Masoneilan
Masoneilan
03/2016
Masoneilan*
171-172 Series
Direct-Operated,
Pressure Reducing Regulator
— —
1st 2nd 3rd 1st 2nd 3rd 4th Option
1 7 X X X X X X
1 NPT or
— Action
1 Reducing 1
Diaphragm
Metal
Trim Size
01 50
Action
Differential
GAS Ends Metal Seat Diaphragm 02 Pressure
2 Flanged 2 Reducing 2 Elastomeric 03
or Soft Seat Diaphragm
04
Threaded
Ends 05
06
08
10
12
14
16
18
20
22
2 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
171 Series 172 Series
NPT or Gas End Connections Threaded or Flanged End Connections
Cast Iron Construction Carbon Steel, Stainless Steel &
The 171 series are direct-operated, pressure reducing Alloy Construction
regulators. They are available in 1/2 through 1 ½ inch (DN15 The 172 series are direct-operated, pressure reducing
through DN40) with NPT or GAS threaded connections. regulators. They are available in 1/2 through 2 inch
The regulators are available only in cast iron. The robust (DN15 through DN50) body sizes and can be supplied with
construction can sustain rugged use. The design can handle a wide range of different end connections.The flanged
inlet pressures up to 580 psig (40 barg). design provides flexibility to meet custom face to face
dimensions as required. The regulators have a compact
Features design and durable construction to sustain rugged use.
• Economical design
• In-line maintenance Features
• Elastomer discs for tight • Versatility
shutoff • In-line maintenance
• Rugged construction • High stability
• Rugged construction
Specifications
Body Specifications
Body Sizes and End Connections Body
• 1/2” through 1 1/2” (DN15 Body Sizes and End Connections
through DN40) NPT or GAS • see 172-table 1
Maximum Inlet Pressure Maximum Inlet Pressure
• 580 psig (40 barg) • see 172-table 5
Maximum Outlet Pressure Set Point Range
• see 171-table 1 • see 172-table 2
Set Point Range Materials of Construction
• 3 to 217 psig (0.21 to 15 barg) • see 172-table 4
see 171-table 1
Temperature Range
Temperature Range • see 172-tables 4, 8, 9
• see 171-tables 3, 4
Pressure Sensing
Pressure Sensing • internal (external on request)
• internal (external on request)
Capacities
Capacities • see 172-tables 5, 6
• see 171-table 6
Allowable Pressure Drop
Weight • see 172-tables 10-14 English units,
• see 171-table 5 15-19 Metric units
Weight
• see 172-tables 20, 21
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 3
29
10
31 17
9
13 (only on request)
18
Materials
12
“A” 1 Cover
11
19 2 Gasket
8 3 L.P. Body
20
4 H.P. Body
7
21 5 Pin
5
6 Plug
22
4 7 Servomotor Flange
23
8 Diaphragm
2b 9 Protection (if requested)
2a
10 O-ring Gasket
6
29 11 Diaphragm Plate
12 Spring
3 1 25 26 2c 13 Spring Cover
14 Lock Nut
16 to10
36 1.1 to 2.5 18 Spring Guide
4 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
171 Series Materials and Dimensions
171 - Table 2 - Standard Material Combinations 171 - Table 3 - Temperature Ranges for Diaphragms
on Spring CrV Steel
Chloroprene (CR)* 32 to 194°F (0 to 90°C)
Body
Ethylene-Propylene (EPDM+PTFE)** 32 to 450°F (0 to 232°C)
Cast Iron*
Fluoroelastomer (FKM+FPM)*** 32 to 392°F (0 to 200°C)
32°F < T < 450°F Stainless Steel** 32 to 450°F (0 to 232°C)
(0°C < T < 232°C)
LP Body Cast Iron 171 - Table 4 - Temperature Ranges for Disc Elastomers
HP Body 316 SS
Fluoroelastomer (FKM)* 32 to 392°F (0 to 200°C)
Cover Carbon Steel
Polytetrafluoroethylene (PTFE)*** 32 to 450°F (0 to 232°C)
Studs Carbon Steel
Stainless Steel** 32 to 450°F (0 to 232°C)
Gasket PTFE
Trim 171 - Table 5 - Assembly Weights
FKM* Air, Gas, Liquids 316 Actuator Size
Disc Size
SS** Steam Service
100/120/130/140 220
Plug Stem 316 SS 1/2” (DN15) 36.8 lbs (16.7 kg) 46.7 lbs (21.2 kg)
Guide Bushing 303 SS 3/4” (DN20) 36.8 lbs (16.7 kg) 46.7 lbs (21.2 kg)
Actuator 1” (DN25) 36.6 lbs (16.6 kg) 46.5 lbs (21.1 kg)
Spring Casing Cast Iron 1 1/2” (DN40) 36.4 lbs (16.5 kg) 46.3 lbs (21 kg)
Actuator Lower
Cast I
Casing 171 - Table 6 - Rated Cv for All Body Sizes with Elastomer
CR (Polychloroprene)* Diaphragm
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 5
172 Series Construction
Materials
31 24
1 Blindhead
13 23 2 (a,b,c,d,e) Gasket Set
3 Body
12
22
4 H.P. Insert
11
5 Inlet Flange
21
10 6 Plug
9
8 20 7 Actuator Diaphragm Case
8 Diaphragm
7 19
9 Protection
2a 18 10 O-Ring
5 13 Spring Case
16c
17c 14 Disc
4
2d 15 Guide
16a 16 (a,b,c,d) Nut
17a 14
17 (a,b,c,d) Stud
18 Screw
2b 3 2c 1 16b 27
17b 19 Diaphragm Plate (lower)
22 20 Spring Button (lower)
25
12 21 Nut
Flanged Construction 22 Ball
26 24 Adjusting Screw
25 Ball Seat
2e
26 Seal Cap
27 Plug Screw
16d
17d
Threaded Construction Optional Sealed Cap
6 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
172 Series Construction
1 Blindhead
2 Gaskets Set
3 Body
4 Plug
5 Inlet Flange
6 H.P. Insert
8 Diaphragm
9 Protection (Option)
10 O-Ring
12 Spring
13 Spring Case
15 Adjusting Screw
17 Nut
19 Screw
20 Nut
22 Screw
Flanged Construction
23 Guide
24 Outlet Flange
25 Disc
26 Stud
27 Nut
28 Plug Screw
29 Screw
31 Ball Seat
Threaded Construction 32 Ball
33 Spring
34 Pin
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 7
172 Series Dimensions
15 " ( 380)
Diam.
( 120)
4¾ "
33.13”
5.8" (147.5) 5.4" (137.5) = =
Dimensions with
balanced
A construction B
Flanged Threaded
A B
8 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
172 Series Dimensions
Flanged Threaded
A B
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 9
172 Series Set Pressure Ranges
Represents standard spring ranges. others are optional, provided upon request.
10 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
172 Series Materials
Body
Carbon Steel* Full Carbon Steel*** 316 SS* Full 316 SS***
32°F < T < 392°F -20°F < T < 482°F -20°F < T < 482°F -320.8°F < T < 482°F
(0°C < T < 200°C) (-29°C < T < 250°C) (-29°C < T < 250°C) (-196°C < T < 250°C)
Trim
Guide Bushing 304 SS / 17-4PH 304 SS / 17-4PH 304 SS / Nitronic 60 304 SS / Nitronic 60
Actuator
Special constructions are available in LCB, WCC (N.A.C.E.), 316L, 317, Duplex, Superduplex, Monel, Hastelloy B/C
Configurations/Material Availability
* Standard - Except Steam Service
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 11
172 Series Cv Ratings
End P Max
Construction
Connection 68°F (20°C) 212°F (100°C) 392°F (200°C) 482°F (250°C) 572°F (300°C)
CS
1566 psig 1566 psig 1566 psig 1566 psig 1566 psig
Full CS 108 barg) (108 barg) (108 barg) (108 barg) (108 barg)
SS
1175 psig 1088 psig 899 psig 841 psig 783 psig
Flanged Full SS
(81 barg) (75 barg) (62 barg) (58 barg) (54 barg)
Full CS NACE 1262 psig 1262 psig 1262 psig 1262 psig 1262 psig
SS NACE (87 barg) (87 barg) (87 barg) (87 barg) (87 barg)
1059 psig 899 psig 841 psig 812 psig 798 psig
Full SS NACE
(73 barg) (62 barg) (58 barg) (56 barg) (55 barg)
4061 psig 3437 psig 2886 psig 2741 psig 2567 paig
1/2” - 1”
(280 barg) (237 barg) (199 barg) (189 barg) (177 barg)
Threaded
1392 psig 1189 psig 986 psig 928 psig 870 psig
1 1/2”
(96 barg) (82 barg) (68 barg) (64 barg) (60 barg)
172 - Table 6 - Rated Cv for All Body Sizes with Elastomer Diaphragm
Body Size
Trim Number
1/2” (DN15) 3/4” (DN20) 1” (DN25) 1 1/2” (DN40) 2” (DN25)
12 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
172 Series Cv Ratings
172 - Table 7 - Rated Cv for All Body Sizes with Metal Diaphragm
Body Size
Trim Number
1/2” (DN15) 3/4” (DN20) 1” (DN25) 1 1/2” (DN40) 2” (DN25)
172 - Table 8 - Temperature Ranges and Pressure Limits for Disc Elastomers
Minimum Temperature Maximum Temperature Maximum Pressure
°C °F °C °F barg psig
Fluorocarbon (FKM-FPM)* -10 14 200 392 40 580
Polytetrafluoroethylene (PTFE)*** -200 -328 250 482 200 2900
Stainless Steel** -196 -321 455 851 280 4060
Special diaphragms are available in NBR (nitrile butadiene, Buna-N or equivalent), HNBR (hydrogenated nitrile), VMQ
(silicone), FVMQ (fluorosilicone), TFE/P (Aflas or equivalent)
Configurations/Material Availability
* Standard - Except Steam Service
** Steam Service
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 13
Allowable Pressure Drops
Room Temperature
Table 10 - Maximum Allowable Pressure Drop (Actuator size 100)
Trim Set Pressure (psig)
Number 65 141 216 292 367 442 518 595 667
1 3996 3920 3845 3770 3694 3619 3543 3466 3329
2 3996 3920 3845 3770 3694 3619 3543 3466 3329
3 3996 3920 3845 3770 3694 3619 3543 3466 3329
4 2519 3920 3845 3770 3694 3619 3543 3466 3329
5 1612 3475 3698 3698 3694 3619 3543 3466 3329
6 1120 2413 2567 2567 2567 2567 2567 2567 3329
8 630 1357 1436 1436 1436 1436 1436 1436 3329
10 403 869 914 914 914 914 914 914 3329
12 280 603 638 638 638 638 638 638 2828
14 206 443 464 464 464 464 464 464 2074
16 157 339 363 363 363 363 363 363 1581
18 124 268 276 276 276 276 276 276 1247
20 101 217 232 232 232 232 232 232 1015
22 83 179 189 189 189 189 189 189 827
T= 302° F
Trim Set Pressure (psig)
Number 65 141 216 292 367 442 518 595 667
1 3082 3007 2931 3118 2780 2705 2630 2553 2415
2 3082 3007 2931 3118 2780 2705 2630 2553 2415
3 3082 3007 2931 1952 2780 2705 2630 2553 2415
4 2519 3007 2931 1098 2780 2705 2630 2553 2415
5 1612 2886 2886 703 2780 2705 2630 2553 2415
6 1120 2002 2002 488 2002 2002 2002 2002 2415
8 630 1117 1117 275 1117 1117 1117 1117 2415
10 403 711 711 176 711 711 711 711 2415
12 280 493 493 122 493 493 493 493 2415
14 206 363 363 90 363 363 363 363 2074
16 157 276 276 69 276 276 276 276 1581
18 124 218 218 54 218 218 218 218 1247
20 101 174 174 44 174 174 174 174 1015
22 83 145 145 36 145 145 145 145 827
T= 572° F
Trim Set Pressure (psig)
Number 65 141 216 292 367 442 518 595 667
1 2531 2455 2380 2305 2229 2154 2078 2132 2002
2 2531 2455 2380 2305 2229 2154 2078 2132 2002
3 2531 2455 2380 2305 2229 2154 2078 2132 2002
4 2519 2455 2380 2305 2229 2154 2078 2132 2002
5 1612 2364 2364 2305 2229 2154 2078 2132 2002
6 1120 1639 1639 1639 1639 1639 1639 2132 2002
8 630 914 914 914 914 914 914 2132 914
10 403 595 595 595 595 595 595 2132 595
12 280 406 406 406 406 406 406 1952 406
14 206 305 305 305 305 305 305 1434 305
16 157 232 232 232 232 232 232 1098 232
18 124 174 174 174 174 174 174 868 174
20 101 145 145 145 145 145 145 703 145
22 83 116 116 116 116 116 116 581 116
14 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
Allowable Pressure Drops
Room Temperature
Table 11 - Maximum Allowable Pressure Drop (Actuator size 120)
Trim Set Pressure (psig)
Number 37 87 136 186 235 284 334 383 428
1 4023 3974 3925 3875 3826 3777 3727 3678 3633
2 4023 3974 3925 3875 3826 3777 3727 3678 3633
3 4023 3974 3925 3875 3826 3777 3727 3678 3633
4 3061 3974 3925 3875 3826 3777 3727 3678 3633
5 1959 3698 3698 3698 3698 3698 3698 3678 3633
6 1360 2567 2567 2567 2567 2567 2567 2567 2567
8 765 1436 1436 1436 1436 1436 1436 1436 1436
10 490 914 914 914 914 914 914 914 914
12 340 638 638 638 638 638 638 638 638
14 250 464 464 464 464 464 464 464 464
16 191 363 363 363 363 363 363 363 363
18 151 276 276 276 276 276 276 276 276
20 122 232 232 232 232 232 232 232 232
22 101 189 189 189 189 189 189 189 189
T= 302° F
Trim Set Pressure (psig)
Number 37 87 136 186 235 284 334 383 428
1 3110 3060 3011 2962 2912 2863 2814 2764 2719
2 3110 3060 3011 2962 2912 2863 2814 2764 2719
3 3110 3060 3011 2962 2912 2863 2814 2764 2719
4 3061 3060 3011 2962 2912 2863 2814 2764 2719
5 1959 2886 2886 2886 2886 2863 2814 2764 2719
6 1360 2002 2002 2002 2002 2002 2002 2002 2002
8 765 1117 1117 1117 1117 1117 1117 1117 1117
10 490 711 711 711 711 711 711 711 711
12 340 493 493 493 493 493 493 493 493
14 250 363 363 363 363 363 363 363 363
16 191 276 276 276 276 276 276 276 276
18 151 218 218 218 218 218 218 218 218
20 122 174 174 174 174 174 174 174 174
22 101 145 145 145 145 145 145 145 145
T-572°F
Trim Set Pressure (psig)
Number 37 87 136 186 235 284 334 383 428
1 2558 2509 2460 2411 2361 2312 2263 2213 2168
2 2558 2509 2460 2411 2361 2312 2263 2213 2168
3 2558 2509 2460 2411 2361 2312 2263 2213 2168
4 2558 2509 2460 2411 2361 2312 2263 2213 2168
5 1959 2364 2364 2364 2361 2312 2263 2213 2168
6 1360 1639 1639 1639 1639 1639 1639 1639 1639
8 765 914 914 914 914 914 914 914 914
10 490 595 595 595 595 595 595 595 595
12 340 406 406 406 406 406 406 406 406
14 250 305 305 305 305 305 305 305 305
16 191 232 232 232 232 232 232 232 232
18 151 174 174 174 174 174 174 174 174
20 122 145 145 145 145 145 145 145 145
22 101 116 116 116 116 116 116 116 116
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 15
Allowable Pressure Drops
Room Temperature
Table 12 - Maximum Allowable Pressure Drop (Actuator size 130)
Trim Set Pressure (psig)
Number 25 61 97 133 170 207 245 283 320
1 4036 4000 3964 3928 3891 3854 3816 3778 3741
2 4036 4000 3964 3928 3891 3854 3816 3778 3741
3 4036 4000 3964 3928 3891 3854 3816 3778 3741
4 2727 4000 3964 3928 3891 3854 3816 3778 3741
5 1745 3698 3964 3928 3698 3698 3698 3698 3698
6 1212 2567 2567 2567 2567 2567 2567 2567 2567
8 682 1436 1436 1436 1436 1436 1436 1436 1436
10 436 914 914 914 914 914 914 914 914
12 303 638 638 638 638 638 638 638 638
14 223 464 464 464 464 464 464 464 464
16 170 363 363 363 363 363 363 363 363
18 135 276 276 276 276 276 276 276 276
20 109 232 232 232 232 232 232 232 232
22 90 189 189 189 189 189 189 189 189
T= 302° F
Trim Set Pressure (psig)
Number 25 61 97 133 170 207 245 283 320
1 3123 3086 3050 3014 2978 2940 2902 2864 2827
2 3123 3086 3050 3014 2978 2940 2902 2864 2827
3 3123 3086 3050 3014 2978 2940 2902 2864 2827
4 2727 3086 3050 3014 2978 2940 2902 2864 2827
5 1745 2886 2886 2886 2886 2886 2886 2864 2827
6 1212 2002 2002 2002 2002 2002 2002 2002 2002
8 682 1117 1117 1117 1117 1117 1117 1117 1117
10 436 711 711 711 711 711 711 711 711
12 303 493 493 493 493 493 493 493 493
14 223 363 363 363 363 363 363 363 363
16 170 276 276 276 276 276 276 276 276
18 135 218 218 218 218 218 218 218 218
20 109 174 174 174 174 174 174 174 174
22 90 145 145 145 145 145 145 145 145
T=572°F
Trim Set Pressure (psig)
Number 25 61 97 133 170 207 245 283 320
1 2572 2535 2499 2463 2426 2389 2351 2313 2276
2 2572 2535 2499 2463 2426 2389 2351 2313 2276
3 2572 2535 2499 2463 2426 2389 2351 2313 2276
4 2572 2535 2499 2463 2426 2389 2351 2313 2276
5 1745 2364 2364 2364 2364 2364 2351 2313 2276
6 1212 1639 1639 1639 1639 1639 1639 1639 1639
8 682 914 914 914 914 914 914 914 914
10 436 595 595 595 595 595 595 595 595
12 303 406 406 406 406 406 406 406 406
14 223 305 305 305 305 305 305 305 305
16 170 232 232 232 232 232 232 232 232
18 135 174 174 174 174 174 174 174 174
20 109 145 145 145 145 145 145 145 145
22 90 116 116 116 116 116 116 116 116
16 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
Allowable Pressure Drops
Room Temperature
Table 13 - Maximum Allowable Pressure Drop (Actuator size 140)
Trim Set Pressure (psig)
Number 10 25 39 54 68 84 100 116 133
1 4051 4036 4022 4007 3993 3977 3961 3945 3928
2 4051 4036 4022 4007 3993 3977 3961 3945 3928
3 4051 4036 4022 4007 3993 3977 3961 3945 3928
4 2606 4036 4022 4007 3993 3977 3961 3945 3928
5 1668 3698 3698 3698 3698 3698 3698 3698 3698
6 1158 2567 2567 2567 2567 2567 2567 2567 2567
8 651 1436 1436 1436 1436 1436 1436 1436 1436
10 417 914 914 914 914 914 914 914 914
12 290 638 638 638 638 638 638 638 638
14 213 464 464 464 464 464 464 464 464
16 163 363 363 363 363 363 363 363 363
18 129 276 276 276 276 276 276 276 276
20 104 232 232 232 232 232 232 232 232
22 86 189 189 189 189 189 189 189 189
T= 302° F
Trim Set Pressure (psig)
Number 10 25 39 54 68 84 100 116 133
1 3137 3123 3108 3094 3079 3063 3047 3031 3014
2 3137 3123 3108 3094 3079 3063 3047 3031 3014
3 3137 3123 3108 3094 3079 3063 3047 3031 3014
4 2606 3123 3108 3094 3079 3063 3047 3031 3014
5 1668 2886 2886 2886 2886 2886 2886 2886 2886
6 1158 2002 2002 2002 2002 2002 2002 2002 2002
8 651 1117 1117 1117 1117 1117 1117 1117 1117
10 417 711 711 711 711 711 711 711 711
12 290 493 493 493 493 493 493 493 493
14 213 363 363 363 363 363 363 363 363
16 163 276 276 276 276 276 276 276 276
18 129 218 218 218 218 218 218 218 218
20 104 174 174 174 174 174 174 174 174
22 86 145 145 145 145 145 145 145 145
T=572°F
Trim Set Pressure (psig)
Number 10 25 39 54 68 84 100 116 133
1 2586 2572 2557 2543 2528 2512 2496 2480 2463
2 2586 2572 2557 2543 2528 2512 2496 2480 2463
3 2586 2572 2557 2543 2528 2512 2496 2480 2463
4 2586 2572 2557 2543 2528 2512 2496 2480 2463
5 1668 2364 2364 2364 2364 2364 2364 2364 2364
6 1158 1639 1639 1639 1639 1639 1639 1639 1639
8 651 914 914 914 914 914 914 914 914
10 417 595 595 595 595 595 595 595 595
12 290 406 406 406 406 406 406 406 406
14 213 305 305 305 305 305 305 305 305
16 163 232 232 232 232 232 232 232 232
18 129 174 174 174 174 174 174 174 174
20 104 145 145 145 145 145 145 145 145
22 86 116 116 116 116 116 116 116 116
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 17
Allowable Pressure Drops
Room Temperature
Table 14 - Maximum Allowable Pressure Drop (Actuator size 220)
Trim Set Pressure (psig)
Number 1.36 5.8 10.2 14.5 18.9 23.2 27.6 33.4 39.2
1 4060 4055 4051 4047 4042 4038 4033 4028 4022
2 4060 4055 4051 4047 4042 4038 4033 4028 4022
3 2184 4055 4051 4047 4042 4038 4033 4028 4022
4 1229 4055 4051 4047 4042 4038 4033 4028 4022
5 786 3346 3698 3698 3698 3698 3698 3698 3698
6 546 2324 2567 2567 2567 2567 2567 2567 2567
8 307 1307 1436 1436 1436 1436 1436 1436 1436
10 197 837 914 914 914 914 914 914 914
12 137 581 638 638 638 638 638 638 638
14 100 427 464 464 464 464 464 464 464
16 77 327 363 363 363 363 363 363 363
18 61 258 276 276 276 276 276 276 276
20 49 209 232 232 232 232 232 232 232
22 41 173 189 189 189 189 189 189 189
T= 302° F
Trim Set Pressure (psig)
Number 1.36 5.8 10.2 14.5 18.9 23.2 27.6 33.4 39.2
1 3146 3142 3137 3133 3128 3124 3120 3114 3108
2 3146 3142 3137 3133 3128 3124 3120 3114 3108
3 2184 3142 3137 3133 3128 3124 3120 3114 3108
4 1229 3142 3137 3133 3128 3124 3120 3114 3108
5 786 2886 2886 2886 2886 2886 2886 2886 2886
6 546 2002 2002 2002 2002 2002 2002 2002 2002
8 307 1117 1117 1117 1117 1117 1117 1117 1117
10 197 711 711 711 711 711 711 711 711
12 137 493 493 493 493 493 493 493 493
14 100 363 363 363 363 363 363 363 363
16 77 276 276 276 276 276 276 276 276
18 61 218 218 218 218 218 218 218 218
20 49 174 174 174 174 174 174 174 174
22 41 145 145 145 145 145 145 145 145
T=572°F
Trim Set Pressure (psig)
Number 1.36 5.8 10.2 14.5 18.9 23.2 27.6 33.4 39.2
1 2595 2590 2586 2582 2577 2573 2569 2563 2557
2 2595 2590 2586 2582 2577 2573 2569 2563 2557
3 2184 2590 2586 2582 2577 2573 2569 2563 2557
4 1229 2590 2586 2582 2577 2573 2569 2563 2557
5 786 2364 2364 2364 2364 2364 2364 2364 2364
6 546 1639 1639 1639 1639 1639 1639 1639 1639
8 307 914 914 914 914 914 914 914 914
10 197 595 595 595 595 595 595 595 595
12 137 406 406 406 406 406 406 406 406
14 100 305 305 305 305 305 305 305 305
16 77 232 232 232 232 232 232 232 232
18 61 174 174 174 174 174 174 174 174
20 49 145 145 145 145 145 145 145 145
22 41 116 116 116 116 116 116 116 116
18 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
Allowable Pressure Drops
Room Temperature
Table 15 - Maximum Allowable Pressure Drop (Actuator size 100)
Trim Set Pressure (barg)
Number 4.5 9.7 14.9 20.1 25.3 30.5 35.7 41 46
1 275.5 270.3 265.1 259.9 254.7 249.5 244.3 239.0 229.5
2 275.5 270.3 265.1 259.9 254.7 249.5 244.3 239.0 229.5
3 275.5 270.3 265.1 259.9 254.7 249.5 244.3 239.0 229.5
4 173.7 270.3 265.1 259.9 254.7 249.5 244.3 239.0 229.5
5 111.2 239.6 255.0 255.0 254.7 249.5 244.3 239.0 229.5
6 77.2 166.4 177.0 177.0 177.0 177.0 177.0 177.0 229.5
8 43.4 93.6 99.0 99.0 99.0 99.0 99.0 99.0 229.5
10 27.8 59.9 63.0 63.0 63.0 63.0 63.0 63.0 229.5
12 19.3 41.6 44.0 44.0 44.0 44.0 44.0 44.0 195
14 14.2 30.6 32.0 32.0 32.0 32.0 32.0 32.0 143
16 10.9 23.4 25.0 25.0 25.0 25.0 25.0 25.0 109
18 8.6 18.5 19.0 19.0 19.0 19.0 19.0 19.0 86
20 6.9 15.0 16.0 16.0 16.0 16.0 16.0 16.0 70
22 5.7 12.4 13.0 13.0 13.0 13.0 13.0 13.0 57
T= 150° C
Trim Set Pressure (barg)
Number 4.5 9.7 14.9 20.1 25.3 30.5 35.7 41 46
1 212.5 207.3 202.1 215.0 191.7 186.5 181.3 176.0 166.5
2 212.5 207.3 202.1 215.0 191.7 186.5 181.3 176.0 166.5
3 212.5 207.3 202.1 134.6 191.7 186.5 181.3 176.0 166.5
4 173.7 207.3 202.1 75.7 191.7 186.5 181.3 176.0 166.5
5 111.2 199.0 199.0 48.5 191.7 186.5 181.3 176.0 166.5
6 77.2 138.0 138.0 33.7 138.0 138.0 138.0 138.0 166.5
8 43.4 77.0 77.0 18.9 77.0 77.0 77.0 77.0 166.5
10 27.8 49.0 49.0 12.1 49.0 49.0 49.0 49.0 166.5
12 19.3 34.0 34.0 8.4 34.0 34.0 34.0 34.0 166.5
14 14.2 25.0 25.0 6.2 25.0 25.0 25.0 25.0 143
16 10.9 19.0 19.0 4.7 19.0 19.0 19.0 19.0 109
18 8.6 15.0 15.0 3.7 15.0 15.0 15.0 15.0 86
20 6.9 12.0 12.0 3.0 12.0 12.0 12.0 12.0 70
22 5.7 10.0 10.0 2.5 10.0 10.0 10.0 10.0 57
T=300°F
Trim Set Pressure (barg)
Number 4.5 9.7 14.9 20.1 25.3 30.5 35.7 41 46
1 174.5 169.3 164.1 158.9 153.7 148.5 143.3 147.0 138
2 174.5 169.3 164.1 158.9 153.7 148.5 143.3 147.0 138
3 174.5 169.3 164.1 158.9 153.7 148.5 143.3 147.0 138
4 173.7 169.3 164.1 158.9 153.7 148.5 143.3 147.0 138
5 111.2 163.0 163.0 158.9 153.7 148.5 143.3 147.0 138
6 77.2 113.0 113.0 113.0 113.0 113.0 113.0 147.0 113
8 43.4 63.0 63.0 63.0 63.0 63.0 63.0 147.0 63
10 27.8 41.0 41.0 41.0 41.0 41.0 41.0 147.0 41
12 19.3 28.0 28.0 28.0 28.0 28.0 28.0 134.6 28
14 14.2 21.0 21.0 21.0 21.0 21.0 21.0 98.9 21
16 10.9 16.0 16.0 16.0 16.0 16.0 16.0 75.7 16
18 8.6 12.0 12.0 12.0 12.0 12.0 12.0 59.8 12
20 6.9 10.0 10.0 10.0 10.0 10.0 10.0 48.5 10
22 5.7 8.0 8.0 8.0 8.0 8.0 8.0 40.1 8
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 19
Allowable Pressure Drops
Room Temperature
Table 16 - Maximum Allowable Pressure Drop (Actuator size 120)
Trim Set Pressure (barg)
Number 2.6 6 9.4 12.8 16.2 19.6 23 26.4 29.5
1 277.4 274.0 270.6 267.2 263.8 260.4 257.0 253.6 250.5
2 277.4 277.4 270.6 267.2 263.8 260.4 257.0 253.6 250.5
3 277.4 277.4 270.6 267.2 263.8 260.4 257.0 253.6 250.5
4 211.0 270.6 270.6 267.2 263.8 260.4 257.0 253.6 250.5
5 135.1 255.0 255.0 255.0 255.0 255.0 255.0 253.6 250.5
6 93.8 177.0 177.0 177.0 177.0 177.0 177.0 177.0 177.0
8 52.8 99.0 99.0 99.0 99.0 99.0 99.0 99.0 99.0
10 33.8 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
12 23.4 44.0 44.0 44.0 44.0 44.0 44.0 44.0 44.0
14 17.2 32.0 32.0 32.0 32.0 32.0 32.0 32.0 32.0
16 13.2 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
18 10.4 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
20 8.4 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
22 7.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
T= 150° C
Trim Set Pressure (barg)
Number 2.6 6 9.4 12.8 16.2 19.6 23 26.4 29.5
1 214.4 211.0 207.6 204.2 200.8 197.4 194.0 190.6 187.5
2 214.4 211.0 207.6 204.2 200.8 197.4 194.0 190.6 187.5
3 214.4 211.0 207.6 204.2 200.8 197.4 194.0 190.6 187.5
4 211.0 211.0 207.6 204.2 200.8 197.4 194.0 190.6 187.5
5 135.1 199.0 199.0 199.0 199.0 197.4 194.0 190.6 187.5
6 93.8 138.0 138.0 138.0 138.0 138.0 138.0 138.0 138.0
8 52.8 77.0 77.0 77.0 77.0 77.0 77.0 77.0 77.0
10 33.8 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0
12 23.4 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0
14 17.2 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
16 13.2 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
18 10.4 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
20 8.4 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
22 7.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
T=300°F
Trim Set Pressure (barg)
Number 2.6 6 9.4 12.8 16.2 19.6 23 26.4 29.5
1 176.4 173.0 169.6 166.2 162.8 159.4 156.0 152.6 149.5
2 176.4 173.0 169.6 166.2 162.8 159.4 156.0 152.6 149.5
3 176.4 173.0 169.6 166.2 162.8 159.4 156.0 152.6 149.5
4 176.4 173.0 169.6 166.2 162.8 159.4 156.0 152.6 149.5
5 135.1 163.0 163.0 163.0 162.8 159.4 156.0 152.6 149.5
6 93.8 113.0 113.0 113.0 113.0 113.0 113.0 113.0 113.0
8 52.8 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
10 33.8 41.0 41.0 41.0 41.0 41.0 41.0 41.0 41.0
12 23.4 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
14 17.2 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0
16 13.2 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
18 10.4 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
20 8.4 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
22 7.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
20 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
Allowable Pressure Drops
Room Temperature
Table 17 - Maximum Allowable Pressure Drop (Actuator size 130)
Trim Set Pressure (barg)
Number 1.7 4.2 6.7 9.2 11.7 14.3 16.9 19.5 22.1
1 278.3 275.8 273.3 270.8 268.3 265.7 263.1 260.5 257.9
2 278.3 275.8 273.3 270.8 268.3 265.7 263.1 260.5 257.9
3 278.3 275.8 273.3 270.8 268.3 265.7 263.1 260.5 257.9
4 188.0 275.8 273.3 270.8 268.3 265.7 263.1 260.5 257.9
5 120.3 255.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0
6 83.6 177.0 177.0 177.0 177.0 177.0 177.0 177.0 177.0
8 47.0 99.0 99.0 99.0 99.0 99.0 99.0 99.0 99.0
10 30.1 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
12 20.9 44.0 44.0 44.0 44.0 44.0 44.0 44.0 44.0
14 15.4 32.0 32.0 32.0 32.0 32.0 32.0 32.0 32.0
16 11.8 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
18 9.3 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
20 7.5 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
22 6.2 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
T= 150° C
Trim Set Pressure (barg)
Number 1.7 4.2 6.7 9.2 11.7 14.3 16.9 19.5 22.1
1 215.3 212.8 210.3 207.8 205.3 202.7 200.1 197.5 194.9
2 215.3 212.8 210.3 207.8 205.3 202.7 200.1 197.5 194.9
3 215.3 212.8 210.3 207.8 205.3 202.7 200.1 197.5 194.9
4 188.0 212.8 210.3 207.8 205.3 202.7 200.1 197.5 194.9
5 120.3 199.0 199.0 199.0 199.0 199.0 199.0 197.5 194.9
6 83.6 138.0 138.0 138.0 138.0 138.0 138.0 138.0 138.0
8 47.0 77.0 77.0 77.0 77.0 77.0 77.0 77.0 77.0
10 30.1 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0
12 20.9 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0
14 15.4 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
16 11.8 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
18 9.3 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
20 7.5 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
22 6.2 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
T=300°C
Trim Set Pressure (barg)
Number 1.7 4.2 6.7 9.2 11.7 14.3 16.9 19.5 22.1
1 177.3 174.8 172.3 169.8 167.3 164.7 162.1 159.5 156.9
2 177.3 174.8 172.3 169.8 167.3 164.7 162.1 159.5 156.9
3 177.3 174.8 172.3 169.8 167.3 164.7 162.1 159.5 156.9
4 177.3 174.8 172.3 169.8 167.3 164.7 162.1 159.5 156.9
5 120.3 163.0 163.0 163.0 163.0 163.0 162.1 159.5 156.9
6 83.6 113.0 113.0 113.0 113.0 113.0 113.0 113.0 113.0
8 47.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
10 30.1 41.0 41.0 41.0 41.0 41.0 41.0 41.0 41.0
12 20.9 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
14 15.4 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0
16 11.8 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
18 9.3 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
20 7.5 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
22 6.2 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 21
Allowable Pressure Drops
Room Temperature
Table 18 - Maximum Allowable Pressure Drop (Actuator size 140)
Trim Set Pressure (barg)
Number 0.7 1.7 2.7 3.7 4.7 5.8 6.9 8 9.2
1 279.3 278.3 277.3 276.3 275.3 274.2 273.1 272.0 270.8
2 279.3 278.3 277.3 276.3 275.3 274.2 273.1 272.0 270.8
3 279.3 278.3 277.3 276.3 275.3 274.2 273.1 272.0 270.8
4 179.6 278.3 277.3 276.3 275.3 274.2 273.1 272.0 270.8
5 115.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0 255.0
6 79.8 177.0 177.0 177.0 177.0 177.0 177.0 177.0 177.0
8 44.9 99.0 99.0 99.0 99.0 99.0 99.0 99.0 99.0
10 28.7 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
12 20.0 44.0 44.0 44.0 44.0 44.0 44.0 44.0 44.0
14 14.7 32.0 32.0 32.0 32.0 32.0 32.0 32.0 32.0
16 11.2 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
18 8.9 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
20 7.2 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
22 5.9 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
T= 150° C
Trim Set Pressure (barg)
Number 0.7 1.7 2.7 3.7 4.7 5.8 6.9 8 9.2
1 216.3 215.3 214.3 213.3 212.3 211.2 210.1 209.0 207.8
2 216.3 215.3 214.3 213.3 212.3 211.2 210.1 209.0 207.8
3 216.3 215.3 214.3 213.3 212.3 211.2 210.1 209.0 207.8
4 179.6 215.3 214.3 213.3 212.3 211.2 210.1 209.0 207.8
5 115.0 199.0 199.0 199.0 199.0 199.0 199.0 199.0 199.0
6 79.8 138.0 138.0 138.0 138.0 138.0 138.0 138.0 138.0
8 44.9 77.0 77.0 77.0 77.0 77.0 77.0 77.0 77.0
10 28.7 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0
12 20.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0
14 14.7 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
16 11.2 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
18 8.9 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
20 7.2 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
22 5.9 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
T=300°C
Trim Set Pressure (barg)
Number 0.7 1.7 2.7 3.7 4.7 5.8 6.9 8 9.2
1 178.3 177.3 176.3 175.3 174.3 173.2 172.1 171.0 169.8
2 178.3 177.3 176.3 175.3 174.3 173.2 172.1 171.0 169.8
3 178.3 177.3 176.3 175.3 174.3 173.2 172.1 171.0 169.8
4 178.3 177.3 176.3 175.3 174.3 173.2 172.1 171.0 169.8
5 115.0 163.0 163.0 163.0 163.0 163.0 163.0 163.0 163.0
6 79.8 113.0 113.0 113.0 113.0 113.0 113.0 113.0 113.0
8 44.9 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
10 28.7 41.0 41.0 41.0 41.0 41.0 41.0 41.0 41.0
12 20.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
14 14.7 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0
16 11.2 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
18 8.9 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
20 7.2 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
22 5.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
22 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
Allowable Pressure Drops
Room Temperature
Table 19 - Maximum Allowable Pressure Drop (Actuator size 220)
Trim Set Pressure (barg)
Number 0.094 0.40 0.70 1.0 1.3 1.6 1.9 2.3 2.7
1 279.9 279.6 279.3 279.0 278.7 278.4 278.1 277.7 277.3
2 279.9 279.6 279.3 279.0 278.7 278.4 278.1 277.7 277.3
3 150.6 279.6 279.3 279.0 278.7 278.4 278.1 277.7 277.3
4 84.7 279.6 279.3 279.0 278.7 278.4 278.1 277.7 277.3
5 54.2 230.7 255.0 255.0 255.0 255.0 255.0 255.0 255.0
6 37.7 160.2 177.0 177.0 177.0 177.0 177.0 177.0 177.0
8 21.2 90.1 99.0 99.0 99.0 99.0 99.0 99.0 99.0
10 13.6 57.7 63.0 63.0 63.0 63.0 63.0 63.0 63.0
12 9.4 40.1 44.0 44.0 44.0 44.0 44.0 44.0 44.0
14 6.9 29.4 32.0 32.0 32.0 32.0 32.0 32.0 32.0
16 5.3 22.5 25.0 25.0 25.0 25.0 25.0 25.0 25.0
18 4.2 17.8 19.0 19.0 19.0 19.0 19.0 19.0 19.0
20 3.4 14.4 16.0 16.0 16.0 16.0 16.0 16.0 16.0
22 2.8 11.9 13.0 13.0 13.0 13.0 13.0 13.0 13.0
T= 150° C
Trim Set Pressure (barg)
Number 0.094 0.40 0.70 1.0 1.3 1.6 1.9 2.3 2.7
1 216.9 216.9 216.3 216.0 215.7 215.4 215.1 214.7 214.3
2 216.9 216.9 216.3 216.0 215.7 215.4 215.1 214.7 214.3
3 150.6 216.9 216.3 216.0 215.7 215.4 215.1 214.7 214.3
4 84.7 216.9 216.3 216.0 215.7 215.4 215.1 214.7 214.3
5 54.2 199.0 199.0 199.0 199.0 199.0 199.0 199.0 199.0
6 37.7 138.0 138.0 138.0 138.0 138.0 138.0 138.0 138.0
8 21.2 77.0 77.0 77.0 77.0 77.0 77.0 77.0 77.0
10 13.6 49.0 49.0 49.0 49.0 49.0 49.0 49.0 49.0
12 9.4 34.0 34.0 34.0 34.0 34.0 34.0 34.0 34.0
14 6.9 25.0 25.0 25.0 25.0 25.0 25.0 25.0 25.0
16 5.3 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
18 4.2 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
20 3.4 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
22 2.8 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
T=300°C
Trim Set Pressure (barg)
Number 0.094 0.40 0.70 1.0 1.3 1.6 1.9 2.3 2.7
1 178.9 178.6 178.3 178.0 177.7 177.4 177.1 176.7 176.3
2 178.9 178.6 178.3 178.0 177.7 177.4 177.1 176.7 176.3
3 150.6 178.6 178.3 178.0 177.7 177.4 177.1 176.7 176.3
4 84.7 178.6 178.3 178.0 177.7 177.4 177.1 176.7 176.3
5 54.2 163.0 163.0 163.0 163.0 163.0 163.0 163.0 163.0
6 37.7 113.0 113.0 113.0 113.0 113.0 113.0 113.0 113.0
8 21.2 63.0 63.0 63.0 63.0 63.0 63.0 63.0 63.0
10 13.6 41.0 41.0 41.0 41.0 41.0 41.0 41.0 41.0
12 9.4 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
14 6.9 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0
16 5.3 16.0 16.0 16.0 16.0 16.0 16.0 16.0 16.0
18 4.2 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0
20 3.4 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
22 2.8 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 23
172 Series Weights
3/4” (DN20) 36.8 lbs (16.7 kg) 43.9 lbs (19.9 kg) 45.9 lbs (20.8 kg) 46.1 lbs (20.9 kg) 47 lbs (21.3 kg)
1” (DN25) 36.6 lbs (16.6 kg) 45.4 lbs (20.6 kg) 47.2 lbs (21.4 kg) 47.4 lbs (21.5 kg) 48.1 lbs (21.8 kg)
1 1/2” (DN40) 36.4 lbs (16.5 kg) 47.6 lbs (21.6 kg) 49.8 lbs (22.6 kg) 52.5 lbs (23.8 kg) 54.7 lbs (24.8 kg)
2” (DN50) N/A 50.9 lbs (23.1 kg) 53.9 lbs (24.1 kg) 54.2 lbs (24.6 kg) 57.5 lbs (26.1 kg)
3/4” (DN20) 46.7 lbs (21.2 kg) 53.8 lbs (24.4 kg) 45.9 lbs (20.8 kg) 56 lbs (25.4 kg) 56.9 lbs (25.8 kg)
1” (DN25) 46.5 lbs (21.1 kg) 55.3 lbs (25.1 kg) 47.2 lbs (21.4 kg) 57.3 lbs (26 kg) 58 lbs (26.3 kg)
1 1/2” (DN40) 46.3 lbs (21 kg) 57.5 lbs (26.1 kg) 49.8 lbs (22.6 k 62.4 lbs (28.3 kg) 64.6 lbs (29.3 kg)
2” (DN50) N/A 60.9 lbs (27.6 kg) 53.9 lbs (24.1 kg) 64.2 lbs (29.1 kg) 67.5 lbs (30.6 kg)
24 | GE Oil & Gas © 2016 General Electric Company. All rights reserved.
© 2016 General Electric Company. All rights reserved. Masoneilan 171-172 Series Pressure Reducing Regulator Tech Specifications | 25
DIRECT SALES OFFICE LOCATIONS
AUSTRALIA ITALY SOUTH AFRICA
Brisbane: Phone: +39-081-7892-111 Phone: +27-11-452-1550
Phone: +61-7-3001-4319 Fax: +39-081-7892-208 Fax: +27-11-452-6542
Fax: +61-7-3001-4399
JAPAN SOUTH & CENTRAL
Perth:
Tokyo AMERICA AND THE CARIBBEAN
Phone: +61-8-6595-7018
Phone: +81-03-6871-9008 Phone: +55-12-2134-1201
Fax: +61 8 6595-7299
Fax: +81-03-6890-4620 Fax: +55-12-2134-1238
Melbourne:
Phone: +61-3-8807-6002 KOREA SPAIN
Fax : +61-3-8807-6577 Phone: +82-2-2274-0748 Phone: +34-93-652-6430
Fax: +82-2-2274-0794 Fax: +34-93-652-6444
BELGIUM
Phone: +32-2-344-0970 MALAYSIA UNITED ARAB EMIRATES
Fax: +32-2-344-1123 Phone: +60-3-2161-0322 Phone: +971-4-8991-777
Fax: +60-3-2163-6312 Fax: +971-4-8991-778
BRAZIL
Phone: +55-19-2104-6900 MEXICO UNITED KINGDOM
Phone: +52-55-3640-5060 Bracknell
CHINA Phone: +44-1344-460-500
Phone: +86-10-5689-3600 THE NETHERLANDS Fax: +44-1344-460-537
Fax: +86-10-5689-3800 Phone: +31-15-3808666
Fax: +31-18-1641438 Skelmersdale
FRANCE Phone: +44-1695-526-00
Courbevoie RUSSIA Fax: +44-1695-526-01
Phone: +33-1-4904-9000 Veliky Novgorod
Fax: +33-1-4904-9010 Phone: +7-8162-55-7898 UNITED STATES
Fax: +7-8162-55-7921 Massachusetts
GERMANY Phone: +1-508-586-4600
Moscow
Ratingen Fax: +1 508-427-8971
Phone: +7 495-585-1276
Phone: +49-2102-108-0
Fax: +7 495-585-1279
Fax: +49-2102-108-111 Corpus Christi, Texas
Phone: +1-361-881-8182
SAUDI ARABIA
INDIA Fax: +1-361-881-8246
Phone: +966-3-341-0278
Mumbai
Fax: +966-3-341-7624 Deer Park, Texas
Phone: +91-22-8354790
Phone: +1-281-884-1000
Fax: +91-22-8354791
SINGAPORE Fax: +1-281-884-1010
New Delhi Phone: +65-6861-6100
Houston, Texas
Phone: +91-11-2-6164175 Fax: +65-6861-7172
Phone: +1-281-671-1640
Fax: +91-11-5-1659635
Fax: +1-281-671-1735
GEA31534A 03/2016