750-375

4 PROFINET IO advanced Fielbus Coupler


2-port switch; 100 Mbit/s; digital, analog and complex signals
132

Marking area
8 01 02 Status

1 2 3 4 5 6 7 8
Address voltage supply
PROFINET IO RUN A
C -System
B
-Power jumer contacts

W
ON D
BF 24V 0V Data contacts

ON
1 DIA Supply
8=OFF:DCP 24 V
I/O 0V
+ +
Supply via

®
750-375

P R O F I
power jumper contacts
24 V

N E T
Fieldbus
connection — —

LNK
RJ-45
X
1 0V
Fieldbus

LNK ACT
connection
RJ-45
X
2

ACT
Configuration and Power jumper contacts
programming interface
(with cover open)

The 750-375 Fieldbus Coupler connects the WAGO-I/O-SYSTEM 750 to


PROFINET IO (open, real-time industrial ETHERNET automation standard).
The coupler identifies the connected I/O modules and creates local process
images for maximum two IO controllers and one IO supervisor according to
preset configurations. The process images may include a mixed arrangement
of analog, digital or specialty modules. Analog and specialty module data is
sent via words and/or bytes; digital data is sent bit by bit.
The fieldbus coupler operates as an IO device in the network. It features an
integrated 2-port switch, simplifying the creation of a line structure without
additional network components.
The device name can be assigned via DCP protocol or set via DIP switch.

Pack.
Description Item No.
Unit System Data
PROFINET IO adv. 2-Port 750-375 1 No. of couplers connected to Master limited by PROFINET specification
PROFINET IO adv. 2-Port/T 750-375/025-000 1 Transmission medium Twisted Pair S-UTP 100 Ω cat. 5
Extended temperature range: -20 °C ... +60 °C Max. length of fieldbus segment 100 m between hub station and 750-375;
max. length of network limited by
PROFINET specification
Baud rate 10 Mbit/s (ETHERNET protocols),
100 Mbit/s full duplex (PROFINET IO)
Transmission method 100Base-TX
Pack. Buscoupler connection 2 x RJ-45
Accessories Item No.
Unit PROFINET IO standard V2.2 (conformance class C, pending)
Miniature WSB Quick marking system
plain 248-501 5
with marking see Section 11

Approvals
Conformity marking 1
Marine applications (versions upon request) GL
r UL 508

WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 - D-32385 Minden Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Subject to design changes 05.01.2015 Hansastr. 27 - D-32423 Minden Fax: +49(0)571/887-169 www.wago.com
4
133

24 V
1 5 DC I/O
24 V /0 V 10 nF modules
DC
0V
2 6
24 V
24 V

INTERFACE
FIELDBUS
ELECTRONICS
FIELDBUS INTERFACE

3 7
0V
ELECTRONICS

0V 10 nF

4 8

750-375

Technical Data General Specifications


Number of I/O modules 64 Operating temperature 0 °C ... +55 °C
with bus extension 250 Wire connection CAGE CLAMP®
Max. input process image 512 bytes Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Max. output process image 512 bytes Strip lengths 8 ... 9 mm / 0.33 in
Configuration via PC Dimensions (mm) W x H x L 62 x 65 x 100
PROFINET IO features Integrated 2-port switch; Height from upper-edge of DIN 35 rail
Auto-negotiation, Auto-MDIX; Weight 150.3 g
Isochronous real-time communication Storage temperature -25 °C ... +85 °C
(pending); Relative air humidity (no condensation) 95 %
Transmission clock: 1 ms (RT), Vibration resistance acc. to IEC 60068-2-6
1, 2, 4 ms (IRT); Shock resistance acc. to IEC 60068-2-27
Device replacement without programming Degree of protection IP20
tool; Shared device EMC immunity of interference acc. to EN 61000-6-2, marine applications 4.1
Protocols Topology detection / LLDP, EMC emission of interference acc. to EN 61000-6-3, marine applications
Network diagnostics / SNMP / MIB-2,
media redundancy / MRP (pending),
Web server / HTTP
Profiles supported PROFIsafe V2, PROFIenergy V1.0
ID code Vendor ID: 0x011D;
Device ID: 0x02EE;
Coupler ID: 0x01000177
Power supply 24 V DC (-25 % ... +30 %)
Input current typ. at rated load (24 V) 500 mA
Efficiency of the power supply (typ.) at
nominal load (24 V) 90 %
Internal current consumption (5 V) 450 mA
Total current for I/O modules (5 V) 1700 mA
Isolation 500 V system/supply