17 September 2024 - 10:54:34

Test
Name Overcurrent test - 40050 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions All preconditions satisfied.

Test result
Test completed with trip. Protection I tripped in 20 ms.
Trip time must be between 0 ms and 1000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 1/16


17 September 2024 - 10:54:34

Trip time must be between 0 ms and 1000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 2/16


17 September 2024 - 10:54:41

Test
Name Selective Overcurrent - 7300 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection S tripped in 804 ms.
Trip time must be between 0 ms and 18000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 3/16


17 September 2024 - 10:54:41

Trip time must be between 0 ms and 18000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 4/16


17 September 2024 - 10:54:48

Test
Name Selective Overcurrent - 7200 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection L tripped in 8042 ms.
Trip time must be between 0 ms and 10000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 5/16


17 September 2024 - 10:54:48

Trip time must be between 0 ms and 10000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 6/16


17 September 2024 - 10:55:04

Test
Name Earthfault

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection G tripped in 102 ms.
Trip time must be between 0 ms and 1000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 7/16


17 September 2024 - 10:55:04

Trip time must be between 0 ms and 1000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 8/16


17 September 2024 - 10:55:10

Test
Name Overload Test 1 - 2800 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection L tripped in 53695 ms.
Trip time must be between 0 ms and 100000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 9/16


17 September 2024 - 10:55:10

Trip time must be between 0 ms and 100000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 10/16


17 September 2024 - 10:56:09

Test
Name Overload Test 2 - 5000A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection L tripped in 16632 ms.
Trip time must be between 0 ms and 45000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 11/16


17 September 2024 - 10:56:09

Trip time must be between 0 ms and 45000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 12/16


17 September 2024 - 10:56:32

Test
Name Overload Test 3 - 7000 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection G tripped in 100 ms.
Trip time must be between 0 ms and 20000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 13/16


17 September 2024 - 10:56:32

Trip time must be between 0 ms and 20000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 14/16


17 September 2024 - 10:56:39

Test
Name Overload Test 4 - 7150 A

Session 17092024_TR6C

Customer ARC

Location Libya

Operator BPC

Device
Tag name TR 6A

Relay Serial Number DLN0013733915000

Circuit Breaker Serial Number CE11102167

Ekip Touch Black

Device settings In = 4000 A


Un = 400 V
fn = 50 Hz

Protection Settings Protection = L


Curve type = t=k/i^2
Threshold = 0.600 In
Time = 8.00 s

Protection = S
Curve type = t=k
Threshold = 1.80 In
Time = 0.80 s

Protection = I
Threshold = 10.00 In

Protection = G
Curve type = t=k
Threshold = 0.200 In
Time = 0.10 s

Preconditions

Test result
Test completed with trip. Protection L tripped in 8151 ms.
Trip time must be between 0 ms and 15000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 15/16


17 September 2024 - 10:56:39

Trip time must be between 0 ms and 15000 ms.

Device descriptor: 162_EkipTouch_M4_v3.79.enc Ekip Connect version: 3.4.4.0 16/16