0% found this document useful (0 votes)
24 views34 pages

UPSmon Manuale Utente en

Uploaded by

Vasya Pupkin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views34 pages

UPSmon Manuale Utente en

Uploaded by

Vasya Pupkin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

UPSMON PRO Windows User Manual

UPSMON PRO Linux --- User Manual


AA. UPSMON PRO Install

A.1. Command : cp UPSMON_PRO_Linux.tar /home/user


A.2. Command : tar -xvf UPSMON_PRO_Linux.tar
A.3. Command : cd UPSMON_PRO_Linux

==> These command will copy and uncompressed this ups monitoring software

==> And the package contains executable files about ups monitoring, configuration, and control

Diagram : UPSMON PRO Install (Ubuntu)


BB. UPSMON PRO Start

B.1. Command : upsmon-pro-start

==> It will ask you the basic information and then auto start ups monitoring service

– a. UPS Connection : 1.RS232 2.USB 3.SNMP-Card 4.UPSMON-PRO

– b. Linux shutdown delay seconds : When power failure occurs, Linux will act
shutdown after this count down seconds

– c. Linux shutdown if battery capacity : Linux act shutdown at once if battery descend
to this level

– d. Linux shutdown if battery backup minutes : Linux act shutdown at once if battery
estimated backup time descend to this minutes

– e. Ups shutdown delay minutes : Once Linux commit shutdown, ups will sustain power
for these minutes

==> UPSMON : UPSMON Start


==> It means the program successfully execute

==> UPSMON : Start Monitor


==> It means the program successfully get ups connection

Diagram : USB Connection


Diagram : RS232 Connection (SuSe)

Diagram : SNMPCard Connection (CentOS)


B.2 Command : upsmon-pro-stop

==> It will stop ups monitoring service

B.3 Command : upsmon-pro-service

==> This command directly start ups monitoring without any information query
(Add this within start daemon)

B.4 Command : upsmon-pro-restart

==> This command will restart the ups monitoring

B.5. Command : upsmon-pro-start-config

==> This command will reset ups connection and shutdown condition

==> Polling Interval : The application query interval to ups (milli second)

Diagram : Start Config


CC. UPSMON PRO Status

C.1 Command : upsmon-pro-status

==> It will repeatedly poll you current ups status until Ctrl-C pressing

– Power Status : Battery Power / Utility Power


– Input Voltage : To display utility power voltage
– Input Frequency : To display utility power frequency
– Output Voltage : To display ups output voltage
– Output Power : To display ups output power
– UPS Status : Normal / Bypass / AVR Boost / AVR Buck / UPS Failed
– UPS Load : To display total capacity of loads
– UPS Temperature : To display ups inside temperature
– UPS Beeper : ON / OFF
– Battery Status: Normal/ Charge/ Discharge / Battery Test / Low Battery / Battery Failed
– Battery Capacity : To display battery percentage level
– Battery Voltage : To display battery its voltage
– Battery Backup Time : To display battery estimated backup time in battery mode
– Battery Test Times : Accumulated times that ups made battery test
– Battery Last Test : The last time this ups made battery test
– Battery Test Result : Normal / Battery Failed / Low Battery
– Battery Power Times : Accumulated times that ups output power supply from batteries
– Battery Power Start : The last time ups switch power from its battery
– Battery Power End : The last time ups switch power to utility
– Battery Age : The age of ups batteries have used
– Ambient Temperature : The sense of environmental temperature
– Ambient Humidity : The sense of environmental humidity
– Upsmon Pro Linux : This ups monitoring software version
– Upsmon Pro Status : Monitoring / Disconnect
– Upsmon Pro Data Update : The data update time
– Upsmon Pro is going to shutdown after XXX seconds : Blackout and shutdown mode
Diagram : UPS Status

C.2 Command : upsmon-pro-info

==> To display ups service / devices information / and configuration.

– Ups Company : The manufacture of the ups


– Ups Model : The ups model name
– Ups Firmware : The ups firmware version
– Rating Input Volt : Ratting Input Voltage
– Rating Output Volt : Ratting Output Voltage
– Upsmon Pro Connect : RS232 / USB / SNMP-Card / UPSMON-PRO
– Upsmon Pro RS232 Port Name and Path : Serial port path (ex : /dev/ttyS0)
– Upsmon Pro Master IP : The IP address of Upsmon Pro Master (RS232 or USB)
– Snmp Card IP : The IP address of snmp card
– Snmp Card firmware : The firmware version of snmp card
– Snmp Card Community : The community of snmp card
– Upsmon Pro Usb VID & PID : Usb vendor ID and Usb product ID
– Upsmon Pro Usb Type : Driver for usb/hid ups equipment
– Polling Interval : The query interval to ups
– Linux shutdown delay seconds : When power failure occurs, Linux will act shutdown
after this count down seconds
– Linux shutdown if battery capacity : Linux act shutdown at once if battery descend to
this level
– Linux shutdown if battery backup minutes : Linux act shutdown at once if ups
estimated battery backup time descend to this minutes
– Ups shutdown delay minutes : Once Linux commit shutdown, ups will sustain power
for these minutes
Diagram : UPS Information

C.3 Command : upsmon-pro-log


==> To list the ups data log

C.4 Command : upsmon-pro-log-erase

==> To erase the ups data log

==> To avoid data conflict, please execute this command without upsmon pro service running

C.5 Command : upsmon-pro-event

==> To list the ups event

C.6 Command : upsmon-pro-log-erase

==> To erase the ups event

==> To avoid data conflict, please execute this command without upsmon pro service running
DD. UPSMON PRO Config

D.1 Command : upsmon-pro-mail

==> This configuration will help you to get email notification once ups events occurs

– a. E-Mail Server Enable : Y / n


– b. E-Mail Server Name or IP : Email server address
– c. E-Mail Server Port : 25 (default)
– d. E-Mail Account : The account of this email server
– e. E-Mail Password : The password of this email account
– f. SSL Requires : This mail server requires an secure connection
– g. E-Mail Sender : The email address of this account
– h. E-Mail Recipient : The recipient who needs to get email notification

D.2 Command : upsmon-pro-mail-test

==> This command will send a test mail to make sure your configuration is success or not
EE. UPSMON PRO Set

E.1 Command : upsmon-pro-test

==> To check the battery health, ups will supply the power shortly from its battery

E.2 Command : upsmon-pro-test-deep

==> To simulate battery capability, ups will supply battery power for its limits

E.3 Command : upsmon-pro-test-cancel

==> With this command, it will cease deep battery power test

Diagram : UPS Batter Test


E.4 Command : upsmon-pro-beeper-on

==> Ups alarm for ups warning condition

E.5 Command : upsmon-pro-beeper-off

==> Ups silence for ups warning condition

E.6 Command : upsmon-pro-ups-reboot

Description : Shutdown Linux and reboot ups after XX minutes

– a. Ups reboot after minutes (defaut : 2) : Ups reboot its power after this minutes
– b. Commit ups reboot (Y / n) :

E.7 Command : upsmon-pro-outlet1-off

==> It will turn ups outlet1 OFF at once

E.8 Command : upsmon-pro-outlet1-on

==> It will turn ups outlet1 ON at once

E.9 Command : upsmon-pro-outlet2-off

==> It will turn ups outlet2 OFF at once

E.10 Command : upsmon-pro-outlet2-on

==> It will turn ups outlet2 ON at once

==> ups outlets control is specific for certain ups


FF. UPSMON PRO Multi-Connect

==> The UPSMON PRO can play the role as Master or Slave

F.1 UPSMON PRO Master

• UPSMON PRO Master : The Linux who physically connects UPS via RS232 or USB
• UPSMON PRO Master : It can share UPS status to the other UPSMON PRO Slaves
• EX : UPSMON PRO Master : 10.192.136.231 (IP Address)

F.2 UPSMON PRO Linux Slave

• UPSMON PRO Slave : The Linux who connect to UPSMON PRO Master via net
• UPSMON PRO Slave : Execute upsmon-pro-start with 4 upsmon-pro parameter
F.3 UPSMON PRO Windows Slave

• UPSMON PRO Slave : The Windows who connect to UPSMON PRO Master via net
• UPSMON PRO Slave : Connect : Choose UPSMON PRO
GG. UPSMON PRO Auto Start

G.1 Command : / path / UPSMON_PRO_Linux / upsmon-pro-service

==> To have a daemon start every time Linux reboot, please add above script into beginning
procedures. Typically this script locate in “/etc/rc.d/” or “/etc/rc.d/rc.local” or
“/etc/init.d/rc.local”. However the name and path vary by the distribution
HH. Q and A

H.1 Linux usb connect Fail :


Command : sudo apt-get install lib32bz2-1.0 (Debian)
Command : sudo apt-get install lib32z1 (Ubuntu / Mint)
Command : yum install glibc.i686 (Fedora / CentOS)

H.2 Linux Display Fail :


Command : sudo apt-get install default-jre
Command : cd UPSMON_PRO_Linux / EXT
Command : java Display

You might also like