuring element are equalized.
SI Units: 3 kPa for a + 3 to +30 kPa
range. 2. Place Z E R O jumper in N O R M position. Figure 2.

4. Turn ZERO adjustment. Figure 13, until output is 3. With input connected to LO side, adjust input to
0.25V dc ±0.001. Clockwise rotation increases lower range value.
^ ^ output. If output of Q.25V dc ±0.001 is not
possible, refer to 2.1.2 Zero Jumper; then Examples
repeat Steps 3 and 4. U.S. Units: 60 inches of water for a - 6 0
to + 6 0 inch range.
5. Adjust input to upper range value.
SI Units: 15 kPa for a - 1 5 to + 1 5 kPa
Examples range.
U.S. Units: 132 inches of water for a + 1 2
to + 132 inch range. 4. Turn ZERO adjustment, Figure 6, until output is
0.25V dc. ±0.001. Clockwise rotation increases
SI Units: 30 kPa for a + 3 to +30 kPa output. If output of 0.25V dc ±0.001 is not
range. possible, refer to 2.1.2 Zero Jumper; then
repeat Steps 3 and 4.
6. Output should be 1.25V dc ±0.0025.-lf it is not,
turn S P A N adjustment to obtain 1.25V dc. 5. Connect input to HI side and adjust input to up-
Clockwise rotation increases output and de- per range value.
creases span.
Examples
Repeat Steps 3 through 6 for required accuracy. U.S. Units: 60 inches of water for a - 6 0
to + 60 inch range.

Upr)cr Range
SI Units: 15 kPa for a - 1 5 to + 1 5 kPa
Value range.
0" •»60"
(0 kpd) (+15 kPa)
6. Output should be 1,25V dc ± 0.0025. If it is not,
turn S P A N adjustment to obtain 1.25V dc.
Span = 120" (30 kPa)
Clockwise rotation increases output and de-
Minus indicates positive pressure creases span.
applied (o LO side E-1XI9W0<II

Figure 11. Example of Span and Range Values for 7. Repeat Steps 3 through 6 for required accuracy.
a Center Zero Calibration

10
IB-12B956

CALIBRATION

8. Adjust Input to 0 inches of water (0 kPa). Table 3. Input Values for Adjusting Overrange
Stop
9. Turn ZERO adjustment until output is 0.75V dc
±0.001. Input
Catalog (115% of M a x i m u m Span)
2.8 A D J U S T I N G O V E R R A N G E S T O P Number
The purpose of this procedure is to position the over- Inches of water kPa
range stop so that it does not interfere with operation
over the calibrated range of the transmitter. Use this 3423T
procedure only if the factory setting of the overrange 3473T
230 56
stop has been disturbed. 3478T
3481T
1. Connect output to calibration circuit as shown In
Figure 3; and connect test hookup as shown in 3424T
Figure 5. Be sure that the seal elements are at the 3474T
747.5 184
same elevation so that head pressures in the 3479T
measuring element are equalized. 3482T

8. Repeat Steps 4 through 7 until required output is


. obtained.

9. Adjust input to 115% of maximum span and note


output. This output must be maintained while
performing Steps 10 through 12.
Screwdriver

10. Tighten upper screw L. This screw will serve as


the pivot point for the overrange stop.

11. Use a screwdriver to adjust overrange stop as


shown In Figure 12. Move stop toward strain
gage until stop contacts force beam. Contact Is
- indicated by a slight decrease in output (0.02V dc
maximum). After adjustment, output must be
within 0.02V dc of value noted In Step 9.
Figure 12. Adjusting Overrange Stop
12. Tighten both screws L securely. After tighten-
ing, output must be within 0.02V dc of value
2. Loosen both screws L, Figure 12. Check over- noted in Step 9.
range stop to be sure it does not obstruct move-
ment of force beam. If it is not, loosen both screws L and repeat
Steps 10 through 12.
3. Place zero jumper In N O R M position. Figure 2.
13. Adjust Input to 0 Inches of water (OkPa). Output
4. Adjust input to 0 inches of water (0 kPa). should return to 0.25V dc ±0.002.

5. Turn ZERO adjustment, Figure 6, until output is If it does not, check for interference between
0.25V dc ±0.001. Clockwise rotation increases overrange stop and force beam. Repeat Steps 9
output. through 13, if necessary.

6. Adjust input to 115% of maximum span, Table 3. 14. Calibrate transmitter for required span.

7. Output should be 1.4V dc ± 0.05. If It Is not, turn


S P A N adjustment to obtain 1.4V dc. Clockwise
rotation Increases output and decreases span.

11
IB-128956

OUBLESHOOTING
4

TROUBLESHOOTING

3.1 G E W E R A L formation on isolating an electronic problem. If the


The symptoms shown in Table 4 provide a guide for transmitter has an optional surge protector, refer to
isolating a problem related to either transmitter in- paragraph 3.3 for information on isolating a problem
stallation or operation. If an operation problem Is In the surge protector circuit. Refer to 1.3 Repalr-
traced to the transmitter electronics, the cause may By-Exchangc Program for information on the
be in the circuit board. Refer to paragraph 3.2 for in- replacement electronics assemblies.

Table 4. Troubleshooting Chart

J^ Problem Possible Cause Action

No output signal a. Transmitter on closed tank liquid a. Recalibrate as required. Refer to


level installation; not calibrated for 2 Calibration.
elevated zero
b. LO side seal element is above HI b. Bring both elements to same
side element elevation."
c. No power to transmitter c. Turn on power.
d. Transmitter leads reversed d. Check electrical connections.
e. Loose wire on transmitter terminal e. Check wiring inside transmitter.
f. Strain gage incorrectly connected f. Cheek adjustment of nuts K and L.
to force beam Refer to 4.1 Replacing Elec-
tronics Assembly.
g. Electronics Assembly g. Refer to 3.2 Troubleshooting
Electronics Assembly,
h. Surge Protector Circuit h. Refer to 3.3 Troubleshooting
Optional Surge Protector.
i. Damaged diaphragm 1. Replace measuring element. Refer

to 4.3 Replacing Measuring Ele-
ment.
(p
Output signal too a. Incorrect calibration a. Recalibrate as required. Refer to
low 2 Calibration.
b. LO side seal element is above HI b. Bring seal elements to same
side element elevation.
c. Strain gage Incorrectly connected c. Check adjustment of nuts K and L.
to force beam Refer to 4.1 Replacing Elec-
tronics Assembly.
d. Electronics d. Refer to 3.2 Troubleshooting
Electronics Assembly.

Output signal too a. Incorrect calibration a. Perform calibration.


high b. HI side seal element is above LO b. Bring seal elements to same
side seal element elevation.
c. Strain gage incorrectly connected c. Check adjustment of nuts K and L.
to force beam Refer to 4.1 Replacing Elec-
tronics Assembly.
d. Electronics d. Refer to 3.2 Troubleshooting
Electronics Assembly.
m
TROUBLESHOOTING

Table 4. Troubleshooting Chart (Cont'd)

Problem Possible Cause Actior>

Output remains at a. No power to transmitter a. Turn on power supply.


0 mA dc b. Transmitter leads reversed b. Check electrical connections.
c. Electronics c. Refer to 3.2 Troubleshooting
Electronics Assembly. Replace
strain gage or circuit board as re-
quired.

Output remains at a. Electronics a. Refer to 3.2 Troubleshooting


4 mA dc Electronics Assembly.

Unable to rezero a. Strain gage incorrectly connected a. Check adjustment of nuts K and L.
to 4 mA dc after to force beam Refer to 4.1 Replacing Elec-
changing span tronics Assembly.
setting

Turning zero or a. Electronics a. Refer to 3.2 Troubleshooting


span adjustment Electronics Assembly.
does not changc
output

Zero shifts on a. Strain gage bracket shifting a. Tighten screws M, Figure 21 or 22,
vibration service to 50 inch-lbs (5.7 Nm).

Zero shifts due to a. Transmitter housing used as a step a. Do not stand on transmitter.
deflection of
housing

3.2 TROUBLESHOOTilMG ELECTRONICS If a problem Is traced to a component on the circuit


ASSEI\fiBLY board, it is recommended that the electronics
If an electronic component malfunctions, it can be assembly be replaced. This is because of the low-
located using Rgure 13 in conjunction with the level signals on the board and the selected com-
troubleshooting flow chart. Figure 14, and the ponents required for proper circuit operation.
schematic diagram in the back of this Instruction
Manual. If the cause Is the strain gage force unit, If it is necessary to replace a component on the cir-
the electronics assembly (strain gage and circuit cuit board, refer to 4.3 Replacing Electronic Com-
board) must be replaced with a factory-tested ponents before making the replacement. After a
assembly. The strain gage and circuit board are fac- component has been replaced, recalibrate the
tory temperature compensated as a matched pair. In- transmitter. If the transmitter cannot be calibrated,
dividual replacement strain gages or circuit boards further troubleshooting is required.
are not available.

13
B-12B956

UBLESHOOTNG

TP7

TP6

TPS

-TP3
e o o o o o o o o o o ooo o
YYF E DRRRC B T G G G A

Span
Potentiomeier

Zero
Potentiometer

Figure 13. Component Locations for Electronics Assembly

1 -.1

14
IB-12B956

TROUBLESHOOTNG

LEGEND

t ^ START

NOTE: M a k o oil voltage I I PROCEDURE


measurutnents with a
precision voltmeter.
OECiSiON
O
STOP

o
Disconnect black and gray
wires from T B 2 on surge pro-
tector circuit board. Power
supply m u s t be connected to
these wires to bypass surge
protector.

Connect power supply 124V


dc : 1 0 % > t o o u t p u t terminals
* (plus, black) and - (minus,
gray). D o not use an output
load resistor.

Connect negative voltmeter


lead to negative terminal of
p o w e r s u p p l y . M a k e all
voltage measurements using
positive lead.

M e a s u r e vol a g o at TPl.
Figure 13.

C h e c k power supply connec-


tions a n d D3

Replace
D 1 or Q l .
1
M e a s u r e voltage
at TP2.

Check a n d Q1
with
ohmmoter.

Yes

Place Z E R O jumper. Figure 2.


in E L / S U P R position.

XC-121Vt33 SH. 1 ol 3

Figure 14. Troubleshooting Flow Chart for Transmitter Electronics

15
IB-12B956

^bUBLESHOOTING

Replace
Turn Z E R O adjustment.
R g u r a 6. until voltage at TP3
rO 11
isSVdc.

' A d j u s Replace
gi ZERO
9V dc ^ ^ potentiometer.

Yes
No

M e a s u r e voltage at TP4. C h e c k for L I is


open LI. OK

Yes
No

Connect a ju nper wire be-


tween T P S anc TP6.

M e a s u r e vol age at TP7.

Rcplace A2

Yes

Connect a jumper wire be-


tween TP4 and TPS. Turn Z E R O adjustment
to obtain > 9V dc
at TP3.

M e a s u r e voltage at 1P7.

M e a s u r e vo( age at TP4,

C - i m - i a u i l S H , 2 of 3

Figure 14. Troubleshooting Flow Chart for Transmitter Electronics (Cont'd)

16
IB-12B956

TROUBLESHOOT^NG

Connect jumper wire be-


tween T P S a n d TP6.
R«pUc«
D2. 02 Of Q3

Measure vo taga at TPS.

Check
D2. 0 2 . 0 3

Disconncct jumper wire. Check R15. R16 a n d S P A N


potentiometer. R a p l a c o if
necessary.

Calibrate traris mitter. refer to


2 C A L I 8 R A T I C N.
C ' l 2 1 1 ' t 3 0 S H 3 el 3

Ra placo
electronics
assombly.

Transmitter
is
OK A

Figure 14. Troubleshooting Flow Chart for Transmitter Electronics (Cont'd)

3.3 TROUBLESHOOTING OPTIONAL A defect in the surge protector circuit can be isolated
SURGE PROTECTOR using the troubleshooting flow chart. Figure 15, in
conjunction with Figures 16 through 18, and the
DANGER schematic diagram in the back of this Instruction
Capacitor CI retains up to 200V dc ofManual. If a problem Is traced to a component,
charge. Bodily contact with the charged replacement of the surge protector circuit board is
capacitor car) result in injury or death.
recommended.
Discharge the capacitor before dis-
assembly of the test circuit.

17
B-12B956

UBLESHOOTNG

Start
)
c
R e m o v e circuit b o a r d from
transmitter. Figuro 16.

M e a s u r o resistance between
terminal B L K o n T B 2 a n d
terminal • o n T B I .
Diode No Replace S u r g e
O h m m e t c r m u s t be capable
V^^SDZ g l o w s ^ ^ Protector
of s u p p l y i n g m o r e t h a n
100 m A d-c in R X 1 position.
Yes

S o t s w i t c h at c h a r g e p o s i -
tion. t h e n return s w i t c h to
No Replace S u r g e test p o s i t i o n
Protector

D i o d e ^ S s ^ No Replace S u r g e
">>w S D l g l o w s ^ ^ Protector
M e a s u r e r e s i s t a n c e betweert
p o s t R ) a n d terminal -
Yes
(minusJ o n T O l .

S e t s w i t c h at c h a r g e p o s i -
tion a n d d i s c annect tost
l e a d s f r o m ci cuit b o a r d .

No Replace ^ u r g e
Protector

C o n n e c t * test lead t o p a d
Yes
X a n d - { m i n u s } lead to ter-
minal - (minusi on T B I .

C o n n c c t s w i t c h , capacitor

d 1 a n d resistor to p o w e r sup-
ply. Figure 17. Set s w i t c h at
c h a r g c position.
S e t s w i t c h at test p o s i t i o n .

C o n n c c t • test lead to ter-


minal • on T B I and
LEGEND No Replace Surge
{miiuis) test load to pad X.
Protector
( ) START

PROCEDURE XB'121Mt4
S e t s w i t c h Bt test position

O DECISION

STOP

o
Figure 15. Troubleshooting Flow Chart for Optional Surge Protector

18
IB-12B956

TROUBLESHOOTING

Insulator

Rgure 16. Removing Surge,Protector

SURGE PROTECTOR
CIRCUIT BOARD

Charge TBI
TMt

S Test Switch R1
200V d c 1GC O h m B
Power CI 10%
Supply 20: 5W
UF

Note:
Oiodas and Resistors may
b o c o n n o c t c d , d e p e n d i n g upon V ''o* J
elecifical c n n n o c t i o n suffix.
iRofer to s c h e m a t i c at back of Pad X o n
tfiis Instruction M a n u a l . ! Componertt Side

P o s t R1

/ . o
o
o \ O \o o Figure 17. Test Circuit for Surge Protector
l - l "i
' i '

Pad X-^ ' O o


nt
o
m 00 R2
3 @o
\ —flZCO-

Rgure 18. Surge Protector Circuit Board

19
IB-12&956

jyAiR

REPAIR

Cover

Potantiomeiars

Strain Gage
Forco Unit

Plastic
Adjustment
Cap

Figure 19. Replacing Electronics on Transmitter with Bolted Cover

4.1 REPLACING ELECTRONICS available. The strain gage force unit and circuit board
ASSEMBLY are temperature compensated together. Individual
replacement strain gages or circuit boards are not
4.1.1 General available. Refer to 3.2 Troubleshooting Elec-
The circuit board and strain gage assembly. Figure 1, tronics Assembly before replacing the electronics
must be replaced as a unit. Field replacement kits are assembly.

20
IB-12B956

REPAIR

Covsr'

Circuit B o a r d
Bracket

i S c r e w D^

Potantiomatars

Basa

Strain G a g a
Force Unit

Figure 20. Replacing Electronics on Transmitter with Threaded Cover

2. Disconnect wires from terminal block T B I on cir-


WARNING cuit board.
The hermetically sealed strain gage is
N O T field-repairable. Tampering with 3.the Remove circuit board as follovk/s:
strain gage cover, the mechanisms inside
the cover, or the external strain gage a. Bolted Cover — Loosen both screwfs A and
wires, can inteiiere with transmitter per- lift circuit board out of base, Figure 19.
formance and thus cause injury and dam-
age property. b. Threaded Cover — Loosen four screws D
and lift circuit board bracket out of base.
4.1.2 Removing Old Electronics Figure 20. Remove board from bracket.
1. Remove cover, Figure 19 or 20.

21
IB-12B956

>AIR

I Screw R|

-Yoke

" \ >
Fiatwasher
— Overrange Stop \f : . In
Screw H

Lockwasher—^

Base

Figure 21. Replacing Measuring Element on Transmitter with Bolted Cover

24
IB-12B956

REPAIR

— i Screw r {
Yoke ft'

Lug o n Force Bea

Figure 22. Replacing Measuring Element on Transmitter with Threaded Cover

25
IB-12B956

ilR

9. Mount circuit board as.follows: 18. Adjust nuts K and L until output is I V dc
±0.007, then tighten nuts. Do not overtighten.
a. Bolted Cover — Mount board in base and re- Output must be I V dc ±0.007 after tightening.
tain with screws A. Be sure wires are not
pinched in board mounting grooves. NOTE
Be sure to replace and securely fasten
b. Threaded Cover — Mount circuit board cover as . soon as maintenance Is com-
bracket in base and retain with screws D. pleted.

10. Connect black and gray wires to terminal blocks 19. Calibrate transmitter. Refer to 2 Calibration.
T B I on circuit board. Black wire connects to +
(plus) terminal and gray wire connects to — 4.3 REPLACING ELECTRONIC
(minus) terminal. COMPONENTS

11. Connect calibration circuit, Figure 3. NOTE


Because of the low signal levels In the cir-
I ^ ^ l a c e ZERO jumper in N O R M position. Figure 2. cuitry on the circuit board, it is recom-
mended that the circuit board be replaced
13. Adjust output with strain gage in its free posi- with one known to be good rather than
tion. Proceed as follows: one repaired.

a. Turn S P A N adjustment fully clockwise If It is necessary to repair a circuit board, carefully


(22-turn potentiometer). follow the procedures listed below. Use care when
replacing components on the circuit board. Surface
b. Remove strain gage from mounting bracket contamination, poor soldering technique, inadequate
and hold strain gage In same orientation as its varnish coating, etc., can cause errors In circuit
mounted position with nothing touching stud. operation.

c. Turn ZERO adjustment until output is 1.263V WARNING


dc ±0.(X)5. Clockwise rotation Increases out- Do not use a soldering iron in an area
put. classed as hazardous by the electrical
code. Explosion or fire may result; thus
d. Turn S P A N adjustment counterclockwise un- causing injury or property damage.
til output Is I V dc ±0.002. Remove instrument from service for
repair in a workshop. Refer to 1.1
Turn ZERO adjustment clockwise until output Removing Transmitter from Service.
is 0.709V dc ±0.002.
Use the following procedure when replacing any
f. Allow strain gage to hang over side of base component on the circuit board:
and proceed to Step 14.
1. Remove circuit board assembly from transmitter.
14. Be sure both sides of measuring element are Refer to 4.1 Replacing Electronics Assembly.
vented. Always handle the circuit board by the edges or
by the circuit board bracket.
15. Lubricate beveled surface of three nuts T, Figure
19 or 20, with Dow Corning Molykote 505, or 2. Scrape the varnish off the appropriate solder
equivalent. pads. •

16. Insert center strain gage stud-into hole In yoke 3. Unsolder and remove old component. Use a
and fasten strain gage to bracket with three nuts 40W soldering Iron. Do not apply more heat than
T. Tighten nuts T to a torque of 8 inch-lbs is necessary to melt the solder. Too much heat
(0.9 Nm). for too long a period of time can damage other
components and the circuitry on the board.
17. Assemble nut K on stud; do not tighten.

26
B-12B956

REPAIR

4. At the holes where the old component was 8. Rinse area with running de-Ionized water for at
dislodged, remove all.old solder from the circuit least 30 seconds.
y pads and the holes in the circuit board.
9. Bake circuit board in a clean, air-circulating oven
5. Solder new component onto the circuit board. for a minimum of 2 hours at 150°F (65'.6®C).
Position component as shown in Figure 14. Use
a 40W soldering iron. Do not apply more heat 10. Apply a uniform coat of HumiseaP 1A20
than is necessary. Too much heat from a larger Polyurethane Insulating Varnish (or equivalent
soldering Iron can damage the new component per MIL-1-46058B). Bare areas must be com-
and the circuitry on the board. Also, too little pletely coated.
heat from a lower wattage soldering iron for too
long a time can do the same. 11. Air dry at room temperature for at least 24 hours.
If a second coat Is required, apply It after the first
6. Remove flux from the circuit board and compo- coat has dried for at least 4 hours but before It
nent leads with a toothbrush and denatured or has dried for 24 hours. The varnish must be
99% isopropyl alcohol. Clean the area at least cured at room temperature; it does not cure
three times. All flux must be removed from the sooner at elevated temperatures.
circuit board.
' Manufactured by Humiseal Div., Columbia Technical Corp.
7. Clean area with Freon TF'.

• Manufactured by E.I. du Pont de Neniours & Co.

''if- '

27
^-126956

ffilES

NOTICE

Information in tHis manual is intended onty to assist our customers in the efficient
operation of our equipment. Use of this manual for any other purpose is specifically pro-
hibited and its contents are not to be reproduced in full or part without prior approval of
Marketing Communications Department, Taylor Instrument Company. Division of
Sybron Corporation.

ked in U.S.A. TP-8202

28
rrtfii i i i i i r inr II iii j a M a a j M r i i a f c h ML..

IB-128320
Issue 1
Oct 1S81

INSTRUCTIONS
GAGE PRESSURE TRANSMITTER
w i t h R e m o t e Seaf E l e m e n t s
3444T, 3445T, 3446T, and 3447T Model B

A
SYBRON Taylor
IB-12B320(AS)
GAGE PRESSURE TRANSMITTER Issuo 1
with Remote Seal Element Nov 1982
3444T. 34457, 34467. and 34477 Model B

A D D E N D A SHEET
Use only with Instruction 13- 12B320, Issue 1.

Page 5: Add the following Infomiation.

3447T — 7r3nsm{rtBr for Extruder Applications 83 — Yugoslavian Safety


Span adj from 2500 to 8,000 psi- Commission Approval
(17 500 to 55 000 kPa) 84 — Canadian Intrinsic Safety — See Table 1
CSA Approval
MEASURING ELEMENT ACTUATION • 88 — Australian Intrinsic Safety
F — Gage Pressure S A A Approval
99 ~ Electrical Code described by
ELECTRICAL CODE Accessory {147) ~ See Table 2
10 — General Purpose
Taylor Standard ^ E A L ELEMENT DIAPHRAGM MATERIAL
21 - U.S. Division 2 - See Table 1 'Z _ Type 316L S S T
USA 3 - Hastelloy-C^

O-3/GL SST p^rAyfKCE: S-Hint/anJ

Page 11: Substitute the following for the corresponding Information on page 11.

2.2 ELECTRICAL CONNECTIONS 2.2.2 All Installations Except European


Flameproof
WARNING Run wiring through the electrical connection hole in
Do N O T make electrical connections the transmitter housing, Rgures 2, 3, 4, and 5. If the
unless the electrical 'code designation transmitter has an external terminal box, Rgure 6,
stamped on the transmitter data plate ' run wiring through one of the connection holes in the
agrees with the classification of the areabox. All connection holes are threaded to accept a
in which the transmitter is to be installed. conduit connection. Always plug any unused con-
Failure to comply with this warning can
nection hole.
result in explosion end fire; leading to in-
jur/ and property damage. Transmitters which have BASEEFA, CENELEC or
S A A electrical code approval are supplied with a
2.2.1 General cable gland installed in the electrical connection hole,
The transmitter is designed to be part of a two-wire Rgure 2. The gland provides for the required sealing
system. The 4 to 20 mA dc output signal and the dc of wiring entering the .housing.
power to the transmitter are carried by the same pair
of wires. The transmitter does not contain a power Make connections to the transmitter terminals as
supply. The necessary power supply can be separate shown on the connection diagram in the back of this
from the instrument load or built in as shown in the manual. For intrinsically safe applications, be sure to
connection diagram in the back of this manual. note the Intrinsic safety barrier requirements shown
on the connection diagram.
The nominal power supply voltage is 24V dc. The
supply voltage at the transmitter terminals must be 2.2.3 European Rameproof Installations
betv/een the limits of 13 and 36V dc. The output losd Transmitters which are approved for use in European
limit depends on the supply voltage as shown In Flameproof code areas are Identified by the Electrical
Table 6.
Code digits 42 in the instrument catalog number

SYBRON Taylor
{B^12B320(AS)

(refer to 1.3 Serial and Catalog Numbers). These « Hawko Type 501/454, size 0, for unarmored
trensm^ers have an external terminal box with an cable ""1
earth terminal and cover lock. Figure 6A.
2.2.4 Shunting Diode
Run v/iring through the 3/4-Inch Int NPT connection The transmitter may have an optional shunting
hole in the terminal box, and make connections as dlode(s} connected between terminals R and M, R1
shown on the connection diagram in the back of this and M or R2 and M. Transmitters with the diode are
manual. Wiring must enter the connection hole identified by the Bectrical Connection Suffix digits
through a B A S E c f A approved flameproof frtting. 02, 03, 04, 05, 07, or 08 in the catalog number. Refer
Use an approved Hawke fitting, or equivalent. to the schematic diagram in the back of this manual.

Hawke flameproof fittings are manufactured by The diode(s) is connected to shunt an external out-
Hawke Cable Glands Limited, Oxford Street West, put meter, and provides a .signal path so that the
Ashton-under-Lyne, Lancashire 0L7 ONA, England. transmitter will continue to operate if the meter is
Two approved fittings for this connection are: removed from the circuit. Do not remove the shunt-
ing diode when connecting an external meter.
« Hawke Type 501/453/T, size 0, for armored
Aable

•Eartf)
/ Terminal

Conn
NPT
/
Conn. Plugged
*

Rgure 6A. Mounting Dimensions for European Rameproof Sectrical Connection

;
.?n-ni£d in U . S . A . ©Tayior Instrument Companv. Division of Sybron Corporation. 1982 TP-11265
NOTICE

Information in this manual is intended only to assist our customers in the efficient operation of our
equipment. Use of this manual for any other purpose is specifically prohibited and its contents are
not to be reproduced In full or part without prior approval of Marketing Communications Depart-
ment, Taylor Instrument Company, Division of Sybron Corporation.

Use of D A N G E R . W A R N I N G , C A U T I O N and NOTE

This publication includes D A N G E R . W A R N I N G , C A U T I O N and NOTE information where


appropriate to point out safety related or other important information.

DANGER — Hazards which will result in severe personal injury or death.

WARNING — Hazards which could result in personal injury.

CAUTION — Hazards which could result in equipment or property damage.

NOTE — Alerts user to pertinent facts and conditions.

Although D A N G E R and W A R N I N G hazards are related to personal injury, and C A U T I O N


hazards are associated with equipment or property damage, it should be understood that opera-
tion of damaged equipment could, under certain operational conditions, result in degraded
process system performance leading to personal injury or death. Therefore, comply fully with all
D A N G E R , W A R N I N G and C A U T I O N notices.

•Prepared by:
MARKETING COMMUNICATIONS DEPARTMENT
TAYLOR INSTRUMENT C O M P A N Y O DIVISION OF S Y B R O N CORPORATION
95 Ames Street. Rochester, New York 14601 U . S . A . V 7ie-235-5000
€1
Printed In U . S . A . TP-9433
IB-12B320

TABLE OF CONTENTS

TABLE OF CONTENTS

Para Page Para Page


1 INTRODUCTION 3' OPERATION
1.1 Description 4 3.1 Putting into Operation 19
1.2 Serial and Catalog Numbers 5 3.2 Field Zero Adjustment 19
1.3 Wetted Material Identification 7 3.3 Surge Protector Option, Accessory (339) ... 19
1.4 Filling Medium Identification 7
1.5 Specifications 7 4 FUNCTIONAL DESCRIPTION
4.1 General 20
2 INSTALLATION 4.2 Zero Elevation and Suppression
2.1 Mounting 11 Adjustments 21
— Seal Element Connections Ref A 4.3 Surge Protector Option, Accessory (339) .. .22
2.2 Electrical Connections 11
2.2.1 General 11 MAINTENANCE
2.2.2 Shunting Diode 11 - Ref B
2.3 Process Installation 17
2.3.1 General 17 DIAGRAMS
2.3.2 Pressure Service 17 — Connection and Schematic
2.3.3 Vacuum Service 17 Diagrams Back of Manual
2.3.4 Determining Span and Range Values 17

Ref A — Refer to Seal Element Section, IB-12B927


Ref B — Refer to Maintenance Section, IB-12B958

ILLUSTRATIONS

Fig- Page Fig. Page


1 Transmitter Housings 4 7 Assembling Optional Mounting Bracket
2 Mounting Dimensions for 3444T and 3445T Kit, Accessory (146) ...16
Transmitters with Bolted Cover 17 8 Pressure Service Installation .. .17
3 Mounting Dimensions for 3444T and 3445T 9 Vacuum Sen/ice Installation . ..17
Transmitters v»/ith Threaded Cover 13 10 Field Zero Adjustment 19
4 Mounting Dimensions for 3446T and 3447T 11 Simplified Diagram of Transmitter ...20
Transmitters with Bolted Cover 14 12 Functional Schematic of Transmitter
5 Mounting Dimensions for 3446T and 3447T Electronics .. .21
Transmitters with Threaded Cover IB 13 Functional Schematic of Optional Surge
6 Mounting Dimensions for Electrical Protector, Accessory (339) . .22
Connection Suffix 03 through 08 .IR

TABLES

Table Page Table Page


1 Electrical Codes for Hazardous Locations 5 Range Limits for 3444T Trans-
(USAandCSA) ... .6 8
2 Electrical Codes for Hazardous Locations 6 Output Load Limits 10
(Europe) 7 Ambient Temperature Limits at Working
3 Range Limits with Zero Jumper Pressure Above Atmospheric in
in Norm Position 8 Ambient Temperature Limits at Minimum
4 Range Limits with Zero Jumper Working Pressure 10
in El/Supr Position ... .8 9 Specific Gravity of Filling Medium 18
IB-12B320

INTRODUCTION

'm-i

INTRODUCTION

If'' S) ^fr^'s^' •

Terminal
Box

THREADED COVER BOLTED COVER

Figure 1. Transmitter Housings

1.1 DESCRIPTION The transmitters are designed to operate as part of a


The Taylor 3444T, 3445T, 3446T, and 3447T Gage two-wire system. They receive power ( + 24V dc)
Pressure Transmitters with remote seal elements are from the same pair of wires over which the output
L instruments which measure gage pressure and signal Is transmitted.
transmit a proportional 4 to 20 mA output signal. The
remote seal element limits process contact to the seal The span of each transmitter is continuously ad-
element surface. justable. The span and zero adjustments are accesa-
ble from the outside of the instrument. All ad-
Several seal element forms are available. They pro- justments to span and zero respond electronically.
vide connection to 1/2-inch threaded pipe, 1-1/2
inch A N S I flanges, and various special fittings. The transmitter housing is low copper content, die-
cast aluminum. The cover can be either bolted or
The transmitters are available in high range forms; threaded, Figure 1. The bolted cover is for use in
and are capable of measuring gage pressure spans General Purpose or Division 2 electrical code areas
from 200 to 20,000 psig {1400 to 140 000 kPa). and for intrinsically safe applications in Division 1
areas. The threaded cover is for use in Division 1
A resistance strain gage bridge circuit converts the electrical code areas. The housing provides radio fre-
gage pressure measurement to an electrical signal. quency interference (RFI) protection; and is water-
The strain gage is hermetically sealed to protect the proof.
bridge circuit from moisture, corrosive en-
vironments, and mechanical damage. The electrical An optional surge protector, Accessory (339). pro-
signal is amplified and converted to a 4 to 20 mA dc tects the transmitter electronics against high-voltsge
signal for transmission to another instrument. surges which are often induced by lightning. On
IB-12B320

INTRODUCTION

transmitters with a bolted cover, the surge protector Under a two-year warranty, the circuit board/sealed
accessory is inside the housing. On transmitters with strain gage assembly or the measuring element is
a threaded cover, the accessory is located in an ex- replaceable through a Repair-By-Exchange Plan.
terna! terminal box. Figure 6.

1.2 S E R I A L A N D C A T A L O G N U M B E R S
/ The serial number stamped on the data plate consists of the catalog number and a sequential Identification
number. The catalog number describes the construction of the transmitter.

An X before the serial number indicates that the instrument has been built to meet a customer's special re-
quirements.

Serial Number 3444T F 3 2 3 (339) - 555 B

Basic Catalog Number


Measuring Element Actuation
Electrical Code
Seal Element Diaphragm Material
Catalog
Seal Element Trim Material
Number
Seal Element Construction
Electrical Connection Suffix
Capillary Length
.Accessories (omitted If not required)
Sequential Identification Number
Model (Design Level)

BASIC CATALOG NUMBER 41 ~ U.S. Division 1 — See Table 1


3444T — High Range Transmitter USA
Span ad] from 250 to 19(X) psP 42 — European Flameproof
(1750 to 13 0 0 0 k P a K CENELEC Approval
3445T — Extra High Range Transmitter 44 — Canadian Division 1 — See Table 1
Span ad] from 700 to 5500 psl^ CSA Approval
(4800 to 38 000 kPa) 81 — U.S. Intrinsic Safety — See Table 1
3446T — Ultra High Range Transmitter USA
Span adj from 2500 to 18,000 psi 82 — European Intrinsic Safety — See Table 2
(17 500 to 125 000 kPa) CENELEC Approval
3447T — Transmitter for Extruder Applications 83 — Yugoslavian Safety
Span adj from 2500 to 8,000 psi Commission Approval
(17 500 to 55 000 kPa) 84 — Canadian Intrinsic Safety — See Table 1
C S A Approval
M E A S U R I N G ELEMENT ACTUATION 88 — Australian Intrinsic Safety
F — Gage Pressure S A A Approval
99 — Electrical Code described by
ELECTRICAL CODE Accessory (147) — See Table 2
10 — General Purpose -
Taylor Standard SEAL ELEMENT DIAPHRAGM MATERIAL
21 - U.S. Division 2 - See Table 1 2 - Type 316L S S T
USA 3 - Hastel!oy-C'
24 — Canadian Division 2 — See Table 1 4 — Monel
C S A Approval ' - 5 - Nickel
25 - U.K. Type N Protection — See Table 2 7 — Tantalum
B A S E E F A Approval •
' T . M . of Union Carbide Corp.
'250 to 1500 psi {1750 to 10 000 kPa) on 3A44TF _'_ _:_3
»700 to 5000 psi (4800 to 35 000 kPa) on 3445TF 8
IB-12B320

INTRODUCTION

Table 1. Electrical Codes for Hazardous Locations (USA and CSA)

Hazardous Location
Electrical Class I Class II Class Hi
Code No.
Oiv 1 Div 2 Oiv 1 Div 2
Groups Groups Groups Groups Div 1 Div 2
A B.C.D A B.C.D E.F.G E.F.G

21
24
41
44
81
84

Table 2. Electrical Codes for Hazardous Locations (Europe!

Catalog Number Digits Oetcription


Electrical Electrical Connection Acc Type of Safety Harardous Area Safety Fot Approvals
Code No. Suffii No. Protection Coda Zone 0 2one 1 Zone 2 Std. Installstien in Authority
BS46S3:
25 Ol.02.03.04.0S,08 t• N E>N II T5 X Pan 3: UK
>972
01,02.04.05 » id EE>ia 11 CT5 X X X EN50020 UK'amlnttwn
B2 08 I 13 EE"a II BT5 K X X IB5S50):Part 7; CENELCC 8ASEEFA
08 t lb EE>i& II C7S X X 19771 cTMjmbe' <sa:es
BS4683:
01.02.04.05,08 tM7) N E>N II T$ X Pan 3r
1372
99 UK
01.02.04.05 (1471 ia EE.ia II CTS X X X BSS601:
08 (1471 •a EE-ia II 8T5 X X X Pan 7:
lb
EE»t> II CTS X X 1977
tCan ^ any acccssory number eieept 11471
'CENELEC m«mt>er states: Ausina, Belgium, Oenm^rk. finlantf, Froftce. W. Gmmanv. Greece. Irclanrt, Italy. LturmJxxi'O.
Neihetlanas, Norway. Ponugal. Spam. Swerten, Swit/Rrlar»<l anrt Uniled Kinpflom
Nole: BASEEFA or EEC cenificd barrier* must be used v/ith the ir>trins>caUv Mie Iransmittcrs fia artri ibl as (xn BASEEFA
cetiificd System Diagram ISOa00«08 Sheet 1. page 2.

fSEAL ELEMENT TRIM MATERIAL 5 — Diaphragm Element


2 - Type 316 S S P Extruder type with union connection 12-1/2'
3 — Hastelloy-C lagging extension, 1 / 2 " — M thread
4 — Monel 6 — Diaphragm Element
5 - Nickel Wafer type for 1-1/2" raised face flange
7 — Tantalum 7 — Diaphragm Element
Button type
SEAL ELEMENT CONSTRUCTION 8 — Diaphragm Element
1 — Diaphragm Element Button type with flange
Pipe connection type, 1/2" Int NPT 9 — Diaphragm Element
2 — Diaphragm Element Button type with union connection
Welding neck type, 1/2" schedule 40 pipe 1-1/2"-16 thread
3 — Diaphragm Element
Union connection type, 2-1/8" —16 thread CAPILLARY LENGTH
4 — Diaphragm Element Digits Indicate length in feet
Extruder type with union connection 01 — one foot (0.31 cm) through
6" lagging e^ctension, 1 / 2 " - 2 0 thread 20 — twenty feet (6.10 m)
99 - Special
'344_TF 26 is type 316L SST
IB-12B320

INTRODUCTION

ELECTRICAL CONNECTION SUFFIX When the instrument has more than one type wetted
01 — Terminal block connection material, the data plate identifies the materials in the
02 — Terminal block with shunting diode and following sequence:
2.5 ohm calibration resistor
03 — Terminal block with shunting diode, 2.5 ohm Process Diaphragm/Trim
calibration resistor, and output test jack
04 — Terminal block with shunting diode, 2.5 ohm 1.4 F I L L I N G M E D I U M I D E N T I F I C A T I O I M
calibration resistor, and output meter with The following abbreviations are stamped on the
0 to 100 linear scale diaphragm capsule to Identify the filling medium:
05 — Terminal block with shunting diode, 2.5 ohm
calibration resistor, and output meter with SI — Silicone
0 to 10 square-root scale F L — Fluorolube
07 — External terminal box with shunting diode
08 — Terminal block with shunting diode, 2.5 ohm 1.5 S P E C I F I C A T I O N S
calibration resistor, and current meter jack SPAN*
across shunting diode 3444T: Adj from 250 to 1900 psI
09 — Defined by a specific accessory number (1750 to 13 000kPa)'
3445T: Adj from 700 to 5500 psi
ACCESSORIES (4800 to 38 000 kPa)'
( 94) - Blind flange; 1-1/2 Inch, Class 2500 A N S I 3446T: Adj from 2500 to 18000 psi
with bolts and nuts for use with Seal (17 500 to 125 000 kPa)
Element Construction Number 6 3447T: Adj from 2500 to 8000 psi
( 96) — Adapter Flange for welded construction (17 500 to 55 000 kPa)
(146) — Mounting Bracket
(147) — Data Plate Indicating that transmitter CALIBRATION A C C U R A C Y (Zero Based)
satisfies requirements for both Electrical 3444T: ± 0 . 5 % of span;
Codes 25 (U.K. Type N Protection) and 0.35% ultimate capability
82 (European Intrinsic Safety) —
See Table 2 3445T: ± 0 . 5 % of span for spans under
(282) — Extra Suppression Spring 3000 psi (20 000 kPa);
(339) — Surge Protector ± 1 . 0 % of span for spans above
3000 psi (20 000 kPa);
EXAMPLE: 0.35% ultimate capability
Serial Number 3444TF10323-0120{339)-555B iden-
tifies a high range transmitter with 250 to 1900 psi 3446T: ± 0 . 5 % of span for spans under
(1750 to 13 000 kPa) adjustable span (3444T). It is ac- 15,000 psi (103 000 kPa);
tuated by gage pressure (F) and Is designed to ± 1.0% of span for spans above
operate in areas designated as General Purpose by 15,000 psi (103 000 kPa);
the electrical code (10). The seal element diaphragm ultimate capability as listed above
is Hastelloy-C (3), the trim is type 316L S S T (2), and
the seal element Is the union connection type (3). 3447T: ± 0 . 5 % of span for spans under
The transmitter has a terminal block connection (01), 5000 psi (34 500 kPa);
a twenty-foot capillary (20), and a surge protector ± 1.0% of span for spans above
(339). The sequential identification number is 555 5000 psi (34 500 kPa);
and the design level is Model B. ultimate capability as listed above

1.3 W E T T E D M A T E R I A L I D E I M T I F I C A T I O N RANGE LIMITS


The following abbreviations are'used on the instru- Refer to Tables 3, 4, and 5
ment data plate to identify materials wetted by the
process. OUTPUT SIGNAL
4 to 20 mA dc
HAST - Hastelloy-C
316 - T y p e 316 S S T •The factory-calibrated span is identified on the side of the strain
MON - Monel gage bracket.

TANT — Tantalum '250 to 1500 psi (1750 to 10 000 kPa) on 3444TF 3


Nl - Nickel »700 to 5000 psi (4800 to 35 000 kPa) on 3445TF 8
IB-12B320

INTRODUCTION

Table 3. Range Limits with Zero Jumper in N O R M Position

Range Limits

Psig Kilopascals
Catalog No. Calibration
Lower Upper Lower Upper
14 m A Output) (20 m A O u t p u t ) (4 m A Output) J20 m A O u t p u t )

3444T Zero Based 0 250 to 1900 0 1750 to 13 000


Suppressed Zero 0 to 475 250 to 1900 0 to 3250
High Range 1750 to 13 000
Elevated Zero - 14.7 to 0 235 to 1900 - 100 to 0 1650 to 13 000
3445T Zero Based 0 700 to 5500 0 4800 to 38 000
Extra Suppressed Zero 0 to 1375 700 to 5500 Oto 9500 4800 to 38 000
High Range Elevated Zero - 14.7 to 0 685 to 5500 - 1 0 0 to 0 4700 to 38 000
3446T Zero Based 0 2500 to 18000 0 17 500 to 125 000
Ultra Suppressed Zero 0 to 4500 2500 to 18000 0 to 31 250 17 500 to 125 000
High Range Elevated Zero - 14.7 to 0 24S5 to 18000 - 1 0 0 to 0 17 400 to 125 000
Zero Based 0 2500 to 8000
3447T 0 17 500 to 55 000
Suppressed Zero 0 to 2000 2500 to 8000
Special 0 to 13 750 17 500 to 55 000
Elevated Zero - 14.7 toO 2485 to 8000 - 100 to 0 17 400 to 55 000

E 1211 LEOA
AH transmitters can be continuously adjusted for any calibration listed.

Table 4. Range Limits with Zero Jumper In EL/SUPR Position

Range Limits

psig kPa
Catalog No. Calibration
Lower Upper Lower Upper
(4 m A Output) (20 m A O u t p u t ) (4 m A Output) (20 m A O u t p u t )
Zero Based 0 250 to 1900 0 1750 to 13 000
3444T
Suppressed Zero 0 to 1650 250 to 1900 Oto 11 250 1750 to 13 000
High Range
Elevated Zero - 14.7 to 0 235 to 1900 - 1 0 0 to 0 1650 to 13 000
3445T Zero Based 0 700 to 5500 0 4800 to 38 000
Extra Suppressed Zero Oto 4800 700 to 5500 Oto 33 200 4800 to 38 000
High Range Elevated Zero - 1 4 . 7 to 0 685 to 5500 - 1 0 0 to 0 4700 to 38 000
3446T Zero Based 0 2500 to 000 0 17 500 to 125 000
Ultra Suppressed Zero Oto 15 500 2500 to 18 000 0 to 107 500 17 500 to 125 000
High Range Elevated Zero - 1 4 . 7 toO 2485 to 18 000 - 1 0 0 to 0 17 400 to 125 000
Zero Based 0 2500 to 8000 0 17 500 to 55 000
3447T
Suppressed Zero 0 to 5500 2500 to 8000 Oto 38 000 17 500 to 55 000
Special
Elevated Zero - 1 4 . 7 toO 2485 to 8000 - 1 0 0 to 0 17 400 to 55 000

AH transmitters can be continuously adjusted for any calibration listed.

. Table 5. Range Limits for 3444T Transmitter with Accessory (282)

Range Limits

psig kPa
Calibration
Lower Upper Lower Upper
(4 m A O u t p u t ) (20 m A Output) (4 m A O u t p u t ) (20 mA Output)
Suppressed Zero 950 to 2600 1200 to 2900 6500 to 17 750 8650 to 20 000
IB-12B320

INTRODUCTION

OUTPUT LOAD LIMITS Maximum


Refer to Table 6 3444TF __1,6,7,8,9: 4,000 psig
(28 000 kPa)
POWER SUPPLY 3444TF __3: 1,500 psIg
24V dc nominal (10 000 kPa)
13V dc min; 36V dc max. across transmitter terminals 3445TF __7,9: 6,000 psig
(40 000 kPa)
POWER CONSUMPTION 3445TF 8: 5.000 psig
0.5W nominal (35 000 kPa)
3446T: 20,000 psig
1.5W max. in overrange condition
(140 000 kPa)
3447T: 8,000 psig
WEIGHTt
(55 000 kPa)
3444T: 6.4 lbs (2.9 kg)
3445T; 6.4 lbs (2.9 kg) OVERRANGE PRESSURE LIMITS
3446T: 7.8 lbs (3.5 kg) Same as working pressure limits
3447T: 7.8 lbs (3.5 kg)
TUBE S Y S T E M FILLING MEDIUM AMBIENT TEMPERATURE LIMITS
3444T: Silicone, DC-200 Standard Refer to Tables 7 and 8
Silicone, DC-702
Ethyl Benzene STORAGE TEMPERATURE LIMITS
Water Glycerine, WG-70 'Optional
- 6 5 ° F to 200°F (-53.9°C to 93.3°C)
Water Glycerine, WG-40 For Water Glycerine filled seal element and capillary,
see Table 7
3445T: Silicone. DC-200 Standard
Silicone, DC-702 S E A L ELEMENT LIMITS'
Ethyl Benzene (without process vacuum)
Water Glycerine. WG-70 "Optional Element above case —
Water Glycerine. WG-40 Not to exceed zero suppression limit
Mercury
Element below case at altitudes
3446T: Mercury below 1000 feet (305 meters) —
15 feet (4.6 meters) max.
3447T: Mercury
Element below case at altitudes
WORKING PRESSURE LIMITS above 1000 feet (305 meters) —
Minimum Reduce limit of 15 feet (4.6 meters) by
Water Glycerine, WG-70: 2.5 psia (17.22 kPa) 0.6 ft per 1000 ft (0.06 m per 100 m)
Water Glycerine, WG-40: 2.5 psia (17.22 kPa)
All other fills:' 0 psia 'Raising or lowering the seal element 1.2 ft (0.37 mm) results in a
zero elevation or suppression of 1 psi (6.9 kPa)
t Add 3 jbs {1.4 kg) for units with threaded cover.
B-12B320

INTRODUCTION

Table 6. Output Load Limits

M a x Transmitter Load (Ohms)*


Supply Elect. Conn Suffix Elect. Conn Suffix
( D C VottsJ 01 02. 03. 04. 05. 07. 08

13 50 0
15 150 100
20 400 350
24 600 550
30 900 850
35 1100 1100

• M a * load is reduced 70Q if transmitter has a surge protector.


Acc (333).

Table 7. Ambient Temperature Limits at Working Pressure above Atmospheric

T e m p e r a t u r e Limits — "F Temperaiore L i m i t s — 'KI


At Workint) Pressures Above Atmospheric At Working Pressures A b o v e Atmospheric
Catalog
T u b e S y s t e m Filling M e d i u m
Number
C a s e & Capillary Seal E l e m e n t C a s e £r Ciiplllary S e a l Element
Min Max Min Max Min Max Min Mat
Silicone. DC-200 -40 185 -40 *350 -40 -40 -177
Silicone. DC-702 -40 -^185 »40 -600* • 4,4,-, ^316'
3444T
3445T Ethyl Benzene -40 -100 '200 -40 •85 -73 -93.3
Water Glycerine. W G - 7 0 ^-20 -•185 •20 »220 -6.7 • 85 -6.7 -104
Water Glycerine. W G - 4 0 -35 - 185 -35 -.-200 -37 *85 -37 -93.3
3445T
3446T Mercury -35 « 185 -35 • 650" -37 >SS -37
3447T

• • W F ( 2 0 4 X ) for 3444TP 3
•750°F <399°C» for 3447T

Table 8. Ambient Temperature Limits at Minimum Working Pressure

T e m p e r a t u r e L i m i t s — "F Temperature L i m i t s — " C


A i Minimum Working Pressures At Minimum Working Pressures
Catalog
T u b e S y s t e m Filling M e d i u m
Number
C a s e & Capillary Seal E t e m c n i C a s e (s Capillary S e a l Element
Min Max Min Max Min Max Min Max
Silicone. DC-200 -40 • ISO - 40 »250 -40 • 85 — 40 t J21
Silicone. DC-702 »40 180 * 40 • 350 - 4,4 • 85 + 177
3444T Ethyl Benzene -40 •flOO - 100 + 100 -40 • 38 -73 • 38
3445T
Waier Glycerine. W G - 7 0 • 20 -^130 • 20 130 -6,7 • 54 -6.7 + 54
Water Glycerine. W G - 4 0 -35 -»-130 -35 130 -37 -t54 • -37 + 54
3445T
344CT Mercury -35 -ISO -35 • 650* -37 + 85 -37 •+343*
3447T

•750''F I399»C» tot 3447T

10
iB-12B320

INSTALLATION

INSTALLATION

2.1 MOUNTING bracket accepts 1-1/4 through 2-inch pipe and can
Refer to 2.3 Process Installation for information on be positioned for use on horizontal or vertical pipes.
locating the transmitter for specific applications. Figures 2 through 5.

Carefully unpack the transmitter and uncoil the tube 2.2 ELECTRICAL CONNECTIONS
system.
WARNING
CAUTION Do N O T make electrical connections
Do not remove the protective cover from unless the electrical code designation
the sea/ element until ready to connect it stamped on the transmitter data plate
to the process. agrees with the classification of the area
in which the transmitter is to be installed.
If the tube system filling medium is mer- Failure to comply with this warning can
cury, avoid mechanical shock and atways result in explosion and fire, leading to in
keep the seal element close to the eleva- jury and property damage.
tion of the transmitter. Lovi/ering the ele-
ment more than 30 inches hehw the case 2.2.1 General
will damage the seal diaphragm. The transmitter is designed to be part of a two-wire
system. The 4 to 20 mA dc output signal and the 24V
Select a mounting location where there Is minimum dc power to the transmitter are carried by the same
vibration. The ambient temperature must not exceed pair of wires. The transmitter does not contain a
the limits listed in Table 7 or 8. power supply. The necessary power supply can be
separate from the instrument load or built in as
Mount the transmitter in a vertical position with the shown in the connection diagram located in the back
measuring element below the case. Figures 2 of this manual.
through 6. Operation is not affected by mounting in
other positions, but some rezeroing may be required If the power supply voltage is greater than 24V dc, do
(refer to 3.2 Field Zero Adjustment). not exceed 36V dc across the transmitter terminals.
The output load limits of the transmitter are shown in
NOTE Table 6. Conduit may be connected to the threaded
If the transmitter cannot be mounted in connection In the transmitter base. Refer to Figures 2
the recommended position, any required through 6.
zero adjustment should be made prior to
Installation. Place the transmitter in the 2.2.2 Shunting Diode
installation position, and check output V^hen the transmitter catalog number contains Elec-
with input adjusted to the lower range trical Connection Suffix digits 02, 03, 04. 05, 07, or
value. Refer to Calibration. 08, a shunting diode(s) is connected between ter-
minals R and M In the terminal box. Refer to the
The transmitter can be mounted using the two schematic diagram in the back of this manual.
5/16-18 mounting holes in the measuring element.
Figures 2 through 5. An optional mounting bracket The diode(s) is connected to shunt an external out-
kit. Accessory (146), provides a bracket, U-bolts, and put meter and provides a signal path if the external
fasteners. Figure 7. The bracket is suitable for either meter is removed from the circuit. Do not remove the
pipe or surface mounting. For pipe mounting, the shunting diode when connecting an external meter.

11
IB-12B320

INSTALLATION

Cl««raac« to
Remov* Cov«r

Oecincat Conn
1'2 Int NPT
Csrih Terminal
lOn Oppoiit* Side)
Cabte Gland Conn

Elsciricsl Conn
1/2 Ini NPT 2 Mt9 Holes
5/1& 18 NO 2 « 1/2 Deep

M19 Bracket
Location

32
A C C E S S O R Y (146)
Pipe Mounting Bracket
fi. 10 9/32

3 1W16
w
2" Pipe
(Can Atso 8 e Mountac)
5-1/4
On 1 1/2 and M / 4 Pipa>
r--M/16
7-15/16

See Not« 2 Brachet Right

HORIZONTAL PIPE M T G

INCHES mm INCHES mm
'32
5/J6 7.94 4-1/16 103.19
F o r reference o n l y ;
7/8 22.23 4-1/4 107.95
1-1/16 26.99 4-9/16 115.69 n o t for c o n s t r u c t i o n .
1-1/4 31.75 5-1/4 133.35
1-3/4 44.45 5-3/8 136.S3
2 50.80 6-3/a 161-93 A l l d i m e n s i o n s in inches.
2-1/8 53.98 6-29/32 175.42
2-5/8 66.68 7-J5/16 201.61
3 76-20 9-1/32 229.39
3-11/16 93.66 10-9/32 261.14

Notes: VERTICAL PIPE M T G -


1. For electrical c o n n e c t i o n suffix 03 t h r o u g h 0 8 . see Figure 6.

2. Bracket c a n be l o c a t e d in a n y o f t h e four d i r e c t i o n s
without dimensional change.

Figure 2. Mounting Dimensions for 3444T and 3445T Transmitters with Bolted Cover

12
1B-12B320

INSTALLATION

A C C E S S O R Y (146) Mounting Bracket

li
I2f.
S 10
m
•'h r—ti i
2"
Brocket Left Brocket Right
( C o n oiso be mounted on\

($«e N o t t 2) C-1210-14B(2)
VERTICAL PIPE MTG
1-1/2 ond t - l / 4 p'pe )

INCHES mm
horizontal PlPt MTC 7/8 22.23
1-1/16 26.99
Notes: 1-1/4 31.75
1. For electrical c o n n e c t i o n suffix 07, see Figure 6 . 1-3/4 44.45
3 76.20
2. Bracket c a n b e l o c a t e d in a n y of t h e four directions 3-9/16 90.49
without dimensional change. 3-11/16 93.66
5-1/4 133.35
e 1S2.40
6-1/8 155-58
6-3/8 161.93
A i l d i m e n s i o n s in inches. For reference o n l y ;
7-1/2 190.50
n o t for c o n s t r u c t i o n . e-5/16 211.14
8-25/32 223.04
10-29/32 277.02
12-5/32 308.77
28 711.20

Figure 3. Mounting Dimensions for 3444T and 3445T Transmitters with Threaded Cover

13
IB-12B320 ' - • •

INSTALLATION

Clearance lo
Rernove Cover

Electrical Conn
1/2 Int NPT
Earth Terminal
(On Opposite Side>
Cable Gland Conn

Electrical Cortti
1/2 Int NPT

2 M t 9 Holes
5't6 18 N C 2 > 1'2 Deep

M 1 9 Biachet
Location t/2

9 29/32
ACCESSORY (1461
Pipe M o u n t i n g Bracket
& r n
I t 5/32 S , P
V -
311/16-
2" Pipe
. (Can Also Be M o u n t e d
/ " O n M / 2 and 1 1/« Pipel H 5-1/4 H ^
M/16
U 7-15/16
2D 7
See Note 2 Brachet Right

HOHtZONTAL PIP€ M T G

i a
INCHES mm INCHES mm
11-5/32
1/2 12.70 4-1/16 103.19
7/8 22.23 4-9/16 115.89 For refere/ice o n l y ;
1-1/16 26.99 51/4 133.35 n o t ior construction.
1-3/4 6-3/8 161.93
2-5/8 66.6a 7-15/16 201.61
1/16 5-1/4
3 76.20 9-29/32 251.62 Alt d i m e n s i o n s in inches.
3-11/16 93.66 11-5/32 283.37 7-15/16

Notes: Bracket (.eft


}. For electrical c o n n e c t i o n suffix 0 3 t h r o u g h 08. isee Figure 6.

VERTICAL PIPE M T G
2. Bracket c a n b e l o c a t e d in a n y of t h e four directions
without dimensional c h a n g e .

Figure 4. Mounting Dimensions for 3446T and 3447T Transminers with Bolted Cover

14
" IB-12B320

INSTALLATION

g Clearonce to
Remove Cover

C(ecir<oi Con
1/2 I3t NPT
(See Mo'e I )
2 Mtq Hoies
V I 6 - I S N C - 2 » l / 2 Deep

Capiilory to
Seal Clement

ACCESSORY ( 1 4 6 ) Pipe M o u n t i n g Bracket

2 P.pe
n olso be mouniled o n \
i/2 on<l 1-1/4 p ipe / Brocket L e f i Brocket Right

<See Note Z) ) H O R I Z O N T A L P I P E MTG VERTICAL PIPE MTC C1210-1 S0(?)

INCHES mm
1/? 1J.70
Notes: 7/8 22.23
1. For electrical c o n n e c t i o n suffix 0 7 . see Figure 6. 1-1/lti 26 99
1-3/4 44.4 5
2. Bracket c a n be l o c a t e d in a n y of t h e four directions 3 «7.20
v/ithout d i m e n s i o n a l c h a n g e . 3-9/16 90.49
3-11/16 93-66
5-1/4 133.35
F o r reference o n l y ;
e 152-40
n o t lor c o n s t r u c t i o n . C-3/8 161.93
71/? 190.50
e-vi6 211.14
A l l d i m e n s i o n s i n inches. 9-11/16 24 6 - 0 6
11-13/16 300.04
13-1/16 331.79
711.20

Rgure 5. Mounting Dinrienslons ifoc 3446T and 3447T Transmitters with Threaded Cover

15
' —•-!'i.11 iia itft•r- rfan Ta-i-a-Wi ntrrnfrnfft ;ir--i •':
IB-12B320

INSTALLATION

INCHES n«n
j/a Z2.Z)
2-)/4 S7.IS
2S/t escs
) 7*20
ELECTRICAL CONNECTION S«* Mot* 1
SUFFIX 03. oa E L E C T R I C A L C O N N E C T I O N S U F F I X <M. 06 sz.ca
I0S.3S
»13/lt M7.M
e t5Z.«
'UI 190S0

Notes:
1. O n instruments with electrical c o d c
25, 82. or 88, output meter is
m o u n t e d in «lectric3l connection o n
other e n d of terminal b o x .

2. Surge protector circuit is housed in


• I Cono termin^l boi when tran&miticr is
U-3-JV4li<lNPT eguipO«d with Accesforv (3391.

ELECTRICAL C O N N E C T I O N S U F F I X 07 c-uii-sa

Figure 6. Mounting Dimensions for Electrical Connection Suffix 03 through 08

Mounting
Washer

Figure 7. .^Assembling Optiorval Mounting. Bracket. Kit, Accessory (146)

16
•r ^ - A. .itiieJ
IB-12B320

INSTALLATION

2.3 PROCESS INSTALLATION


Q Remote Soal
Elamont
2.3.1 Goneral H
Datum
Installations for gage pressure measurement are Line at
shown In Figures 8 and 9. The seal element can be
connected to a process pipe as shown, or to any
process vessel.
Process
Pipe
The transmitter datum line is at the center of the tube m
system connection in the measuring element body.
When the datum line is above or below the elevation
of the seal element, the head pressure developed by Figure 9. • Vacuum Service Installation
the liquid fill in the tube system must be considered
when determining range values for calibration. Refer
to 2.3.4 Determining Span and Range Values. tions are shown in Figure 9. Connect the element to
the side or top of the pipe to avoid collection of sedi-
ment on the seal element diaphragm.

Jal 2.3.4 Determining Span and Range Values


All transmitters are factory calibrated per customer
a specifications. If the application is changed, deter-
mine the required span and range values using the
following Information.
R e m o t e Seal

a i
Element
Span is a function of the change in process pres-
sure. The range values are the end points of the
Datum
Line •E>- span. The lower range value is the net pressure ap-
plied to the measuring element when the process
pressure is at its minimum value. The upper range
value is the net pressure applied when the process
J1 Process
pressure is at its maximum value.
Pipe
3
o > When the transmitter datum line. Figure 8, is at the
same elevation as the seal element, the lower range
Figure 8. Pressure Service Installation value and upper range value are equal to the
minimum and maximum process pressures, respec-
tively.
2.3.2 Pressure Service
Recommended installations for pressure service are When the transmitter datum line is above or below
shown in Figure 8. If the transmitter is located above the seal element connection, a head pressure is
the elevation of the seal element, dimension E Is developed by the liquid fill In the tube system. This
limited depending upon the tube system filling pressure must be taken into account when determin-
medium. If the filling medium is mercury, dimension ing range values.
E must not exceed 30 inches (762 mm). For all other
filling mediums, dimension E must not exceed 30 feet Example:
(9.14 m). Connect the element to the side or top of U.S. Units: In the pressure service in-
the pipe to avoid collection of sediment on the proc- stallation shown In Figure 8, assume that
ess diaphragm. the process pressure varies from 150 to
350 psig, and the tube system filling
2.3.3 Vacuum Service medium is Silicone DC-200. The required
When the process pressure range Includes pressures transmitter span is 200 psi. The specific
below atmospheric, the transmitter datum line must gravity of the liquid fill is 0.92, Table 9.
be at or below the elevation of the seal element to in-
sure that the pressure in the measuring element body If the transmitter is mounted 20 feet
Is always greater than 0 psia. Recommended Installa- below the seal element (S = 20 feet), a

17
IB-12B320

INSTALLATION

Table 9. Specific Gravity of Filling Medium

Tube System Filling IVTedium Specific Gravity

Silicone, DC-200 0.92


Silicone, DC-702 1.07
Ethyt Benzene 0.87
Water Glycerine, WG-70 1.07
Water Glycerine, WG-40 1.16
Mercury 13.55

head of 20 feet of liquid is added to the If the transmitter is mounted 600 cm


minimum and maximum process pres- below the seal element (S = 600 cm), a
sures. The 20-ft head is equivalent to 8.0 head of 600 cm of liquid Is added to the
psig (20 ft X 0.92 x 0.433 psi/ft). Thus, the minimum and maximum process pres-
lower range value is 158.0 psig and the sures. The 600-cm head Is equivalent to
upper range value is 358.0 psig. 54 kPa (600 cm x 0.92 x 0.098 kPa/cm).
Thus, the lower range value is 1054 kPa
Example: and the upper range value is 2454 kPa.
SI Units: In the pressure service Installa-
tion shown In Figure 8, assume that the If the transmitter referred to In the examples is
process pressure varies from 1000 kPa to mounted above the seal element (E = 20 ft or 600
2400 kPa, and the tube system filling cm), the 8.0 psig (54 kPa) head pressure is sub-
medium is Silicone DC-200. The required tracted from the niinimum and maximum process
transmitter span is 1400 kPa. The specific pressures to obtain the range values.
gravity of the liquid fill is 0.92, Table 9.

18

.•fe-'
IB-12B320

OPERATION

IS

OPERATION

\ 1

1
m. m . u s < ^
E Zero
I i II«> 'Adjustment

I nito ^
Zaro S - • - \ ' 1
jjustmont h^-'.^
THREADED COVER BOLTED COVER

Figure 10. Field Zero Adjustment

3.1 PUTTING INTO OPERATION large quantities of electrical energy (2500V dc max-
1. Make sure transmitter has been properly In- imum) which have been induced In a transmission
stalled. Refer to 2 Installation. line. These large quantities of energy can be induced
In the signal transmission lines by lightning discharge
2. Turn on power to transmitter. or by nearby electrical equipment. The dissipation of
this energy prevents damage to transmitter circuitry
3.2 FIELD ZERO ADJUSTMENT connected to the transmission line.
The zero adjustment is accessible on the outside of
the housing, Figure 10. The transmitter can be The surge protector will not protect the Instrument in
zeroed while rt is in operation, providing the process case of a direct lightning strike. The surge protector
pressure can be precisely measured to determine the is designed to operate and recover automatically; It
required transmitter output value. If it is not practical does not require periodic testing or adjustment.
to measure the process pressure, the unit should be
precisely zeroed prior to installation. This can be On transmitters with a bolted cover, the surge pro-
done by placing the transmitter housing and seal ele- tector circuit is located In the terminal box in the base
ment in their installation position, and zeroing the of the housing. Figure 1. On transmitters with a
output with the input adjusted to its lower range threaded cover, the surge protector circuit is located
value. Refer to Calibration, IB-12B958. in the external terminal box. Figure 6.

3.3 SURGE PROTECTOR OPTION.


ACCESSORY t339)
Accessory (339) provides a built-in surge protection
circuit. The surge protector is designed to dissipate

19
IB-12B320

FUNCTIONAL DESCRIPTION

FUNCTIOIMAL D E S C R I P T I O N

• Output

Figure 11. Simplified Diagram of Transmitter

4.1 G E N E R A L set from the center of the beam, the force develops
A simplified diagram of the transmitter with the elec- clockwise torque. The force beam, pivoting from the
tronics in block diagram form is shown in Figure 11. offset flexure, tips to the right.
A functional schematic of the transmitter electronics
is shown in Figure 12. This motion of the force beam is transferred to the
strain gage force unit through the connecting wire.
An increase In process pressure increases the pres- The strain gage force unit contains four strain gages
sure of the liquid fill in back of the process dia- connected in a bridge configuration. Movement of
phragm. This pressure increase, acting on the the force beam causes the strain gages to change
primary diaphragm, develops force against the bot- resistance. This change in resistance produces a dif-
tom of the force beam. Since the flexure pivot is off- ferential signal which is proportional to the input dif-
IB-12B320

FUNCTIONAL DESCRIPTION

Figure 12. Functional Schematic of Transmitter Electronics

ferential pressure. This differentia! signal is applied to 4.2 ZERO ELEVATION A N D


the inputs of amplifier A2, which drives the output SUPPRESSION ADJUSTMENTS
current regulator Q2, Q3. The design of the current Zero elevation or suppression adjustments are re-
regulator limits the maximum output current. quired when it is necessary to bias the output to
compensate for the effect of initial process pressure.
One side of the bridge connects to the zero circuitry They can also compensate for head pressure devel-
and the non-inverting input of amplifier A2. The oped when the seal element is above or below the
other side of the bridge connects to the inverting in- elevation of the transmitter case. The zero elevation
put of amplifier A2 (via R I D and the span circuitry and suppression capability is provided by the zero ad-
{via R6). justment, Figure 12.

The span adjustment, R14, adjusts the closed loop When the minimum process pressure is greater than
gain of amplifier A2. It can be set to give a transmit- 0 psig (0 kPa), the transmitter output will be above
ter output current of 20 mA at the required upper the required zero value (4 mA) at minimum pressure.
range limit. By turning the zero screw, the output can be sup-
pressed to the required zero value. If a very large
The zero adjustment, R12, can be set to give a amount of suppression is required, an optional extra
transmitter output current of 4 mA at the required suppression spring. Accessory (282), provides
lower range limrt. Most of this current Is supplied by mechanical suppression which adds to the electrical
the voltage regulator circuit, minimizing the interac- suppression capability.
tion between the span and zero adjustments.
When the minimum process pressure Is less than 0
A zero jumper can be positioned between R17 and psIg (a vacuum), the output will be below the re-
RIO to provide increased zero elevation or suppres- quired 4 mA zero value at minimum pressure. By
sion capability. turning the zero screw, the output can be elevated
to the required zero value.

21
IB-12B320

FUNCTIONAL DESCRIPTION

Induced
Vottage

/
Transmission
/77 Line A-UII-B

Figure 13. Functional Schematic of Optional Surge Protector, Accessory <339)

Elevation and suppression adjustments are made as turn on. When the surge voltage exceeds the firing
part of the transmitter calibration procedure. The in- voltage (approximately 90V dc) of the surge diodes,
itial process pressures and/or head pressures are the diodes conduct^and short the surge voltage to
simulated by air pressure applied to the seal element. ground. The surge diodes conduct either trans-
versely from line-to-line or longitudinally from line-to-
4.3 S U R G E PROTECTOR OPTION, ground. If only one surge diode fired or one fired
A C C E S S O R Y (339) ahead of the other, the voltage surge would continue
The surge protector circuit. Figure 13, protects the toward the protected instrument circuitry. Then, the
transmitter electronics from being damaged by high voltage surge would be slowed further by r-c net-
voltage surges. When a surge voltage is induced in works R1 and C2 or R2 and C3 until Zener diode D1
the transmission line, the leading edge of the surge is conducts. The Zener diode conducts only trans-
slowed down by an r-c network consisting of resis- versely from line-to-line. It will limit the maximum
tors Rt, Figure 13, which represent the resistances of voltage applied to the protected transmitter circuit at
the transmission line and capacitor 01. the Zener voltage. Resistors R1 and R2 limit the cur-
rent flow through the Zener diode.
"he time delay due to the r-c network allows surge
liodes (gas discharge tubes) SD1 and SD2 time to

22
IB-12B320

NOTES

23

,1 1/
IB-12B229
Issue 2
Oct 1981

INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTER
with Remote Seal Elements
3423T and 3424T Model B

SYBRON Taylor
NOTICE

Information In this manual is intended only to assist our customers In the efficient operation of our
equipment. Use of this manual for any other purpose Is specifically prohibited and its contents are
not to be reproduced in full or part without prior approval of Marketing Communications Depart-
ment, Taylor Instrument Company, Division of Sybron Corporation.

Use of D A N G E R , W A R N I N G , C A U T I O N and NOTE

This publication includes D A N G E R . W A R N I N G , C A U T I O N and NOTE information where


appropriate to point out safety related or other Important information.

DANGER — Hazards which will result In severe personal injury or.death. -

WARNING — Hazards which could result in personal Injury.

CAUTION — Hazards which could result In equipment or property damage.

NOTE — Alerts user to pertinent facts and conditions.

Although D A N G E R and W A R N I N G hazards are related to personal injury, and C A U T I O N


hazards are associated with equipment or property damage, it should be understood that opera-
tion of damaged equipment could, under certain operational conditions, result in degraded
process system performance leading to personal injury or death. Therefore, comply fully with all
D A N G E R . W A R N I N G and C A U T I O N notices.

Prepared by:
MARKETING COMMUNICATIONS DEPARTMENT
TAYLOR INSTRUMENT C O M P A N Y o DIVISION OF S Y B R O N CORPORATION
. 95 Ames Street. Rochester. New York 14601 U.S.A. 716-235-5p00

Printed in U . S . A .
TP-9913

.M", 'I'
IB-12B229(AS}
DIFFERENTIAL PRESSURE TRANSMITTER Issue 1
with Remote Seal Elements Nov 1982
3423T and 3424T Model B

A D D E N D A SHEET
Use onfy with Instruction IB-12B229, issue 1.

Page 5: Add the following information.

MEASURING ELEMENT ACTUATION 88 — Australian Intrinsic Safety


D — Dffferential Pressure S A A Approval
^ — Electrical Code described by
ELECTRICAL CODE Accessory (147) — See Table 2
10 — General Purpose JA/ETTED MATERIAL
Taylor Standard — Hastelloy-C .diaphragm and
21 U.S. Oivtsion 2 ~ See Table 1 type 316 S S T Tr-ir,^
USA 26 - Type 316 SST>
24 — Canadian Division 2 — See Table 1 36 - Hastelloy-C
CSA Approval 46 — Monel
25 — U.K. Type N Protection — See Table 2 56 - Nickel
BASEEFA Approval 76 — Tantalum
99 — Special

- 04>- TYPE 3IC. S S T PER NACEL

Page 10: Substitute the following for the corresponding information on page 10.

2.3 ELECTRICAL CONNECTIONS limit depends on the supply voltage as shown in


Table 5.
WARNING
D o N O T make electrica/ connections 2.3.2 All Installations Except European
unless the electrical code designation Flameproof
stamped on the transmitter data plate Run wiring through the electrical connection hole in
agrees with the classification of the the areatransmitter housing, Rgures 2 and 3. If the trans-
in which the transmitter is to be installed.mitter has an external terminal box. Figure 3, run wir-
Failure to comply with this warning can
ing through one of the connection holes In the box.
result in explosion and fire; leading toAll in-
connection holes are threaded to accept a conduit
Jury and property damage. connection. Always plug any unused connection
hole.
2.3.1 General
The transmitter is designed to be part of a two-vi^re Transmitters which have BASEEFA, CENELEC or
system. The 4 to 20 mA dc output signal and the dc S A A electrical code approval are supplied with a
power to the transmitter are carried by the same pair cable gland installed in the electrical connection hole.
of wires. The transmitter does not contain a power Figure 2. The gland provides for the required sealing
supply. The necessary power supply can be separate of wiring entering the housing.
from the instrument load or built in as shown in the
connection diagram in the back of this manual.
Make connections to the transmitter terminals as
shown on the connection diagram in the back of this
The nominal power supply voltage Is 24V dc. The manual. For intrinsically safe applications, be sure to
supply voltage at the transmitter terminals must be
note the Intrinsic safety barrier requirements shown
between the Ilmrts of 13 and 36V dc. The output load
on the connection diagram.

SYBRON Taylor
IB-12B229(AS}

#
' 2.3.3 E u r o p e a n F l a m e p r o o f Installations • Hawke Type 501/453/T, size 0, for armored
Transmitters which are approved for use in European cable
Rameproof code areas are identified by the Bectricai
Code digits 42 in the instrument catalog number ® Hawke Type 501/454, size 0, for unarmored
(refer to 1.3 Serial and Catalog Numbers). These cable
transmitters have an external terminal box with an
earth terminal and cover lock, Figure 3A. 2.3.4 Shunting Diode
The transmitter may have an optional shunting
Run wiring through the3/4-jnch Int NPT connection diode(s) connected between terminals R and M, R1
hole in the terminal box, and make connections as and M or R2 and M. Transmitters with the diode are
shown on the connection diagram in the back of this identified by the Electrical Connection Suffix digits
manual. Wiring must enter the connection hole 02, 03, 04, 05, 07, or 08 in the catalog number. Refer
through a BASEEFA approved flameproof fitting. to the schematic diagram in the back of this manual.
Use an approved Hawke fitting, or equivalent..
The diode(s) is connected to shunt an external out-
Hawks flameproof fittings are manufactured by put meter, and provides a signal path so that the
J a w k e Cable Glands Limited, Oxford Street West, transmitter will continue to operate If the meter is
^P^hton-under-Lyne, Lancashire 0L7 ONA, England. removed from the circuit. Oo not remove the shunt-
Two approved fittings for this connection are: ing diode when connecting an external meter.

Conn. P l u g g e d

Figure 3A. Mounting Dimensions for European Flameproof Bectricai Connection

^ e d In U . S . A . ©Taylor Instrument Company. Otvision of Sybron Corporation, 1S82 TP-tl265


IB-12B229

T A B L E OF C O N T E N T S

TABLE OF CONTENTS

Para ' Page Para Page


1 INTRODUCTION 3 OPERATION
1.1 Description 4 3.1 Putting into Operation 14
1.2 Serial and Catalog Numbers 5 3.2 Field Zero Adjustment 14
1.3 Wetted Material Identification 7 3.2.1 Flow Installations 14
1.4 Specifications .7 3.2.2 Liquid Level Installations 14
3.3 Surge Protector Option, Accessory (339) ... 15
2 INSTALLATION
2.1 Mounting 10 4 FUNCTIONAL D E S C R I P T I O N
2.2 Process Connections 10 4.1 General 16
2.3 Electrical Connections 10 4.2 Zero Elevation and Suppression
2.3.1 General 10 Adjustments 17
2.3.2 Shunting Diode 10 4.3 Surge Protector Option, Accessory (339) ...18
— Seal Element Connections' Ref A
— Process lr»statlation Ref B DIAGRAMS
— Connection and Schematic
Diagrams Back of Manual

Ref A — Refer to Seal Element Section. IB-12B924


Ref B — Refer to Process Installation, IB-12B925

ILLUSTRATIONS

Fig. Page Fig. Page


1 Transmitter Housings 4 5 Field Zero Adjustment 14
2 Mounting Dimensions for Transmitter w/lth 6 Simplified Diagram of Transmitter 16
Bolted Cover 11 7 Functional Schematic of Transmitter
3 Mounting Dimensions for Transmitter with Electronics 17
Threaded Cover 12 8 Functional Schematic of Optional Surge
4 Assembling Optional Mounting Bracket Protector, Accessory (339) 18
Kit, Accessory 046) 13

TABLES

Table Page Table Page


1 Electrical Codes for Hazardous Locations 4 Range Limits with Zero Jumper
(USAandCSA) 6 in El/Supr Position
2 Electrical Codes for Hazardous Locations 5 Output Load Limits
(Europe) 6
3 Range Limits with Zero Jumper
In Norm Position 8
IB-12B229

INTRODUCTION

INTRODUCTION

:ti

THREADED COVER BOLTED COVER

Figure 1. Transmitter Housings

1.1 DESCRIPTION signal. The strain gage Is hermetically sealed to pro-


The Taylor 3423T and 3424T Differential Pressure tect the bridge circuit from moisture, corrosive en-
Transmitters with remote seal elements are instru- vironments, and mechanical damage. The electrical
ents which measure process differential pressure signal is amplified and converted to a 4 to 20 mA dc
c nd transmit a proportional 4 to 20 mA dc electrical
output signal.
signal for transmission to another Instrument.

The transmitters are designed to operate as part of a


Several seal element types are available. They pro- two-wire system. They receive power ( + 24V dc)
vide process connection to chemical tees, 3-inch from the same pair of wires over which the output
A N S I flanges, or 1/2-inch welding necks. An ex- signal Is transmitted.
tended diaphragm element, suitable for connection
to a 3-inch flanged tank nozzle or flanged tee, per- The span of each transmitter is continuously ad-
mits the process diaphragm to be located flush with justable. The span and zero adjustments are accessi-
the inside of a tank or pipe. ble from the outside of the instrument. All ad-
justments to span and zero respond electronically.
The transmitters are available in medium and high
range forms, providing capability for measuring dif- The transmitter housing is low copper content, die-
ferential- spans from 25 to 650 inches of water (6 to cast aluminum. The cover can be either bolted or
160 kPa) at operating pressures ranging from full threaded. Figure 1. The bolted cover is for use in
vacuum to 1500 psig (10 000 kPa). General Purpose or Division 2 electrical code areas
and for intrinsically safe applications in Division 1
A resistance strain gage bridge circuit converts the areas. The threaded cover is for use in Division 1
differential pressure measurement to an electrical electrical code areas. The housing provides radio fre-
IB-12B229

INTRODUCTION

quency interference (RFl) protection; and Is water- accessory Is inside the housing. On transmitters with
proof. a threaded cover, the accessory is located in an ex-
ternal terminal box. Figure 3.
An optional surge protector. Accessory (339), pro-
tects the transmitter electronics against high-voltage Under a two-year warranty, the circuit board/sealed
surges which are often Induced by lightning. On strain gage assembly or the measuring element is
transmitters with a bolted cover, the surge protector replaceable through a Repair-By-Exchange Plan.

1.2 S E R I A L A N D C A T A L O G N U M B E R S
The serial number stamped on the data plate consists of the catalog number and a sequential Identification
number. The catalog number describes the construction of the transmitter.

An X before the serial number indicates that the Instrument has been built to meet a customer's special re-
quirements.

Serial Number 3423T D 10 2 6 3 - 0 1 00 15 (339) - 555 8

Basic Catalog Number


Measuring Element Actuation
Electrical Code
Wetted Material
Catalog
Seal Element Construction
Number
Electrical Connection Suffix _
Extended Diaphragm Length-
Capillary Length
Accessories (omitted if not required).
Sequential Identification Number
Model (Design Level)

B A S I C CATALOG NUMBER. 81 — U.S. Intrinsic Safety — See Table 1


3423T — Medium Range Transmitter USA
Span adj from 25 to 200 In. water 82 — European Intrinsic Safety — See Table 2
(6 to 50 kPa) CENELEC Approval
3424T — High Range Transmitter 83 — Yugoslavian Safety
Span adj from 200 to 650 in. water Commission Approval
(50 to 160 kPa) 84 — Canadian Intrinsic Safety — See Table 1
CSA Approval
MEASURING ELEMENT ACTUATION 88 — Australian Intrinsic Safety
D — Differential Pressure SAA Approval
99 — Electrical Code described by
ELECTRICAL CODE Accessory (147) — See Table 2
10 — General Purpose WETTED MATERIAL
Taylor Standard 16 — Hastelloy-CVdIaphragm and
21 - U.S. Division 2 - See Table 1 type 316 S S T
USA 26 - Type 316 SST^
24 — Canadian Division 2 — See Table 1 36 - Hastelloy-C
CSA Approval 46 — Monel
25 - U.K. Type N Protection - See Table 2 56 — Nickel
BASEEFA Approval 76 — Tantalum
41 - U.S. Division 1 - See Table 1 99 - Special
USA
42 — European Flameproof
CENELEC Approval
44 — Canadian Division 1 — See Table 1 ' T . M . of Union Carbide Corp.
CSA Approval 'For 3 4 2 _ T D 263- type 316L SST
I8-12B229

^INTRODUCTION

Table 1. Electrical Codes for Hazardous Locations (USA and CSA)

Hazardous Location
Electrical Class I Class M Class Ml
Code No.
Oiv 1 Div 2 Div 1 Div 2
Groups Groups Groups Groups Div 1 Div 2
A B.C.O A B.C.D E.F.G E.F.G

21
\
24
41
44
81
84

Table 2. Electrical Codes for Hazardous Locations (Europe)

Catalog Number Digits Description


Electrical Electrical Connection Acc Type ol Safety Hazardous Area Safety For Approvals
Code No. Suflli No. Protection Code Zor>e 0 Zona 1 Zona 2 Std. Installation in Authority

8$4683>
25 01.02.a3.M.06.08 f N E>N II 75 X Part 3: UK
.igjT'

Ot.02,04,05 1 <a EE.id II CT5 X X X EN00020 UK dnd other


82 08 t •a EE'<a II BT5 X X X IBS560t:Pari 7: CENEUC BASEEFA
08 t tb EEiib II GTS X X 1977) member states

BS46S3:
01.02.04.05.06 1147) N, EiN II T5 X Part 3:
1972
99 UK
01.02.04,05 11471 is EEiia II CTS X X X eSS601:
<a E£<ia It BTS X X X Pan 7;
08 (147)
ib EExrb II CT5 X X 1977

ICan be any accessorv number eicepi (147)


•CENELEC rr^embef states: Austri*. Belgium, Denmark. Finland, Franec, W- Germany, Greece. Ireland, Italy. Luacmbouffl,
Netherlands. Norway. Portugal. Spain, Sweden. Switzerland and United Kingdom
Note; BASEEFA of EEC ceniliod barriers must be used with the inifinsically safe transmitters <i« and ib) as per BASEEFA
certified System Diagram IS080040a Sheet I. page 2.

SEAL ELEMEiNT CONSTRUCTION ELECTRICAL CONNECTION SUFFIX


1 — Diaphragm Element 01 — Terminal block connection
Chemical Tee Type 02 — Terminal block with shunting diode and
3 — Diaphragm Element 2.5 ohm calibration resistor
Wafer Type for use with • 03 — Terminal block with shunting diode, 2.5 ohm
3-inch A N S I flanges calibration resistor, and output test jack
4 — Diaphragm Element 04 — Terminal block with shunting diode, 2.5 ohm
Welding Neck Type, 1/2 Inch calibration resistor, and output meter
schedule 40 pipe with 0 to 100 linear scale
7 — Diaphragm Element 05 — Terminal block with shunting diode, 2.5 ohm
Extended Type with 3-inch, calibration resistor, and output meter
Class 150 A N S I raised face flange with 0 to 10 square-root scale
8 — Diaphragm Element 07 — External terminal box with shunting diode
Extended Type with 3-Inch, 08 — Terminal block with shunting diode, 2.5 ohm
- Class 300 A N S I raised face flange calibration resistor, and current meter
jack across shunting diode
IB-12B229

INTRODUCTION

EXTENDED DIAPHRAGM LENGTH HAST - Hastelioy-C .


00 — No.extension 316 - Type 316 S S T
0 2 - 2 Inches (5.1 cm) MON - Monel
0 4 - 4 inches (10.2 cm) TANT — Tantalum
0 6 - 6 inches (15.2 cm) Nl - Nickel
09 - Special
When the instrument has more than one type wetted
CAPILLARY LENGTH material, the data plate Identifies the materials in the
Digits indicate k/igth in feet: following sequence:
05 through 35 — 5 through 35 feet
(1.52 m through 10.67 m) Process Diaphragm — Trim
99 -- Special
1.4 SPECIFICATIONS
ACCESSORIES
(129) — 3-inch, Class 150 A N S I raised face slip-on SPAN*
flange with stud bolts and nuts for use 3423T: Adj from 25 to 200 in. water
with Seal Element Construction No. 3. (6 to 50 kPa)
(130) — 3-inch, Class 300 A N S I raised face slip-on 3424T: Adj from 200 to 650 In. water
flange with stud bolts and nuts for use (50 to 160 kPa)
with Seal Element Construction No. 3.
(131) — 3-inch, Class 600 A N S I raised face slip-on CALIBRATION A C C U R A C Y (Zero Based)
flange with stud bolts and nuts for use + 0.5% of span [0.25% ultimate capability to 150
with Seal Element Construction No. 3. in. water (0.37 kPa) span; ± 0 . 5 % ultimate
(132) — 3-inch, Class 900 ANSI raised face slip-on capability over 150 In. water (37 kPa) span)
flange with stud bolts and nuts for use
with Seal Element Construction No. 3. RANGE LIMITS
1146) — Mounting Bracket Refer to Tables 3 and 4
(147) — Data Plate indicating that transmitter
satisfies requirements for both Electrical WORKING PRESSURE LIMITS
Codes 25 (U.K. Type N Protection) and Minimum
82 (European Intrinsic Safety) — 0 psia at 300°F (149°C) maximum when seal
See Table 2 elements are at or above elevation of
(339) — Surge Protector transmitter'

EXAMPLE: Maximum
Serial Number 3423TD10263-010015(339)-555B iden- 3423T, 3424TD 1: 300 psIg (2000 kPa)
tifies a medium range transmitter (3423T) adjustable 3423T, 3424TD 3: Same as rating for
from 25 to 200 Inches of water (6 to 50 kPa), and ac- A N S I flange but not
tuated-by differential pressure (D). It is designed to to exceed 1500 psig
operate In areas designated as general purpose by (10 000 kPa)
the electrical code (10). The process wetted material 3423T, 3424TD 4: 1500 psig (lOOOOkPa)
is type 316 SST (26), the seal element construction is to 400 (204^0
the wafer type for use with 3-inch A N S I flanges (3), 3423T, 3424TD 564: 1000 psig (7 000 kPa)
and the transmitter has a terminal block connection to 400 °F (204 ^ 0
(01). The diaphragm is not extended (00), and
capillary length Is 15 feet (15). The transmitter has a
surge protector (339). The sequential identification
number is 555, and the design level is Model B.
' T h e factory-calibrated span is identified on the side of the strain
gage bracket.
1.3 W E T T E D M A T E R I A L I D E N T I F I C A T I O N
'On vacuum service installations, seal element can be located
The following abbreviations are used on the Instru- beiow transmitter when minimum process pressure is above
ment data plate to identify materials wetted by the 0 psia. Refer to Proccss Installation for limits.
process.
IB-12B229

INTRODUCTION

Table 3. Range Limits with Zero Jumper m N O R M Position

Range Limits

Inches of Water Kilopascals


Catalog No. Calibration
Lower Upper Lower Upper
(4 m A Output) (20 m A Output) (4 m A Output) (20 m A Output)
Zero Based 0 + 25 to +200 0 +6 to +50
3423T Suppressed Zero 0 to » 50 + 25 to +200 0 to +12 + 6 to +50
M e d i u m Range Elevated Zero - 5 0 to 0 -25 to +200 - 1 2 toO -6 to +50
Center Zero - 5 0 to 12.5 + 12.5 to +50 - 1 2 to - 3 +3 to +12
Zero Based 0 + 200 to +650 0 + 50 to +160
3424T Suppressed Zero 0 to + 1 6 0 + 200 to +650 0 to + 4 0 + 50 to + 160
High Range Elevated Zero - 160 to 0 + 40 to +650 - 4 0 to 0 + 10 to + 160
Center Zero - 160 to - 1 0 0 + 100 to + 160 - 4 0 to - 2 5 + 25 to +40
All transmitters can be continuously adjusted for any calibration listed.
E-13n.200

Table 4. Range Limits with Zero Jumper in EL/SUPR Postion

Range Limits

Inches of Water KilopascaJs


Catalog N o . Calibration
Low/er Upper Lower Upper
(4 m A O u t p u t ) (20 m A O u t p u t ) (4 m A Output) (20 m A Output)
Zero Based 0 + 25 to +200 0 +6 to +50
3423T Suppressed Zero 0 to + 175 + 25 to + 200 0 to +44 + 6 to +50
M e d i u m Range Elevated Zero - 170 to 0 -145 to +200 - 42 to 0 -36 to + 50
Center Zero - 1 0 0 to - 1 2 . 5 + 12.5 to + 100 - 2 5 to - 3 +3 to +25

Zero Based 0 + 200 to +650 0 + 50 to +160


3424T Suppressed Zero Oto +450 + 200 to +650 0 to 110 + 50 to +160
High Range Elevated Zero - 650 to 0 Oto +650 - 1 6 0 to 0 0 to +160
Center Zero - 3 2 5 to - 1 0 0 + 100 to +325 - 8 0 to - 2 5 + 25 to +80

All transmitters can be continuously adjusted for any calibration listed. E - m i » i

.3423T, 3424TD 7.8: Class 150 Flange OUTPUT SIGNAL


at 100°F (38°C) 4 to 20 mA dc
is 275 psig
(1900 kPa) OUTPUT LOAD LIMITS - Refer to Table 5
at 400°F (204°C|
is 180 psig POWER SUPPLY
(1240 kPa) 24V dc nominal
Class 300 Flange 13V dc min, 36V dc max. across transmitter
at 100°F (38°C) terminals
is 720 psig
(5000 kPa)
at 4 0 0 T (20400
is 665 psig
(4580 kPa)

T T y • PI'
IB-12B229

INTRODUCTION

Table 5. Output Load Limits

M a x Transmitter Load (Ohms)*


Supply Elect. C o n n Suffix Elect. Conn Suffix
(DC Votts) 01 02. 03. 04. 05. 07. 08

13 50 0
15 150 100
20 400 350
24 600 550
30 900 850
35 1150 1100

•Max load is reduced 70Q if transmitter has a surge protector.


Acc (339).

POWER CONSUMPTION STORAGE TEMPERATURE LIMITS


0.5W nominal - 6 5 ° F (-54°C) min,
1.5W max. In overrange condition + 200OF (93°C) max.

WEIGHT' (Less seal elements) S E A L ELEMENT ELEVATION


3423T: 10.9 lbs (4.9 kg) Minimum Pressure — 0 psia:
3424T: 8.9 lbs (4.0 kgl Elements must be at or above elevation of
transmitter
AMBIENT TEMPERATURE LIMITS
Housing and Measuring Element: Minimum Pressure — Atmospheric:
-40°F (-40°C) min, Elements can be above or below elevation of
+ 185°F (85°C) max. transmitter
Capillary:
-40°F (~40°C) min, If element is belov^, limits are as follows:
+ 180<'F (82°C) max. 3423T: 31 ft (9.5 m) max.
Seal Elements: 3424T: 30 ft (9.1 m) max.
-40OF ( - 4 0 ° C ) min, (If transmitter Is more than 1000 ft (305 m) above
+ 400°F (204OC) max. sea level, reduce limit by 1.2 ft (36.6 cm) per
1000 ft (305 m) of altitude]
*Add 3 ibs (1.4 kg) for unrts with threaded cover.
IB-12B229

INSTALLATION

INSTALLATION

2.1 M O U N T I N G 2.3 ELECTRICAL CONNECTIONS


Refer to Process Installation Section, IB-12B925,
for information on locating the transmitter for WARNING
specific applications. Do N O T make electrical connections
unless the electrical code designation
Carefully unpack the transmitter and uncoil the tube stamped on the transmitter data plate
system. agrees with the classification of the area
in which the transmitter is to be installed.
CAUTION Failure to comply with this warning can
The process diaphragms will be damaged result in explosion and fire; leading to in-
if the seal elements are lowered too far jury and property damage.
below the transmitter, especially when
used on vacuum service. Refer to 1.4 2.3.1 General
Specifications. The transmitter Is designed to be part of a two-wire
system. The 4 to 20 mA dc output signal and the 24V
Do not remove the protective covers fromdc power to the transmitter are carried by the same
the seal elements until ready to connect pair of wires. The transmitter does not contain a
them to the process. power supply. The-necessary power supply can be
separate from the instrument load or built in as
Select a mounting location where there is minimum shown in the connection diagram located in the back
vibration. Ambient temperature must not exceed the of this manual.
limits listed under 1.4 Specifications.
If the power supply voltage Is greater than 24V dc, do
Mount the transmitter with the measuring element not exceed 36V dc across the transmitter terminals.
below the case as shown in Figures 2 and 3. Opera- The output load limits of the transmitter are shown in
tion is not affected by mounting in other positions Table 6. Conduit may be connected to the threaded
but some rezeroing will be required. Refer to 3.2 connection in the transmitter base. Refer to Figures 2
Field Zero Adjustment. and 3.

The transmitter can be mounted using the two 2.3.2 S h u n t i n g Diode


15/16-18 mounting holes in the measuring element. When the transmitter catalog number contains Elec-
Figures 2 and 3. trical Connection Suffix digits 02. 03, 04, 05, 07, or
08, a shunting diode(s) is connected between ter-
An optional mounting bracket kit. Accessory (146), minals R and M in the terminal box. Refer to the
provides a bracket. U-bolts, spacer, and fasteners. schematic diagram in the back of this manual.
Figure 4. The bracket is suitable for either pipe or sur-
face mounting. For pipe mounting, the bracket ac- The dlode(s) is connected to shunt an external out-
cepts M / 4 through 2-inch pipe and can be posi- put meter and provides a signal path if the external
tioned for use on horizontal or vertical pipes, Rgures meter Is removed from the circuit. Do not remove the
2 and 3. shunting diode when connecting an external output
meter.
2.2 P R O C E S S C O N N E C T I O N S
Refer to Process Installation Section for Informa-
tion on locating the transmitter for specific applica-
tions.

10
1B-12B229

INSTALLATION

CiMrttnc* to
ftemov* Cover

Electrical Conn
Earth Terminal 1/2 Ini NPT
COn Opposite Side)
ble Gland Conn

Mounting Brachet
Electrical Conn location
1
1/2 Int NPT
Capillary to t
B D
High Pressure
Sool Element . + +
2 Mounting Holes 3/4
5-1^6 • 18 NC 2 X 1/2 Deep
<0n Opposite Side of Element}
4 3-1/4 ^

C A l A L O C NO. A U C D
3423T 8-23/32 3-1/22 12-3/16 1-3/4
34 24T 7-3/4 2-1/4 12-7/IC 3/4

A C C E S S O R Y N O . (146) Pipe M t g Bracket

wm
! '. I
&-1/8 •T4-5/B
?'• Pipe
9-3/16- 7-5/16 {Can also be mounted
on 1-1/2 and 1-1/4 pipe)

Bracket Left HORIZONTAL PIPE MTG

ah Siti -5-13/16-

5-1/8
7-7/16
Bracket Right
4 5/B

7-5/16
u
aa ^ ^ ^ See Note 1
342_TD -03. -08
342 TO •04. -05
VERTICAL PIPE MTC
INCHES mm INCHES mm
1/2 12.70 4-5/8 117.48
11/16 1 7.46 5-1/8 1 30.1 8
Notes: 3/4 19.05 5-3/8 136.53
1. O n instruments w i t h electrical c o d e 25. S2, 1-3/4 44.45 5-13/16 147.04
For reference only:
or 8S. o u t p u t moter i s m o u n t e d in electrical 2-1/8 53.98 6-3/8 161-93
not for c o n s t r u c t i o n
c o n n e c t i o n on other end of tarminal box. 2-1/4 57.15 7-5/16 185.74
A l l d i m e n s i o n s in Inches. 2-1/2 63.bO 7-7/16 18B.91
2. Capillary from transmitter to seal e l e m e n t i» 2-5/8 66.68 7-1/2 190.50
the s a m e length for b o t h elements. 3 76 20 7-3/4 196.85
3-7/32 81-76 8-5/32 207.17
3-1/4 82.55 8-23/32 221.4 6
4-1/16 103.19 9-3/16 233-36
4-3/16 1 0 6 . 3 6 -. 12-3/16 309.56
4-1/4 107.95 12-7/16 315.91
4-«/16 115-89 12-1/2 317.50

Rgure 2. Mounting Dimensions for Transmitter with Bolted Cover

11
B-12B229

INSTALLATION

i Cleorance to
Remove Cover

Mowflling Srocket
Locotion
electrical Conn
1/2 inf N P T
Copillory To
High Pressure
Seal Element
(See N o t e 1)

2 Mounting Holes
Capillory to 5/16-18 NC-2 11/2 Oaep
Low Pressure
Seol Element (On Opposite Side Of Element)

A C C E S S O R Y N O . (146) Pipe M t g Bracket c-iri»-i>4<»i

li D

t.
2*Pipe
Crocket Left n o l i o be mounted on^
-1/2 and i-t/4 pipe j
VERTICAL PIPE HTG
HOaiZONTiL PIPE MTC

INCHES mm INCHES mm
Terminal 6os 5/16 7.94 • 5-1/8 130.18
( S e e N o t e 2) 1/2 12.70 6 152.40

\
11/16 17.46 6-1/8 155.58
3/4 19.05 6-3/8 161.93
7/8 22.23 7-1/2 190.50
15/16 23.81 7-11/16 195-26
1-3/4 44.4S 8-1/4 209.55
2-1/4 57.15 8-11/16 220.66
2-1/2 63.50 91/16 230.19
Elecincoi /
p' ^ cieinH Z-5/8 66.68 9-21/32 245.27
Conn 3 76.20 10-5/8 269.88
« - 3 . . J 3 / 4 l f . i NPT M/4 82.55 121/2 317.50
-••1/2 88.90 14-3/32 357.98
J 9/16 90.49 14-11/32 364.33
•«1 ' / 1 6 1 12.71 28 '11.20
c IXTALOG NO. A B C O "-S/S 117.48
342 3 T 10-5/8 3-7/32 14-3/32 1-3/4
3424T 9-21/32 2-1/4 14-11/32 3/4
Notes:
1. Capillary f r o m transmitter t o seat element i s
the s a m e length for both elements.

2. S u r g e protector circuit Is h o u s a d in terminal


For referenco only: A l l d u n e n s i o n s in I n c h e s . box w h e n tronsmitter is e q u i p p e d with
not for c o n s t r u c t i o n A c c e s s o r y [339).

Figure 3. Mounting Dimensions for Transmitter with Threaded Cover

12
B-12B229

INSTALLATION

Mounting
Bracket

Figure 4. Assembling Optional Mounting Bracket Kit, Accessory (146)

13
, IB-12B229

_ OPERATION

OPERATION

Zero
Adjustment

Zero '"-I
Adjustment

THREADED COVER BOLTED COVER

Figure 5. Field Zero Adjustment

3.1 P U T T I N G I N T O O P E R A T I O N 2. Determine the required output using the ap-


This section describes start-up of the transnr>itter plicable following equation:
assuming that it has been installed as recommended
in the Process I n s t a l l a t i o n S e c t i o n . a. Using U.S. Units: (1)

Turn on power to transmitter, then use the following (Ref Level — Min Level) Gt
procedure under 3.2 Field Zero A d j u s t m e n t . Out = 16 + 4
Span

3.2 FIELD ZERO ADJUSTMENT where Out Output in milliamperes


Min Level Lowest level to be measured,
Flow Installations inches above datum line
1. Shut off flow to obtain zero differential across Ref Level = Any known level between
measuring element. minimum and maximum,
inches above datum line
2. Output should be 4 mA dc with flow shut off. Gt = Specific gravity of liquid in
tank
If it is not, turn ZERO adjustment. Figure 5, to Span = Transmitter span setting,
obtain required output. Clockwise rotation in- inches of water
creases output.

3.2.2 L i q u i d Level I n s t a l l a t i o n s
1. Bring liquid up to minimum jevel or to a known
reference level.

14

I j.T'u.j'gr.-
IB-12B229

OPERATION

b. Using SI Units: (2) 3.3 SURGE PROTECTOR OPTION,


ACCESSORY (339)
J {Ref Level - Min Level) (Gt) (C) Accessory (339) provides a built-in surge protection
Out = 16 + 4
Span circuit. The surge protector is designed to dissipate
large quantities of electrical energy {2500V dc max-
where Out Output in mllliamperes imum) which have been Induced in a transmission
Min Level Lowest level to be measured, line. These large quantities of energy can be induced
centimeters above datum line in the signal transmission lines by lightning discharge
Ref Level = Any known level between or by nearby electrical equipment. The dissipation of
niinlmum and maximum, this energy prevents damage t o transmitter circuitry
centimeters above datum line connected to the transmission llnew
6t = Specific gravity of liquid in
tank The surge protector will not protect the instrument in
C = 0.098 (kilopascal conversion case of a direct lightning strike. The surge protector
constant, kPa/cm) is designed to operate and recover automatically. It
Span = Transmitter span setting, does not require periodic testing or adjustment.
kPa
On transmitters with a bolted cover, the surge pro-
NOTE tector circuit is located in the terminal box in the base
Transmitter datum line is at center of the of the housing. Figure 1. On transmitters with a
H I side process diaphragm. threaded cover, the surge protector circuit is located
in the external terminal box. Figure 3.
3. If output does not agree with value calculated in
Step 2, turn ZERO adjustment. Figure 5, to ob-
tain required output. Clockwise rotation in-
creases output.

15
IB-12B229

FUNCTIONAL DESCRIPTION

FUIMCTIONAL DESCRIPTION

• Output

Seal E l e m e n t Seal E l e m e n t
LO HI

Figure 6. Simplified Diagram of Transmitter

4.1 GENERAL An increase in differential pressure, acting on the


A simplified diagram of the transmitter with the elec- process diaphragm. Is transferred through the liquid
tronics in block diagram form is shown in Figure 6. A fill to the primary diaphragm. Force is developed
functional schematic of the transmitter electronics is which causes the force beam to pivot around the
shown in Figure 7. thrust pivot and seal. The motion of the force beam

16
' /
IB-12B229

FUNCTIONAL DESCRIPTION

R12
Zero
Adjustment

RL
Output
Load

RFI 1
FILTER 1

Figure 7. Functional Schematic of Transmitter Electronics

is transferred to the strain gage force unit through A zero jumper can be positioned between R17 and
the connecting wire. The strain gage force unit con- RIO to provide increased zero elevation or suppres-
tains four strain gages connected in a bridge con- sion capability.
figuration. Movement of the force beam causes the
strain gages to change resistance. This change in 4.2 ZERO E L E V A T I O N A N D
resistance produces a differential signal which is pro- SUPPRESSION A D J U S T M E N T S
portional t o the input differential pressure. This dif- Zero elevation or suppression adjustments are re-
ferential signal is applied to the inputs of amplifier quired when it is necessary to bias the output to
A2, which drives the output current regulator 0 2 . compensate for the effect of initial head pressures
Q3. The design of the current regulator limits the which are often encountered in liquid leveJ applica-
maximum output current. tions. The initial head pressure is developed by a dif-
ference in elevation between the seal elements or by
One side of the bridge connects t o the zero circuitry a column of process liquid which remains constant as
and the non-inverting input of amplifier A2. The the tank level changes. The zero elevation and sup-
other side of the bridge connects to the inverting in- pression capability is provided by the zero adjust-
put of amplifier A2 (via R I D and the span circuitry ment. Figure 7.
(via R6).
W h e n the LO side seal element is located above the
The span adjustment. R14, adjusts the closed loop H I side seal element, as in a liquid level instaliation,
gain of amplifier A2. It can be set to give a transmit- the difference in elevation produces an initial head
ter output current of 20 mA at the required upper pressure which is applied to the low side of the
range limit of the input. primary diaphragm. This causes the output to be
belov^ the required zero value (4 mA) at minimum
The zero adjustment, R12, can be set t o give a level. By turning the zero screw, the output can be
transmitter output current of 4 m A at the required e l e v a t e d to the required zero value.
lower range limit. Most of this current is supplied by
the voltage regulator circuit, minimizing the interac- If the LO side seal element is located below the HI
tion between the span and zero adjustments. side sea! element, initial output will be above the re-

17
I ' IB-12B229

•UNCTIONAL DESCRIPTION

Induced
Voltage

fit

/
Transmission
Line A'lTivn

Figure 8. Functional Schematic of Optional Surge Protector, Accessory (339)

quired zero value (4 m A ) . By turning the zero screw, The time delay due to the r-c network allows surge
the output can be s u p p r e s s e d to the required zero diodes (gas discharge'tubes) SD1 and SD2 time to
value. turn on. When the surge voltage exceeds the firing
voltage (approximately 90V dc) of the surge diodes,
Elevation or suppression adjustments are made as the diodes conduct and short the surge voltage to
part of the transmitter calibration procedure. The ground. The surge diodes conduct either trans-
head pressures are simulated by calibration pressures versely from line-to-line or longitudinally from line-to-
applied to the high or low side of the measuring ele- ground. If only one surge diode fired or one fired
ment. ahead of the other, the voltage surge would continue
toward the protected instrument circuitry. Then, the
4.3 SURGE PROTECTOR OPTION, voltage surge would be slowed further by r-c net-
A C C E S S O R Y (339) v>/orks R1 and C2 or R2 and C3 until 2ener diode D1
The surge protector circuit, Figure 8, protects the conducts. The Zener diode conducts only trans-
transmitter electronics from being damaged by high versely from line-to-line. It will limit the maximum
^ o l t a g e surges. When a surge voltage is induced in voltage applied to the protected transmitter circuit at
the transmission line, the leading edge of the surge is the Zener voltage. Resistors R1 and R2 limit the cur-
slowed down by an r-c network consisting of resis- rent flow through the Zener diode.
tors Rt, Figure 8, which represent the resistances of
the transmission line and capacitor 01.

18
1> IB-12B229

NOTES

19
15
T Y P E : Teflon lined wafer butterfly valve w i t h stainless steel disc
and molded teflon resilient backed seat.
SIZE: 5 0 - 5 0 0 mm.

R A T I N G : 10 bar tight shut-off.


G E N E R A L A P P L I C A T I O N : This new valve, oriented to the
chemical processing industry, offers an Improved design for
services, where elastomers are unsuitable.
The main feature of this valve combines the resiliency of the
rubber back-up material and tho chcmical resistance of the teflon
lined s e a t . .

FEATURES

o O N E - P I E C E W A F E R T H I N D I S C - S T E M for
high strength and absolutely positive disc
control, provides t h e very m i n i m u m obstruc-
tion t o flow.

e THE ROUNDED POLISHED DISC AND


H U B E D G E gives full c o n c e n t r i c s e a t i n g a n d
m a x i m u m seat life.

o S E A T D E S I G N has the famous Keystone


dove-tail retention.
N o b o n d i n g is r e q u i r e d . T h e r u b b e r m a t e r i a l
offers resilient b a c k - u p t o t h e t e f l o n c o v e r i n g
for positive s e a l i n g at t h e r a t e d pressure.

o THE INTEGRALLY MOLDED TEFLON


S E A T L I N E R e x t e n d s o v e r seat face to m a k e
c o n t a c t w i t h line f l a n g e t o p r o v i d e t h e seal,
e l i m i n a t i n g all r e q u i r e m e n t s for g a s k e t i n g .

o P R I M A R Y S E A L f o r m e d by the seat/shafl/hub
c o n t a c t exceeds t h e p r e s s u r e r a t i n g of t h e
valve.
B o d y is t o t a l l y I s o l a t e d f r o m f l o w i n g m e d i u m .

o DROP-TIGHT SHUT-OFF is a s s u r e d by
f a c t o r y test of e v e r y v a l v e t o full rating.

o S E C O N D A R Y S H A F T S E A L is self a d j u s t i n g .

9 T O P - B U S H I N G absorbs operator side thrust.

o T O P - P L A T E S are standardized for operator


interchangeabillty.

COPYRIGHT 1 f l 7 7 K u k'pvct/^r.^ Int«rr.at;i-.na! i n f c . n o . i n . T - fti")


KEYSTONE FIGURE 9-18-T BUTTERFLY VALVES

L - D - . J
DN 5 0 - 2 5 0 ON 3 0 0 - 5 0 0

VALVE D I M E N S I O N S
SIZE A B C D E F G 0 V\/EIGHT
mm mm mm mm mm mm mm mm mm - kg

50 51 109 108 41 102 32 14.3 33 3.0


65 64 129 122 44 102 32 14.3 48 3.5
80 76 144 132 44 102 32 14.3 64 4.0
100 102 164 152 51 102 32 15.9 90 5.5
125 127 194 152 53 102 32 19.0 117 • 7.2
150 146 220 173 53 102 32 19.0 138 8.5
200 197 275 • 64 152 32 22.2 188 15.0
250 248 330 229 64 152 32 28.6 241 20;5
300 298 377 308 76 152 51 28.6 290 31.0
350 337 429 305 76 152 51 28.6 328 40.0
400 387 489 329 102 152 51 41.3 373 56.0
450 438 546 368 108 203 57 47.6 424 92.0
500 489 600 403 127 203 57 47.6 473 112.0

STANDARD MATERIAL SPECIFICATION

Figure 9-18-T Available on special order

Body Cast iron Alumtntum. Ductile iron


Body screws Steel
Disc Stainless steel
Shaft Stainless steel
Seal Teflon
Packing EPDM •
Bushing Polyacetal

Other materials or combinations of materials are available on special order.

ISENTATIVE: OPERATORS: M A N U A L . PNEUMATIC A N D ELECTRIC OPERATORS AVAILABLE FOR ALL SIZES.

J
WAFER-STYLE BUTTERFLY VALVE
INSTALLATION FIG. 9

PROPER
IIMSTALLATION IMPROPER
PROCEDURE TECHNIQUES

PipftworK op«n«<} to allow valve free Pipework not spread sufficiently


Bmry. disc in ««m>-closed position. could tear rubber, disc poMaon
open will foul flange ar>d
score disc edge.

» ! I i!

/ri'iniS-TfilfrfiTtfii'-hfrr'

I i

n Valve in semi-open position to pro-


tuct disc trd9e 8r>d reduce rut>teT
Disc OS shown in fully closed
position causes seat aistonion.
. interforencti dunng installation and thnn subjected to flange dnw will
' / stdfl up, this helps reduce initial close rubber round disc creating yi(\ •
fTid!' 'd^h lOTQue build up. exccssive torque in wntiaf operation.
T I

sv.-v---:'.? -

/tD< *

DISC should be turned to full open GASKETS NOT R E C O M U £ N D E O


position after flange alignment and
before evenly pulling up flange bolts.
Kfn i'^Q/
Do not me gaskets J r' I iiui r ^
! kJ

f ^ f

VI M - 0 0 9
K E Y S T O N E V A L V E ( E U R O P A ) B.V.
B R E D A , THE N E T H E R L A N D S
rNSTALLATION A N D M A I N T E N A N C E INSTRUCTIONS

FIGURE 9 BUTTERFLY VALVE

Flange a n d Pipe Compatabilrty. Fig. 9 valve is designed 3. -Tack-weld the flanges to the pipe.
for use w i t h the most common DIN and A N S I Flange stan-
dards, as specified by the purchaser. 4. Remove the bolting and the valve from between the
flanges.
Valves produced to meet installation requirements of one
standard may not be suitable w i t h another standard. Important: Do not finish-weld the flanges to the pipe
Flanges have to meet following requirements: w i t h the valve bolted between the flanges
— The mating Inside diameter should be: as this win result'in serious heat-damage to
the seat.
m i n i m u m : The valve Q-Dlmension + adequate disc
clearance. 5. Finish-weld the flanges to the pipe and allow the flanges
maximum : The outside diameter (CD) of standard pipe to cool completely.
for the nominal size (Iso-recommendation
6. Install the valve now according to the procedure for in-
R336).
stalling in existing systems.
— if the flange (or pipe) is provided with a raised face, the
diameter of this shali be at least 10 m m larger than the
YY-dlmension of the valve. Maintenance.
— The bolt pattern shad allow centering of the valve in the Routine maintenance or lubrication is not required
line either by the inscribed circle of the bolts touching
the body-CD or by drilled holes in the lugs of the larger R e m o v i n g t h e valve f r o m the p i p e - l i n e .
k valves. 1. Turn the disc to nearly closed position (The disc is in
— The bolt-pattern must clear the hubs of the valve. line w i t h the paralell flats or keyway in the stem).
The use of the flange-gaskets should be avoided since 2. Loosen all flange bolts and remove the bolts which pre-
it might damage the valve. The Keystone seat-face vent removing the valve.
design eliminates the need for gaskets.
3. Spread the flanges w i t h adequate tooling, and remove
Installation in t h e Pipe-Line (Information) the valve.
Fig. 9 valve will control flow equally in either direction.
The r e c o m m e n d e d installation-position is the shaft' hori- Valve disassembly.
zontal and the lower disc-edge opening downstream.
1. Turn the disc to almost open position.
(Especially for slurry service and media w i t h a tendency
2. Remove actuator.
for sedimentation).
3. Remove the t w o body-screws.
A valve is no crow-bar. Do not use the valve to spread the
4. Remove the lower part of the body. This is more or less
flanges. Seatdamage during installation or in operation
held by the seat dove-tail. Use t w o screwdrivers in the
might be the result.
body-splits to separate t h e m and pull the bottom-part
Do not use flange-gaskets!
off w i t h a twisting motion.
The valve can be installed in the pipe-line either w i t h or
5. Pull the disc-stem and seat out of the body toppart.
without the actuator mounted on top of the valve. Make
6. Remove bushing and packing from the body toppart.
sure that you can turn the disc by hand so you can feel a
7. To remove the disc-stem from the seat, deform the seat
mismatch, resulting in a disc touching the adjacent piping.
Into a long „ o v a l " sufficient to clear the end of the short
k Installation in t h e Pipe-Line (Procedure). stem, move the short stem-end out of the seat-bore, and
' in an existing system. pull the long end from the seat stem hole, using a t w i s t -
1. Check whether the flange distance meets the valve face- ing motion.
to-face dimension. Spread w i t h adequate tooling the
flanges for easy insertion of the valve. Note: If you have complaints to make, mention the serial
2. Insert some flange-bolts In the flanges, to help you bear number on the valve tag-plate.
the valve after insertion.
3. Close the valve, so far, that the disc-edge is at least 10 Valve a s s e m b l y .
mm w i t h i n tha body. 1. Clean all parts. If possible use silicone-oil o n the disc-
4. Insert the valve between the flanges, center the valve stem to facilitate assembly. If the valve has to be provi-
body and insert all flange-bolts. ded w i t h a teflon-seat preheat this seat during half an
5. Open the valve completely. (The disc is in line w i t h the hour in nearly boiling water to ease assembly.
paralell flats or keyway in the stem). 2. Insert the long stem-end of the disc-stem into a seat
6. Maintain the valve to flange alignment while gradually stem-hole using a twisting motion.
removing the flange-spreaders and tightening the flange- 3. Deform the seat into a long „ o v a l " sufficient to clear the
bolts handtight. end of the short stem. W i t h the disc-stem simulating an
7. Slowly close the valve clockwise to check for adequate open position, move the short stem-end into the elong-
disc clearance. ated seat-bore and assemble the short stem-end Into
the other seat stem-hole by releasing the distorted seat.
8. Return the disc to full open position and cross-tighten
all bolting to the proper torque. 4. Push the long stem-end of the disc-stem/seat unit into
the body toppart. Push the seat dove-tail In place.
kin new systems. 5. Assemble the packing and bushing.
" l . V\/ith the disc in near-closed position center each mating 6. Assemble the bottom part of the body. Over one body
flange w i t h the valve body. Span the body w i t h some split a little rectangular Is casted w h i c h indicates in
flange-bolts' and tighten the bolts. w h i c h position the bottom part has to be mounted. In-
2. Use the flange-valvo-flange assembly for fit-up and cen- stall the body screws and tighten securely. Take care
tering to the pipe. that body pans are aligned completely.
MOUNTING
VALVE DIMENSIONS
VALVE SIZE SHAFT OlAM. A R C n YY 0 F F G eolT NO HOLE
Tim inch mm men mm inch mm incn CIRCLE HOLES OlAM.
60
2 14,3 SI 109 108 41 B6 33 30 102 32 14.3 9.6 82 4 11
GS
i'l, 14.3 64 129 122 44 97 46 3.S 102 32 14.3 •/I. 9.5 62 4 11
80 3 14.3 76 144 132 44 113 64 4,0 102 32 14.3 •/I. 9.6 62 ' 4 11
100 4 1&9 v.. 102 164 '6? SI 144 90 6.6 102 32 15,9 11,1 Vi. B2 4 11
t35 5 19.0 V. 127 194 162 63 l«7 U7 7,2 102 32 19 0 12,7 V, S2 4 1)
160 0 19.0 V. 146 220 173 S3 19S 138 S.5 102 32 190 V. 12,7 62 4 11
200 e 22.2 197 27S 211 64 262 IBB 16 0 162 32 22,2 169 127 4 U
ALL OtMENSIONS IN cnm.
V o o
NO. NAME
1 eusHiNC
2 SHAFT SEAL

3 UPPEfl 800V
1. . D - .
DISC STEM
SEAT
LOWER eODV
eOOY SCREWS

SPECIFY SIZE, FIGURE NUM8En. PART NAME & MATEfltAl WHEN ORDERING PARTS
- - G ^ - - .PARALLEL FLAfS

NOTES:
1. VALVE RATED AT 10 OAR PRESSURE
OlFFtHENllAL IN THE CLOSED POSITION.
2. SUITABLE FOR MOUNTING aeiWEEN
DIN PN. lODHHLEO FLANGES.
lOIHER FLANGES ON fttOUtST)
3. -Q - IS iMt OlSCCHUflOAL DIMENSION
AT FACE Qf VALVE, hOR DISC CLEARANCE
INTO PIKE, FiniMG OR EQUIPMENT.
4. TOP-PLATL MOUNItNC rOH HANDLE
I H R O n i t PLAItS. KEYSTONE GEAR
OPERAIORS. OR POWER ACIUATORS.
S- ON PIECE DiSC'STEU REQUIRES TWO
PIECE BOLTED BODY,

50-200 mm FIG. 9
RUBBER SEATED Keysw^B
S T A N D A R D PATTERN

COD 0 1 ' 4

COPYRIGHT 1977 t>v Ktytions Intorniiiontl inc.

I
-MO.UNIIMQ.
HOLES
VALVE D I M E N S I O N S
SHAFT OlAM VALVE SIZE A 8 C Q E F
D VY G KEY-SI2e BOLT •NO . HOLE
m<Ti inch mm CIRCLE HOLES OlAM
inert "0 mm mm
inch inch
10 240 330 229 64 303 24t 20,5 1S2 32 26.6 'V, 64116.4 'ly'!. 127 4 14
300 12 38.0 29^ 377 30S 76 ' 352 290 31.0 162 51 2B.6 fl.4>fl.4 127 4 14

/ 45V±N \

NO. NAME
BUSHING

UPPER eoov
OlSC-STEU

SEAT

D LOWER BOOV

BOOV SCREWS

SPECIFy SIZE. FIGURE NUMBER. PART NAME & MATERIAL W H E N ORDERING PARTS.

NOTES:
1. VALVE RATED AT 10 BAR PRESSURE
Dif FERENTIAL IN THE CLOSED POSITION.
2. SUITABLE FOR MOUNTING BETWEEN
OIN PN. 10 DRILLED FLANGES
(OTHER FLANGES ON flEQUEST)
3. "Q•• IS THE DISC CHOROAL DIMENSION
AT FACE OF VALVE. FOR DISC CLEARANCE
INTO PIPE. FITTING OR EQUIPMENT.
4. TOP-PLATfc MOUNTING FOR HANDLE
FOR S I Z E X)0 THROTTLE PLATES, KEvSTONf GCAfl
OPERATORS. Ofl POWER ACTUATORS.
5. ON PIECE DiSC'STEM REQUIRES TWO
PIECE BOLTED BOOV,

250-300 mm FIG. 9
RUBBER SEATED SicYSTBNE
STANDARD PAHERN

0 0 9 02/2

C O P Y R I G H T 1 9 7 7 by K«yitor>s lniarr>«tional inc.


VALVE D I M E N S I O N S
REY-SIZE BOLT NO. HOLE
B C 0 YY Q WEIGHT b h t, CIRCLE HOLES DiAM,
ko mm mm mm liibT^
429 305 76 40? 328 40,0 152 51 28.6 r/i 0.4.6,4 127 4 14
469 329 102 462 37 3 560 152 51 41,3 12,7.9.5 127 U
•>4B 36d 108 519 424 920 203 57 47,6 12,7.9,5 'ij V, 165 21
600 403 127 673 473 «12.0 203 67 ' 47,6 12,7-9.5 ItiS 21

NO. NAME
1 BUSHING
2 SHAFT SEAL
3 UPPER BODV
4 SEAT
5 DISCSTEU
6 LOWER BODY
7 0OOY SCREWS

SPECIFY SIZE. FIGURE NUMBER. PART NAMe & MATERIA) WHEN OROERINC PARTS.

NOTES:
J. VAlVt RATED AT 10 BAR PRESSURE
OlFHLHtNTIAL IN THE CLOSED POSITION.
2. SUITABLE FOR MOUNTING BErWEEN
OIN PN. U) DRILLED FLANGES.
(OTHER FLANOtS ON ReQUEST).
3. Q • IS TMfc DISC CHORDAl DIMENSION
AT FACE OF VAlVt, FOR DISC CLEARANCE
INIO PIPE, FITTING 00 EQUIPMENT.
4. TOP PLATE MOUNTING FOR HANDLE
THHOTflE PUkTES. KEYSTONE GEAR
OPtRATDHS. OR POWER ACTUATORS.
5. ON PIECE DISC-SUM RtaulRtS TWO
PitC't OOLTED fJUDY.
B. DOrTEO LINF INDICATES DiSC STf M OF
DUCTILE IHON AND ii 1AINLESS STEtL.

3 5 0 - 5 0 0 m m FIG. 9
RUBBER SEATED BiptSWNB
S T A N D A R D PATTERN

009-03/5

C O P Y R I G H T 1 9 7 7 by K e y i i o n e Iniarnaiionai inc.
FIGURE

T Y P E : Compact pneumatic rotary actuator set for 90® rotation.

R A T I N G : Maximum pressure up to 9 bars.

R A N G E: Operating pressure range: Air to air 1.5-8.0 bars


Spring to air 4 . 0 - 8 . 0 bars.

G E N E R A L A P P L I C A T I O N : Specially designed for direct


mounting on Keystone Butterfly Valves to ensure reliable
remote operation under the most severe working condi-
tions. Also suitable for remote control of other quarter
turn devices.

FEATURES:
e R A C K A N D PINIOW system guarantees a
constant output torque during a complete valve
cycle thus making it more suitable for throttling
control applications. Type 7 9 0 - 1 0 0 and 7 9 0 -
140 have scotch yoke mechanism.

• H O U S I N G is deep black hard-anodized alumi-


nium making the actuators suitable for corrosi-
ve surroundings, including salt spray environ-
ments.

o ACETAL LUBRICATED output shaft supports.


Bearings provide longer life w i t h a minimum of
maintenance.

e Because of the simple piston drive c o n c e p t ,


this actuator requires less dynamic seals in
operation than the more popular types currently
available. This means less chance for air
leakage.

o D I R E C T M O U N T I N G to Keystone butterfly
valves eliminates specially made adaptations
and guarantees proper alignment w i t h the
valve-stem. This reduces assembly time and
possible damage through bad installation.

0 NO EXTERNALPIPING.

o U N I Q U E M A N U A L O V E R R I D E system for
emergency operation has been built into the
position indicator knob.

o Available in t w o basic models.


— air to air operation
— air to spring operation.

o S T A N D A R D Keystone accessories available


as easy build on modules without special
brackets
— 4-Way Solenoid valve
— Limitswitch box

F
— Positioner

COPVRtriu-r 1 C TO/A 0 1
w^mm

k •-V • > • ^

P C D 2 62.6 mm
P C D 3 1270 mm
eti PCO L 165.1 mm

57
r S

m
f f p ^ V )

La fs.
kl-tJ
1 •iii-- -s
B2
- i ^
k 65

ACTUATED DIMENSIONS IN M M RATED OUTPUT TORQUES (N NM

SuitabiB
Weight for valve AIRSUPPLY IN BAR
Action Type A B1 B2 C D £ F kg mm 3
Tvp« 4 5 6 7 8
Air •79CK)03 133 89 4S 103 125 86 52 2.5 ; 40-100 790-003 i 16 X, 3t 37 43 49
to 790-006 "i 178 69 69 103 13S 66 52 3.0 40-100 790056 1 37 49 62 74 86 98
Air 7M-012 ; 318 109 109 127 147 111 63 6.0 . 65-150 790^12 74 98 123 148 172 197
'79(M18 ; 216 142 74 175 152 69 9,3 [ 66-i» 730^)16 • 106 142 179 •215 2S6 290
-790-036 . 284 142 142 175 196 152 89 13.0 • 69-300 790-C36 ' 221 295 369 443 516 S90
:79o o7o : 401 263 138 216 239 203 114 26.0 200-f00- TSfMTO • 400 535 666 799 864 929
' 790-140 ^ 526 263 263 316 239 203 114 35,0 ;:20l>«00 '750-140 861 1148 1435 1722 1894 2022
• 790-280 j 790-280 ''j

790^8 210 165 45 103 125 66 52 4.0 , 40-100


m
7900038
7900065 330 1« 103 125 66 52 6.1 ? 40-100 790-0065^
'ing 790-012S 388 194 194 127 147 111 63 n.5 i 65-160 790012S •
i 790-018S 305 231 74 175 196 152 69 14.8 65-300' 790^163'
1
.790-n'WS 462 231 231 175 196 152 69 2S.5 ) 65-300! .7S0036S- %
•;790-«70S 604 466 133 216 239 2C3 114 42.0 ; 200-600, 790070SJ
•790-1403 932 466 466 216 239 208 114 67,0 ; 200600; ;790-140S"
^730-280?
'' • - ••)

ACTUATION MOUNTtNG FLANGE

Actuator Shsfthofo Mounting flange Bolts


Stat
790-003 ISI 19.0 X l2.7(Fto($) 2 4 xMIO
79000C($) 19.0 >12.7 (Fbtsl
2 4 t MIO
790-012 iS) 19,0 X 12.7 (Fba) 2 4 i MIO
790-018 ($> e 28,6 (Key) 2-»3 4 X MIO/4 I MI2
790-036 (SJ 0 28.6 (Key} 2-f3 4 xMIO/4 I M12
790-C70 ISI 3^4 4 X M12/4 1M16
O 47.6 und B 57.3 (KeyJ
790-140 <S1 0 47,6 und O 57.3 CKeyl 3*4 4 I M12/4 •<M16
Notes:
1) S t a n d a r d s p r i n g 8 0
2) T h e r a t e d o u t p u t t o r q u e s i n c l u d e a s a f e t y f a c t o r .

Figure 790 - Pneumatic Actuator

Keystone datasheat 790-010

. Copyright by Keystone International Inc. 83/ tO


M a y charige without notice.
POSITION INDICATOR
EMBODYING SIMPLE
MANUAL OVER-RIDE

CORROSION-RESISTANT
FASTENINGS
PNEUMATIC DOUBLE ACTING

PISTON SEALS ROTARY ACTUATOR Kbyswms


FIGUR 7 9 0 - 0 0 3 THRU 7 9 0 - 0 3 6
790-11/2

COFYRIGHT 1977 by Keyiton* lm«fnat«ntf inc


ACTU4T0M OUTPUT SKAFTIOHf
VALVf DIMeNSlC'»iS 10ft 12
IACTUATO* 0 A
TVPf
FIC 790 mm
OIA
mm
FLAT
ifieft
VALVE-SIZE
mm 1 inch
2S t 30
1^ 62
c

79
1 0

28
E

97
YY

90
Q WEIGHT ko
FlC.9 F'G5
10 0.7
OOl-OOft' 40 44 82 94 30 B7 87
012 11.0 V. t2.» V, 30 ».t
211 — —
•0 t ftl 109 108 41 103 88 33 8.0 3.1
ee Th 94 129 <22 44 102 87 48 9,6 4.4
140** 1% 80 % 76 144 192 44 102 119 84 4.0 46
too—
274 — — too 4 t02 164 tS2 61 102 144 90 66 7J
12ft s 127 194 192 93 103 187 117 T3 8.7
• KEVSm ISO e 14« 220 173 U 102 19S 138 9.6 11.4
200 « 197 27S 3M 84 162 262 166 19,0 19.4
ONLY FOR «00 mm, 2B0 10 249 330 228 94 192 303 241 20.6 27,0
AVAtlAtU ACCfSSCHRES: 300 12 29a 377 306 76
I.UWITSWTCHBOX 192 392 290 31,0 400
3 SOlfNCXOVALVt 350 14 337 429
3. PO&lTtON 308 78 (62 402 328 400 60.0
400 Ift 3B7 489 329 102 162 492 373 68.0 81 0
4S0 IB 439 543 388 108 203 919 424 92.0 1010
500 20 499 600 403 127 203 673 473 12.0 S4.0
A U DtMENSlONS IN fnm.

ACTUATOR DIMENSIONS
OUTPUT
ACTUATOR VALVE SIZE RANGE AT • BAR J U V W
mm •NCFI
X WEIGHT
>>«
IN Nm bw
790-003 2S- 60 1:2 38 104 8» 135 86 2.9
[TSO-OOE as-100 2'A-4 76 v«- <04 89 178 8« 3.0
790-0t3 I2&-160 S-6 >90 •A" 127 109 218 112
L
790-03« I3S-300 6<I3 490 vr 175 141 282 162 13,0
790-100 200-400 9-16 9S0 V 2>9 243 411 203 26 0
790-140 2CI0 5 0 0 9-20 ISSO 'A- 2)6 299 677 203 1 44.5
ALL DIMENSIONS <N mm.

NOTES:
1. 8TAN0AR0 ACTUAtON MQUNTtNQ AS SHOWN.
2. ACTUATOR RATING: t.S BAR • t.O BAR AT
—40^T0«0^.
X 90* OPERATION PHOVIOEO.
4. F I G . * . 10 ft 12RATEDAT(0BAR PRESSURE
DIFFERENTIAL IN THE CLOSED POSITION.
5, BROKEN OUTLINE 0£T«OTES FIG. 13 BODY
WITH TAPPED LUGS.
6- - 0 • IS THE DtSC CHOHOAL DIMENSION AT
FACE OF VALVE FOR DISC CLEARANCE
INTO PIPE FITTING OR EOOIPMENT.
r MOUNTING FIG. 7®0-003 ON 2S-40n«»i USE SPEOAl
AOAFTERPLArE DIMENSION NOT INOICATEO.

FIG. 790 DOUBLE ACTING PNEUMATIC


ROTARY ACTUATOR FOR RUBBER \Frs70iie
SEATED VALVES

79001/5
c e a r a o T a

Quality Assurance Department

The following image quality is


poor due to original page quality

www.cleardata.co.uk
tel: 01670 356 734 fax: 01670 356 439
14: FROf'! rvCO iJPL.'JES TO 01978782343 P.Ob

<
X

. 1 A \'NiiL

?? C <J ^

i\ aiu! S i t ^ ' n ^ I n : ^ i i u c u o n s
R o . a i \ P n e u i i i a l i c P o s i t i o n e r

I.
•2-HPF-;-2l?irj3 1 : FR'Qn Ti'Cu K'-nL^.'ES TG 01S7S78234.3 P.05

Static p<jrfonnance
Hyit«ro5i?
fl'5peatf)Diliiv
Liiitoniy . <1 .0%
S u p p l y Proufu'""? fcfl^: Mlnitnal
SenSi'Mfy : < :.o%
Pow&f 2 5 % dfli/iaricn gives full oifierentia
.M' Consii'inplk;'* • 0,6 c t m 9 1 6 9 S ' t ) at baiartce v^ith
GO P S i G {A car) supply
; 2 s e c o n d s p-^t I X ctjbic lO
(1 6 4 Litres) o l Actuator Disp'^^ceriifint
Wrtig^! 4 lb {1,85 ki|)
30-1 p i i g (150 p s i g max.)
S t p p l y Pressure 2 - 8 2 5 oar g (10 uar g ma*.)
, 3 - 1 5 p s i ; 0 , 2 t O 1,0'oaOovof
Sigiftl R a n g o ;
9 0 * rr.ov©(iiBr»t • C A W '
3 - l i p ^ (0.2 l o 1.0 bar) Ov&r
6 5 ' rrovernent • C A M 2
3 - 9 psi ( 0 2 t o 0 6 D a r ) O R
9 O 5 p s t ( 0 , 6 to 1,0 M r } O v a r
6 5 * (TiOuHiTient • G A M 3
C A M C n a r a c t e n s t i t s . ' Linear
(otlier available o n roquest) •
Te^npflratiire Aanc;© ; •20'Ctc»70'C
tP65 rated w h e n switches

Reuofi procedure
) . R & m s v d positlonsr cover.
2 .nenio-ve i rc: p from t o p ot caiTS'^an
S.Refrioyfe w^acer irom camsnaft,
J Fit c a r . assBmbJy onto h e x a g o n c a m s n a f r w i i n adjustlrig a n d
d a m p i n p s c r e w s t o w a r d s the> outttoord 6 n d
N o t e : The ass9mi5 y h a s m a d e with a tight fr- onto the
^ o * a g o n ghatt in order to eliminate any b a c k l a s h . It m a y be
nece^r-ary to drive the a s s g m b t y o v . v the shaft T o d o this, us©

i ViN- I the origir^a! s p a c e r a s a Onit a n d rwe the a s s o m b l y over tha


shaft U5irg a ligi't h a r ^ n c r .
? Fit ths rftiCioswitcMetmina' plate a s ^ o w n liSlrvg the t w o M 5
1 . ; scrc.^t h s a g o n socket c ^ p s c r e w s .
6 Sot ' h s Cv in aocotdfijice «witr t^n p r o c e d u r e
7 R e t i '.•^6 cover

Cbm setting procedure


1 b o t h cianif;«n^ st^m'S. oi> tjrnlng e e c h s c r e w
J-
eppTj^Tiateiy ' . 5 tur,-s anti-clOvisA/^5©.
2 Ope'jita positionG^/actuator to d o s e ooaition.
3 AdiLSt ' C L O S E * acJju5t:fi9 s c r e w b y t m n a j c l o c K w i s a unt). 'o-ver
c a m jusi triggers fixi lower switch.
4 . 0 p c T a ' e p o s i t o n e r to epe-^ position
fvAdiust ' • C P E M " a d ijst^ig s c r e w by tu'-^ '^g £nt••clock\^'^co ur.ti
r - T - r ijpper CBfTi lust triQQe'S tho upper ssMtch
-U.

'
B
J
6 Tighten both clampfr>g s c r e w s to lock tho COTS m the
P0siti0f\.

11 7.Opefat0 the posit o.'>cr/r.cu«'^tor c p ^ h a n d c ' o i e d to c h o c k ' h o


c£.m o p o a t i c n 'e-iiS.j'tnecossar^*
U : So Fi-rjl'1 TYCO IJHLI'ES TO 01978782343 P.Q4

f^'sdbflck 3-
' . :\ '.iVj c-Mii
(n foct 0'
'.(••r i f l j f r«'yerte acilrtgi
. i , f 4 —

Tf'Tl,

/ S M O J
:— 11 o o * o i e o
- M frCH,! ^.'le;-' ^signal a* dressjrb g ^ s e
iS CW.1V1 •itAltCii-ti-'K J -ctt M-5 nitg, uews
zonn 1/aBSP 9 ftf>i ilvo

- f-^rcci'k J loLn c-en 93.5


SuiJi^i -cO'i,
IZ-JDSP

I 1. \ i 1/4 DPP

1 \ ^ 1 — ' J ;
I \ Outiw-conn. !_[_' ? . Vlauaipowon
'. til
V 4 DB -c rF ' ir.C«C3iar
Pp.-' lOv/ cn o'lv A '10 iCtnaJO' cperi port)
-J w . i c i.'jv'.' a CcrWvii entry • P G I f , 5
- C'.'.W-cc'in 8 V4 B S P actuatof dc&sd poii)

O ' - S B ' Wc-virgLna* P • C o T i c t e i S M ^ir 00nr>9cticn T- £«hau5i X'- Contfol lir®

• my^^-WssmmimmmmmMm^mmmmm •siv.

l.ipot fint-: vnga 3 - i S pai ^0,2 • 1 0 b i r ) sts'iderd


spV 3 - .9 PS. (0,2 • 0.6 ftar) 9 • 15 psi (0.6 - 1 0 eflf),
c"i2ri.c;&iii:ics Lneat
3 - ioSij c a m curve 1, f Ange: 3 • 15 P3i - 5 0 ' mo^'enisnt.
C'JFVU 5, range; 3 - 9 psi or 9 - 1 5 p s i = 65'" ino>/eai6rit.
CUIV9 3 . 'ai"igd. 3 • 15 psi = 6 5 ' movsi-nent.
oihCfr cliaractenstica o n raauest.

coir,projr,eid a'r or g a s , d u s t arid oii free wiin 6 tiller element to iiiei.


Sufvi/f?3:ufo 3 0 - 1 0 0 ps' {150 p s i max,) 2 • 3 t><ir (10 biir rnaA j

0 6 cirr, 'ii b a ' a n c o d coi-^gil-on with 6 0 p s i (d bar) suppi-/. .


for rnvni. I t."- eotal tump,i'atuf6
•5* to '-•'f5G-p(.20'' t o - r O ' C ) .
r^Cu.TJnQ pcjiit,on as rociJi'ed. N s limitaficjns,
connactlors mc^ritlnc) m universal m o u r . - n g kit for Fig 7 9 0 / 7 9 6 s s r i a s actuators,
a'I ccnno:'ons. siioply a n d output V«}' B $ P , signat i / 3 " fiSP

M d t C ' i i ; I s of a n o c i s e O aiuminiiirn alloy (siftintasA jitet^i optional)


CO^jtfllCtfOM • Vtvaj rii;til{) ruboer
ettiu^ids^ btsel
covor anoaiseci aiurnii'Jiuiti aiioy (stainless stool opiicnal),

We'tjnt 1 a G k g (4 lo.)

Option;: .nstrMrnent air 0 • 5 0 psi P • 2 bar) • 1 orf.


S u D U y a t 0 • 1 5 0 p$i (D • S Oar, • 2 oil
si'i^is poieooiJble t-irnw ".OA j - j o v A C
•r.-|ur.;n,Q projtiTiity typi? N T 2 A 0 - N ,
FPur- ' Y C O UHLVES TO 9197S782343 P . iU3

1 Sprlry siiei 30 Cam 2 Nylon-minion


Sv.'f 1 StSif»toS« steel 3 0 3 S 2 i 31 Locking plate 1 Stainless steel 3 0 3 S 2 1
1 S i a i n l s s s stael 3 0 3 S 2 1 32 Feedback carr. 1 G l a s s reinforced
i-r j' r ^ .-.aKJli; icllc)' 1 • acetal resin
C.'>p\ivG s.-rcw/ y StCiinier,:-. A2 33 Body 1 ProsGOfo dio cast
f Stainldss 303S21 Aluminium L W 2 4
7 /ico'.si-Jjiack v'i-: FfK'dCSck spring 1
1 N&oc'ene
'
U.'.cr.'ir, 35 S c r e w grub 1 Sratnlass steel A2
Stainless st&el 3 0 3 S 2 1 3B reeJoac!* spring rate
' • ' v r D o c i piv"/ • Stainlssb stee! 302/303 aajusier 1 Acotai
• 1 ^Jvo bocy 1 /^loiTt.n!urr» H E 3 0 3'/ AdjosTet'?ero teedbacK
C-rrig >r hJitrilo soring * Stainless steel 3 0 3 S 2 1
Jjf'.orc ' Stain'o^s siool 38 Locator •small bsarlng 1 Stainwss steel 3 0 3 5 2 '
' t 1 Stainless stee' 3 0 3 S 2 1 39 Aim-teeObaci' 1 Stainless steel 3 0 4 S 1 5
*J b j s PC'i-g 1 Bffi5sCZl2i 40 Bush-f©9dh>ac<< SffT. 1 Stainless stoet 3 0 3 S 2 1
* 1 b'.ai 1 Stainless stsel 5 0 2 S 2 5 41 Piii'Smeli b-eanng 1 Stainless sieoi 3 0 3 S 2 1
: ^rlC.tp 1 AJuniini'jm 2 0 1 F C 1 02 Spaccr-iJuppori toodback
•1 .Vti " Pressure d'ti cas^ arm 1 Aceta!
AJuminium U«i2'i S c c k ^ i iifead c a p s c r c w •i Stamless steel A 2
fixfcef '«.3Ci C.1 S t a nidSB a clip 1 Spring steel
Nilfilo 46 Waeher-smaii soaring 2 . Nylon
} Position ifidiC^tor 1 •icet 3'-yei!ow 46 Bsarlng needle roller 1 -

P^l . ' M l iMdit-aiC : Po.ycarOonaio-bivOl: 47 Sv/iich riiounting ptato I Steel


ACa'/iiC .nssf: AS Terminal block 1 Bakt^ito
_J ^ ' ' c a ; v i.'. '.cnvu s S c r e w pan head 2 Stool
i • w rg ^
Nrtnie 50 Spacer 2 r.Vlon
»-'r<n h c i f cci'-.. 2 Spfing £te«y 51 l.'icrosw)tofi-V9 o r V 3 ? .
0 1 Steel 52 S c t w pan noad 2 Steol
• •• (.'• tir.'.o • Stainless stec^ A2 53 O-ring 1 Niirik>
t S t a oJass s ' M i A ? 54 1 Steel
1 M, • iPMr £5 C'rcfp 1 Spring stee!
iIiZ-APR-2i3G3 Ff^OM TYCO UhL'JES TO 0197S7823>}3 P. 0 2

tsjita
fkhv CcnUo/

A pneumatic positioner with the unique option of


K B ^ N E either proximity or electric integral limitswitches.
The positioner, in line with other of the Keystone
accessories, Is suitable for direct mounting to the
range of pneumatic actuators.

Fealur23
• CoTipact • i r i o j n ' e j dir^scily ar>d
rjfaiiy to ;r'0 fictjotor s t e r r . y / m o s r i s o !
siandsrcl W
• Cioctkvvise Of counicr-c'oc^,^'!^© m o d e l s .
• Mu sil vu^.'.efSDle p a r t s
ccairi.'eteiv^rtciy-dd.
Wighij. visual "Qcai .ndtcatior, o? a c t u a t o r
Dosiion
• Slcibli! p^sitionirig cKu'w^ciei'Stie-i aio
p'jvicie;! lor b o i l i btnaii unci lirgt?
actuslcrs
• OooO v!^r^t;on r e s i s ' s n t c f i a i o c ' e ' . s i i c s
• A c t i o n (airect o ' lO/erue) is easily
t6"6r;'.acf ill tl^tt t-olo Oy ttr'i-'ig c a m a ; i d
'•ever^Hno ai; c o i ' ' i ? c t i o n .
• roac:>i:'t .ndir, ud 2 lobe can.
• Costor^sfid CJH-I proJiimg 13 posa'bid 10
gTve specify ch;>rHctei1satiOfi.
• Soanancizerowcij'-Gtwii
• U'sntle for dcub'O'Ocvng c single-acting
CO
• Ufte^'ictoc norm?; pressure
IluClL. i5,or>s

General application
The Ky/srone positioner is designed I'or 5ne
proportional operation of 1/^ turn rotary
actuators, it is generally coupled a/iaily 10
the shaft of the actuator, the indlcafor gives
visual position of Ih© final control e'emeni
Tj^e action is based on a tofca balance
principle.
I^J
I
r-ci'i danijiiny A.t't'^.lri. t > rr Ov' iii^^fOxiTot^-'j 1 S 'i.rr • •
V.
^
TD
O p r t a t e t n e f-oMioncrJeOuAto' (o l^c C i O S f
il i i
A'^'.Al trh3 C L O S E 3!3juili>.g !>}• t'jir-.flg o docr.rrtVs Ihe ' a v « f t d P i ^usj 0{>,i'<*s:-.'fi' V-HIJI-/"
'-•J
i.
O&erJlct:.;- { ^ i v t i o n e r i n M e cjKLr. p r - M f o s
c

AJjUSl adjusting s ^ ' c w t:> il Riiti r.^orKwiSt ur.ui f i c i;cper c?ni ji?". c p e r ^ ' i - i :rit". u p f T '

Mf.r.U-n Dulfi darrtpiiq fiCie/.-s ' o l o r i 'J-o- ''^ini'; m it'O i-'.'! oosili'/n

S ^ c f i l e i h c (xj^rtioni-'/JC'uaiOt biitrs 0''Cf-J.nd C r 0 3 E D rhtitVim) siic ( n i n i'i>^-rt-.5ior.. ^n-J tc-3Cj"ic5t if


n-: f i s i a r v

MICPOSW^'O^./Ttl^MlKAL PLAIE

P
fn

ADJUSTING ^-CLAMPING SCFfCAa

S E C T i Q .NjAt P L A N V I Vv'

Relr<»lii p r o c e d u r e

1. Re/fjcrvH pasiJitxier ooi.>et.


2 R'»rr»,)«e circlijj from top nr carnshsrt
ijj
3. RcfTrovti i p a c e i i'ra'ii camsf^au. <1
4. Fit a>3Dnit)ty on-o h e « i j y i n cams^citt v^iy-i rdjustir.5 tcie^'?, to.vDtiJs »ic- o u t o o j r d erid. CD
-0
r-fDte:- The assorriaiy n a s t^ccn marJe wi'Ji a i > h i t.i o n i o itic sr>3ft if) c<der to •olitn.nuto CC«
any tVicWiis'i. II rnaj' be nc<0?Aarj' to ilrr^j irj«» ir.vr tha s U ' i l t . l o ito ttiis. a v i ttic u'igiii«! s p o t ' ; ro
u
a s a <lnft a n o Qti-.v^ u i e a s s o m M y o'-ef the s/'-aft i r j n ? . a iigrit r.an-.iTic-r. -t.
5 fit the micf0S'«vitcfV'ieffT>insl plate <is sfiflwn, 'j=cnf, ttio {'Am W 5 f^-xaa^jt; scckot c<ip scfC-»»-i. 01
6. Set tnc c a n .s in a c c o t d a n c c wttn tho iirocc-.iurc '
7. F « - n i m e co-Air.

Keystt^ne reserves the ri<^h( to <'hange prodiici designs' ynci.6j)ecir«caiion.s wit!u>ui n o i k c


Keystone/!"yc<' Va'ves A Conliof.s. M c i k l c w o c i d Roa«!, t»n,in!0}ne.
G L A S G O W G51 4f>LT.

Tel: t O M I ) S to 3 1 2 1 . ^ x . (0141} S10 4724. Kfih A u g . 1 9 9 8 (Rerv [ M ; ' "D

v
>—•
A hlgCa INTERNATIONAL LTD. COMPANY
Q
•^ticr-J

Sellirj' pxvccdurv .Q
I'J
t a = . g i » - r 7 i : 3 a n c T I L s^^r^cs a c t u a l u r i I
' XJ
w t e ;we-E.2t p - o H D H - a r . K l ffs; JV.tO'Y -r^ac; nr.. J . r- • - W - f c fo^ov.Tv'i Tsn
's-fiysni 0"-<.ct oru«.r. o . J t ' a t - c •if-w'^ayj-ij ^^anal Cjie." iijciiijfoo. ••''ou'^ 3»ai ti-i^ ?c!:iCi':if li. jfi Ci.l>SrC 1

I J. » rttro) p c . i ' O ' i flr.c tP iJ I K * t ' ^ ; ;ri ;o;;Ot t'.t f>3VWi'>rf ..^art a e at a t'> tTK I'-x'^q fucfr.^; ra fxj

cofrt-:!'- (nc-j-.'acJ lotn^ sct.istor cyv^ rania..-,-. vxn.^xf


Q

» - '-1 a r w i-ocjcavinc sigtiatto U.iS'S acina'of). -snsu o V'^tt'^a ac^ualf* ss in tts O P E N {'«iiiy e.
C'.'-Tv-^ tr!<it uw- 'f-^rs on tcpc-5 it'spiXai'^fi-t jJjfi': ca» ^'"iS'o iMe ioi"^i:u.t.r»3i a*is r.i v - c fjosiiunr?
?
Aw-V ^ o< 3i.,arr),ima{i;!y 0 and g t a c l i i a l i y f r j i j irfK. I ' t n r a«-;y3t-jr|ktst i,--!' f ) c o
p3':i!icrt a i l ^ e S-gnaf •couc.''r.to J psig, tvo an;u55rnit»R is rio'.-e^s-t'Y " "
• t'-c k ' O f M» f-aitiyitci e c f i f o f i i r c « u-ry «it st»tt>«!iUk: loric}fUi;liti<'jl cf I'l--
hj tr, tno ocruatwi f.y'iric5.if
3- ID
t f o sctuhK/.' l o e i . not Cioee ^ij^y at 3 r-SHj. jurr. tf'e f-2vu'>vr> .-c-i^ ^idJlli,^^>•} niif h'--. o; 2 -tT,. ir<r.c>'..v.s'i a.n? ifc^ O
» r.-^vi'^ tr,o. ItT ». caru n^ tin- ;j-i:-,:ii:r;ci is r-o'ff';;iy v<.t.T {r\3<ri>frfi-t OfjR'e bearing asa-nst trvi • Con:tr.yi.» l i o y z e i o ' s o - ' c c i - v ccJi-t-v'js. " ' ;z

i ^ i f i c v j - : . i - i c M C C K - v t tO£'Jlt 0 illd fl'rect action;


—i
if I'le odiialof roacng.-ittic CLCXStT- ocsn-co l i e ^ c e tii- h'cphl r.,-}uces to ? r^ic; tu/;. u t J-o^sgc': -.-to n,-t i r >
i ' l i • I r o c ? t v C ' f i e f - . o ' l * - ' t i a t a i i i i - c i D ' - ' . - v i s P l O f n J t o r i of U ' t i i . c ' = ' i i c j n e r s n a f ' v . i ; : c a u s e t - i R r a m t oc r - m p r c s s i "i^; sp'inci u- • turn ar,tj<ir<kvr<30 ancf slep < C c n t i n c c u m i . r c o is cdffectly rfsMievect '

r " ( j ' i ' . ' j t fi' !. i - n i -rtnt f o i a i i w o l j A i r r t i o n r r r , h a < t \ > ti c . ' u . s e t h e c a m i n r o f r : p » - e s s t n c spring
G.-adi-?Jiy inaeas-a m e sgi^ai to \ 5 ufaig It the actuatw U-'-.t fc<yJies M-j O P l ' n po-jnion a.s tno r(v -ft« c-'^o
4 Uicn no sflinsimfifit IS nccessafy. m
PIP air P'D.'ts O^'J-'TI ID f i y 1 (of difCCl aciion 3NCL I u;.!': Ic-t U'i
o.
't tlw; a c f j a l w (10G2 f>'j: iu-i O F f c N jKrSffian at 15 ps-g. Jnfi. is .ndiv.ti.e Ci tr-e .sprinq (z:^ being ( O l s r r * the
ut nftiiiscfcvv .n ranueatJjL'sJmcnt collar, (se?. r-»n.3). u.mt/»e <v,ttaf n a n o n s r y nsLng a ii.;y?.go» w / c n r n a n i j-irri
tne icr.nQ <:i.oMUy Ttjis v.iii i«>ovf tfi-i iK-j-aixt even h/rtt.er a^/ay iio'n M i y O P E r : ^jod m c ^^u, :ia.ustr,ci sc.cw

V - - ^ •
\ \f must Oi.'uiwdto achieve Of'^ N- '

7.
X^yQp I Cofivecsely. it ^fw b c v m fesi.UQ-:} i W ^ K p o s i S o n tnAor^ 15 psig. tirtn U m spong r.Kgnoy ant.-cJockwsc wrtn .c^pect to
--iri tn^ jatr. a<l|i«j,tin^ coOar. Again lo-oajust trie zero ^-ck-.v to achieve exact M l y O P E N

W ) € oxo"! •- H ^ r r ;
An, Q j u •\r>> a n d rar.yR sottmui ar« incjh'y lofrracta^e ana s e a s 2 to 7 must h e r ^ c a t e d until z-yrc a r d i p a n ar.>

NOTt:
In ' A e K ^ \o 7. clocfrv*(Sd ai<J aor, cjcc'^/n j .-otaftons are a z v:e» M Iroro t^ft ;.i;;u5tif>3 lu.t y n n ol tn.- r;f)'ir>3. i_i

G'
1 - , Direoy O . p e r a t i o n Hejujcjoriai s o c « t t—
"jj
'Zero actios -a
CO
-0
OD
Teertoaci: c a m ro
u
, G a i o screw
'.•J

t t
O^J'p

((^M
\ (
OxOr—
A O . . Q i l
Ji - . - . 4
rr - 7
t :
Rantje adjiisirtient collar
o
-.1
^ H e . lock ciut
FIG 2 • Resettle Ooerajfon
i m3.
VViriou dia^i
Switc)i<nGl5 icAh]
yJcro-sv/itch detairs

SldOtiaril V 9 type, iJiigle pote dou&la ihrow ( S P D T ) .


S<<>niCA ratings a s iahie bclovc

W i r i n g d i a g r a m for R o l a r y P n e u m a t i c P o s i t i o n e r with 2 m i c r e - s w i t c h e s
VOLTAGH RESISTlVe TUNGSIEN LAMP LOAD INDUCTIVE
LOAD (Amps) LOAD
tVolls) (Amps) NC NO (Amps)

T AC BLUF
f"!
fO
m '.25 2 1- ID
'X' 250 'lO 1.5 1 10 DOTTOM SV.'irCH i:ClOSF)
a-

DC
TOP SWI»Cn lOrF.M)

Up to 15 {5 3 5 ts
30 to 3 1.5 10
50 3 , OS 0.8 2.5
75 1 0.6 0.6 0.5
125 0.5 05 0.5 0 07
2b0 0 25 0 25 0 25 0.03

Proxinjity switch dCf'T'l^"

T,t>r.. Peppfjrt A Furti? NJi'-vi-iN or a s spec.fieci


QuJttrt/ 2 iv.licncs per yrsit
U< S f ) . ' m j ijiSJ.incc: irnni tuan^^um (inetfll trjcni NO, f>e|)sr^tlo a^npiifiuf required W i j i o g d i a g r a / n for R o l n r y P n e u m a t i c P o s i t i o n e r w i t h 2 P<-oximirv s w i t c h e s .
LLI
SbCpIy 5 V D C (Pi approx. 1 V.OHm)
•^•')rpt;fa"'j'e ruev.t:- . 2 6 ' C to ' V O ' C
RtT'ttifioR' <0 Olmtit
Hyste'Cf'S cO.OoJTtm Ty->3'1
Scnsnc 3b5eri - or a c c v e
Cfcos-jr ;;it.'scn; • iinA or
Switdiiny isn: • l-^Hz "i.ijrirr«nn.

Swrtcj-iffitirication
S^JTTOM S'MTCH tCLOSt:)

TOP sv/iTCrt

I SWiTr.H sv;n"CHFurjCTJON
! NUMBER

CLOSL LfMJr

O P r N LIM'T
bnitdl d^^-
!VJ

"0
fnpui siflna "J
^"^'^irit'.*^® - ihe p o - i H r r . f j -tvAmum s . j n a ' C L O S S C ' c c r f c t ocwrjro-. -e--' -
i r C O P t N V f f j v c f & e y p e f a t i o n ($oe ' ' carp c.•w^^ct^;n3t•c^ ftn.^'

curve niiK-: r^. _ .-n-


_ __ .. ^ ^^...i,.. .,(««• iiic iiia/ii c^.vd'
ojr.-v; 2. t a o g c 3 9 1 i .v - , ; ,.v 61. "
2. movoi/iom
t.i.»fv« 3.'arKje. 3 t&psi ti;* •/i
".-Ti
f ^pft -ca>rr- tcxuf^ r,c«y scjov/ ,r. e ^ C i CC'RU-
Sjpply
.iOfripitvccn .iif o- itiy. ou^t a n c ^.n
f 'hp f04?jonjt»ai-^t5rf5 trw J c u W e ' D ' a t ttic:->p'>- f ' e ; »>3fL li M i c y i i '-i^r ctemefij tc -filei
i j p p i v Cri.5Sur« Sfi - 10U jn- "I;-'? ? a ba- -lO b.->; max
0 ij cffn tn tifil.-jficir.! c.ridi'iu' v/-;t/i iCt p-.i f i triC.
? P C V I on t a w f o ^ c v 'c t - e r o i r t . o n e r c o v r ir.e zero U s g ' & e marijr^r. are d . s w - s w ^ ' c n g U ' e Jf^^r.vgrse
nf c.e r^r^ion-. B..,ore tP.c .r.<icatcf co-.-er, e n s u . - t..at i h c co.er s o Ctai tf.8
a " v / / ' r j . c a t e s tna -^.j u : oogfcc". sctunior. - i ' i-'ui un-
En VI foortK: Ml ;i!
<• '""lu •»: UC ' r ( ? c *tO -< ' . T i , ) .
nouf^fing a n d
a j (eijU'rei). N o fijiiiiHiicr*,
corneclfous fr.OniiL'f^ krt ufMvsfsai mnunCr.o htt i-.-i h.y.700.'.''yf> c i n p s C
nctuaio.'f.. x>
{iir r^'ififit'CTkjns ^iupfiy ar>o Oirtput M T stCf-'al 1/e' »3S»'.
•/ f V VijurHa!- m
e re !nfi }>«3«J icOteJ »citf-a mtxrur.j kjt tyic^
I f»0(>miur,' »••»•« hwo^lrjji^urifl ccmfewxa « M a : c i ' £ i s or nousmg entfji&sa aiumifiiL.-n a=Jo>' (.ilaiu'es:; ste.-: optlood!
t tTu sccfcct coiisln.fiticn (fiaprtr&fltii nrtnfo iijticc/
1 iffBw kt Kiu 0 a^ficajkin. rti> t' >.aivc s^jci"* sraiftieis
<QVCf isficvjisPfT aiu'rii;..um .ii'oy isiainiwss stf.-u rfU'Oo:,!;

Wcignl
- b (l.aiKgi

Oplfons gitii^s inb«rufji^i« a-f 0 - 3(j psi {O 2 y a r j - i o;r


o u t V l y a ' r O l a C o a n ' C • 8 t>ir) - Putt,
•njr-jfHi Ismn sv.ri;tics siiKltep-jrcOaiiDlsthfc-w f>t>y V 3 . l U A P ^ O V A C
afo*(ftiir,r s r i i s r i a f'«;fnef( jv F u c h s i-.vJ f'-iv-vn-r.

FIG 4 - nirppf O o e r a l j Q n
-0
GO
-0
CO
f.J
Ji
CJ

il.

\ j P-. .y.
©
1 \ I

tM^e*
FfG.5 ' Reverse Opcna^iort
16
BLSaOA
PRESS-AIR L
Pneumatic Pre-ssure Transmitter 1 9 7 7 - 1 1 - 0 1

OPERATING AND INSTALLATION INSTRUCTIONS

>•»'•_ - • '--i _ •- > 4 -

PRESS-AIR L 80

CONTENTS

1 APPLICATION
2 TECHNICAL SPECIFICATION

3 PRINCIPLE OF OPERATION
^ INSTALLATION
5 AND'JUSTMENT
6 MAINTENANCE

V A L M E T O y . I N S T R U M E N T W O R K S . ^ ^ f ^ l - ^ i l V S i ^s'S's^^M^^
1. APPLICATION •—

^ b PRESS-AIR L flange type pressure The transmitter converts the pressure


a c t i n g on i t s measuring diaphragm
3
transmitter is used for level -
measurements in open vessels. i n t o a pneumatic standard signal of
Equipped with an a u x i l i a r y flange the 0.2 to 1.0 bar or 3 to 15 p s i :
transmitter can be used for measuring
also other types of small pressures.

2. TECHNICAL SPECIFICATION

Measuring ranges:
0 -»• 0.2 to 2.5 bar
t ESS-AIR L UQ 0 AO to 600 mbar
Max. e l e v a t i o n = max. range
3
ESS-AIR L 80 •- • •
minus span
Range e l e v a t i o n
0.2 to 1.0 bar or 3 to 15 psi
Output signal
bar or 20 psi
Supply pressure
Max. operating temperature
+60
- ambient
-•process f l u i d + 100 c
Output a i r capacity
- v/ith i n j e c t o r r e s t r i c t i o n k 1 i t r e s / m i n (at STP)
- with pressure a m p l i f i e r 25 l i t r e s / m i n (at STP)

Steady-state a i r consumption
- with i n j e c t o r r e s t r i c t i o n 5 1itres/min (at STP)
- with pressure a m p l i f i e r 7 Utres/min (at STP)

curacy (without elevation spring)


#-
nominal error
non-1inear i ty
1.0 %
±0.5 %
3
- hysteresis 0.5 %
- dead band -- -- - 0.1 ^
E f f e c t of ambient temperature change
on zero
- minimum range 0 . 1 ^ A

- maximum range 0.02 %rc


Effect of 0.1 bar change in supply
pressure on zero 1.0 %
Materials
- flange and diaphragm A c i d - r e s i s t a n t steel AISI 316
- transmitter section Light a l l o y , steel and brass
- case Cast l i g h t a l l o y , epoxy.powder painted

Oimens ions
See f i g . 2 "Dimensions"
Connect ions
^ ^ p r o c e s s
DIN flange NS80 NPIO
^ ^ s i gna 1 tubes

We i g h t NPSF female thread, A supply, 0.output J

7 . 6 kg
-c

1/4-18 NPSF
^^ J
112
220
Figure 2 - Dimensions

PRINCIPLE OF OPERATION ( F i g . .3)

9 0

Figure 3 " P r i n c i p l e of operation

The transmitter operates on the force r e s t r i c t i o n 12. Nozzle pressure is


balance p r i n c i p l e . amplified in the i n j e c t o r r e s t r i c t i o n
The measuring element consists of an . and taken to output connection 10
o i l - f i l l e d twin-diaphragm c e l l ( 9 ) . and feedback bellows A.
A pressure acting on the diaphragm Output pressure Increases u n t i l the
generates a force which acts on the force of the feedback bellows
lower end of feedback lever 7 through overcomes, the force of the diaphragm
rod 8. Adjustment bearing 5 serves cell. Also zero a d j u s t i n g spring 3
as the fulcrum of the feedback lever. and range e l e v a t i o n spring 6 a f f e c t
Feedback bellows k acts on the upper the reaching of a state of e q u i l i b r i u m
end of the lever.
Measuring range span can be changed
As the pressure to be measured
Increases, flapper 2 approaches noz- by a d j u s t i n g lever r a t i o : \2'
21 e 1, caus i ng the nozzle pressure to It is possible to use a pressure
increase. Supply pressure 11 is a m p l i f i e r in place of the I n j e c t o r
taken "to the nozzle through i n j e c t o r restriction.
k. INSTALLATION

The transmitter flange is fixed on Range e l e v a t i o n device


3
the side of a vessel or pipe. Standard
adjustment has been carried out with If the zero level in the vessel d i f f e r s
the transmitter In v e r t i c a l p o s i t i o n . from the level of the measuring
Therefore, I f the transmitter Is diaphragm ( f i g . . the h y d r o s t a t i c '
mounted in some other p o s i t i o n , a pressure between the two l e v e l s must
checking adjustment should be c a r r i e d be overcome by means of a range
out in the operating p o s i t i o n . e l e v a t i o n device.
The transmitter flange is attached to If the t r a n s m i t t e r is not equipped
an NS80 NPIO counter-flange, for with a range e l e v a t i o n device when
example DIN 2633 welded flange or DIN d e l i v e r e d , the device Is easy to I n s t a l l
26^3 c o l l a r flange. l a t e r in the f o l l o w i n g manner ( f i g . 5 ) :
Mount the e l e v a t i o n device In p o s i t i o n
Dimensions o f the sealing ring between in such a manner that the end of
the flanges are }kO mm/^ 86 mm. spring 16 Is Inserted Into hole 15 In
Four MI6 or 5 / 8 " bolts are required part 13. Secure the device with
for mounting the transmitter. screws I 7 . Remove plug 2k ( f i g . 7)
at the bottom o f the pneumatic
l ^ r connecting the signal tubes the
section o f the u n i t , and t i g h t e n the 3
bottom of the unit is provided with
spring In p o s i t i o n with screw
NPSF female threads that accept
through the plug hole.
connectors equipped with, for example,
NPT thread. Designations:
A supply, 0 output.

Figure - H = Span
0 = Range zero level
S = Range e l e v a t i o n

Figure 5 !
5. ADJUSTMENT

Before d e l i v e r y , the transmitter is 5. Fasten rod 8 by t i g h t e n i n g the


e i t h e r provided with basic adjustment screws in part I3. Set the output
or adjusted f o r - t h e desired range as pressure to 0.2 bar or 3 psi by means
speci fied In the order. o f the zero a d j u s t i n g screw.
I f the transmitter has been disassembled
f o r , for example, maintenance purposes,
adjustment is carried out s t a r t i n g
from section A. When checking the
range adjustment or when a d j u s t i n g the B. Pressure test
u n i t for a new range, s t a r t from section C.
With adjustment bearing 5 in Its
The adjustment requires two pressure
lowest p o s i t i o n , i.e." at maximum range,
reducers and two manometers ( f i g . 6a)
apply an overload pressure to the
or a VALMET AIR-TEST t e s t i n g u n i t ( f i g . 6b)
' d I aphragm ce.l I :
An NS80 b l i n d flange, which has a PRESS-AIR L i)0: 6.0 bar
connector for a pressure tube, Is PRESS-AIR L 80: 1 . 5 bar
fastened with sealing against the
diaphragm c e l l of the t r a n s m i t t e r . These pressures correspond to
After tightening the r e t a i n i n g b o l t s approximately 2 . 5 - f o l d overloads.
between the flanges, check the Reduce the pressure to zero and raise
tightness of screws 26. i t back to f u l l value. Repeat t h i s a
(S few times. If the output pressure
A. Basic adjustment deviates from 0.2 bar or 3 psi while
diaphragm pressure is at zero, r e c t i f y
1. Remove plug 2A. Loosen the two the error by means of the zero
r e t a i n i n g screws of part 13 through a d j u s t i n g screw.
the plug hole In such a manner that A f t e r t h i s , apply a few more
rod 8 Is able to move f r e e l y . overpressure impulses to the diaphragm
2. Loosen locking screw 21, and move cell. I f the output pressure s t i l l
adjustment bearing 5 with the a d j u s t i n g ' changes by more than 0.02 bar or 0.3
screw to the max. range In accordance p s i , the diaphragm c e l l should be
with the approximate value scale. replaced. The error may be caused
Tighten screw 21. a l s o by a f a u l t In the i n j e c t o r ,
3. Adjust feedback lever 7 and cover r e s t r i c t i o n or pressure a m p l i f i e r .
plate 20 p a r a l l e l with each other by
placing a 6 . 0 mm thick piece of metal
between the upper part o f the cover
plate and the feedback lever. Press
the feedback lever against the C. Measuring range adjustment
adjustment bearing and the piece of
(f metal, and adjust flapper a d j u s t i n g
Without range e l e v a t i o n spring:
screw 18 for 0.2 bar or 3 psi output
pressure. Do not turn a d j u s t i n g 1. Loosen locking screw 21, and move
screw 18 a f t e r t h i s . adjustment bearing 5 with a d j u s t i n g
k. Remove the piece of metal mentioned screw 19 to the desired measuring
above, and adjust zero a d j u s t i n g screw range in accordance with the approximate
25 for 0.2 bar or 3 psi output pressure. value scale. Tighten screw 21.

. V

7 6 fe«r
O
I-
-t-H t-

ri |U>t* I

figure 6a Figure 6b
3

Fi gure

With range e l e v a t i o n spring:


T, With diaphragm pressure at zero, 1. Loosen locking screw 21, and move
3
adjust zero a d j u s t i n g screw 25 for 0.2 adjustment bearing 5 with a d j u s t i n g
bar or 3 psi output pressure. I f the screw 19 to the desired range In
adjustment, of the zero a d j u s t i n g screw accordance with the approximate value
is not s u f f i c i e n t , a l t e r the f a s t e n i n g scale. Tighten screw 21.
of rod 8: loosen the r e t a i n i n g screv/s 2. Adjust the diaphragm pressure to
of part 13 and adjust the zero value S ( f i g . A) corresponding to the
a d j u s t i n g screw for 0.2 bar or 3 psI zero p o i n t o f the range. Adjust screw
output pressure. Then tighten the 22 in the e l e v a t i o n device for 0.2 bar
r e t a i n i n g screws of part 13. or 3 psi output pressure.
3. Adjust the diaphragm c e l l pressure
3. Increase the diaphragm pressure by
to correspond to the upper-range value
the amount of pressure H ( f i g . k)
of the desired measuring range".
corresponding to range span. Total
Move adjustment bearing 5 u n t i l the pressure is thus S + H. Move '
output pressure is 1.0 bar or 15 p s i . adjustment bearing 5 u n t i l the output
5. Adjustments 2 and k affect each pressure Is 1.0 bar or 15 p s i .
other. For t h i s reason they must be
Adjustments 2 and 3 a f f e c t each
^ D e a t e d u n t i l the desired accuracy
other. For this reason they must be
^ftreached.
repeated u n t i l the desired accuracy
Is reached. In the f i n a l stage the 3
adjustment In step 2 Is carried out
by means of zero a d j u s t i n g screw 25.
6. MAINTENANCE

Servicing should be carried out at The body of the i n j e c t o r r e s t r i c t i o n


regular i n t e r v a l s . Air ducts are consists of a metal block. The actual
washed with benzine and 0 rings are r e s t r i c t i o n Is located at the bottom
checked. Dried or damaged seals are o f t h i s body s e c t i o n , which has to be
replaced. Before reassembly the 0 removed to be able to clean the
rings are lubricated l i g h t l y with restriction. Draw out the r e s t r i c t i o n
s i l i c o n e grease to ensure t i g h t n e s s . by means ofl an M3 screw. Remove any
Make sure that the nozzle t i p is p i t c h formations with benzine. After
undamaged and s t r a i g h t , and that the c l e a n i n g , l u b r i c a t e the 0 rings
flapper surface is smooth. If there l i g h t l y w i t h s i l i c o n e grease, Insert
are any p i t c h - l i k e formations on the the r e s t r i c t i o n in p o s i t i o n , and
f l a p p e r , remove them with benzine. fasten the body s e c t i o n ,
The nozzle t i p can be straightened in A 1.2 mm nozzle is used with i n j e c t o r
the following manner: Place a piece restriction. I f the r e s t r i c t i o n is
of fine-grade water sanding paper replaced with a pressure a m p l i f i e r ,
( e . g . no. C ^00) between the nozzle the nozzle must be changed for a 0.5 mm
and the flapper. Press the flapper one. After changing the nozzle i t is
l i g h t l y towards the nozzle and withdraw necessary to check the adjustment.
the sanding paper. If t h i s has no
e f f e c t , the parts in question should
Maintenance and checking of operation
a be replaced. The flapper can be
removed by undoing the two r e t a i n i n g
of the pressure a m p l i f i e r are described
in i n s t r u c t i o n l e a f l e t G4l0 A.
screws at i t s lower edge. Unscrew
the nozzle with a 6 mm wrench.

Replacing the"diaphragm c e l l (fig. 8)


Figure 8
Procedure:

1. Loosen the two r e t a i n i n g screv;s of


part 5.
2. Undo screws 1.
3 - Remove the diaphragm c e l l r e t a i n i n g 5. Reassemble the u n i t In reverse
r i n g 2 and withdraw the diaphragm c e l l order. To ensure t i g h t n e s s , replace
w i t h Its connecting rod PTFE seal 3 with a new one.
4 . Unscrew the rod from the diaphragm 6. Check the adjustment and r e - f a s t e n
ce I I . part 5 f t n a l l y .
3

3
17
Series 240
Pneumatic Control Volves lype 241-1 and lype 241-7
Globe Valve Type 241 with Micro-trim Element

Fig. 2 • Type 241 -7 Control Valve

1. Design and principle of operation


The T ) ^ 241-1 and Type 241-7 Pneumatic Because of their modular-assembly design, the
Control Valves eoch consist of a single-seated actuators con be exchanged, and the standard
Type 241 Globe Valve and either a lype 271 version can be retrofitted to a version with either
or Type 3277 Pneumotic Actuator (second for on extension bonnet (insulating section} or bel-
integrol positioner attochment). lows seol bonnet (metd bellows seol).

Edition Febfuory 1996 Mounting and operating instructions

EB 8 0 1 5 / 8 0 1 8 E
The process mediumflows through the vafve in valve whenever pressure on the diaphragm is
the direction indicated by the arrow. In this pro- reduced or the oir supply foils. There ore tv/o
cess, the closure member, volve plug (3), is od- fail-safe actions:
jusled in response to sigr>al pressure changes - Actuator stem "extends"
(bench range) ocring on the diaphrogm of the - Actuotor stem "retrocts"
actuator. The valve plug (3) ond attach«j octua- Depending on the valve action, the valve
tor stem (8.1) are connected via the stem con- opens {flow-to-open) or closes (flow-to-
nector (7) and sealed by meons of o spring- cbse), resp, as increasing signal pressure
boded PTFE V-ring pocking (4.2). overcomes the force exerted by the springs.
Depending on how the compression ^rings
For tfie valve version hoving a micro-trim ele-
ore arranged In ^ e actuator (top or bottom,
ment, this element is.installed in the valve body
resp.), the spring force opens or closes the
insteod of the usual seat/plug combination.

^ Type 271 Pneumatic Actuator

Fig. 3.1 •Type24M Control Valve Fig. 3.2 • Micro-trim element


15 Pfugstem
Id \^lveplug
17 Seotbody
18 Spring
19 Sertnut
S ^ Type 3277 Pneumatic Actuotor

Fig. 3.3 • Type 241 -7 Control Valve

). N^lvebody
1.1 bonnet nuts
2 S^lvessat
3 NAilveplug
4.1 Packing spring
4.2 Stuffing box pocking
5 Malve t«nnet
5.1 Guide bushing
5.2 Tt^reoded bushing
5.3 Travel indicator
6 Plug stem
6.1 Coupling nut
6.2 Locknut
6.3 Yoke (sizes ON 200 ond 250)
7 ^e«n connector (coupling}
8 Pneumatk octuotor
8.1 Actuator stem
8.2 Annubr (clamping) nut (or octuotor

Fig. 3.4 • Control Volve, sizes ON 200 and 250


1.1 Exchanging tfie actuators 2. Assembling/disassembling the valve and
Instead of the standard octuotor version, a octuator; adjustments (Pig. 3)
model with an additional handwheel con be If the valve and actuator have not been pre-
mounted to the valve. In addition, electrically assembled at the Victory or if a different (or
operated actuators can be attached as well. larger) version is to be used instead of the
Pneumatic actuator models exhibiting differ- original model, proceed as instructed below:
ent sizes can be used in place of the standard NOTE
pneumatic actuator (with or vtnthout hand- When disassembling actuotor version "Actu-
wheel drive). ator stem extends" and, in particular, using a
If the travel range of the actuator is larger version with pre-loaded actuator springs, al-
than thot of the valve, the octuotor spring os- v ^ s opply pressure to the bottom loading
sembly will be pre-loaded ex-foctory, ^sur- pressure connection before disassembling
ing that the travels correlate as they should. the actuator!
Loosen both the locknut (6.2) and the coup-
ling nut (6.1) on the valve. Press the valve
plug with the attached plug stem firmly in the
seat ring. Then, turn down both the coupling
and the locknut.
Remove the clamps of the stem connector (7)
and the annular nut (8.2) on the actuator (8).
Slide the annular nut over the plug stem.
Place the actuator on the valve bonnet (5),
and thread tight using the annular nut (8.2).
On the actuator's nameplate, read both the
bench range (or pre-loaded range) and the
actuator action (e.g., 0.2 to 1 bar and "Actu-
ator stem extends").
The lower value of the signal range corre-
sponds to the lower-range value (start) to be
adjusted. The upper value corresponds to the
upper-range value (end) to be adjusted.
Version: Actuator stem "extends
Apply the loading pressure which corre-
sponds to the lower-range value (e.g.,
0.2 bar) to the bottom diaphragm chamber.
Version: Actuator stem "retrods":
Apply the loading pressure v^ich corre-
sponds to the upper-range value (e.g., 1 bar)
to the top diaphragm chamber.
Manually turn the coupling nut (6.1) until it
contacts the actuator stem (8.1). Then, turn a
quarter revolution further, and retain the po-
sition using the locknut (6.2).
Attach the stem connector clamps (7), and
tightly screw together. Align the travel indica-
tor scale (5.3) in line with the coupling tip.
2.1 Pre-loading the springs for actuotor ac- 3. Installation
tion: Actuator stem "extends" 3.1 Mounting position
in order to obtain Increased thrusts for these There Is no prescribed n^ounting position.
actuators, up to 25 % (octuotor effective Hov/ever, for valves sizes DN 100 or above,
areas 80 to 240 cm^ - 12.5 %) of their travel install the actuator vertically upright in order
or signal pressure ^ n con be pre-iooded tofacilitate ony maintenance required.
when adjusting the actuator springs. Always install tfte valve free of stress! If
If a pre-tension of, for example, 12.5 % is necessary, support piping near the process
desired for a signal range between 0.2 and connections. Never attach the braces to the
1 bar, the signal ronge is shifted upward valve or actuator!
0.1 bar from 0.3 to 1.1 bar (here, 0.1 bar
Thoroughly flush the pipe prior to installing
corresponds to 12.5 %]. theval^.
In the adjustment procedure of the vatve, the
lower-range value is now to be adjusted to
3.2 Loading pressure connection
0.3 bar as required.
For actuator action "Actuotor stem extends',
Always mark tfie new signal range from 0.3
connect the loading pressure to the bottom
to 1.1 bar as the pre-loaded signal range on
diaphragm case. For actuotor action "Actua-
tf>e nomeplate!
tor stem retracts", connect It to the top cose.
NOTE: For Type 3277 Linear Actuator (far in-
2.2 F^e-loaded octuator springs e x - f o d o r y tegral positioner attachment), the bottom
An adhesive label identifies actuators which looding pressure connection is locot^ lot-
have been pre-loaded (without the attached erolly on the yoke v^lch is ottached to the
valve) by the manufacturer. Moreover, such a bottom diaphragm case.
case can easily be seen by three extended
bolts and nuts (Fig. 5) on the bottom dia-
3.3 Strainer, bypass line
phragm case. These bolts and nuts allow the
pre-tensioned actuator springs to be uni- We recommend that a SAMSON strainer
formly released, in a criss-cross pattern, (Strainer Type 2) be installed upstream of the
when disassembling the actuator. voh^body.
lb enable moint^ance without disrupting
operation, good practice calls far o shut-off
valve to be installed both upstream of the
strainer and dov/nstream of the valve. In ad-
dition, a bypass line is recommended.

3.4 Bellows test connection (Fig. 8}


For tf)e bellows seal version, o test (inspec-
tion) connection (G 1/8) is located at the top
flange, used to inspect and monitor the effec-
tiveness of the bellows sealing. We recom-
n^end especially for liquids and steams that a
suitable leakage indicator (e.g., contact-
making pressure gouge, runoff in an open
tank or inspection gloss) be connected.
4. Operation (8.1). Bolt together both diaphragm coses
4.1 Reversing the actuator action (Figs. 4 ogoin.
and 5) For the Type 271 Pneumotic Actuotor, screw
the vent plug (9) out of the top diaphragm

A When disossembting the control


volve, first remove pressure from the
corresponding section of the plant.
cose (8.5) and into the bottom diophrogm
cose (8.6).
For the Type 3277 Pneumatic Actuator for in-
Recommendation: Drain the pipe,
and remove thevoke. tegrol positioner ottochment, screw the vent
If the octuator oction need be reversed, pro- plug (9) out of thetopdiaphragm case.
ceed as instructed beiow: The actuator springs, now pressing upward
Separate the actuator (8) from the valve. For against the diophragm, open the valve by
this purpose, perform the following for octua- way of the actuator stem (8.1) and the at-
tor action: Actuator stem "extends": First tached valve plug. The loading pressure is in-
apply a pressure which exceeds the lower- troduced to the top diaphrogm chamber via
range value to the octuator (see nomeplote). the top loading pressure connection (10). If
the signal pressure increases, it closes the
Loosen the coupling clamps connecting the
valve, overpowering theforce exerted by the
actuator stem ond the plug stem, and un-
actuator sprir»gs.
thread the annular nut 18.2). Lift the actuator
off the valve, Mount the actuator to the valve as instructed
in section 2.
4.1.1 Reversing the actuator action from Ac-
tuotor stem "extends" to "retracts" 4.1.2 Reversing the actuator action from Ac-
tuator stem "retracts" to "extends"
Unscrew the hexagonal bolts and nuts (8.10)
connecting both diophrogm cases, Unscrew the hexagonal nuts and bolts con-
lake special care with actuators whose necting both diaphrogm cases. Lift off the top
diaphrogm case.
springs hove been pre-loaded at the foc-
toryl (Distinguished by the extended bolts Pull the actuator stem (8.1), diaphragm plate
ond nuts on the bottom diophragm case.) (8.7) and diaphragm (8.4) out of the bottom
lb proceed, first untum the short bolts, then, diaphragm cose (8.6). Remove the actuator
slovi^y and uniformly and, in o criss-cross springs (8.3). Unthreod the upper nut (8.8),
pattern, loosen the long bolts and nuts until counter holding the other lower nut (8.9) and
the actuator springs are relieved of tension. not damaging the actuator stem.
Turn over the diaphragm plate along with the
Lift off the top diaphragm cose. diaphragm, and thread on the nut ogoin.
Remove the actuator springs (8.3). Pull the Push the octuator stem (8.1) through the bot-
actuator stem (8.1), diophrogm plate (8.7) tom diaphragm case (8.6), and install the oc-
and diaphragm (8.4) out of the bottom dia- tuator spring (8.3). Attach the top diaphragm
phrogm cose (8.6). Unthread the upper nut cose (8.5). Bolt together both diaphragm
(8.8), counter holding the other lower nut cases again. Unscrew the vent plug (9) and
(8.9) and not damaging the diaphragm stem. screw into the top diaphrogm cose (8.5)
Turn over tfie diophrogm plate olong with tf>e (Type 271 Linear Actuator). For the Type
diophrogm, and thread on the nut again. 3277 Pneunxjtic Actuator, screw a vent plug
Apply lubricant to the actuator stem (order in the top diaphragm cose.
no.: 8150-0043). Place the diaphragm plate The actuator springs, now pressing dov/n-
in the top diaphragm cose (8.5), install the word against the diophragm, cbse tf>e vaive
actuator springs (8.3), and slide the bottom by way of the actuator stem and the plug
diaphragm case (8.6) over the actuotor stem
r stem, Hie looding pressure is i n t r o d u ^ to
the bottom diaphragm cose via the bottom
looding pressure connection. If the signal
pressure increases, it opens the valve, over-
powering the force exerted by the actuator
springs. Mount octuator to the valve as in-
Further detolls regarding the pneumotic oc-
tuotor con be found in the follov^ng "Moun-
ting and operating instructions":
- EB 8310 E (Type 3271 Pneumatic Actua-
tor)
- EB 8311 E (Type 3277 Linear Actuator for
stmcted in section 2. integral positior>er attachment).

>

8.10

Fig. 4 Type 3271


Actuator stem "retracts A b a t o r stem "extends"

Extansion nuts
indicate pivtensioned springtl

8.1 Aduotorslem
8.2 Annulor {domping) nul
8.3 Actuator spring(s)
8.4 Oiophrogm
8.5 lop diaphragm cose
8.6 Bottom diaphrogm one
8.7 Diaphrogm plate
8.8 Lower nut
8.9 Upper nut
8.10 NutsandboHs
9 V^piug
10 Looding prasturs connecHon

Fig. 5 • Type 3277 Pneumatic Actuator


5. Faults and how to correct Remove the associated nuts (1.1,6.1 and 6.2).
If external leokoge occurs, the couse may be Remove the valve bonnet (5), and unscrew
contributoble to a faulty stuffing box or, as re- the threaded bushing (5.2). Press out
gards the bellows version, also a defective damaged stuffing box packing (4.2) using
metal bellows. the plug stem (6). Pull out the valve plug (3)
If the valve does not tightly seal, impervious olong with the plug stem (4). Remove the
shut-off can be impaired by dirt or other pocking wosher (4.3) and the pocking spring
fareign particles lodged between the valve (4.1), and clean the packing chamber.
seat and vatve plug {or by damaged sealing Apply lubricant to the individual ports of the
edges). new stuffing box packing and also to the plug
We recommend that the parts be disas- stem (order no.: 8150-0111).
sembled, thoroughly cleaned and, if neces- Insert the plug stem (6) olong with the ot-
sary, replaced. tached valve plug (3) In the valve bonnet (5).
Place the valve bonnet on the valve body (1)
When disassembling the control
A vake, first relieve the pressure from
the corresponding section of the
ogoln, and secure the bolts using the hexogo-
nol nuts (1.1) (note the tightening toque ac-
cording to the table). Install the pocking
f^nt end drain. Recommendation: spring (4.1) and the packing vi^sfier (4.3),
Remove the valve. and slide the new stuffing box packing (4.2)
carefully over the plug stem in tfie packing
5.1 Replacing the stuffing box packing for compartment. Screw in the threaded bushing
standard valve versions (5.2), and turn tight. Screw the bcknut (6.2)
If the valve leaks around the stuffing box, this and the coupling nut (6.1) onto the plug
is good indication thot the stuffing box pack- stem (6).
ing (4.2) need be replaced as instructed Mount tf>e actuotor to the volve and adjust the
below: lower or upper-range value as instructed in
Seporate the octuotor (8) from the valve. For section 2.
this purpose, perform the following for ver-
sion; Actuator stem "extends". First apply a 5.2 Replacing the valve seat and valve plug
pressure whicfi exceeds the lower-range
If tfie valve leaks, the reason preventing posi-
value to the actuator (see nameplote).
tive shut-off may be impurities or domoged
Disconnect the coupling clamps connecting
the actuator stem and the plug stem, and un- sealing edges,
thread tf)e annular nut (8.2). Lift the actuator In the first cose, thoroughly clean tfw as-
off the valve. sociated ports. In the second case, replace.

4 Stuffing box pocking


4.1 Packing spring
4.2 PTFEV-ring pocking
4.3 Pocking washer
5 Votval^net
5.2 Threockd bushing
6 Plug stem

Fig. 6 - Repkxing the stuffing box pocking, sizes 15 to 150 (left) and DN 200 and 250(ri
5.2.1 \^)ve plug cleaning) on both the threod and the sealing
It is good proctice to also reploce the stuffing conus (order no. 8150-0119) and screw in.
box pocking (4.2) when adding the volve Place l+>e valve bonnet (5) on the valve body
plug. Reploce the plug os instructed below again, and secure the bolts using the hexogo-
(see Fig. 3). Perfom the some steps as in- nol nuts (1.1). The table lists ii\e tightening
structed in section 5.1. However, install o new torques for the seatrings and nuts holding the
plug with ottoched plug stem in place of the body flange (permissible deviation ±10 %).
old one. The worn plug con possibly be used Version ynth mkro-trim element (Fig. 3.2)
ogain after it has been re-worlced (see section In this version, the complete micro-trim ele-
5.2.1.1). Apply lubricant to the plug stem ment can be unscrewed from the voWe body
prior to inserting (order no. 8150-0111). using o socket v^rench (v^dth across flats
SW 27) and subsequently taken opart for
cleoning purposes.
5.2.1.1 Re-working the valve plug
If the individual parts ore damaged, the
Slight damoges on the sealing edges of the micro-trim element should be completely re-
voi^ plug can be corrected by re-tuming. placed.
For valve plugs with soft sealing, re-working
SAMSON seat wrench tool
is possible only up to dimension x, and only
for vahres with a seat bore above 12 mm More details ond infonrnation on the as-
(Fig. 7). sembly procedure con be found in publica-
tion WA 029.
With seat bores of 63 or above, the entire
sealing ring can be replaced should it be Seat bore
12 24...48 63...80 100...2C10
necessary (the plug parts ore screwed mm
together). X (max.) mm 0.5 1.0 2.0 2.5

5.2.2Va\ve seal
Reploce the valve seat (2) os insh\icted
below:
Unthreod the hexagonal nuts (1.1), and lift
the valve bonnet (5), plug stem (6) and actua- * yvs
tor (8) off the valve body (1). Unscrew the
valve seat (2) using the appropriate seat
wrench tool (see table), and apply lubricant
' 1
730.
to the new valve sect (or possibly the old
valve seat after re-working or thorough Fig. 7 V a K ' e p l u g w i lisoft sealing

I b b l e S e c t v n e n c h a n d tightening torques
Nomind size Seal wrench Seotltireod lorque Nuts(].l)ond Ibrque

DN Order no. mm Nm boibl5.4) Nm

15...25 9110-2403 M32xl ,5 170 4xMlO 10

32...50 9110-24^ M58x1.5 500 4xMl2 30

65 ond 80 9110-2467 M90xl.5 1050 4xM16 60

100 9110-2471 MllOxl.5 1550 4xM20 100

125 9110-4075 M 125x1.5 1900 8xMl6 60

150 9110-4076 M 152x1.5 2600 8xM20 100

200 ond 250 0900-0172 M 230x3 4500 BxM27 390


5.3 Replocing the stuffing box packing, valve We advise the use of a SAMSON assembly
plug, valve seat and beliows (for valv^ pliers (Fig. 8.2), in which the plug stems with
extension bonnet or bellows seal bonnet) 10 and 16 mm 0 can be clamped in the vice.
(Figs. 3 and 8). See else sections 5.1 Apply lubricant to either the new or old, re-
and 5.2. worked valve plug (3) (order no. 8150-
Separate the actuator (8) from the valve. For 0111). Check whether the two kx:king
this purpose, perform the following for ver* v«3shers (6.4) ore still confined to the plug
sion: Actuator stem "extends". First apply o stem extension (6.3). Then, screw the plug
pressure v.'hich exceeds the lower-rang value stem tight in the plug stem extension (6.3)
to the actuator (see nameplate). (tightening torque 50 Nm for 0 10, 80 Nm
Loosen the coupling clamps connecting the for0 16mm).
actuator s t ^ and the plug stem, and un- Sizes DN 200 and 250:
thread the annular nut (8.2). Lift the octuotor Remove the hexagonal screws (3.3), strain-
off the valve. ing ring (3.5) and flange (3.6). Unscrew the
Remove the nuts (6.1 and 6.2) and bolts valve plug from the plug stem using a suitable
(5.4). Unloosen the threaded bushing (5.2). tool, preventing distortion of the plug stem
Remove the valve bonnet (5). (this is o part with the bellows). Assemde the
NOTE new valve plug in reverse order
When removing the valve bonnet, take extra Parts 3.5, 3.6 and 3.7 are omitted for the ex-
care not to damage the stuffing box packing tension bonnet version, whereby the valve
(4.2) by the thread of the plug stem extension plug (3) and plug stem (6) are one part.
(6.3). AKvoys remove the stuffing box pack-
ing from the bonnet, and check whether it is 5.3.3 Valve seat
suitable for further use. Replace as instructed in section 5.2.2.
Remove tf>e hexagonal nuts (1.1). Remove
the intermediate piece (12), plug stem (6)
5.3.4 Bellows
and valve plug (3) from the valve b ^ y ( l ) .
Sizes DN 15 to 150:
Unscrew the valve plug (3) along with the ot-
5.3.1 Stuffing box packing
toched plug stem (6) from the plug stem ex-
(Figs. 2,6 and 8)
tension (6.3), considwing section 5.3.2. Un-
Reploce as instructed in section 5.1. To push thread the nut (6.5) using the SAMSON
out, a suitable tool con be used instead of the socket wrench tool (order no.: 9250-
plug stem. 0677.72). Pull the metal bellows (6.6) afong
with welded plug stem extension out of the
5.3.2 Valve plug intennediate piece (12). Clean the sealing
surfaces on the intermediate piece. Push the
Sizes DN 15 to 150
replacement bellows in the intermediote
Unscrewing the plug stem (6) from the plug
piece, and tightly thread on the nut (6.5).
stem extension (6.3) requires that two nuts
Check v,4>ether the two locking washers (6.4)
(for counter holding) be screwed to the pro-
are still situated in the plug stem (6). Apply lu-
truding threod of the extension. In order to
bricant (order no. 8150-0119) to the threod
prevent damage with the bellows version, al-
of the plug stem, and screw the plug stem
ways make sure that no torque is transmitted
tightly in the plug stem extension (6.3) (tighte-
to the bellov^ which is screwed to the inter-
ning torque 50 Nm for 10, 80 Nm for
mediate piece.
16 mm).

10
Sizes DN 200 and 250: 5.3.5 Re-assembling
Unscrew the valve plug (3) from tlie plug stem Ploce the intermediate piece (12) on the valve
OS instructed in section 5.3.2, and pull out the body (1), and secure using tf>e hexogonol
metal bellows (6.6) together with the plug nuts(l.l).
stem (6) upvi«3rds out of the intemr>ediate Place the valve bonnet (5) on the intermediate
piece (12). piece, and secure using the bolts (5.4) and
Replace the sealing ring (6.7), and insert the nuts. Tighten the threaded bushing (5.2).
new plug stem with metol bellov^ section Screw b ^ the locknut (6.2) and the coupling
(6.6). nut (6.1) onto the plug stem extension (6.3).
Screw on the valve plug, ond secure using the Mount the actuator to the valve, and odjust
straining ring (3.5), flange (3.6) and screws the lower and upper-range value as in-
(3.7). structed in section 2.

1.1 Nuts
3 VbUpbg
3.5 draining (tension) ring
3.6 Flonge
37 ScriMi
4.2 Stuffing box pod(ing
5 V d U bonnet
5.2 Threaded bushing
5.4 Bolts
6 Plugstem
6.1 Coupling mrt
6.2 Lodcnut
6.3 Plug stem extension
6.4 Locking washers
ON 15 to 80 order no. 8382-2317
ON 100 to 150 onJer no. 8382-2321
6.5 Nut (sizes DN15 to 150)
6.6 Metdbellovsrs
6.7 Seotingring(DN 200 ond 250)
6.8 Seolingring(DN 200 and 250)
11 Bellosws test connection
12 Intermediate piece

Fig. 8.1 DNlStolSOwithmetalbellov/s,


no bellows (6.6) with extension bonnet

Fig. 8.3 • DN 200and 250with melol bellcws


(and flow divider)
no bellows (6.6) with extension bonnet

Fig. 8.2 Clamping tool, tong order no. 9129-1995

11
5.4 Repbcing the stuffing box packing (or 5.4.1 Size DN40
sealing ring) ^ bolanced valve plug (Fig. 9)
Unscrew Hie threaded bushing (5.2). Remove
After unthreading the hexogonal nuts (1.1),
the stuffing box packing (4.2), packing
remove both the actuator (8) and the valve washer (4.3) and the packing spring (4.1).
bonnet (5) from the volve body. Push out bushing (3.2), and replace the stuff-
For this purpose, perform the following for ing box pocking (3.1). Clean the bore in the
N^rsion: Actuator stem "extends". First apply vah'e bonnet. Apply lubricant to the bushing
a pressure which exceeds the bwer value of (3.2) (order no. 8150-0111), and press in.
the signal range to the actuator (see name- Also apply lubricant to the plug stem (6) and
plate). the efWive areas of the packing (3.1).
Remove the stem connector (7) and the asso- For further assembly, proceed as instructed in
ciated nuts (6.1 and 6.2). Pull the plug stem section 2.
ond the valve plug (3) out of the valve bonnet.

DN 65 and 80
Sb48miTi Sb38mm

DN40 DN 50

S — r"
/

3 Valve plug
3.1 Exiting, sealing ring
3.2 Bushing
DN 100 to 150 3.3 Wcuher;ring
3.4 Screw
6 Plug stem

Fig. 9 - Balanced valve plug

12
5.4.2 Sizes DN 50 to 150 - Sharp recessed groove:
Remove the screw (3.4), screw retention end Stainless steel: DIN-WN 1.4571
wosher (3.3). Reploce the stuffing box pack- - Flat recessed groove:
ing (3.1). Insert tfie washer (3.3). Insert the Material: Hostelby
screw (3.4) and retention, and screw Hght.
Apply lubricant to the p>lug stem (6) and the 6.2 Votve seat
effective areas of the stuffing box packing The moterial number is either stomped in or
(3.1) (order no. 8150-0111). For further engraved.
assembly, proceed as instructed in section 2. When Stdlited, "st" is stamped in.

5.4.3 Sizes DN 200 and 250 6.3 Valve plug


Remove the screw (3.4) along with the reten- Material identification:
tion. Lift off the ring (3.3), and r^loce the - No groove below the connecting threod:
stuffing box packing or sealing ring (3.1). In- Stainless steel: DIN-WN 1.4006
sert the ring (3.3). Insert the screw (3.4) - Sharp recessed groove below the
along with retention, ond screw tight. connect ing thread:
Apply lubricant to the plug stem (6) and ef- Stainless steel: DIN-WN 1 .4571
fective areas of the stuffing box pocking (3.1) - Two sharp recessed grooves:
lorderno. 8150-0111). Stainless steel: DIN-WN 1.4301
For further assembly, proceed as instructed in - Flat recessed groove below the connect-
section 2. ing threod:
Material: Hostelloy
For other materials, either the material num-
6. Identifying mork of the guide bushing,
ber or designation is engrci>^.
valve seat and volve plug
The Kvs value and characteristic are
6.1 Guide bushing
engraved on the valve plug.
Material identification: When Stellited, "st" is engraved.
- No groove on the plane surfoce:
Stainless steel; DIN-WN 1.4305

7. Description of the nomepbte

1 'type designoHon
' SAMSON 1 2 1 3 2 M^iFication index
6
3 Material
' 4 Pos, 5 DN
4 Order no. (pos.) and modification index
PN| 7 (C 8 1 9 10 1 11 5 hem. no, of order
6 Nominol size DN
7 Nominal pressure PN
8 Knvolue
9 ChortxlerisHc:
Gl EQUAL PERCENT,, INUNEAfi
SAMSON 1 1 10 Seoling:
ME METAL. PTSOR
11 D Pressure bolondng
1 or 3 flcv divider
CI 12 iCv 13 1
r 1
ANSI version
12 ANSI O o u (pressure rating)
13 CvvduelKnxl.lT)
Fig. 10 Nameplcrte on control valve

13
1 T)pe designaHon
2 Modification inctex
SAMSON 1 12 1 3 4 3 Elective diophrogmoraa
H 5 4 Actuotoroction:
F 6 M 7 FA Actuator stem "extends"
FE Actuator stem 'refracts'
5 Travel
6 Benchrange(spring range)
Fig. 1 \ NameplateonType271 Actuator 7 Bench ronge wfth *pre-tensioned' sprir>gs

8. Dimensions in mm and weights


Stondord version
hfemindw DN 15 20 25 32 40 50 65 80 100 125 150 200 250
LengthL 130 150 160 180 200 230 290 310 350 400 480 600 730
Height HI 80 285 325
wim ^20 290
cm' 240 285 325
350 305 345
495 525
700 355 395 485
5S0»
1400 1002
2100 U33
2800 1426
H 360 390
with S700 220 260 350
380>1 415"
1400 805
S2100 1060
H2 approx. 40 72 98 118 144 175 235 1 260
H4 120
wim 240 385 425
350 405 445
595 625
700 455 495 585
615^) 6S0>|

with^octuator 5 5 7 11 12 15 24 30 42 80 120 330 380


approx. kg

^' Body tnaterial cast iron G G 25


\fersion with exiMuion bonnet or bellows sed bonnet, sizes DN15 to 150
DN 15 20 25 32 40 50 65 80 100 125 150
Height 625 655
H6 Short/with bellows 405 395 435 635
645'
E^g/long w. bellows 710 700 740 875 865 985
Short/with bellows 10 17 18 21 32 38 60 105 150
Appr kg Long/long w. bellows 12 13 14 21 22 25 36 42 68 1)3 158

14
' VtrsionwithextwwoobonnrterbaWows teal bof»o«t, D N 200 ond 250
Extension isonnet BelovNtiaol bonnet

1 ActuatorflHectiva area on^ 1400 2100 2800 1400 2100 2800

1 Height H6with 1:^200


] DN250 1250 1480 1453 1687

V^^igh1approx kg DN200 380 400 400 390 410 410


DN250 450 450 440 460 460
430

Pneumatic actuator

Actuator size cm^ 80 120 240 350 700 1400 2100 2800

E>iamelerD 150 168 240 280 390 530 670 770

Height H7 62 70 62 82 134 197 373 366

Height H8 163 157 163 183 235 298 374 467

H 3 (or octuotor disossembljr 430 430 430 460 695 1815 2375 2368

H 5 for octuator disossembfy 530 530 530 560 795

looding prMsure connection a GINPn G(NPr) G{NPT1 G(NPr) G3/4 G1


1/4 1/8 1/4 3/8

Weight W 271 Without/ 2 2 5 8 22 70 280 350


•pprex.kg vxilhhancWieel 9 27 12 330 400
13

VMghl^3277 Without/ 3.2 9 12 26


opprox.kg vfilhhandwhed 12 17 31

'///////////Z '////////////
— 00-^a
0D 0D

t J H7

H7
H3 1
nr T
H3
H5
HI I HI

Type 2 4 1 ) H4 yWM TyptU]-7


v j DN15lol50 H MSrll-MJ . DN15lo150
J N
H2 J> s;
H2
H2
L — L -
^ I
^241-1
O N 200 to 250

u
i
H6
H6 DN15to150 D N 200 to 250

.7 ^
s j

15
10. Customer inquiries
Alwoys specify the following important
information (see also nameplote): ' •
1. Order number
2. Type, product number, nominal size and
valve version
3. Pressure and temperature of tfie process
medium f
4. Rote of flow in mVh
5. Bencf) range (e.g., signal range 0.2 to 1
bar) of the respective octuator
6. Indication wf>ether or not a stroiner is
instolled
7. Instollotiondrowing

SAMSON A G AAESS-UNO REGELTECHNIK $


WwsmullerslraRe 3 D-60314 Franlcfuft am Moin ^
Posriaclil01901 D-60019FronkfurlQmMoin 3
lelefon(069)4 0090 leiefax(069}4009507 Efi 8 0 1 5 / 8 0 1 8 E >
Series 240
Globe Ntolve Type 241

1. Design and principle of operation motic, electric or hond-operated), brms the


The single-seated Type 241 Globe Valve is control valve assembly. An extension bonnet
designed occording to the modular-assembly (insuloting section) or bellows seal bonnet
principie. This vofve subassembly combined bellows) can be odded to the standard
with an actuotor subassembly (either pneu- valve version.

Edition November 1995 Mounting and operating instructions

EB 8015-1 E
Travel a^MkMirt I5to80 100to150 200 a. 250
t Dimension A for 75 90 165
dosed vdve ±0.1 ±0.1 (225)

DN 200 and 250

1.1 Bonnatnuh
2 Nbfveseot
3 VaKvplug
4.1 Pocicing spring
4.2 PTFEringpocking
5 Vblvaboonef
5.1 G u i ^ bushing
5.2 Threaded busliing
5.3 Trovd indicator
6 Plug stem
6.1 OMplingnut
6.2 Locknut
6.3 Yoke (DN 200 and 250)
7 Stem connector (coupling)
DN15tol00 6 Actuator
8.1 Actuator stem
Fig. 2 Sectionol drawings of Type 241 Gldse Valve 8.2 Nut
The process medium flows through the valve Stroir^ be installed upstream of tfie valve
in the direction indicated by the arrow. In body.
this process, the clo^re member, the valve In order to avoid disrupting plant operoHon
pli^ (3), is odjusted in response to signal when servicing, v/e also recommerKi that a
pressure chonges acting on the diaphragm shut-off valve be installed both upstream of
of the actuator. the strainer and downsfream of tf)e volve. A
The valve plug (3) ond attached actuator stem bypass line is also recommended.
(8.1) ore connected via the stem connector
(7) and sealed by means of a spring-loaded 2.4 Bellov^ test connection (Pig. 5.1)
PTFE ring packing (4.2). In order to check tfie beik>ws ^ leokoge, the
metol bellov^ version contoins a bellows test
2. Installotion connection (G 1 /8) on tf)e top flange. Espe-
cially for liquids and steam we recommend
2.1 Assembling the valve and octuotor,
that a suitable leakage indicator (such as a
making adjustments
contoct-makir>g pressure gauge, run-off in an
open pan or sight gksss) be connected.
NOTE
When assembling, always observe the
"Mounting and operating instructions" of 3. Operating
the actuator selected. Observe tfte operating notes of the actuotor
being used. They con be found in the corre-
2.1.1 Travel adjustment spofKling operating manual.
When the valve and actuator are delivered
as separate subassemblies, dimension A 4. Troubleshooting
(from the top edge of the coupling nut to the IMPORTANT:
(op edge of the valve bonnet) is adjusted ac- When performing any type of servicing,
cording to tfie table presented in Fig. 2. Al- remove the actuator from the valve! For this
ways check this dimension when assembling. purpose, remove tf>e stem connector (7) and
nut (8.2), and lift the octuator off the valve.
2.2 Mounting position if external leakage occurs, the reason nxiy be
There is no prescribed mounting position. a defective stuffing box or, when equipped
However, olv^oys note the limitations pertain- with a bellows, the metal bellows.
ing to the octuator in use. if the valve does not tightly seal, the reason
Otherwise, it is good practice to install the oc- preventing positive shut-off may be dirt or
tuator vertically upright for valve sizes DN other foreign matter lodged between the
100 and above, focilitating any mointenonce valve seat and the valve plug. Another reason
required. may be domoged sealing edges.
Install the valve free of stressi If necessary, It is good practice to remove the ports, clean
support piping neor the process connections. than thoroughly and, v^en necessary, re-
Never attadi broces lo the valve or the oduotori ploce.
Thoroughly flush through the line prior to in- When assembling the valve, always
stalling the ^(ve!
A remove pressure from the corre*
spending part of the plant! Recom-
mendation: Remove the device.
2.3 Strainer, bypass line
We recommend that a SAMSON Type 2
4.1 Repbcing the stuffing box pocking for 4.2 Replocing the valve seat the valve plug
standord vol^ versions If the valve does not tightly seal, the reason
If the valve leaks around the stuffing box, re- preventing tighte shut-off may be contribut-
ploce its ring packing (4.2) as instructed oble to impurities or damaged sealing edges.
below: In the case of impurities, thoroughly cleon the
Renr)ove the nuts (1.1,6.1 and 6.2) ports. In the second case, replace.
Lift off the valve bonnet (5). Unscrew the
threoded bushing (5.2). Press out ^ dom- 4.2.1 Valve plug
oged ring packing (4.2) with the aid of the We recommend that the PTFE ring packing
plug stem (6). Pull out the vai>^ plug (3) v/ith (4.2) also be replaced when renewing the
attached plug stem (6). Remove ^ e pocking valve plug.
washer (4.3) and the packing spring (4.1),
Replace the valve plug as insMicted below
and clean the packing chamber
(Fig. 2):
Apply lubricant (order number 8150-0112
Perform the same steps as instructed in sec-
to the individual ports of the new packing
tion 4.1. However, install a new plug with at-
and to the plug stem.
tached plug stem in place of the old, worn
Insert the plug stem (6) v/ith attached plug (3) vaive plug. The old plug may still be suitable
in the valve bonnet (5). Place the valve bonnet for used after it has been re-worked (see sec-
on the volve body again, and secure with the tion 4.2.1.1). Apply lubricant (order num-
nuts (1.1), noting the tightening torques ac- ber: 8150-0112) to the plug stem prior in-
cording to the toble. Install the packing spring serting!
(4.1) and the packing washer (4.3), and
carefully slide the new packing (4.2) over the 4.2.1.1 Re*working the valve plug
plug stem and into the packing chamber.
Minor don>age on ^ e sealir>g edges of the
Thread in and tighten the threaded bushing
plug con often be corrected by re-tuming.
(5.2). Screw the locknut (6.2) and the coup- Re-working plugs with soft sealing is only
ling nut (6.1) onto plug stem (6), and adjust possible up to dimension x, and only h^r
dimension A according to thetablein Fig. 2.

4 Pocking
i, 1 Pod(ing spring
4.2 PTFf ringpcxiing
4.3 Packing wosher
5 Vblvebonn«(
5.2 Threoded bushing
6 Plugsiem

Fig. 3 • Exchanging the stuffing box packing DN15tol50( left) andDN200ond 250 (right)
valves having a sect bore larger than 12 mm toble), and apply lubricant (order number
(Fig. 4). 8150-0119) to the thread or sealing conus of
If necessary, the entire sealing ring can be ex- either the new valve seat (or to the old seat
chonged for sect bores 63 or greater (the again folbv/ing re-woHcing or thorough
plug parts are screvii«d together). cleaning!), and screw In. Place the valve bon-
net [5] again on the vak^ body, and secure
4.2.2 Volve seat using the nuts (1.1), noting the tightening tor-
ques for the seat rings and nuts of the body
Reploce the valve seot (2) as instructed flonge as listed in tf>e tables (permissible de-
below: viation ±10%).
Unthread the nuts (I.IK ond lift the valve SAMSON seat wrench tool
bonnet (5) vvith plug stem (6) ond octuator (8) Further details and notes important to assem-
hrom the valve body (1). Unscrew the seat (2) bling can be found In the publication WA
using the appropriote seat wrench tool (see 029

Se^bofB 12 24 ID 63to 100 lo


mm 46 80 200
x(mcK.lmm 0.5 1.0 2.0 2.5

Fig. 4 Plug with soft sealing

"bble Seat wrench and tightening torque


Nominal size Seat wrench Soot ihfood Tightening torque Nuh(1.1)(nd Harrfue
ON Order number fTlff) Nm bob (5.4) Nm
15tQ25 9110-2403 M32x1.5 170 4xM10 10
32le50 9110-2464 M58x1.5 500 4xM12 y>
65 ond 80 9110-2467 M90x1.5 1050 4xM16 60
100 9110-2471 Mn0x1.5 1550 4xM20 100
125 9110-4075 M125x1.5 1900 8xM16 60
150 9110-4076 M152x1.5 2600 6xM20 100
200 ond 250 0900-0172 M230x3 4500 8xM27 390
4.3 Replacing the stuffing box packing, Check whether the tv«3 locking washers (6.4)
valve plug, valve seat and bellows for are still situated in the plug stem (6). T h ^ ,
valves with firmly screw the plug stem in the plug stem ex-
(Pigs. 3 end 5). See also sections 4.1 and tension (6.3). (Torque 50 Nm for 0 10,
4.2. SONmfor 0 16 mm).
Remove the nuts (6.1 and 6.2] and bolts Sizes DN 200 and 250:
(5.4). Unloosen the threaded bushing (5.2). Remove the hexagonal screws, tension ring
(3.5) andflange (3.6). Unscrew the plug from
Lift off the valve bonnet (5).
the plug stem. Use a stuioble tool in order to
CAUTION
prevent the plug stem (the part with the bel-
When removing the valve bonnet, make
sure tfrat the thread o^ the plug stem exten- lows) from turning. Assemble the new valve
sion (6.3) does not damage the PTFE rir>g plug in the reverse sequence.
packing (4.2)1 Parts 3.5,3.6 and 3.7 are omitted for the ex-
tension bonnet version. The valve plug (3)
and plug stem (6) are one part.
Akvays remove the pocking from the valve
bonnet, and check whether suitable for re-
use. 4.3.3 Valve seat
Remove the nuts (1.1); lift the intermediate Replace as instructed in section 4.2.2.
piece (12) with plug stem (6) and plug (3) off
the valve body. 4.3.4 Metal bellows
Sizes DN 15 to 150:
4.3.1 Stuffing box packir>g Unscrew the valve plug (3) with attached plug
(Figs. 2,3 and 5) stem from the plug stem extension (6.3), con-
Replace as instructed in section 4.1. To push sidering section 4.3.2.
the packing out, a suitable tool can be used in Unthread the nut (6.5) using the SAMSOM
place of the pi ug stem. wrench tool (order number 9250-0677.72).
Pull the metal bellows (6.6) with welded on
4.3.2 Valve plug plug stem extension out of ihe intermediate
piece (12).
Sizes DN 15 to 150:
Clean the sealing surfaces on the Interme-
Unscrewing the vah^e plug (6) from the plug
diate piece. Slide a new bellows in the Inter-
stem extension (6.3) requires that two nuts,
mediate piece, and Rrmly thread on the nut
for counter-holding, be screwed onto the pro- (6.5). Check whether the two locking washers
truding thread of the extension, in order to (6.4) are still situated in the plug stem exten-
prevent damoge v/hen working with the bel- sion.
lov/s version, always make certain that no
torque is transmitted to the bellows, this of Apply lubricant (order number: 8150-0119)
which is screwed to the i ntermediote piece. to the thread of the plug stem, and firmly
We recommend the use a SAMSON assem- screw the plug stem in the plug stem exten-
sion (6.3). (Torque 50 Nm for 10, 80 Nm for
bly pliers (Pig. 5.2), permitting plug s t ^ s
16 mm).
with 10 and 16 mm 0 to be clamped in a
vice. Sizes DN 200 and 250:
Unscrew the plug (3) from the plug stem oc-
Apply lubricant (order number: 8150*0112)
cordlng to section 4.3.2, and pull the metal
to the new or old, re-worked valve plug (3)
bellows (6.6), together with the plug stem (6),
plug stem (6).
upNvards out of the intermediate piece (12).
Reploce the sealing ring [6.7], and insert Place the volve bonnet (5) on the intermediate
the
new plug stem with metal bellows (6.6). piece, and secure using the bolts (5.4) and
Screw on the plug, and secure with the ten- nuts. Tighten the threaded bushing (5.2).
sion ring (3.5), Bange (3.6) orKi screws (3.7). Screw the locknut (6.2) arvd the coupling nut
(6.1) onto the plug stem extension (6.3). Ad-
just dimension A according to Fig. 2.
4.3.5 Reassembling
Place the intermediate piece (12) on the s^lve
body, and secure usirtg the nuts (1.1).

1.1 Bonne(tw(s
3 Vfaivepkig
3.5 1»n$ionring
3.6 Fkmge
3.7 Screws
4.2 PTFEringpocking
5 Vi^bmnel
5.2 Threoded bustling
5.4 Bohs
6 Plugsiem
6.1 Coupling nut
6.2 Lod^
6.3 Extended plug Stan
6.4 locking wQsh^
DN15k>80
ORW number 8382-2317
DN100tol50
Order nwmkwr 8382-2321
6.5 Nut (DN1510 150)
6.6 Metol bellows
6.7 S«ilingring(ON200and250}
6.8 Sealing ring (DN 200 and 250)
11 Belk>wslestconnectioif2
12 Intermediate piece

Fig. 5.1 DN 15to150with metal bel-


lows;
with the extension bonnet (insulating
section), the metal bellows (6.6) is
omitted
Fig. 5.3 • DN 200 and 250 with metal bel-
lows (andflow disturber);
with the extension bonnet (insulating sec-
tion) the metal bellows (6.6) is omitted

Fig. 5.2 • Tongs tool order number: 9129-1995


4.4 Replocing the packing (or sealing ring) Clean Hie bore in the vaK^ bonnet. Apply lu-
for boionced valve plugs (Fig. 6) bricant (order number 815(M)112} to the
Remove the stem connector (7) and the nuts bushing (3.2), and press in.
(6.1 and 6.2). Pull the plug stem v/ith at- Also apply lubricant (order number 8150-
tached plug (3) out of the valve bonnet. 0112) to the plug stem (6) and contacting
(running) surfoceof the packing (3.1).
4.4.1 SizeDN40on(y
Unscrev/ the threaded bushing (5.2). Remove 4.4.2 Sizes DN 50 to 150
the PTFE ring packing (4.2), packing v/asher Remove the screw (3.4) with locking device
(4.3) and packing spring (4.1). Push out the and packing washer (3.3). Replace the pock-
bushing (3.2), and replace the packing (3.1). ing (3.1). Insert the packing washer (3.3). In-

DN65and 80
Sb48< Sb38i

D N 4 0 D N 5 0

m
3.2-
3.1 •

s j
r
1 1

3 Valve plug
DNlOOtolSO 3.1 Pocking, lealing ring
3.2 Bushing
3.3 V*Aisher(diKj,ring
3.4 Screw
6 Plug stem

Fig. 6 - Babnced valve plug


stall the screw (3.4) with locking device, and 5.2 Vtolve seat -
screw in tight. Apply lubricant (order num- The moterial number Is either stamped in or
ber 815(M)112) to the plug stem (6) and the engraved.
contacting surfoce of the packing (3.1).
^M)en Stellited, "st" is stamped in.

4.4.3 Sizes DN 200 and 250


5.3 Valve plug
Remove the screw (3.4) with locking device.
Materia) identrficotion:
Lift off the ring (3.3), and reploce the packing
<x seoling ring (3.1). Insert the ring (3.3). In- - No groove bebw the connecting threod:
sert tf>e screw (3.4) with locking device, and Material: DIN-WN 1.4006
screw in tight. - Sharp recessed groove below the con-
Apply lubricant (order number: 8150-0112) necting threod:
to the plug stem [6] and the contacting sur- Material: DIN-WN 1.4571
face of the pocking (3.1). - Two sharp recessed grooves:
Moterial: DIN-WN 1.4301

5. Identification morking of the guide bush- - Plot recessed groove below the connecting
ing, valve seat and vake plug threod
Material: Hastelloy
For other materials, either the material num-
5.1 Guide bushing
ber or the designation is engraved.
Material id^tification:
The Kvs value ond chorocteristk ore en-
• No groove on the plane surfoce:
graved on tf^ valve plug.
Material: DIN-WN 1.4305
When Stellited, "st" is engraved.
- Sharp recessed groove:
Material: DIN-WN 1.4571
- Flat recessed groove:
Material: Hosldloy

6. Description of the nomepkrte

1 lyp« (Jnignahon
SAMSON 1 2| 3 2 Modification index
4 3 Motariol
Pos. 5 DN 6 4 Order no. (pos.) and modiKcolion index
PNl 7 K.,, 8 19 10 i n 5 Item. no. of order
6 Nomtnol sin DN
7 Nominal preuura PN
8 Kvtvolue
9 ChoroderisHc;
Gl EQUAL POCENT., INUNEAR
SAMSON 10 Seoling:
MEAtflAl.PTSOFT
11 D Pressure bdoncing
CI 12 Cv 13 i T 1 orSflow divider
ANSIvenion
Fig. 7 12 ANSI doss (pressure rating)
Nomeplote on valve 13 Cvvalue(K»xl.17)
7. Dimensions in mm and Nights
Standard version
Nominal size DN 15 20 25 32 40 50 65 80 100 125 150 200 250
LengthL 130 150 160 180 200 230 290 310 350 400 480 600 730
H 805 fiO^
with actuator 360 390 Achxitor
1400cm^
220 260 350
1060 fiir
380" 415" /^tucrtor
2800 on^
H2 app 40 72 98 118 144 175 235 260
rox.
Weight, appro*, kg 5 5 7 n 12 15 24 30 42 80 120 330 380

, Vanionwith exl»nsion bonnet or bellows s«ol bonnet Qnlermocfkite piec^ for sizes DN15 to 150
Nominol size DN 15 20 25 32 40 50 65 80 100 125 150
625 655
Swt/wijh bellows 405 395 435 635
645'» 680"
lang^TongMiA brfw* 710 700 740 875 865 985
WlBight, Short/>vith beilosws 8 9 10 17 18 21 32 38 60 105 150
12 13 14 21 22 25 36 42 68 113 158

Vsnionw^ extension bonnet or bellows seol bonnet (intermediate piece) for sizes DN 200and 250
Vsraionwith: Extension bonnet Bellows seal bonnet
AcMoron' 1400 2100 2800 1400 2100 2800
HeightH6with: DN200
1250 1480 1453 1687
DN250
VtMght, opprax. kg DN 200 380 400 400 390 410 410
DN250 430 450 450 440 460 460

Body moterial cost iron GG 25

M8'

O"
H
H6

sJ
i H6

J ^

H2

DN15tol50 DN 200 and 250

10
8. Customer inquiries
(Always specify the following important in-
fonnotionl)
1. Order number (stamped on the nameplote)
2. lype, product number, nominal size and
version of the valve
3. Pressure end temperoture of tfw liquid
4. Rate of flow in m^/h
5. Indication wf>etfier a strainer is installed
6. Installation drawing

11
]V

SAMSON CON^iCXS (LONDON) LTD.


^T,. 50.HcWwpeAvenue CB-Redki.SunByRHI 2N.{London)
Telephone (01737) 7663 91/2/3 • Tx. 885 085
TeWaK(01737)765472 EB 8015-1 E u
Pneumatic Vafve Positioner

Type 765

S/?^^ SON CoNTRalS

ReOHtf^L CCd'il

1. C<ai8truction and mode o f operation


Itie pnexmatio positioner assiires a
preselected relationship betveen the
i ^ v e stea position (controlled variable)

K
and the controller output signal (signal
input). I t ccnpares the output signal
of a pnetaatic or electropaeumatic
control device to the control valve
position and controls the output
pressure connected to the poeuiBatic
actuator.
The positioner essentially consists

of a lever with shaft sad measureoent
spring, the diaphragm and the jnematic
control system vith nozzle, flapper
plate and a i ^ l i f i e r . * - 1 ,
"Bie type 765-^ version has aulditional
aanoiaeters for output pressiire and
input prassure. Figure 1: Type 765
The positioner operates on the force balance principle. The controlled variable *
i s the position of the final ctmtrol element, particularly the stroke of a control
valve. The input w is the output signal of a pneumatic controller. The output y of
the positioner i s the air pressure Pg^.
For every positiwi of the valve there i s a corresponding torsion o f the measuring
spring ( 3 ) . Whenever the actuator or valve stem plate (20) and the pin (1.1) move,
the lever (1) and other transfer elements ( 2 . 1 , 2 . 2 , 3.1) cause the spring (3) to
rotate and the spring torsion i s altered.
Tte input, a signal (p^) in the standard pneumatic range, produces a force on the
diai^agm (>4) which i s balanced by the torsion load of the spring (3). I f the signal
Pg changes, then the feeler pin (5.1) moves, "fte flapper plate (6) follows this
motion and influences the nozzle ( 7 ) .
The supply air i s piped to the pnei»atic amplifier (8) and flows via the Xp-throttle
(9) and the nozzle (7) against the flapper plate (6). A change in either the signal
input or the actuator position causes a pressufe change before and after the s ^ l i f i e r .
The output pressure p^t controlled by the an?>lifier (8) flows t h r o u ^ the adjustable
volume throttle (10) to the pneiaaatic actuator. Adjustable needle valves (9 and 10)
are used for optiaizatioo and stabilization of the positicm-control-loop.
The lever (1) and the measuring spring (3) contained within the positioner are
adaptable to the desired valve stroke and the span of the input signal.

Editic» Novaber 1979 Mounting end operating inttrucHon

EB8106E
1 J.1

I Stroke

Supply P(i Pc

Figure 2: Schematic of the positioner 2.1 Mounting positions of


nozzle and flapper for
"direct action" »

Legenda for figure 2 and 3


1. Lever for valve stroke
2A 23 2.2 3 1.3 1 1.1 Pin
1.3 Spacer tush
I 2
2.2
Shaft
Zero adjusting screv
2.3 Attachment screw
2.U Take off device
3 Measurement spring
3.1 Take off ring
3.2 Screw
Diaphragm
^ O 5
5.1
Coupling
Feeler pin

A 6
7
7.1
Flapper plate
Hozzle
Nozzle block with
operating direction symbol
7.2 Cover plate
8 Aa^lifier
1 1 ^ ^ ^ ^ ^ 9 Xp-adjustment
K) 8 71 72 9 11 6 12 10 Voluste adjustment
11 Mounting screw
20 Plate (attached to valve stes)
Figure 3: Positioner without cover
2. Attachment
"Rie attacfaaent parts vith the product otoiber i s used for attachsent of the
poBitiooer to cast fraaie valreB and the attachaeot kit vith the product nuober
1«400-5T'>7» which additiooally contains a aount vith hose clasps, i s required for rod
valves (spacer 'bolts).
Before actual attachment o f the positioner, the coordination of the positioner and
actuator aust b« laid dovn, as the positicmer is fitted either to the right or
l e f t of the valve. Please note the correapwding illustrations 7 t o 10 in section b . l .

2.1 Attachaent to cast frmme type valve (figures and 5)


Screv the plate (20) vith screws (21) (in the case of figure 5, additionally with
washer) to the coupling c l a ^ (22) of the valve. Unscrew the cover of the positioner
and attach the device to the frsme of the valve vith mounting screv (11).

2.2 Attachawnt to rod type valve (figure 6)


Screw plate (20) with screw (21) in off-centre position on the travel indicator (2>»)
of the valve stem (23).
Place the mowt (28) onto rod (27). Place the opened clamps (26) around the mount and
rod and s l i ^ t l y t i ^ t e n these. Shift the mount imtil the plate centre (20) and mount
hold are flashed at half valve strc^ce. Secure the clasps and mount the positioner
with attachment screw (11) to the mount.

2.3 Housing cover


After attachment of the positioner, make sure that, when the vadve is f i t t e d , the
vent stopper on the housing points downwards.

1 20 1.1 1.2 21 22 23 1.2 21 25 22

Figure h: Attachment in the case Figure 5 s* Attachment in the case


of cast frame version (e.g. type 2Uo) of cast frsBie version (e.g. type S^iO)
Valve DH 15...80 with actuator 80 Valve la 15...80 with actuator 350 cm^
or 2H0 c ^ and Wl 100. ..150 with 700 cm^ and M 20...80 with 700 cm^

I Lever
1.1 Pin
1.2 Hut
II Mounting screw
20 Plate
21 Screv
22 Coi^ling
23 Valve stem
2k Travel indicator
25 Indicator
26 Hose claa^
27 Valve rod (stabled)
28 Mount
28 27 26 20 1.2 1.1 21 24 23

Figure 6: Attachment in the case of rod


type valve ( e . g . type 201)
3. Air cwinections
:nie air ccnnectionB are designed in the fom of hose with RPT thread, nie normal
types of screw coonections for metal and copper pipes or for plastic h(»es can 1>e used.
Before connectitm of the a i r - l i n e s , blow throu^ these well. The outpxrt pressure i s
conveyed to the upper or underside of the actuator in accordance with figures 7 to 10.

U. Operation

U.I Coordinaticm of positioner and actuator


The position of attachment i s dependent on the type of actuator, of input signal and
o f the operating direction. Ihe mounting of the positioner has t o he arranged according
t o Pig. 7 to 10.
Each Buhsequent conversira such as, fo example reversing of operating direction of
the positioner or reversing of the actuator, "spring opening" to "spring closing"
actuator or vice versa, also means an alteration of the positioner's place of
attachment.

m
Pe-

T
Air si^ly - Lever
Plat*

Figure 7: "Spring closing" actuator Figure 8: "Spring closing" actuator


attached on the l e f t , attached t o the r i g h t ,
operating direction » operating direction<>

^Ttrrj'

Air supply

Figure 9: "Spring opening" actuator Figure 10: "Spring opening" actuator


attached to the r i ^ t , attached to the l e f t ,
operating direction » operating d i r e c t i o n O

U.1.1 Detemination and reversion of the operating directiwi (figures 7 to v


figure 11)'
For an increase in the input pressure pg (signal input), the output pressure pat may
increase (direct action » ) or may decrease (reverse acti<Mi<>). Ihis is exactly the
saae for a decreasing input signal p^; in the case of direct a c t i m ^ , a decreasing
output pressure i s obtained and an increasing output pressure i s obtained in the case
of reverse actionO.
Itiere are lateral markings for the operating direction (>^and<>) ont the nozzle block
( 7 . 1 ) . One of the two markings i s covered by the angular tab of the covering plate
( 7 . 2 ) with the result that the v i s i b l e narking indicates which operating direction
has been set.
I f the desired operating direction (figures 7 to 10) does not agree with the v i s i b l e
marking or i f ^ e operating direction is to be altered, proceed as follows: unscrew
both screws (7.3) of the covering plate whilst holding the nozzle block. Benove the
cover plate.
4
Once agkin place the nosile block (7.1) in position shifted liy t80° sad secure ^ i e ,
It i s absolutely necessary to ensure the correct positira of the aoxile block with
the flapper plate t o the feeler pin of the coupling (5) as shown in figure 11. I f ,
after Isying dovn coordination, the operating direction is to be reversed, the
positioner must be screved onto the other side of the valve. Ensure correct
positioning of lever (1) and plate (20) (figures 7 to 10).

Increasing/increasing operating direction


Flapper plate belov the feeler pin

7.1 Rotzle block


7.2 Cover plate
7.3 Screw Flapper
plate

Increasing/decreasing operating direction


Flapper plate above the feeler pin

Visible Flapper
•ariciog ^ ^ plate
Figure 11: Reversal of the nozKle block

H.2 Beginning of operation and signal input span


Each positioner contains a aeasurenent spring (1,2 or 3) ^ i c h can be adapted to the
desired valve stroke and the span of the input signal. Ohe lettering inside of the
cover specifies the relationship of the valve stroke and the signal input span A p.
Honnaly this i s 0.8 bar. A signal input span of O.^t bar i s only required for split
range operation. The range can be altered by subsequently replacing (section U.5)
the aeasurenent spring.
When adjusting the positioner, the stroke must be adapted to the signal input and
vice versa. In the case of a signal input span Ap of 0.8 bar ( e . g . froa 0 . 2 . ^ 1 bar)»
the stroke must also pass through i t s coi^lete range of 0...100^. n»e beginning of
operation i s then at 0.2 and the end value at 1 bsr. During s p l i t range operation,
the actuator operates with the lower sipial input span 4p of O.b bar. In this case,
the beginning of operation i s either at 0.2 bar or at 0.6 bar and, accordingly, the
end valxie i s at 0.6 or 1 bar.
The beginning of operation i s set with the screw ( 2 . 2 ) , the signal input span and
thus the end value i s set witti pin ( 1 . 1 ) . For adjuBt»ent, the control signal input E
Bust be linked to a coepressed air source with a maxinxn of 1.5 bar via a signal
pressure regulator and a control aancmeter and the supply air input Z must be linked
to an air supply.

U.2.1 Adfjusting the beginning of operation ( e . g . 0.2 bar)


(Refer also to section U.3}
Adjust the input pressiire t o a 0.2 bar beginning of operation the signal pressure
regulator. Turn screv (2.2) until the valve stes thus begins to aove fros i t s rest
position (observe the valve stea with travel indicator). Renove the input pressure
f r » the regulator and slowly increase once again. Check whether the valv« stem begins
t o Bove at' exactly 0.2 bar and, i f necessary, correct this.
5
k.a.2 AdJuating th* Biaa&l jpput. rang* p 0 . 2 . . . 1 bar)
or the atroke (Q...1001) ^ " ^
Once the beginning o f operation has been adjuated, increase the input pressure with
regulator t o 1 bar. At the end value of exactly 1 bar, the ralve stem aust be at a
standstill and must thus have passed throu^ 100* stroke. I f the end value i s not
correct, the pin (1.1) must be shifted as follows for correction:
S i i f t to the lever end > stroke increases
Shift to the point of rotation > stroke decreases
After correction, remove the input pressure and increase this once again. First of
a l l check the beginning of operation and then the end value. Repeat correction until
both values are correct.

>>.3 Ad.iuatBent of the P-band (Xp)


The Xp-throttle (9) is normally set to a lower value (open approximately 1 rotation).
In the case of unstable behaviour of the position control loop, the range oust be
increased. However*, remember that the end value of the signal input i s also altered
t y means o f subsequent correction. Therefore, after this, the beginning of operation
and the end value must be checked and, i f necessary, correct i t .

Ad-iustaent of the voltnw (Q)


In order to enable better adaptation of the positioner to the dynamic behaviotir of
smaller actuators, the air output capacity can be accordingly reduced from i t s maximum
value by means of the volume throttle (10).

Replaceaent of the Beaaurettent spring (figure 3)


I f the range is to be altered or converted to s p l i t range operation, the measurement
apring must be replaced as follows:
First of a l l unscrew screw (3.2) from the measurement spring, then release the screw
( 2 . 3 ) and remove the lever with shaft.
Replace the measurement spring, then place the lever with shaft t h r o u ^ the measure-
ment spring and bush with zero point adjustment (2.U). Secure the measurement spring
with screw ( 3 . 2 ) . Shift the bush and shaft towards each other so that the screw (2.3)
meets the flattened part of the shaft. Secure screw ( 2 . 3 h there should be a play
of 0 . 1 . . . 0 , 2 mm between the lever ( l ) , the spacer bush ( 1 . 3 ) , the measurement spring
(3) and the housing.

5. Use of the po8iti<»er as poeumatic aotion tranamitter (figure 12)


In thia applicatiwi, the travel of a controlled valve or another device i s measured
and converted into an output aignal (p^^) frcm 0 . 2 . . . 1 bar or 1 . . . 0 . 2 bar. Refer t o
figure 12 for attachment.

•ote^ The viaible marking of operating direction on the nozzle block must always be
aet t o reverse action <>.

The relation of 0...lOOj valve travel to the output signal 0 . 2 . . . 1 bar (or 1 . . . 0 . 2
bar) i s laid down during the setting of beginning of operation Ucrew 2.2) and end
value (pin 1.1). Operations then correspond with those in sections 1.2.1. and 1».2.2.
"spring cloaing" actuator

Pg-^ incre&sing/pj^ increasing Pg^ increaeing/pj^ decreasing


{ 0 . 2 . . . 1 bar) ( 1 . . . 0 . 2 bar)

PA-*

"Spring opening" actuator

Pg^ increasing/pj^ increasing pg^ increasing/Pj^ decreasing


{ 0 . 2 . . . 1 bar) ( 1 . . . 0 . 2 bar)
. Psf

Air supply

Figure 12: Pneumatic notion traosnitter

6. A t f ' • ' ^ B t of t%K> devices (as positiooer and aotion transmitter)


I f two derices are to be attached, f i r s t of a l l the place of attachment of the
positioner must be laid down in accordance with figures 7 to 10.
It i s then aaly possible t o attach the motion transmitter to the other side of the
valve. I f the relatiaiship of the input pressure Pg^ to the output signal p^ (figure
12) does Dot agree with the required relationship, the aotion transmitter must be
shifted by 180®. The valve travel i s then transferred via plate (20) from the attached
asseably to the other side of the valve stem (refer t o figure 13, figures U and 5 ) .
In order to enable attachment of the plate t o the valve stem, the coupling (22) must
be ranoved and the clamp without stay oust be replaced by a clamp with stay (refer
to section 7 . 2 . 1 ) for the order number).
I f the cou^ing consists of clanqo without stays with a indicator (figure 5 ) , an
additional indicator (order number 0.200-007'*) must be mounted for the second plate.
Proceed in accordance with sections U.2.1, 1».2.2 and 5 for adjustment of the
positioner and pneumatic motion transmitter.

Plate

Positioner

Figure 13: Schematic for attachment


AcceBBoriea, attachment parts
7.1 AcceBsories

order number
Measurement spring 1 0 . 2 . . . 1 bar 1190-0736
Measureaent spring 2 0 . 2 . . . 0 » 6 or 0 , 6 . . . 1 bar (split range) 1190-0737
as well as for 0 . 2 . . . 1 bar
Measurwent spring 3 0 . 2 . . . 0 , 6 or 0 , 6 . . . 1 bar (split range) 1190-0738
Lever I 157 nn 1190-2983
Lever I I 210 mn 1190-3916
Manoneter attachment block vith mancneter (bar) Il»00-57l»8
7.2 Attachment components

Attachment kit for cast frame valves l'»00-57'*5


in accordance with Ramur
Attacbsent k i t for cast frame and rod type valves ll»00-57l»7
rod diameter 1 8 . . . 3 2 BBD in accordance vith Bamur

7.2.1 Additional attachment Darts

Clamp with stay for 80 and 2l»0 a ? actuator 0.300-032l»


Clamp with stay for 350 and 700 eas^ actuator 0.300-052U
Indicator 0.200-007l»

8. Dimensions in mm

Air connections
Supply, input and output pressure connections: IfPT l/h"

1/U" - 18 HPT

Remote
control signal-

Signal pressure-

Air supply —

1A" - 18 MPT connectioos Nsnur rib

-Hounting
screw M8

SAMSON AG
MESS- UNO REGELTECHNIK
D 6000 Frankfurt 1 • Telefon (0611) 40091
WajimGllentro6e3 TtiM 417288 tomd EB8106E
Poslfoch 4147
Series 240

Pneumatic Control Valve Type 241-1

1. -ngtructioD and Mode of Operation


The lype 2U1-1 Pneximatic Control Valve
coH^irises a Type 2Ul Single-Ported Globe
Valve and a Type 271 Pneiunetic Actuator.
means of the modular assea^ly tyi>e
the actuators are exchangeable and the
Standard version can be coopleted t o a
version with insiLlating section or a
version with additional metal bellovs
seal.
The medium flews throu£^ the valve as
indicated by the arrow. The position
of the plug (3) i s changed by the signal
pressure acting on the diaphragm of the
actuator.
The valve plug stem (6) with the atta-
ched plug i s connected to the stem (6.1)
of the actuator via the cov^ling (T)
and i s sealed by means of the spring-
loaded PTFE-V-ring packing Cj.Z).
Depending on the position of the springs
inside the actuator they open or close the
valve when the pressure acting on the
diaphragB i s reduced or upon air failure,
"nie valve closes or opens with increa-
sing pressure ag&iast the force of the
springs.

. 1 Possibilities of exchan^ng the Actuator


The lype 2Ul Valve can be eqiiipped with a Type 271 Pneumatic Actuator (with or
without handwheel), a Type 273 Hand-operated Actuator* or an Electric Actuator.
A pneumatic actuator (with or without handirtieel) can be exchanged for a pneumatic
actuator of different effective area in the case of nominal valve sizes of
to do nm. Tables 1 and 2 indicate which valve can be combined with which
actuator.
If the actuator (80 or 2140 cm^) for valves DH to 80 OOB i s exchanged for a
larger actuator (350 or TOO co^), also the coupling nut (6.1)and the coupling (7)
must be exchanged. The new co\q>ling to be installed i s supplied with the new
actuator ( i t is part of the actuator). "Die new coupling nut (having a top
diaiKter of 16 mm) and the pointer required in addition are included in an extra
package (Product Ho. 1.UOO-$310) attached t o the actuators 350 ci^ and 700 c ^ .

Edition August 1980 Mounting ond operating instruction

EB 8015 E
Table of contents Page
1. Conctruction and Node of operation 1

1.1 Prasibilities o f excbaQging the Actuator 1

2. Assen^ly of valve and activator 5

3- Valve &d.iiist!Dent 6

3.1 Position of Lou-noise plug 6


3.2 Travel adjustment 6
3.3 Adjustaent of the signal pressure value 6
k. Mounting 7

k.^ Mounting 7
k.2 Signal pressure piping 7
U.3 Strainer, by-pass line 7
k.k Test connection 7

5- Operation 7

5.1 Reversal of actuator action 7

6. Troublesshooting 6

6.1 Beplacement of the stuffing box packing of valves in 6


standard version
6.2 Replacement of plug and/or seat 9
6.2.1 .1 Reworking the plug 9
6.3 Replacement of stiiffing box packing, plug. seat, and bellovs 9
of valves vitb insulating section or metal bellows seal
6.U Replacement of sealing of balanced pliigs 11

7. Siicn of f ^ d e busbinx and threaded bushing , seat and plux 12

8. Description of nameplate 13

9- Lubricants 13

10. Enquiries 13
Table t Possibilities of exchanging the actuator for standard-version valves

valve DM Pneuaatic Actuator l^pe 371 (vith or without handwheel)


80 und 240 cb2 for travel 15 wu
15...80
350 ct? for travel 15 «
20...60 700 CB^ for travel 15 am
100...150 700 CB? for travel 30 ma

In the case of noain&l valve sizes of 15 t o BBD and a k value


of 0.1 to 1.0 a 3^0 CB^ actuator i s not required.

Table 2 Possibilities of exchanging the actuators for valves with balanced plug.

Valve Pneumatic Actuator Type 271 (vith or without handwheel)


o
25...80 80 iind 2l»0 cm for travel 15 mm
350 CB for travel 15 nmi
100...150 700 cm^ for travel 30 no

1 Valve body
1.1 Huts
2 Seat
3 Plug
Spring
k.2 PTFE-V-ring packing
3 Bonnet
S.1 Guide bushing
^.2 Threaded bushing
5.3 Travel indicator
6 Plug stem
6.1 Coupling nut
6.2 Lock nut
7 Coupling
8 Actuator
8.1 Actuator stea
8.2 Rut for actuator

Fig. 2 • Sectional viev Type 2l4l-1


Actuator^

Extra package
attached to 350 and
700 cm^ actuators;
can be purchased
separately, specify
Product NaUOO-SSlft
Includes coupling nut
and pointer.

Valve

DN15...eO DN 100... 150

Assembly of the various valves and actuators with their covq>lingB


2. Aaseably of valve and >ctx»tor
I f the valve and the actxiator bave not been a s s e ^ l e d already ^ the manuTactiirer,
or i f the original actiiator o f a valve i s to be exchanged for an actuator of a
different version, asseably shall be effected as described belov.
Caution;
In the case of valves with "spring closing" actuator apply actuator with s i ^ a l
pressure prior disassenbly that the plug removes Trom seat.
2.1 Type 271 P n e ' A c t u a t o r vith or <Ht-hont. inanual adjustaent
(Pigs. 2 and 3, T ^ l e s 1 and 2)
2.1.1. Actuator with dO ^ d 2k0 cb^ diai^u-am on Mi 15 to 80 valves
and actuator vith 700 cmi^ diaphragi on M 100 t o 150 valves
Remove claops of cov^ling (7) and nut (8.2) from the actuator ( 8 ) . Place actuator
(8) on bonnet (5)» attach and t i ^ t e n nut ( 6 . 2 ) . Attach the tvo c l a n ^ of the
coupling (7) to the actuator stea (6.1) and nut (6.1) as shown in H g . 3 and
screv together using the tvo hex head bolts and niits that are part of the coupling.
2.1.2 Actuator vith 350 ca^ diaphraii^ on DH 15 to dO valves
Reaove c l a a ^ of coupling (7) &nd nut (8.2) from the actuator ( 8 ) . Remove coupling
nut (6.1) from valve and replace by coupling nut fr<» the extra package. Place
actuator (tt) on bonnet ( 5 ) , attach and t i ^ t e n nut ( 6 . 2 ) . Attach the tvo clangs
of the coupling (7) to actuator stem (8.1) and nut (6.1) as shown in Fig. U.
Place pointer (6.3) form the etra packaige on the ri^t-hand c l a ^ s so that i t s
t i p points to the travel indicator (5.3) and screv together using the two }fex
head bolts and nuts that are part of the coupling.

8.1
7
5 Bonnet
5 5.3 Travel
indicator
5.3 6.3 Pointer
7 Coupling
6.1 Actuator
stem

Fig, 3 • (top viev) Fig. U • (top viev)


Position of coupling of ON 15 to'80 Position of coupling and pointer of
valves with 80 and 2k0 cin2 actuator, DH 15 to 80 valves vith 350 cm^
and o f DM 100 to 150 valves vitb 700 ciT actuator, and DR 20 to 80 valves vith
actuator. 700 CB^ actuator.
2.1.3 Actuator vith 700 a ^ diaphragg on Ml 20 to 60 valve
A) Valve vith "spring closing** actuator
Heoove clangs of coupling (7)and nut (6.2) from the actuator ( 8 ) . Reaove coupling
nut (6.1) f r { » valve and replace by coupling nut from the extra package. Apply a
signal pressure t o the diaphragm of actuator (8) (air connection at lover actuator
case). Reduce signal pressure until actuator stem (6.1) contacts nut ( 6 . 2 ) .
Attach the tvo claims of the coiqiling (7) to the actuator stem (6.1) and nut (6.1)
as shown in Fig. It. Place pointer (6.3) from the extra package on the ri^t-hand
claiq> so that i t s t i p points to the travel indicator (5*3) and screv together
using the tvo hex head bolts and nuts that are part of the coi^ling.
B) V^,ve vitb "spring opening" actuator
Remove clasps of coupling (7) and nut (6.2) from the actuator ( 8 ) . Reaove coi^ling
nut (6.1) from valve and replace by co;q>ling nut from the extra package. Place
actuator (8) on beonnet ( 5 ) , attach and t i ^ t e n nut ( 6 . 2 ) . Apply s i g n ^ pressure
to the diaphragm (air cwinection at upper actuator case) until actuator stem (6.1)
contacts nut ( 6 . 1 ) . Further assembly as described in A), secOTd section.
3 . Valve ad.iu8tmeDt
Vftieo the v&lve i s supplied assembled coiqpletely vith the actuator, the signal
pressure range has l>eeD adjusted the ntanufacturer ia compliance with the
actuator signal pressure range (indicated on the actuator nameplate or on the tag
attached to the valve).
3.1 Position of the low^nois plug
Valves having a seat hore of 38 mm or greater are equipped vith low-noise plugs
(as/mnetrical plug configuration). In order to achieve optimum efficiency, the
plug should be installed as shown in Fig. 5. Subsequent checking i s possible by
removing the bonnet ( 5 ) .

Stud
5 Bonnet
6 Plug stem
Direction of flow 6.1 Coupling nut
(valve entry) 6.2 Luck nut

15...80 100...150

(at closing valve) 75 + 0,1 90 + 0,2


Fig. 5 • Position of the
asyBBBetrical lov-noise plug Fig. 6 * Travel adjustment
3.g Travel adjustment (Fig. 6)
When valve and actuator are supplied separately, the dimension x has been adjusted
according t o Table Fig. 6. When the actuator i s mounted on the valve so adjusted,
a zero shift of up to + of the signal pressure range may occur due to the
actuator manufacturing tolerances.We, therefore, recomnend to check dimension x
upon assembly of valve and actuator using Table in Fig. 6 and, i f necessary,
adjust the coupling nut (6.1) as follows:
Loosen lock nut ( 6 . 2 ) , adjust coupling nut (6.1) in compliance with dimension x and
t i ^ t e n lock nut again.
Caution: The dimensions specified in the table are applicable only i f the springs
have not been pretensioned. In the case of an actuator vith pretensioned springs,
adjust valve as described in section 3.3.2
I f a more precise adjustment of the sipial pressure lover-range or iq>per-range
values is required, the valve w i l l have to be adjusted as described in section 3.3
3.3 Adjustment of the signal lover-range value (valve vith "spring closing" actuator)
or the siimal pressure upper-range value (valve vith "spring opening" actuator) (Fig.
Exaiaple: Signal pressure range 0,2 to 1 bar
3.3.1 Valve with "spring closing;" actuator
Loosen coupling (7) and lock nut ( 6 . 2 ) . Apply signal pressure to the actuator (8)
(air connection at lower actuator case). Reduce signal pressure until the pressure
gauge indicates the desired signal pressure lower-range value (0,2 bar). Turn
manually nut (6.1) until i t contacts the actuator stem ( 6 . I ) . T i ^ t e n lock nut (6.2)
and screws of coupling (7)<
3.3.2 Valve with "spring closing" actuator vith pretensioned apringa
In the case of DN 15 to 80 spring pretension may amount to approx. I^X of the nominal
travel or the signal pressure span; resp. in the case of DH 1O0 to 1^0 approx. 23%'
I f , for instance, a pretension of 0,1 bar i s desired with the signal pressure range
being 0,2 to 1 bar, the signal pressure lower-range value is shifted to 0,3 bar.
Adjustment shall be accomplished in con^liance with section 3.3.1.
3.3.3 Valve with "spring openinf^" actuator
Loosen coupling (7) 6uid lock nut ( 6 . 2 ) . Apply the signal pressure to the actuator (8)
(air connection at iqpper actuator case). tncrease s i ^ a l pressure until the pressure
gauge indicates the desired signal pressure upper-range value (1 bar). Turn mantially
nut (6.1) until i t contacts the actuator stem and the plug sealing edge contacts
the seat sealing edge. T i ^ t e n lock nut (6.2) and screws of coupling (7)<
6
U. Mounting
4.1 ttountipg poaition
Ibe Talve s s s e i ^ l y may be nounted ID any desired positicm. l ^ e T & l v e oust be in-
stalled free of stress. If necessary, support the piping near the point of coonec-
tiOT. Sever attach supports to the valve or the diwauraqi actuator.
Flush pipe thorou^ly prior to installing the valve.

Signal pressure piping


Connect signal pressure pipe to the lower actuator case of valves vith "spring
closing" actuator and to the upper actuator case of valves vith "spring opening"
actuator.
With an effective diaiduragm area of 80 and 2U0 CB^:
"nureaded connecti<» B 1/U".
With an effective diaphragm area of 350 and TOO cur:
Threaded connection R 3/8".
><•3 Strainer, by-pass line
It i s recoosnended to i n s t a l l a SAMSON Strainer type 2 ahead of the control valve.
For the maintenance of the control valve without interrupting process operations,
i t i s recosnended to i n s t a l l a by-pass line vith shutoff valves.
U.U Test connection (Fig. 11)
The version vith metal bellows seal i s provided vith a test conaec^ioa (11) at
i t s top f1ange for checking the replaceable stainless steel bellows (6.6). It i s
recomiended naioly for fluids and vapours to cumect there a suitable leakage
warning (as contact pressure switch, run off into a open pot or inspection glass).

5. Operation
5.1 Reversal of actuator action
If actuator action should be reversed carry out as described below, (no additions^
conqponents or special tools are required for thi3).ReDove coupling (7) and nut (6.2)
and l i f t actuator off the bonoet ( $ ) .

S i ^ a l pressure

8.1 Actuator stem 6.5 Upper diaphragm case 8.9 Nut


8.2 Mut 6.0 Lover diaphragm case 9 Vent plug
8.3 Springs 8.7 Diaphragm plate 10 Signal pressure
8.'i Diaphrags 8.8 lut connection
Fig. 7 • Sectional viev of actuator
5.1.1 Valve with "spring clogipg" actuator to valve with "spring o]pening" actuator
Unscrew screws and nuts of actuator and remove upper diaphrago case ( 8 . 3 ) . Take
out springs (6.3) and withdraw actuator s t e s (6.1) with diaphragm plate (6.7) and
diaphragm (6.4) fron lover case ( 6 . 6 ) . Unscrew nut (6.6) while holding the nut (6.9)
so as not t o damage the actuator steiB (6.1) Turn over diaphragm plate with d i a -
phragm and replace nut. Grease actuator stem with lubricant (Ordering No. 8.160-0119},
Put diaphragm plate (8.7) into upper case insert springs and push lower diaphragm
case over actuator stem ( 6 . 1 ) . Screw cases together again, and unscrew vent
plug (9) from iipper case and screw i t into the lover case.
Itie springs, ^rtiich now exert a force against the diaphragm plate from lower side
open the valve through actuator sten and valve stem. The signal pressure i s trans-
ferred t h r o u ^ the upper connection (10) into the i^per diaphragm chaoiber. If the
s i ^ a l pressure r i s e s , i s t closes the valve against the force of the springs.
Assemble actuator and valve as described in section 2.
5.1.2 Valve with "spring opening" actuator t o valve with "spring closing" actuator
Unscrew screws and nuts of actuator and remove upper diaphragm case (8.5) withdraw
actuator stes (6.1) with diaphragm plate (8.7) and diaphragm (6.U} from lover
case ( 6 . 6 ) . Take out springs ( 6 . 3 ) . Unscrew nut (6.6) while holding the nut (6.9)
so as not to damage the actuator stem. Turn diaphragm plate and diaphragm over
and replace nut. Push actuator stem (8.1) t h r o u ^ lover diaf^agm case and insert
springs. Replace upper diaj^agm case. Screw cases together again, and unscrew
vent plut (9) from lower case and screw i t into the upper case.
Ibe springs, which now exert a force against the diaphragm from above, thus close
the valve t h r o u ^ the actuator stem and valve stem. The control pressure is trans-
ferred t h r o u ^ the lover connection into the lover diaphragm chamber. I f the
control pressure r i s e s , i t opens the valve against the force of the springs
Assemble actuator and valve as described in section 2.
For further detedls see the mounting and operating instruction for the pneuaatic
actuator EB 8075/8085.

6. Troubleshooting
6.1 Replacement of the stuffing box packing of valves in standard version
I f there is a leak at the vadve stuffing box the packing (U.2) shall be replaced
as f o l l o v s :
Remove co\q)ling (7) and nut (8.2) and l i f t actuator (8) o f f the bonnet ( 5 ) .

I4.1 Spring
k.2 Packing
Disk
» 5 Bonnet
5.2 Threaded bushing
\ 6 Plitg stem
>

Fig. 8 * Replacement o f the stuTfiag box packiug

Caution:
In the case o f valves vith "spring closing" apply actuator vith signal pressure
prior disasseBd>l3r that the plug removes from seat.
Remove nuts ( 1 . 1 , 6.1 and 6 . 2 ) , bonnet (5) and unscrew threaded bushing (5«2).
Push out the defect packing (^.2) using the plug stem ( 6 ) . Pull out plug vith
plug stem. Remove disc Ct.S) and spring (U.I) and clean packing chamber.
Gease the coB^>onents o f the new packing (U.2) and plug stem vith lubricant (9<1)
(see section 9 ) .
Install plug stem (6) vith plug into bonnet ( 5 ) . Place bonnet again on valve body
and attach vith nuts ( 1 . 1 ) . Install spring {h.\) and disc (U.3) and s l i p new packing
carefully over the plug stem into the packing chamber, i ^ l y and tighten f i m l y
threaded bushing (5>2). Screw lock nut (6.2) and nut (6.1) on plug stem.
Install actuator as described in section 2 . Adjust signal pressure lower—range
value or upper-range value as described in section 3.3.
8
6»g Replaceaept of pluj^ and/or s o t ;
If the ralue does not shut off pfop^^^t the cause may be:
a) T i ^ t Bhutoff i s prevented by dirt or foreign matter between seat and plug.
b) Sealing edges of plug and/or seat are defect.
6.2.1 Plug
It IS recoBMended to replace the stuffily box packing C^.S) when replacing the
plug. Replace plug as foUovs (see Fig. 2):
Carry out the procedure described i o section 6.1. Beplace old plug by a new plug
(3) with plug stea (6). Perhaps the old plug can be used again after i t baa been
revorked (see section 6 . 2 . 1 . 1 ) . Crease plug stem (6) with lubricant (9>1) (see
section 9} prior to iostallation. In the case of an asymetrical plug bear in
•ind the mounting position (see section 3)I
6.2.1.1 Reworkim the plug
Minor defects at the sealing edges of the plug can be reooTed by reworking.
In the case of soft-seat plugs reworking i s possible only up to diaension x and
only with valves having a seat bore of more than 12 ma (Pig. 9).

seat bor 0 x (max.)


12 0,3 nm
2U... i»8 1 mm
63...130 3*0 nn

Pig. 9 • Reworking a soft-seat plug


6.2.2 Seat
Replace seat (2) as follows: Unscrew nut (1.1) and l i f t bonnet ($} together with
plug stem (6) and actuator (8) off the body. Unscrew seat using the proper seat
wrench (see Table 3). Apply lubricant 9.2 (see section 9) to new seat (or the old
seat following reworking or thorou^ cleaning) at thread and at the sealing cone,
and screw in.Place bonnet (5) on body again and fasten by laeans of nuts ( 1 . 1 ) .

Table 3 Table U Table 5


Seat thread Torque DR Screws Torque
Seat wrench Product-Mo.
for DH M 32 X 1,5 160 Nm 15...25 1> X M 10 20 Rm
15... 25 9.110-l61il« M 58 X 1,5 590 Na 32...50 b X M 12 35 Nm
32... 50 9.110-1653 M 90 X 1,5 11(00 KB 65.-.80 IT X H 16 90 Nm
65... 80 9.110-1661 M 110 X 1,5 2030 Itm 100 U X N 20 1T0 Sa
100 9.110-1668 K 125 X 1,5 22]»0 Hm 125 8 X M 16 90 8a
125... 150 1.230-1822 M 152 X 1.5 2520 Hm 150 8 X M 20 170 Bm

6.3 Replaceaent of stuffing boa packing, plu<^. aeat^ and bellows of valves with
insulating sectioo or metal bellows seal
IFigs. 2,10 and 11)- See also section 6.1 and 6.2
Remove coupling (7) and nut ( 8 . 2 ) . Lift actuator (8) off b<Mmet (5).
Remove nuts (6.1, 6.2) and bolts ( 5 . ^ ) . Loosen threaded bushing and resiOTe bonnet.
Caution; When reaoving the b<»met, make sure that the stuffing box packing (t».2)
w i l l not be damaged by the thread of the plug stea extension (6.3). ReBX>ve packing
in any case from bonnet and check whether i t i s s t i l l f i t for further use. Reaove
nuts ( 1 . 1 ) ; remove intermediate section (12) with plug stem (6) and plug (3) from
body ( 1 ) .
6.3.1 Stuffing box packing
Replace as described in section 6.1. For pushing out another tool may be used in
place of the plug stea.
Fig. 10 ' Insiilstiog sectioo Pig. 11 ' Metal bellows seal

it.2 Packiag
5 Bonnet
5.2 Threated bitshing
Screws
6 Plug stem
6.1 Coupling nut
6.3 Plug stem extension
6.U Ball
6.5 Nut
6.6 Metal bellows
n Test connection
12 Intermediate section
13 Insulating section

6.3.2 Plug
For screwing out the plug i t is necessary to screw two lock nuts on the exposed
thread of the extension for counterholding. When valves with metal bellows seal
are involved i t i s absolutely necessary to ensure that no tor<iue i s transferred
t o the bellows which is screwed together with the plug stem extension. It i s
recomnended to prepare a clanging tool (Fig. 12) for the vise and use i t .
Caution, the sealing edge of the plug must'nt be danaged.
Crease plug stem (6) of new or old, reworked plug (3) with lubricant 9«1 (see
section 9 ) . Check whether ball (d.M i s s t i l l located in the plug stem ( 6 ) ;
subsequently, screw the plug stem firmly into plug stem extension.
Caution : If a standard valve version i s to be converted into a versira with
metal bellows seal or insulation section at a later date, the plug stem (6) must
be bored as shown in Pig. 13 to accomodate the ball (6.U).
K)
6.U.1 Moninal sizes 25 to ma (Fig. 14)
Seat bor ne-seal PTFE-seal
Unscrew threaded bushing Remore pacJung (U.2), disc {k.3) and spring ( l i . l ) .
3 10 10 (125* Pxisb out bushing (3.2) and replace sealing ring (3.1). Clean bor i s bonnet ( $ } .
6 10 10 ( l 4 j » Grease bushing (3.2) with liibricant (9>1} (see section 9) and press in. Also* grease
12 14 10 (16)* plug stem (6) and contact surface of sealing ring (3.1) with l u b r i c u t l^ten
24 27 29 proced as described in s e c t i « i 2,
31 34 36
3a 41 42
46 51 52 6.4.2 Homiaal sizes 5Q to 150 ma (Fig. 1?)
63 66 67 Remove screw ( 3 . 4 ) , serrated lock washer and disc (3.3). Replace sealing ring (3>1)«
BO 83 84 Install disc (3.3)• attach screw (3.4) with serrated lock washer and screw in
100 103 106 firmly. Grease plug stem (6) and contact surface of seciling ring (3>1) with l u b r i -
110 113 116 cant 9«1« Then proceed as described in section 2.
130 133 136

* Do not Clamp t h i s plugs at

Botm suilable fa- aztarBal the external Diameter


diurUr ef tb«
{•M Table bMidM)
Fig. 12 ' Clashing tool and table external diameter of the plug

Fig. 13 ' Boring of plug stem for


version with Bietal bellows seal or
insulation section. «K> • 16 Fig. 14 Fig. 15
Balanced plug DN 25...40 Balanced plug DR $0 or

6.3.3 Seat
Replace as described in section 6.2.2 7. 3igp of g\iide buehing (5»1) and threaded bushing ( 5 . 2 ) . seat (2) and plug (3)
7.1 Guide - and threaded bushing
6.3.^ Bcllowa
no groove at plane surface Material : 1.4006
Unscrew plug (3) with plug stem (6) from plug stem extension (6.3), see sec- Vshrap cutted out groove Material : 1.4571
tion 6.3.2. Unscrew nut (6.5) using SA^fiON-socket wrench (Product Ho. 9.250-0677.72). "LTplane cutted out groove Material : Hastell^
Pull bellows (6.6) with welded-on plug stem extension (6.3) from intermediate
section. Clean sealing surfaces of inteiraediate section. Slip new bellows into
intermediate section and screw in firmly nut (6.5)' Check irtiether ball (6.4) is 7.2 Seat
s t i l l located in the plug stem (6). Grease plug stem thread with lubricant 9.2 1.1 Sign of material; Material-Ro. i s staved in or engraved
(see section 9) and screw plug stem firmly into the plug stem extension (6.3).
1.2 For stellited seats "st" is engraved

6.3.5 Asseafely 7.3 Plug


Place intermediate section (12) on body (1) and fasten with nuts (1.1). Place bonnet 1.1 Sign of material
(5) on intermediate sectioo and fasten with bolts (5.^) and nuts. Ti^ten threaded no groove below threaded connection Material: 1.4006
bushing (5.2). Screw lock nut (6.2) and nut (6.1) on plug stem extension (6.3). Vsharp cutted out groove Material: 1.4571
Attach actuator as described in section 2. Adjust actuator as described in section 2. Uplane cutted out groove Material: Hastellcv
other materials: material nun^er or designation are engraved.
6.4 Replacement of sealing of balances PI'IUTT
1.2 k -value and characteristic (glp or l i n ) are engraved.
Remove actuator (8) and bonnet (5) after Tunscrewing nuts ( I . I ) . Remove coupling (7) 1.3 F ^ stellited p l ^ "st" is engraved behind k^ -value
and nuts (6.1 and 6 . 2 ) . Push out plug stem (6) with plug (3) from btmnet. and characteristic (glp or l i n ) .
11 12
8. Description of Nameplate

Material designation
Type d e s i g n a t i o n
Product No.
Order number
Metallic or PTFE seal
Flow c h a r a c t e r i s t i c
(equal percentage ( g l p ) or l i n e a r (lin|
value
Nominal p r e s s u r e

Fig. 16 * Naaeplate

9» Lubricants; The following lubricants are available:


9.1 Lubricant Ordering Ho. 8.150-0112
9.2 Lubricant Ordering No. 8.150-0119

10. Enquiries
When making enquiries please advise the following
1. Order No. (embossed in naoeplate)
2. Typet product number, nominal size uid valve version
3. Pressure and ten^erature of the medium
1|.Rate o f fluw in m /h
Signal pressure range ( e . g . 0,2 to 1 bar) of attached actuator
6. lias a strainer been installed?
7. Installation drawing

Foreign patens for Pneumatic Actuator l^pe 271 ^


Great Britain, France, I t a l y , Retherland, Austria

SAMSON AG
MESS- UNO REGEITECHNIK
0 6000 Frankfurt I - Telafon (0611)40090
WeiwnOilanh-ofi* 3 T«l«x 417288 toms d EB 8015 E
Po(lfodi4147
13
Series 5000
Electropneumotic Converters
fi/p Converters)

Type 5288

Fig. 1 • Type 5288-11 -


i / p Converter, plug-in Fig. 2 ' Type 5288-1? Double i / p Converter,
instruaent for seasuring plug-in iostrusent, upper conversion unit
c i r c u i t e , without cover without cover plate and lower conversion
plate (20) unit with cover plate

1. Description

1,1 Application
Instruments serve for conversion of a
standard dc current signal into a
standard pneumatic signal of
0 . 2 . . . 1 . 0 bar or 3...15 p s i ,
primarily for the change-over from
electrical measuring systems to
pneumatic controllers, or from Fig. 3 • Type 528P-5l» i / p Converter
electrical controllers to pneumatic for valve positiiMing, switchboard
control valves. instrument (bousing open)

Bditiem April 1983 Mounting and operating Instruction

EB 5 2 8 8 E
1.2 Versions 1.3 Construction and aode of operation
Type ( F i g . l ) • i / p Converter, According to the version the instruments
plug-in instrunent vith 1 i / p conversion are equipped with one or two i / p
unit. conversion units, which operates on
the force balance principle. These units
Type- 5288-12 (Fig,2) • Double i / p Con- essentialy consist of a cast block with
verter, plug-in instrument vith 2 i/p the electrical measuring systen vith
conversion units. balance beam, a feetback bellows or
Type 5288-1U • i / p Converter, switchboard compensating diaphragm and a nozzle
instruaeDt for mounting on top hat r a i l s . with pneumatic amplifier.
Type 5288-51 • i / p Converter for valve The d.c. current i fed via the soldered
positioning, plug-in instrument vith connection (19) flows through the c o i l (2)
1 i / p conversion unit. which is located in the field of a permanent
Type 5288-52 • Double i / p Converter, magnet (1). The force of the c o i l ( 2 ) ,
plug-in instruaent vith 2 i / p conversion which i s proportional to the current i ,
units. and the force generated by the output
pressure p^ in the feedback bellows
Type 3288-5'< (Fig.3) • i / p Converter for are balanced in the beam (3)>
valve positioning, svitchboard instrusent
with 1 i / p conversion unit for mounting The supply air (p^) supplies the
on top hat r a i l s . amplifier (11) and flows through the
restriction (10), the nozzle (9) and
hits the flapper ( 8 ) . If the input
current i increases, the force of the
c o i l (2) increases and the flapper (8)
Dioves closer to the nozzle. Due to
this the pressure in the nozzle is
increased and the output pressure of
the amplifier, which has passed to the
output of the instrument and to the
feedback bellows ( 6 ) , is also increased.
The pressure increases until a new
balance state is reached and the
output pressure PA is proportional to
the current i .

The adjustment of lower range (adjuster


zero 15) and measuring span (adjuster
span IT) are independent each of other.
In case of plug-in instrument the air
delivery is adjustable at the restriction
(12) to a miniamn value " ^ i n " or a
maximum value "Qmax** • Switchboard
instrument 5288-5^ is designed only for
"QmffK"(aee techn. Dat.)

The i / p conversion units for plug-in-


and switchboard instruments have the
same mode of operation. But the lypes
5288-51, 5288-52 and 5288-5>« i / p Con-
verters for valve positioning are
equipped with a diaphra^a in place of
the feedback bellows ( 6 ) , beyond which
the fine adjustments for lover range
and measuring span drop out.
1Pemanent oagnet
2Coil
3Beaa with ^alance v e i ^ t
hCross spring pivot
5Spring
6Feedback bellows
6Flapper
9Nozzle
10 Restriction
11 Amplifier
13 VoluBC r e s t r i c t i « i
13 Cast block
li<Zero point spring
Zero point adjuster (2^ro)
16 Printed c i r c u i t board
17 Potentioaeter for neasuring
10 9 8 I* n 3 s span adjustsent (span)
19 Soldered connection

E Front panel
Pig. U • Scheaatic diagram of the
i / p Measuring Converter (Plug-in version)

l.b Technical Data

i/p M f c n h g Convartar
T«pa n»4lS3l»4XS288l4 53IB«, 5388-52 | 5288-54
InpMl 4-30 mA 4-30 mA (on nqwM 4-12 or 12-30 inA)

Ovtpul a2-)X)barO_1Spi4 02-1J) bar or 04-2.0 bar*


max. a 0 2 - U bar moa. 04)4-2.3 bdr
P-15 fm or 6-30 pa*
moL 03-18 p)i mK.0«-34p4
Airdatvery oIQmk.: 2.5m,»/h 3Jm,»/1i
•art connactad vo umat > OiOS dm* man, cionnadad ««luina:
>0025 dm>
OS D^/ft • KT
i L oomadad v«h«nas > 0006
Supply U±01bcr(30±1.Spit U±01baror2.4±ftIbv
00±1.5piior36±lip4
<008M.*/h
linaar diorDdvirtk of inpul o n r f M ^
< 0 2 % of v o n
Tsmwol boMd <a2%a'9an <l%oi9Wt

Effact* bi % ei i p a i wpplyi02V01 bar


MrUim* Mmpardura lowar R>«a vtAta < 0 0 2 V ^ <OJM*/«C
<004V%
Loorf Aorodanrfc
Enviwwiwnlel candManf. pniMNMIVV%«M|^Ni

^njtackon ffp9 Phig^rt irarwianBt niMifaeard laraiinote IP 00


twild^BW J imcvmarti wi» cennadion taUa: f 50
^ 5 3 M - . } : 04419 1y»aS»8-.3;075la I j p * S2S8-.4: O t f

' Special <m*ort with ewlpul agmb uptomoamun S bor er 73 pa radmuin panTiwMi nppV or pramn oi 54 bar or 78
08-14.: 05-25; 07-3^ l^-SJ. 1.9-13 or 71iJU bar. Fvntwr <Mi*h on r«)uHl.
** PoMV tafmi^Bon par i/p conwaon uril wlh uppiy or prauurt M bar.
2. Installation
Plug-in instrument
2.1 Plug-in instruaent
The converter i s generally supplied
in ready wired racks. I t i s then a o36 asa a30 o33
conponent of a prefabricated autofflation
unit. All connections, e l e c t r i c a l and
pneumatic take place vith plug-in
connection established automatically
when the \init is inserted.
When inserting the unit, ensure, that
the printed circuit board i s not t i l t e d , bVU 4(01- .30 mA
i . e . slides freely into the top and
bottom guide r a i l s . Front panel must
' Only (or th* Mcond i/p csnvenicn vM
be fixed with two screws. For renoving- cl th* Typn $288-13/ 53
after loosening the fixing screws- use
the grips at front panel, the pneumatic
connections shut off autosatically. Fig. 5
Connection for switchboard instruments
2.2 Switchboard instrument see figures for dimension.
Install switchboard instrument v e r t i -
cally on top hat r a i l s 35mm wide to
DIN EN 5C023. The supply air must be dry and free
of o i l and dust, the supply air
pressure is to be set t o 1.1* ^ 0.1 bar
2.2.1 Electrical connection (20 ^ 1.5 p s i ) . Other pressures to
For connection see diagram f i g . 5 max. S.lt 1 0.1 (78psi) for special
versions see techn. Data. The
For switchboard instruaent the servicing schedules of lined up
connection i s to be carried out at reducing stations must be respected.
terminals for wires 0.5 to 2.5om' or The air lines should be carefully
connection cable. blown-out before connection.

2.2.2 Pneumatic connection


The pneumatic connections air supply
and output are designed in the form
of tapped hole NPT 1/8" (or G 1/8).
The normal type of screw connections
for metal or plastic pipes can be
used. For connections see figures
for dimension.

14 20 21 5 22 23

I
) Zero point s p r i n g
lb Zero point r i n « adjustaient spring
id Screw
?i Piste
22 Lever
?3 Screv

Pig. 6 • Section of converter (turned 180®)


3. Qperation 3.g Adjustment of measuring span

Ad.iugti »nt of zero point (lower 3.2.1 Converter for meaauring circuits
Feed upper range value 20giA to the in-
put of the converter and adjust
3.1.1 Converter for •easuriim circuits measuring span adjuster "Span" (t8)
Before putting the converter into servis, that output at pressure gauge indicates
the zero actjustnent should be checked 1 bar.
as follows (in case of switchboard
instruBent the housing sust be opened): If adjustibility i s not sufficient
(e.g. in case o f change over from
Connect the output of the unit vith 0...20mA to ii...20aA or revers).
a pressure gauge (range 0 . . . t . 6 bar» Readjust potenti<»eter "Span" to
sin. grade 1) and set supply a i r i t s middle rtmge and shift plate (21)
pressure to l.b bar. until output indicates 1 bar, loosen
Peed the lower-range signal (ii or 0mA) screw (20) a l i t t l e before and
to the input of the converter (see retighten afterwards.
f i g . 5) via a convenient d . c . current
source. (In case of OnA the input i s Lastly recheck both values, lower
open). The output pressure at pressure and upper range.
gauge must indicate the value 0.2 bar.
If not, the zero point adjuster "Zero" 3.2.2 Converter for valve positioning
(1?) oust be adjustet to the required
value. Feed upper range value 20mA to the input
of the converter, the output must in-
If adjustibility i s not sufficient dicate corresponding value at pressure
( e . g . in case of change over fr<»i gauge. In case of bigger deviations
0 to U nA or to 0 mA) the zero point loosen screw (20) a l i t t l e and shift
preadjustoent, after removing the cover plate (21) until upper range value of
plate^should be changed as follows: measuring range is attained, retighten
Adjust zero point adjuster (2^ro) so screw (20).
that zero point spring (lli) i s tensioned,
then adjust zero point by turning the Lastly recheck both values, lower
lever (22), loosen screw (23) before and upper range.
and retighten afterwards. Correct small
deviations at zero point adjuster (Zero). 3.3 Adjustment of volume restriction
The volume restriction (12) of
3.1.2 Converter for valve positioning plug-in instrument can be adjusted by
Connect the output of the unit vith a turning the restriction 90® to max. or
pressure gauge. Set supply air pressure min. air delivery (preset t o max. in
to a value O.b bar higher than the manufacture, see techn.* data)
outputsignal ( e . g . output 0 . b . . . 2 bar -
supply s i r i s to be set to bar). For plug-in instrument the restriction
Feed UmA to the input of the converter (12) i s situated to the rig^it of printed
via a convenient dc current source, circuit board. For switchboard instruments
pressure gauge must indicate the lower- the restrictions drops out (air delivery
range value of the output signal. • max.)
In case of bigger diviations adjust
lever (22) after loosening screw (23)
to attain accurate output signal.
Tighten screw (23) again.
it. Maintenance The adjustment by the manufacturer is
carried out as described above to
Air supply following conditions:
Volume restriction (12) is set to Qnax.
Efficient function of the converter at output a hose of Umn internal
will only be assured i f air supply is diameter and 2m lenght with additional
well cleaned before beeing supplied t o volume Iccm is connected. Checked with
the unit. Filter and condensaition same hose and container 230ccffl.
drain of the reducing station oust be
checked regularly. For damping, only o i l supplied by the
manufacturer (Ordering Mo. 6.130-0105)
should be used. It should be put bet-
U.2 Cleaning of restriction (10) ween the danping surfaces in the form
The restriction i s situated laterally of a 0 3 droplet.
in a boring in the housing, in case
of plug-in instruments, the cover
plate nust be removed.
If output pressure i s to low or
output signal f a l l s out, restriction (10)
could be clogged. Therefore remove
screw, l i f t out sieve and clean.

fa.3 Adjustment of daaping (Fig. 7)


The danping, i s adjusted by the msinu-
facturer.
Subsequently the adjustment can also
be corrected to the conditions of the
plant. Therefore connect the output of
converter with a convenient hose suid (or)
container. Set air delivery to the
desired value (Q max or Q min.).
Regulate input signal until output
indicates approx. 0.6 bar at pressure
gauge. Mow find, by turning screw ( l )
and touching balancing beam (3)* the
point when unit just stops hunting.
Then turn out screw (1) one turn (nore
damping) now the unit will not hunt
when the beaa (3) i s touched.
3. Dimensions in aw

Type 5288-11/-12 and Type 528&-51/-52 Plug-in instnuwnts

J 3

4
m

' Of^jr (or Ih* seond i/p CcuwOTon uni


of (h* Typ« S288-12/-S2

Type 5288-l'» and Type 5288-5*' Switchboard instruments

wMh cptwcWoo Hn»<woli witfi cobW

m MmA
SAMSON AG
MESS- UND (tEGEUKHNtK
D6000 Fronkfurtl • Tetflfon (0611) 40090
WMmOkntraSe3 ' Telex 417288 tarnsd EB 5 2 8 8 E
FWoch4147
18
» • *

GRAVITROL®
DENSITY METER
MARK 5
with Pneumatic Transmission

AND MAINTENANCE
!NSTRUCTiONS
Fig. 1
SHIPPING DIMENSIONS {Approx. )

Plywood C a s e : - Timber C a s e : -
1500 X 540 X 690 m m . 1580 X 610 X 710 m m .
Net weight 77 kg. Net weight 77 kg.
Gross weicht 130 ky- Grofis w.'ichi- \ fiO Wo.
PRINCIPLE OF OPERATION COMMISSIONING

1.1 The p r o c e s s liquid flows through the tube loop 2.1 The operational environment is of c o n s i d e r -
(A), fig. 1, pivoted on flexures (B) a b o u t a. able i m p o r t a n c e in obtaining optimum
horizontal axis which p a s s e s through the performance. The application should be con -
flexible connectors (C). The weight of the tube sidered in detail since carefxil installationwill
loop and contents is transferred to the w e i g h - ensure accurate trouble-free operation. A
beam (D) and 'counterpoised by tiie balance solid foundatioi\ must be provided to isolate
weight (E) which is adjustable along the b e a m . the density m e t e r from plant vibration and in
p a r t i c u l a r l y a d v e r s e conditions, anti-vibration
1.2 A change in density of the fluid produces a moimtings may a l s o be required. To ensure
directly proportional change of force on the that no s t r e s s , or vibration is transmitted to
w e i g h - b e a m , which is measured by a pneu- the instrument the connecting pipework should
matic force-balance system, consisting of be attached with flexible connectors.
nozzle and flapper (F), relay (G) and feedback
bellows (H), The output signal of 0.2-1.0
bar (3 - 15 p. s. i . g . ) is directly proportional
to the density change. 2.2 If the atmosphere is particularly c o r r o s i v e it
m a y be advisable to provide air purging to the
instrument c a s e . Special precautions may
1.3 The density span corresponding to 0. 2 ~ 1. 0 a l s o be n e c e s s a r y if t h e - t e m p e r a t u r e of the
bar is determined by the position of the span- liquid is lower than ambient. Under sucK"
adjustor (I) acting on the f o r c e - b a r (JJ and is conditions condensation m a y form on the tube
adjustable between 0. 02 and 0 . 5 g / c m ^ . loop causing a z e r o shift.

1.4 The range for a given span depends upon the


weight (E) which can be positioned in a c c o r d - 2,3 Since the m e t e r m e a s u r e s the density of the
ance with the density to be m e a s u r e d . This tube loop contents, m e a s u r e m e n t will be un-
adjustment is independent of the span adjust~ affected by particle s i z e provided that the
ment. The range and span can be verified by p a r t i c l e s are s m a l l in c o m p a r i s o n with the
using the s c a l e - p a n to hang known weights on s i z e of the bore. A slurry must be circulated
the pivot (L,) to s i m u l a t e density changes through the tube loop at a sufficient rate to
( 5 . 4 - 5 . 14). prevent the d e p o s i t i o n of s o l i d s . The
recommended minimum velocity for s l u r r i e s
1.5 The dashpot (M) and the adjustable damping i s 2 . 2 m / 8 equivalent to a f l o w r a t e of 53 1/min
restrictor (N) in t h e relay (G) prevent ( 7 0 0 g a l / h ) in a 23 m m b o r e tube loop, or
oscillation of the system. 130 1 / m i n (1700 g a l / h ) for a 36 m m b o r e .

230 mm 1275 mm

i In BSP PI. int. tNLET


220 mm
A OUTLET TEMPCOMP
*
4 : L

70 mm-
480 mm

900 mm 980 mm

a 250mm
j i . _ L
225mm l85nYm

A — 130 mm x 80 mm floor
flanges with 2 — 11 mm dia.
fixing holes pitched at 90 mm

^iB.2
'2.4 For clean liquids a high velocity is only r e - 3.7 Slacken nuts (V) to r e l e a s e weigh-beam.
quired on start up to d e a r the air from the Check piston is iii centre of dashpot (M) by
passing length of 24 swg wire round piston.
tube loop. The r e c o m m e n d e d minimum
Fill dasKpot with silicone fluid provided until
velocity is 1 m / s , 25 1/min (330 gal/h) for a
level is 5 m m abo\'e piston,
23 m m bore, or 60 1/min (800 gal/h) for a
36 m m bore tube loop. For the 25 m m bore
glass tube loop the recommended minimum 3.8 RemON'e transmitter (and . temperature c o m -
velocity for clean liquids is 1.1 m / s , 55 1 / m i n pensation unit) force bar transit clips, ensuring
{360 gal/h). the flexures arc uiidamaged.

2.5 V/hen the air has been cleared from the tube 3.9 AU t r a n s i t locks must be used in r e v e r s e
loop the velocity may be decreased, b u t the o r d e r t o above if meter is moved subsequently.
mean density of the tube loop contents will then
change more slowly.
AIR SUPPLY
INSTALLATION
4.1 The instrument should be supplied with c o m -
3.1 Mount density meter on legs (fig. 2) or other p r e s s e d air from a r e g u l a t o r capable of
suitably prepared stand and comaect p r o c e s s delivering 15 1/min ( 0 . 5 SCFM) at 1 . 4 bar
pipework. Ensure tube loop remains dry, A (20 p. s . i . g . ) fig. 4.
typical installation is shown in fig. 3.
4.2 A drip-well f o l l o w e d by a filter should be
3.2 Remove cover and release four r e d transit installed u p s t r e a m of each regulator, or
brackets (Q and R) by removing top screws alternatively one of the c o m m e r c i a l l y avail-
able units can be employed in which regulator,
(store in tapped holes); slacken lower s c r e w s ,
pressure gauge, filter and d r i p - w e l l are in-
slide bracket clear and re-tighten.
corporated in the same a s s e m b l y .

3.3 Level the meter to spirit-level (P) using the


four levelling screws (O) and tighten lock-nuts. 4.3 The air line from the regulator to the density
m e t e r supply connection should be as short as
Secure meter to stand by locking grub screws
possible and must not be emiiller than 7 m m
at top of legs.
bore. Copper, aluminium or nylon tube is
recommended. The air pipe to the receiving
3.4 Slacken and r e - s e c u r e clamp bars (S) to allow
instrument shoxild not be smaller than 5 m m
free movement of tube loop.
b o r e , and again, copper, aluminium or nylon
tube should be used. It i s essential that this
3.5 Lift tube loop and insert link (T) ensuring that
pipe should have no leaks and after start up all
pivots and jewels are correctly seated. Do joints should be tested with soap solution. The
not alter screw adjustments. Allow load on pipe to the receiver can be as long as 125 m ,
nnk to be applied gently to prevent damage to but should be k e p t at a minimum to avoid
jewels. transmission lag.

3.6 Remove outer two screws from weigh-beam


4.4 The usual precautions to ensure a clean dry
locking plate (U) then release central screw
air supply must be observed. Pipes should be
(heads painted red).

FLUSHING VALVE

AIR D R Y I N G VALVE
PRESSURE GAUGE

t X f =1
PROCESS PIPE W O R K

I
OUTLET FLEXIBLE
VALVE CONNECTION

Fig. 3
20 mm PER METRE
SLOPE W I T H FLOW M A I N 12 mm PIPE
OR LARGER

UNREGULATED
AIR SUPPY

SUMP

INTO FINAL FILTERS


& REGULATOR UNITS
OF DENSITY METER
& CONTROLLER

T O DRAIN

Fig. 4
I installed with a falling slope so that moisture weight values corresponding to minimum and
f can flow to suitably placed drain points. If a m a x i m u m density.
supply is taken from an overhead air pipe the
connection should be made with the ' T ' piece F o r example with a 25 m m tube l o o p : -
pointing upwards. When installing new pipe- Density 1.0 g / c m ^ = 3 0 0 g (12.1)
work, j o i n t i n g compounds should be used Scale pan weight = 200g
sparingly and applied o n l y t o male threads, Range 1.1 - 1.2 g / c m ^ c o r r e s p o n d i n g to
a 0,2 - 1.0 bar change in output.
START U P Weight for minimum density = 1.1 x 300 = 330g
(0. 2 bar)
5.1 Connect a clean dry regulated air supply of Weightfor maximum density = 1 . 2 x 300 = 360g
1, 4 bar (20 p. s, i, g , ) to the supply connection ( 1 . 0 bar)
fig. 5 ( 4 . 1 - 4 . 4 ) .
Hence the weights to be added, allo\ving for
5.2 Connect the receiver to the outpiit connection the 200 g scale pan, are 130 g for minimum
and make sure that the damping restrictor (N) density.plus a further 30 g for the maximum
density output signal. The span, 0. 1 g / c m ^
is open.
i s thus equal to 30 g on the scale pan a n d
equal to a 0. 8 bar chemge in outpiit.
5.3 Set over-range nuts (V) one turn m o r e than i s
required for- an output signal of 0. 2 - 1 . 0 bar 5.6 For an i n s t r u m e n t with temperature'
(3 - 15 p. s . i . g , ) . compensation, see section 6.
5.7 Hang the scale pan from the weigh-beam pivot
^,4 Before checkingthe calibration, verifythat the
and add 130 g. P o s i t i o n - the weigh-beam
• tube loop i s clean and dry.
balance weight so that the output is 0, 2 bar.
5.8 The addition of a further 30 g should give a n '
5«5 A scale pan and box of weights are supplied
output of 1 . 0 bar. If the correct output is not
for calibration. The data plate gives t h e
obtained, s p a n - ad j u s t e r (I) must be r e -
positioned; moving the span-adjuster towards
Tit the f e e d b a c k bellows i n c r e a s e s the span.
While correctingthe span, position the balance
weight to keepthe outpxit signal on the receiver
scale.

K>«
.OiltOTION 5.9 After adjustment secure the span-adjuster.
ONLT
5.10 Set the range with the balance w e i g h t for
minimum and maximum density when the span
nKrf>ATui{
has been established,
kTO
UUKur
CLOU J
o» oyritt 5.11 With the weight equivalent to m i d s c a l e , 145 g
CONNC
I TCN r 3 on the scale pan, the output should be 0. 6 bar,

5.12 Adjust t h e damping r e s t V i c t o r (N) for


optimum signal stability and speed response.
Fig. 5
5»13 Return the weights to their box. Replace the 6.5 Calibration Example:
scale pan under the spring clips on the base Equivalent weight for
l.Og/cm^ 300g ( U . l )
plate. Replacc the instriiment c o v e r and
Scalc pan weight = 200g
secure the locks.
Reference temperature = 20OC
TEMPERATURE COMPENSATION
Density range at ref.
temp. ' - 1.1 - 1.2 g/cm3
6.1 Certain applications such as the measurement
Temperature t r a n s -
of the concentration of a solution require the
mitter range = 30 - 80®C
suppression of density signals caused entirely
Temperature trans-
by process t e m p e r a t u r e changes. This
mitter signal = 0.2 - 1.0 bar
suppression or compensation is achieved by
Temperature compen-
applying a force c h a n g e to the measuring
sation range = 40 - 8 0 ° C
system which is equal and o p p o s i t e to the
(0.36 - 1.0 bar)
force change caused by temperature effects.
Density temperature
relationship of
6.2 The signal from a temperature transmitter is = 0.8 X 1 0 ' ^ g / c m ^ / ° C
process liquid
fed into the temperature compensation unit
(connection marked ' T E M P ' ) . The force
6.6 Determine the density range at the maximum
applied to the w e i g h - b e a m force-bar is
compensation temperature, 8 0 ° C
determined by the position of the compensation
i . e . minimum density = 1 . 1 - ( 6 0 x 0. 8 x 1 0 " ^ )
adjuster (fig. 6).
= 1.052 g / c m ^
Maximum density - 1.152 g / c m ^
COMPENSATION ADJUSTER
fIXED COUNTERBALANCF This is the range to which the transmitter is
set, as follows:
Weight for minimum
density = 1 , 0 5 2 x 300
feri LJ ^ U.J - • 315.6g (0.2 bar)
Weight for maximum
WEIGH BEAM
FORCE BAR
density = 345.6g (1.0 bar)

COMPENSATION BELLOWS

CCMTTT OWM 0,*fl9'*ffiJfe


J
DENSITY METER
BASE PNEUMATIC TEMPERATURE SIGNAL

Fig. 6
6.3 A s the force applied is proportional to the
temperature changethe compensation obtained
is linear. Wlier.e the density-temperature
r e l a t i o n s h i p of the process liquid is non-
linear, or c h a n g e s over the density range
Fig.
(e.g. due to changes in the proportion of liquid
to solid in a slurry), then the linear coefficient 6.7 Feed a signal corresponding to the maximum>
which gives rise to least error is used. compensation temperature into the - '-TEMP-'
connection and continue as 5.7 to. 5.12 using a
115.6g at 5.7 and 1.30.6g at 5.11.
6.4 • The maximum compensation available is for a
temperature c h a n g e producing a change in
6.8 For a change of temperature from 8 0 ° C down
density equal to the span of the instrument.
to 40®C the density of the p r o c e s s liquidr.in^..
c r e a s e s by:
e.g. Density meter
" 0:65 g/cm^' - - O r 8 ^ 1 0 " ^ ( 8 0 - 4 0 ) - = - - - 0. 0 3 2 g / c m ^
span
which is 32%-of the density span (6.4). For
P r o c e s s liquid c o - this density signal to be s u p p r e s s e d the
efficient of thermal temperature compensation unit must decrease
expansion 0.5 X 10 '^/OC the d e n s i t y meter output by 0 . 0 3 2 g / c m ^
(0.256 bar).
i . e . density-temp,
0 . 5 X 10 " ^ g / c m ^ / ° C 6.9 With 145.6g on the scale pan, equivalent of
relationship
maximum d e n s i t y at 8 0 ° C (1. 152 g / c m ^ ) ,
decrease the signal applied to the temperature
then," maximum
compensation unit to 0.36 bar corresponding
temperature change
0. 05 to 4 0 ° C . The density meter output should
for which compensation
can be applied 0.5 X 10 '^^lOOOC then be:
1.0 - 0 . 2 5 6 s 0.744 bar
p.10 If the required degree of compensation is not c a r r i e r - c a s t i n g brackets (Q), and a brus}i or
obtained, the p o s i t i o n of the compensa- pxiU-through used. The flexible connectors
tion adjuster must be altered. To increase (C) s h o u l d not be r e m o v e d for routine
the a m o u n t of compensation the adjuster cleaning ( 1 0 . 1 ) ,
should be p o s i t i o n e d nearer to the
compensation flexures. 7.4 It is essential that the range should be verified
before returning t h e instrvmnent to service
6.11 If an adjustment is made at 6.10 it will be (5. 4 - 5 . 13).
necessary to r e - s e t the density meter range.
Apply a signal corresponding to the maximum 7.5 . Pneumatic System
compensation temperature at 8 0 ° C {1.0 bar) For relay maintenance see 8, 2,
and with 145.6g on s c a l e pan equivalent to
maximum density at 80®C (1, 052 g / c m ^ ) . A d - 7.6 The nozzle and flapper may require cleaning
just weight E (fig.l) to give a density meter if sooting occurs,
output of 1.0 bar.
7.7 Lock over-range nuts{V). Rotate flapper away
6.1Z Return weights to box. Replace scale pan from the nozzle after moving it against spring
under clips and secure cover. to release from locating pin. Remove nozzle,
clean with r e v e r s e air blast and replace ( 9 , 4 ) ,
MAINTENANCE
7.8 In the case of damage or replacement of parts,
Under certain working conditions cleaning of the following procedures are given, but should
tube loop or pneumatic system parts may be only be xmdertaken by an experienced instru-
necessary. ment fitter.

7.2 Tube Loop RELAY TYPE R . A . 2


Should a deposit settle inside the tube loop an
output error will become apparent because of 8.1 The relay, fig. 8 is of the continuous bleed
the increased weight and decreased volume. type and consumes a maximum of 15 1 / m i n
In m o s t instances the deposit can be remo\'cd (0, 5 SCFM), The r e s t r i c t o r feeding the
by flushing with a solvent that does not affect nozzle is sitaxated on the side of the relay
the wetted parts (see fig, 3), mounting b l o c k and can be cleared by d e -
pressing the external pin. Included in the
7.3 if m o r e extensive cleaning is n e c e s s a r y the outlet of the mounting block is an adjustable
tube loop can be removed, after clamping tube dgunping restrictor (N), When setting up the
relay ensure that the restrictor i s open. Air

FOR RELAY ADJUSTMENT ONLY

ATMOSPHERE
-0
NEEDLE 0-20 PSIG
VALVE GAUGE

SCREWS

INPUT

i „ 20 PSIG
tL J .j REGULATED
A N D FILTERED
SUPPLY

Fig. 8
passes through a filter disc to the restrictor 9,5 Release o v e r - r a n g e nuts (V) one more turn,
and then to tlic nozzle. Air a l s o flows to the each than i s necessary to o b t a i n full-scale
supply port of t h e valve. A s the nozzle oxitput and clieck range (5. 4 - 5 . 14).
• flapper relationship changes, the resxdting
back pressure on the diaphragm also cJianees. R E P L A C E M E N T OF F L E X I B L E CONNECTORS
If the change increases the back p r e s s u r e , the OR TUBE LOOP F L E X U R E S
diaphragm v / i i l move down closing the supply
port and opening the vent port. This decreases 10.1 T h e pressure alignment must be checkcd
the output pressure fed to the bellows and the ( 1 1 , 3 - 1 1 . 1 8 ) if the flexible connectors are
receiving instrument. removed for cleaning or replacement, or if
the tube loop flexures are replaced.
8.2 The only m a i n t e n a n c e required is the
occasional cleaning of the filter disc and the 10.2 Raise bottom c l a m p - b a r (S) to support tube
restrictor pricker unitwitli benzine or similar loop, r e m o v e linlt (T) and secure transit
solvent. Access to the filter disc is obtained brackets (Q),
by removing the two 10 - 32 UNF s c r e w s .
10.3 Remove daniaged flexures andfit replaccmentsi
8.3 Relay adjustment: The relay is r e v e r s e acting
in operation. Decreasing the nozzle pressure 10.4 Remove flexible connectors for cleaning or
from 4 - 3 p. s . i . g, increases the outpxit from replacement.
3 - 15 p. s. i. g.
10.5 Wheix replacing flexible connectors ensure the
8.4 The tappet has been set during calibration, but ' O ' ring seals are seated correctly. Replace-
should it be accessary to check the setting, all flange screws holding flexible connector
proceed as follows:- and screw in until finger tight. Slacken all
ccrev/s so t h a t flexible connectors can be
8.5 Disconnect tiic nozzle pipe at the relay base. rotated to take up ideal central position and
finally tighten flange s c r e w s . The amount of
8.6 Connect a needle valve and pressure gauge to location provided by the flanges should. be
the noz7.1c comiection fig. 8, and a pressure sxifficient t o m a i n t a i n axes of flexible
gauge or manometer to the output connection. connectors and rect of meter concentric,
AXter final fitting, bellows corrugations musl
8.7 The needle valve slioxild be closed until the be cqui-spaccd and free from distortion.
pressure indicated on the gauge is 4 p. c . i . g .
Carefully adjust the tappet with a A/F NB Correct a l i g n m e n t of flexible
spanner \mtil the output is 3 p. s, i, g. connectors i s essential if pressure
a l i g n m e n t of the meter is to be
8.8 By opening the needle valve, decrease the achieved over its w h o l e working,
pressure to 3 p. s . i . g . The output pressure pressure range ( 1 1 . 1 ) .
will be between 13 - l 6 p . s . i , g . , a gain of
10 - 13. 10.6 Unclamp lube loop (3.2, 3.4 and 3.5).

8.9 Reconnect tlie nozzle pipe and check for lealcs 10.7 Check the p r e s s u r e alignment ( 1 1 , 3 - 11,18),^
with soap solution.

8.10 Check the range. (5.4 - 5.13). PRESSURE ALIGNMENT

ALIGNMENT OF MEASURING S Y S T E M
11.1 The p r e s s u r e alignment i s true v/hen the h o r i -
9.1 Set weigh-beam parallel v/ith base, previously zontal tube loop flexures are on the- same
.. set true to spirit-level (P), using o v e r - r a n g e plane as the p r e s s u r e centres of the flexible
nuts (V). connectors. If this condition is not satisfied
then a p r o c e s s p r e s s u r e will produce a
9.2 The screw-adjusters at top and bottom of link m o m e n t about the t-ube loop flexure axis,
(T) provide adjustment to ensure tube loop is resulting ii: an output signal e r r o r .
also par:tllel v/ith base. The bracket housing
t h e screw-adjuster at top of link provides 11.2 The meter i s pressure aligned by pressurising
a d j u s l T n e n t to ensure linl: is vertical, cach flexible connector separately and ad-
justing the horizontal flexures until minimum
9.3 If the transmitter bar and force-bar (J) are output error i s observed.
not parallel tlie vortical r i d e r - r o d in span-
adjuster (I) should be r e - s e t . 11.3 Raise the bottom t u b c - c l a m p bar (S) to support
tube loop, remove link (T) zuid secure transit
9.4 Adjust nozzle height to give an output signal brackets (Q).
of 0. 5 - 0, 7 bar (8 - 10 p. s. i. g . ) ,
,1.4 S l a c k e n eight flange screws (W), insert 11.15 S e c u r e the tube loop ( 1 1 . 3 ) , remove the
blanking plates, fig. 9 between tube flange and blanking plates and release tube loop ( 1 1 . 5 ) .
'O' ring carrier and tighten flange s c r e w s .
11.16 F i l l the tube loop with water or p r o c e s s liquid
of constant density, taking care that all the air
•50 mm- is expelled. P r e s s u r i s e and check for m i n i -
- 38 mm- m u m output error making adjustments equally
to both flexures as n e c e s s a r y .

11.17 Finally t i g h t e n clamp screws (X) to lock


38 mm position of flexures and r e - c h e c k p r e s s u r e
END FOR USE W I T H alignment.
40mm TUBE LOOP
95 mm
11.18 Empty tube loop and dry. Recouple the p r o -
c e s s pipework and check the r ^ g e (5,4 - 5.14),

50 mm
NOTE With tube loops where blanking plates can-
•END FOR USE W I T H
25mm TUBE LOOP not be inserted ( e . g . g l a s s tube loop) both
sides of the tube loop have to be pressure
aligned simultaneously ( 1 1 , 1 6 ) unless an
internal method of isolating each flexible
Fig. 9
^11.5 Unclamptube loop ( 3 . 2 , 3 . 4 and 3 , 5 ) . connector can be achieved.

11.6 Hang scale-pan from weigh-beam pivot and Before such a p r e s s u r e alignment it must
add gram-weights to give an output signal of be checked that both horizontal flexures a r e
0. 6 bar (9 p. s . i , g . ) . the same height above a suitable datum and
truely horizontal.
11.7 Unlock the f o u r flexure adjustment clamp
screws (X) and lightly re-tighten. EQUIVALENT WEIGHT

11.8 Connect a clean r e g u l a t e d a i r , water or 12.1 The equivalent weight for density 1, 000 g / c m ^
p r o c c s s liquid supplyto one of the pipe flanges i s the total weight which must be added to the
(see 12. 3). If liquid is used, ensure that all weigh-beam, at the scale-pan pivot (L). t o
the air is expelled from the flexible corniector simulate a fluid of density 1 , 0 0 0 g / c m ^ when
before proceeding with the alignment. the tube loop is dry.

11.9 Repeatedly apply t h e maximum working 12.2 The equivalent weight for density 1 . 0 0 0 g / c m ^
p r e s s u r e xintil a consistent reading is obtained will require verification i£ a replacement tube
in the unprcssurised condition. Take care not " loop is fitted or the tube suspension bridge (Z)
to damage the flexible connectors byexceeding moved.
the working pressure,
12.3 A clean, a i r - f r e e water supply c a p a b l e of
11.10 P r e s s u r i s e the flexible connector and note the delivering the necessary (2. 3) flowis required
^ change in outpxit. If the output signal i n - as well as a means of accurately measuring
c r e a s e s , the horizontal flexure, adjacent to the water temperature close to the inlet or
the flexible connector being p r e s s u r i s e d , must outlet connection.
be raised by means of the adjusting screws (Y)
on the flexure mounting blocks. Similarly if 12.4 Water is advised for this p r o c e s s but any suit-
the output falls the horizontal flexure must be able liquid whose density can be ascertained
lowered. Care must be taken to ensure that to the required accuracy ( 1 2 . 1 0 ) may be used,
equal height changes are made at each end of
the flexure to keep them horizontal. 12.5 Disconnect the meter from the p r o c e s s pipe-
work. (Note 3, 9).
11.11 Continue adjusting the height of the flexure
until there is a minimum change in output over 12.6 Connect the m e t e r to the water supply.
the working pressure range.
12.7 Position span-adjuster (I) 15 - 20 m m from
11.12 Similarly pressure a l i g n the other flexible free end of transinitter bar to o b t a i n high
connector (11,8 - 11.11). sensitivity (fine span).

11.13 Repeat the a d j u s t m e n t on each connector 12.8 P a s s water through the tube loop for about
alternately imtil there is a minimum change three minutes to ensure that all the air has
in output over the working p r e s s u r e range, been clcared from the tube loop and that the
water temperature has stabilised.
I 11.14 P r e s s u r i s e both flexible connectors together
f and make any adjustment necessary equally on 12.9 Position balance weight (E) to give an output
all four adjusters (Y), signal of 0. 6 bar (9 p. s . i. g , ) .
12.10 Note the water temperature and obtain the by the density of water at measured temperature
density from temperature density tables. The (12.10). The quotient obtained i s the weight
density must be known to better than of the equivalent to density 1, 000 g / c m ^ .
finest span of the meter.
12.14 Newweight values for minimum and maximmn
12.11 Discoimect meter from water supply. Com- density must be c a l c u l a t e d <5.5) if the
pletely dry out tube loop. equivalent weight f o r density 1 . 0 0 0 g / c m ^
differs from the value given on the data plate.
12.12 Hang scale-pan (K) from pivot (L.) and a d d
gram w e i g h t s to r e s t o r e the 0 . 6 bar 12.15 Recouplc the density meter to the process
(9 p. s. i. g . ) output signal as at 12. 9. pipework.

12.13 Divide the total weight added to weigh-beam 12.16 Re-calibrate the range ( 5 . 4 - 5 . 1 4 ) .

FAULT FINDING

SYMPTOM CAUSE REMEDY

Output will not rise with No or inadequate air supply Check air supply (4. 1),
increasing density
Damping restrictor (N) fully closed Open damper restrictor (N),

Air l e a k s . Check with soap solution.

Incorrectly set over-range nuts (V). Reset o v e r - r a n g e nuts (5.3).

Output will not fall with Blocked r c s t r i c t o r . P r e s s restrictor pricker on


decreasing density relay (G)

Blockcd nozzle. Clean nozzle ( 7 . 7 ) ,

Incorrectly set over-range nuts (V). Reset o v e r - r a n g e (5. 3).

Dashpot piston touching cylinder. Centralise piston in


cylinder (3, 7),

Hysteresis Over-range nut stud touching Set stud to ensure


weigh-beam. clearance.

Incorrectly located link (T), Locate link correctly (3. 5).

Loose or buckled flexures. Secure or replace


flexures (10,1 - 10.3).

Tube loop touching clamps (S & Q) Reposition c l a m p s .

Damaged weigh-beam force bars (J) Reposition or replace force


bar (J)

Damaged link in adjusters (I). Renew link.

SPARES

Description Part No. Per Set

CONNECTION FLANGES

Stainless Steel 1 " BS 10 'E' (25mm tube loop) D23284/1 2


Stainless Steel l i " BS 10 ' E ' (40 m m tube loop) .. D23284/2 2
P . T . F . E . Lined 1" BS 10 ' E' .. • C38116/1 2
SPARES (Continued) Description Part No. Per Set

FLEXIBLE CONNECTORS (C)

25 mm Stainless Steel B38058


40 m m Stainless Steel B38059
25 m m P. T . F. E. A32621

TUBE CARRIER INSERTS

25 m m Stainless Steel A47406/1


40 m m Stainless Steel A47406/2
Insert for glass tube loop A47466/1
Asbestos packing for above insert A35311

TUBE LOOPS

25 m m Stainless Steel C38068/1


40 m m Stainless Steel C38068/2
25 m m Glass B32692

SEALS

25 m m tube loop size ' 0 ' Ring .. .. BS1806 No. 216


4 0 m m tube loop size 'O' Ring .. .. .. BS1806 No. 222
'O' Rings are available in Neoprene, Nitrile, P. T . F . E. ^ Silicone and Viton.
(Please state material when ordering)

FLEXURES

* Stainless Steel 40 mm CRS (weigh-bcam) A29619/1


* Stainless Steel 50 mm CRS (tube loop) A29619/2
* Phosphor bronze 15 mm CRS (transmitter &t TC Units) A29651

TRANSMITTER

* Tube loop/weigh-beam link (T) A35304


* Pivot screw A35305
* Jewel screw A35306
Dashpot (clear moulding) A32619
Dashpot piston assembly A47490-1
* Silicone dashpot fluid (8 dram vial or 1 bottle) A35334/-
Transmitter unit complete B38226/1
Temperature compensation unit complete B38227/2
Phosphor bronze bellows assembly (H) A38082
Nozzle A47427
Nozzle -flapper A29649
Relay RA2 (G) B18968
Restrictor pricker unit A35427
Force bar (J) A47696
Adjuster link A47436

TOOLS

Spanner 8 A / F A35341
Spanner 13 A / F - 17 A / F A35336
Allen keys 2, 2. 6, 4, 5 A / F and Special 5 A / F A35335/1-5

NOTES 1, The above spares cover standard m c t e r s j non-standard spares available on application.

2. Always advise serial number of density meter when ordering spares.

3. Letters in brackets refer to fig. 1.

4. Items marked * arc recommended spares - one spare set being despatched w i t h meter.
Fisher Controls GmbH Geschaftsberelch Instruments
Ein Untefnehmen dor Fisher Controls Corporation of Delaware, U.S.A.
Alb.-Magniis-Str. 11 Tel. (02122) 3 1 4 0 1 1 Technische Euros: Pinneborg Solingen Offenbach/M. Miinchen
Postfach 1 9 0 5 2 0 Telex 8 5 1 4 8 3 2 (csd Tel. (04101) 78 51 Tel. ( 0 2 1 2 2 ) 3 1 4 0 1 1 Tel. (0611) 8 3 1 0 8 4 Tel. ( 0 8 9 ) 7 1 4 1 0 0 2
D - 5 6 5 0 Solingenig Telex 2 1 8 9 1 4 2 fcpd Telex 8 5 1 4 8 3 2 fcsd T e l e x 4 1 5 2 6 2 9 food Telex 5 212 7 4 3 ( c m d
. weitere fisher Controls Verkaufs- und Service-Nicderlassungen in mehr als 5 0 Landorn der Erde

Anderungen vorbehalten

M.I. 126 November, 1975. Printed in England by Roffey & Clark Ltd. , Croydon.
19
. '1 ' •
:i 6 - S e b - ! 9 9 14:33 John Sharman 0148A 86625S P. 01

BERTHOLD
Sorbiji House
Mulberry' Busines!< Park
Wokingham
Berkshire
RG4I 2GV
/ Tel: 0118 977 300J
Fa:i:0118 977 3493
e-maih John_Shannan''alesginc.com

Attn: Paul Shore

Company: Dairy Crest Ingredients SDI

Fax: 01978 782343

From: JOHN SHARMAN

Phone: 01484 866254


Fax: 01484 866255

Date: 16 September, 1999


, Pages including this
cover page: 2

Paul,

Enclosed is our quotation for the replacement amplifier and spares for the detector

Should sou I j^uire any further information, please give me a call

Reuards

John

00

f \
(J - C".^
16-Sep-99 14 : 33 John Shat^man 01484 866255 P . 02

BERTHOLD
Sorbus House
Mulbem' Business Park
Wokingham
Berkshire
RG41 2GY
Tel: 0118 977 3003
Fax:01I8 977 3493
e-mail: J ofa n_S harm a nfa; egginc.com

16 SL'ptember. 1999

Attn: Paul Shore


Daif)' Crest Ingredients SDI
Pickill Lane
Marchwiel
Wretham
L M 3 01IE

Quotation no: 2164 JS

Spares for Berthold LB379 Density Gauge

Comprising
Pan no- Description:
I off 81474-2 LB386-1C Microprocessor based densit\' gauge amplifier
Output ()/4-2UmA isolated.
Automatic decay compensation.
2 open collector outputs for min/ma.\ alarm.
I open collector for failure alarm
20 character alphanumeric display
Data storage in EEPROM for up to 3 data scls for different products
Input for temperature compensation 0/4-2(imA or PTloo
Digital inputs for a) extemaJ setting of current output range b) external setting of
calibration sets or start slop signal for the measurement
Supply 115 V 47-601-b.
19" Rack mounting
Weight aj^rov. 8kg.

1 off 16651 Complete clectroiiics for S/6 Detector


11.405

I off 16625 PM Tube cr\ stal combination £1.038

Prices are ex works Germany

E>clivcr>': 4-6 weeks

Vahdit>-: days

Tcniis of pavmcnt: net 30 davs


Contactless Measurements

n EGsiG BERTHOLD
Process Control Division
The In Line Density iVieter
The Compelling Some Examples for
Advantages Application
Noncontact, continuous measure- Simple installation in existing Sugar industry
ment without contact with medium pipelines. For measurement of thin and thick juice
being measured. and milk of lime.
High statistical accuracy and
Minimum radiation exposure longterm stability by use of highly Milk Industry
(dose rate ^ 1 ^ Sv/h (0.1 mrem/h) at sensitive scintillation counter with Concentration measurements on
10 cm (4") distance from surface). patented drift compensation. whole milk, skim milk, and whey for
control of evaporators.
^^^Am radiation source In ultrasafe Application In food industry.
capsule with long half-life Beverage Industry
(433 years). Calibration and measurement output For monitoring mixing of concentrate
directly in measured variables and water.
Complete stainless steel construc- (g/cm^, %. °Bx, °Be, g/l).
tion of measuring section. Power Plants f
Very simple calibration by micropro- Concentration measurements of lime
cessor controlled amplifier. and limestone gas desulfurizing sys-
tems (scrubbers) in flue.

Starch Production
Measurement of starch suspensions.

Chemical Industry
Measurement of acids, alkalis, suspen-
sions, concentration of anti-freezing
compounds, bulk density determination
in washing powder

Textile Industry
Measurement of foaming of dyeing
liquor

Density measurement in a flue gas


desulfurizing facility.
Photo by pem^ission of Necl<anverke
andKRCCo.

J } ^ EGkG berthold
In Line Density Measurement Facility
Technical Data
LB 386-1 C
An Evaluation Unit with iViany Advantages LB 3 7 9 Measuring System Connections: Flanges according to ttie following
specifications are available: DIN 2576, or
ANSI B 16.5,150 Ib./sq. in, or threaded
Versatile connection pipe SC 65 in accordance with
• Storage for 3 different products: • Detector failure alarm Approval No.: BW/19/78 (applies to Germany and Austria only) DIN 11851. Measuring path with rubber or
- calibration data US licence No: NR-O-101 -B PTFE coating available on request (only with
• Check of the evaluation unit by flanged design).
- temperature compensation means of a "watch-dog"
- range of current outputs Detector Sz6-G5 44/5: Scintillation counter with Nat (Tl) crystal Product temperature: Measuring tube without lining: -190^^ C to
• Alarm via relay output 44/5. With drift compensation circuit. +260°C (-31(r to 500" F: 80 to 560 K);
# Selection of data sets via keyboard measuring tube with rubber coating: - 3 0 to
• Interference due to external sources
or external switch Explosion protection: EEx de II cT6. PTB No. 81/1049 +80^ C ( - 2 2 to 176° F: 243 to 353 K);
of radiation can be suppressed, e.g. measuring tube with PTFE coating: -190° C
# Two isolated current outputs per during non-destructive testing to + 260® C (-310 to 500° F; 80 to 560 K)
Temperature range: - 20 °C to + 50 °C ( - 4 to +122° F)
channel 0/4-20 mA (253 to 323 K). Standard water cooling for
• The measurement can be stopped
Output 1 for density or concentration higher temperatures Housing: Stainless steel 1.4301 (304)
via external contact at which point
Output 2 either for density/concen-
the last measured value will be held, Radioactive nuclide: "'Am Protection class: IP65(NEMA 4)
tration or product temperature Source:
e.g. during empty pipe condition. Activity: 1110 to 3700 MBq (30 to 100 mCi)
The ranges for both current outputs Approx. 16 kg (401b.)
in ultrasafe (special form) design Weight:
are freely selectable • Operating via foil-keypad. To protect
the system against unauthorized Measuring tube: ND 65, NP 10 {ZVi' 150 Ib./sq. in), stainless Connecting cable: 7-core. shielded. 7 x 1.5 mm^. max. cable
• Input for temperature signal:
data manipulation, the keyboard steei 1.4571 or 1.4401 (316), material 1.4301 length between detector and evaluation unit
PtIOOor 0/4-20 mA 500 m (1.500')
can be locked by entering a pass- (304) for pipes with linings
• Test function for detector signal and word.
current outputs
9 Calibration possible with only one Data Outputs Evaluation Unit LB 386-1 C Outputs:
measuring point • Printout via printer interface Analog outputs; 0/4-20 mA isolated max. 500 n
per channel:
For highly accurate measurements (RS 232 or line current) for a) 1 X density or concentration
Assembly: 19" Rack. 3 HE. 84 BE. protection type IP 20.
one may use up to 10 calibration a) calibration data weight approx. 6 kg b) 1 X temperature signal
points. Thus one gets an exact b) product temperature or 2nd range for density or
linearization of the output signal c) average value of density or Power supply: 250/220/125/110/24 V, + 10-15%, 47-64 Hz concentration
even with "difficult" products, such concentration 2 4 V » (18-36V)
Threshold outputs; 2 open collector outputs per channel for
as NaOH or H2SO4 The measured value averaged max. and min. values, 24 V/0.2 A
Power consumption: at 250/220/125/110/24 V 15 VA
over the interval time {freely at 24V=:20W Collective failure Open collector 24 V/0.2 A
Reliable selectable between 1 -1440 min.) message:
# Storage of all calibration data in is printed out. Temperature range: 0-50 ®C (273 to 323 K)
no condensation Option:
EE-Prom without auxiliary power for • RS 232 interface for data transfer to
at least 25 years a master computer Storage of ail Relay outputs for all Switching capacity: 30V,80W
parameters: for up to 3 different products open collector outputs: load, 250 V. 2000 VA
Type: single changer

Printer Interface: RS 232, 75 to 9600 Bd and line current


Inputs: 75 to 9600 Bd
Analog inputs: Temperature compensation with R 100 in
4-wire network Computer interface: RS232, 9600 Bd
Measuring range: 20 charcters. alphanumeric display in g/cm^.
Display:
- 2 0 0 to 400 'C (73 to 673 K). g/l, %. ^Be. °Bx (selected by DIP-switches)
Inputs for temperature signal 0/4-20 mA, Data input via keyboard with dialog, German,
DENSITY METER LB3d6-tC Temperature range freely selectable English or French (selectable): data manipu-
between - 9 9 and +999' C (174 to 1277 K) lation possible only after password entry

ooo
Digital inputs: a) Input for external start/stop of Time constant; 5-9999 s with automatic reduction to 1 /10 of


CHI Italog

measurement this value in case of sudden density changes
b) Input for external range switching of the

m ooe
Csmpul*


Ota
• or
current output Automatic decay
compensation:
for "'Cs. ®°Co, Am and
for each channel
selectable

m • oo
c) External selection of the product
CHI MM

• fl
parameters. Weight approx. 6 kg

9 oo•
Run/Macwn

© CH2 CiMt

• Design modificatk^n may occur without notice. Shieidings see special brochure.

BERTHOLD
y ^ ^ ^ W Radiation Measuring Instruments for Industry. Science and Medicine I

Laboratorium Prof. Dr. BerthoW GmbH & Co. KG • RO. Box 100163 • D-75312 Bad WikJbad-Gennany • Ptione
Great (+49) 7081/177-0 • Fax
Britain USA(+49) 7081/177-100
Belgium China Frar>ce
(+32)2-2516010 (+86) 1065544525 (+33)146498333 (+44)1582713324 (+1)4234832118
^ EGiiG BERTHOLD Fax (+32) 2-2515699 Fax (+86) 1065545692 Fax (+33) 146498334 Fax (+44) 1582 766832 Fax (+1)4234812432
With the LB 379 Measuring Section Scale Drawings

The Principle of
Measurement
The density measurement Is based on ^ ULlt ttt^illl
the absorption method. The radiation cooMng water cooling water
connaotion connection
emitted by an radiation source Is
attenuated by the product being mea-
sured. A detector measures residual
incoming radiation and delivers an
output signal dependent on radiation
intensity. The microprocessor unit Unadedpipe threactodptpe
connecMon
transforms the detector signal Into a connection SC6Snt18S1
current signal. The ^^'Am radiation
offers several advantages when used
In chemical production:

• The radiation attenuation depends V. -


A 1
on the atomic number of the ab- i
sorber If the concentration of a
material with high atomic number in
a liquid, (e.g., HCI, H2SO4, CaO, etc.
in water) must be determined, very
high measurement accuracies can na 2S0
be attained thereby. ^ wHh gfe^ coatInQ en- ail
with PTEE coating co Kt
Some examples:
H2O-HCI ± 0.022 % HCL Density measuring system with Flanged density measuring system
H2O-H2SO4 ± 0.038 % H2SO4 threaded pipe connection
H20-Ca(0H)2 ±0.017%Ca(OH)2 („milkpipe screw connection")
H20-Ti02 ± 0.014 %Ti02
NaHgO-NaOH ± 0.033 % NaOH
Low-fat milk ± 0.075 %TS
Starch suspension ± 0.085 %TS
Sugar solution ± 0.095 %TS

Chemical reactions In which materials 4 m


with high atomic number are depo-
sited can be monitored. This is possi-
ble even when no density change, or
a Si
\
only a minimal change occurs.

84 X 5.08 » 426.72-
Radiation Protection 465.1
The TVansducer
483 0.8
The measuring system has been tested The internal pipe section is completely The electronics of the detector are
by the Physikallsch-Technische Bun- smooth on the inside and is resistant to equipped with drift compensation. This
desanstalt (PTB), German Federal corrosion and abrasion from most prod- provides high long-term stability assuring
Standards Laboratory, and by the Aust- ucts. On request, a rubber or teflon lining that the measuring unit will deliver reli-
rian Study Commission for Atomic can be installed. Also, with the contact- able measuring results even under
Energy as well as by the US Nuclear less measurement, no failures occur adverse installation conditions.
Regulatory Commission. The USNRC from fowling of electrodes, prisms, or
has registered the gauge for General other sensors. The measuring unit can The measuring signal is transmitted
Licence distribution. A design approval therefore be installed for products with digitally. This transmission method is
was granted In the above named (X)un- high viscosity and high solids content. protected against interference and
trles meaning that the operating com- permits signal transmission over long
pany does not require the usual hand- For food Industry applications the distances. Thus, the evaluation unit can
ling licence. The radiation level 10 cm (4") measuring unit can be integrated" In the be Installed without any problem in a
from the surface is only 1 /u Sv/h norma! cleaning cycle without any prob- remote location.
(0.1 mrenrvh). Therefore, the in line lem. Due to the stainless steel construc-
density meter can be installed in the tion of the measuring sectk>n and its
vicinity of the work place. compact design, it can easily be integ-
rated Into existing facilities. 19" frame Range ND10

^ EGsiG BERTHOLD ^ EQsiG BERTHOLD


• J

I
•fT! ' "i

y-m

Bauartgeprufte Radiometrische
DichtemeBanlage

».-it

Radiometric Density Measuring


System
.i'tV t -'Vs • "•^^-vr'-- V- - i V

;J;r/»t r
. Inhalt Seite Content Page
^ 1. Checkliste 1. Check List
B Kurzanleitung fur die Inbelriebnahrhe der Brief instructions for Startup of Density
DichtemeBanlage LB 379 1 Measuring System LB 379 1
2. Genehmigung zum Umgang mit 2. Licence for Handling
radioaktiven Stoffen 2 Radioactive Materials 2
3. Auflagen der Genehmigungsbehorde 3. Condilionso'Use 2
fur den Benutzer 2
4. Aufbau der Anlage und 4. System Design
Einsatzbedingungen 3 and Operating Instructions 3
5. MeSprinzip 4 • 5. N4easuring Principle '. 4
a Szintillomcler 6 6. Scintillometer 6
7. MeBverslarker 6 7. Measuring Amplifier 6
8. Montage...... 8 8. Installation ; 8
.9. Anschlusse 9 9. Connections 9
9.1 Szintillationszahlsr 9 9.1 Scintillation Counter 9
9.2 MeBverstarker 9 9.2 Measuring Amplifier 9
10. Inbetriebnahme 10 10. Startup 10
10.1 LB 3897 Power Supply 10 10.1 LB 3897 Power Supply 10
10.2 LB 3822 Temperature Compensation 10 10.2 LB 3822 Temperature Compensation 10
^10.3 LB3831 Ratemeter 10 10.3 LB3831 Ratemeter 10
P I 0.4 LB 3806 Adaption 10 10.4 LB 3806 Adaption Unit 10
11. Beispiel 1 11 11. Example 1 11
12. V^e ist vorzugehen, wenn koine Angaben 12. How to Proceed when no Information is
in der Tabelle Seite 5 eingetragen sind? 12 Given in Table on f^ge 5 12
12.1 Bestimmung der Unterdruckung u 12 12.1 Calculating the Suppression u 13
12.2 Bestimmung des Bristellwertes fur den 12.2 Determining the Temperature Coefficien!
"Temperaturkoeffizient 14 Setting 14
13. Anzelgetragheit 14 13. Indicator Time Constant 14
14. KalibrlerungderAn'age 15 14. Calibrating the System 15
14.1 Ka'ibrierung ohne Unearisierung 16 14.1 Calibration without Linearization 16
(mit Beispiel 2) (with Example 2)
14.2 Kalibrierung mit Linearisierung 17 14.2 Calibration with Linearization 17
(mit Beispiel 3) (v/ith Example 3)
15. Nachkaiibrierung und Konfrollwert 19 15. Recalibralionand Reference Value 19
16. Umkalibrierung auf anderen 16. Recalibration to Different
DichtemeBbereich 20 Density Ranges 20
•16.1 VergrdBerung Oder Verkieinerung des 16.1 increasing or Decreasing the Range
MeBbereichs bei gleichem MeBmedium 20 for the same Liquid 20
6.2 Bnsatz der MeBanlage fur ein anderes 16.2 Using the System
P MeBprobtem 20 fora Different Application 20
17. Szintiliometerspannung 21 17. ScintillometerVoltage 21
18. Einstellung derAlarme 22 18. Alarm Threshold Setting 22
19. Brucken 23 19. Wire Links 23
20. Blindeinschube/Blindslecker 23 20. Blank Modules /Dummy Connectors 23
21. Strahlenschutz 24 21. Radiation Protection 24

Anlage Enclosure
Bauartzulassungsschein BW/29/78 Certification BW/29/78
Dichteeichkurven (SK 974) Calibration Curve SK 974
MaBbild der MeBstrecke (15113.002) Dimension Drawing (15113.002)
Bedienungsanleitung fur Sondereinschube Operating Instruction for Special Modules (Option)
(falls vorhanden) Connection Diagram
AnschluBplan Circuit Diagrams
Uberrahmen-Verdrahtungsplan
Schaltplane
(Szintillationszahler, Bnzeieinschube)
CHECKLISTE CHECKLIST
1. Kurzanlcitung fur die inbetriebnahme 1. Brief Instructions for Startup
der DichtemeBanlage LB 379 of Density Measuring System LB 379
Wir empfehlen dringend, vor d&r Inbetriebnahme It is essentia! t o study the Operating InstrucUons
der Mel^nlage die Bedienungsanleitung durchzu- before starting up the measuring system. Special
lesen. Insbesondere verweisen wirauf die Auflagen reference should be made t o theconditions for radi-
d e r Genehmigungsbehordo im Bauartzuiassungs- ation protection Imposed by our Approval Authority.
schein.

fj?' •• ' "".or ' ! « '2 ; 9- •o:


f -
o

f {
' •o
. cs -
• W «s « «
! MX < t ••-> O
' o• oo

1. FQlfen der gemaB Bedienungsanleitung montierten 1. nil measuring path with fluid of a known density
und angeschlossenen MeBstrecke mil Medium be- after first having installed and connected it as
kannter Dichte. described in the Operating Instructions.
2. ADAPTION UNIT LB 3806: 2. ADAPTION UNIT LB 3806:
Schiebeschalter HOCHSPANNUNG auf AUTO. Set HV sliding switch to AUTO.
3. POWER SUPPLY LB 3897: 3. POWER SUPPLY LB 3897:
Netzschal'er aul ON. Kontroliampe leuchlet auf. Ab- Main switch to ON. The pilot lamp lights up. Wait
v/arten, bis Blinklicht STORUNG (ADAPTION UNIT until the flashing FAULT light (ADArTION UNIT LB
LB 3806) nach max. 20 s eriischt. 3806) goes out after max. 20 s.
4. TEMP. COMP. LB 3822: 4. TEMP. COMP. LB 3822:
Gegebenenfalls Polenliometer 0 0 0 - 3 0 0 °C auf Where applicable adjust 000 — 300 °C potentiometer
Bezugstsmperaturdes Mediums. Potentiometer T.K to mean temperature of fluid and TO potentiometer
auf gemaG Beispiel 1 (Seite 11) bzw. 12.2 (Seite 14) to the value indicated in Example 1 (Page 11)
ermll'elten Wert einstellen. or Section 12.2 (Page 14). Set sliding switch to
Schiebeschalter auf ON. ON.
5. RATEMETER LB 3831: 5. RATEMETER LB 3831:
Schalter TRAGHEIT auf 1 (5 s), Potentiometer BE- Set TIME CONSTANT switch to 1 (5 s) and RANGE
REIOH auf Einsteliwert u aus Tabelle Seite 12 {gege- potentiometer to the setting u indicated in the Table
benenfalls siehc 14.). on page 13 (see Section 14 where applicable).
6. ADAPTION UNIT LB 3806: 6. ADAPTION UNIT LB 3806:
Mil dem 4-slufigen Dekadenschalter EMPFINDLICH- Using the 4-decade sensitivity switch, adjust the
KEIT Anzeige auf den der Dichte entsprechenden instrument reading to a value v/hich corresponds
Anzeigewert einstellen. (Eine Vergr63erung des 2ah- to the density (increasing the numerical value
lenwertes bewegt den Zeiger in Richtung kleinere shifts the indicator towards lower density).
Dichte.)
7. Gegebenenlalls genaue Kalibrierung gemaB Punkt 7. if necessary recalibrate accurately in accordance
14. der Bedienungsanleilung vornehmen. with Section 7 of Operating Instructions.
8. RATEMETER LB 3831: 8. RATEMETER LB 3831:
Schaiter TRAGHEIT auf maximal zuiassige Anzeige- Set TIME CONSTANT switch to maximum permiss-
Iragheit stellen. ible indicator time lag.
9. THRESHOLD UNIT LB 3862: 9. THRESHOLD UNIT LB 3862:
Gegebenenfalls Alarme A (MAX) und B (MIN.) ein- Adjust Alarm threshold A (HIGH) and B (LOW) as
slellen. required.
10. Ca. ein- bis zweimal jahriich EMPFINDLICHKEIT 10. Adjust the SENSITIVITY (ADAPTION UNIT LB 3806)
(ADAPTION UNIT LB 3806) nachstellen. approx. every 6 to 12 months.
11. Bel Erweiterung um bzw. Herausnahme von Ein- 11. When adding or removing modules:
schuben: Abschnitl 19. (Brucken) und 20. (Blind- Refer to Sections 21 (v/ire links) and 22 (blank
einschube/Blindstecker) beachten! . _ modules/dummy plugs).
2, Genehmigung 2. Licence
zum Umgang mit radioaktiven Stoffen for Handling Radioactive Materials
Fur die MeSanlage LB 379 liegt eine Bauartzulassung Users of radioactive substances normally require a speci-
Nr. BW/29/78 des Ministeriums fur Arbeit, Gesundheit al licerice. The reievanl national laws and regulalions
und Soziaiordnung Baden-Wurtlemberg vor. Eine Geneh- must be obsen/ed.
migung zum Unigang mit radioaktiven Stoflen isl zum The technical description which must accompany the
Betreiben in der Bundesrepublik Deutschiand deshaib application will be supplied on request free of charge.
nicht erforderlich.
Die Verwendung der Aniage ist jedoch der zuslandigen
Behorde vorher anzuzeigen. In aller Regel wurde dies
von uns vor Versand der Aniage fur Sie erledigt, wenn
nicht spezlell etwas anderes vereinbart war.
Wir mochten in diesem Zusammenhang ausdruckllch auf
die Beachtung von Punkt 3. der Bedienungsanleitung
hinweisen.

3. Auflagen der Genehmigungsbehorde 3. Conditions of Use


fur den Benutzer
Die MeBanlage LB 379 wurde von der Physikalisch- The fvleasuring System LB 379 has been approved by
Technischen Bundesanstalt, Braunschweig, bauartge- the Physikalisch Technische Bundesanstalt, Braun-
pruft (Prufschein 6.32-R33). Aufgrund dieser Prufung schv/eig (German Standards Office - Test Certificate
wurde vom Minislerium fur Arbeit, Gesundheit und Soziai- 6.32-R33). Based on this Certificate the system has been
ordnung Baden-Wurttemberg eine Bauartzulassung ge- appro^/ed for general use in the Federal Republic of
maS §§22ff der Stiahlenschutzverordnung erteilt. Wit Germany. This approval is subject to the following (gene-
dieser Bauartzulassung sind fur den Anwender Auflagen ral) conditions which must be obseived by the user:
verbunden, die verbindlich einzuhalten sind. The instrument musl be clearly and permanently marked
Wir verv/eisen auf den der Bedienungsanleitung beilie- wilh the radiation warning symbol and the word "RADIO-
genden Zulassungsschein Nr. BW/29/78, speziel! auf die ACTIVE". These markings musl not be removed or
Punkte .Auflagen 1 bis 4" (Seile 3 des Zulassungs- deleted.
scheins) und ..Hinweise 1 bis A" (Seiten 4 und 5 des If any change or damage to a Density Measuring Syslem
Zulassungsscheins)! is found the manufacturer must be consulted immediately
in order to remedy the damage. In case the possibility
of damage to the containment of the source cannot be
excluded the appropriate supervisory authority must also
be notified and a leakage check carried out by the body
nominated by the supervisory authority.
Density Measuring Systems which are taken out of ser-
vice musl not be included in ordinary refuse but should
be returned either to the manufacturer or to a public
radioactive waste disposal centre. •
The user of an approved system must ensure thai the
actual pressure of the liquid being monitored does' not
exceed 10 bar in the measuring system.
No features of the system which are vital for radiation
protection must be modified in any way.
A system which as a result of v/ear, damage or destruc-
tion no longer complies wilh the requirements of the
approving authority must be taken out of Service. The
user of the system musl immediately take all protective
measures required to prevent any radiation damage. The
relevant authority must be notified without delay.
4. Aufbau 4. System Design
der Aniage und Einsatzbedingungen and Operating Conditions
•ZusammengefaSt ate mechanische Bnheit sind das MeB- The measuring pipe with standard flanges, tfne ^^'Am
rohr mil Normflanschen, der ^•''Am-Strahler und ein fur source and a detector, consisting of a scintillometer
Gammastrahlung hochstempfindliches Szintillorrjeterals extremely sensitive to gamma radiation, have been com-
Detektor. Die mit dem Medium in Benlihrung kommenden bined to form one mechanical unit. Those parts v/hich
Teile (gerades Rohrstiick ohne Einbauten, poliert, 250 come into contact with the liquid (straight pipe section
mm lang, niit Ranschen NW65 ND10 DIN 2576} sind aus without internal fittings, polished, length 250 mm, with
Werkstoff 1.4541, alleanderen AuBenteile aus nichtroslen- flanges nominal bore 65 mm. nominal pressure 10 bar
dem Stahl slrahlwasserdicht (IP 65) gefertigt. to DIN 2576) are made of material No. 1.4541. all other
external parts erf stainless steel conform to the require-
ments of IP 65 Oet-prooO-
Achtung! important!
Die verplombten Schrauben der MeBstrecke durfen The sealed screws in the measuring path must not
nicht geoffnet werden, da sonst die Bauartzulas- be opened for this will invalidate the approval! Cor-
sung ihreGuitigkelt verliert! Aggressive oderabras- rosive or abrasive fluids for which the resistance
sive Medlen, fur die die Bestandigkeit des Werk- of material No. 1.4541 is not guaranteed must not be
stoffes 1.4541 nichl garantiert werden kann, durfen measured with this system as this might jeopardise
aus strahienschutztechnischen Griinden nicht in radiation protection!
der MeBstrecke gefahiren werden. (For fluids of this kind measuring paths lined with FTFE,
(Fur soiche Median sind v/erkseitig mit PTFE, Gummi Oder rubber or equivalent materials can be supplied on re-
ahnlichem ausgekleidete MeBstrecken lieferbar). Vom quest.) The user must ensure that the pressure in the
Kunden muB sichergestelil werden, daB der Druck in der measuring path cannot exceed 70 bar (cf. BW/29/78/
MeSstrecke 10 bar nicht uberschreiten kann (vergleiche "Conditions", Item 4).
BW/29/78 ^Auflagen". Punkt 4).
Als ..praktisches Optimum" zwischen den Forderungen As an "optimum compromise" between the needs of
der Industrie einerseits und der Wahl des gunstigsten industry on one hand and the ideal measuring path
MeBweges fur statistische Genauigkeit und Langzeitsta- for optimum statistical accuracy and long-term stability
bilitat andererseits v/urde die Nennweite auf NW65 fest- on the other, a nominal inside diameter of 65 mm was
gelegt (eftektiver MeBweg — 68 mm). chosen (effective measuring path length 68 mm).
Die Verarbeilung der WeBsignale ertolgt im DichtemeB- The detector output signals are processed in the density
• verslarker. measuring amplifier.

^ f s - r g v ^ -
5. IWeBprinzip 5. Measuring Principle
K i e radiomelrische Dichlemessung bietet die Mogiich- Radiometric density measurement offers the possibility
keit, Messungen kontlnuieilich und beriihrungslos direkt of performing continuous measurements direct on the
an der ProzeBleitung vorzunehmen und erfullt dabei process line whilst avoiding direct contact with the fluid
gieichzerttg alls an eine derartige MeBeinrichtung zu stei- and at the same time meeting all demands normally
fenden Anforderungen. wie groBe Langzeitstabilital, hohe made on systems of the type, I. e. high longtime stability,
NuIlpunktkonstanzundweitestgehendeWartungsfreiheit. low zero drift and minimum maintenance requirements.
Das MeBprinzip beruht auf der Absorption von Gamma- The measuring principle is based on the absorption of
strahlen beim Durchgajig durch das zu untersuchende gamma rays as they penetrate the material being moni-
Material aijf einem genau definierten Strahlenv/eg. tored on an accurately defined radiation path. The system
utilises Ihe relatively low-energy ("soft") 60 keV radiation
Die MeBanlage nutztdie relaliv niederenergetische C,wei-
of ^-JiAm, the absorption depending not only on the den-
che") 60keV-Strahlung von 24iAm, die Absorption ist
sity but also on the atomic number of the absorbing
dabei auBer von der Dichte zusatzlicli abhangig von der
sutDstance (this allows the extremely specific deter-
Ordnungszahl des absorbierenden Materials. (Hierdurch
mination of substances with high atomic numbers in
lassen sich hochspezifische Bestimmungen von hoher-
liquids with lowet atomic numbers).
atomigen Sto'fen in niederatomaren Russigkeiten rea-
lisieren). The necessary detection sensitivity for a given difference
Die erforderliche Anzeigeempfindlichkeit fur einen vor- in density p^i^ to p^a^ is achieved by zero suppression
gegebenen Dichteunterschied p.^j^ bis wird durch (internal bias potential). This approach offers the system
NullpunWunterdruckung ^egenspannung im Gerat) er- user considerable advantages for density measurements
reichL DIese Art der MeBproblemlosung bielet be! Dichte- which, however, are outside the terms of reference of
^messungen erhebliche Vorteile beim Betreiben der An- these Instructions (if requested, we will be pleased to
Page, auf die hier nichl naher eingegangen werden soil. send you a leaflet on this subject which explains the
(Auf Wunsch senden wir Ihnen eine Informationsschrift precise operation and illustrates the resulting advan-
uber dieses Thema mit Erkiarung der Arbeitsweise und tages).
Darstellung der daraus resultierenden Vorteile gerne zu). The SUPPRESSION is defined as the indicator deflection
Als UWTHRDROCKUNG definieren wir den Ausschlag from the true zero point of radiation (for o — infinity) to
vom tatsachlichen Nutlpunkt der Strahiung (fur p un- the midscale value of the mean operating density (see
endlich) bis zur Skalenmltte fijr die mittlere belriebs- drawing SK 974). The required setting u of Ihe RANGE
maBige Dichte (siehe hierzu Zeichnung SK974). Der potentiometer v/ill depend on the liquid and on the re-
erforderllche Einstellwert u am Poll BEREICH hangt ab quired range span (indicator range in g/cm^). In your case
vom Medium und von der GroBe des gewunschlen the following values will apply:
MeBbereiches (= Anzeigebereich in g/cm^). In Ihrem
Anwendungsfall gelten nachslehende Werle.
MeOstelie MeObereich Medium Strahlerstarke Einsfe!!werl u Absorptionskoeffizient
Measuring point
Measuring range Ruid Source inter^sity Setting u Absorption coeffident

Poti BEREICH Poii Spfeizung


(g/cni^) (ma ^-'VJD) RANGE Pot. Spread Pot n

Beispiet (siehe 13) 20°Bnx-0.126 Zuckeriosung 100 ..66,8 V - 0.162


Example (see 2(yBrix-0,126
J3) Sugar Solution

(Bei def Berechnung des oben angegebenen Wertes fiir u sind die Besonderheifen des MeBproblems berucksichtigl)
(The specific characteristics of your application have f>een allowed for in the calculation of the ab

Interessiert primar nicht die Dichte, sondern die Zu- If the composition rather than the density of the ma-
sammensetzung eines Sloffes und isl mil wesentlichen terial is of primary interest, and if major density changes
Dichteanderungen durch Temperalurschv>'ankungen zu due to temperature fluctuations are expected, then the
rechnen, so kompensiert man den Gnflu3 der Temperatur influence of the temperature is compensated (installation
p n b a u eines Temperaturfuhiors und zusalzlicher Ein- of a temperature sensor and an additional module in
schub im DichtemeDverstarker). the density measuring amplifier.
- 6. Szintiilometer 6. Scintillometer
Im Szintiilomeler werden Normimpulse erzeugP^ Auch The scintillomeler generates standard pulses, the number
^ i e Hochspannungserzeugung und -regelung erfolgt im of pulses per second depending on the density. The
Szinliliatidnszahler. Zur Kon'irolle der Hochspannung scintillation counter also generates and stabilizes the HV
wird eine Sleuerspannung Ober das Kabel zum Dichte- supply which is monitored by a control voltage feedback
meBgerat zuruckgefuhrt. Ourch die Potentiaitrennung through the cable to the density measuring unit. Maxi-
zwiscfien Szintiilomelef und MeBverstarker und durch die mum interference protection of the system is ensured by
symmetrische Ubsrtragung der Norrnimpulse ergibt sich isolating the scintillometer from the measuring amplifier
eine hohe Storsicherheit der Anlage. and by symmetrical\ransm\ss\or\ of the standard pulses.

Die Anzahl der Impulse/s ist von der Dichte abhangig.

7. MeBverstarker 7. Measuring Amplifier


Die Weilerverarbeitung und Umsetzung der vom Szin- The amplifier processes and converts the standard pul-
tillationszahlsr kommenden Normimpuise in der Dichte ses generated by the scintillation counter into output
proportlonale Ausgangssignale (0—10V und 0/4— 20 signals proportional to the density (0—10 V and 0/4—20
mA) erfolgt im Verslarker. Er ist in moderner Technik mA). The amplifier is of modern modular design based on
|jn Einzeleinschuben auf Europakarlen aufgebaut. Jeder European standard printed circuit cards. Each in-
Einzelcinschub entspiicht einer Funklionseinheit und wird dividual module covers a separate system function and
in einen fertig verdrahteten 19"-Baugruppentrager mit is plugged into a fully wired 19 inch chassis with a height
einer Hohe von 3 U (ca. 135mm) eingesetzt. Die Zusam- of 3 U (approx. 135 mm). The configuration of individual
menstellung der Elnzeleinschube ist dern MeBproblem modules v/ill depend on the actual application, but the
angepaSL Grundsatzlich vorhanden sind folgende Ein- following will always be included:
schube:
Anpassung (Adaption) LB 3806 Adaption Unit LB 3806
(Anpassung der Impulszahl an das MeSproblem und (Adapts the number of count pulses to the individual
Hoohspannungskontrolle, Testeingang) application and provides HV check plus test input)
Ratemeter LB 3831 Ratemeter LB 3831
(mit den Einsteilorganen fur IvIeBbereich (= Unter- (with controls for range (— suppression), time constant,
dfuckung), Tragheit, Feineinstellung der Impulszahl fine adjustment of number of count pulses and 0—
und der Erzeugung der Ausgangssignale 0—10 Vso- 10 V output signal generation plus sub-card for out-
svie mit Sub-Steckkarte fur Ausgangsstrom put current)
LB 3851 for 0 / 4 - 2 0 m A
LB 3852 lur0/4-20rnA LB 3853 f o r 0 / 4 - 2 0 r a A (electrically isolated).
LB 3853 fur 0 / 4 - 2 0 mA (mit Potentialtrennung).
Anzeige (Analog-Display) LB 3886 Analog Display LB 3886
(mit Prazisionsanzeigelnstrument) (with direct-reading precision instrument)
. Netzteil (Power Supply) LB 3897 Power Supply LB 3897
I (Erzeugung derVersorgungsspannungen fur den Ver- (generates amplifier power supplies)
starker)
Je nach DichtemeOproblem kommen zusatzlich bzw. The following additiorral and/or alternative modules are
alternatlv zum Einsatz: used depending on ttie requirements of the application:
Linearization LB 3 8 4 4 / L B 3845 u. LB 3846 Linearization L B 3 8 4 4 / L B 3 8 4 5 or LB3846
(fest vorgegebene/einstellbare Linearisierung des (preset/adjustable linearization of density signal)
Dichtesignals)
Temperatur Kompensation LB 3822 Temperature Compensation LB 3822
(fur ein auf eine Bezugstemperatur kompensiertes (for a density signal compensated to a gFven refer-
Dichtesignal) ence temperature)
Grenzwert (Threshoid) LB 3862 Threshold LB 3862
(fur zwei innsrhalb des Bereiches beliebig einstell- (for two thresholds freely adjustable over the full range)
bare Grenzwerte)
Unused positions in the chassis are filled with blank
Die nichJ benotigten Ratze im Baugruppentrager sind modules C-'^'ith appropriate wire links) or covered with
durch Blindeinschube (mit entsprechenden Brucken) blanking plates.
bzw. durch Blindplatten ausgefullL
^ o r non-standards applications, different module con-
(Fur Sonderanwendungen konnen auch Bnschube in figurations can be housed in a specially v^ired chas-
andererZusammenstellung im spezialverdrahteten Bau- sis — in this case refer to the special wiring diagram.)
gruppentrager — siehe dann spezicllen Verdrahtungs-
|)!an — untergebracht sein.. .
m - :
t r.
;eo - O -
/
ie
j CO
g "
. o&
p

: oo oo H.
OJ
oo
( e> © o 0 ,
2 A B oo
M OOOQ I

LB 3897 Netzteil
Power supply

LB 3886 Anzeige
Analog Display

LB 3344 Linearization

LB 3822 Temperatur Kompensaticn


Temperature Compensation

LB 3831 Ratemeter

LB 3806-1
Adaption Unit
' 8. Montage 8. Installation
lie Abmessungen der MeBstrecke entsprechen beilie^ The dimensions of the measuring system are indicated
.giender Zeichnung 15113.002. Der Einbau in die Pro- on the enclosed drawing No. 15113.002. The connec-
duktleitung erfolgt uber die AnschluBflansche NW65ND tion to the product line is made through Ihe connecting
10 DIN 257& flanges supplied — inside dia. 65, nominal pressure 10
bar to DIN 2576.
Durch mechanisch soliden Aufbau der kompletten MeB-
strecke sind aile .Fehlermogiichkeiten, die sich durch The mechanically rigid construction of the complete as-
geometrische Anderungen in der Anordnung ergeben sembly eliminates all potential error sources which might
konnen, ellminlert. otherwise result from geometrical changes in the arran-
gement.
Besteht die Gefahr, daB sich im ProzeBrohr Luftblasen
Oder Ablagerungen und Anbackungen bilden konnen, If there is any risk of air bubbles, sediments or caked
so ist dafur Sorge zu tragen, daB sie sich nicht in der deposits forming in the process pipe it must be ensured
that they cannot accumulate in the measuring path. The
MeBslrecke festselzen. Die MeBanlage miBt die Absorp- measuring system measures the absorption in the fluid
tion im Medium (proportional zu DIchte mal MeSweg) (proportional to the density multiplied by the measuring
und somit bei nichl ganz gefulllem Rohr den ..Fullungs- path length), and when the pipe is not complelely filled
grad". Durch Montage in einer steigenden Oder senk- it therefore measures the "filling ratio". In most cases
rechten Leitung konnen Lufteinschlusse oder Ablage- trapped air or deposits .can be prevented by installing
rungen meist verhindert werden. the system in a rising or vertical line.
AuBerdem muB darauf geachtet werden, daB auf die It is also Important to ensure that no vibrations can
MeBstrecke keine Vibrationen iibertragen werden be transmitted to the measuring path.
konnen.
Changes in wall thickness (due to aggressive or
kWandstarkenanderungen {durch aggressive oderabras-
abrasive fluids) will also, affect the density reading.
'sive Medien) ergeben ebenfalls eine Anderung der Dich-
Attention is once more drawn to Sections 5 and 6 of the
teanzeige. Wr verweisen an dieser Stelle nochmals nach-
Operating Instructions.
druckilch aut Punkt 3. und 4. der Bedienungsaneitung.
The temperature of the scintillometer must not exceed
Die Temperatur des Szintiilometers dart 325 K ( + 5 0 ^ )
325 K (+ 50 °C). If necessary, the water cooling system
nicht ubcrsteigen. Wenn erforderlich, muB die serlen-
available as standard option must be connected (1/4"
maBig vorhandene Wasserkuhlung angeschlossen wer-
BSP thread) I
den (Gewinde R1/4").
(Versuche im Werk ergaben, daB bei Umgebungstem- (Work tests have shown that at ambient temperatures
peraturen urn 300 K mit einer Produkttemperatur von around 300 K and a product temperature of 355 K the
355 K die zulassige Temperatur von 325 K am Szintil- permissible temperature limit of 325 K is not exceeded
lometer nicht uberschritten wird). at the scintillometer).
Bei Dichtemessung mit Temperaturkompensation wird In the case of temperature compensated density meas-
ein Temperalurfuhler (PtlOO) zusatzlich an geeigneter urements an additional temperature sensor (R 100) is
Slelle in das Produktrohr eingebauL installed in the product line at a suitable point.
Das Szintillometer ist in Ex-geschutzter Ausfuhrung (Ex The scintillometer is supplied in a flameproof enclosure
d3nG5) ausgeiuhrt. Der MeBverstarker — je nach An- (Ex d 3n G5). The measuring amplifier — a 19" rack
wendungsfall als 19"-Einschub oder als 19"-Einschub in module or a 19" module in a field chassis (IP 55) de-
FeWgehause (IP 55) — ist dagegen in einem Bereich pending on the application — on the other hand must be
aufzustellen, in dem Ex-Schutz nichl erforderlich ist. located in an area where no explosion protection is
required.
9. Anschiiisse 9. Connections
Szintiiialionszahler und gegebenenfails Temperalurfuhter The scintillation counter and the temperature sensor (if
v/erden uber handelsubliche Kabel mil dem Dichte- provided) are connected to the density measuring unit
meBgerat verbunden, wobei 'uf den Szintillationszahter- through standard cables; a 7-core screened cable, e. g.
anschluB ein 7-adriges. abgeschirmtes Kabel (bis 100 m LIY-CY 7 X 1.5/155 or "Oiiflex" SY 7 x 1.5, for the sdntiliaii-
Z.B. LIY-CY 7X1,0/105. bis ca 500 m z.B. LIY-CY7X on counter and a 4-core cable for the temperature sensor.
1,5/155) und fiir den Temperaturfuhler ein 4-adriges Kabel
vorzusehen isl The connecting cable only carries low voltage as the
HV supply is generated and stabilized in the probe (Ger-
Das AnschluBkabel fuhrt nur Niederspannung, die Hoch-
man latent).
spannungserzeugung und -regelung (DBP) eriolgt in der
Sonde.

9.1 Szintillationszahler 9.1 Scintillation Counter


Nach Losen von 4 Zylinderschrauben M 5 x 12 kann der After releasing lour M 5X12 cap screws the cover of
Deckel des Szintiiiometers at^genommen v/erden, der the scintillometer can be removed, exposing the termi-
AnschluBraum liegt frei. Die Abschirmung des Kabels nal compartment The cable screen is connected to the
vvird koaxial mit Hilfe der Kabelschelle direkt hinter der housing coaxiaJJy by means of the cable clamp directly
Kabeleiniuhrung mit dem Gehause verbunden. Die Klem- behind the cable entry. Terminals 1 to 7 are connected
men 1 — 7 werden mit den entsprechenden Bngangs- to the corresporiding input terminals of the measuring
klemmen des MeBverstarkers verbunden, wobei im amplifier, cores 4 and 7 being taken to the appro-
Szintillationszahler die Adern 4 und 7 auf die entspre- priately marked terminals in the scintillation counter.
chend gekennzeichneie Klemme gelegt vyerden. Im ein- For further details see enclosed terminal diagram.
zelnen gilt der beiliegende AnschluBplan.

9.2 MeBverstarker 9.2 Measuring Amplifier


Die Anschlusse am MeBverstarker erfolgen an den The an-iplifier connections are made to the terminal strips
Klemmleisten auf der Ruckseite des Gerates gemaB An- at the rear of the unit as shown on the terminal dia-
schluBplan, v,/obei das KatDel sov/ohl angeklemmt als gram. The leads can be secured either with terminal
auch — nach Anbringen entsprechender Steckverbinder screws or by fitting cable lugs to the cable ends. The
an den Kabelenden — angesteckt werden kann. Dabei terminal strips are divided into several tenninal blocks,
sind die Klemmleisten in mehrere „BI6cke" aufgeteilt, separate blocks being provided for:
die im. einzelnen vorgesehen sind fur
Scintillometer connections
SzintillometeranschluB (7 terminals and green/yellow earth screw for cable
(7 Klemmen und grun-gelbe Masseschraube fur Ka- screen)
belabschirmung)
TemperatureSensor Connections
TemperalurfuhleranschluB (for f^ 100 in 4-wire network)
(fur R100 in 4-Leiterschaltung)
Outputs
Ausgange (0-10Vand0/4 - 2 0 m A )
( 0 - 1 0 V und 0 / 4 - 2 0 mA)
Thresholds
Grenz-A^erte (2 change-o\^contacts and 2 open-collector outputs)
(2 Umschaltkontakte und 2 open-collector) The main supply is connected to 3 temninals (live, neu-
Der NelzanschluB erfolgt iiber 3 AnschluBklemmen (Ph, tral, earth). Chec* for correct mains voltage.
Mp, Schutzleiter), auf die angegebene Netzspannung
ist zu achteni
'10. inbetriebnahme 10. Startup
^'br dem Snschalten des Gerates vvird die WeBstrecke Before switching on the system, the'measurlng path is
lil dem zu messenden Medium bekannter Dichte inner- filled with the fluid to be monitored, the density of which
ha!b des gewiinschien MeBbereichs gefu!lt(zur Beslim- is known and within the required measuring range (for
mung eines KontroIK^rtes bei leerem Rohr vergleiche determining a reference value with the process pipe
Abschnitt 15. „Nachkalibrieaing und Kontrollwert"). empty see Section 15 "Recalibration and Reference
Value").
Sinnvoll wird in der beschriebenen Reihenfolge weiter
vorgegangen. It is recommended to proceed as follows:

10.1 Power Supply LB 3897 (Netztell) 10.1 Power Supply LB 3897


NETZ-Schalter auf QN, die eingebaute Kontrollampe Set POWER switch to ON. The pilot lamps light up to
signalisiert die vorhandene Netzspannung. indicate that power is available.
Nach dem Einschalteri der Netzspannung benotigt die After the power has been switched on the automatic HV
Hochspannungsautomatik c a 20 Sekunden um auf ei- supply will need approx. 20 sec to stabilize at a value
nen Wert innerhalb ihres Arbeitsbereiches einzuregeln. within its operatitig range. The red FAULT light (LED) will
Wahrend dieser Zeit blinkt die rote Leuchtdiode STO- flash during this period.
RUNG.

10.2 Temperature Compensation LB 3822 10.2 Temperature Compensation LB 3822


(remperatur-Kompensation) (only for measurements with temperature
Ijnur bei Messungen mil Temperatur-Kompensation). compensation)
'potentiometer 0—300°C auf die mittlere Temperatur der Set 0—300 °C potentiometer to the mean temperature
ROssigkeit stellen (der Einsielibereich des 3-Gang-Poten- of the fluid (the range of adjustment to the 3-turn po-
tiometers entspricht 0—3(X)®C). tentiomeler is equivalent to 0 — 300 °C).
Potentiometer T.K. auf den gemaB Beispiel 1. berechneten Set TV potentiometer to the value calculated in accor-
Werl stelien. dance with Example 1 in Section 11.
Schiebeschalter in Stellung EIN bringea Set sliding switch to ON.

10.3 RatemeterLB3831 10.3 Ratemeter LB 3831


Schalter TRAGHEIT auf 1 (5 s) Adjust suppression u with the DENSITY RANGE poten-
Unterdriickung u aui der Skala des Potentiometers tiometer to the value indicated in the table in Section 5
BEREICH auf den in der Tabelle unter Abschnitt 5. ,.Me3- "Measuring Principle" (max. adjustment — 20 scales
prinzip" angegebenen Wert einstcllen (max. einstellbar suppression x 10 V per s c a l e 2 0 0 V).
sind 20 Skalen Unterdruckung x lO V pro Skala - 200 V). The setting range is sv/itch selectable between 0—lOOV
Der Bnstellbereich ist durch den Schalter auf 0—100 ( 0 - 1 0 scales) and 1 0 0 - 2 0 0 V (10-20 scales).
( 0 - 1 0 Skalen) und 1 0 0 - 2 0 0 V (10-20 Skalen) um- One full turn of the potentiometer is therefore equivalenl
schaltbar. to 10 V (1 scale).
Bne Umdrehung des Polenliometers « iOV (1 Skala).

.10.4 Adaption LB 3806 10.4 Adaption U n i t L B 3 8 0 6


f (Sonde nanpassung) Set sliding switch HV to AUTO.
Schiebeschalter Hochspannung auf AUTO Using the 4-decade switch, adjust the reading to the
Mil dem 4-stufigen Dekadenschalter wird die Anzeige value which corresponds to the density (see SK 974).
auf den der Dichte entsprechenden Anzeigewert ein- Increasing the numerical value will shift the indicator
gestellt (siehe hierzu SK 974). Eine VergroBerung des towards zero or lower densities, and reducing it will shift
Zahlenwertes bev/egt datjei den Zeiger nach unten (in the indicator towards 10 V or higher densities.
Richtung 0 bwz. kleinere Dichte), eine Verkleinerung nach The "sensitivity" potentiometer on the ratemeter LB 3831
oben in RIchlung 10 V (zu groBer Dichle). provides an additional fine adjustment.
Mil dem Potentiometer „Empfindlichkeit" am Ratemeter,
LB 3831 kann noch eine Feineinstellung der Empfindlich-
keit vorgenommen werden.

10
11. B e i s p i e t l 11. Example 1
(Der MeBweg isl fest vorgegeben durch den Innendurch^- (The length ot the measuring path is fixed by ihe inside
messer des MeBrohres zu 6,8 cm*). diameter of the measuring pipe which is 6,8 cm*).
Bei ausgekleideter MeSstrecke (FTFE, Gummi) ist der When a lined measuring path is used (PTFE, rubber)
Faklor im Verhaltnis der Durchmesser zu korrigieren, Ihe factor must be corrected in proportion lo the dla-
z B . bei 6,2 cm Innendurchmesser zu meler, e. g. with an inside diameter of 6,2 cm as follows:
9500 6,2 = 8660 X 6.2 = 8660
6.8 b.o
•) Er ist in die Einstellwerte eingerechnet, braucht also *) This is already included in the settings and does not
nicht mehr berucksichtigl zu werden. have to be allowed for separately.
Zu messen sei eine Zuckerlosung im Berelch 60—80° Ruid monitored: sugar solution within the range 60—80°
Brix entsprechend 1,289—1,415 g/cm^ Die mittlere Tem- BrIx, which is equivalent to 1.289—1.415 g/crn^. The mean
peratur sei 50 der Temperaturkoeffizient temperature is 50°C, the temperature coefficient

0,0006 0.0006
cm3 cm-'
Der (im Werk) errechnete Bnsteilwert u — in der Tabelle The setting u (calculated by the manufacturer), which the
(Sella 5) als Beispiel eingelragen — ist Table on page 5 quotes as an example, is
u = 86,8 V (8,68 Skalen) u = 86,8 V (8,68 scales)
Der einzustellende Wert am Potentiometer T.K (Einschub- The setting of the TC potentiometer (TEMP. COMP. mo-
TEMP. COMP.) errechnet sich aus dule) is calculated from
T.K = 9500 X Teniperaturkoeffizient x Absorptions- TC — 9500 X temperature coefficient x absorption
koeffizient coefficient

und mil dem Absorptionskoeffizient aus Tabelle Seite 9 and with the absorption coefficient from the Table on
page 7
T.K. - 9500 X 0,0006 x 0.162 - 0,92
TO = 9500 X 0,0006 x 0.162 0.92
Damil ergeben sich lur das Beispiel folgende Einstel-
lungen: This produces the following settings for our example:
Am Ratemeler LB 3831 On Ratemeler LB 3831
Poti BEREICH (=Unterdruckung) 86,8 V RANGE potentiometer 86,8 V
(8.68Skaleti) (suppression) .-^8,68 scales

An TEMP. COMP. LB 3822 TEMP. COMP. LB 3822


0 - 300 °C potentiometer 050
Poti 0 - 3 0 0 °C 050 TC potentiometer 092
Poti T.K 092

11
12. Wie ist vorzugehen, 12. How to Proceed when no Information is
wenn keine Angaben in derTabelle Given in Table on Page 7
^ Seite 5 eingetragen sind?
Es besteht die Mdgllchkelt, daB bei der Projektierung It is possible that the exact data of the application were
der DichtemeGanlage im Werk die genauen Daten des not known v/hen {tie Density Measuring System was pre-
MeBproblems nichl bekannt waren, daB die Daten nicht pared by the manufacturer, that the data have not been
in die Bedienungsanleitung ubertragen wurden oderdaB transferred into the operating instructions, or that the
die Originalbedienungsanleitung nicht vorliegt. Prinzipieil original operating instructions are no longer available, in
bestehen dann folgende Moglichkeiten, urn eine Inbe- that case there are the following basic possibilities of
triebnahme init vernunfligem Aufwand (ohne zig-faches using the system without an unreasonable amount of pre-
Umfuilen zwischen zwei Dichtssverten) vorzunehmen. paration O-S-without countless refilling be^^/een two
density values).
Ein Anruf im Werk mil genauer Schilderung des MeB-
problems fuhrt zur Berechnung der Einstellwerte. Im A telephone call to the manufacturer with an accurate
Regelfall kann diese Berechnung kurzfristig durchgefuhrt description of the measuring application will allow the
werden, ^ n e Berechnung vor Ori laBt sich wegen der settings to be calculated. This calculation can normally be
Komplexitat bei Americium-Dichte-Messungen nicht carried out at short notice (a calculation on the spot is
durchfuhren.) impracticable because of the complexity of Americum
density measurements).

12.1 BestimmungderUnterdruckungu(=Einstellwert
des Potentiometers BEREICH)
Eine erste ungefahre Bestimmung der Unterdruckung
nn aus der folgenden Tabelie entnommen werden. Die
enaue Bestimmung erfolgt dann, vvie unter Abschnitt
„Kalibrierung", Seite 9, beschrieben.
ACHTUNG!
Die Tabellenv/erte sind nur ungenau und nur fur eine
erste Einstellung gedacht. wenn keine genaueren An-
gaben vorliegen!

Bnsteliv/erte Unterdruckung u (v) (Poli BEF^EICH)


mit/ohne Linearisierung LB 3844

mit Absofptlonskoeffi2ient * fur:


MeBbereich
A p(g/cfn3) M CH, CHOH AljOa Ca{0H)2 H2SO4 HCL

0.175 0,170 0.165 0.205 0.430 0,235 0,460

0,05 172/116 178/120 183/124 148/100 73/50 130/88 68/47


0,10 89/ 61 91/ 62 94/ 64 77/ 53 39/28 68/47 37/26
0,20 47/ 33 48/ 34 50/ 35 41/ 29 22/16 36/26 21/16
0,30 33/ 24 34/ 24 35/ 25 29/ 21 17/13 26/19 16/12
0,40 26/ 19 27/ 20 27/ 20 23/ 17 14/11 21/16 14/11
0,50 22/ 16 22/ 16 23/ 17 20/ 15 18/14
- 0,75 17/ 13 17/ 13 17/ 13 15/ 12 14/11
1.00 14/ 11 14/ 11 15/ 12

*) Die Wcrte fur u sind nur angenahert. Fur die erste Bnslellung konnen die Werte jedoch fur gleichartige Stoffgruppen aus derTabelle
enlnommen werden ^ B. fur Kohlenwasserstoffeaus der CHj-Spalte). Im Zweifelsfalle kleinere Weiteeir\stellen, um Utsersteuerung des
Verstarkers zu vermeiden!

Angenahert kann die etfordeiliche Unterdruckung u auch wie folgi berechnet werden:

ohne Uneatisierung mit Linearisterung


.u —10 1 inV
-1-1 u- 20
/ 3

' bei susgckleideter MeSstrecKe tatsScWichen Innenraumdurcruiiessef in (cm) berucksichilgen!

12
12.1 Calculating the Suppression u
. ( = setting of DENSITY RANGE potentiometer)
A first approximate determination of the suppression can
be made with (he Table below. An accurate determination
can then foliow as described under "Calibration" on
page 12.
IMPORTAhfT!
The figures in the Table for guidance are only intended
for an approximate adjustment when no detailed infor-
mation is available.

Settings for Suppression u {DENSITY RANGE) potentiometer)


with/without Linearization LB 3844 in v

with absorption coefficient * for:


Meas. range
A p (g/cm3) HjO CH2 CHOH AI2O3 Ca{0H)2 H2SO4 HCL

0.175 0.170 0,165 0.205 0,430 0,235 0,460

0.05 172/116 178/120 183/124 148/100 73/50 130/88 68/47


0.10 89/ 61 91/ 62 94/ 64 77/ 53 39/28 68/47 37/26
0.20 47/ 33 48/ 34 50/ 35 41/ 29 22/16 36/26 21/16
0,30 33/ 24 34/ 24 35/ 25 29/ 21 17/13 26/19 16/12
0,40 26/ 19 27/ 20 27/ 20 23/ 17 14/11 21/16 14/11
0,50 22/ 16 22/ 16 23/ 17 20/ 15 - 18/14 -

0.75 17/ 13 17/ 13 17/ 13 15/ 12 - 14/11 -

1,00 14/ 11 14/ 11 15/ 12 — — — —

•) The values for u are approximate only. For adjustment, however, the values for similar types of material can be taken from the Table
(e.g. for hydrocartwr^ from the CHg oalumn). V\'her) in doubt always select a lower value to prevent overloading the amplifier!

An approximate calculation of the required suppession u can also made be as follows:

witfxjut Linearization with Linearization

u-10 1 +1 in V 20 1
u — + 0.5 + 5
eAp-Ti-6.8**_, J 3 'J

" ) in tho caso of lined measuring paths uso the actual inside diameter in (cm) I

%fi)C -

13
12.2 Besttmmung des Einstellwertes fur den 12.2 Determining the Temperature Coefficient
^ ^ Temperaturkoefflzjenten (Potentiometer T.K.) Setting (TC Potentiometer)
^ ^ v l i t dem Wert u (aus vorstehender Tabelle) kann der Based on the value for u (from Table atx)ve) the appro-
Einstellwert fur das RDtentiometer T.K. gemaS Beispiel 1 ximate setting for the TC potentiometer can be deter-
(Seite 11) ungefahr ermittelt wefden. mined in accordance with Example 1 (page 11).
Ist kein geeigneter u-Werl in der Tabelie enthallen bzw. If the Table gives no suitable u value, or in case a more
fur die genauere Besiimmuhg, kann experimentell wie accurate determination is necessary, the foltowing
tolgt vorgegangen werden: experiment will be found useful:
Die MeBslrecke vvird mil Produkt gefullt. (Dabei wird die nil the measuring path with liquid product (the closer the
ErnniUlung des EinstelKverles umso genauer, je genauer conditions during this experiment reflect the reallife den-
die betriebsmaBige Dichte und die betriebsmaGige Tem- sity and temperature, the more accurate the resulting
peratur mit den Versuchsbedingungen ubereinstimmen.) setting will be). The 0 - 3 0 0 ° C potentiometer is set to the
Das Potentiomeler 0— 300 ®C wird auf den Wert fur die value representing the existing temperature. The TC
vortiandene Temperatur eingestellt. Das Potentiometer potentiometer is adjusted so that the reading does not
T.K wird so eingestellt, daB sich bei Erwarmen oder Ab- change v/hen the temperature of the fluid monitored rises
kuhlen des K4eBgutes keine Anzeigeanderung ergibt. or drops.
Wandert die Anzeige beim Erwarmen (bzw. beim Ab- If the indicator shifts towards a lower density as the
kuhlen) zu kleinerer Dichte (bzw. groBerer Dichte beim temperature rises (or to a higher density as the temper-
Abkiihlen), so ist unterkompensiert und der Einstellwert ature drops), then the system is under-compensated and
T.K entsprechend zu vergroBern (und umgekehrt). the TC setting must be increased accordingly (and vice-
versa).
ACHTUNG!
Der Temperaturluhler muB fur diesen Versuch die glei- IMPORTANT!
che Temperatur wie das MeSgut annehmen konnen For this experiment the temperature sensor must be
emperatur-Ubergangszeiten beachten)! capable of reaching the same temperature as the fluid
(note temperature stabilisation times)!

13. Anzeigetragheit 13. Indicator Time Constant


(Ratemeter LB 3831) (Ratemeter LB 3831)
Bei betriebsmaBig sehr langsamen Dichteanderungen If the rate of density changes is inherently low it is
empfiehit sich die Einstellung TRAGHEIT 3 (60 s), da bei recommended to select TIME CONSTANT 3 (60 s)
groBerTragheit die statistischen Anzeigeschwankungen because the statistical fluctuations of the reading become
kieiner sind (die hohere Ablesegenauigkeit nach dem smaller as the time constant increases (the higher accu-
Umschalten auf groBere Tragheit kann eine geringe racy of reading after switching to a longer time constant
Nachstellung erfordcrn). Sind schnelie Dichteanderun- may require a slight readjustment). Where fast density
gen zu enA/arten, so muR mit TRAGHEIT 2 (30 s) oder 1 changes are expected, the settings TIME CONSTANT 2
(5 s) gearbeitet werden. (30 s) or 1 (5 s) should be selected.
W V i Ird nur die Tragheit umgeschaltet, so bleibt die mitt- If only the time constant is changed then the mean
~ e ere
r Anzeige erhalten. Bei Umschaltungen bzw. Einstel- reading v/ill remain unchanged. Therefore, when set-
lungen am Gerat, die Anzeigeanderungen verursachen tings are changed oradjustments made which may alter
(wie z. B. bei der Inbetriebnahme bzw. Kalibrierung der the reading (e. g. initial startup or calibration of the system)
Aniage), empfiehlt sich deshalb. zunachst mit TRAGHEIT it is recommended to select initially TIME CONSTANT 1.
1 zu arbeiten. Ist der Anzeigeendwert ungefahr erreicht. Once the final reading is being approached, the system
wird wieder auf die groSere Tragheit zuriickgeschaltet. can be switched back to a longer time constant.

14
14. Kalibrierung der Antage 14. Calibrating the System
Wie bei alien elektronischen MeBgeraten hochster Pra- As v/iih air high-precision electronic measuring systems,
zision sollte auch beim DichtemeBverstarker die end- the density measuring amplifier should only be finally
giiltige Einslellung auf den ge^Aajhschten DichtemeBbe- adjusted to the required density range after the unit'had
-reicii erst vorgenommen werden, wenn das Gerat einige been switched on for several hours.
Stunden eingeschaltet war.
The physical law of y ray absorption implies that its
Das Schwachungsgesetz fur Y-Strahler ergib! physika- variation v/ith the density follows an exponential func-
lisch eine exponentielle Abhangigkeit von der Dichte. tion. At small density ranges or with high suppression
Bei kleinem Dichtebereich bzw. hoher Unterdruckung (u > 5,5 scales) this dependence is virtually linear even
(u > 55 V (5,5 Skalen) ist die Abhangigkeil auch ohne without additional linearieation unit.
zusatzliche Unearisierungseinheit fast linear.
Setting the system to a given density value in conjunc-
Die unter Punkt 10. beschriebene Gerateelnstellung auf tion with the suppression calculated by the manufacturer
einen oinzigen Dichtewert in Verbindung mit der im Werk (description see Section 10) will, for example, be sufficient
berechneten Unterdruckung genugt beispielsweise zur for controlling a certain nominal density value or for
Regelung auf einen bestimmten Dichtesollwert Oder zur differentiating between different densities (this method
Unterscheidung verschiedener Dichtewerte. (Sie isl in will always be more accurate than an "uncontrolled"
jedem Fall genauer afs eine„unkontrolliefte" Versleltung adjustment of all parameters).
aller Parameter.)
We therefore recommend to start with the above set-
Wir empfehlen aus diesem Grund, mit dieser Einstellung tings and to carry out the calibration described below only
zu beginnen und die im folgenden beschriebene Ka- when a check shows unacceptably high deviations from
librierung nur vorzunehmen, wenn sich unzulassig hohe the standard values.
Abweichungen bei der Kontrolle zeigen sollten.
An accurate absolute measurement over the full range,
Eine genaue Absolutmessung im ganzen Bereich er- however, requires at least two fillings of the measuring
fordert mindeslens zwei Fullungen der fvleSslrecke bei path with fluids of widely diverging densities v/hich are
moglichst verschiedenen Dichten innerhalb des MeBbe- still within tfie overall measuring range. At a given known
reiches. Bei bekannter Unterdruckung erhalt man fur den suppression, the shape of the calibration curve for the
Verstarker ohne Linearislerung die Form der Eichkun/e amplifier without linearization unit is shown on the en-
aus der beiliegenden Zeichnung SK974. closed drawing SK 974.

15
14.1 ICalibrierung ohne Linearisierung (mit Beispiel 2) 14.1 Calibration wHhout Linearization
(Nur durchlesen. wenn in den Verslarker weder Einschub (with Example 2)
LB 3844 noch LB 3845 Oder LB 3846 eingebaut ist). (Only applicable lo amplifiers not including modules
Die relative Dichteskala auf der beiliegenden Zeichnung LB 3844 or LB 3845 or LB 3846).
' SK974 wifd ersetzt durch die gewunschte absolute Dich- The relative density scale on the enclosed drawing
teskala. Der Kurvenschar wird die der Unterdruckung u SK 974 is replaced by the required absolute density scale,
zugehorige Efchkurveentnommen (im gezeichneten Bei- and the calibration curve corresponding to the cal-
spiel 2: u - 20 V (2 SkalOT]). culated suppression u is selected from the family of
Man fulll die MeBstrecke mit Flussigkeit kleiner Dichie curves (in Example 2 below: u - 2 scales = 20 V).
Pi und stent durch Anderung.am 4-stufigen Dekaden- The measuring path is filled with liquid of low density
schalter die Anzeige auf den Sollwert A, (im Beispiel p ,and the reading is adjusted with the 4-decade switch
2,0 V), wobei eine VergroOerung des Zahlenwertes den to the nominal value A, (in our example 2.0 V), any
Zeiger in Richtung OVbewegt. .increase in the numerical value shifting the indicator
towards OV.

Beispief 2 Example 2
Dichte p = 1,0 2,0 g/cm^ Density p = 1,0 2.0 g/cm3
alter Einstellwerl BEREICH u = 20 V (2 Skalen) old DENSITY RANGE setting u = 20 V (2 scales)
Wird nun umgefullt aut groBe Dichte p2, so wird im all- When the measuring path is refilled with the higher
gemeinen ein vom Solfwerl A2 (im Beispiel 8,9 V) ab- density liquid Psthen the reading A2' obtained (in our
v/eichender Istwert ^ Beispiel 8.3 V) abgelesen. example 8.3 V) will generally deviate slightly from the
Die Unterdruckung ist jeizt zu andern auf den neuen expected nominal value A j (in our example 8.9 V). In
Wert V. that case the suppression must be changed to the new
value V.
v = (u-5) Ag-A i + 5
A2'-A,
v-(u-5) + 5
Der neue Wert v wird am Poti BEREICH eingestellt V-A,
und anschlieBend mit dem 4-stufigen Dekadenschalter
auf den Sollwert A j fim B ^ i e l 8,9 V) eingestellL The RANGE potentiometer is set to the new value v,
and finally the 4-decade switch is adjusted to the nominal
=•(20 ~ 5) 2.0 + 5 == 21,4V(2.14 Skalen) value for A2 (in our example 8.9 V).
8,3-2,0
V = (20 - 5) ~ ^ Q + 5 = 21,4 (2,14 scales)
neuer Einstellwert BERBCH v ~ 21,4 (2,14 Skalen) 8.3 - 2.0

new DENSITY RANGE setting v = 21,4 V (2,14 scales)

fimax
Dichte [g/cm3]

16
1 4 ^ Kalibrierung mit Linearisierung 14.2 Calibration y/ith Linearization
(Nuf durchlesea wenn die Einschube LB 3844 / LB 3845 (Only applicable to amplifiers incorporating modules
Oder LB 3846 in den Versiarker eingebaul sind). LB 3844, LB 3B45 or LB 3846).
Fur einen linearen Zusammenhang zwischen Anzeige Special linearization units are used to obtain a linear
.(Ausgangssigna'sn) und Dichle werden spezielle Lineari- correspondence between tfie instrument reading (output
sierungseinheiten vewendeL Linearisierung ist Z-B. er- signals) and the density.
forderiich, weiin die Dichtemessung fur die Bilanzierung Linearization is necessary, for example, when (he den-
(eventuell in \fefbindung mil einer Durchfluf5mc6ein- sity measurements are used for preparing a material
richtung) verv\'ende{ wird. Wunschenswert ist Linearisie- balance (possibly in conjunction with a flow meter).
rung oft bei Einsteltv/erten u < 55 V (5,5 Skalen). Linearization is often desirable for suppression settings
of u < 55 V (5,5 scales).'
BiUe FuBnote bei Tfi (Seite 20) beachten! See footnote at 76 (page 20), please!

1 4 ^ 1 Standan^Unearisierung LB 3844 14.2.1 Standard Linearization LB 3844


(mIt Beisptel 3) (v/ith Example 3)
Man fullt die M ^ t r e c k e mit Russigkeit Kleiner Dichte The measuring path is filled with liquid of low density
P, (im Bespiel 1,05 g/cm3) und regelt mit dem 4-stu- p, (in our example 1.05 g/cm3) and the instrument
figen DekadenschaJter genau auf den Sollwert fur p, reading is accurately adjusted with the 4-decade switch
ein (Im Beispiel 1.0 NO- to the nominal value for p, (in our example 1.0 V).
Nach Bnfulien groBer Dichte p2 (im Beispiel 1,45 g/cm^) After refilling with liquid of high density P2 (in our ex-
wird sich im aBgemeinen nicht der Sollwert f(jr pj (im ample 1.45 g/cm3) it will generally be found that the
Beispiel 9,0 V), sondern ein mehr oder weniger davon actual reading obtained the nominal value for pg (in
abweichender Istwert (Im Beispiel 8,0 V) ergeben. Man our example 9.0 V). Next, the density P2' associated v/ith
liest die dem Istwert zugehdrige Dichte pg' ab (im Bei- the actual value is read off (in our example 1.40 g/cm^),
spiel 1,40 g/cm3) und errechnet daraus den Wert v and from this the value v is calculated (see Example 3).
(siehe Beispiel 3).
1
1 v=(u-5) + 5
v = (u-5) + 5 1 + P2 (22 - e-^--" • n - (P2 - Pi)
1 Pj • e-3.4 n -(P2"pi) P2-P,
P2-P,
T| from Table on page 5
T1 aus Tabelle Seite 5 The DENSITY RANGE potentiometer is set to the new
Der neue Wert v wird am Poti BEREICH eingestellt und value v. and finally the 4-decade switch is adjusted to
anschlieBend mil dem 4-stufigen Dekadenschalter auf the nominal value for P2 (in our example 9.0 V).
den Sollwert p^ Om Beispiel 9,0 V) eingeslellt.

Beispiel 3 Example 3

Dichte: 1,0 .....1,5 g/cm^ Density: 1.0 1.5 g/cm^

alter Elnsteilwert u: 13 V (1,3 Skalen) old setting u: 13 V (1,3 scales)

neuer Einsteltweit v: 13,9 V (1,39 Skalen) new setting v: 14 V (1,39 scales)

1
5 - 13.9 V (1.39 Skalen)
X e-3'4 X 0,162 (1.45 - 1.05)
' ^1.45 - 1

17
lA^.i Einstelibare Linearislerung 14.2.2 Adjustable Linoarization
L B 3845 Oder L B 3846 LB 3845 Or LB 3846
Bel Verwendung derUnearisierungseinheit LB 3845 muB When using the Linearization Unit LB 3845, the RANGE
ein fester Wert am Roti BEREICH eingestellt sein. Der potentiometer must be set to a fixed value. The precise
genaue Wert ist am Poll angegeben, er darf nicht ver- setting is marked on the potentiometer and must not be
andert v/erden. altered.
(Wljrde versehentiich die Bnslellung verandert, so kon- (If the setting has inadvertently been altered the following
nen folgende Werte eingestellt werdea values can be adjusted.
bei LB 3845-1/1 30V for LB 3845-1/1 30V
beiLB3845-2/1 19V for LB 3845-2/1 19 V
bei LB 3845-3 OV for LB 3845-3 OV
bei LB 3846-1+2 OV for LB 3846-1+2 OV
An der Unearisierungseinheit wird am Poti SPRBZUNG The SPREAD potentiometer on the Unearization Unit is
^ der Im Wetk errechnete Wfert adjusted to the
Spretzung S - (slehe Tabelie Seite 5} SPREAD S = (see table page 5)
eingestellL Die MeBstrecke wird mil Russigkeit kleiner value calculated by the manufacturer. The measuring
Dichte p, gefiiJIt. mil dem 4-stufigen Dekadenschalter path is filled with liquid of a known low density p /
v/ird der Sollwert fur p, genau eingeregelL Nach Umful- and the 4-decade switch is set lo the exact nominal
ten auf pjwifd die Anzeige kontrolliert. value for p,. After refilling with pj the display is checked.
&gibt sich eine Abweichung, so wird analog der Abbil- If a deviation is found, then the new SPREAD value is
dung bei Beispiel 3 (Setle 11) die neue Spreizung er- calculated as illustrated in Example 3 (page 13) as
rechnet zu: follows:

S, - (S+RV) - RV
A2'-A, S, = (S + R v ) ^ 2 ^ - R v
A2 A,
RVbei Rvfor
LB 3845-1/1 - 2.49 LB 3845-1/1 2.49
LB 3845-2/1 - 2.49 LB 3845-2/1 2.49
LB 3845-3 - 4.32 LB 3845-3 4,32
IB3846-1+2 -16.9 LB 3846-1 + 2 16,9

und dieser neue Wert am Potentiometer eingestellt An- and the Sf^EAD potentiometer is adjusted to this new
schlieBend wird mil dem Dekadenschalter auf den Soll- value. Finally, the decade switch is adjusted lo. the
kwert A2 fur p^ nachgeslellL nominal value A2 for p^.

18
15. Nachkalibnerung und Kontrollwert 15. Recalibration and Reference Value
Durch die groQe Halbwertszeit von 24iAm (433 Jahre) Due to the long half-life of ^-^Am (433 years) the annual
betragt der jahrliche Intensitalsverlust der Slrahlung nur intensity decay of the radiation is only 0.16 %. This means
0,16 %. Dies bedeutet, daB fur nahezu alle MeBprobleme that one annual recalibration of the sensitivity will be
eine jahrliche Nachstellung der Empfindllchkeit aus- sufficient for practically all applications. Recalibration in
reichend ist Lediglich Messungen mil extremer Anfor- six month intervals will only be necessary where extreme
derung an die Genauigkeil erfordern eine halbjahrliche accuracy is demanded.
Nachstellung.
Hierzu wird bei bekannter Dichte (z.B. uber Proben- To adjust the sensitivity, set the 4-decade switch to the
nominal value for a given known density, or alternatively
nahme) bzw. bei leerer MeBstrecke mil dem 4-slu(igen
to the reference value while the measuring path is left
Dekadenschalter auf den Sollwert fur die Dichte bzw. den
empty.
Kontrollwert (bei leerer f\/leSstrecke) nachgestellt.
Zur Schaffung eines Kontrollwertes (zur gelegentlichen In order to obtain a reference value (for occasional checks
Nullpunktkontrolle des Verstarkers) kann es vofteilhaft of the amplifier zero setting) it is advisable to proceed as
sein, bei vollig entleerlem MeBrohr mit dem 4-stufigen follows: Drain the measuring pipe conipletely sel the 4-
Dekadenschalter eine Anzeige in der Nahe der Skalen- decade switch to obtain a reading near midscaleand note
mitte einzustellen, und diesen Wert und den zugehori- down both this reading and the corresponding switch
gen Einstellwert 2u notieren. Der Kontrollv/ert solite erst setting. The reference value should only be determined
nach endgiiitiger Kalibrierung bestimmt werden, wenn after final calibration when the suppression (RANGE po-
die Unterdruckung (Poti BEREICH) nicht mehr verandert tentiometer) will not be altered any more.
wird.
Spannung Volt Potential Volts
an dsn TesitMcrisen 0 -10 V at test sockets 0 - » v
<3es Ralemeters 163831 of ratemeler LB3831

Kontrollwert . Reference value


on decade swixn
am Dekadenschalter

Durch diesen Test wird gleichzeitig die eingestellte Un- This test at the same time checks the preset suppression
terdruckung und damit die Stabllitat der Versorgungs- and consequently of the supply voltage.
Spannung uberprufL IMPORTANT!
ACHTUNG/ Because of the high detection sensitivity of the Density
•Wegcn der hohen Nachv^/eisempfindlichkeit der MeB- Measuring System the pipe must be completely drained
anlage fur Dichteunterschiede mud das Rohr vollig ent- as even minute traces of liquid will alter the reading.
leert sein. da schon geringste Mengen Material eir)e Following the manual sensitivity adjustnient the reference
andere Anzeige ergeben. value should also be determined again (with maximum
Nach der jahrlichen Empfindlichkeitsnachstellung sollte suppression (20 scales] the natural radiation decay will
auch der Kontrollwerl neu bestimmt v/erden (der natCir- change the potential across the RANGE potentiometer
liche Sirahlerzerfall bewirkt bei voll aufgedrehter Unter- by approx. 0.3 V per annum).
driickung f20 Skalen] am Potentiometer BEREICfH eine
jahrliche Anderung von ca. 0,3 V).

19
16. Umkalibrierung 16. Recalibration
auf anderen DichtemeBbereich to Different Density Ranges
Soli die DichtemeBanJage an ein geandertes MeGpro- To adapt the density measuring system to a dilierent
blem angepaBl werden, so wird dazu wie foigt vorge- application, proceed as follows:
gangen:

16.1 VergroBerung Oder Verklelnerung 16.1 increasing or Decreasing the Range


d e s MeBbereichs bei gleichem MeBmedium for the Same Liquid
Der •nsteiiwert fur die Urtferdruckung Ui (Potentiometer The suppression setting ui (DENSITY RANGE potentio-
BEREICH) wird auf d a i neuen Wert U2 wie folgt geandert: meter) is adjusted to the new value U2 as follows:

u? = (Ui - 5) X 5
Beispiel: Example:
A p j - 0,126 g/cm3
A Pi =0.126 g/cm3
Ui = &6^V(8,68 Skaien)
u, = 86,8 V (8.68 scales)
A p2 — 0,150 g/cm3
Ug - (86.8 _- CN . a i 2 6 + 5 " 73,8V(7^8 Skaien)
5) A p 2 " 0.150 g/cm3
0.150
U2 = (86.8-5) x ^ ^ + 5 - 7 3 , 8 V ( 7 , 3 8 s c a l e 3 )
Bei grpBeren Andenmgen empfiehit sich anschlieBend
leine Uberprufung urKJ gegebenenfalls genaue Einstel-
!ung gemaB Punkt 14. der Bedienungsanleitung. In case of major changes v/e recommend a subsequent
check and. if nccessary, accurate readjustment as des-
cribed in Section 14 of the Operating Instructions.

16.2 Einsatz der MeBanfage fur ein anderes MeB- 16.2 Using the System for a Different Application
problem (und ein anderes MeBmedium) (and a different Liquid)
Die ersten Einstellwerle fur das MeBproblem sind gemaS The initial settings for the application concerned are
Punkt 12. der Bedienungsanleitung zu bestimmen. Die determined in accordance v/ith Section 12 of the Oper-
genaue Bnstellung erfolgt gemaS Punkt 14. der Bedie- ating instructions. Rnal adjustment is made as described
nungsanleitung. in Seclion 14 of the Operating Instructions.
ACH7UNG! IMPORTANT!
Bei MeOverstarkern mit Unearisierung LB 3844-1 sollte When using amplifiers with linearization LB 3844-1,
bei Anderung des BnsteOwertes fur u urn grower ca. another submoduie should be inserted into the linea-
2VA0.2 Sf<aJen ein neuer Subeinschub in die Uneari- rization unit for alteration of the setting of u for more
sierung eingesetzt werdenJ than approx. 2 V^0.2 scales
Fragen Sis im Zweifelsialle in einem unserer Buros Oder In case of doubt, ask one of our agents or the factory.
im Werk nach.

20
17. Szintitlometerspannung 17. Scintillometer Voltage
(Hochspannungseinheit im Szintillometer.-Kontrolle und (HV supply in scintiliometer-check and adjustment with
Einsteilung in ADAPTION LB 3806). ADAPTION UNtT LB 3806).
Urn Alterungs- und Temperatureinflusse unwirksam zu In. order to counteract ageing and temperature effects,
machen, wird die Hochspannung automalisch so ge- the HV supply is automatically regulated (German patent)
regeU (DBP), daB dte ImpulsgroSe nach Verstarkung so that the pulse amplitude always remains constant
konstant ist Priftstabi(isierung). Eine EInsteliung der after amplification (drift stabilisation). This obviates the
Szintiilometerspannung fur den Betrieb erubrigt sich s o need to adjust the scintillometer voltage during normal
mit (Schalterstellung AUTO). Die Schalterstellung MAN operation (switch position AUTO.). The WAN. (manual)
(manuell) dagegen erlaubt eine Funktionskontrolle des switch position, however, permits performance checks of
Szintillationszahlers, speziell des Fotovervielfachers. Mit the scintillation counter, and especially of the photo-
dem sich uber dem Schiebeschalter befindenden mehr- multiplier. In this switch position the HV supply can be
gangigen Potentiometer kann die Hochspannung in die- adjusted between 500 and 1500 V by means of the multi-
ser Stellung im Bereich zwischen ca. 500 — 1500 V turn helipot above the sliding switch, tf the HV supply is
verandert werden. Stellt man die Hochspannung ein, auf adjusted to that voltage at which the amplifier operates
die der Verstarker in Stellung AUTO einregelt (die Hoch- (reference voltage across the output sockets, 1 V across
spannung kann uber eine Referenzspannung an den the sockets being equivalent to 300 V HV) then a change
Ausgangsbuchsen genau gamessen werden. wobei 1V in reference voltage by approx. ± 0.3 V (equivalent to
Spannung an den Buchsen 300 V Hochspannung ent- approx. ± 90 V HV) must only cause a slight change in
spricht), so darf eine Anderung der Referenzspannung indicator reading (operating point along the voltage
urn c a ± 0,3 V {entspricht ca. ± 90 V Hochspannung) nur pjateau) — major changes indicate a fault in the scin-
eine geringe Anzeigeanderung bewirken (Arbeitspunkt tillometer.
im Spannungsplateau). Bei groBeren Anderungen der
Anzeige liegt ein Defekt im Szintillometer vor. If, in the AUTO mode, the automatic HV supply is unable
to establish an operating point within its range of control
Kann die Hochspannungsautomalik in Stellung AUTO then this is caused by a scintillometer fault (or a con-
keinen Arbeitspunkt innerhalb ihres Regelbereiches ein- tinuity fault). The faults are indicated by a flashing "FAULT"
stellen, so liegt ein Defekt im Szintillometer (oder eine light (LED).
Leitungsunterbrechung) vor. Diese Storung wird durch
Blinken der Leuchtdiode STORUNG signalisiert.

21
18. Einsteliung der Alarme 18. Alarm Threshold Setting
(EinschubLB3861) (Module LB 3861)
Die beiden Relals der Doppel-Grenzwert-Einheit sind vom The two relays of the dual threshold unit are preset by
Werk als MAX.- (A) und MIN.-Relais in Ruhestromschal- the manufacturer as normally closed HIGH (A) and LOW
tung ausgelegt, d. h., beide Relais sind im ..normalen" (B) relay, contacts, i.e. the relays are energised within
Dichtebereich angezogen und fallen beim Eintreten des the norma! density rar>ge and drop out when the threshold
2u alarmierenden Betriebszustandes (oder bei Netzaus- value is exceeded or the mains supply should fail. This
fal!) ab. Sie bieten mil dieser Schaltungsarl hochsle circuit configuration offers maximum alarm reliability. A
Alarmsicherheit. Bei vorhandener Netzspannung wird dropped-out relay (alarm condition) is indicated by the
das abgefallene Relais (Alarmsitualion) durch das Auf- associated LED as iona as mains power is available.
leuchten der zugehorigen Leuchtdiode angezeigt.
Sie Skalenteiiung auf den Polentiometern A (MAX.) und The scale divisions on the HIGH (A) and LOW (B) po-
B (MIN.) Ist linear und enlsprichl der Skala des Anzeige- tentiometers are linear and correspond to the scale of
instnjmentes (O-lOV) im Bnschub LB 3886. Die Schalt- the indicating instrument (0—10 V) in module LB 3886.
punkte konnen beliebig innerhalb des MeSbereiches The alarm thresholds can be adjusted over the full
eingestellt werden. Es ergeben sich Kontaklzustande wie measuring range. TTie possible contact conditions are
in der Tabelle dargestelll indicated in the Table below.
Durch Umloten einer Brucke kann der MIN.- In einen By resoldering a v/ire link, the LOW threshold can be
MAX-Alarm umgeandert werden (sInngemaBes gilt converted into a HIGH threshold(conversely, the same
fur den MAX-Alarm). Dadurch konnen z.B. Vor- und applies to the HIGH threshold). This makes it possible,
Hauptalarm fur MAX signalisiert werden. AuBerdem be- for example, to provide HIGH and HIGH HIGH alarms.
steht fur spezielle Anwendungen die Moglichkeit, die Re- For special applications there is in addition the possibility
lais an getrennten Eingangen zu betreiben. of operating the relays with separate inputs. Further details
see Data Sheet for this Module.
Nahere Informationen hierzu siehe Datenblatt des Ein-
schubs.

Re ais Kontakte g eschlossen Open Coll sclor (npn)

Dichte A (MAX) LED B (MIN.) LED A (MAX) B (MIN.) A (MAX) B (MIN.)

NORMAL angezogen aus angezogen aus 31 - 3 0 35-34 leitend leitend

groSer MAX abgefallen an angezogen aus 31 - 3 2 35-34 sperrt leitend

Kleiner MiN. angezogen aus abgefallen an 31 - 3 0 35-36 leitend sperri

Stromausfall abgefallen an abgefallen aus 31 - 3 2 35-36 - -

AuOer den Kontakten der Retais sind fur MAX und MIN. je ein Open-Collector-Ausgang herausgefuhrt (max. + 30 V; 0.1 A).

Relay Contact s closed Open Coll BcJor (npn)


IDensity A (HIGH) LED B (LOW) LED A (HIGH) B (LOW) A (MAX) 8 (MiN.)

Normal picked-up OFF picked-up OFF 31 - 3 0 35-34 turned-on turned-on

>H1GH dropped-out ON picked-up OFF 31 - 3 2 35-34 turned-off turned-on

<LOW. picked-up OFF dropped-out ON 31 - 3 0 35-36 turned-on turned-olf

Power failure dropped-out ON dropped-out OFF 31 - 3 2 35-36

Addition to Ihe relay contacts, one open-colleclor oulpul each is provided for HIGH and LOW (max. + 30 V; 0.1 A)

22
19. Brucken 19. Wire Links
Das Ch'chtemeSger^ wurde bei der Priifung in unserem This Density Measuring System has been preset at our
Werk auf die vorgesehene MeBaufgabe eingestellt. Bei works for its specific application. If the amplifier is sub-
- nachtraglicher Efweiterung des MeBverstarkers urn zu- sequently extended by additional modules (e. g. temper-
satzliche Einschiibe (z. B. Temperaturkompensation) ature compensation), or if a module" is replaced, the wire
Oder bei Austausch eines Bnschubs sind anhand des links in the printed circuit boards must be checked
jeweiligen Schallplanes die Brucken in den Platinen zu against the appropriate circuit diagrams and modified as
uberprtifen bzw. den Bedingungen entsprechend zu required.
andera

20. Biindeinschube/Blindstecker 20. Blank Modules / Dummy Connectors


Die fur die Bnschube DECAY-COMP., TEMP COMP The positions reserved in the chassis for the DECAY-
und LINEARIZATION im Baugruppentrager reservierten COMP., TEMP. COMP and LINEARIZATION modules
Ratze (siehe beiliegenden Uberrahmenplan) mussen bei (see enclosed chassis plan) must be blanked off by blank
Fehlen diescr Bnschube durch Biindeinschube/Blind- modules/dummy connectors if they are not included.
stecker gebruck! werden. Bei der Prufung der Aniage When checking out the module the system configuration
wurde die dem Auftragsumfang entsprechende Ausle- was arranged according to the specific requirements,
g u r ^ vorgenommen, bei nachtraglicher Erweiterung Oder and the same procedure must be adapted when sub-
ErUfernen eines Eir^schubs ist entsprechend zu verfahren sequently adding or removing a module (blank modules
^Hndeinschube sirxJ liefertDar unter der Typen-Nr. LB are available under reference LB 3825).
3825).
IMPORTANT!
ACHTUNG! For removing and replacing modules the screwdriver
Zum Herauszlehen und Einsetzen von Einschuben mOs- slots in the quick-release mechanism must be hori-
sen die Schraubenzieherschlitze der Schnellverschlus- zontal!
se horizontal stehen!

23
21. Strahlenschutz 21. Radiation Protection
jBngebaut in die MeSstrecke ist ein 2<tAm-Strahler von The measuring system incorporates a ^'''Am source with
maximal 100 mCi (3.7 x IQS x i/s). Die Abschlr- a max. dose rate of 100 mCi (3,7 x 109 x i/s). The shielding
mung der Strahlung wurde so effektiv ausgelegt, daB of the source has t>een designed so efficienily that the
die fiir die Erteilung der Bauartzulassung eriaubten dose rate is smaller by a factor of at least 10 than the
Oosisleistungen (in 10cm Abstand —1 m r e m ^ — 2,78 x dose rate limit required for type approval in the Federal
10"® W/kg) mindestens urn den Faktor 10 unterschrit- Republic of Germany (at 10 cm distance — 1 mrem/h —
ten v^erden. Der SUahlenschutz wird hierdurch beson- 2.78X10*3 W/kg). This greatly simplifies radiation pro-
ders vereinfacht, es entstehen keine Kontrollbereiche. tection, and no controlled zones are created. This ob-
Abschrankungen bzw. zeitiiche Begrenzungen des viates the need to provide physical access barriers or to
Aufenthaltes am MeSort konnen ebenso entfallen wie limit the duration of stay in the direct vicinity of the source,
arztliche oder meBtechnische Uberwachung des Bedie- as well as medical and radiometric checks of the staff
nungspersonals. unnecessary.
Wiederholungsprijfungen des eingebauten Strahlers auf Repeat checks of the built-in source for containment leaks
Dichtigkeit der UmhuDung sind nicht erforderlich (ver- are no longer required in the Federal Republic of Ger-
glelche Bauartzulassungsschein BW/29/78, Seile 2). W\r many. However, reference is made in this context to
verv/eisen in diesem Zusanrimenhang jedoch auf Punkt 3. Section 3 of the Operating Instructions.
der Bedienungsanleitung.
The sealed screws in the measuring system must
Die verstegelten Schrauben der MeBeinrichtung not be tampered with!
dUrfen nicht geoffnet werden!
After serious disturbances, e.g. fire or explosion, where
Nach schv/eren Betriebsstorungen, wie z.B.. Brand oder there is a likelihood that the source or the shielding has
Explosion, bei der die WShrscheinlichkeit besteht, dal3 been damaged, the person responsible for radiation
|Strah!er oder Abschirmung In Mitleidenschaft gezogen protection within the company must be notified immedi-
worden sind, Ist unverzDglich der im Werk zustandige ately. He should contact our firm if he has found any
Strahlenschutzbeauftragte zu verstandigen. Er setzt sich defects which may adversely affect the safety or perfor-
dann gegebenenfalis mil unserer Firma in Verbindung, mance of the system.
wenn latsachlich Fehler, die die Sicherheit oder Funklion
der Aniage beeintrachtigen. festgestelll werden. Radioactive sources which are no longer needed or have
reached the end of their useful life must be returned
Nicht mehr l^enotigte oder abgeklungene radioaktive to the national radioactive waste disposal centre or to the
Strahler mussen an die staatJiche Sammelstelle fur radio- manufacturer.
aktive Abfalle, an den Ueferanten oder an den Hersteller
It is recommended lo formalise these points in inlernal
atjgegeben werden.
procedural instructions which take account of the specific
Es empfiehlt sich. diese Punkte in einer internen oder auf conditions in the user's establishment.
den Betrieb der Aniage zugeschnitlenen Dienstanwei-
sung festzulegen.

24
Stammwerk Factory
LABORATORiUM PROF. DR. BERTHOLD
D 7547 Wildbad 1 • Postfach 160
Phone 0 70.81/39 81 1616x07 24 019

Vertrieb in der BRD German Sales Office


LABORATORIUM PROF. DR. BERTHOLD
Abteiiung Industrie
D 7547 Wildbad 1 • Postfach 160
Phone 0 70 81/39 81 • Telex 07 24 019

Verkaufsburos und Servicestellen in der BRD Branch offices In Germany with full
mit alien Verkaufs- und Servicemoglichkeiten sales and service facilities

Buro Berlin Buro Koln


1000 Berlin 46 • Siemensstra5e 13 5060 Bergisch-Gladbach 1 • Eichenhainallee 63
Telefon 0 30/771 20 11 Telefon 0 22 04 / 6 70 01 • Telex 08 878 538

Buro Hannover Biiro Miinchen


3004 Isemhagen 1 • Stemensstrafle 4 8000 Miinchen 40 • Karl-Theodor-StraBe 29
Telefon 05 11/6 17 51 - Telex 09 21 273 Telefon 0 89/33 40 01

Export Office
LABORATORIUM PROF. DR. BERTHOLD
- EXPORTABTEILUNG -
D 7547 Wildbad 1 • Postfach 160
Phone 0 70 81/39 81 • Telex 07 24 019

Auslandische Niederlassungen mit alien Subsidiary and affiliated companies


VerkaufS' und Servicemdglichkeiten with full sales and service facilities

Austria Great Britain


BERTHOLD-ANALYTISCHE INSTRUMENTE LABORATORY IMPEX LIMITED
VERTRIEBSGESELLSCHAFT MBH Lion Road
L Witzelsbergergasse 10/28
A-1150 Wien
Twickenham Middlesex
England

Belgium Spain
BENELUX ANALYTICAL INSTRUMENTS SA ICAINSA
Vaartijk 22 Plaza de Almuncear, 7
B-1800 Vilvoorde Madrid 8
Spain

France Sw^erland
BERTHOLD FRANCE SA MASSINI AG
68bts. Rue Sartoris HonggerstraBe 122
F-92250 La Garenne-Colombes CH-8105 Regensdorf
o
t
o Vertretungen in zahlreichen Landern Representation in all other countries,
c
o
Namen und Adressen auf Anfrage Names and Addresses on request
OS-May-OZ 11:47 John Shar-m>an OO 44 1484 866255 P . Oi

.75 Engineering
102 Commercial Rd
Skelmanthorpe
Huddersfteld
HbH 9DS

Te}:^44 I4H4 866254


Fax:^44 14S4 866255
e-mail: Jser^gineennguk(a)aol.com

C csiT.ipany: Jsi^/ Cfest

From: JCHE^ SHARftflAW

Phone: 01-^84 86S254


Fa^L: 01484 866255

Date: 3 tlflay, 2 0 0 2
tziclut^iff^^ fbis cover
page: 1

Chris,

Price for updating the Berthold Density gauge is:


Quotation No: 2.^56

Prtcc
Qty J-.::. r;o Hescription

LB 3E6-1C Density Evaluation Unit (1 cbajintl)


outnuts a) 0''4-20 in A isolated for densii>
h) (1/4-20 mA iso'ated for density or
product temperature (reversible)
digital 2 open collectors for max and nui
output: 1 open collector for malfunction nidicat.^i
I'lpur- temperature compensation Pt lUO
or 0'4-20 mA ^reversible)
memo»"y for 3 calibration sets for ditTe-en{ O M K I J C I S
data storage in l-EPROM
d'pital a) external setting ofcurrcnt .ante
d'splay: 20 characters, alphanumeric
automatic deaiy compensation
Suppiv Voltage I 15 V - 47 . 65 H?

a.f woi'li'i

Vqtttzs oi' ir.sRl: rjel 30 days

John
Tpmpe/Q/o/"-
innsmtter
O/t -lOmfJ

— +

uii-iso-m
Kanalt/Chaofuli
K>nal Siorung
l/Oujnne/l
mot. I /ru'n- failure
moM. I min.
^•[••••{QaQiiQcaGiaDD
^ L^ L^
1^1 1^1 U\ \2]1

trr.
PPOVJUDV'. WW(
Ziyy ' ^
i9\i8 47 33\373S\353i\33 32\31
— — + — -f. — +•
oderlor
a. »>

+ - ri <i.5
f: k:
M
ZUV'
k ^ £ S- r •'
V0 2,1 Q Q '1
'r, fV. .
'"S 'cri ^o ly.

«M
«»: C»
oi a C Q.
Oder/or nha
oc 0
6 c
i?) k3
Uromousgonae
HQli* unttr AOtchirmung Tiing
dit Curreni output i
O/i/'fOmA Poieniialfrei
thflding isolated
mo** aU«'t

Ab 51. (IBZ800-51)
From SIO^ iLB3BOO-Si)
Kabtldurchfuhrunj am izinlilloiionsr&hitr \01:Klmmecinum.3)bisS)\ ,
CASL£ PAiSAOi AT JHt SCIHULlAim COUHTtR J 1 1 ^ Abaw
''H=r4-Hr-»IH'-I
kaM soo3m
— P**-
kf
Anscwuopfon LB 386-fC mȣ/with;.,
C«nn«ction di'ogrom' Sz 6 ' G 5 ••• i f] 'i j j j- 'Tf^^H
t^Jillfi T/tO

I /ao

CM- '0

Cc^ - -

r i I I I ^
Countrates Date Lab values Temperature
g/cmVg/l/%/''Be
1100 cps 1110 1120
1101 cps nil 1121
1102 cps 1112 1122
1103 cps 1113 1123
1104 cps 1114 1124
1105 cps 1115 1125
1106 cps 1116 1126
1107 cps 1117 1127
1108 cps 1118 1128
1109 cps 1119 1129

i 1130 Calibration mode


1131 Zero countrate cps
1132 Measuring path
cm
1133 Absorption coefficient aj
1134 Absorption coefficient
1135 Absorption coefficient aj
1136 Factor (•)
1137 Offset ( ± )
1138 Quad, error
1140 Current output 1: 0/4 mA
1141 Current output 1: 20 mA
1142 2. range: 0/4 mA
1143 2. range: 20 mA
1144 Threshold min
1145 Threshold max
1146 Hysteresis
1147 Linear temp.coefficient TC^
1148 Quadrat, temp.coefficient TCj
1149 Reference temperature
0/79J S-J^Jg^f

TAO

fOO

Cc-^ - It
/Li

( ))0
f
a-
/ i ' 11 "" * J
SET-UP PROTOCOL LB 386.1C V.2.0

Channel 1

Measuring Point
Radioactive Source: No Activity: Isotope:
Pipeline: mm Material:
Irradiation angle: 907457307others

Code No. Function Value

Password
Instrument ID
Print interval mm
Program version

1010 Time constant


1011 Automatic switchover
1012 Countrate threshold min cps
1013 Countrate threshold max cps

1020 Temperature compensation


0 = off; 1 = on
Current input for temperature:
1021 0/4 mA 'C

t
1022 20 mA
Current output for temperature:
1023 0/4 mA =C
1024 20 mA

You might also like