0% found this document useful (0 votes)
14 views40 pages

Eaton EX RT en Manual

Uploaded by

jhonatan.s.n94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views40 pages

Eaton EX RT en Manual

Uploaded by

jhonatan.s.n94
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

www.eaton.

com

EX RT 5 3:1
EX RT 7 3:1
EX RT 11 3:1

Installation and user


manual

English

Français

Deutsch

Italiano

Español

Nederlands
3400772400/AD
www.eaton.com

EX RT 5 3:1
EX RT 7 3:1
EX RT 11 3:1

Installation and user


manual
Introduction

Thank you for selecting an EATON product to protect your equipment.

The EX RT range has been designed with the utmost care.


We recommend that you take the time to read this manual to take full advantage of the many features of
your UPS.

Warning: this is a class A UPS product. In a domestic environment, this product may cause radio
interference, in which case, the user may be required to take additional measures.
If the device must be installed in overvoltage category III or IV environments, additional upstream
overvoltage protection must be provided for.

To discover the entire range of EATON products and the options available for the EX RT range,
we invite you to visit our web site at www.eaton.com or contact your EATON representative.

Environmental protection
EATON cares about the environmental impact of its products and has therefore implemented an eco-design
process for the entire life cycle of the EX RT product: design, usage and recycling.

Using this document


Information may be found primarily by checking:
zz the contents,
zz the index.

Icons

Important instructions that must always be followed.

Information, tips, help.

Visual indication.

Action.

Audible alarm.

In the illustrations on the following pages, the symbols below are used:

LED off.

LED on.

LED flashing.

Page 2 - 34007724EN/AD
Contents

1. Presentation
1.1 Standard configurations ........................................................................................ 5
Tower configuration .................................................................................................. 5
Rack configuration .................................................................................................... 5
1.2 Rear panels .............................................................................................................. 6
Power module EX RT 5/7/11 . ................................................................................... 6
Battery module EX RT EXB 7/11 .............................................................................. 6
1.3 Display and control panel ...................................................................................... 7
1.4 Options ............................................................................................................... 7
Rack mounting kits ................................................................................................... 7
Transformer for galvanic isolation or earthing arrangement change ........................ 8
Battery extensions for UPS backup times up to 60 minutes ................................... 9
CLA module (Long backup time charger) for backup times from 2 to 8 hours ........ 9
Modules integration system ................................................................................... 10
Battery module with Remote Emergency Power Off function (REPO) . ................ 10
Battery extension cable (1,8 m / 6 ft) ..................................................................... 10

2. Installation
2.1 Unpacking and parts check . ................................................................................ 11
Power module . ....................................................................................................... 11
Battery module ....................................................................................................... 11
2.2 Installation in tower configuration ..................................................................... 12
2.3 Installation in rack configuration ....................................................................... 13
Adjustment of the orientation of the logo and control panels ................................ 13
Battery module rack mounting (optional rail required) ............................................ 13
Power or battery module rack mounting (optional rail required) ............................ 14
2.4 Communication ports . ........................................................................................ 16
Connection to the RS232 communication port........................................................ 16
Connection to the communications port by relays.................................................. 16
Remote Power Off . ................................................................................................ 17
Remote Power Off communication port.................................................................. 17
Installation of communication cards (optional, standard with
the Network Pack version)....................................................................................... 17
2.5 Installation depending on the system earthing arrangement (SEA) ............. 18
UPS with common Normal and Bypass AC inputs.................................................. 18
UPS with separate Normal and Bypass AC inputs.................................................. 18
UPS with separate Normal and Bypass AC inputs, supplied
by separate sources................................................................................................. 19
Frequency converter (without Bypass AC input)..................................................... 19
Hot standby ............................................................................................................. 19
2.6 Required protective devices and cable cross-sections .................................... 20
Recommended upstream protection ...................................................................... 20
Recommended downstream protection ................................................................. 20
Required cable cross-section .................................................................................. 20
2.7 Connections of input/output power cables ....................................................... 21
UPS with common Normal and Bypass AC sources .............................................. 21
UPS with separate Normal and Bypass AC sources .............................................. 22
Frequency converter................................................................................................ 23
Connection of battery cables................................................................................... 24
Connection of galvanic isolation transformer........................................................... 24
Connection of CLA module...................................................................................... 25

34007724EN/AD - Page 3
Contents

3. Operation
3.1 Initial start up ........................................................................................................ 26
UPS personalisation................................................................................................. 26
Accessing personalisation with front panel buttons................................................ 26
Access to the personalisation through external software....................................... 27
3.2 Final start up sequence ........................................................................................ 27
3.3 Operating modes .................................................................................................. 28
Normal (double conversion) mode........................................................................... 28
Eco mode ............................................................................................................. 28
3.4 Operation on battery power . ............................................................................. 29
Transfer to battery power........................................................................................ 29
Threshold for the low-battery warning..................................................................... 29
End of backup time.................................................................................................. 29
3.5 Return of Normal AC source . ............................................................................. 29
3.6 Shut down ............................................................................................................. 30

4. Maintenance
4.1 Troubleshooting . .................................................................................................. 31
4.2 Hot-swapping the power module ....................................................................... 32
Disconnecting the power module............................................................................ 32
Reconnecting the power module............................................................................. 33
4.3 Hot-swapping the battery module . .................................................................... 33
Disconnecting the battery module........................................................................... 33
Reconnecting the battery module............................................................................ 33
4.4 Training center ...................................................................................................... 34

5. Appendices
5.1 Technical specifications ....................................................................................... 35
Electrical characteristics........................................................................................... 35
Thermal characteristics............................................................................................ 38
5.2 Glossary ............................................................................................................. 38

Page 4 - 34007724EN/AD
1. Presentation

1.1 Standard configurations


Tower configuration Dimensions in mm/
inches (H x W x D)
EX RT 5
EX RT 7
444 x 131 x 635
EX RT 11
EX RT EXB 7
EX RT EXB 11

Weight in kg/lbs

EX RT 5
22.5
EX RT 7
EX RT 11 27.5

EX RT EXB 7 64.5

EX RT EXB 11 68.5

Battery module
(EX RT EXB 7/11)

Power module
(EX RT 5/7/11)

Rack configuration
Dimensions in mm/
Power module (EX RT 5/7/11) inches (H x W x D)
EX RT 5
EX RT 7
EX RT 11 131 (3U) x 444 x 635
EX RT EXB 7
EX RT EXB 11

Weight in kg/lbs

EX RT 5
22.5
EX RT 7
EX RT 11 27.5

EX RT EXB 7 64.5

EX RT EXB 11 68.5

Battery module
(EX RT EXB 7/11)

34007724EN/AD - Page 5
1. Presentation

1.2 Rear panels


Power module EX RT 5/7/11
1 Slot for communication cards.
3
1
2 Communication port by relays.
2
4 3 Remote Emergency Power Off communication port (REPO).
5
4 Connectors for automatic detection of battery module(s).

5 RS232 communications port.

6 Battery module connectors (to the UPS or to other battery


modules).

7 Manual Bypass switch.


6

8 Output terminal block.

9 Normal AC source circuit-breaker.


7
NORMAL

10 Normal AC source terminal block.


PASS
BY

8
9 11 Bypass AC source terminal block.
10
11

Battery module EX RT EXB 7/11

4 Connectors for automatic detection of battery module(s).

6 Battery module connectors (to the UPS or to other battery


modules).

12 Battery circuit breaker.

12

Page 6 - 34007724EN/AD
1. Presentation

1.3 Display and control panel


13 14 15 16 13 Load protected LED.

14 Operation on battery LED.

E X 1 1 R T 3:1 15 Operation on bypass LED.

16 Fault LED.

17 Alphanumeric display.

18 UPS OFF button.


LOAD LEVEL
4 kW / 5 kVA 17 19 20 Function buttons (scroll up /
scroll down).

21 UPS ON button (or function button


OFF ON
in personalisation mode).

18 19 20 21

1.4 Options
Rack mounting kits
Telescopic rails for Power module mounting in 19" enclosure with mounting hardware
(Part number 68001)

22 Ear hangup.

22
23 Rear bracket system for
transportation.
23
25 24 Telescopic rails, 639 mm to
1005 mm length (27.36" to 39.96").
24
25 Input/Output box bracket system.

Telescopic rails for Battery module mounting in 19" enclosure with mounting hardware
(Part number 68002)

22 Ear hangup.
22
23 Rear bracket system for
23 transportation.

24 Telescopic rails, 639 mm to


1005 mm length (27.36" to 39.96").
24

34007724EN/AD - Page 7
1. Presentation

Transformer for galvanic isolation or earthing arrangement change


(Part number 68003)
This module is necessary either when a downstream neutral system from the UPS upstream is required, or
when a different power source connects the automatic bypass for higher availability.

Example of EX RT transformer connected upstream for EX RT galvanic isolation

Battery module (EX RT EXB)

Power module (EX RT 5/7/11)

Transformer module (EX RT)

Normal AC input

UPS output to load

Bypass AC input

Page 8 - 34007724EN/AD
1. Presentation

Battery extensions for UPS backup times up to 60 minutes (at full load)
EX RT offers a standard backup time of 5/9 minutes at full load.
To increase backup time, it is possible to connect EX RT EXB 7/11 modules to the UPSs.

Battery extensions for EX RT 5, EX RT 7 or EX RT 11

EX RT 5/7
+ EX RT EXB 7 RT EX RT EXB 7 EX RT EXB 7 EX RT EXB 7 EX RT EXB 7 EX RT EXB 7

EX RT 11
/ + /
EX RT
+ /
EX RT
+ /
EX RT
+ /
EX RT
+ /
EX RT
+ EX RTEXB 11 EXB 11 EXB 11 EXB 11 EXB 11 EXB 11

5 kVA: 9 min 26 min 42 min 60 min 72 min 87 min


7 kVA: 7 min 20 min 32 min 45 min 57 min 70 min
11 kVA: 5 min 14 min 22 min 30 min 42 min 53 min

CLA module (Long backup time charger) for backup times from 2 to 8 hours
(Part number 68004)
Very long backup times, from 2 to 8 hours at full load, require a EX RT CLA module.

EX RT CLA EX RT 5/7/11

50A

~
NORMAL
PASS
BY

Battery backup Recommended batteries for:


time EX RT 5 EX RT 7 EX RT 11
2 hours 50 Ah 65 Ah 100 Ah
4 hours 100 Ah 130 Ah 200 Ah
8 hours 200 Ah 260 Ah 400 Ah

Total battery voltage : 240 V DC (20 x 12V DC).


The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation
section).

34007724EN/AD - Page 9
1. Presentation

Modules integration system (Part number 68005)


Modules integration system for
extended backup time configurations
to conveniently stack and secure up
to 8 modules on the same cart (swivel
Transformer module wheels with brakes, leveling feet,
seismic side panels, plates to lock
modules and screws included).
Power module

Batteries
modules

Battery module with Remote Emergency Power Off function (REPO)


Part number:
EX RT EXB 7 EPO: 68079
EX RT EXB 11 EPO: 68119

12 Battery circuit breaker with Remote Emergency Power OFF shunt trip.

Battery extension cable (1,8 m / 6 ft, Part number 68006)

This extended battery cable will be used instead of the standard battery cable when battery modules are
distant from each other (located in two different enclosures, for instance).

Page 10 - 34007724EN/AD
2. Installation

2.1 Unpacking and parts check


Power module

23
22

24

30

31
25 26

Battery module

27
28

29

32
25 24

22 Two sets of tower stands. 27 Tower stand expanders.


23 RS232 communications cable. 28 Battery cable.
24 Product documentation. 29 Battery communication cable.
25 Telescopic rails for rack enclosure with 30 Input/Output junction box (with 11 insulated ferrules).
mounting hardware (optional, or standard
31 Network Management card (optional, or standard in
with Network Pack version).
Network Pack version).
26 Solution-Pac power management suite
32 Bezel screw driver.
CD-ROM.

Packaging must be destroyed according to waste management standards. Recycling icons are displayed for
easy selection.

A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out
on these modules must be done so by qualified staff.

34007724EN/AD - Page 11
2. Installation

2.2 Installation in tower configuration

Use the tower stand template provided with the battery module.

1 2

3
3
4
4
4
4

Follow steps 1 to 4 to adjust the tower stands for the upright position.

Always keep 150 mm free space behind the UPS rear panel.
The distance between the tower stands should be 450 mm.

Page 12 - 34007724EN/AD
2. Installation

2.3 Installation in rack configuration


We recommend to mount the battery module first, then mount the power module above the battery

Adjustment of the orientation of the logo and control panels

4
1
2 5
3
6

Battery module rack mounting (optional rails required, part number: 68002)
The battery module is very heavy. To ease its rack integration, we strongly recommend to remove the
battery trays as explained below:

2
2

1
1
1

3
3

4
4
34007724EN/AD - Page 13
2. Installation

Power or battery module rack mounting (optional rails required, part number: 68001)

Follow steps 1 to 4 for rack mounting the UPS onto the rails.

3
2
4

4
1

The rails and the necessary mounting hardware are supplied by EATON.

Note for step 1: it is possible to adjust the position of both front mounting ears.

Page 14 - 34007724EN/AD
2. Installation

Rear bracket system (included with rail kits, part numbers 68001 and 68002)
To be used if you need to move the
rack enclosure with UPS already
rack-mounted inside.

2 2

Input/output junction box bracket system (included with power module rail kit, part
number 68001)
This bracket will maintain the Input/Output box at the rear of the rack enclosure when hot-swapping the
power module.
It will then be easier to slide the replacement module into the connectors of the Input/Output box.

1
2

4
3
3

34007724EN/AD - Page 15
2. Installation

2.4 Communication ports


EX RT provides 3 communication methods that can be used simultaneously:
zz The COM port provides RS232 communications using EATON SHUT protocol. Compatible with most
power management software applications available into the enclosed Solution Pac CD-Rom.
zz The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries
(formerly AS400) and more.
zz The slot is compatible with any EATON communication card (check www.eaton.com web site for the
complete list of compatible cards).

Connection to the RS232 communication port

1 - Connect the RS 232 23


communications cable to the serial
port on the computer.
23
2 - Connect the other end of the
communications cable 23 to the RS
232 5 communications port on the
UPS.
5
The UPS can now communicate with
various EATON power management
application software. Please note
that the configuration software is
included with Personal Solution Pac
for Windows.
NORMAL
PASS
BY

Connection to the communication port by relays 2

zz Pin 1, 2: not used,


zz Pin 3: Remote Power Off signal (5 to 27 V DC, 10 mA max),
5 4 3 2 1 zz Pin 4: Operation on mains (not on battery),
9 8 7 6 zz Pin 5: User common,
zz Pin 6: Operation on automatic by-pass,
n.c. n.o. n.o. n.o. n.o. zz Pin 7: Low battery,
zz Pin 8: Load protected,
zz Pin 9: Operation on battery.
common
n.o.: contact normally open.
n.c.: contact normally closed.

When the status is active, the contact between the common (Pin 5) and the relevant information pin is
closed.

Output relays specifications


zz Voltage: 48 V DC max,
zz Current: 2 A max,
zz Power: 62,5 VA, 30 W.
Example: for 48 V DC, Imax = 625 mA

Page 16 - 34007724EN/AD
2. Installation

Remote Power Off


Installation of a Remote power off function must be carried out in compliance with applicable regulations.

In order to fully de-energize devices and EX RT with an RPO port, it is necessary :


- To use a two-position switch (Normally Open or Closed contact should be held more than 1 second to be
taken into account).
- To use battery cabinet(s) EX RT EXB EPO.
- To connect to this RPO switch a device that allows to trip all breaker(s) located upstream(1) AC NORMAL
and AC BY PASS as well as downstream(2) the EX RT. This can be achieved through by means of a shunt
trip.

(1) If not, the output devices will remain powered through the AC BY PASS if RPO switch has been
loosened.
(2) If not, the output devices will remain powered several seconds after the RPO activation.

Remote Power Off communication port 3


Used in conjunction with the optional EPO battery module, this port enables total isolation of all power
sources connected to the UPS in case of emergency (the cable is not provided).

Remote power off contact normally open Remote power off contact normally closed

RJ11 RJ11

654321 654321
5 V DC to
27 V DC

5 V DC to
27 V DC

zz Signal:
- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.

Installation of communication cards (optional, standard with the Network Pack version)

1 Communication card.

It is not necessary to shut down the


UPS to install the communication card:

ETHERNET Setting/Sensor
1 - Remove the slot cover secured by
100M 10M UPS data Reset
two screws.

2 - Insert the card 1 into the slot.

3 - Secure the card with both screws.


NORMAL
PASS
BY

34007724EN/AD - Page 17
2. Installation

2.5 Installation depending on the system earthing arrangement (SEA)

EX RT must be fed from a 3-phase source with neutral.

UPS with common Normal and Bypass AC inputs

Main
low-voltage 11
switchboard
(MLVS)
Bypass AC
Normal AC
10 8 load

Changement de SLT entre amont et aval ou isolation galvanique requis

Main Bypass AC
low-voltage 11
switchboard
(MLVS)

10 8 load
Normal AC

ASI avec réseaux d'entrée AC Normal et AC Bypass séparés


Main Bypass AC
low-voltage 11
switchboard
(*)
(MLVS)

10 8 load
Normal AC

Changement de SLT entre amont et aval ou isolation galvanique requis

Main Bypass AC
low-voltage 11
switchboard
(MLVS) (*)

10 8 load
Normal AC

(*): The transformer is not necessary if:


zz Normal and Bypass AC inputs are connected to the same source,
zz and wires cross sections and wires lengths on Normal and Bypass inputs are identical,
zz and upstream protection is provided by only one switch with RCD (residual current device) for Normal
and Bypass inputs.

Page 18 - 34007724EN/AD
2. Installation

UPS with separate Normal and Bypass AC inputs, supplied by separate sources

Bypass AC
MLVS 1 11

MLVS 2 load
10 8
Normal AC

or

Bypass AC
MLVS 1 11

MLVS 2 10 8
load
Normal AC

Change in SEA between upstream and downstream or galvanic isolation required

Bypass AC
MLVS 1 11

MLVS 2 10 8
load
Normal AC

Frequency converter (without Bypass AC input)


Configuration used when the frequency of the application differs from the Mains (Example: marine
requirements).

Main
low-voltage 11
switchboard
(MLVS)
Normal AC
10 8 load

Hot stand by
Configuration used to provide full redundancy (N+1) to critical loads.
Main
low-voltage Bypass AC
switchboard 11
(MLVS)

10 8
Normal AC
(*)
(see page 18)

11

Normal AC
10 8 load

34007724EN/AD - Page 19
2. Installation

2.6 Required protective devices and cable cross-sections


Recommended upstream protection

UPS Common AC inputs Separate AC inputs


power Upstream circuit-breaker Upstream circuit-breaker Upstream circuit-breaker
rating Normal / Bypass AC sources Normal AC source Bypass AC source
5 kVA D curve - 40 A C curve - 32 A D curve - 40 A
7 kVA D curve - 40 A C curve - 32 A D curve - 40 A
11 kVA D curve - 63 A C curve - 40 A D curve - 63 A

Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the
positions of the protection devices, the characteristics of the internal UPS fuses and UPS line currents
under overload conditions.

Recommended downstream protection


UPS power Downstream The indicated protection ensures
rating circuit breaker discrimination for each output circuit
downstream of the UPS, whether
Z curve - 10 A
5 kVA supplied by the Normal or the Bypass
C curve - 4 A AC source.
Z curve - 10 A If these recommendations are not
7 kVA followed, protection discrimination
C curve - 4 A is not achieved and may result in a
Z curve - 10 A potential power interruption to the
11 kVA connected devices.
C curve - 6 A

Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the
positions of the protection devices, the characteristics of the internal UPS fuses and UPS line currents
under overload conditions.

Required cable cross-sections


zz Terminal-block cable capacity: 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
zz Capacity for earthing conductor: 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).

Page 20 - 34007724EN/AD
2. Installation

2.7 Connections of input/output power cables


zz This type of connection must be carried out by qualified electrical personnel.
zz Before carrying out any connection, check that the battery circuit breaker 12 and that the upstream
protection devices (Normal and Bypass AC sources) are open ("0").
zz EX RT UPS always comes from factory with Normal and Bypass AC inputs already connected together,
using a bridge.
zz Use included insulated ferrules with stranded wires.

UPS with common Normal and Bypass AC sources


To access the connection terminal
blocks, see section 1.2 "Rear panel":
t
1 - Remove the terminal block cover
(5 screws),
Outpu L
N

Bypas
s Input
L2
2 - Insert the Normal AC cable through
the cable gland,
ut N2
ier Inp
Rectif L1
L1
L2
L3
N1

3 - Connect the 5 wires to the Normal


1 AC terminal block,

1 Always connect the earthing

1 1 wire first.
1
4 - Insert the output cable to the load
through the output cable gland,
5 - Connect the 3 wires to the output
terminal block,
6 - Refit the terminal block cover and
Outpu
N
t
L
tighten the cable glands,
7 - Secure the junction Input/Output
N1
Rectif
L3
ier Inp
L2
ut
L1
L1
Bypas
s Input

N2
L2
5 box to the rear of the power module
by means of the 3 screws.
4

3 2

t
Outpu L
N

s Input
Bypas

6
ut L2
N2
ier Inp
Rectif L1
L1
L2
L3
N1

6 6 6
6

7
AL
φ NORM

7
66074
Card Settings

7
data
UPS

ETHERNET
10
100
Reset

RS232 Download
MAC=00E0D8FF855E

ON
1 2
IP=

34007724EN/AD - Page 21
2. Installation

UPS with separate Normal and Bypass AC sources


1 - Remove the terminal block cover
(5 screws),
t
2 - Remove the bridge connected
between L2 and L1,
Outpu L
N

Bypas
s Input 3 - Insert the Normal AC cable through
2
ut L2
N2

the cable gland,


ier Inp
Rectif L1
L1
L2
L3
N1

1 4 - Connect the 5 wires to the Normal


AC terminal block,
1 Always connect the earthing
1 wire first.
1 1
5 - Insert the Output cable to the load
through the Output cable gland,
6 - Connect the 3 wires to the output
terminal block,
t
7 - Insert the Bypass cable through the
6
Outpu L
N

cable gland,
s Input

8 - Connect the 3 wires to the Bypass


Bypas
ut L2
N2
ier Inp
Rectif L1
L1
L2
L3

AC terminal block,
N1

8 5 9 - Refit the terminal block cover and


tighten the cable glands,
4 10 - Secure the junction Input/Output
box to the rear of the power module
by means of the 3 screws.
3 7

t
Outpu L
N

s Input
Bypas
ut L2
N2
ier Inp

9
Rectif L1
L1
L2
L3
N1

9
9 9
9

AL
10
φ NORM

10
66074

10
Card Settings

data
UPS

ETHERNET
10
100
Reset

RS232 Download
MAC=00E0D8FF855E

ON
1 2
IP=

Page 22 - 34007724EN/AD
2. Installation

Frequency converter
1 - Remove the terminal block cover
(5 screws),
t
2 - Remove the bridge connected
between L2 and L1,
Outpu L
N

Bypas
s Input 3 - Insert the Normal AC cable through
2
L2

the cable gland,


ut N2
ier Inp
Rectif L1
L1
L2
L3
N1

1 4 - Connect the 5 wires to the Normal


AC terminal block,

1 1 Always connect the earthing


wire first.
1 1
5 - Insert the Output cable suppling the
load through the Output cable gland,
6 - Connect the 3 wires to output
terminal block,

6
t
Outpu L

Do not connect anything to the


N

ut
Bypas
N2
s Input
L2
Bypass AC terminal block,
ier Inp
Rectif L1
L1
L2
L3
N1

5 7 - Refit the terminal block cover and


tighten the cable glands,
4 8 - Secure the junction Input/Output
box to the rear of the power module
by means of the 3 screws.
3

t
Outpu L
N

s Input
Bypas
ut L2
N2

7
ier Inp
Rectif L1
L1
L2
L3
N1

7 7 7
7

NORM
AL
8
φ

8
66074
Card Settings

8
data
UPS

ETHERNET
10
100
Reset

RS232 Download
MAC=00E0D8FF855E

ON
1 2
IP=

34007724EN/AD - Page 23
2. Installation

Connection of battery cables


1 - Check that the battery circuit
4 breaker 12 is OFF ("0" position),
2 - Connect the battery power cable
29 28 to the connectors 6 of the power
and battery modules,
3 - Connect the battery detection cable
29 to the connectors 4 of the power
and battery modules,
28

NORMAL
12
PASS
BY

Connection of galvanic isolation transformer

INPUT

N
L

OUTPUT

N
L

Transformer Input

Transformer Output

zz Output cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
zz Input cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).

Page 24 - 34007724EN/AD
2. Installation

Connection of CLA module

29
BATTERY

28
_

AC INPUT

N
L

To battery

NORMAL
PASS
BY
AC Input

zz Connect the battery cable 28 (provided with the CLA module) between the power module and the CLA
module.
zz Connect the cable 29 (provided with the CLA module) between the power module and the CLA module.
zz Connect the battery:
- cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
zz Use a circuit-breaker (curve B, 50 A) for cable protection.
zz Connect the input cable of the CLA module to the AC input:
- AC input cable cross-section (not provided) : 2,5 mm².
zz Use a circuit-breaker (curve C, 10 A) for cable protection.

34007724EN/AD - Page 25
3. Operation

3.1 Initial start up


15 Check that the manual bypass switch 7 is on Normal position.
Set the normal AC source circuit-breaker 9 to the "I" position.
Set the battery circuit breaker 12 to the "I" position.
The load is powered via the bypass AC source, but not protected by
the UPS.
PRESS ONTO START Batteries are recharging, an eight-hour recharge period is necessary
UPS to get full backup time.
LED 15 is ON.
OFF ON

UPS personalisation
If specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.
It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for
Windows included in the EATON Solution-Pac power management suite CD-ROM.

Accessing personalisation with front panel buttons

zz Press "scroll up" 19 and "scroll down" 20 function buttons


together for more than 3 seconds.
UPS SET UP zz Press the function button 20 placed under the ENT word to
EXIT ENT
enter the set up mode and follow the LCD messages using the
buttons now defined as select keys.
OFF ON

19 20

Local settings
Function Factory setting Options
Language English French, Spanish, German, Italian.
Date / time format International format US format (MM-DD-YYYY/HH:MM AM/PM).
(DD-MM-YYYY/HH:MM)
Date / time change Time in France MM-DD-YYYY/HH:MM adjustable.
Audible alarm Quick beeps Slow beeps.

Personnalisation de la sortie
Function Factory setting Options Comments
Output voltage 230 Volts AC 200/208/220/240/250
Frequency converter Disabled Enabled Bypass AC source disabled.
Output frequency Auto ranging 50/60 Hz User selectable under
frequency converter mode.
Eco mode Disabled Enabled See glossary.
Hot standby Disabled Enabled N+1 redundancy
(See section 2.5 "Hot
standby").
Operating mode Industrial I/T Network (*)
Transfer on Bypass AC If the Bypass AC source If the Bypass AC source
(*)
source is out of tolerances is inside tolerances
Break time 10 ms 10 to 200 ms Break time calibration during
(by steps of 10 ms) load transfer on Bypass AC
source out of tolerances.
Overload level 102 % 50/70 %

(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.
- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity
(with potential 10 ms break).
Page 26 - 34007724EN/AD
3. Operation

ON/OFF features
Function Factory setting Options Comments
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled Enables automatic restart of the system
even if normal AC source is restored before
the end of the shutdown sequence.
Automatic restart Enabled Disabled UPS restarts automatically
when normal AC source is restored.
Sleep mode Disabled Automatic shudown on battery if output
Enabled
load level < 10%.
UPS ON/OFF by software Enabled Disabled Enables consideration of shutdown
or restart orders from software to be
authorized.

Personnalisation batterie
Function Factory setting Options Comments
Battery test Every week No test / daily / monthly
Low battery signal 20 % 0 to 100 % 1% increment.
Run time choice UPS reads # of battery From 50 to 400 Ah Requires EX RT CLA if using
modules connected options (see section 1.4
"Battery extensions").
Battery deep discharge Enabled Disabled If disabled, lost of EATON
protection warranty.

zz Use EXIT key when set up is completed.


zz These parameters are only adjustable if UPS is OFF.

Access to the personalisation through external software


zz Insert the Solution-Pac CD ROM in your CD drive.
zz At the first Navigator Screen, select "Installation" and follow the instructions to install Personal
Solution-Pac for Windows.
zz If nothing appears, launch startup.exe
zz Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.

3.2 Final start up sequence


zz Press the ON button more than 3 seconds.
zz After UPS internal test sequence, the green LED 13 goes on.

During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated
break.

34007724EN/AD - Page 27
3. Operation

3.3 Operating modes


Normal (double conversion) mode

13 This is the standard operating mode, set by default in the


factory.
Two possible choices.
1 - Normal AC source available:
LED 13 is ON.

LOAD LEVEL The load is protected by the UPS.


4 kW / 5 kVA
Scroll up 19 and scroll down 20 function buttons allow you
OFF ON to read the UPS measurements (Normal AC source voltage,
Bypass AC source voltage, operating mode, battery capacity
and UPS Serial Number).

19 20 21

13 14

2 - Normal AC source not available:


LED 13 flashes.
LED 14 is ON.
The audible alarm sounds intermittently.
BACKUP TIME
10 minutes The load is supplied by the UPS from battery power.

OFF ON Do not operate the manual Bypass switch 7 when the UPS is
in the normal mode.

Eco mode
13 15
The main advantage of the Eco mode (see glossary) is that it
reduces the consumption of electrical power.
Three possible choices:

1 - Bypass AC source available:


LEDs 13 and 15 are ON.
ECO MODE The load is supplied in ECO mode.
4 kW / 5 kVA

OFF ON

13

2 - Bypass AC source not available:


LED 13 is ON.
The audio alarm sounds intermittently.
The load is automatically supplied in Normal mode via the
Normal AC input.

13 14
OFF ON
3 - Both Normal and Bypass AC sources not available or out of
tolerance:
LED 13 is ON.
LED 14 is ON.
The audio alarm sounds intermittently.

The load is supplied by the UPS from battery power.


The display indicates the battery remaining backup time.
OFF ON

Page 28 - 34007724EN/AD
3. Operation

3.4 Operation on battery power


The load continues to be protected by the UPS when the Normal AC source is not available. Power is
supplied by the battery.

Transfer to battery power

13 14 LED 13 is ON.
LED 14 is ON.
The audio alarm beeps every 10 seconds.

The load is supplied by the battery.


The display indicates the battery remaining backup time.
BACKUP TIME
10 minutes

OFF ON

Threshold for the low-battery warning

13 14 LED 13 is ON.
LED 14 flashes.
The audio alarm beeps every 3 seconds.

Low battery warning on display. There is very little remaining


BACKUP TIME battery backup time. Close all applications because UPS
2 minutes automatic shutdown is impending.

OFF ON

End of backup time

13 14 15 LED 13 and 14 are OFF.


The audio alarm is stopped.

The load is transferred to the Bypass AC source if available. In this


case, the LED 15 is ON.
STOP
END BACKUP TIME

OFF ON

3.5 Return of Normal AC source


After an outage, the UPS restarts automatically when AC power is restored (unless this function has been
disabled via UPS personalisation).

34007724EN/AD - Page 29
3. Operation

3.6 Shut down


15 1 - Press the OFF button 18 more than 3 seconds.

The load is no longer protected by the UPS. It is


powered via the bypass AC source. If the UPS is set in
frequency converter mode, the load will not be
powered.
LOAD LEVEL If the bypass AC source is out of tolerance, the UPS
4 kW / 5 kVA
will generate a 10 ms output calibrated break.
OFF ON 2 - Set the battery circuit breaker(s) 12 to the "0" position.
3 - Set the Normal AC source circuit-breaker 9 to the "0"
position.
4 - For a full shutdown of UPS and connected load, the
18
12 9 NORMAL
PASS
BY

Page 30 - 34007724EN/AD
4. Maintenance

4.1 Troubleshooting
If any of LEDs 15 or 16 is on, there is an operating anomaly or an alarm.
Use "scroll up" or "scroll down" function button to reset the audible alarm.

Troubleshooting not requiring EATON after-sales support:


Indication Signification Correction
Led 15 is on, AC source is not connected Rewire correctly the normal AC
the alphanumeric display shows: to the correct terminals. source.
BAD CONNECTION
REWIRE AC NORMAL
Led 15 is on, Load supplied by bypass AC Push the ON button for more than
the alphanumeric display shows: source. 3 seconds.
LOAD LEVEL
Xx kW / XX KVA
Led 15 is on*, UPS overload. Check the power drawn by the
the alphanumeric display shows: equipment and disconnect any
THERMAL OVERLOAD non-priority devices.
1XX%
Led 16 is on, Short circuit conditions on output Check if any device is shorted or
the alphanumeric display shows: devices. failed.
CURRENT OVERLOAD
Audible alarm is on, Junction of Input/Output box Check if the junction Input/Output
the alphanumeric display shows: not correctly screwed.
I/O BOX REMOVED

(*) : if bypass AC source available.

Troubleshooting requiring EATON after-sales support:


Indication Signification Correction
Leds 15 * and 16 are on Internal fault and transfer of load Follow the UPS replacement
and audible alarm is on. on bypass AC source. procedure (see section 4.3).
The alphanumeric display shows: Call the after sales support
xxx FAULT department.
www.eaton.com
Led 15 is on* and audible alarm is Battery fault during the battery Follow the battery replacement
on. test. procedure (see section 4.3).
the alphanumeric display shows: Call the after sales support
BATTERY FAULT department.
Led 15 is on, Static switch failure. Follow the UPS replacement
the alphanumeric display shows: procedure (see section 4.3).
SHUTDOWN Call the after sales support
STATIC SW FAILED department.
Audible alarm is on, and the Batteries may have exceeded Call the local after sales support:
alphanumeric display shows: there rated life period. Battery www.eaton.com, "Contact Us"
BATTERY CHECK capacity is severely reduced. section**.
www.eaton.com

(*): if bypass AC source is available.


(**): to reset this alarm permanently, press both function buttons 19 and 20 for more than 3 seconds and
access the LCM Setup menu.

34007724EN/AD - Page 31
4. Maintenance

4.2 Hot-swapping the power module

This operation can be performed without interrupting the load.

Disconnecting the power module


15
zz Stop the UPS with the OFF button 18 (press more than 3
seconds).
zz Check if UPS is on bypass AC source:
led 15 is on (If led 15 is not on, do not turn the manual bypass
and call the after sales support department).
XXX FAULT zz Turn the manual bypass switch 7 to the BYPASS position.
1CXXXXXXX zz Switch the battery circuit breaker(s) 12 to the "0" position.
zz Switch the Normal AC source circuit-breaker 9 to the "0"
OFF ON position and wait 30 seconds.
zz Remove the three fixing screws to free the junction Input/
Output box.
zz Disconnect the battery cables 28 and 29 from the power
18 module.

The power module can be replaced.


The connected equipment is powered by the Bypass AC
Tower configuration source.

29

28

12

Rack configuration

Page 32 - 34007724EN/AD
4. Maintenance

Reconnecting the power module


15 zz Secure the Input/Output junction box using the three screws.
zz Reconnect the battery cables 28 and 29 to the power
module.
zz Switch the battery circuit breaker(s) 12 to the "I" position.
zz Switch the Normal AC source circuit-breaker 9 to the "I"
position.
LOAD LEVEL
zz Turn the manual bypass switch from the BYPASS to the
4 kW / 5 kVA
NORMAL position.
zz Check that the led 15 is on.
OFF ON
zz Follow initial start up sequence (see section 3.1) in order to
personalize the UPS.
zz Push the ON button 21 for more than 3 seconds.
21 The green led 13 is on, and the connected equipment is now
protected by the UPS.

4.3 Hot-swapping the battery module


Disconnecting the battery module

29 29 28 zz Switch the battery circuit breaker(s) 12 to the "0" position.


zz Disconnect the battery cables 28 and 29 from the power
module.

The battery module can be replaced. The connected equipment


is powered by the UPS.
It is also possible to replace battery trays instead of battery
module.
Contact your nearest after sales support service.
To remove battery trays:
zz First, switch the battery circuit breaker(s) 12 to the "0"
position.
zz See section 2.3 and follow instructions to remove battery
trays.
NORMAL
PASS
BY

28 12

Reconnecting the battery module

zz Reconnect the battery cables 28 and 29 to the power


module.
zz Switch the battery circuit breaker(s) 12 to the "I" position.

To reconnect battery trays:


See section 2.3 and follow the reverse instructions.
zz When battery module front panel is closed, connect the
battery cables 28 and 29 to the power module.
zz Switch the battery circuit breaker(s) 12 to the "I" position.

34007724EN/AD - Page 33
4. Maintenance

4.4 Training Center


To allow you to use EATON products effectively and carry out basic maintenance, we offer a complete
range of technical training courses in English and French.

For further information, please visit our website: www.eaton.com

Page 34 - 34007724EN/AD
5. Appendices

5.1 Technical specifications


Electrical characteristics
I/T network and industrial operating modes
Mode Industrial mode I/T network mode
Overload, and Bypass Same as I/T network mode, but the UPS Load is transfered to Bypass AC
AC source in tolerance. does not return to normal mode if overload source.
released. UPS returns to normal mode if
overload released.
Overload, and Bypass Load is transfered to Bypass AC source The UPS shuts down and load is not
AC source not in with 10 milliseconds output break. The transfered to Bypass AC source.
tolerance. UPS does not return to normal mode if
overload released.
Output short circuit and Load is transfered to Bypass AC source, The load remains powered by the
Bypass AC source in the UPS returns to normal mode if the UPS.
tolerance. short circuit is released by downstream The UPS shuts down after 3 minutes
circuit breaker action (see section 2.6). if the short circuit remains.
Output short circuit and The load is transfered to Bypass AC source The load remains powered by the
Bypass AC source not with 10 milliseconds output break. The UPS. The UPS shuts down after 3
in tolerance. UPS does not return to normal mode if the minutes if the short circuit remains.
short circuit is released by downstream
circuit breaker action (see section 2.6).

Selection of protection devices


UPS unit with common Normal and Bypass AC inputs

11

Upstream Normal Downstream


circuit breaker AC source circuit breaker
Bypass AC circuit Input Output
Normal AC (not supplied) fuse fuse (not supplied)
breaker
10 8
9

UPS unit with separate Normal and Bypass AC inputs

Upstream
circuit breaker
Bypass AC (not supplied)
11
Normal
Upstream AC source Downstream
circuit breaker circuit Output circuit breaker
Input fuse
Normal AC (not supplied) breaker fuse (not supplied)
10 8
9

When sizing the upstream circuit breakers, the parameters presented below must be taken into account:

Line current values


UPS Continuous current Continuous current Input fuse rating Output fuse rating
power rating at 400/320 Volts at 320 Volts and
and nominal load overload = 110 %
limited to 2 minutes
5 kVA 9/10 A 11 A 25 A 80 A
7 kVA 10/11 A 12 A 25 A 80 A
11 kVA 15/19 A 21 A 30 A 100 A

Discrimination of upstream/downstream protections mentioned in paragraph 2.6 is achieved for a 30 m


cable length and 10 mm2 cross section.
Circuit breaker capacity must be selected according to the installation, length and cross section of cables.

34007724EN/AD - Page 35
5. Appendices

Time/current curves for UPS Normal AC source circuit-breaker


t (s)
103

102

10

10- 1

-2
10

I / In
-3
10
0 1 2 3 4 5 6 7 8 9 10
1,25 1,5

Time/current curves for UPS input and output fuses


t (s) t (s)
104
103

103
2
10

102
10

10
1

1
10- 1

I (A) 10- 1
-2
10
10 102 103

Intput fuses of Intput fuses of -2


10
EX RT 5: 25 A EX RT 11: 30 A
EX RT 7: 25 A

10- 3

I (A)
10- 4 2 3
10 10 10 104

Output fuses of Output fuses of


EX RT 5: 80 A EX RT 11: 100 A
EX RT 7: 80 A
Page 36 - 34007724EN/AD
5. Appendices

UPS Input / output characteristics

Source Voltage Frequency


Normal AC source 320 to 465 Volts AC 40 to 70 Hz
Bypass AC source 187 to 264 Volts AC* 48 to 52 Hz**
Load output 230 Volts AC (200/208/220/240/250 V 50/60 Hz autoranging
are possible values) (or frequency converter)

(*): depends on output voltage setting, can be modified by software.


(**): set to +/- 4% by default, (1,2,4,8 are possible values), can be modified by software.

Power supplied as a function of input voltage

P/Pn
100%

70%

U
250V 320V 465V

Permissible UPS overloads as a function of time

P/Pn

1.5

1.25

1.1

1.02 t
0.5s 30s 60s 120s

Short-circuit current provided by the UPS in Normal or Batterie mode


zz EX RT 5: 110 A for 80 ms.
zz EX RT 7: 110 A for 80 ms.
zz EX RT 11: 150 A for 80 ms.

EX RT Transformer
Nominal power 11 kVA
Nominal current 63 A
Input voltage 160-280 Volts AC
Voltage drop 7 Volts at nominal load
Frequency 50/60 Hz (+/-10 %)
Isolation (EN 61558-1-2-4) 3.75 kV / 5 M ohms
Operating temperature From 0° to +40°C
Max. operating rel. humidity 95 %
Derating / altitude Pn -10 % > 1000 m
Dimensions HxWxD (tower) 444 x 131 x 635 mm
Dimensions HxWxD (rack 3U) 131 x 444 x 635 mm
Weight 86.5 kg

34007724EN/AD - Page 37
5. Appendices

EX RT CLA module

zz AC input voltage: 160-280 Volts AC,


zz Input frequency: 40-70 Hz,
zz Battery charge current: 6 A DC,
zz Recharge time to recover 90% of the rated backup time after discharge at full load:

Configuration for Configuration for Configuration for


2 hours backup time 4 hours backup time 8 hours backup time
EX RT 5 5 hours 12 hours 20 hours
EX RT 7 5 hours 12 hours 20 hours
EX RT 11 7 hours 15 hours 24 hours

Thermal characteristics
zz The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20
to +25°C range.
zz Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at
temperatures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery
manufacturers no longer guarantee operation due to the risk of thermal runaway.
◗ Air enters through the front and exits through the back.

5.2 Glossary
Backup time Time that the connected loads can operate on battery power.

Bypass AC source Source supplying the bypass line. The load can be transferred to the bypass line if
an overload occurs on the UPS output, for maintenance or in the event of a
malfunction.

ECO mode Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user. This mode reduces the consumption of
electrical power.

Load Devices or systems connected to the UPS output.

Manual bypass Rotary switch controlled by the user, used to connect the loads directly to the
AC source.
Transfer of the load to the manual bypass enables UPS maintenance without
interrupting the supply of power to the connected loads.

Normal (double conversion) mode


The normal UPS operating mode in which the AC source supplies the UPS which
in turn supplies the connected loads (after electronic double conversion).

Normal AC source Normal source of power for the UPS.

Relay contacts Contacts supplying information to the user in the form of signals.

UPS Uninterruptible Power Supply.

Page 38 - 34007724EN/AD

You might also like