X67PS1300

X67PS1300

1 General information
This system supply module converts the 24 VDC I/O supply voltage into the electrically isolated X2X Link power
supply. The module provides 15 W of output power for additional X67 modules on the bus.
■ Electrical isolation of supply and X2X Link power supply
■ Protection with redundancy during parallel operation of multiple system supply modules
■ Short circuit protection
■ Overload protection

2 Order data
Model number Short description Figure
System supply modules
X67PS1300 X67 system supply module 24 VDC, X2X Link power supply 15
W, reverse polarity protection, short circuit protection, overload
protection, parallel connection possible, redundancy operation
possible

Table 1: X67PS1300 - Order data


Required accessories
For a general overview, see section "Accessories - General overview" of the X67 system user's manual.

3 Technical data
Model number X67PS1300
Short description
System power supply modules Electrically isolated X2X Link power supply
General information
Status indicators Input voltage OK, output voltage OK
Connection type
X2X Link power supply output M12, B-keyed
X2X Link power supply input M8, 4-pin
Power consumption
Internal 3W
Certifications
CE Yes
KC Yes
EAC Yes
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
ATEX Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 - Max. 60°C
TÜV 05 ATEX 7201X
X2X Link power supply input
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC

Table 2: X67PS1300 - Technical data

Data sheet V2.25 1


X67PS1300
Model number X67PS1300
Nominal current 0.75 A
Fuse Integrated
X2X Link power supply output
Nominal voltage 20 VDC
Nominal current 0.75 A
Nominal output power 15 W
Efficiency >80%
Parallel connection Yes 1)
Redundant operation Yes, when input voltages are the same
Supply failure bridging >5 ms at 24 VDCIn and IOut = 0.75 A
Overload characteristics Short circuit protection, overload protection
Isolation voltage between input and output 500 VEff
I/O power supply
Nominal voltage 24 VDC
Voltage range 18 to 30 VDC
Integrated protection Reverse polarity protection
Electrical properties
Electrical isolation X2X Link supply isolated from X2X Link power supply
Operating conditions
Mounting orientation
Any Yes
Installation elevation above sea level
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP67
Ambient conditions
Temperature
Operation -25 to 60°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Mechanical properties
Dimensions
Width 53 mm
Height 85 mm
Depth 42 mm
Weight 225 g
Torque for connections
M8 Max. 0.4 Nm
M12 Max. 0.6 Nm

Table 2: X67PS1300 - Technical data


1) In parallel operation, only 90% of the rated power can be assumed. It is important to make sure that all power supplies operated in parallel are switched
on and off at the same time.

4 LED status indicators


Figure LED Color Status Description
Status indicator 1: green Status indicator 1: Status indicator for X2X Link
Color Status Description
Green On X2X Link power supply is within the valid limits
Status indicator 2: Status indicator for the I/O power supply
Color Status Description
Orange On I/O power supply voltage within the valid range

Status indicator 2: orange

2 Data sheet V2.25


X67PS1300

5 Connection elements

X2X Link
Connection A: Input
Connection B: Output

24 VDC I/O power supply


Connection C: Supply
Connection D: Routing

6 X2X Link
This module is connected to X2X Link using pre-assembled cables. The connection is made using M12 circular
connectors.
Connection Pinout
3 Pin Description
A
1 X2X+
2 X2X
2 3 X2X⊥
4 X2X\
4
1 Shield connection made via threaded insert in the module.

A → B-keyed (male), input


B 3 B → B-keyed (female), output

4
1

7 24 VDC I/O power supply


The I/O power supply is connected via M8 connectors C and D. The I/O power supply is connected via connector
C (male). Connector D (female) is used to route the I/O power supply to other modules.

Information:
The maximum permissible current for the I/O power supply is 8 A (4 A per connection pin)!
Connection Pinout
2 Pin Description
C
1 1 24 VDC
2 24 VDC
4
3 GND
4 GND
3
C → Connector (male) in module, feed for I/O power supply
D 2 D → Connection (female) in module, routing of I/O power supply
1

Data sheet V2.25 3


X67PS1300

8 Maximum number of modules connected


With a large number of modules connected, the following must be taken into account:
• The total power consumption of all modules is not permitted to exceed 15 W.
• In addition, the internal resistance of the connection cable between the individual modules must also be
taken into account.
Example
20 X67DM1321 modules should be connected to the system supply module.
This is possible according to the data sheet: 20 * 0.75 W power consumption = 15 W total power consumption.
The sum of the cable resistance values when using long connection cables between the modules, however, results
in an additional voltage drop. The supply voltage drops below 18 V, which results in a situation where the function-
ality of the modules can no longer be guaranteed.
Solution: Add more system supply modules

9 Operating in Automation Studio

Information:
This module does not have to be integrated in the project in Automation Studio.

4 Data sheet V2.25