Cable Stay Specification
Cable Stay Specification
2022
6.10.7 The scope includes cost of all materials, labour, equipment & operations
required to do this test.
This section of the specifications covers the requirements for the materials,
fabrication, testing, transportation, installation, and corrosion protection system
for the stay cables and the dampers.
It includes the stay components which are part of the structure, such as the guide
pipes, the anchorage bearing plates, erection devices and incidental materials and
labour necessary to form a complete stay cable system to support the bridge
structure in accordance with the design, the applicable standards, specifications
and/or special provisions.
In addition, the scope of work shall include the necessary preparations and design
of all anti-vibration measures that will be necessary if dampers need to be
installed.
All materials and workmanship shall comply with the requirements in the codes
and standards, including amendments to these, stated in these Specifications and
in other codes and standards referred to from these codes and standards.
The stay cable system shall comply with the requirements of Post Tensioning
Institute and in addition, the system shall comply with excerpts listed below, taken
from FIB Bulletin No.30 if Post Tensioning Institute is not up-to-date for a state-
of-the-art technology.
The stay cables shall be supplied, fabricated, delivered, tested, installed, stressed
and permanently protected by the Contractor in accordance with the requirements
of this Chapter of the Specifications and the following general requirements:
(a) PTI Recommendations for Stay Cable Design, Testing, Installation 7th
Edition published in Nov. 2018.
(b) Fib Bulletin 30 : Acceptance of stay cable system using prestressing steels.
(c) Structural design of steel components shall comply with EN 1993, IRC 22,
IRC 24, IRC 112
(d) Fabrication of steel components shall be in accordance with the
requirements of the structural steel specifications.
The stay cable system shall be supplied by a specialist Supplier with previous
experience in the design, supply and installation of the specified system. The
appointment of the stay cable Supplier shall be subject to the approval of MRIDC.
The stay cables include the stay anchorage components, which are part of the
structure, such as the Guide pipe and the anchorage bearing plates connecting the
stays to the pylons and superstructure.
The stay cable system as shown on the Drawings consists of parallel individually
PE-sheathed seven wire galvanized mono-strands with wedge anchorages and an
outer High-Density Polyethylene (HDPE) pipe. The stay cable system shall be
designed such that the replacement of any cable can be carried out, if required,
strand by strand, in order to minimize any traffic disruption during the replacement.
Similarly, the filling of the anchorages with a cement grout or other such hardening
material which would prevent strand by strand replacement is not permitted.
The space between the strands and the outer HDPE sheath shall not be filled.
The system design shall also provide for the assessment and adjustment of the
tension of the stays both during construction and in service. During initial stay
installation this may be done strand-by- strand, subject to the Engineer-In-
consent to the methods adopted. After structural completion of the bridge the
assessment of the stay forces and their final adjustment shall be by hydraulic jack,
The use of shims to provide for the final stay tension adjustments is not permitted.
It is envisaged that, in service, any future monitoring or re-stressing of stays shall
be carried out from the pylon. The required over length of strands should therefore
be provided at the pylon anchorages. The over length of strands shall be completely
protected against corrosion and soiling.
The system design shall allow destressing and removal of the stay cables by the
reversal, at any time during construction or in service, of the erection operations.
6.11.3 MATERIALS
i) STRAND
The cable shall be made of hot galvanised strands in HDPE sheathing. The stay
cable shall be Galvanised, waxed, HDPE sheathed stay strands.
The main tensile elements of PSS (Parallel Strand System) stays are coated strands
to the requirements of NF A35-035 (Edition 2001) shall be Grade 1860 MPa,
Galvanized, Wax filled, PE-coated, seven wire low relaxation class 2 with following
properties.
Recommended Characteristic
Type of Diameter Tensile Cross Section
Tolerance on Ultimate Force
Steel mm Strength MPa mm2
mass % kN
Strands 15.7 1860 150 ±2 279
Relaxation 1000 h at 0.70 GUTS, 200 C Note more than 2.5% ISO 15630-3
bulletin-30
(1)
(2) A filler of wax between the prestressing steel and the sheathing (if any)
or the stay pipe
(a) Zinc coating: the zinc coating of wire shall be in accordance with prEN
10337: 2003 and EN ISO 15630 - 3 and shall be applied before the last wire
drawing operation. The coating shall be of uniform thickness (without drops or
local thickenings). The weight of zinc coating on the finished product shall not be
less than 190 g/m2 and not more than 350 g/m2 with an average not less than
250 g/m2
(b) HDPE coating: The HDPE coating shall be extruded around the strand and
the protective filler. It shall tightly follow the outer contour of the strand, and it
shall have a minimum thickness of 1.5 mm (-0, + 0. 25). It shall not necessarily
be circular at the outer periphery. The outer diameter of the coated strand shall
not exceed 19.5 mm. The coating material shall be virgin HDPE in black colour.
The properties of the sheathing material PE shall be as per table 6.18 below:
Property Requirement Test method
Melt index 0.35 g and per 10 ISO 1133
minutes under 5 kg
Specific weight, Density g/cm³ 0.9 g/cm3) ISO 1183
Carbon black 2.3 0.3% ISO 6964
Dispersion of the carbon black Index is max. 3 ISO 18553
Distribution of the carbon black Index is max. C 2 ISO 18553
Tensile strength 22 MPa on raw material ISO 527-2
18 MPa on pipe
Elongation at break at 23° C 600 % on raw material ISO 527-2,
500 % on sheathing 50 mm/minute (speed on test)
Elongation at break at 20° C 150 % on raw material ISO 527-2,
100 % on sheathing
The strand supplier shall manufacture under an accredited quality assurance system
and shall provide a full manufacturing test plan for the approval of the Contractor
and the consent of the Engineer-In-Charge. The test plan shall include all tests as
specified below.
Static Test
One static test of failure shall be conducted after completion of each strand fatigue
test. Specimen shall provide not less than 95 per cent of the Minimum Ultimate
Tensile Strength (MUTS) in the static test without failure.
Ductility Testing:
One specimen of sufficient length for three tests shall be sampled from each unit of
production and "One Pin Test" shall be carried out. The test sampling and procedure
-Tensioning Institute's Recommendations
for Stay Cable Design, Testing and Installation (2001). For acceptance, the tensile
force in the sample during the One Pin Test shall be equal at least 80% of the
ultimate strength of the sample. The sample taken for the One Pin Test shall be long
enough for two ultimate strength tests and three One Pin Tests. If the first specimen
fails the One Pin Test, two additional samples shall be tested. If both samples pass,
the material is acceptable, if either of two additional samples fails, the material from
which the sample was taken shall be rejected.
Completed strand:
The test requirements on individually sheathed polyethylene strand are given in
table 6.21 below. Performance tests in accordance with PTI clause 3.3.9 have to be
conducted under an accredited quality assurance system at factory
or an independent laboratory. Past test results for Chemical resistance, Chloride
permeability and salt spray (fog) test may be accepted.
Table 6.21: Characteristics of the sheathed and waxed stay cable strand
Performance Test for Individually Sheathed Strand:
The Contractor shall furnish to the MRIDC Engineer in charge, a report for test
performed in accordance with Section 3.3.9 of PTI's Recommendations for Stay
Cable Design, Testing and Installation (2001), prepared by an independent
laboratory documenting compliance with items (I) to (6) below:
All deliveries of strand to site shall accompany the manufacturer's test certificates
for each cast of steel, detailing the chemical analysis and the results of all tests
on samples taken from both wire and strand made from that cast and the results
of all other testing. Any previous test results /report shall be accepted for above
mentioned requirement.
iv) PACKING OF STRAND
(a) Coiling: the coiling diameter shall be not less than the 60 times the diameter of
the outer coating of the strand.
(b) Packing: The packing of the coils shall be either reel less coils which are
protected in such a manner that Strand is not damaged during handling of coils.
Alternatively, the wooden reels can also be used.
The Contractor shall check the reliability of the type of packing proposed by the
strand manufacturer regarding the mechanical protection of the strand, to
ensure the strand is not damaged in transit or when delivered to the Site.
v) STAY CABLE PIPE
Stay cable outer pipe shall consist of high-density polyethylene (HDPE) pipe
conforming to the following requirements.
The maximum standard dimension ratio (SDR) shall be 32 for un-grouted stay
cable system proposed in this project. However, the minimum thickness of HDPE
pipe shall be 5 mm.
The surface of the HDPE pipe shall carry double helical ribs to mitigate the effect
of rain and wind induced vibrations of the stay cables.
The HDPE pipe sheathing shall be either White (RAL 9003) or any other approved
colour such as yellow (RAL 1003). Stay cable pipes shall be co-extruded with
fully bonded black core and coloured exterior HDPE pipe. The outer stay pipe
shall be coloured with the colour specified by MRIDC. The Contractor shall be
permitted to propose a full thickness colour HDPE pipe, provided that these
The manufactured HDPE pipe shall be tested for durability under natural light
and UV. The change of tensile strength and elongation and of color shall be
documented as a function of time and exposure conditions at the particular
location of the structure.
The Specialist Contractor shall submit test evidence of the colored HDPE pipe
mechanical resistance against ultraviolet degradation for a minimum of 25 years,
and color change for a minimum of 15 years.
Test on the UV-stability have to be submitted to the owner for endorsement
(Xenon WOM test according to ISO 4892-2, the colorimetric measurement for
colour fading according to ISO 11664-4 and mechanical is assessed according to
ISO 6259-1&3, or similar).
WOM test are preferred as they uses Xenon-arc lamp which has the spectral
energy distribution close to natural sunlight. SEPAP test are not allowed as they
use mercury arc lamp which doesn0t represent natural sunlight accurately.
The HDPE pipe material shall be virgin and shall meet the specific cell category
requirements for CLASS PE 325443 and CLASS PE 345444 materials as defined
by table 1 of ASTM D3350. The resultant acceptable range of primary properties
for these HDPE materials is as shown in table below:
The use of recycled polyethylene is prohibited. The stay pipe supplier must have
a quality management organization in accordance with the NF EN ISO 9001:2015
standard. The pipes may be provided with double helical ribs on the surface to
control vibrations due to rain and water. Generally, stay cable straight segments
connected by mirror welding.
In addition to the above requirements, the thickness of stay pipes which are
injected with filler shall be Øext /17 and which are not injected with filler may be
reduced to Øext /32 where Øext is the stay pipe outside diameter, but thickness
shall not be less than 5.0 mm.
The Contractor shall ensure that packaging, handling and shipping of the pipe is
done in such a way by the manufacturer that the pipe is not damaged when
delivered at Site. Prior to the delivery of pipe sheathing at Site, the Contractor
shall provide a certificate of analysis, in duplicate, for each shipment, stating the
material meets this Specification together with the results of all tests.
The contractor responsible for the installation of the stay cables shall have a
quality management system in compliance with ISO 9001: 2015 standards, or
equivalent, covering all aspects of quality control, supply and installation of the
stay cable system execution documents
The following documents shall be present on site:
Assembly outline drawings of the stay cable system, with connections to the
deck and pylon and with the vibration damping devices (if any)
Certificates of the quality control testing of the stay cable components
(traceability)
Deck construction programme
Tolerances on the structural parts of the deck and pylon (particularly for the stay
cable anchorage orientation)
Definition of the cable forces and elongations (from the Designer).
The following method statements for stay cables shall be present on site:
Site preparation: Definition of the storage areas, access and platforms for the
cable installation, space requirements for the stay cable installation.
High quality materials shall be used whose properties are generally regulated by
national or international standards, including the respective test procedures.
Minimum requirements are proposed below. Even higher quality standards may
be specified by the Designer. The main materials for stay cables and their
corrosion protection considered here are:
In the approval and suitability tests, the properties of all materials used must be
checked and recorded in the test reports. The test results must comply with the
specifications. In addition, the cable supplier has to perform tests on samples of
all important stay cable components upon delivery of the stay cable materials.
Test results shall be recorded and checked for compliance.
vii) ANCHORAGES
All anchorages and its components shall be capable of developing at least the
Guaranteed Minimum Breaking Load of the tensile elements i.e., strand.
The steel wires of the strands shall not be in contact with any other steel
elements, other than the gripping wedges to avoid fretting corrosion, which may
be detrimental to the fatigue endurance of the stays.
The anchorages shall allow a negative adjustment of the stay cable force
(increase in cable length) by a minimum of 40mm for all cables.
The angular deviation between the steel guide pipe and the centreline of each
stay shall not exceed±0.30 degrees and the bearing plates together with steel
guide pipes shall follow the cable tangent to consider cable sag.
The anchorage device shall be capable of transmitting the full ultimate tensile
force of the cable- All other components such as bearing plates, guide pipe and
guide deviators/damper shown on the drawings shall be of suitable type and
sufficient strength for the intended use.
The stay cable supplier shall submit to MRIDC upon his request results of full-
scale fatigue, static and water tightness tests.
The design of the cable guide system must take account of transverse and
flexural forces resulting from:
All stays cables shall have the capability for force adjustments achieved by re-
positioning the anchorage with respect to the structure. This tension adjustment
shall be made by means of a threaded tube and ring nut assembly. The use of shims
to provide for stay tension adjustments is not permitted. The adjustment amplitude
shall be sufficient to account for the following:
a) Uncertainty regarding the "neutral" position of the anchorages;
b) Uncertainty of the construction loadings and of the stiffness of the structure (deck
& tower);
c) Uncertainty of the unstressed length tension, and temperature of the stay cable;
d) Extension of the stay cable to attain the required preloading;
e) Provision for future increase in dead load (overlay/ resurfacing. widening). etc.;
f) Provision for future increase in the live load:
g) Deformation of the structure resulting from concrete creep and shrinkage or
constructional Inaccuracies. corresponding to mid span deck deflection of L/ 1000
where L is the length of the relevant stay;
h) A safety factor to the satisfaction of the MRIDC Engineer in charge
Possibility of Directional Adjustment
The orientation of connecting parts and anchorage heads must take account of the
ideal cable stay alignment (catenary) under the service conditions of the unloaded
structure.
The anchorages must be capable of accepting static angular deviations in excess of
the installation tolerances of the connecting parts.
If the external anti corrosion barrier is replaced by a local casing in the anchorage.
It must be injected with an appropriate blocking medium. This blocking medium shall
be a flexible material. Hard material (resin) filling or cement grout shall not be
allowed in the anchorage zone. At the end of the stay cable, the outer casing shall
be closed with a watertight cap attached to the anchorage head and covering at
least the entire area of the strand terminations. This cap shall be removable for
inspection of the strand terminations.
This integrity and continuity of the waterproofing must be consistent with the other
functions of the anchorage and maintained under all service conditions (vibration,
movement. ageing, temperature variations, etc.). This shall be demonstrated by the
water tightness test as per PTI Recommendations for Stay Cable Design, Testing,
Installation 7th Edition published in Nov. 2018.
The sealing of the anchorage must be effective as soon as the strand is installed to
prevent ingress of water in the anchorage during installation phase.
Protection against Wear
To prevent fretting corrosion and fatigue, no steel to steel contact between the
strand and the parts of the transition zone shall be allowed.
Steps must be taken to prevent fretting corrosion and fatigue at critical points: at
each deviation of the strand, where the strand enters the anchorage head etc. In
order to avoid an accumulation of causes of fatigue (axial and flexural action effects)
at the anchorage head, steps must be taken to guide lateral displacement of strands.
Cement grout filling or resin filling of any part of the anchorage is not permitted-
Removability
The stay cable design shall be such that the replacement of any cable can be done
in compliance with the site safety regulations and with minimum traffic disruption.
The replacement of a full cable shall be possible with the closure of only the one
traffic lane adjacent to the stay.
i. Strand
The conformity of the strand to the specifications defined in para 6.11.3 is submitted
to acceptance testing, carried out:
Standard Properties
On each sample one series of tests is carried out as follows:
One tensile test.
One determination of the mass per unit length;
One control of the metallic coating (mass of coating per unit area. adhesive strength
and continuity), applicable for galvanized strand only;
One control of straightness
Particular Properties
Unless otherwise agreed, the following tests shall be carried out on one sample per
inspection unit or fraction thereof:
one fatigue test.
one deflected tensile test.
For each test, 3 samples shall be selected. If the test on the first sample fails, two
more tests shall be carried out. If either of the two additional tests fails, the quantity
of strands represented by the three samples shall be rejected.
Relaxation Test
One test per Production unit , but limited to max 1 test per 200MT.
HDPE Sheath and stay Pipe
The conformity of the HDPE sheathing and stay pipe to the specifications is subject
to acceptance testing carried out:
Inspection unit for sampling: the unit of HDPE production by the same batch is one
production process with a maximum of 30 tons of HDPE.
For each production unit, at least three samples are taken: one sample shall be
taken at the beginning of the production, another one close to the middle and a
last one at the end.
Standard Properties
On each sample, one series of tests is carried out to determine:
Unless otherwise agreed prior to starting the production, one accelerated artificial
ageing test shall confirm the durability calculation made. Test results on similar
HDPE formulations shall be supplied by the stay cable supplier at tender stage.
ii. Fully Assembled Stay Cable system
Qualification of the stay cable system is based on the following tests on the fully
assembled cable:
three fatigue and ultimate strength tests, on representative units of the bridge,
unless evidence of previous tests is submitted and accepted by the MRIDC Engineer
in charge; as per PTI DC45-2 or fib30 with static anchorage deviation during test
(10mrad)
two fatigue and ultimate strength tests, on medium unit, unless evidence of
previous tests is submitted and accepted by the MRIDC Engineer in charge; as per
CIP with dynamic anchorage deviation during test (5 +/-5mrad)
one water tightness test on a reduced unit. unless evidence of previous test is
submitted and accepted by the MRIDC Engineer in charge.
All test data and results shall be submitted to the MRIDC Engineer in charge.
Fabrication of anchors and cables shall not begin until the required tests (or
previous test reports) are successfully completed (submitted) and written approval
is given by the MRIDC Engineer in charge.
Test parameters and acceptance criteria shall be as detailed in 6.2.1 of FIB bulletin
30 for stay cable, except where otherwise stated below.
Unless otherwise accepted by the MRIDC Engineer in charge, three complete fully
assembled stay cable specimens shall be fabricated for testing, one specimen shall
be made representing the smallest stay cable, a midrange stay cable and a large
(the largest when the laboratory testing machine is of sufficient capacity) stay cable
in the bridge. Each specimen shall be fully representative of all details and
procedures for production anchorages.
Stay cables shall be tested with all load bearing appurtenances. They shall include
an active anchorage and a passive anchorage. Strand deviations shall be
representative of the most severe installed stay cable deviations.
The specimen shall undergo two million cycles of the following loading: the axial
stress varies sinusoidally between 0.45 GUTS and 0.45 GUTS - 200 MPa. At the
same time, the stay cable anchorage shall be supported on wedge-shaped shim
-shaped cable
profile.
Test parameters and acceptance criteria shall be as detailed in 11.2.2.2of CIP for
stay cable, except where otherwise stated below.
Unless otherwise accepted by the MRIDC Engineer in charge, two complete fully
assembled stay cable specimens shall be fabricated for testing, the specimen shall
be chosen as the midrange of the stay cable supplier range (typically between 37
and 61 strands). Each specimen shall be fully representative of all details and
procedures for production anchorages.
Stay cables shall be tested with all load bearing appurtenances. They shall include
an active anchorage and a passive anchorage. Strand deviations shall be
representative of the most severe installed stay cable deviations.
The specimen shall undergo two million cycles of the following loading: the axial
stress varies sinusoidally between 0.45 GUTS and 0.45 GUTS - 200 MPa. At the
same time, the angular deviation of the stay cable shall vary from 0 to 10mrad (ie
5 +/-5mrad).
92% of the Actual Ultimate Tensile Strength (AUTS) of the cable calculated from
the actual strength of the strands
The strain of the specimen under the maximum load is greater than 1.5%.
allowing for deformation inherent to the operation of the anchorages (working-in
of jaws etc.)
The sample is set up in a steel tube inclined at a typical stay cable angle. As shown
on the drawing below this tube serves as a tank for water head of 3 Ms on the
sample as well as a structural member to stress the stay cable and bend it. The
sample shall not be injected with void filler to carry out the test.
After installation of the sample, the cable is stressed up to 0.20 fGUTS, and the tube
is filled with dyed water. The top anchorage shall allow the cable to be stressed. In
case of stay cable with void filler over the full length or when the Stay pipe is
attached at both end of the cable the connection of the stay pipe shall reproduce
the reality of the connection and shall also is stressed. If thermal variations create
stresses in stay pipes connected at both ends. the sample shall be set in a manner
that this phenomenon shall be tested.
a) loading cycles between 0.2 and 0.5 fGUTS using an appropriate jack at the top
anchorage. The force in the cable is then permanently set to 0.3 fGUTS
b) 8 thermal cycles obtained through a central heating device heating the water in
the steel tube from 200 C up to 700 C. Two cycles are applied each week.
c) Simultaneously the stay cable specimen will be bent using a transverse jack and
a sliding bearing plate under the top anchorage with a stroke of +/-150 mm (angle
of deviation of 4+/-25 milli radians). 250 cycles are applied per week, alternatively
cold and hot.
After this loading sequence, the sample is dismantled carefully; then opened to
check that no traces of water are present on the strands, the test is deemed to be
positive if no trace of colouring is found inside the anchorage or anchorage cap.
Only stay cable systems having previously passed such testing witnessed by a third
party can be qualified.
A reference of a fatigue test and a water tightness test passed successfully as per
above specifications shall be submitted to the MRIDC Engineer in charge at the
tender stage.
Any previous test, conducted for a previous project as per the present
specifications: may be proposed to the MRIDC Engineer in charge as the basis for
stay cable approval in lieu of the tests specified elsewhere of this tender document.
At a minimum, the stay cable supplier shall provide the following tests:
- 3 x FIB bulletin 30 or PTI DC45-2 for fatigue and tensile test with static angular
deviation
AND
- 2x CIP for fatigue and tensile test with dynamic angular deviation
The quality control tests must establish that the strands supplied for this project
have geometrical, mechanical and fatigue characteristics equal to the ones used in
the fatigue tests for the previous projects. Further, it must be demonstrated with
shop drawings that the stay anchorage hardware proposed is the same as in the
previous tests.
detailed drawings. All design and drawings shall be submitted to the Engineer for
approval before start of fabrication.
Features of Saddle
The saddle system shall be designed to provide continuity of the strands through
the pylon. The load transfer capacity across the saddle provided by friction
developed between strand and non-metallic part of the saddle body shall be
sufficient to prevent strand slipping under any construction or in service.
The saddle system shall allow for strand-by-strand installation, inspection and
replacement.
The saddle system shall have identical performance characteristics, durability,
design life, and fatigue performance to those of the stay cable anchorage.
Saddles of cables shall satisfy the same fatigue and tensile performance as the
cable anchorages. Testing of a particular saddle design shall be done with one
representative stay cable as suggested in clauses 6.2.2.1-6.2.2.4 of FIB Bulletin No.
30: Acceptance of Stay Cable Systems using Pre-stressing Steel (2005).
The saddle shall be adequate for both extradosed bridge and stay cable bridge and
therefore shall be qualified for both loading application un-dependently from project
type to be applied. Therefore, the two sets of tests parameters below shall be
performed.
Stay cable bridge Extradosed post tensioning
bridge
Maximum stress 45% GUTS 60% GUTS
max
Stress variation Ds 200 MPa 140 MPa
Static deviation 10 mrad 10 mrad
angle
Saddle opening 60 deg 60 deg
angle
Number of strandsMedium range unit (31 to 61) Medium range unit (31 to 61)
Table 23: test parameter
The objective of the saddle fatigue and tensile test is to confirm the performance
of the saddle in terms of fretting fatigue at the entrance into the saddle.
The Contractor shall submit detailed calculation, principle drawings to the MRIDC
for approval prior to fabricating and installing the cable damper.
GENERAL
Stay cables shall be installed in accordance with the procedures prescribed by the
stay cable system Supplier. The Contractor shall submit, for the consent of the
Engineer-In-Charge, the method of working which describes the installation
procedure, a description of the main items of the equipment required, as well as
the construction supervision program for cable installation including the cable force
and the calculated extension of each stay cable.
The stay cable erection procedure shall be compatible with the methods and
sequence of construction for the main bridges. Consent to the Contractor's method
of working and working drawings shall not relieve the Contractor from his
responsibility for performing the work in accordance with the Contract. Stay cables
may be fabricated into full length cables or erected in-situ strand by strand.
During all stages of construction, restraints such as collar rings or P.E ropes tied
around individual stays and anchored to the deck and/or the previous anchor shall
be employed to control stay cable oscillation.
HANDLING
The Contractor's method of working shall include procedures, which ensure that stay
cable components will not be damaged during handling.
Stay cable components shall be protected from corrosives, heat, abrasion and other
harmful effects throughout fabrication, storage, delivery and installation.
The minimum bending radius for the HDPE outer sheath shall be, during fabrication,
transport, storage or installation of stay cables, 25 times its outside diameter. This
shall be increased to 60 times its outside diameter for any extended storage period.
All damage to stay cables or components thereof shall be evaluated by the Contractor
and remedied prior to installation of the stays. Any damaged strand, outer HDPE
sheath or load carrying components shall be replaced. Damage to other non-load
carrying components may be repaired subject to the Engineer-In-Charge's consent
to the repair procedures and a satisfactory repair.
STRESSING
Jacks and gauges for stay cable installation shall be calibrated, using a load cell or
calibrated static load machine, within one month prior to the beginning of cable
installation, and every 6 months thereafter for the duration of cable installation. The
6 monthly re-calibration may be performed using a master gauge, provided that the
master gauge has been calibrated with the field gauges at the time of the initial jack
calibration.
In-situ erected stay cables may be tensioned strand by strand provided that it can
be demonstrated, to the satisfaction of the Engineer-In-Charge, that the tension and
extension of each strand is equalized within a range of ±2.5%GUTS. The calculated
extension of each cable shall be based on the test results corresponding to the coils
from which it was manufactured.
Stay cables shall be capable of being further tensioned, dimensioned and re-
tensioned more than once during the construction of the bridge. The stressing to the
`Final Stay Force' at the time of final cable tension adjustment shall be carried out
by full jacking of the live anchorage and adjustment of the threaded tube and nut
setting. It is not permitted to detention or retention strand by strand in such a way
that already "gripped" and newly "gripped" lengths overlap by more than 50%. No
"gripped" lengths of strand shall be left permanently within the stressed portion of
the stay.
FINISHING
After the final cable tension adjustment of all stay cables has been completed the
stressing records of all stays including the extension records shall be submitted for
the approval of the Engineer-In-Charge. Finishing of the anchorage and transition
zones may commence providing the Engineer-In-Charge's approval of these records
has been given.
A detailed maintenance manual for the stay cables shall be provided for facilitating
future maintenance.
Description of how to monitor the stay cables for excessive wind induced vibration
regularly during major wind events.
Description of how to maintain the internal and eventual external dampers.
Description of how to inspect and ensure that the dampers are functioning.
Description of how to inspect any relative movements of the components inside
the anchorages.
Description of how to inspect the cable anchorage hidden within the anchorage
tube (inspection using an endoscope).
Description of how to inspect and maintain the HDPE sheathing extruded on
the main tensile element or the HDPE stay pipe.
Principles of how to measure the stay cable forces and the eigen-frequencies of
the stay cables.
The contents of the manual shall include, but not be limited to the following parts:
Scope
How to use the manual
Periodic inspection and maintenance
Exceptional inspection
Component description
During the design life of the structure the stay cables shall be inspected at regular
intervals mentioned below (included in general site surveillance) to either confirm
the good performance or to detect any relevant damage early. If any damage is
detected, this may be reason for an exceptional inspection, and the relevant
component(s) should be subjected to maintenance, repair and / or replacement as
applicable.
Documentation of inspections of a structure may include, but may not be limited to,
the following information:
Date of inspection, name of inspectors
Programme of inspection
Data collected during the inspection and / or monitoring
Observation of defects, photographic documentation etc,
Initial Inspection
The initial inspection shall be performed at the end of construction, at the time of
handover of the structure to the owner- This initial inspection shall establish a proper
reference ("birth certificate") of the structure and the stay cables for future
inspections, and shall include at least the following:
Routine Inspection
Routine inspection is achieved as "walk-through" inspection on the structure typically
performed once a year. Routine inspection may include, but may not be limited to,
the following observations, made usually visually without the use of auxiliary
instruments:
Proper condition and position of stay pipes, welds. wrappings, guide deviators,
clamps, damping devices, etc.
Condition of anti-vandalism protection
Qualitative control of cable sag
Signs Of stains, leaks and deformations in anchorage caps and plates
Checking of installed monitoring system
Unusual cable vibrations.
Detailed Inspection
For detailed inspections special measuring tools and adequate access means such as
trolleys, scaffolding, etc, should be used. In addition to the controls for routine
inspection, detailed inspection may include, but may not be limited to, the following
examinations:
Monitoring
As an option, The monitoring of the Stay Cable shall be submitted by the Stay Cable
Supplier / Firm / Agency. The 10% of the Stay Cable shall be monitored permanently
for Cable tension.
The Stay Cable force monitoring system operating modes shall be as online remote
monitoring and offline monitoring.
Damaged stay cables must be repaired as soon as possible in order to prevent further
damage to tensile elements, filling materials, HDPE pipe and anchorage components
(FIP Recommendations [23]).
AERODYNAMIC REQUIREMENTS
Outer Casing Profile
Due to structural issues, the drag force on stay cables shall be minimized. Moreover,
the risk of rain and wind induced vibration shall be prevented by adequate cuter
casing surfacing.
The stay cable supplier shall propose an outer casing surface carrying relief, such as
spiral ridges for example, with a demonstrated efficiency against rain and wind
induced vibration. At least one laboratory testing reports shall be submitted at tender
stage to demonstrate the rain and wind stability of the stay pipe against rain & wind
induced vibration.
The dampers shall have a stroke able to accommodate vibration amplitude of ±L/500
of the cable.
Stay cables >80m in length shall be provided damping systems to obtain a
logarithmic decrement greater than 3% on any cable, whatever the cable vibration
amplitude
The proposed damping system shall be fully integrated in the anchorage zone so as
to minimize aesthetical impact. It shall be easily accessed for inspection and
maintenance during the life of the bridge.
6.12.1 The Bridge Monitoring System covers the use of the devices which enables
the continuous monitoring of static and dynamic parameters of the main
structural elements.
Monitoring system shall be designed within the scope of the application project
in order to collect data in a data collection unit placed in a section of the bridges
which can be easily accessed.
All devices used must have the precision and interval characteristics
appropriate with dimensions so that they can provide the detection of the
appropriate calculation notifications. Also, durability of all the transducers and
data acquisition system must be guaranteed.
The Bridge Monitoring System (BMS) shall include the following elements:
Dynamic stay cable force control system; determination of force in the
monitored cables at every moment shall be provided. Stay cable force control
BMS (Bridge Monitoring System) will report the actual situation of the Bridges
at any time by warning or Internet messages (e-mail or SMS).
The system shall be warranted for the duration of 3 years as of the date of
commissioning. Faulty components shall be replaced within 3 months as of the
date of determination of the defect. Contractor of Monitoring system shall
provide training in the use of the system with at least one operator.
6.12.3 Dynamic cable force control system for the stay cable system
Load compartments shall be equipped with at least 8 cables. The final selection
of cables supervised shall be verified with the bridge designer.
Parameter Value
Measurement type Static or dynamic
Global error <0.5 kN
Span 160 kN
Material Stainless steel
Operating temperature -25°C to 75°C
Protection Class IP67
Current conditioning system types Isotension / voltage
Isotension / current
Force control system shall carry out the rain flow analysis of the data in real time.
Table 6.24: Cable parameters
6.12.4 Characteristics of the load compartments shall meet the following
requirements:
i. Earthquake monitoring system shall include the following elements:
1 x 3D accelerometers, at each shore
1 x 3D accelerometers, at each pylon, at deck elevation
1 x 3D accelerometers, at each top of pylon
1 x 3D accelerometers, on decks mid- span, on the upstream side
Parameter Value
Measuring range +/-2g
Use temperature -20°C / +80°C
Shock >1500g
Average life 10 years
Power consumption <1,5 W
Protection index IP65
Wind and meteorological monitoring system shall meet the following requirements:
Parameter Value
Wind speed measuring range 0-100m/s
Wind direction measuring range 0-355°
Air temperature measurement range +/-50°C
Air relative humidity measurement range 0-100%
Luminosity measurement range 0-100W/m2
Sampling frequency 0 ila 20Hz
Use temperature -50°C / +50°C
Average life 10 years
Power consumption <3 W
Protection index IP65