Technical data sheet

Quotation 2400230.3

Project Office 60 Nguyen Du, Hanoi


Designation PAU
Item

Unit execution Weatherproof unit

Casing Outside Powder coated


colour approx. RAL 7035

Range TI-50

Supply air Extract air


Airflow section 09/18 09/18
Airflow 12300 m³/h 3.42m³/s 11070 m³/h 3.08m³/s
External pressure drop 600 Pa -300 Pa / +300 Pa 600 Pa -300 Pa / +300 Pa

Air velocity (EN 13053) 1.84 m/s (V3) 1.66 m/s (V2)
Electrical fan power 6.46 kW 5.02 kW
SFPv value (EN 16798-3) 1,763 W/m³/s 1,493 W/m³/s
SFP class (EN 16798-3) SFP3 SFP3

Total weight approx. 2368.0 kg

Energy Efficiency Class


Eurovent 2016 (winter) B N
Calculation data are based on dry conditions with a mixing ratio of: 80% and an outdoor temperature of: 11.0°C

Eurovent 2020 (summer) B


Calculation data are based on the conditions of the town NOI BAI INTL in Viet Nam (ASHRAE 2017: summer dry bulb temperature = 36.1°C, summer wet bulb
temperature = 27.3°C, summer dew point temperature = 24.4°C and dry winter temperature = 11°C)

AHU manufacturers association -

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 1 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
Supply air

Outdoor air chamber


Airflow 12300 m³/h Pressure drop 0 Pa
Unit/Length of component 09/18 - L8
Drain pan 1.4301

Pre-filter
Design Flat filter Calculated pressure drop 100 Pa
Class G4
Filter
Airflow 12300 m³/h Calculated pressure drop 155 Pa
Design Bag filter Pcs. 3 x 1/1 (592x592)
Class F7 3 x 1/2 (287x592)
Eurovent Class E Air velocity 1.84 m/s
Mounting frame 1 (max. F9) Powder coated Filter surface 11.70 m²
Unit/Length of component 09/18 - L4 Weight of component 41.0 kg

Delivered not mounted


Accessories
1 measuring pipe with connection to the maintenance side 1.0 kg
Rotary heat exchanger
Airflow 12300 m³/h Pressure drop 179 Pa
Design Sorptionsrotor Capacity -149.08 kW
Type / RRU-N-E18-18-1770-290 Supply air / Humidity 29.2 °C / 68%
Purging chamber - exhaust air / Humidity 37.2 °C / 57%
Outdoor air / Humidity 40.0 °C / 58% Temperature eff. (humid) 72.3 %
Extract air / Humidity 25.0 °C / 60% Temperature eff. (EN308) 76.5 %
Unit/Length of component 18/18 - L12 Humidity efficiency 65.2 %
H-class (EN 13053) H1
Weight of component 267.0 kg

Accessories
1 rotor speed control mounted and wired 0.0 kg
1 rotor speed control with run protection Micromax 370 for Size 06-36 for 1.0 kg
Rotortypen P, E and K respectively Size 06-30 for Rotortyp N

Direct expansion coil, (two circuit)


Airflow 12300 m³/h Pressure drop dry 128 Pa
Design Cu/Al
Air inlet / Humidity 29.2 °C / 68%
Air outlet / Humidity 18.5 °C / 95%
Refrigerant R410A Cooling capacity 92.50 kW
Evaporation temperature 8.5 °C
Unit/Length of component 09/18 - L8 Weight of component 105.0 kg
Additional
1 Frame from stainless steel 1.4301 0.0 kg
1 collector from Cu 0.0 kg
1 cover for collector at air inlet and air outlet 0.0 kg

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 2 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
Additional
1 coil with precoated fins 0.0 kg
Drain pan 1.4301
Coil face air velocity: 2.5 m/s

Fan
Airflow 12300 m³/h External pressure drop 600 Pa
Design Plug fan Internal pressure drop 562 Pa
Unit connection Vibration-isolated Installation loss 14 Pa
Fan speed 2306 1/min Dynamic pressure drop 137 Pa
Unit/Length of component 09/18 - L10 Total pressure drop 1313 Pa
Shaft power 5.7 kW
Efficiency 79 %
P-class (EN 13053) P1
Weight of component 180.6 kg

Sound power f Hz 63 125 250 500 1k 2k 4k 8k


Unit suction 76 dB(A) 47 52 73 66 66 66 63 64 dB(A)
83 dB 73 68 82 69 66 65 62 65 dB
Unit discharge side 96 dB(A) 54 63 83 88 93 88 85 82 dB(A)
98 dB 80 79 92 91 93 87 84 83 dB
Beside the unit 66 dB(A) 54 49 62 57 61 52 46 40 dB(A)
81 dB 80 65 70 60 61 51 45 39 dB
Fan accessories
1 Measuring pipe with connection to the maintenance side 200-1400 1.0 kg
1 Mounting set Powder coated 0.0 kg
Motor
Power 7.5 kW Current 14.9 A
Type 132 Efficiency class IE3
Nominal speed / Frequency 1460 1/min / 50 Hz Protection class / insulation IP IP55 / ISO F
Voltage 400 V Weight 0.0 kg
Operating pressure nominal airflow 2273 Pa
( ; K=258; Air density 1,14 kg/m³)
Fan speed n = 2306 1/min - f = 79 Hz
Calculated max. Speed n = 2450 1/min - f = 84 Hz
P-class (EN 13053) P1
Absorbed electrical power Pm = 6.46 kW
SFP-class acc. EN 16798-3 SFP3

ErP information (to 327/2011/EG)


ErP tier 2015 Measurement category A
Efficiency grade actual 69 Efficiency category static
Efficiency grade required 62 Variable speed drive None
Overall efficiency 67.8 %
For further Information see data of fan manufacturer
The fan system effect is taken into account in the fan performances.
Accessories
1 Cable access M20 (PG 13), Sleeve length 42mm 0.1 kg
1 Cable access M25 (PG 16), Sleeve length 42mm 0.1 kg
1 PTC 0.0 kg

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 3 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
Extract air

Empty chamber
Airflow 11070 m³/h Pressure drop 0 Pa
Unit/Length of component 09/18 - L6

Pre-filter
Design Flat filter Calculated pressure drop 97 Pa
Class G4
Filter
Airflow 11070 m³/h Calculated pressure drop 150 Pa
Design Bag filter Pcs. 3 x 1/1 (592x592)
Class F7 3 x 1/2 (287x592)
Eurovent Class E Air velocity 1.66 m/s
Mounting frame 1 (max. F9) Powder coated Filter surface 11.70 m²
Unit/Length of component 09/18 - L4 Weight of component 41.0 kg

Delivered not mounted


Accessories
1 measuring pipe with connection to the maintenance side 1.0 kg
Rotary heat exchanger
Airflow 11070 m³/h Pressure drop 160 Pa
Unit/Length of component 18/18 - L12

Fan
Airflow 11070 m³/h External pressure drop 600 Pa
Design Plug fan Internal pressure drop 407 Pa
Unit connection Vibration-isolated Installation loss 11 Pa
Fan speed 2110 1/min Dynamic pressure drop 111 Pa
Unit/Length of component 09/18 - L12 Total pressure drop 1129 Pa
Shaft power 4.4 kW
Efficiency 79 %
P-class (EN 13053) P1
Weight of component 171.6 kg

Sound power f Hz 63 125 250 500 1k 2k 4k 8k


Unit suction 75 dB(A) 45 50 71 65 67 68 65 65 dB(A)
81 dB 71 66 80 68 67 67 64 66 dB
Unit discharge side 93 dB(A) 52 61 81 85 90 85 82 80 dB(A)
95 dB 78 77 90 88 90 84 81 81 dB
Beside the unit 63 dB(A) 52 47 60 54 58 49 43 40 dB(A)
79 dB 78 63 68 57 58 48 42 37 dB
Fan accessories
1 Measuring pipe with connection to the maintenance side 200-1400 1.0 kg
1 Mounting set Powder coated 0.0 kg
Motor
Power 5.5 kW Current 11.1 A
Type 132 Efficiency class IE3
Nominal speed / Frequency 1455 1/min / 50 Hz Protection class / insulation IP IP55 / ISO F
Voltage 400 V Weight 0.0 kg

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 4 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
Operating pressure nominal airflow 1841 Pa
( ; K=258; Air density 1,14 kg/m³)
Fan speed n = 2110 1/min - f = 73 Hz
Calculated max. Speed n = 2210 1/min - f = 76 Hz
P-class (EN 13053) P1
Absorbed electrical power Pm = 5.02 kW
SFP-class acc. EN 16798-3 SFP3

ErP information (to 327/2011/EG)


ErP tier 2015 Measurement category A
Efficiency grade actual 698 Efficiency category static
Efficiency grade required 62 Variable speed drive None
Overall efficiency 67.2 %
For further Information see data of fan manufacturer
The fan system effect is taken into account in the fan performances.
Accessories
1 Cable access M20 (PG 13), Sleeve length 42mm 0.1 kg
1 Cable access M25 (PG 16), Sleeve length 42mm 0.1 kg
1 PTC 0.0 kg

Casing - Weatherproof incl. base frame with thermal break (Down)


Supply air panel Floor Frame Insulation Weight
inside inside
1 9/18 - L12 - U120 Powder coated Powder coated Powder coat 50 258.0 kg
1 18/18 - L12 - U120 Powder coated Powder coated Powder coat 50 338.0 kg
1 9/18 - L18 - U120 Powder coated Powder coated Powder coat 50 336.0 kg
3 Front panels 82.0 kg
Extract air panel Floor Frame Insulation
inside inside
1 9/18 - L10 Powder coated Powder coated Powder coat 50 192.0 kg
1 9/18 - L12 Powder coated Powder coated Powder coat 50 193.0 kg
3 Front panels 82.0 kg
Casing accessories
2 Access door
4 Access door
3 Access door
1 Weatherproof hood Powder coated 9/18 40.0 kg
3 Duct connection frame, powder coated 30.0 kg

General accessories
1 L Assembly material 5.0 kg

Legend E = Spare part L = Loose delivery D = Direct delivery O = Optional Bs = on-site, by others Bg = Delivered by ot
all flexible connections with Potentialausgleich!

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 5 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
General notes on AHU technology

The mechanical and thermal characteristics of the AHU-casing according to DIN EN 1886 are type-examination tested by T ÜV Süd. The
following classes for an AHU model box have been evaluated and confirmed:

· Thermal transmittance: T2
· Thermal bridging: TB1
· Air tightness: L1 (M), L2 (R)
· Filter Bypass leakage: F9
· Casing strength: D1 (M), D2 (R)

Despite of the thermal insulation and decoupling mentioned above, a completely non-condensing operation cannot be guaranteed. Any
tendency to condensation and the amount of condensate which might occur depends on actual operation conditions.

All wiring of Air Handling Units (e.g. lighting) which have been delivered in sections or partly knocked down has to be performed by others
and is not scope of supply and service of robatherm.

General notes on controls and cooling technology

Scope of delivery and services


Components, devices, services that are not explicitly listed in our technical data sheet are not included in our scope of delivery and services,
but must be provided by the customer professionally.

Only electrical components that have been tested for electromagnetic compatibility are used. Furthermore, these are installed on the AHU in
accordance with the recognized technical rules for EMC.

Unless otherwise specified, electric wiring and/or hydraulic or cooling tubing will be installed on the roof of robatherm indoor Air Handling
Units. The necessary working space shall be kept entirely clear, special attention shall be taken on sufficient distance to beams, ductwork
etc.

Testing according to DIN EN 60204-1 (VDE 0113-1) is not included in our scope of supply. If desired, we will prepare a corresponding offer
for components that are included in our scope of delivery. Independently of this, the electrical test according to DIN VDE 0100-600 must be
carried out by the customer for the entire system after completion.

Depending on the refrigerant category according to ISO 817, only l imited filling quantities are permitted, especially for flammable and toxic
refrigerants. In Europe, the maximum filling quantities must be in accordance with DIN EN 378 -1 and are determined on the basis of the
access area, the installation site and respective refrigerant cate gory. Internationally, calculation is made according to ISO 5149.

For refrigerants with safety class A2L, the relevant standard IEC 60335-2-40 must also be taken into account. For split air conditioners with
refrigerant R32, the instructions and the planning notes have to be observed.

In the case of direct expansion coil with external refrigeration s ystem, the system installer is responsible for compliance with the maximum
permitted filling quantity.

Please make sure that, in addition to the preceding information, the requirements specified in our instructions are observed,
available under www.robatherm.com/en/download s.

Nguyen,Hung
01.08.2024 Quotation / Project 2400230.3 / Office 60 Nguyen Du, Hanoi
Page: 6 / 6 - INTAP Version 2.65 Designation PAU
www.robatherm.com Item
1224 1020
50 ca. 418 kg ca. 286 kg

50
703

703

1048
1224
500/132
12 4 6

2166
703

998
8 4 12 8 500/132
10

264
120
1224 1224 1836
ca. 382 kg ca. 622 kg ca. 662 kg
1162

1162

1936
387

387

H9/6 H9/6 H12/6 H9/6

70 3468 120
3658
1162

1936
387

H9/8 H9/6 H12/6 H9/4.5 H9/6

Type of Unit 09/18


306 4284 120 Project Office 60 Nguyen Du, Hanoi
4710 Unit / Item PAU /
Text Offer Number 2400230.3
Drawn By / Date HN / 8/1/2024