EDİSON TRAFO ENERJİ METAL SAN. VE TİC.LTD ŞTİ.
TECHNICAL OFFER
3‐Phase Hermetically Sealed Oil Immersed Distribution Transformers Technical Specification
item Description Unit Particulars
1 Rated Power KVA 100
2 HV & LV windings material Copper
3 Applied Standard IEC 60076
4 Primary Voltage KV 20
5 Secondary Voltage (at No‐load) KV 0.4
6 Rated Primary Current A 2.89
7 Rated secondary current A 144.34
8 Frequency Hz 50
9 Vector Group Dyn11
10 Voltage Regulation % ±2 * 2.5%
11 Maximum Ambient Temperature °C 50
12 Maximum Temperature Rise for oil °C 50
13 Maximum Temperature Rise for winding °C 55
14 No‐load losses (W) 260
15 Copper losses (at 75 °C) (W) 1475
16 Impedance Voltage (IEC Tolerance Applied) % 4
17 Transformer Type Hermetically Sealed
18 Cooling Method ONAN
19 Weight of oil kg 130
20 Total weight of transformer kg 680
21 Over all Dimensions Length x Width x Height mm 1150 x 760 x 1360
Tolerance in dimensions and weights ±10 %
E-Posta: Edison.com.tr@gmail.com
E-Posta: info@edison-tr.com Web site: www.edison-tr.com
EVREN 7 CADDE SK. NO:13/B BATIKENT MH / ŞANLIURFA