SUB-METERING SUGGESTIONS
Location/System Water Supply Gas/Fuel kWHr BTU OTHERS
Plumbing and drainage system
Sewage treatment plant Y
Makeup water transfer pump for Cooling Tower Y
Makeup water booster pump for Cooling Tower Y
Domestic water transfer pump for Condotel Y
Domestic water booster pump for Condotel Y
Submersible pump at basement floors Y
Filtration system of domestic water for Condotel Y
Sumpit for Condotel Liftwell Y
Fire fighting system
Main fire pump Y
Jockey hydrant fire pump Y
Fire alarm system
Fire alarm control panels Y
Smoke extraction and pressurization system
Smoke extraction fan & Makeup-air fan for Corridor at Condotel floors Y
Smoke extraction fan & Makeup-air fan for Corridor at Level 18 Y
Smoke extraction fan & Makeup-air fan for Basement floors Y
Pressurization fan for Condotel lift shafts & lobbies Y
Pressurization fan for Fire lift shafts & lift lobbies Y
Pressurization fan for Service lift shafts & lift lobbies Y
Pressurization fan for Podium lift shafts & lift lobbies Y
Pressurization fan for All Staircases & vestibules Y
Pressurization fan for ramp separation buffer Y
CCTV system
Camera Y
DVR or NVR Y
Monitor Y
Computer Y
Printer Y
UPS Y
Switch Hub Y
Public Audio
Amplifier Y
Voice Alarm Router Y
Voice Alarm Controller Y
DVD player Y
1
Location/System Water Supply Gas/Fuel kWHr BTU OTHERS
General ventilation system
Common condotel unit's toilet exhaust fan Y
Common condotel unit's kitchen exhaust fan Y
Common condotel unit's ELV room exhaust fan Y
Common condotel unit's EL room exhaust fan Y
Common condotel unit's rubbish room exhaust fan Y
Diesel pump room exhaust fan Y
Diesel generator room exhaust fan Y
Telecom exhaust fan Y
Garbage room exhaust fan Y
Shared techincal rooms exhaust fan Y
STP room exhaust fan Y
Car parking exhaust fan and makeup-air fan Y
Air conditioning system
Precool air handling unit served condotel floors Y Y
Air conditioning served GYM and KID PLAY Y Y
Air conditioning served Main Switch Board room Y Y
Air conditioning served Transformer room Y Y
Pump served heat exchanger for level 18 pool Y
Air conditioning served FCC room Y Y
Air conditioning served Security room Y Y
Air conditioning served Telecom room Y Y
Air conditioning served Server room Y Y
Lift
Condo-Tel & skybar Passenger Lift Y
Service Lift Y
Fireman's Lift Y
BMS system
DDC panel Y
BMS server Y
Lighting system
Façade lighting Y
Basement parking lighting Y
EM & EX lighting Y
Common area at condotel floor lighting Y
Lighting at shared technical rooms Y
Lighting at building management office Y
Smart Control for Car-parking
CPU + Monitor Y
1
Location/System Water Supply Gas/Fuel kWHr BTU OTHERS
Camera Y
Barrier Y
LED indicator screen Y
Kios car finding Y
Carparking Zone Controller Y
Car stacking unit Y
Motobike stacking unit Y
Access Control system
DCU Y
Computer Y
Gym equipment
Treadmill Y
Hot & cold water dispenser Y
L18 Swimming pool
Filtration pump Y Y
UV/Ozone equipment Y
Dosing pump Y
Boiler Y Y
Lighting Y
Chiller system
Chiller unit Y Y Y
Evaporator pump Y
Condenser pump Y
Cooling tower Y Y
Level 3, 4 - Spa/Wellness area Y Y
Condotel unit Y Y
Generator system Y
Water feature system Y Y
Boiler system Y Y
NOTES:
1. Consultant to review and made amendment as requried
1. All sub-metering facilities shall be monitored by BMS except for GAS meter.
2. For shared"Common" facilities amoungst different property components, sub-metering
shall be proivded for each component.