UPSMON PRO Windows User Manual
UPSMON PRO Linux --- User Manual
AA. UPSMON PRO Install
A.1. Command : cp UPSMON_PRO_Linux.tar /home/user
A.2. Command : tar -xvf UPSMON_PRO_Linux.tar
A.3. Command : cd UPSMON_PRO_Linux
==> These command will copy and uncompressed this ups monitoring software
==> And the package contains executable files about ups monitoring, configuration, and control
                           Diagram : UPSMON PRO Install (Ubuntu)
BB. UPSMON PRO Start
B.1. Command : upsmon-pro-start
==> It will ask you the basic information and then auto start ups monitoring service
       –   a. UPS Connection : 1.RS232 2.USB 3.SNMP-Card 4.UPSMON-PRO
       –   b. Linux shutdown delay seconds : When power failure occurs, Linux will act
           shutdown after this count down seconds
       –   c. Linux shutdown if battery capacity : Linux act shutdown at once if battery descend
           to this level
       –   d. Linux shutdown if battery backup minutes : Linux act shutdown at once if battery
           estimated backup time descend to this minutes
       –   e. Ups shutdown delay minutes : Once Linux commit shutdown, ups will sustain power
           for these minutes
       ==> UPSMON : UPSMON Start
       ==> It means the program successfully execute
       ==> UPSMON : Start Monitor
       ==> It means the program successfully get ups connection
                                   Diagram : USB Connection
   Diagram : RS232 Connection (SuSe)
Diagram : SNMPCard Connection (CentOS)
B.2 Command : upsmon-pro-stop
==> It will stop ups monitoring service
B.3 Command : upsmon-pro-service
==> This command directly start ups monitoring without any information query
      (Add this within start daemon)
B.4 Command : upsmon-pro-restart
==> This command will restart the ups monitoring
B.5. Command : upsmon-pro-start-config
==> This command will reset ups connection and shutdown condition
==> Polling Interval : The application query interval to ups (milli second)
                                       Diagram : Start Config
CC. UPSMON PRO Status
C.1 Command : upsmon-pro-status
==> It will repeatedly poll you current ups status until Ctrl-C pressing
       –   Power Status : Battery Power / Utility Power
       –   Input Voltage : To display utility power voltage
       –   Input Frequency : To display utility power frequency
       –   Output Voltage : To display ups output voltage
       –   Output Power : To display ups output power
       –   UPS Status : Normal / Bypass / AVR Boost / AVR Buck / UPS Failed
       –   UPS Load : To display total capacity of loads
       –   UPS Temperature : To display ups inside temperature
       –   UPS Beeper : ON / OFF
       –   Battery Status: Normal/ Charge/ Discharge / Battery Test / Low Battery / Battery Failed
       –   Battery Capacity : To display battery percentage level
       –   Battery Voltage : To display battery its voltage
       –   Battery Backup Time : To display battery estimated backup time in battery mode
       –   Battery Test Times : Accumulated times that ups made battery test
       –   Battery Last Test : The last time this ups made battery test
       –   Battery Test Result : Normal / Battery Failed / Low Battery
       –   Battery Power Times : Accumulated times that ups output power supply from batteries
       –   Battery Power Start : The last time ups switch power from its battery
       –   Battery Power End : The last time ups switch power to utility
       –   Battery Age : The age of ups batteries have used
       –   Ambient Temperature : The sense of environmental temperature
       –   Ambient Humidity : The sense of environmental humidity
       –   Upsmon Pro Linux : This ups monitoring software version
       –   Upsmon Pro Status : Monitoring / Disconnect
       –   Upsmon Pro Data Update : The data update time
       –   Upsmon Pro is going to shutdown after XXX seconds : Blackout and shutdown mode
                                      Diagram : UPS Status
C.2 Command : upsmon-pro-info
==> To display ups service / devices information / and configuration.
       – Ups Company : The manufacture of the ups
       – Ups Model : The ups model name
       – Ups Firmware : The ups firmware version
       – Rating Input Volt : Ratting Input Voltage
       – Rating Output Volt : Ratting Output Voltage
       – Upsmon Pro Connect : RS232 / USB / SNMP-Card / UPSMON-PRO
       – Upsmon Pro RS232 Port Name and Path : Serial port path (ex : /dev/ttyS0)
       – Upsmon Pro Master IP : The IP address of Upsmon Pro Master (RS232 or USB)
       – Snmp Card IP : The IP address of snmp card
       – Snmp Card firmware : The firmware version of snmp card
       – Snmp Card Community : The community of snmp card
       – Upsmon Pro Usb VID & PID : Usb vendor ID and Usb product ID
       – Upsmon Pro Usb Type : Driver for usb/hid ups equipment
       – Polling Interval : The query interval to ups
       – Linux shutdown delay seconds : When power failure occurs, Linux will act shutdown
         after this count down seconds
       – Linux shutdown if battery capacity : Linux act shutdown at once if battery descend to
         this level
       – Linux shutdown if battery backup minutes : Linux act shutdown at once if ups
         estimated battery backup time descend to this minutes
       – Ups shutdown delay minutes : Once Linux commit shutdown, ups will sustain power
         for these minutes
                                  Diagram : UPS Information
C.3 Command : upsmon-pro-log
==> To list the ups data log
C.4 Command : upsmon-pro-log-erase
==> To erase the ups data log
==> To avoid data conflict, please execute this command without upsmon pro service running
C.5 Command : upsmon-pro-event
==> To list the ups event
C.6 Command : upsmon-pro-log-erase
==> To erase the ups event
==> To avoid data conflict, please execute this command without upsmon pro service running
DD. UPSMON PRO Config
D.1 Command : upsmon-pro-mail
==> This configuration will help you to get email notification once ups events occurs
       –   a. E-Mail Server Enable : Y / n
       –   b. E-Mail Server Name or IP : Email server address
       –   c. E-Mail Server Port : 25 (default)
       –   d. E-Mail Account : The account of this email server
       –   e. E-Mail Password : The password of this email account
       –   f. SSL Requires : This mail server requires an secure connection
       –   g. E-Mail Sender : The email address of this account
       –   h. E-Mail Recipient : The recipient who needs to get email notification
D.2 Command : upsmon-pro-mail-test
==> This command will send a test mail to make sure your configuration is success or not
EE. UPSMON PRO Set
E.1 Command : upsmon-pro-test
==> To check the battery health, ups will supply the power shortly from its battery
E.2 Command : upsmon-pro-test-deep
==> To simulate battery capability, ups will supply battery power for its limits
E.3 Command : upsmon-pro-test-cancel
==> With this command, it will cease deep battery power test
                                     Diagram : UPS Batter Test
E.4 Command : upsmon-pro-beeper-on
==> Ups alarm for ups warning condition
E.5 Command : upsmon-pro-beeper-off
==> Ups silence for ups warning condition
E.6 Command : upsmon-pro-ups-reboot
Description : Shutdown Linux and reboot ups after XX minutes
       – a. Ups reboot after minutes (defaut : 2) : Ups reboot its power after this minutes
       – b. Commit ups reboot             (Y / n) :
E.7 Command : upsmon-pro-outlet1-off
==> It will turn ups outlet1 OFF at once
E.8 Command : upsmon-pro-outlet1-on
==> It will turn ups outlet1 ON at once
E.9 Command : upsmon-pro-outlet2-off
==> It will turn ups outlet2 OFF at once
E.10 Command : upsmon-pro-outlet2-on
==> It will turn ups outlet2 ON at once
==> ups outlets control is specific for certain ups
FF. UPSMON PRO Multi-Connect
==> The UPSMON PRO can play the role as Master or Slave
F.1 UPSMON PRO Master
   •   UPSMON PRO Master : The Linux who physically connects UPS via RS232 or USB
   •   UPSMON PRO Master : It can share UPS status to the other UPSMON PRO Slaves
   •   EX : UPSMON PRO Master : 10.192.136.231 (IP Address)
F.2 UPSMON PRO Linux Slave
   •   UPSMON PRO Slave : The Linux who connect to UPSMON PRO Master via net
   •   UPSMON PRO Slave : Execute upsmon-pro-start with 4 upsmon-pro parameter
F.3 UPSMON PRO Windows Slave
  •   UPSMON PRO Slave : The Windows who connect to UPSMON PRO Master via net
  •   UPSMON PRO Slave : Connect : Choose UPSMON PRO
GG. UPSMON PRO Auto Start
G.1 Command : / path / UPSMON_PRO_Linux / upsmon-pro-service
==> To have a daemon start every time Linux reboot, please add above script into beginning
procedures. Typically this script locate in “/etc/rc.d/” or “/etc/rc.d/rc.local” or
“/etc/init.d/rc.local”. However the name and path vary by the distribution
HH. Q and A
H.1 Linux usb connect Fail :
Command : sudo apt-get install lib32bz2-1.0   (Debian)
Command : sudo apt-get install lib32z1        (Ubuntu / Mint)
Command : yum install glibc.i686              (Fedora / CentOS)
H.2 Linux Display Fail :
Command : sudo apt-get install default-jre
Command : cd UPSMON_PRO_Linux / EXT
Command : java Display