19XR
19XR
2
   In addition, Carrier’s semi-hermetic      refrigerant flow evenly over the length    Other languages are available.
design eliminates:                           of the vessel for improved efficiency.     Automatic capacity override func-
• Compressor shaft seals that require        Closely spaced intermediate sup-           tion unloads the compressor whenev-
    maintenance and increase the likeli-     port sheets prevent tube sagging and       er key safety limits are approached,
    hood of refrigerant leaks                vibration, thereby increasing heat         increasing unit life.
• Shaft alignment problems that occur        exchanger life.                            Chilled water reset can be accom-
    with open-drive designs during           Refrigerant filter drier isolation         plished manually or automatically from
    start-up and operation, when equip-      valves allow filter replacement without    the building management system.
    ment temperature variations cause        pumping down the chiller, which means      Reset saves energy when warmer
    thermal expansion                        less service time and less expense.        chilled water can be used.
• High noise levels that are common
                                             FLASC (flash subcooler), located in        Demand limiting feature limits the
    with air-cooled motors, which radi-
                                             the bottom of the condenser, increases     power draw of the chiller during peak
    ate noise to the machine room
                                             the refrigeration effect by cooling con-   loading conditions. When incorporated
    and adjacent areas
                                             densed liquid refrigerant to a lower       into the Carrier Comfort Network®
• Machine room cooling requirements
                                             temperature, resulting in reduced com-     building automation system, a red line
    associated with air-cooled motors,
                                             pressor power consumption.                 command holds chillers at their present
    which dissipate heat to the machine
                                             Ball-type or linear float valves           capacity and prevents any other
    room
                                             provide precise refrigerant metering       chillers from starting. If a load shed
High-efficiency copper rotor mo-                                                        signal is received, the compressors
                                             over a wide variety of operating condi-
tors are available on select models.                                                    are unloaded to avoid high demand
                                             tions. As a result, optimal refrigerant
Compressors are 100% run-tested              levels can be maintained in the con-       charges whenever possible.
to ensure proper operation of all com-       denser and cooler to achieve the great-    Ramp loading ensures a smooth pull-
pressor systems, including oil manage-       est efficiency without unintentional hot   down of water loop temperature and
ment, vibration, electrical, power trans-    gas bypass or flooding.                    prevents a rapid increase in compres-
mission, and compression.                                                               sor power consumption during the
                                             Microprocessor control features            pulldown period.
Heat exchanger features                      Direct digital Product Integrated
The American Society of Mechani-                                                        Automated controls test can be ex-
                                             Control (PIC) provides unmatched           ecuted prior to start-up to verify that
cal Engineers (ASME) standard re-            flexibility and functionality. Each unit
quires the use of an independent agen-                                                  the entire control system is functioning
                                             integrates directly with the Carrier       properly.
cy to certify the design, manufacture,       Comfort Network® (CCN) system, pro-
and testing of all heat exchangers, en-      viding a system solution to controls ap-   365-day real time clock feature al-
suring the ultimate in heat exchanger        plications. The PIC control can be con-    lows the operator to program a yearly
safety, reliability, and long life.          figured to display units in English or     schedule for each week, weekends,
Refrigerant-cooled VFD (19XRV)               metric, and provides unparalleled ease     and holidays.
helps reduce VFD size and ensures prop-      of operation.                              Occupancy schedules can be pro-
er cooling of the transistors for extended      The default display offers all-in-one   grammed into the controller to ensure
life. Using R-134a refrigerant instead of    glance review of key chiller operation     that the chiller only operates when
water also eliminates costly maintenance     data, simplifying the interaction be-      cooling is required.
associated with the water cooling pump,      tween chiller and user.                    Extensive service menu features in-
heat exchanger and rubber tubing used                                                   clude password protection to prevent un-
                                             Features include:
with water-cooled VFDs.                                                                 authorized access to the service menu.
1-in. tubes (optional) provide opti-         • Display of over 125 operating, sta-      Built-in diagnostic capabilities assist in
mized cost and less pressure drop than          tus, and diagnostic messages for        troubleshooting and recommend proper
                                                improved user interface
the default 3/4-in. tubes.                                                              corrective action for pre-set alarms, re-
                                             • Monitoring of over 100 functions         sulting in greater operating time.
Tube expansion at center support                and conditions to protect the chiller
sheets prevents unwanted tube                   from abnormal conditions                Alarm file maintains the last 25 time
movement and vibration, thereby              • Modular pull-out/plug-in design,         and date-stamped alarm and alert mes-
reducing the possibility of premature           reducing wiring requirements and        sages in memory; this function reduces
tube failure.                                   providing easy installation             troubleshooting time and cost.
Double-grooved tube sheet holes              • Low-voltage (24 v) design, providing     Configuration data backup in non-
reduce the possibility of leaks between         the ultimate assurance of personal      volatile memory provides protection
the water and refrigerant system, in-           safety and control integrity            during power failures and eliminates
creasing product reliability.                   The display modes include 4 standard    time-consuming control reconfiguration.
Condenser baffle prevents direct im-         languages:                                 19XR refrigeration cycle
pingement of high velocity compressor        • English                                  The compressor continuously draws
gas onto the condenser tubes. The baf-       • Chinese
fle eliminates the related vibration and                                                refrigerant vapor from the cooler at a
                                             • Japanese (PIC II and PIC III only)       rate set by the amount of guide vane
wear of the tubes and distributes the        • Korean (PIC II and PIC III only)         opening. As the compressor suction
                                                                                                                                 3
Features/Benefits (cont)
reduces the pressure in the cooler, the       The liquid refrigerant passes through   condenser also cools the motor, oil and
remaining refrigerant boils at a fairly    orifices into the FLASC (flash subcool-    optional variable speed drive.
low temperature (typically 38 to 42 F      er) chamber. Since the FLASC cham-            The refrigeration cycle for a
[3 to 6 C]). The energy required for       ber is at a lower pressure, part of the    19XR,XRV chiller with two-stage com-
boiling is obtained from the water flow-   liquid refrigerant flashes to vapor,       pressor is similar to the one described
ing through the cooler tubes. With heat    thereby cooling the remaining liquid.      above, with the following exception:
energy removed, the water becomes          The FLASC vapor is recondensed on          Liquid refrigerant from the condenser
cold enough to use in an air-condition-    the tubes which are cooled by entering     flows into an economizer at intermedi-
ing circuit or process liquid cooling.     condenser water. The liquid drains into    ate pressure. In the economizer, vapor
   After taking heat from the water, the   a float valve chamber between the          is separated from the liquid; the sepa-
refrigerant vapor is compressed. Com-      FLASC chamber and cooler. Here, the        rated vapor flows to the second stage
pression adds still more heat energy       AccuMeter™ float valve forms a liquid      of the compressor and the liquid flows
and the refrigerant is quite warm (typi-   seal to keep FLASC chamber vapor           into the cooler. Since the economizer
cally 98 to 102 F [37 to 40 C]) when it    from entering the cooler. When liquid      gas has to pass through only half of the
is discharged from the compressor into     refrigerant passes through the valve,      compression cycle to reach condenser
the condenser.                             some of it flashes to vapor in the re-     pressure, a saving in power is
                                           duced pressure on the cooler side. In      achieved. The energy removed from
   Relatively cool (typically 65 to 90 F   flashing, it removes heat from the re-
[18 to 32 C]) water flowing into the                                                  the vaporized refrigerant allows the liq-
                                           maining liquid. The refrigerant is now     uid refrigerant in the cooler to absorb
condenser tubes removes heat from the      at a temperature and pressure at which
refrigerant, and the vapor condenses to                                               more heat when it evaporates and
                                           the cycle began. Refrigerant from the      thereby benefits the cooling cycle.
liquid.
                                                  REFRIGERATION CYCLE
                                           19XR,XRV SINGLE-STAGE COMPRESSOR
4
                                                         REFRIGERATION CYCLE (cont)
                                          19XR,XRV TWO-STAGE COMPRESSOR FRAME SIZE E
                              ISOLATION
                              VALVE                                                FLASC CHAMBER
                                                                                                               CONDENSER
                                                                                                               WATER
                                                                       FLOAT
                                                                       VALVE
                                                                       CHAMBER
                                                                                          HOT GAS BYPASS (OPTIONAL)
          MOISTURE/       FILTER          REFRIGERANT
          FLOW            DRIER           COOLING                                DAMPER
          INDICATOR                       ISOLATION                              VALVE
                                          VALVE
                                ORIFICE
                      ROTOR     FITTING TRANSMISSION                              REFRIGERANT            HGBP VALVE
                                                                                  ISOLATION VALVE
                                                                                                                             REFRIGERANT
                                MOTOR                                                                                        LIQUID
                                                                                                                             REFRIGERANT
            ORIFICE                                                                                                          VAPOR
                                                                                 FLOAT BALL VALVE
            FITTING
                                                                                                                             REFRIGERANT
                                                                                                                             LIQUID/VAPOR
   THERMOSTATIC                                  IMPELLERS
   EXPANSION
   VALVE (TXV)                  OIL COOLER                COMPRESSOR
                                                BACK PRESSURE
                                                ORIFICE (INTEGRAL
                                                TO MOTOR SHELL)
                  ORIFICE
OPTIONAL UNIT
MOUNTED VFD
(VARIABLE
FREQUENCY
DRIVE) HEAT
EXCHANGER                                                                                                                                   a19-2029
                                                                                                                           CHILLED
                                                                                                                           WATER
                                                        COOLER
                                                        ISOLATION
                                                        VALVE
                                                        (OPTION)
                                                                                                                                                       5
Features/Benefits (cont)
                      ISOLATION
                      VALVE                                                      FLASC CHAMBER
                      (OPTION)
                                                                                                               CONDENSER
                                                                                                               WATER
                                                                               DAMPER
                                                                               VALVE
                           ORIFICE
                   ROTOR                                                         REFRIGERANT             HGBP
                           FITTING TRANSMISSION
                                                                                 ISOLATION VALVE         VALVE
                                                                                                                              REFRIGERANT
                                                                    ECONOMIZER                                                LIQUID
                                                                                                                              REFRIGERANT
                                                                                     LOW SIDE                                 VAPOR
                                                                                     FLOAT VALVE
                                                                                                                              REFRIGERANT
                                                                                                                              LIQUID/VAPOR
                                                      COMPRESSOR
    THERMOSTATIC                          IMPELLERS
    EXPANSION
    VALVE (TXV)             OIL COOLER
                                           BACK PRESSURE
                                           ORIFICE (INTEGRAL
                                           TO MOTOR SHELL)
                                                                                                                           CHILLED
                                                                                                                           WATER
                                                                                                                                             a19-
                                                                                                                                             2087
                                                   COOLER
                                                   ISOLATION
                                                   VALVE
                                                   (OPTION)
6
Model number nomenclature
19XR– 52 51 3 8 H UG T* 64
    Description
    19XR– — High Efficiency Semi-Hermetic                                                                    Special Order Indicator
              Centrifugal Liquid Chiller                                                                     – — Standard
    19XRV — High Efficiency Semi-Hermetic                                                                    S — Special Order
              Centrifugal Liquid Chiller with
              Unit-Mounted VFD                                                                              Motor Voltage Code
                                                                                                            Code Volts-Phase-Hertz
    Cooler Size†                                                                                             60 — 200-3-60
    10-12 (Frame 1)                                                                                          61 — 230-3-60
    15-17 (Frame 1)                                                                                          62 — 380-3-60
    20-22 (Frame 2)                                                                                          63 — 416-3-60
    30-32 (Frame 3)                                                                                          64 — 460-3-60
    35-37 (Frame 3)                                                                                          65 — 575-3-60
    40-42 (Frame 4)                                                                                          66 — 2400-3-60
    45-47 (Frame 4)                                                                                          67 — 3300-3-60
    50-54 (Frame 5)                                                                                          68 — 4160-3-60
    5A-5C (Frame 5)**                                                                                        69 — 6900-3-60
    55-59 (Frame 5)                                                                                          50 — 230-3-50
    5F-5H (Frame 5)**                                                                                        52 — 400-3-50
    5K-5R (Frame 5)††                                                                                        53 — 3000-3-50
    5T-5Z (Frame 5)††                                                                                        54 — 3300-3-50
    60-64 (Frame 6)                                                                                          55 — 6300-3-50
    6K-6R (Frame 6)††                                                                                        5A — 10000-3-50
    65-69 (Frame 6)                                                                                          5B — 11000-3-50
    6T-6Z (Frame 6)††                                                                                        6A — 11000-3-60
    70-74 (Frame 7)                                                                                          6B — 11000-3-60
    7K-7R (Frame 7)††                                                                                        6C — 13800-3-60
    75-79 (Frame 7)
    7T-7Z (Frame 7)††
    80-84 (Frame 8)                                                                                           Motor Efficiency Code
    8K-8R (Frame 8)††                                                                                         Compressor Frame 2, 3, 4, 5
    85-89 (Frame 8)                                                                                           H — High Efficiency
    8T-8Z (Frame 8)††                                                                                         S — Standard Efficiency
                                                                                     *      Digit 15 will refer to the Gear Code for the following models:
                                                                                            1. Digit 10 (Compressor Frame) is E or
                                                                                            2. Digit 10 (Compressor Frame) is 3 and Digit 13 of the
                                                                                            Motor Code is U.
                                                                                     †      Frame sizes 1 through 6 available on single-stage units
                                                                                            only.
                                                                                     **     Refer to 19XR,XRV Computer Selection Program for details
                                                                                            on these sizes.
                                                                                     ††     Frame sizes with K-R and T-Z are with 1-in. OD evaporator
    Quality Assurance                           AHRI (Air-Conditioning, Heating,            tubing.
                                                                                     ***    Refer to the 19XR,XRV Computer Selection Program for
    ISO 9001:2008 certified processes             and Refrigeration Institute)              motor size details.
                                                    Performance Certified
SEISMICOMPLIANT*
* Meets IBC 2006, ASCE-7-05, CBC 2007, and OSHPD seismic requirements.
Seismic rating available on select models.
                                                                    1216                                                                                     7
Model number nomenclature (cont)
                             19XR TWO-STAGE COMPRESSOR FRAME SIZE 6 AND 7
                                                                 Quality Assurance
                                                                 ISO 9001:2008 certified processes
                                                                  AHRI (Air-Conditioning, Heating,
                                                                    and Refrigeration Institute)
                                                                      Performance Certified
8
Chiller components
                           COMPRESSOR COMPONENTS
                       19XR,XRV SINGLE-STAGE COMPRESSOR
1 2 3 4 5 6
                                    16      15   14   13                                             a19-2037
                                                               12        11       10 9       8   7
                                               LEGEND
             1   —   Motor Stator                    9     —   Impeller
             2   —   Motor Rotor                     10    —   Pipe Diffuser
             3   —   Motor Shaft Journal Bearings    11    —   High Speed Pinion Gear
             4   —   Low Speed Bull Gear             12    —   Oil Heater
             5   —   High Speed Shaft Thrust Bearing 13    —   High Speed Shaft Bearing
             6   —   High Speed Shaft Bearing        14    —   Oil Pump Motor
             7   —   Variable Inlet Guide Vanes      15    —   Oil Pump Cover
             8   —   Impeller Shroud                 16    —   Oil Filter
                                                                                                                9
Chiller components (cont)
                        COMPRESSOR COMPONENTS
              19XR,XRV TWO-STAGE COMPRESSOR FRAME SIZE E
              1                          2
10
          9                              8             7                       5                 a19-2030
                                                                 6
                                                       LEGEND
                  1   —   Motor Stator                      6—       Oil Heater
                  2   —   Motor Shaft Bearings              7—       High Speed Shaft Bearings
                  3   —   Transmission                      8—       Oil Pump
                  4   —   Variable Inlet Guide Vanes        9—       Motor Cooling
                  5   —   Impellers                        10 —      Motor Rotor
10
               COMPRESSOR COMPONENTS
     19XR TWO-STAGE COMPRESSOR FRAME SIZES 6 AND 7
            1             2
                                                     3
                                                                             4
10
                                           8
                                                      7                6
                  9
                                                                                 a19-2089
                                      LEGEND
1    —   Motor Stator                      6—    High Speed Shaft Bearings
2    —   Motor Shaft Bearings              7—    Oil Heater
3    —   Transmission                      8—    Oil Pump
4    —   Impellers                         9—    Oil Filters
5    —   Variable Inlet Guide Vanes       10 —   Motor Rotor
                                                                                            11
Chiller components (cont)
                                            FRONT VIEW
                                             1                                                                           LEGEND
                                                      2                                            1—    Guide Vane Actuator
                                                               3                                   2—    Suction Elbow
                                                                                                   3—    International Chiller Visual Control (ICVC)
                                                                        4                          4—    Chiller Identification Nameplate
                                                                            5                      5—    Cooler Auto Reset Relief Valves
 15                                                                                   6            6—    Cooler Pressure Transducer
                                                                                                   7—    Condenser In/Out Temperature Thermistors
                                                                                                   8—    Cooler In/Out Temperature Thermistors
                                                                                                   9—    Refrigerant Storage Tank Connection Valve
                                                                                                  10 —   Typical Flange Connection
                                                                                                  11 —   Oil Drain Valve
     14                                                                                           12 —   Oil Level Sight Glasses
                                                                                                  13 —   Refrigerant Oil Cooler (Hidden)
                                                                                                  14 —   Auxiliary Power Panel
                                                                                                  15 —   Motor Housing
      13 12
               11
                     10
                                                                                          8
                                     9
                                         REAR VIEW
                          16                17             18 19                20                                      LEGEND
                                                                                                  16 —   Condenser Auto. Reset Relief Valves
                                                                                                  17 —   Motor Circuit Breaker
                                                                                                  18 —   Solid-State Starter Control Display
                                                                                                  19 —   Unit-Mounted Starter or VFD (Optional)
 33                                                                                                      Solid-State Starter Shown
                                                                                 21               20 —   Motor Sight Glass
                                                                                                  21 —   Cooler Return-End Waterbox Cover
                                                                                                  22 —   ASME Nameplate (One Hidden)
                                                                                                  23 —   Typical Waterbox Drain Port
                                                                                                  24 —   Condenser Return-End Waterbox Cover
                                                                                                  25 —   Refrigerant Moisture/Flow Indicator
                                                                                                  26 —   Refrigerant Filter/Drier
                                                                                                  27 —   Liquid Line Isolation Valve (Optional)
                                                                                                  28 —   Liquid Float Valve Chamber
                                                                                                  29 —   Refrigerant Charging Valve (Hidden)
                                                                                                  30 —   Vessel Take-Apart Connector
                                                                                                  31 —   Discharge Isolation Valve (Optional)
                                                                                                  32 —   Condenser Pressure Transducer
                                                                                                  33 —   Refrigerant Charging Valve/Pumpout
                                                                                                         Connection
                                                                                      22
 32
     31
          30         28        27   26 25        24       23       22
                29
12
                                               19XR,XRV TWO-STAGE COMPRESSOR FRAME SIZE E
FRONT VIEW
       16                                                                                                                       LEGEND
                                                                                                        1   —   Guide Vane Actuator
                                           1                                                            2   —   Suction Elbow
                                                             2
                                                                                                        3   —   Chiller Identification Nameplate
                                                                      3                                 4   —   Condenser Auto Reset Relief Valves
                                                                                                        5   —   Condenser In/Out Temperature Thermistors
                                                                               4                        6   —   Cooler In/Out Temperature Thermistors
                                                                                                        7   —   Cooler Pressure Transducer
                                                                                        5               8   —   Refrigerant Storage Tank Connection Valve
                                                                                                        9   —   Refrigerant Isolation Valve
                                                                                                       10   —   Chiller Visual Controller/ International Chiller
                                                                                                                Visual Control (ICVC)
                                                                                                       11   —   Typical Flange Connection
                                                                                                       12   —   Oil Level Sight Glasses
                                                                                                       13   —   Oil Drain Charging Valve
15                                                                                                     14   —   Auxiliary Power Panel
                                                                                                       15   —   Refrigerant Oil Cooler (Hidden)
                                                                                                       16   —   Compressor Motor Housing
 14
      13
                 12
                       11
                                 10
                                       9
                                                8
                                                         7                          6
REAR VIEW
                                                                 19   20                                              LEGEND
                                                                                                       17   Damper Valve (Hidden)
                                                                                                            —
                                  17                                                                        Cooler Auto. Reset Relief Valves
                                                                                             21        18   —
                                               18                                                      19   Solid-State Starter Control Display (Optional)
                                                                                                            —
           36                                                                                               Unit-Mounted Starter (Optional)
                                                                                                       20   —
                                                                                                       21   Motor Sight Glass
                                                                                                            —
                                                                                                       22   Cooler Return-End Waterbox Cover
                                                                                                            —
                                                                                                       23   ASME Nameplate
                                                                                                            —
                                                                                              22
                                                                                                       24   Vessel Take-Apart Connector
                                                                                                            —
                                                                                                       25   Typical Waterbox Drain Port
                                                                                                            —
                                                                                                       26   Condenser Return-End Waterbox Cover
                                                                                                            —
                                                                                                       27   Refrigerant Moisture/Flow Indicator
                                                                                                            —
                                                                                                       28   Refrigerant Filter/Drier
                                                                                                            —
                                                                                                       29   Liquid Line Isolation Valve (Optional)
                                                                                                            —
                                                                                                       30   Linear Float Valve Chamber
                                                                                                            —
                                                                                                       31   Refrigerant Charging Valve (Hidden)
                                                                                                            —
                                                                                                       32   Economizer Float Ball Valve Assembly (Inside)
                                                                                                            —
35                                                                                                          Economizer Assembly
                                                                                                       33   —
                                                                                                       34   Discharge Isolation Valve (Optional)
                                                                                                            —
                                                                                                       35   Condenser Pressure Transducer
                                                                                                            —
       34                                                                                                   Refrigerant Charging Valve/Pumpout
                                                                                                       36 — Connection
                      31
            33   32
                            30                                                                    23
                                      29       28   27
                                                                                        24
                                                                               25
                                                     26                   23
                                                                                                                                                                   13
Chiller components (cont)
FRONT VIEW
                    15                                                                                                          LEGEND
                                                                                                       1   —   Guide Vane Actuator*
                                          1                                                                    Suction Elbow
                                                         2 3          4                                2   —
                                                                                                       3   —   Chiller Identification Nameplate
                                                                                                       4   —   Auxiliary Power Panel
                                                                                   5                   5   —   Condenser Auto. Reset Relief Valves
                                                                                                       6   —   Condenser Return End Waterbox Cover
                                                                                                       7   —   Cooler Return End Waterbox Cover
                                                                                                       8   —   Cooler Auto. Reset Relief Valves
                                                                                                       9   —   Cooler Pressure Transducer
                                                                                                      10   —   Liquid Line Isolation Valve (Optional)
                                                                                             6        11   —   Refrigerant Storage Tank Connection Valve
                                                                                                      12   —   HMI (Human Machine Interface) Panel
                                                                                                      13   —   Typical Flange Connection
                                                                                                      14   —   Oil Level Sight Glasses
                                                                                                      15   —   Compressor Motor Housing
                                                                                                      *See certified drawing for Frame 7 location.
                                                                                                        a19-2079
               14
                             13
                                  12
                                       11 10                                   7
                                                                  8
                                                9
REAR VIEW
                                                                          16       17                                      LEGEND
                                                                                                      16   Oil Cooler
                                                                                                           —
                                                                                             18       17   Oil Drain Changing Valve (Hidden)
                                                                                                           —
                                   33          34
                                                                                                      18   Motor Sight Glass
                                                                                                           —
                                                                                                      19   Cooler In/Out Temperature Thermistors
                                                                                                           —
              31 32                                                                                        Typical Waterbox Drain Port
                                                                                                      20   —
 30                                                                                                   21   Vessel Take-Apart Connector
                                                                                                           —
                                                                                                      22   Condenser In/Out Temperature Thermistors
                                                                                                           —
                                                                                                      23   ASME Nameplate
                                                                                                           —
                                                                                                      24   Refrigerant Moisture/Flow Indicator
                                                                                                           —
                                                                                                      25   Refrigerant Filter/Drier
                                                                                                           —
                                                                                                      26   High Side Float Chamber
                                                                                                           —
                                                                                                      27   High Side Float Ball Valve Assembly (Inside)
                                                                                                           —
                                                                                                      28   Economizer Assembly
                                                                                                           —
                                                                                                      29   Economizer Float Ball Assembly (Inside)
                                                                                                           —
                                                                                                      30   Cooler Auto. Reset Relief Valve
                                                                                                           —
                                                                                                 19        Condenser Pressure Transducer
                                                                                                      31   —
                                                                                                           Refrigerant Charging Valve/Pumpout
                                                                                                      32 — Connection
                                                                                                      33 — Damper Valve
                                                                                                      34 — Discharge Isolation Valve (Optional)
                                                                                             20
                    29 28   27                      25   24
                                  26
                                                                                        21
23 22
14
Physical data
                                      19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                         STANDARD AND HIGH-EFFICIENCY MOTORS
                                                       COMPRESSOR FRAME SIZE 2†
                                      ENGLISH                                                                     SI
                              60 Hz                  50 Hz                                          60 Hz                      50 Hz
 MOTOR Compressor                                           End Bell Compressor                                                              End Bell
 CODE              Stator          Rotor     Stator  Rotor   Cover               Stator  Rotor                          Stator     Rotor      Cover
        Weight**                                                      Weight**
          (lb)    Weight††         Weight   Weight†† Weight Weight      (kg)    Weight†† Weight                        Weight††    Weight    Weight
                    (lb)            (lb)      (lb)    (lb)    (lb)                (kg)    (kg)                           (kg)       (kg)       (kg)
                                                                                                                                                    15
Physical data (cont)
                                      19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                      STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                       COMPRESSOR FRAME SIZE 3†
                                      ENGLISH                                                                     SI
                              60 Hz                  50 Hz                                          60 Hz                      50 Hz
 MOTOR Compressor                                               End Bell Compressor                                                          End Bell
  CODE             Stator          Rotor     Stator      Rotor   Cover               Stator             Rotor           Stator     Rotor      Cover
        Weight**                                                          Weight**
          (lb)    Weight††         Weight   Weight††     Weight Weight      (kg)    Weight††            Weight         Weight††    Weight    Weight
                    (lb)            (lb)      (lb)        (lb)    (lb)                (kg)               (kg)            (kg)       (kg)       (kg)
16
                                       19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                       STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                       COMPRESSOR FRAME SIZE 4†
                                      ENGLISH                                                                       SI
                              60 Hz                 50 Hz                                             60 Hz     50 Hz
         Compressor                                                           Compressor
MOTOR                                                             End Bell                                                             End Bell
          Weight**                                                 Cover       Weight**                                                 Cover
 CODE        (lb)     Stator  Rotor   Stator  Rotor                               (kg)     Stator  Rotor   Stator    Rotor
         Fixed Ring/ Weight†† Weight Weight†† Weight              Weight      Fixed Ring/ Weight†† Weight Weight†† Weight              Weight
                       (lb)    (lb)    (lb)    (lb)                 (lb)                    (kg)    (kg)    (kg)      (kg)               (kg)
          Split Ring                                                           Split Ring
*Total compressor weight is the sum of the compressor aerodynamic            **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell           included. Applicable to standard compressors only. For high lift com-
cover weights.                                                               pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                    ††Stator weight includes the stator and shell.
                                                                                                                                                17
Physical data (cont)
                                      19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                      STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                  COMPRESSOR FRAME SIZE 4† (cont)
                                      ENGLISH                                                                   SI
                              60 Hz                  50 Hz                                        60 Hz                     50 Hz
          Compressor                                                 Compressor
 MOTOR     Weight**                                         End Bell  Weight**                                                            End Bell
 CODE                  Stator      Rotor     Stator  Rotor   Cover               Stator Rotor                         Stator    Rotor      Cover
              (lb)                                                       (kg)
          Fixed Ring/ Weight††     Weight   Weight†† Weight Weight Fixed Ring/ Weight†† Weight                       Weight††   Weight    Weight
           Split Ring   (lb)        (lb)      (lb)    (lb)    (lb)    Split Ring  (kg)   (kg)                          (kg)      (kg)       (kg)
*Total compressor weight is the sum of the compressor aerodynamic          **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell         included. Applicable to standard compressors only. For high lift com-
cover weights.                                                             pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                  ††Stator weight includes the stator and shell.
18
                                      19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                      STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                       COMPRESSOR FRAME SIZE 5†
                                      ENGLISH                                                                   SI
                              60 Hz                  50 Hz                                        60 Hz                     50 Hz
 MOTOR Compressor                                           End Bell Compressor                                                           End Bell
 CODE              Stator          Rotor     Stator  Rotor   Cover               Stator  Rotor                        Stator    Rotor      Cover
        Weight**                                                      Weight**
          (lb)    Weight††         Weight   Weight†† Weight Weight      (kg)    Weight†† Weight                      Weight††   Weight    Weight
                    (lb)            (lb)      (lb)    (lb)    (lb)                (kg)    (kg)                         (kg)      (kg)       (kg)
*Total compressor weight is the sum of the compressor aerodynamic          **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell         included. Applicable to standard compressors only. For high lift com-
cover weights.                                                             pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                  ††Stator weight includes the stator and shell.
                                                                                                                                                  19
Physical data (cont)
                                       19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                       STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                   COMPRESSOR FRAME SIZE 5† (cont)
                                       ENGLISH                                                                   SI
                               60 Hz                  50 Hz                                        60 Hz                     50 Hz
 MOTOR Compressor                                            End Bell Compressor                                                           End Bell
 CODE              Stator          Rotor      Stator  Rotor   Cover               Stator  Rotor                        Stator    Rotor      Cover
        Weight**                                                       Weight**
          (lb)    Weight††         Weight    Weight†† Weight Weight      (kg)    Weight†† Weight                      Weight††   Weight    Weight
                    (lb)            (lb)       (lb)    (lb)    (lb)                (kg)    (kg)                         (kg)      (kg)       (kg)
*Total compressor weight is the sum of the compressor aerodynamic          **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell         included. Applicable to standard compressors only. For high lift com-
cover weights.                                                             pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                  ††Stator weight includes the stator and shell.
20
                                      19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                      STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                       COMPRESSOR FRAME SIZE E†
                                      ENGLISH                                                                   SI
                              60 Hz                  50 Hz                                        60 Hz                     50 Hz
 MOTOR Compressor                                           End Bell Compressor                                                           End Bell
 CODE              Stator          Rotor     Stator  Rotor   Cover               Stator  Rotor                        Stator    Rotor      Cover
        Weight**                                                      Weight**
          (lb)    Weight††         Weight   Weight†† Weight Weight      (kg)    Weight†† Weight                      Weight††   Weight    Weight
                    (lb)            (lb)      (lb)    (lb)    (lb)                (kg)    (kg)                         (kg)      (kg)       (kg)
*Total compressor weight is the sum of the compressor aerodynamic          **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell         included. Applicable to standard compressors only. For high lift com-
cover weights.                                                             pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                  ††Stator weight includes the stator and shell.
                                                                                                                                                  21
Physical data (cont)
                                       19XR,XRV COMPRESSOR AND MOTOR WEIGHTS*—
                                       STANDARD AND HIGH-EFFICIENCY MOTORS (cont)
                                                   COMPRESSOR FRAME SIZE E† (cont)
                                       ENGLISH                                                                   SI
                               60 Hz                  50 Hz                                        60 Hz                     50 Hz
 MOTOR Compressor                                            End Bell Compressor                                                           End Bell
 CODE              Stator          Rotor      Stator  Rotor   Cover               Stator  Rotor                        Stator    Rotor      Cover
        Weight**                                                       Weight**
          (lb)    Weight††         Weight    Weight†† Weight Weight      (kg)    Weight†† Weight                      Weight††   Weight    Weight
                    (lb)            (lb)       (lb)    (lb)    (lb)                (kg)    (kg)                         (kg)      (kg)       (kg)
*Total compressor weight is the sum of the compressor aerodynamic          **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell         included. Applicable to standard compressors only. For high lift com-
cover weights.                                                             pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 7.                                  ††Stator weight includes the stator and shell.
22
                          19XR COMPRESSOR AND MOTOR WEIGHTS*— HIGH-EFFICIENCY MOTORS
                                                COMPRESSOR FRAME SIZE 6, 60 Hz†
                                     ENGLISH                                                              SI
  MOTOR                         STATOR AND ROTOR AND          END BELL                           STATOR AND ROTOR AND           END BELL
               COMPRESSOR        HOUSING     SHAFT             COVER         COMPRESSOR           HOUSING     SHAFT              COVER
  CODE           WEIGHT**                                                      WEIGHT**
                   (lb)           WEIGHT     WEIGHT            WEIGHT            (kg)              WEIGHT    WEIGHT              WEIGHT
                                    (lb)      (lb)              (lb)                                 (kg)      (kg)               (kg)
Voltage: 2400-3-60
     N                10,287         5929          1212          1021              4666              2689            550            463
     P                10,287         6021          1230          1021              4666              2731            558            463
     Q                10,287         6112          1248          1021              4666              2772            566            463
     R                10,287         6190          1264          1021              4666              2808            573            463
     S                10,287         6268          1280          1021              4666              2843            581            463
     T                10,287         6259          1280          1021              4666              2839            581            463
Voltage: 3300-3-60
     N                10,287         5927          1212          1021              4666              2688            550            463
     P                10,287         6019          1230          1021              4666              2730            558            463
     Q                10,287         6110          1248          1021              4666              2771            566            463
     R                10,287         6187          1264          1021              4666              2806            573            463
     S                10,287         6263          1280          1021              4666              2841            581            463
     T                10,287         6277          1280          1021              4666              2847            581            463
Voltage: 4160-3-60
     N                10,287         6103          1247          1021              4666              2768            566            463
     P                10,287         6103          1248          1021              4666              2768            566            463
     Q                10,287         6103          1248          1021              4666              2768            566            463
     R                10,287         6185          1264          1021              4666              2805            573            463
     S                10,287         6268          1280          1021              4666              2843            581            463
     T                10,287         6268          1280          1021              4666              2843            581            463
Voltage: 6900-3-60
     N                10,287         6558          1316          1021              4666              2975            600            463
     P                10,287         6559          1316          1021              4666              2975            600            463
     Q                10,287         6559          1316          1021              4666              2975            600            463
     R                10,287         6566          1316          1021              4666              2978            600            463
     S                10,287         6574          1316          1021              4666              2982            600            463
     T                10,287         6604          1351          1021              4666              2996            613            463
Voltage: 11000-3-60
     N                10,287         6587          1351          1021              4666              2988            613            463
     P                10,287         6587          1351          1021              4666              2988            613            463
     Q                10,287         6587          1351          1021              4666              2988            613            463
     R                10,287         6716          1385          1021              4666              3036            628            463
     S                10,287         6844          1419          1021              4666              3104            644            463
     T                10,287         6844          1419          1021              4666              3104            644            463
Voltage: 13800-3-60
     N                10,287         6554          1351          1021              4666              2973            613            463
     P                10,287         6554          1351          1021              4666              2973            613            463
     Q                10,287         6554          1351          1021              4666              2973            613            463
     R                10,287         6709          1385          1021              4666              3043            628            463
     S                10,287         6864          1419          1021              4666              3113            644            463
     T                10,287         6864          1419          1021              4666              3113            644            463
*Total compressor weight is the sum of the compressor aerodynamic       **Compressor aerodynamic component weight only, motor weight not
components (compressor weight column), stator, rotor, and end bell      included. Applicable to standard compressors only. For high lift com-
cover weights.                                                          pressors, contact Carrier Chiller Marketing for weights.
†See Model Number Nomenclature on page 8.
                                                                                                                                          23
Physical data (cont)
                      19XR COMPRESSOR AND MOTOR WEIGHTS*— HIGH-EFFICIENCY MOTORS (cont)
                                                  COMPRESSOR FRAME SIZE 6, 50 Hz†
                                      ENGLISH                                                   SI
  MOTOR                          STATOR AND ROTOR AND END BELL                         STATOR AND ROTOR AND END BELL
               COMPRESSOR         HOUSING     SHAFT    COVER              COMPRESSOR    HOUSING     SHAFT    COVER
   CODE          WEIGHT†                                                    WEIGHT†
                   (lb)            WEIGHT     WEIGHT   WEIGHT                 (kg)       WEIGHT    WEIGHT    WEIGHT
                                     (lb)      (lb)     (lb)                               (kg)      (kg)     (kg)
Voltage: 3000-3-50
     N                10,287          5918          1212           1021      4666         2684       550      463
     P                10,287          6006          1230           1021      4666         2724       558      463
     Q                10,287          6094          1248           1021      4666         2764       566      463
     R                10,287          6184          1264           1021      4666         2805       573      463
     S                10,287          6274          1280           1021      4666         2846       581      463
     T                10,287          6296          1280           1021      4666         2856       581      463
Voltage: 3300-3-50
     N                10,287          5913          1212           1021      4666         2682       550      463
     P                10,287          6007          1230           1021      4666         2725       558      463
     Q                10,287          6101          1248           1021      4666         2767       566      463
     R                10,287          6192          1264           1021      4666         2809       573      463
     S                10,287          6283          1280           1021      4666         2850       581      463
     T                10,287          6266          1280           1021      4666         2842       581      463
Voltage: 6300-3-50
     N                10,287          6277          1280           1021      4666         2847       581      463
     P                10,287          6333          1298           1021      4666         2873       589      463
     Q                10,287          6389          1316           1021      4666         2898       600      463
     R                10,287          6473          1316           1021      4666         2936       600      463
     S                10,287          6556          1316           1021      4666         2974       600      463
     T                10,287          6609          1351           1021      4666         2998       613      463
Voltage: 10000-3-50
     N                10,287          6281          1280           1021      4666         2849       581      463
     P                10,287          6281          1281           1021      4666         2849       581      463
     Q                10,287          6281          1281           1021      4666         2849       581      463
     R                10,287          6441          1316           1021      4666         2922       600      463
     S                10,287          6600          1351           1021      4666         2994       613      463
     T                10,287          6156          1351           1021      4666         2792       613      463
Voltage: 11000-3-50
     N                10,287          6600          1351           1021      4666         2994       613      463
     P                10,287          6600          1351           1021      4666         2994       613      463
     Q                10,287          6600          1351           1021      4666         2994       613      463
     R                10,287          6765          1385           1021      4666         3069       628      463
     S                10,287          6930          1419           1021      4666         3143       644      463
     T                10,287          6930          1419           1021      4666         3143       644      463
*Total compressor weight is the sum of the compressor aerodynamic
components (compressor weight column), stator, rotor, and end bell
cover weights.
†See Model Number Nomenclature on page 8.
**Compressor aerodynamic component weight only, motor weight not
included. Applicable to standard compressors only. For high lift com-
pressors, contact Carrier Chiller Marketing for weights.
24
                      19XR COMPRESSOR AND MOTOR WEIGHTS*— HIGH-EFFICIENCY MOTORS (cont)
                                                  COMPRESSOR FRAME SIZE 7, 60 Hz†
                                       ENGLISH                                                      SI
  MOTOR                           STATOR AND ROTOR AND           END BELL                  STATOR AND ROTOR AND   END BELL
               COMPRESSOR          HOUSING     SHAFT              COVER       COMPRESSOR    HOUSING     SHAFT      COVER
  CODE           WEIGHT**                                                       WEIGHT**
                   (lb)             WEIGHT     WEIGHT             WEIGHT          (kg)       WEIGHT    WEIGHT      WEIGHT
                                      (lb)      (lb)               (lb)                        (kg)      (kg)       (kg)
Voltage: 2400-3-60
     U                16,024           6719           1443              983      7268         3048       654        446
     V                16,024           6718           1443              983      7268         3047       654        446
     W                16,024           6717           1443              983      7268         3047       654        446
     X                16,024           6811           1460              983      7268         3089       662        446
     Y                16,024           6906           1476              983      7268         3132       670        446
     Z                16,024           7073           1509              983      7268         3208       684        446
Voltage: 3300-3-60
     U                16,024           6723           1443              983      7268         3049       654        446
     V                16,024           6730           1443              983      7268         3053       654        446
     W                16,024           6736           1443              983      7268         3055       654        446
     X                16,024           6816           1460              983      7268         3092       662        446
     Y                16,024           6895           1476              983      7268         3128       670        446
     Z                16,024           7055           1509              983      7268         3200       684        446
Voltage: 4160-3-60
     U                16,024           6739           1443              983      7268         3057       654        446
     V                16,024           6721           1443              983      7268         3049       654        446
     W                16,024           6703           1443              983      7268         3040       654        446
     X                16,024           6778           1460              983      7268         3074       662        446
     Y                16,024           6853           1476              983      7268         3108       670        446
     Z                16,024           7069           1509              983      7268         3206       684        446
Voltage: 6900-3-60
     U                16,024           6730           1443              983      7268         3053       654        446
     V                16,024           6909           1476              983      7268         3134       670        446
     W                16,024           7088           1509              983      7268         3215       684        446
     X                16,024           7076           1509              983      7268         3210       684        446
     Y                16,024           7064           1509              983      7268         3204       684        446
     Z                16,024           7141           1542              983      7268         3239       699        446
Voltage: 11000-3-60
     U                16,024           7042           1509              983      7268         3194       684        446
     V                16,024           7085           1526              983      7268         3214       692        446
     W                16,024           7128           1542              983      7268         3233       699        446
     X                16,024           7131           1542              983      7268         3235       699        446
     Y                16,024           7135           1542              983      7268         3236       699        446
     Z                16,024           7313           1575              983      7268         3317       714        446
Voltage: 13800-3-60
     U                16,024           7073           1509              983      7268         3208       684        446
     V                16,024           7109           1526              983      7268         3225       692        446
     W                16,024           7146           1542              983      7268         3241       699        446
     X                16,024           7146           1542              983      7268         3241       699        446
     Y                16,024           7146           1542              983      7268         3241       699        446
     Z                16,024           7295           1575              983      7268         3309       714        446
*Total compressor weight is the sum of the compressor aerodynamic
components (compressor weight column), stator, rotor, and end bell
cover weights.
†See Model Number Nomenclature on page 8.
**Compressor aerodynamic component weight only, motor weight not
included. Applicable to standard compressors only. For high lift com-
pressors, contact Carrier Chiller Marketing for weights.
                                                                                                                          25
Physical data (cont)
                      19XR COMPRESSOR AND MOTOR WEIGHTS*— HIGH-EFFICIENCY MOTORS (cont)
                                                  COMPRESSOR FRAME SIZE 7, 50 Hz†
                                       ENGLISH                                                      SI
  MOTOR                           STATOR AND ROTOR AND           END BELL                  STATOR AND ROTOR AND   END BELL
               COMPRESSOR          HOUSING     SHAFT              COVER       COMPRESSOR    HOUSING     SHAFT      COVER
   CODE          WEIGHT**                                                       WEIGHT**
                   (lb)             WEIGHT     WEIGHT             WEIGHT          (kg)       WEIGHT    WEIGHT      WEIGHT
                                      (lb)      (lb)               (lb)                        (kg)      (kg)       (kg)
Voltage: 3000-3-50
     U                16,024          6725            1443              983      7268         3050       654        446
     V                16,024          6716            1443              983      7268         3046       654        446
     W                16,024          6706            1443              983      7268         3042       654        446
     X                16,024          6802            1460              983      7268         3085       662        446
     Y                16,024          6899            1476              983      7268         3129       670        446
     Z                16,024          7066            1509              983      7268         3205       684        446
Voltage: 3300-3-50
     U                16,024          6743            1443              983      7268         3059       654        446
     V                16,024          6739            1443              983      7268         3057       654        446
     W                16,024          6734            1443              983      7268         3054       654        446
     X                16,024          6826            1460              983      7268         3096       662        446
     Y                16,024          6917            1476              983      7268         3137       670        446
     Z                16,024          7075            1509              983      7268         3209       684        446
Voltage: 6300-3-50
     U                16,024          6743            1443              983      7268         3059       654        446
     V                16,024          6900            1476              983      7268         3130       670        446
     W                16,024          7058            1509              983      7268         3201       684        446
     X                16,024          7130            1526              983      7268         3234       692        446
     Y                16,024          7203            1542              983      7268         3267       699        446
     Z                16,024          7203            1542              983      7268         3267       699        446
Voltage: 10000-3-50
     U                16,024          6904            1476              983      7268         3132       670        446
     V                16,024          6907            1476              983      7268         3133       670        446
     W                16,024          6910            1476              983      7268         3134       670        446
     X                16,024          7074            1509              983      7268         3209       684        446
     Y                16,024          7238            1542              983      7268         3283       699        446
     Z                16,024          7401            1575              983      7268         3357       714        446
Voltage: 11000-3-50
     U                16,024          7139            1509              983      7268         3238       684        446
     V                16,024          7186            1526              983      7268         3260       692        446
     W                16,024          7234            1542              983      7268         3281       699        446
     X                16,024          7234            1542              983      7268         3281       699        446
     Y                16,024          7234            1542              983      7268         3281       699        446
     Z                16,024          7383            1575              983      7268         3349       714        446
*Total compressor weight is the sum of the compressor aerodynamic
components (compressor weight column), stator, rotor, and end bell
cover weights.
†See Model Number Nomenclature on page 8.
**Compressor aerodynamic component weight only, motor weight not
included. Applicable to standard compressors only. For high lift com-
pressors, contact Carrier Chiller Marketing for weights.
26
                                  COMPONENT WEIGHTS — SINGLE-STAGE COMPRESSORS AND
                                  TWO-STAGE COMPRESSORS FRAME 6, FRAME 7, AND FRAME E
                                         lb       kg     lb      kg         lb      kg       lb     kg       lb      kg       lb      kg      lb      kg
Suction Pipe Assembly
                                         116       53    185      84        239     108     407     185      310     141     486      220     613     278
(includes Flanges)
Discharge Assembly                       100       45    125      57        157      71     325     147      290     132     256     116      312     142
Control Panel† (Frames 2-5, E)            34       15     34      15        34       15      34      15       34      15       —      —       —       —
Optional Cooler Inlet Isolation Valve         8     4     13         6      20          9    24      11       24      11      26       12      28      13
Optional Discharge Isolation Valve        26       12     46      21        74       34     108      49       93      42     277       91     324     147
Std Tier VFD — 380, 400, and 460-v
                                         650      295    650     295        —       —        —      —        —       —       —        —       —       —
(230, 335, 445 A)
Std Tier VFD — 380, 400, and 460-v       —        —     1035     469     1035       469      —      —        —       —       —        —       —       —
(485, 550 A)
Std Tier VFD — 380, 400, and 460-v       —        —     1600     726     1600       726      —      —        —       —       —        —       —       —
(605, 680 A)
Std Tier VFD — 380, 400, and 460-v
                                         —        —      —       —       1600       726      —      —        —       —       —        —       —       —
(765 A)
Std Tier VFD — 380, 400, and 460-v
                                         —        —      —       —       1600       726     1600    726     1600     726     —        —       —       —
(855, 960, 1070 A)
Std Tier VFD — 380, 400, and 460-v       —        —      —       —       3000      1361     3000   1361     3000    1361     —        —       —       —
(1275 A)
Std Tier VFD — 380, 400, and 460-v
                                         —        —      —       —          —       —       3000   1361     3000    1361     —        —       —       —
(1530 A)
LiquiFlo™ 2 VFD — 380, 400, and
                                        1600      726   1600     726        —       —        —      —        —       —       —        —       —       —
460-v (442 A)
LiquiFlo 2 VFD — 380, 400, and 460-v
(608 A)                                  —        —     1600     726     1600       726      —      —        —       —       —        —       —       —
LiquiFlo 2 VFD — 380, 400, and 460-v
                                         —        —      —       —       2800      1270     2800   1270     2800    1270     —        —       —       —
(900 A)
LiquiFlo 2 VFD — 380, 400, and 460-v     —        —      —       —       2850      1293     2850   1293     2850    1293     —        —       —       —
(1200 A)
LiquiFlo 2 VFD — 575-v (390 A)          2200      998   2200     998        —       —        —      —        —       —       —        —       —       —
VFD Shelf                                —        —      —       —       1049       476     1049    476     1049     476     —        —       —       —
HMI Panel (Frames 6 and 7 only)          —        —      —       —          —       —        —      —        —       —       25       11       25      11
Auxiliary Control Panel
                                         —        —      —       —          —       —        —      —        —       —      190       86      190      86
(Frames 6 and 7 only)
Economizer Cover                         —        —      —       —          —       —        —      —        120      54    132       60      182      83
High Side Float Chamber Cover            —        —      —       —          —       —        —      —        296     134    132       60      182      83
*To determine compressor frame size, refer to 19XR,XRV Computer Selection         NOTE: VFD sizes are available on select heat exchanger models; consult the
Program.                                                                          19XR,XRV Computer Selection program.
†Included in total cooler weight.
                                                                                                                                                        27
Physical data (cont)
     19XR,XRV HEAT EXCHANGER WEIGHTS — SINGLE-STAGE COMPRESSOR AND TWO-STAGE COMPRESSOR
                        FRAME SIZE E — DRIVE END ENTERING COOLER WATER
                                                  ENGLISH                                                                              SI
               Dry Rigging Weight                                                               Dry Rigging Weight
  CODE†                                                     Machine Charge                                                                   Machine Charge
                      (lb)*                                                                            (kg)*
              Cooler      Condenser       Refrigerant Weight (lb)         Water Weight (lb)    Cooler      Condenser       Refrigerant Weight (kg)        Water Weight (kg)
               Only         Only           Cooler    Condenser          Cooler   Condenser      Only         Only           Cooler     Condenser         Cooler  Condenser
     10         2707          2704           328        226               283        348        1229          1228           149          103             128        158
     11         2777          2772           357        226               309        374        1261          1258           162          103             140        170
     12         2848          2857           387        226               335        407        1293          1297           176          103             152        185
     15         2968          2984           405        275               327        402        1346          1355           184          125             148        183
     16         3054          3068           441        275               359        435        1387          1393           200          125             163        197
     17         3141          3173           477        275               391        475        1426          1441           217          125             178        216
     20         3407          3373           416        252               402        398        1547          1531           189          114             183        181
     21         3555          3540           459        252               456        462        1614          1607           208          114             207        210
     22         3711          3704           505        252               514        526        1685          1682           229          114             233        239
     30         4071          3694           510        308               464        464        1848          1677           232          140             211        211
     31         4253          3899           565        308               531        543        1931          1770           257          140             241        247
     32         4445          4100           626        308               601        621        2018          1861           284          140             273        282
     35         4343          4606           577        349               511        513        1972          2091           262          158             232        233
     36         4551          4840           639        349               587        603        2066          2197           290          158             266        274
     37         4769          5069           709        349               667        692        2165          2301           322          158             303        314
     40         4908          5039           726        338               863        915        2228          2288           330          153             392        415
     41         5078          5232           783        338               930        995        2305          2375           355          153             422        452
     42         5226          5424           840        338               990       1074        2373          2462           381          153             449        488
     45         5363          5602           821        383               938        998        2435          2543           373          174             426        453
     46         5559          5824           874        383              1014       1088        2524          2644           397          174             460        494
     47         5730          6044           949        383              1083       1179        2601          2744           431          174             492        535
     50         5713          6090           897        446              1101       1225        2594          2765           407          202             500        556
     51         5940          6283           974        446              1192       1304        2697          2852           442          202             541        592
     52         6083          6464          1021        446              1248       1379        2762          2935           464          202             567        626
     53         6141          6529          1010        446              1277       1409        2788          2964           459          202             580        640
     54         6192          6591           987        446              1302       1439        2811          2992           448          202             591        653
     55         6257          6785          1014        504              1201       1339        2841          3080           460          229             545        608
     56         6517          7007          1101        504              1304       1429        2959          3181           500          229             592        649
     57         6682          7215          1154        504              1369       1514        3034          3276           524          229             622        687
     58         6751          7291          1143        504              1401       1550        3065          3310           519          229             636        704
     59         6811          7363          1116        504              1430       1583        3092          3343           507          229             649        719
     5A         5124           —             491         —               1023        —          2326           —             223           —              464         —
     5B         5177           —             510         —               1050        —          2350           —             232           —              477         —
     5C         5243           —             532         —               1079        —          2380           —             242           —              490         —
     5F         5577           —             553         —               1113        —          2532           —             251           —              505         —
     5G         5640           —             575         —               1143        —          2561           —             261           —              519         —
     5H         5716           —             600         —               1176        —          2595           —             272           —              534         —
     5K         4993           —             673         —               1067        —          2267           —             306           —              484         —
     5L         5090           —             706         —               1118        —          2311           —             321           —              508         —
     5M         5165           —             742         —               1162        —          2345           —             337           —              528         —
     5P         5041           —             641         —               1111        —          2289           —             291           —              504         —
     5Q         5131           —             678         —               1155        —          2329           —             308           —              524         —
     5R         5214           —             709         —               1206        —          2367           —             322           —              548         —
     5T         5425           —             768         —               1162        —          2463           —             349           —              528         —
     5U         5534           —             801         —               1220        —          2512           —             364           —              554         —
     5V         5620           —             843         —               1270        —          2551           —             383           —              577         —
     5X         5484           —             730         —               1212        —          2490           —             331           —              550         —
     5Y         5584           —             769         —               1262        —          2535           —             349           —              573         —
     5Z         5678           —             805         —               1320        —          2578           —             365           —              599         —
     60         6719          6764          1091        479              1400       1521        3050          3071           495          217             636        691
     61         6895          6949          1150        479              1470       1597        3130          3155           522          217             667        725
     62         7038          7130          1202        479              1527       1671        3195          3237           546          217             693        759
     63         7103          7199          1202        479              1559       1704        3225          3268           546          217             708        774
     64         7161          7264          1178        479              1587       1735        3251          3298           535          217             720        788
     65         7392          6782          1241        542              1530       1667        3356          3079           563          246             695        757
     66         7594          7894          1309        542              1610       1753        3448          3584           594          246             731        796
     67         7759          8102          1369        542              1674       1838        3523          3678           622          246             760        834
     68         7836          8182          1359        542              1711       1875        3558          3715           617          246             777        851
     69         7905          8258          1332        542              1743       1911        3589          3749           605          246             791        868
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635-mm]      2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution
wall).                                                                                           piping weight.
†Heat exchanger frame sizes 1 through 6 available on single-stage chillers only.              3. For special tubes refer to the 19XR,XRV Computer Selection Program.
NOTES:                                                                                        4. All weights for standard 2-pass NIH (nozzle-in-head) design.
 1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution pip-    5. For “E” compressor, add 1054 lb (478 kg) steel weight and 283 lb (128 kg) refriger-
     ing weight.                                                                                 ant weight for economizer assembly.
28
     19XR,XRV HEAT EXCHANGER WEIGHTS — SINGLE-STAGE COMPRESSOR AND TWO-STAGE COMPRESSOR
                      FRAME SIZE E — DRIVE END ENTERING COOLER WATER (cont)
                                                   ENGLISH                                                                             SI
               Dry Rigging Weight                                                                Dry Rigging Weight
                                                             Machine Charge                                                                  Machine Charge
                      (lb)*                                                                             (kg)*
 CODE†
                                                Refrigerant                 Water Weight                                        Refrigerant                 Water Weight
              Cooler      Condenser              Weight (lb)                    (lb)            Cooler      Condenser           Weight (kg)                     (kg)
               Only         Only                                                                 Only         Only
                                            Cooler   Condenser           Cooler   Condenser                                 Cooler   Condenser           Cooler   Condenser
    6K          5,716          —              760          —              1291        —          2595           —            345          —                586        —
    6L          5,804          —              797          —              1341        —          2635           —            362          —                609        —
    6M          5,894          —              828          —              1399        —          2676           —            376          —                635        —
    6P          5,768          —              725          —              1338        —          2619           —            329          —                607        —
    6Q          5,852          —              764          —              1385        —          2657           —            347          —                629        —
    6R          5,938          —              798          —              1439        —          2696           —            362          —                653        —
    6T          6,230          —              863          —              1405        —          2828           —            392          —                638        —
    6U          6,330          —              905          —              1462        —          2874           —            411          —                664        —
    6V          6,433          —              941          —              1528        —          2921           —            427          —                694        —
    6X          6,293          —              823          —              1459        —          2857           —            374          —                662        —
    6Y          6,388          —              868          —              1512        —          2900           —            394          —                686        —
    6Z          6,487          —              906          —              1574        —          2945           —            411          —                715        —
    70          9,942        10,786          1409         840             2008       2225        4514          4897          640         381               912       1010
    71         10,330        11,211          1539         840             2164       2389        4690          5090          699         381               982       1085
    72         10,632        11,622          1646         840             2286       2548        4827          5276          747         381              1038       1157
    73         10,715        11,737          1622         840             2328       2604        4865          5329          736         381              1057       1182
    74         10,790        11,775          1584         840             2366       2622        4899          5346          719         381              1074       1190
    75         10,840        11,859          1599         950             2183       2431        4921          5384          726         431               991       1104
    76         11,289        12,345          1747         950             2361       2619        5125          5605          793         431              1072       1189
    77         11,638        12,814          1869         950             2501       2801        5284          5818          849         431              1135       1272
    78         11,738        12,949          1849         950             2548       2864        5329          5879          839         431              1157       1300
    79         11,828        12,994          1806         950             2592       2885        5370          5899          820         431              1177       1310
    7K          8,728          —             1047          —              1948        —          3963           —            475          —                884        —
    7L          8,959          —             1132          —              2094        —          4067           —            514          —                951        —
    7M          9,161          —             1214          —              2229        —          4159           —            551          —               1012        —
    7P          8,792          —             1002          —              2010        —          3992           —            455          —                913        —
    7Q          9,023          —             1087          —              2156        —          4096           —            493          —                979        —
    7R          9,229          —             1167          —              2295        —          4190           —            530          —               1042        —
    7T          9,431          —             1194          —              2115        —          4282           —            542          —                960        —
    7U          9,698          —             1292          —              2282        —          4403           —            587          —               1036        —
    7V          9,932          —             1403          —              2436        —          4509           —            637          —               1106        —
    7X          9,510          —             1142          —              2185        —          4318           —            518          —                992        —
    7Y          9,777          —             1240          —              2352        —          4439           —            563          —               1068        —
    7Z         10,016          —             1347          —              2511        —          4547           —            612          —               1140        —
    80         12,664        12,753          1700         836             2726       2977        5749          5790          772         380              1238       1352
    81         12,998        13,149          1812         836             2863       3143        5901          5970          823         380              1300       1427
    82         13,347        13,545          1928         836             3005       3309        6060          6149          875         380              1364       1502
    83         13,437        13,872          1877         836             3053       3476        6100          6298          852         380              1386       1578
    84         13,523        14,217          1840         836             3099       3651        6139          6455          835         380              1407       1658
    85         13,804        14,008          1927         945             2951       3238        6267          6360          875         429              1340       1470
    86         14,191        14,465          2054         945             3108       3428        6443          6567          933         429              1411       1556
    87         14,597        14,923          2186         945             3271       3618        6627          6775          992         429              1485       1643
    88         14,705        15,311          2142         945             3325       3608        6676          6951          972         429              1510       1638
    89         14,808        15,721          2099         945             3378       4009        6723          7137          953         429              1534       1820
    8K         11,153          —             1385          —              2760        —          5063           —            629          —               1253        —
    8L         11,400          —             1484          —              2926        —          5176           —            674          —               1328        —
    8M         11,650          —             1589          —              3088        —          5289           —            721          —               1402        —
    8P         11,219          —             1334          —              2830        —          5093           —            606          —               1285        —
    8Q         11,470          —             1430          —              2999        —          5207           —            649          —               1362        —
    8R         11,719          —             1535          —              3161        —          5320           —            697          —               1435        —
    8T         12,069          —             1580          —              2991        —          5479           —            717          —               1358        —
    8U         12,357          —             1694          —              3180        —          5610           —            769          —               1444        —
    8V         12,645          —             1814          —              3365        —          5741           —            824          —               1528        —
    8X         12,152          —             1522          —              3070        —          5517           —            691          —               1394        —
    8Y         12,444          —             1632          —              3264        —          5650           —            741          —               1482        —
    8Z         12,733          —             1752          —              3448        —          5781           —            795          —               1565        —
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635-mm]      2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution
wall).                                                                                           piping weight.
†Heat exchanger frame sizes 1 through 6 available on single-stage chillers only.              3. For special tubes refer to the 19XR,XRV Computer Selection Program.
NOTES:                                                                                        4. All weights for standard 2-pass NIH (nozzle-in-head) design.
 1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution pip-    5. For “E” compressor, add 1054 lb (478 kg) steel weight and 283 lb (128 kg) refriger-
     ing weight.                                                                                 ant weight for economizer assembly.
                                                                                                                                                                               29
Physical data (cont)
     19XR,XRV HEAT EXCHANGER WEIGHTS — SINGLE-STAGE COMPRESSOR AND TWO-STAGE COMPRESSOR
                      FRAME SIZE E — COMPRESSOR END ENTERING COOLER WATER
                                                  ENGLISH                                                                              SI
               Dry Rigging Weight                            Machine Charge                     Dry Rigging Weight                           Machine Charge
 CODE†                (lb)*                                                                            (kg)*
              Cooler      Condenser       Refrigerant Weight (lb)         Water Weight (lb)     Cooler     Condenser       Refrigerant Weight (kg)        Water Weight (kg)
               Only         Only           Cooler    Condenser          Cooler   Condenser       Only        Only           Cooler    Condenser          Cooler  Condenser
    10         2707           2704           290        200               283        348         1228          1227          132           91             128        158
    11         2777           2772           310        200               309        374         1260          1257          141           91             140        170
    12         2848           2857           330        200               335        407         1292          1296          150           91             152        185
    15         2968           2984           320        250               327        402         1346          1354          145         113              148        182
    16         3054           3068           340        250               359        435         1385          1392          154         113              163        197
    17         3141           3173           370        250               391        475         1425          1439          168         113              177        215
    20         3407           3373           345        225               402        398         1545          1530          156         102              182        181
    21         3555           3540           385        225               456        462         1613          1606          175         102              207        210
    22         3711           3704           435        225               514        526         1683          1680          197         102              233        239
    30         4071           3694           350        260               464        464         1847          1676          159         118              210        210
    31         4253           3899           420        260               531        543         1929          1769          191         118              241        246
    32         4445           4100           490        260               601        621         2016          1860          222         118              273        282
    35         4343           4606           400        310               511        513         1970          2089          181         141              232        233
    36         4551           4840           480        310               587        603         2064          2195          218         141              266        274
    37         4769           5069           550        310               667        692         2163          2299          249         141              303        314
    40         4908           5039           560        338               863        915         2226          2286          254         153              391        415
    41         5078           5232           630        338               930        995         2303          2373          286         153              422        451
    42         5226           5424           690        338               990       1074         2370          2460          313         153              449        487
    45         5363           5602           640        383               938        998         2433          2541          290         174              425        453
    46         5559           5824           720        383              1014       1088         2522          2642          327         174              460        494
    47         5730           6044           790        383              1083       1179         2599          2742          358         174              491        535
    50         5713           6090           750        446              1101       1225         2591          2762          340         202              499        556
    51         5940           6283           840        446              1192       1304         2694          2850          381         202              541        591
    52         6083           6464           900        446              1248       1379         2759          2932          408         202              566        626
    53         6141           6529           900        446              1277       1409         2788          2964          408         202              580        640
    54         6192           6591           900        446              1302       1439         2811          2992          408         202              591        653
    55         6257           6785           870        509              1201       1339         2838          3078          395         231              545        607
    56         6517           7007           940        509              1304       1429         2956          3178          426         231              591        648
    57         6682           7215           980        509              1369       1514         3031          3273          445         231              621        687
    58         6751           7291           980        509              1401       1550         3065          3310          445         231              636        704
    59         6811           7363           980        509              1430       1583         3092          3343          445         231              649        719
    5A         5124            —             500         —               1023        —           2324           —            227          —               464         —
    5B         5177            —             520         —               1050        —           2348           —            236          —               476         —
    5C         5243            —             550         —               1079        —           2378           —            249          —               489         —
    5F         5577            —             550         —               1113        —           2530           —            249          —               505         —
    5G         5640            —             570         —               1143        —           2558           —            259          —               518         —
    5H         5716            —             600         —               1176        —           2593           —            272          —               533         —
    5K         4993            —             673         —               1067        —           2267           —            306          —               484         —
    5L         5090            —             706         —               1118        —           2311           —            321          —               508         —
    5M         5165            —             742         —               1162        —           2345           —            337          —               528         —
    5P         5041            —             641         —               1111        —           2289           —            291          —               504         —
    5Q         5131            —             678         —               1155        —           2329           —            308          —               524         —
    5R         5214            —             709         —               1206        —           2367           —            322          —               548         —
    5T         5425            —             768         —               1162        —           2463           —            349          —               528         —
    5U         5534            —             801         —               1220        —           2512           —            364          —               554         —
    5V         5620            —             843         —               1270        —           2551           —            383          —               577         —
    5X         5484            —             730         —               1212        —           2490           —            331          —               550         —
    5Y         5584            —             769         —               1262        —           2535           —            349          —               573         —
    5Z         5678            —             805         —               1320        —           2578           —            365          —               599         —
    60         6719           6764           940        479              1400       1521         3048          3068          426         217              635        690
    61         6895           6949           980        479              1470       1597         3128          3152          445         217              667        724
    62         7038           7130          1020        479              1527       1671         3192          3234          463         217              693        758
    63         7103           7199          1020        479              1559       1704         3225          3268          463         217              708        773
    64         7161           7264          1020        479              1587       1735         3251          3298          463         217              720        788
    65         7392           7682          1020        542              1530       1667         3353          3484          463         246              694        756
    66         7594           7894          1060        542              1610       1753         3445          3581          481         246              730        795
    67         7759           8102          1090        542              1674       1838         3519          3675          494         246              759        834
    68         7836           8182          1090        542              1711       1875         3558          3715          494         246              777        851
    69         7905           8258          1090        542              1743       1911         3589          3749          494         246              791        868
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635-mm]      2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution
wall).                                                                                           piping weight.
†Heat exchanger frame sizes 1 through 6 available on single-stage chillers only.              3. For special tubes refer to the 19XR,XRV Computer Selection Program.
NOTES:                                                                                        4. All weights for standard 2-pass NIH (nozzle-in-head) design.
 1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution pip-    5. For “E” compressor, add 1054 lb (478 kg) steel weight and 283 lb (128 kg) refriger-
     ing weight.                                                                                 ant weight for economizer assembly.
30
     19XR,XRV HEAT EXCHANGER WEIGHTS — SINGLE-STAGE COMPRESSOR AND TWO-STAGE COMPRESSOR
                   FRAME SIZE E — COMPRESSOR END ENTERING COOLER WATER (cont)
                                                   ENGLISH                                                                               SI
               Dry Rigging Weight                            Machine Charge                       Dry Rigging Weight                           Machine Charge
  CODE†               (lb)*                                                                              (kg)*
              Cooler      Condenser        Refrigerant Weight (lb)         Water Weight (lb)     Cooler      Condenser      Refrigerant Weight (kg)        Water Weight (kg)
               Only         Only           Cooler     Condenser          Cooler   Condenser       Only         Only          Cooler    Condenser          Cooler  Condenser
    6K          5,716          —             760          —               1291        —           2595           —            345          —                586       —
    6L          5,804          —             797          —               1341        —           2635           —            362          —                609       —
    6M          5,894          —             828          —               1399        —           2676           —            376          —                635       —
    6P          5,768          —             725          —               1338        —           2619           —            329          —                607       —
    6Q          5,852          —             764          —               1385        —           2657           —            347          —                629       —
    6R          5,938          —             798          —               1439        —           2696           —            362          —                653       —
    6T          6,230          —             863          —               1405        —           2828           —            392          —                638       —
    6U          6,330          —             905          —               1462        —           2874           —            411          —                664       —
    6V          6,433          —             941          —               1528        —           2921           —            427          —                694       —
    6X          6,293          —             823          —               1459        —           2857           —            374          —                662       —
    6Y          6,388          —             868          —               1512        —           2900           —            394          —                686       —
    6Z          6,487          —             906          —               1574        —           2945           —            411          —                715       —
    70          9,942        10,786         1220         840              2008       2225         4510          4893          553         381               911      1009
    71         10,330        11,211         1340         840              2164       2389         4686          5085          608         381               982      1084
    72         10,632        11,622         1440         840              2286       2548         4823          5278          653         381              1037      1156
    73         10,715        11,737         1440         840              2328       2604         4865          5329          654         381              1057      1182
    74         10,790        11,775         1440         840              2366       2622         4899          5346          654         381              1074      1190
    75         10,840        11,859         1365         950              2183       2431         4917          5379          619         431               990      1103
    76         11,289        12,345         1505         950              2361       2619         5121          5600          683         431              1071      1188
    77         11,638        12,814         1625         950              2501       2801         5279          5812          737         431              1134      1271
    78         11,738        12,949         1625         950              2548       2864         5329          5879          738         431              1157      1300
    79         11,828        12,994         1625         950              2592       2885         5370          5899          738         431              1177      1310
    7K          8,728          —            1047          —               1948        —           3963           —            475          —                884       —
    7L          8,959          —            1132          —               2094        —           4067           —            514          —                951       —
    7M          9,161          —            1214          —               2229        —           4159           —            551          —               1012       —
    7P          8,792          —            1002          —               2010        —           3992           —            455          —                913       —
    7Q          9,023          —            1087          —               2156        —           4096           —            493          —                979       —
    7R          9,229          —            1167          —               2295        —           4190           —            530          —               1042       —
    7T          9,431          —            1194          —               2115        —           4282           —            542          —                960       —
    7U          9,698          —            1292          —               2282        —           4403           —            587          —               1036       —
    7V          9,932          —            1403          —               2436        —           4509           —            637          —               1106       —
    7X          9,510          —            1142          —               2185        —           4318           —            518          —                992       —
    7Y          9,777          —            1240          —               2352        —           4439           —            563          —               1068       —
    7Z         10,016          —            1347          —               2511        —           4547           —            612          —               1140       —
    80         12,664        12,753         1500         836              2726       2977         5744          5785          680         379              1236      1350
    81         12,998        13,149         1620         836              2863       3143         5896          5964          735         379              1299      1426
    82         13,347        13,545         1730         836              3005       3309         6054          6144          785         379              1363      1501
    83         13,437        13,872         1730         836              3053       3476         6100          6298          785         379              1386      1578
    84         13,523        14,217         1730         836              3099       3651         6139          6455          785         379              1407      1658
    85         13,804        14,008         1690         945              2951       3238         6261          6354          767         429              1339      1469
    86         14,191        14,465         1820         945              3108       3428         6437          6561          826         429              1410      1555
    87         14,597        14,923         1940         945              3271       3618         6621          6769          880         429              1484      1641
    88         14,705        15,311         1940         945              3325       3808         6676          6951          881         429              1510      1729
    89         14,808        15,721         1940         945              3378       4009         6723          7137          881         429              1534      1820
    8K         11,153          —            1385          —               2760        —           5063           —            629          —               1253       —
    8L         11,400          —            1484          —               2926        —           5176           —            674          —               1328       —
    8M         11,650          —            1589          —               3088        —           5289           —            721          —               1402       —
    8P         11,219          —            1334          —               2830        —           5093           —            606          —               1285       —
    8Q         11,470          —            1430          —               2999        —           5207           —            649          —               1362       —
    8R         11,719          —            1535          —               3161        —           5320           —            697          —               1435       —
    8T         12,069          —            1580          —               2991        —           5479           —            717          —               1358       —
    8U         12,357          —            1694          —               3180        —           5610           —            769          —               1444       —
    8V         12,645          —            1814          —               3365        —           5741           —            824          —               1528       —
    8X         12,152          —            1522          —               3070        —           5517           —            691          —               1394       —
    8Y         12,444          —            1632          —               3264        —           5650           —            741          —               1482       —
    8Z         12,733          —            1752          —               3448        —           5781           —            795          —               1565       —
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635-mm]       5. For “E” compressor, add 1054 lb (478 kg) steel weight and 283 lb (128 kg) refriger-
wall).                                                                                            ant weight for economizer assembly.
†Heat exchanger frame sizes 1 through 6 available on single-stage chillers only.
NOTES:
 1. Cooler includes the control panel (ICVC), suction elbow, and 1/2 the distribution pip-
     ing weight.
 2. Condenser includes float valve and sump, discharge elbow, and 1/2 the distribution
     piping weight.
 3. For special tubes refer to the 19XR,XRV Computer Selection Program.
 4. All weights for standard 2-pass NIH (nozzle-in-head) design.
                                                                                                                                                                                31
Physical data (cont)
                                              19XR TWO-STAGE COMPRESSOR FRAME SIZE 6
                                                 HEAT EXCHANGER WEIGHTS (ENGLISH)
                             DRY RIGGING WEIGHT (lb)*                     REFRIGERANT WEIGHT (lb)                          WATER WEIGHT (lb)
      CODE†
                       COOLER ONLY      CONDENSER ONLY                 COOLER ONLY  CONDENSER ONLY                 COOLER ONLY    CONDENSER ONLY
        A40               16,877             18,542                       1647              927                       4328               4553
        A41               17,270             19,062                       1773              927                       4557               4890
        A42               17,690             19,565                       1887              927                       4816               5213
        A45               16,968             18,493                       1599              927                       4453               4582
        A46               17,371             19,063                       1714              927                       4701               4949
        A47               17,761             19,578                       1837              927                       4941               5281
32
                                              19XR TWO-STAGE COMPRESSOR FRAME SIZE 6
                                                    HEAT EXCHANGER WEIGHTS (SI)
                             DRY RIGGING WEIGHT (kg)*                       REFRIGERANT WEIGHT (kg)                            WATER WEIGHT (kg)
      CODE†               COOLER           CONDENSER                       COOLER        CONDENSER                       COOLER          CONDENSER
                           ONLY               ONLY                          ONLY            ONLY                          ONLY              ONLY
        A40                7655              8 410                           747              420                         1963               2065
        A41                7833              8 646                           804              420                         2067               2218
        A42                8024              8 875                           856              420                         2184               2365
        A45                7697              8 388                           725              420                         2020               2078
        A46                7879              8 647                           777              420                         2132               2245
        A47                8056              8 880                           833              420                         2241               2395
                                                                                                                                                                 33
Physical data (cont)
                                       19XR TWO-STAGE COMPRESSOR FRAME SIZE 7
                                          HEAT EXCHANGER WEIGHTS (ENGLISH)
                         DRY RIGGING WEIGHT (lb)*               REFRIGERANT WEIGHT (lb)                       WATER WEIGHT (lb)
     CODE†
                   COOLER ONLY      CONDENSER ONLY           COOLER ONLY  CONDENSER ONLY            COOLER ONLY      CONDENSER ONLY
       B60            24,704               —                    2273             —                      6,340                 —
       B61            25,337               —                    2355             —                      6,737                 —
       B62            25,964               —                    2460             —                      7,116                 —
       B65            25,014               —                    2185             —                      6,485                 —
       B66            25,631               —                    2275             —                      6,873                 —
       B67            26,264               —                    2379             —                      7,255                 —
34
                                       19XR TWO-STAGE COMPRESSOR FRAME SIZE 7
                                        HEAT EXCHANGER WEIGHTS (ENGLISH) (cont)
                        DRY RIGGING WEIGHT (lb)*                REFRIGERANT WEIGHT (lb)                      WATER WEIGHT (lb)
     CODE†
                   COOLER ONLY     CONDENSER ONLY            COOLER ONLY  CONDENSER ONLY             COOLER ONLY    CONDENSER ONLY
       D60             —                38,296                   —               2097                    —                11,473
       D61             —                39,624                   —               2097                    —                12,309
       D62             —                41,031                   —               2097                    —                13,210
       D65             —                37,624                   —               2097                    —                11,617
       D66             —                38,837                   —               2097                    —                12,387
       D67             —                40,460                   —               2097                    —                13,410
                                                                                                                                             35
Physical data (cont)
                                       19XR TWO-STAGE COMPRESSOR FRAME SIZE 7
                                             HEAT EXCHANGER WEIGHTS (SI)
                         DRY RIGGING WEIGHT (kg)*               REFRIGERANT WEIGHT (kg)                     WATER WEIGHT (kg)
     CODE†
                   COOLER ONLY      CONDENSER ONLY           COOLER ONLY  CONDENSER ONLY            COOLER ONLY    CONDENSER ONLY
       B60            11 206               —                    1031             —                     2876                —
       B61            11 493               —                    1068             —                     3056                —
       B62            11 777               —                    1116             —                     3228                —
       B65            11 346               —                     991             —                     2941                —
       B66            11 626               —                    1032             —                     3118                —
       B67            11 913               —                    1079             —                     3291                —
36
                                       19XR TWO-STAGE COMPRESSOR FRAME SIZE 7
                                          HEAT EXCHANGER WEIGHTS (SI) (cont)
                        DRY RIGGING WEIGHT (lb)*                REFRIGERANT WEIGHT (lb)                      WATER WEIGHT (lb)
     CODE†
                   COOLER ONLY     CONDENSER ONLY            COOLER ONLY  CONDENSER ONLY             COOLER ONLY    CONDENSER ONLY
       D60             —                17 371                   —               951                     —                 5204
       D61             —                17 973                   —               951                     —                 5583
       D62             —                18 611                   —               951                     —                 5992
       D65             —                17 066                   —               951                     —                 5269
       D66             —                17 616                   —               951                     —                 5619
       D67             —                18 352                   —               951                     —                 6083
                                                                                                                                             37
Physical data (cont)
                                     19XR TWO-STAGE COMPRESSOR FRAME SIZES 6 AND 7
                                                  ECONOMIZER WEIGHT
                 DRY WEIGHT       REFRIGERANT                                      DRY WEIGHT       REFRIGERANT
 FRAME SIZE                                          OPERATION WEIGHT (lb)                                            OPERATION WEIGHT (kg)
                    (lb)*          WEIGHT (lb)                                        (kg)*          WEIGHT (kg)
     XR6            1589              360                        1949                  721              163                        884
     XR7            2749              646                        3395                 1247              293                       1540
*Includes economizer weight and all the connecting piping to the
compressor.
                                ADDITIONAL WEIGHTS FOR 19XR,XRV MARINE WATERBOXES*
                            150 psig (1034 kPa) MARINE WATERBOXES — SINGLE-STAGE COMPRESSORS
150 psig (1034 kPa) MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 6 ENGLISH (lb)
38
                            ADDITIONAL WEIGHTS FOR 19XR,XRV MARINE WATERBOXES* (cont)
               150 psig (1034 kPa) MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 6 — SI (kg)
150 psig (1034 kPa) MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 7 — ENGLISH (lb)
150 psig (1034 kPa) MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 7 — SI (kg)
                                                                                                                              39
Physical data (cont)
                             ADDITIONAL WEIGHTS FOR 19XR,XRV MARINE WATERBOXES* (cont)
       300 psig (2068 kPa) ASME MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 6* — ENGLISH (lb)
300 psig (2068 kPa) ASME MARINE WATERBOXES — TWO-STAGE COMPRESSORS, FRAME SIZE 6* — SI (kg)
40
                                 19XR,XRV WATERBOX COVER WEIGHTS — ENGLISH (lb)
                                                FRAMES 1, 2, AND 3; COOLER
                                                                                  COOLER
                                                Frame 1                           Frame 2                          Frame 3
      WATERBOX DESCRIPTION
                                        Standard                         Standard                         Standard
                                        Nozzles           Flanged        Nozzles            Flanged       Nozzles            Flanged
NIH, 1 Pass Cover, 150 psig               177              204             287               318             287              318
NIH, 2 Pass Cover, 150 psig               185              218             287               340             287              340
NIH, 3 Pass Cover, 150 psig               180              196             294               310             294              310
MWB End Cover, 150 psig                    —                —              315               315             315              315
NIH/MWB Return Cover, 150 psig            136              136             243               243             243              243
NIH, 1 Pass Cover, 300 psig               248              301             411               486             411              486
NIH, 2 Pass Cover, 300 psig               255              324             411               518             411              518
NIH, 3 Pass Cover, 300 psig               253              288             433               468             433              468
NIH Plain End Cover, 300 psig             175              175             291               291             291              291
MWB End Cover, 300 psig                    —                —              619               619             619              619
MWB Return Cover, 300 psig                 —                —              445               445             445              445
    LEGEND                                                          NOTE: Weight for 2-pass cover, 150 psig, is included in the heat
NIH — Nozzle-in-Head                                                exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
                                                                               CONDENSER
                                                Frame 1                           Frame 2                          Frame 3
      WATERBOX DESCRIPTION
                                        Standard          Flanged        Standard           Flanged       Standard           Flanged
                                        Nozzles                          Nozzles                          Nozzles
NIH, 1 Pass Cover, 150 psig               177               204             260               297            260               297
NIH, 2 Pass Cover, 150 psig               185               218             265               318            265               318
NIH, 3 Pass Cover, 150 psig               180               196             272               288            272               288
MWB End Cover, 150 psig                    —                —               234               234            234               234
NIH/MWB Return Cover, 150 psig            136               136             225               225            225               225
NIH, 1 Pass Cover, 300 psig               248               301             379               454            379               454
NIH, 2 Pass Cover, 300 psig               255               324             379               486            379               486
NIH, 3 Pass Cover, 300 psig               253               288             401               436            401               436
NIH Plain End Cover, 300 psig             175               175             270               270            270               270
MWB End Cover, 300 psig                    —                —               474               474            474               474
MWB Return Cover, 300 psig                 —                —               359               359            359               359
    LEGEND                                                          NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat
NIH — Nozzle-in-Head                                                exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
                                                                                                                                       41
Physical data (cont)
                              19XR,XRV WATERBOX COVER WEIGHTS — ENGLISH (lb) (cont)
                                             FRAMES 4, 5, AND 6; COOLER
                                                                                       COOLER
                                                    Frame 4                            Frame 5                        Frame 6
         WATERBOX DESCRIPTION
                                           Standard                           Standard                       Standard
                                                              Flanged                            Flanged                        Flanged
                                           Nozzles                            Nozzles                        Nozzles
NIH, 1 Pass Cover, 150 psig                   148              185              168               229           187               223
NIH, 2 Pass Cover, 150 psig                   202              256              224               276           257               330
NIH, 3 Pass Cover, 150 psig                   473              489              617               634           765               791
MWB End Cover, 150 psig                       317              317              393               393           487               487
NIH/MWB Return Cover, 150 psig                138              138              154               154           172               172
NIH, 1 Pass Cover, 300 psig                   633              709              764               839           978              1053
NIH, 2 Pass Cover, 300 psig                   626              689              761               867           927              1078
NIH, 3 Pass Cover, 300 psig                   660              694              795               830           997              1050
NIH/MWB End Cover, 300 psig                   522              522              658               658           834               834
     LEGEND                                                          NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat
NIH — Nozzle-in-Head                                                 exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
                                                                                   CONDENSER
                                                    Frame 4                            Frame 5                        Frame 6
         WATERBOX DESCRIPTION
                                            Standard          Flanged         Standard           Flanged     Standard        Flanged
                                            Nozzles                           Nozzles                        Nozzles
NIH, 1 Pass Cover, 150 psig                   148               185              168               229          187               223
NIH, 2 Pass Cover, 150 psig                   191               245              224               298          245               330
NIH, 3 Pass Cover, 150 psig                   503               519              629               655          772               843
MWB End Cover and Bolt-on End Cover,          317               317              393               393          487               487
150 psig
NIH/MWB Return Cover, 150 psig                138               138              154               154          172               172
NIH, 1 Pass Cover, 300 psig                   633               709              764               839          978              1053
NIH, 2 Pass Cover, 300 psig                   622               729              727               878          923              1074
NIH, 3 Pass Cover, 300 psig                   655               689              785               838          995              1049
NIH/MWB End Cover, 300 psig                   522               522              658               658          834               834
    LEGEND                                                           NOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat
NIH — Nozzle-in-Head                                                 exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
42
                              19XR,XRV WATERBOX COVER WEIGHTS — ENGLISH (lb) (cont)
                                              FRAMES 7 AND 8; COOLER
                                                                                        COOLER
                                                                  Frame 7                                Frame 8
                WATERBOX DESCRIPTION
                                                     Standard Nozzles         Flanged      Standard Nozzles           Flanged
                                                                                      CONDENSER
                                                                    Frame 7                                 Frame 8
                 WATERBOX DESCRIPTION
                                                         Standard                                Standard
                                                         Nozzles               Flanged           Nozzles              Flanged
                                                                                                                                43
Physical data (cont)
                            19XR,XRV WATERBOX COVER WEIGHTS — ENGLISH (lb) (cont)
                                       TWO-STAGE COMPRESSOR FRAME 6; COOLER FRAME A
                                                                                           COOLER
                                                                                           FRAME A
          WATERBOX DESCRIPTION                     PASSES
                                                                  STANDARD NOZZLES                          FLANGED
                                                                                       CONDENSER
                                                                       FRAME A                              FRAME B
          WATERBOX DESCRIPTION                     PASSES
                                                               STANDARD                         STANDARD
                                                                NOZZLES          FLANGED         NOZZLES             FLANGED
44
                               19XR,XRV WATERBOX COVER WEIGHTS — ENGLISH (lb) (cont)
                                  TWO-STAGE COMPRESSOR FRAME 7; COOLER FRAMES B, C
                                                                                           COOLER
                                                                         FRAME B                              FRAME C
          WATERBOX DESCRIPTION                    PASSES
                                                             STANDARD                               STANDARD
                                                              NOZZLES              FLANGED           NOZZLES            FLANGED
                                                                                    CONDENSER
                                                                  FRAME C                                   FRAME D
      WATERBOX DESCRIPTION               PASSES
                                                                                                  STANDARD
                                                    STANDARD NOZZLES          FLANGED                                   FLANGED
                                                                                                   NOZZLES
Dished Head, 150 psi                         1             1380                  1600                1849                2029
MWB End Cover, 150 psi                       1             1367                  1367                1835                1835
MWB End Cover (ASME), 300 psi                1             3639                  3639                5249                5249
Dished Head, 150 psig                        2             1589                  1919                2076                2406
Dished Head (Return Cover), 150 psig         2             1367                  1367                1836                1836
MWB End Cover, 150 psig                      2             1497                  1497                1988                1988
MWB (Return Cover), 150 psi                  2             1367                  1367                1836                1836
MWB End Cover (ASME), 300 psig               2             3639                  3639                5249                5249
MWB (Return Cover) (ASME), 300 psig          2             3639                  3639                5249                5249
Dished Head, 150 psi                         3             1514                  1612                2028                2126
MWB End Cover, 150 psig                      3             1493                  1493                1993                1993
MWB End Cover (ASME), 300 psig               3             3639                  3639                5249                5249
          LEGEND
ASME — American Society of Mechanical Engineers                   NOTES:
MWB — Marine Waterbox                                              1. Consult factory for 1 and 3 pass data.
                                                                   2. Weight for dished head cover is included in the heat exchanger
                                                                      weights shown on pages 32-37.
                                                                   3. 2 pass weight difference is due to division plate.
                                                                                                                                  45
Physical data (cont)
                                 19XR,XRV WATERBOX COVER WEIGHTS — SI (kg)
                                             FRAMES 1, 2, 3; COOLER
                                                                                     COOLER
                                                  Frame 1                            Frame 2                        Frame 3
         WATERBOX DESCRIPTION
                                         Standard                           Standard                       Standard
                                         Nozzles            Flanged         Nozzles            Flanged     Nozzles            Flanged
FRAMES 1, 2, 3; CONDENSER
                                                                                CONDENSER
                                                  Frame 1                            Frame 2                        Frame 3
        WATERBOX DESCRIPTION
                                         Standard                           Standard                       Standard
                                         Nozzles            Flanged         Nozzles         Flanged        Nozzles         Flanged
46
                                 19XR,XRV WATERBOX COVER WEIGHTS — SI (kg) (cont)
                                                 FRAMES 4, 5, 6; COOLER
                                                                                      COOLER
                                                        Frame 4                       Frame 5                       Frame 6
          WATERBOX DESCRIPTION
                                                Standard                     Standard                      Standard
                                                Nozzles       Flanged        Nozzles        Flanged        Nozzles        Flanged
FRAMES 4, 5, 6; CONDENSER
                                                                                  CONDENSER
                                                        Frame 4                       Frame 5                       Frame 6
          WATERBOX DESCRIPTION
                                                Standard      Flanged        Standard       Flanged        Standard       Flanged
                                                Nozzles                      Nozzles                       Nozzles
NIH, 1 Pass Cover, 1034 kPa                        67             84            76              104            85             101
NIH, 2 Pass Cover, 1034 kPa                        87             111           102             135           111             150
NIH, 3 Pass Cover, 1034 kPa                       228             235           285             297           350             382
MWB End Cover and Bolt-on End Cover, 1034 kPa     144             144           178             178           221             221
NIH/MWB Return Cover, 1034 kPa                     63             63             70             70             78             78
NIH, 1 Pass Cover, 2068 kPa                       287             322           347             381           444             478
NIH, 2 Pass Cover, 2068 kPa                       282             331           330             393           419             487
NIH, 3 Pass Cover, 2068 kPa                       297             313           356             376           451             476
NIH/MWB End Cover, 2068 kPa                       237             237           298             298           378             378
    LEGEND                                                        NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the heat
NIH — Nozzle-in-Head                                              exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
                                                                                                                                    47
Physical data (cont)
                                 19XR,XRV WATERBOX COVER WEIGHTS — SI (kg) (cont)
                                              FRAMES 7 AND 8; COOLER
                                                                                       COOLER
                                                                   Frame 7                                 Frame 8
                WATERBOX DESCRIPTION
                                                        Standard             Flanged            Standard             Flanged
                                                        Nozzles                                 Nozzles
                                                                                    CONDENSER
                                                                   Frame 7                                 Frame 8
                WATERBOX DESCRIPTION
                                                        Standard             Flanged            Standard             Flanged
                                                        Nozzles                                 Nozzles
NIH, 1 Pass Cover, 1034 kPa                               149                 200                 189                  224
NIH, 2 Pass Cover, 1034 kPa                               183                 236                 230                  300
NIH, 3 Pass Cover, 1034 kPa                               554                 580                 666                  693
MWB End Cover, 1034 kPa                                   354                 354                 457                  457
Bolt-on MWB End Cover, 1034 kPa                           318                 318                 593                  593
NIH/MWB Return Cover, 1034 kPa                            143                 143                 183                  183
NIH, 1 Pass Cover, 2068 kPa                               767                 840                 901                  976
NIH, 2 Pass Cover, 2068 kPa                               738                 845                 859                 1008
NIH, 3 Pass Cover, 2068 kPa                               777                 831                 904                  958
NIH/MWB End Cover, 2068 kPa                               579                 579                 760                  760
      LEGEND                                                NOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in the heat
NIH — Nozzle-in-Head                                        exchanger weights shown on pages 28-31.
MWB — Marine Waterbox
48
                                 19XR,XRV WATERBOX COVER WEIGHTS — SI (kg) (cont)
                                       TWO-STAGE COMPRESSOR FRAME 6; COOLER FRAME A
                                                                                          COOLER
                                                                                          FRAME A
          WATERBOX DESCRIPTION                     PASSES
                                                                  STANDARD NOZZLES                         FLANGED
          LEGEND                                               NOTES:
ASME — American Society of Mechanical Engineers                 1. Consult factory for 1 and 3 pass data.
MWB — Marine Waterbox                                           2. Weight for dished head cover is included in the heat exchanger
                                                                   weights shown on pages 32-37.
                                                                3. 2 pass weight difference is due to division plate.
                                                                                       CONDENSER
                                                                        FRAME A                            FRAME B
          WATERBOX DESCRIPTION                     PASSES
                                                              STANDARD                           STANDARD
                                                               NOZZLES            FLANGED         NOZZLES            FLANGED
          LEGEND                                               NOTES:
ASME — American Society of Mechanical Engineers                 1. Consult factory for 1 and 3 pass data.
MWB — Marine Waterbox                                           2. Weight for dished head cover is included in the heat exchanger
                                                                   weights shown on pages 32-37.
                                                                3. 2 pass weight difference is due to division plate.
                                                                                                                               49
Physical data (cont)
                                 19XR,XRV WATERBOX COVER WEIGHTS — SI (kg) (cont)
                                 TWO-STAGE COMPRESSOR FRAME 7; COOLER FRAMES B, C
                                                                                      COOLER
                                                                   FRAME B                              FRAME C
          WATERBOX DESCRIPTION                    PASSES
                                                           STANDARD                           STANDARD
                                                            NOZZLES         FLANGED            NOZZLES           FLANGED
          LEGEND                                              NOTES:
ASME — American Society of Mechanical Engineers                1. Consult factory for 1 and 3 pass data.
MWB — Marine Waterbox                                          2. Weight for dished head cover is included in the heat exchanger
                                                                  weights shown on pages 32-37.
                                                               3. 2 pass weight difference is due to division plate.
                                                                                    CONDENSER
                                                                   FRAME C                              FRAME D
          WATERBOX DESCRIPTION                    PASSES
                                                           STANDARD                           STANDARD
                                                                            FLANGED                              FLANGED
                                                            NOZZLES                            NOZZLES
Dished Head, 150 psi                                1        626                726               839                  920
MWB End Cover, 150 psi                              1        620                620               832                  832
MWB End Cover (ASME), 300 psi                       1       1651               1651             2353                 2353
Dished Head, 150 psig                               2        721                870               942                1091
Dished Head (Return Cover), 150 psig                2        620                620               833                  833
MWB End Cover, 150 psig                             2        679                679               902                  902
MWB (Return Cover), 150 psi                         2        620                620               833                  833
MWB End Cover (ASME), 300 psig                      2       1651               1651             2381                 2381
MWB (Return Cover) (ASME), 300 psig                 2       1651               1651             2381                 2381
Dished Head, 150 psi                                3        687                731               920                  964
MWB End Cover, 150 psig                             3        677                677               904                  904
MWB End Cover (ASME), 300 psig                      3       1651               1651             2381                 2381
          LEGEND                                              NOTES:
ASME — American Society of Mechanical Engineers                1. Consult factory for 1 and 3 pass data.
MWB — Marine Waterbox                                          2. Weight for dished head cover is included in the heat exchanger
                                                                  weights shown on pages 32-37.
                                                               3. 2 pass weight difference is due to division plate.
50
Options and accessories
                                                                                                                     OPTION  ACCESSORY
                                                       ITEM                                                        (FACTORY     (FIELD
                                                                                                                  INSTALLED) INSTALLED)
Unit-Mounted Variable Frequency Drive (Available for Low Voltage Only)                                                 X
Free-Standing Low Voltage Variable Frequency Drive                                                                                 X
Free-Standing Medium Voltage Variable Frequency Drive                                                                              X
Free-Standing Starter                                                                                                  X
Unit-Mounted Low-Voltage Wye-Delta or Solid-State Starters
                                                                                                                        X
(Available on Heat Exchanger Frame Sizes 1 to 7 Only)
Shipped Factory Charged with Refrigerant (can be shipped separate)                                                      X
One, 2, or 3 Pass Cooler or Condenser Water-side Construction                                                           X
Hot Gas Bypass                                                                                                          X
Thermal Insulation (Except Waterbox Covers)                                                                             X
Nozzle-in Head Waterbox, 300 psig (2068 kPa)                                                                            X
Marine Waterboxes, 150 psig (1034 kPa)*                                                                                 X
Marine Waterboxes, 300 psig (2068 kPa), ASME Certified*                                                                 X
Marine Bolt-on Waterboxes for Condenser, 150 psig (1034 kPa) with Titanium-Clad Tubesheets                              X
(Available on Condenser Frame Sizes 4 to 8 Only)
Flanged Cooler and/or Condenser Waterbox Nozzles†                                                                       X
Waterbox Hinges                                                                                                         X
Zinc Anodes                                                                                                             X
0.028 or 0.035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Copper Tubing — Cooler/Condenser                  X
0.028 or 0.035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Copper Tubing —                                  X
Cooler/Condenser
0.028 or 0.035 in. (0.711 or 0.889 mm) Smooth Bore/Externally Enhanced Cupronickel Tubing —
                                                                                                                        X
Cooler/Condenser
0.028 or 0.035 in. (0.711 or 0.889 mm) Internally/Externally Enhanced Cupronickel Tubing —
Cooler/Condenser                                                                                                        X
0.025 or 0.028 in. (0.635 or 0.711 mm) Wall Tubes, Titanium, Internally Enhanced — Condenser                            X
Export Crating                                                                                                          X
Customer Factory Performance Testing                                                                                    X
Extended Warranty (North America only)                                                                                  X
Service Contract                                                                                                        X
Refrigerant Isolation Valves                                                                                            X
Unit-Mounted Pumpout Unit (Available on Heat Exchanger Frames Sizes 2 to 5, E Only)                                     X
Seismic Kit (Select Models)                                                                                             X
Stand-Alone Pumpout Unit                                                                                                                X
Separate Storage Tank and Pumpout Unit                                                                                                  X
Soleplate Package                                                                                                                       X
Multiple Chiller System Remote Temperature Sensor                                                                                       X
BACnet** Communication Option (Compressor Frames 2 to 5, E, BACnet over MS/TP)                                          X
BACnet** Communication Option (Compressor Frames 6 and 7)                                                               X
BACnet** Carrier Translator (Compressor Frames 2 to 5, E)                                                                               X
LonWorks†† Carrier Translator (Compressor Frames 2 to 5, E)                                                                             X
Discharge Line Sound Reduction Kit (Compressor Frames 2 to 5, E)                                                                        X
Acoustical Sound Insulation Kit (Compressor Frames 2 to 5, E)                                                                           X
Spring Isolator Kit                                                                                                                     X
*Optional marine waterboxes are available for 19XR heat exchanger        NOTE: The BACnet option for 19XR Compressor Frames 6 and 7 (PIC
frames 2-8 and 19XR two-stage compressors frame sizes 6 and 7, heat      5 controls) provides BACnet over IP communication only. This option
exchanger frame sizes A, B, C, and D. Standard waterboxes for both       disables CCN communication and i-Vu® considers this option to be a
19XR and 19XRV chillers are nozzle-in-head type, 150 psig (1034 kPa).    third-party device. For higher levels of integration, contact your local
†Standard waterbox nozzles are Victaulic type. Flanged nozzles are       Carrier Controls office.
available as an option with either nozzle-in-head type waterboxes or
marine waterboxes.
**BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating, and Air-Conditioning Engineers) (English units
of measure only).
††LonWorks is a registered trademark of Echelon Corporation.
                                                                                                                                             51
Options and accessories (cont)
                               UNIT-MOUNTED STARTER AND VFD FEATURES AND OPTIONS*
                                    ITEM                                WYE-DELTA               SOLID STATE                 VFD
ISM                                                                         S                       N/A                      S
Branch Oil Pump Circuit Breaker                                             S                        S                       S
Controls/Oil Heater Transformer with Branch Circuit Breaker                 S                        S                       S
Microprocessor Based Overload Trip Protection                               S                        S                       S
Main Power Disconnect (Non-Fused Type)                                      S                       N/A                     N/A
Main Power Circuit Breaker                                                 N/A                       S                       S
High Interrupt Capacity Main Circuit Breaker                                O                        O                       O
Phase Loss/Reversal Imbalance Protection                                    S                        S                       S
Three Phase Ground Fault Protection†                                        O                        O                       S
Integral SCR Bypass Contactor                                              N/A                       S                      N/A
Three-Phase Ammeter                                                         O                        O                      N/A
Three-Phase Voltmeter                                                       O                        O                      N/A
Three-Phase Over/Under Voltage Protection                                   S                        S                       S
Power Factor Digital Display                                                S                        S                       S
Frequency Digital Display                                                   S                        S                       S
Digital Watt Display                                                        O                        O                       O
Digital Watt Hour Display                                                   O                        O                       O
Digital Power Factor Display                                                O                        O                       O
Demand Kilowatt Display                                                     O                        O                       O
Lightning Arrestor and Surge Capacitor Package                              O                        O                      N/A
Power Factor Correction Capacitors                                          O                        O                      N/A
         LEGEND                                               *For free-standing starters, refer to the E-CAT Free Standing Starters
ISM —   Integrated Starter Module                             builder software. Refer to the E-CAT Chiller builder software for all VFD
N/A —   Not Applicable                                        options, as some options may not be available for all VFD models.
O   —   Optional                                              †Low voltage: phase to phase and phase to ground. Medium voltage:
S   —   Standard Feature                                      phase to phase and phase to ground.
SCR —   Silicon Control Rectifier
VFD —   Variable Frequency Drive
52
Dimensions
                                               19XR,XRV DIMENSIONS (Nozzle-in-Head Waterbox)
                                                                                                                                                                                  53
Dimensions (cont)
19XR,XRV DIMENSIONS
                                                                                                                                                         2' MIN
                                                A                                                                                                      (610 mm)
                                                                                                                                        NOTE: Nozzle-in-head
                                                                                                    2'-6" MIN                           (NIH) waterbox shown.
                                                                                                    (762 mm)
                                               SERVICE AREA
54
           19XR DIMENSIONS — TWO-STAGE COMPRESSOR FRAME SIZES 6 AND 7 (Dished Head Waterbox)
    COOLER              CONDENSER                              A (Length, Dished Head Waterbox)                                           19XR
     HEAT                  HEAT                       1-Pass                 2-Pass             3-Pass                                  B WIDTH               19XR
  EXCHANGER             EXCHANGER                                                                                                                           C HEIGHT
     SIZE                  SIZE                ft-in.          mm         ft-in.            mm        ft-in.         mm            ft-in.          mm
      A4*                   A4*               17- 8            5385     17- 63/4            5353    17- 63/4         5353        10- 31/8         3127
        A6*                   A6*             19- 8            5994     19- 63/4            5962    19- 63/4         5962        10- 31/8         3127
        A4*                   B4*             17- 8            5385     17-   73/   8       5369    17-   73 /   8   5369        10- 81/2         3264
        A6*                   B6*             19- 8            5994     19- 73/8            5978    19- 73/8         5978        10- 81/2         3264
                                                                                                                                                               See
        B6*                   C6*             20- 0            6096     19- 111/8           6074    19- 9            6120        12- 05/8         3674
                                                                                                                                                              Note 6
        B8*                   C8*             22- 0            6096     21-   111/      8   6684    21- 9            6629        12-    51/   2   3797
        C6*                   C6*             20- 41/4         6204     19- 111/8           6074    19- 113/4        6090        12- 51/2         3797
        C6*                   D6*             20- 41/4         6204     20- 0               6096    20- 01/2         6109        13- 2            4013
        C8*                   D8*             20- 0            6096     21- 111/8           6684    21- 9            6629        13- 2            4013
*Assumes both cooler and condenser nozzles on same end of chiller.                           3. Dimensions are approximate. Certified drawings available upon request.
NOTES:                                                                                       4. ‘A’ length dimensions shown are for standard 150 psig (1034 kPa) design and
 1. Service access should be provided per American Society of Heating, Refrig-                  flanged connections.
    erating, and Air-Conditioning Engineers (ASHRAE) 15, latest edition, National            5. Table contains heat exchanger dimensions for largest type shown.
    Fire Protection Association (NFPA) 70, and local safety code.                            6. 19XR heights can vary depending on the configuration. Check 19XR certified
 2. Allow at least 5 ft (1524 mm) overhead clearance for service rigging.                       drawings for height information.
                                                                 MOTOR SERVICE
                                                                 CLEARANCE
                                                                 6’ (1829 mm)
                                                                                             FRAME 6 COMPRESSOR 5’-0” (1524 MM)
                CLEARANCE FOR
                                                                                             FRAME 7 COMPRESSOR 6’-4” (1900 MM)
                 TUBE REMOVAL
                                                                                             RECOMMENDED OVERHEAD SERVICE CLEARANCE
                     SPACE FOR
                    EITHER END
                                                                                                                                                          3'-8" MIN
                                                  A                                                                                                      (1118 mm)
                                                                                                                                    B               FRAME 6 COMPRESSOR
                                                                                                     2'-11" MIN                                           4'-1" MIN
                                                                                                     (889 mm)                                            (1245 mm)
                                                                                                                                                    FRAME 7 COMPRESSOR
SERVICE AREA
                                                                                                                                                                       55
Dimensions (cont)
         19XR DIMENSIONS — TWO-STAGE COMPRESSOR FRAME SIZES 6 AND 7 (150 psig Marine Waterbox)
    COOLER             CONDENSER                                 A (LENGTH, MARINE WATERBOX)                                                           19XR
     HEAT                 HEAT                        1-Pass                 2-Pass          3-Pass                                                  B WIDTH             19XR
  EXCHANGER            EXCHANGER                                                                                                                                       C HEIGHT
     SIZE                 SIZE                ft-in.             mm        ft-in.              mm          ft-in.               mm          ft-in.             mm
      A4*                  A4*               23- 13/4            7055    21- 81/2             6617        20- 11               6375    10- 63/8                3210
        A6*                  A6*             25- 13/4            7665    23- 81/2             7226        22- 11               6985    10- 63/8                3210
        A4*                  B4*             23-   13/      4    7055    22-    13 /    4     6750        21-   13/     4      6446    11- 01/8                3356
        A6*                  B6*             25- 13/4            7665    24- 13/4             7360        23- 13/4             7055    11- 01/8                3356
                                                                                                                                                                          See
        B6*                  C6*             26- 63/4            8097    25- 21/2             7680        24- 23/4             7385    12- 37/8                3756
                                                                                                                                                                         Note 6
        B8*                  C8*             28-   63/      4    8706    27-    21 /    2     8293        26-   23/     4      7994    12-    103/    8        3921
        C6*                  C6*             26- 63/4            8097    25- 47/8             7744        24- 23/4             8097    12- 37/8                3756
        C6*                  D6*             26- 11              8204    25- 71/8             25705       24- 7                7493    13- 65/8                4131
        C8*                  D8*             28- 63/4            8706    27- 21/2             8293        26- 23/4             7994    13- 65/8                4131
*Assumes both cooler and condenser nozzles on same end of chiller.                                  3. Dimensions are approximate. Certified drawings available upon request.
NOTES:                                                                                              4. ‘A’ length dimensions shown are for standard 150 psig (1034 kPa) design and
 1. Service access should be provided per American Society of Heating, Refrig-                         flanged connections.
    erating, and Air-Conditioning Engineers (ASHRAE) 15, latest edition, National                   5. Table contains largest of all configurations of the type shown.
    Fire Protection Association (NFPA) 70, and local safety code.                                   6. 19XR heights can vary depending on the configuration. Check 19XR certified
 2. Allow at least 5 ft (1524 mm) overhead clearance for service rigging.                              drawings for height information.
     19XR DIMENSIONS — TWO-STAGE COMPRESSOR FRAME SIZES 6 AND 7 (300 psig ASME Marine Waterbox)
   COOLER             CONDENSER                                   A (Length, Marine Waterbox)                                                    19XR
    HEAT                 HEAT                      1-Pass                    2-Pass                              3-Pass                        B WIDTH                   19XR
 EXCHANGER            EXCHANGER                                                                                                                                        C HEIGHT
    SIZE                 SIZE                ft-in.             mm        ft-in.              mm          ft-in.               mm       ft-in.                 mm
     A4*                  A4*               21- 51/2            6541     20- 5               6223        19- 51/2             5931    10- 85/8             3267
       A6*                  A6*             23- 51/2            7150     22- 5               6833        21- 51/2             6541    10- 85/8             3267
       A4*                  B4*             21-   51/   2       6541     20-   7 1 /2        6287        19-   5 1 /2         5931    11- 23/8             3413
       A6*                  B6*             23- 51/2            7150     22- 71/2            6287        21- 51/2             6541    11- 27/8             3426
                                                                                                                                                                         See
       B6*                  C6*             24- 53/4            7462     23- 13/4            7055        22- 13/4             6750    12- 61/8             3813         Note 6
       C6*                  C6*             24-   53/   4       7462     23-   2 1 /2        7074        22-   1 3 /4         6750    13-   0 7 /8         3884
       B8*                  C8*             26- 53/4            8071     25- 13/4            7664        24- 13/4             7360    12- 61/8             3813
       C6*                  D6*             24- 73/4            7512     23- 31/2            7099        22- 33/4             6801    13- 91/2             4204
       C8*                  D8*             26- 53/4            8071     25- 13/4            7664        24- 13/4             7360    13- 91/2             4204
*Assumes both cooler and condenser nozzles on same end of chiller.                                  3. Dimensions are approximate. Certified drawings available upon request.
NOTES:                                                                                              4. ‘A’ length dimensions shown are for standard 150 psig (1034 kPa) design and
 1. Service access should be provided per American Society of Heating, Refrig-                         flanged connections.
    erating, and Air-Conditioning Engineers (ASHRAE) 15, latest edition, National                   5. Table contains largest of all configurations of the type shown.
    Fire Protection Association (NFPA) 70, and local safety code.                                   6. 19XR heights can vary depending on the configuration. Check 19XR certified
 2. Allow at least 5 ft (1524 mm) overhead clearance for service rigging.                              drawings for height information.
                                                                               NOZZLE SIZE
                                                                                                NOZZLE SIZE (in.)
HEAT EXCHANGER                                                                                 (Nominal Pipe Size)
  FRAME SIZE                                                    Cooler                                                                      Condenser
                                   1-Pass                       2-Pass                      3-Pass                          1-Pass           2-Pass                   3-Pass
           1                          8                            6                           6                               8                6                        6
           2                         10                            8                           6                              10                8                        6
           3                         10                            8                           6                              10                8                        6
           4                         10                            8                           6                              10                8                        6
           5                         10                            8                           6                              10               10                        8
           6                         10                           10                           8                              10               10                        8
           7                         14                           12                          10                              14               12                       12
           8                         14                           14                          12                              14               18                       12
           A                         20                           16                          12                              20               16                       14
           B                         20                           18                          14                              20               18                       14
           C                         20                           18                          14                              24               20                       16
           D                         —                            —                           —                               24               20                       16
56
Selection procedure
Compressor motor controllers                                                         Capacitors/power factors
Compressor motors, as well as controls and accessories,                              Power factor considerations may indicate use of capaci-
require the use of starting equipment systems specifically                           tors. Properly sized capacitors improve power factors, es-
designed for 19XR or 19XRV chillers. Consult your local                              pecially at part load. The 19XR,XRV Computer Selection
Carrier representative regarding design information for the                          program can select the proper capacitor size required for
selection of starters.                                                               the application.
Electrical data
                                                                      AUXILIARY RATINGS
                                                                           (Oil Pump)
                                                                      (3 Phase, 50/60 Hz)
                                                          MIN/MAX
                            AVERAGE                        MOTOR                                                                         INRUSH
        ITEM                                                                          FLA            LRA          SEALED kva
                               kW                    VOLTAGE/FREQUENCY                                                                     kva
                                                           V-Ph-Hz
                                1.35                     200/240-3-60                 5.15           24.5             1.96                9.34
                                1.30                     380/460-3-60                 2.55           13.1             1.86                9.53
      OIL PUMP                  1.37                     507/619-3-60                 2.54           25.0             2.48               24.38
                                1.50                     220/240-3-50                 5.74           28.0             2.29               11.15
                                1.50                     346/440-3-50                 3.07           12.2             2.09                8.30
     LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
                                 —
NOTE:FLA = Sealed kva • 1000/  3 • volts
                          —
LRA = Inrush kva • 1000/  3 • volts
                                                                    AUXILIARY RATINGS
                                                                 (Controls, Oil Sump Heater)
            ITEM                                 POWER SUPPLY                      SEALED kva                      AVERAGE WATTS
          CONTROLS                                  24-vac                            0.2                                 200
                                                                                                                         1500
                                                                                                                 (Frame 2 Compressor)
                                                                                                                         1800
                                                                                                                (Frame 3,4 Compressor)
                                   115 V or 230 V, Single Phase, 50 or 60 Hz           —
                                                                                                                         2200
      OIL SUMP HEATER                                                                                          (Frame 5, E Compressor)
           V-Ph-Hz                                                                                                       1800
                                                                                                                  (Frame 4 SRD Only)
                                                                                                                         3000
                                                                                                                 (Frame 6 Compressor)
                                       380 V, 50 or 60 Hz; 460 V, 50 or 60 Hz          —
                                                                                                                         3500
                                                                                                                 (Frame 7 Compressor)
         LEGEND
SRD — Split Ring Diffuser
NOTES:
 1. Oil sump heater only operates when the compressor is off.
 2. Power to oil heater/controls must be on circuits that can provide continuous
    service when the compressor is disconnected.
                                                                                                                                                  57
Controls
Microprocessor controls                                         • Compressor starter faults
Microprocessor controls provide the safety, interlock, ca-      • Compressor surge protection*
pacity control, and indications necessary to operate the        • Low level ground fault
chiller in a safe and efficient manner.                             Low voltage — phase to phase and phase to ground
                                                                    Medium voltage — phase to phase and phase to ground
Control system                                                  • Cooler freeze protection
The microprocessor control on each Carrier centrifugal
system is factory mounted, wired, and tested to ensure ma-
                                                                Capacity control
chine protection and efficient capacity control. In addition,   • Leaving chilled water control
the program logic ensures proper starting, stopping, and        • Entering chilled water control
recycling of the chiller and provides a communication link      • Ice build control
to the Carrier Comfort Network® (CCN) system.                   • Soft loading control by temperature or load ramping
                                                                • Guide vane actuator module
Features                                                        • Hot gas bypass valve
Control system                                                  • Power (demand) limiter
                                                                • Auto. chilled water reset
• Component test and diagnostic check                           • Variable chiller optimization (VDO) (available on com-
• Programmable recycle allows chiller to recycle at opti-         pressor frame sizes 4 and 5 with diffuser control
  mum loads for decreased operating costs                         enabled)
• Menu-driven keypad interface for status display, set          • Compressor surge prevention control
  point control, and system configuration
• CCN compatible                                                Interlocks
• Primary and secondary status messages                         • Manual/automatic remote start
• Individual start/stop schedules for local and CCN opera-      • Starting/stopping sequence
  tion modes                                                           Pre-lube/post-lube
• Recall of up to 25 alarm/alert messages with diagnostic              Pre-flow/post-flow
  help                                                          • Compressor starter run interlock
• Two-chiller lead/lag with third chiller standby is standard   • Pre-start check of safeties and alerts
• Optional soft stop unloading closes guide vanes to            • Low chilled water (load) recycle
  unload the motor to the configured amperage level             • Monitor/number compressor starts and run hours
  prior to stopping                                             • Manual reset of safeties
• Languages pre-programmed at factory for English and
  Chinese                                                       Indications
• An ILT (international language translator) is available for   • Chiller operating status message
  conversion of extended ASCII characters                       • Power-on
                                                                • Pre-start diagnostic check
Safety cutouts                                                  • Compressor motor amps
• Bearing oil high temperature*                                 • Pre-alarm alert††
• Motor high temperature*†                                      • Alarm
• Refrigerant (condenser) high pressure*†                       • Contact for remote alarm
• Refrigerant (cooler) low temperature*†                        • Safety shutdown messages
• Lube oil low pressure                                         • Elapsed time (hours of operation)
• Compressor (refrigerant) discharge temperature*               • Chiller input kW
• Under voltage**
• Over voltage**                                                *These can be configured by user to provide alert indication at user-
• Oil pump motor overload                                       defined limit.
                                                                †Override protection: Causes compressor to first unload and then, if
• Motor overload†                                               necessary, shut down.
• Motor acceleration time                                       **Will not require manual reset or cause an alarm if auto-restart after
• Intermittent power loss                                       power failure is enabled.
                                                                ††By display code only.
58
Typical piping and wiring
                                   19XR CHILLER WITH FREE-STANDING STARTER OR VFD
a19-2069
VFD OR STARTER
15
                   LEGEND                           NOTES:
                                                     1. Wiring and piping shown are for general point-of-connection only and are not
  1 — Disconnect                                        intended to show details for a specific installation. Certified field wiring and
  2 — Free-standing Compressor Motor Starter            dimensional diagrams are available on request.
      or VFD                                         2. All wiring must comply with applicable codes.
  3 — Compressor Motor Terminal Box                  3. Wiring not shown for optional devices such as:
                                                        • Remote Start/Stop
  4 — Power Panel                                       • Remote Alarms
  5 — Control Panel                                     • Optional Safety Device
  6 — Vents                                             • 4 to 20 mA Resets
                                                        • Optional Remote Sensors
  7 — Pressure Gages                                 4. Oil pump disconnect may be located within the enclosure of Item 2 — Free-
  8 — Chilled Water Pump                                standing Compressor Motor Starter or VFD.
                                                     5. IMPORTANT: Carrier suggests that a structural engineer be consulted if trans-
  9 — Condenser Water Pump                              mission of vibrations from mechanical equipment is of concern.
 10 — Chilled Water Pump Starter                     6. Isolation valves are recommended on the cooler and condenser piping to each
 11 — Condensing Water Pump Starter                     chiller for service.
                                                     7. Operating environment — Chiller should be installed in an indoor environment
 12 — Cooling Tower Fan Starter                         where the ambient temperature is 40 to 104 F (4 to 40 C) with a relative humidity
      (Low Fan, High Fan)                               (non-condensing) of 95% or less. To ensure that electrical components operate
 13 — Disconnect                                        properly, do not locate the chiller in an area exposed to dust, dirt, corrosive
 14 — Oil Pump Disconnect (See Note 4)                  fumes, or excessive heat and humidity.
 15 — Strainers
                 le43r
        Piping
                           le12r
        Control Wiring
                         le14r
        Power Wiring
                                                                                                                                            59
Typical piping and wiring (cont)
                               19XR CHILLER WITH OPTIONAL UNIT-MOUNTED STARTER OR VFD
a19-1597ef
12
                         LEGEND                   NOTES:
                                                   1. Wiring and piping shown are for general point-of-connection only and are not
      1   —
          Disconnect                                  intended to show details for a specific installation. Certified field wiring and
      2   —
          Unit-Mounted Starter or VFD                 dimensional diagrams are available on request.
      3   —
          Control Panel                            2. All wiring must comply with applicable codes.
                                                   3. Wiring not shown for optional devices such as:
      4   —
          Power Panel                                 • Remote Start/Stop
      5   —
          Vents                                       • Remote Alarms
      6   —
          Pressure Gages                              • Optional Safety Device
                                                      • 4 to 20 mA Resets
      7   —
          Chilled Water Pump                          • Optional Remote Sensors
      8   —
          Condenser Water Pump                     4. IMPORTANT: Carrier suggests that a structural engineer be consulted if trans-
                                                      mission of vibrations from mechanical equipment is of concern.
      9   —
          Chilled Water Pump Starter               5. Isolation valves are recommended on the cooler and condenser piping to each
     10   —
          Condensing Water Pump Starter               chiller for service.
     11   —
          Cooling Tower Fan Starter                6. Operating environment — Chiller should be installed in an indoor environment
          (Low Fan, High Fan)                         where the ambient temperature is 40 to 104 F (4 to 40 C) with a relative humidity
                                                      (non-condensing) of 95% or less. To ensure that electrical components operate
     12 — Strainers                                   properly, do not locate the chiller in an area exposed to dust, dirt, corrosive
              Piping                                  fumes, or excessive heat and humidity.
                       le43r
              Control Wiring    le12r
              Power Wiring     le14r
60
Application data
                             19XR,XRV SINGLE-STAGE COMPRESSOR MACHINE FOOTPRINT
a19-1547tf
          19XR,XRV                                                                               DIMENSIONS
       HEAT EXCHANGER                       A                            B                 C               D                      E                  F                  G
             SIZE                    ft-in. mm     ft-in.                     mm ft-in.        mm   ft-in.   mm        ft-in.         mm    ft-in.       mm    ft-in.       mm
              10-12                10- 71/4 3232 4-101/4                     1480 0-1          25 0-35/8      92      1-31/4          382    0-9         229   0-1/2        13
              15-17                12-103/4 3931 4-101/4                     1480 0-1          25   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
              20-22                10-   71 /   4   3232 5-   41 /   4       1632 0-1          25   0-35/   8   92    1-31/   4       382   0-9          229   0-1/2        13
              30-32                12-103/4 3931 5- 41/4                     1632 0             0   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
              35-37                14- 71/4 4451 5- 41/4                     1632 0             0   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
              40-42                12-103/4 3931 6- 0                        1829 0-11/2       38   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
              45-47                14- 71/4 4451 6- 0                        1829 0-11/2       38   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
       50-54, 5A-5C, 5K-5R         12-103/4 3931 6- 51/2                     1968 0- 1/2       13   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
       55-59, 5F-5H, 5T-5Z         14- 71/4 4451 6- 51/2                     1968 0- 1/2       13   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
           60-64, 6K-6R            12-103/4 3931 6- 91/2                     2070 0- 1/2       13   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
           65-69, 6T-6Z            14- 71/4 4451 6- 91/2                     2070 0- 1/2       13   0-35/8      92    1-31/4          382   0-9          229   0-1/2        13
           70-74, 7K-7R            15- 17/8 4620 7-101/2                     2400 0- 1/4        6   0-615/16    176   1-10            559    1-4         406   0-3/4        19
           75-79, 7T-7Z            17- 17/8 5229 7-101/2                     2400 0- 1/4        6   0-615/16    176   1-10            559    1-4         406   0-3/4        19
           80-84, 8K-8R            15- 17/8 4620 8- 93/4                     2686 0-15/16      24   0-615/16    176   1-10            559    1-4         406   0-1/16       2
           85-89, 8T-8Z            17- 17/8 5229 8- 93/4                     2686 0-15/16      24   0-615/16    176   1-10            559    1-4         406   0-1/16       2
 NOTES:
  1. X-X dimension refers to accessory soleplate. See page 63.
  2. Y-Y dimension refers to standard support plate. See page 63.
                                                                                                                                                                                 61
Application data (cont)
                                                                                                                                                                                     F
                                                                                                                                        Y                 Y
                                                                                                                    SUPPORT PLATE
              OUTSIDE EDGE OF
              COOLER TUBESHEET
              (TYPICAL BOTH ENDS)
                                                                                                                   CL
                                                                                                                        COOLER
                                                                                                                                                                                     B
             OUTSIDE EDGE OF
             CONDENSER TUBESHEET
             (TYPICAL BOTH ENDS)
                                                                                                 CL
                                                                                                      VESSELS
                                                                                                                                       E
                                    0'-0 1/2"
                                     [13mm]
                                     TYPICAL                                                               CL
                                                                                                                CONDENSER
X X
                                      0'-3"                                                                                       D
                                    [76mm]                                                                                                                                           G
                                    TYPICAL                                                                                                                   C
                              OPTIONAL
                              SOLEPLATE
            19XR                                                                                        DIMENSIONS
       HEAT EXCHANGER                                    A                   B                   C              D                               E                  F                 G
             SIZE                               ft-in.       mm     ft-in.       mm     ft-in.         mm ft-in. mm                    ft-in.       mm    ft-in.       mm   ft-in.       mm
     COOLER          CONDENSER
                             A4               14- 87/8       4492 10- 01/8       3051 0-47/16          113        1-10           559   1-4          406       —        —     —           —
        A4
                             B4               14-   87 /8    4492 10-   5 3 /8   3177 0-47/16          113        1-10           559   1-4          406       —        —     —           —
                             A6               16- 87/8       5102 10- 01/8       3051 0-47/16          113        1-10           559   1-4          406       —        —     —           —
        A6
                             B6               16- 87/8       5102 10- 53/8       3177 0-47/16          113        1-10           559   1-4          406       —        —     —           —
        B6                   C6               16- 8          5080 11-11          3632 0-4              102        1-10           559   1-4          406       —        —    0-1          25
        B8                   C8               18- 8          5690 11-11          3632 0-4              102        1-10           559   1-4          406       —        —    0-1          25
                             C6               16- 8          5080 12- 41/2       3662 0-4              102        1-10           559   1-4          406       —        —     0-1         25
        C6
                             D6               16- 8          5080 13- 2          4013 0-4              102        1-10           559   1-4          406       —        —     —           —
        C8                   D8               18- 8          5690 13- 2          4013 0-4              102        1-10           559   1-4          406       —        —     —           —
 NOTES:
  1. X-X dimension refers to accessory soleplate. See page 63.
  2. Y-Y dimension refers to standard support plate. See page 63.
62
      19XR,XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE
                                                                                                   COMPRESSOR
                                                                                                   FRAME SIZE 7: 0’-1/2” (13);
                                                                                                   ALL OTHERS: 0’-3/8” (10)
A19-2295
ELASTOMERIC PADS
                                                                              VIEW Y-Y
                                                          ISOLATION WITH STANDARD PACKAGE ONLY
a19-
/LEG
      SOLEPLATE                                                                                     COMPRESSOR
   COMPRESSOR                                                                                       FRAME SIZE 7:
   FRAME SIZE 7:                                                                                    0´-1 3/4˝ (45);
   1 1/4˝ (32) THK;                                                                                 ALL OTHERS: 0´-1 3/8˝ (35);
    ALL OTHERS:                                                                    a19-2275
       1˝ (25) THK.
VIEW X-X
           NOTES:
            1. Dimensions in ( ) are in millimeters.
            2. Accessory (Carrier-supplied, field-installed) soleplate package includes 4 sole-
               plates, 16 jacking screws and leveling pads. Isolation package is also required.
            3. Jacking screws to be removed after grout has set.
            4. Thickness of grout will vary, depending on the amount necessary to level chiller.
               Use only pre-mixed non-shrinking grout, Ceilcote 748 OR Embeco 636 Plus
               Grout, 0-1½ (38.1) to 0-2¼ (57) thick.
                                                                                                                                  63
Application data (cont)
a19-1370tf
FRAMES 1, 2, AND 3
                                                  a19-1548ef
          11               12               9                        6               3             2
                                                                                         CL
               COND CL                                                                      COND
                                COOLER CL                                CL COOLER
                                                    8           5
10 1
7 4
FRAMES 4, 5, AND 6
64
                                            19XR,XRV NOZZLE ARRANGEMENTS (cont)
                                                 NOZZLE-IN-HEAD WATERBOXES (cont)
a19-
1562
tf
FRAMES 7 AND 8
12 3
                                                                                       6
     11                                             9
                                                                     8
                           COND.                                             5                                   COND.
                                                                                                                                    1
     10
                                                  COOLER                                  COOLER
                                                                 7
                                                                         4
              19XR TWO-STAGE COMPRESSORS FRAME SIZES 6 AND 7 (HEAT EXCHANGER FRAMES A, B, C, and D)
                   NOZZLE ARRANGEMENT CODES FOR 19XR TWO-STAGE COMPRESSORS FRAME SIZES 6 AND 7
                                                                                                                                        65
Application data (cont)
a19-1245tf
                                                         FRAMES 2 AND 3†
     †There is no Frame 1 marine waterbox.
                                                   NOZZLE ARRANGEMENT CODES
a19-1246tf
FRAMES 4, 5, AND 6
66
                       19XR,XRV NOZZLE ARRANGEMENTS (cont)
                               MARINE WATERBOXES (cont)
a19-1274tf
                                    FRAMES 7 AND 8
                              NOZZLE ARRANGEMENT CODES
14 4
13 3
                                            10
                                                     7
                                                                                      COND.              2
12         COND.
                                                 9
                           COOLER                    6               COOLER
                                                                                                         1
11
                                                     5
                                             8
a19-2296
                                                                                                             67
Application data (cont)
                                                        RELIEF VALVE LOCATIONS
68
            RELIEF VALVE ARRANGEMENT, TWO-STAGE COMPRESSOR FRAME SIZE 6 (Refer to page 71)
    COOLER HEAT           CONDENSER HEAT              WITH/WITHOUT DISCHARGE                       COOLER      CONDENSER
     EXCHANGER              EXCHANGER                                                 VIEW CODE
     FRAME SIZE*            FRAME SIZE*                   ISOLATION VALVE                         NO. VALVES   NO. VALVES
                                                   With Optional Isolation Valve         G            2            4
                                   A4
                                                   Without Optional Isolation Valve      H            4            4
           A4
                                                   With Optional Isolation Valve         G            2            4
                                   B4
                                                   Without Optional Isolation Valve      H            4            4
                                                   With Optional Isolation Valve         G            2            4
                                   A6
                                                   Without Optional Isolation Valve      H            4            4
           A6
                                                   With Optional Isolation Valve         G            2            4
                                   B6
                                                   Without Optional Isolation Valve      H            4            4
*See page 8 for cooler and condenser size codes.
            RELIEF VALVE ARRANGEMENT, TWO-STAGE COMPRESSOR FRAME SIZE 7 (Refer to page 71)
    COOLER HEAT           CONDENSER HEAT
     EXCHANGER              EXCHANGER                 WITH/WITHOUT DISCHARGE          VIEW CODE    COOLER      CONDENSER
                                                          ISOLATION VALVE                         NO. VALVES   NO. VALVES
     FRAME SIZE*            FRAME SIZE*
                                                   With Optional Isolation Valve          I           2            6
           B6                      C6
                                                   Without Optional Isolation Valve       J           4            6
                                                   With Optional Isolation Valve          I           2            6
           B8                      C8
                                                   Without Optional Isolation Valve       J           4            6
                                                   With Optional Isolation Valve          I           2            6
                                   C6
                                                   Without Optional Isolation Valve       J           4            6
           C6
                                                   With Optional Isolation Valve          I           2            6
                                   D6
                                                   Without Optional Isolation Valve       J           4            6
                                                   With Optional Isolation Valve          I           3            6
           C8                      D8
                                                   Without Optional Isolation Valve       J           6            6
*See page 8 for cooler and condenser size codes.
                                                                                                                        69
Application data (cont)
a19-1497ef a19-1496ef
A B
a19-1498ef a19-1499ef
                                         C                                       D
                                    FRAME 1-6                                FRAME 7, 8
CONDENSER
CONDENSER
COOLER COOLER
                                                                                                   a19-1501ef
 a19-1500ef
E F
70
                                       RELIEF VALVE ARRANGEMENTS (cont)
                                                                                                     a19-2084
a19-2085
CONDENSER CONDENSER
              COOLER
                                                                     COOLER
a19-2272 a19-2273
                                                                                                                71
Application data (cont)
Vent and drain connections                                      ASME stamping
Nozzle-in-head waterboxes have vent and drain connec-           All 19XR,XRV heat exchangers are constructed in accor-
tions on covers. Marine waterboxes have vent and drain          dance with ASHRAE (American Society of Heating, Refrig-
connections on waterbox shells.                                 erating, and Air-Conditioning Engineers) 15 Safety Code for
  Provide high points of the chiller piping system with vents   Mechanical Refrigeration (latest edition). This code, in turn,
and the low points with drains. If shutoff valves are provid-   requires conformance with ASME (American Society of Me-
ed in the main water pipes near the unit, a minimal             chanical Engineers) Code for Unfired Pressure Vessels wher-
amount of system water is lost when the heat exchangers         ever applicable.
are drained. This reduces the time required for drainage          Each vessel is constructed and certified in accordance
and saves on the cost of re-treating the system water.          with ASME Section 8, Division 1.
  It is recommended that pressure gages be provided at          Relief valve discharge pipe sizing
points of entering and leaving water to measure pressure
drop through the heat exchanger. Gages may be installed         See pages 68 and 69 for number of relief valves and locations.
as shown in Pressure Gage Location table. Pressure gages           Relief-valve discharge piping size should be calculated per
installed at the vent and drain connections do not include      ASHRAE 15, latest edition, code using the tabulated C fac-
nozzle pressure losses.                                         tors for each vessel shown in the tables on pages 73 and 74.
  Use a reliable differential pressure gage to measure pres-      Carrier further recommends that an oxygen sensor be in-
sure differential when determining water flow. Regular gages    stalled to protect personnel. Sensor should be able to sense
of the required pressure range do not have the accuracy to      the depletion or displacement of oxygen in the machine
provide accurate measurement of flow conditions.                room below 19.5% volume oxygen per ASHRAE 15, lat-
               PRESSURE GAGE LOCATION                           est edition.
     NUMBER
                              GAGE LOCATION
       OF
     PASSES                 (Cooler or Condenser)
      1 or 3      One gage in each waterbox
        2         Two gages in waterbox with nozzles
72
 19XR,XRV RELIEF VALVE DISCHARGE PIPE SIZING, SINGLE-STAGE COMPRESSORS AND TWO-STAGE
                              COMPRESSORS FRAME SIZE E
                                              VESSEL         RELIEF VALVE     FIELD CONNECTION SIZE
HEAT EXCHANGER        FRAME SIZE        REQUIRED C FACTOR   RATED C FACTOR
                                            (lb air/Min)       (lb air/Min)           (FPT)
                        10 to 12                30.0                48.4               1
                        15 to 17                36.0                48.4               1
                        20 to 22                35.7                48.4               1
                        30 to 32                43.8                72.1              11/4
                        35 to 37                49.9                72.1              11/4
                        40 to 42                50.4                72.1              11/4
                        45 to 47                57.4                72.1              11/4
                        50 to 54,
                                               53.7               72.1                11/4
                     5A-5C, 5K-5R
                        55 to 59,
                      5F-5H, 5T-5Z             61.1               72.1                11/4
   COOLER
                        60 to 64,              57.0               72.1                11/4
                        6K to 6R
                        65 to 69,
                                               64.9               72.1                11/4
                        6T to 6Z
                        70 to 74,
                        7K to 7R               77.0              144.2                11/4
                        75 to 79,              88.0              144.2                11/4
                        7T to 7Z
                        80 to 84,
                                               87.7              144.2                11/4
                        8K to 8R
                        85 to 89.
                        8T to 8Z              100.3              144.2                11/4
                        10 to 12               31.7               48.4                 1
                        15 to 17               38.0               48.4                 1
                        20 to 22               34.0               48.4                 1
                        30 to 32               41.8               72.1                11/4
                        35 to 37               47.6               72.1                11/4
                        40 to 42               47.1               72.1                11/4
                        45 to 47               53.7               72.1                11/4
                        50 to 54               51.2               72.1                11/4
                        55 to 59               58.3               72.1                11/4
                        60 to 64               55.3               72.1                11/4
                        65 to 69               63.0               72.1                11/4
                        70 to 74
                                               72.3              144.2                11/4
  CONDENSER        Compressor Frame 5
                        75 to 79
                   Compressor Frame 5          82.7              144.2                11/4
                        80 to 84               80.7              144.2                11/4
                   Compressor Frame 5
                        85 to 89
                                               92.3              144.2                11/4
                   Compressor Frame 5
                        70 to 74
                   Compressor Frame E          88.3              144.2                11/4
                        75 to 79               98.7              144.2                11/4
                   Compressor Frame E
                        80 to 84
                                               96.7              144.2                11/4
                   Compressor Frame E
                        85 to 89
                   Compressor Frame E         108.3              144.2                11/4
                                                                                                 73
 Application data (cont)
         19XR RELIEF VALVE DISCHARGE PIPE SIZING, TWO-STAGE COMPRESSORS FRAME SIZE 6 AND 7
*The condenser discharge required C factor is the combined values of the condenser, high-side float, and economizer.
Design pressures
Design and test pressures for heat exchangers are listed below.
                                              DESIGN AND MINIMUM TEST PRESSURES
                                                                  SHELL SIDE            STANDARD TUBE SIDE             OPTIONAL TUBE SIDE
       VESSEL                       PRESSURES                     (Refrigerant)                (Water)                       (Water)
                                                                 psig       kPa           psig         kPa              psig         kPa
                        Design                                   185       1276           150          1034             300          2068
                        Leak Test (min)                          185       1276           150          1034             300          2068
Cooler
                        Hydrostatic Test                          —          —            195          1344             390          2690
                        Proof Test (min Pneumatic)               204       1407            —            —                —            —
                        Design                                   185       1276           150          1034             300          2068
                        Leak Test (min)                          185       1276           150          1034             300          2068
Condenser
                        Hydrostatic Test                          —          —            195          1344             390          2690
                        Proof Test (min Pneumatic)               204       1407            —            —                —            —
                        Design                                   185       1276            —            —                —            —
Economizer              Leak Test (min)                          185       1276            —            —                —            —
Frame Size E            Hydrostatic Test                          —          —             —            —                —            —
                        Proof Test (min Pneumatic)               204       1407            —            —                —            —
                        Design                                   185       1276            —            —                —            —
Economizer,             Leak Test (min)                          185       1276            —            —                —            —
Frame Sizes 6 and 7     Hydrostatic Test                          —          —             —            —                —            —
                        Proof Test (min Pneumatic)               204       1407            —            —                —            —
74
                                       HEAT EXCHANGER MATERIAL SPECIFICATIONS
                   ITEM                                  MATERIAL                                SPECIFICATION
Shell                                                     HR Steel             ASME SA516 GR .70
Tube Sheet                                                HR Steel             ASME SA516 GR .70
Flat Covers                                               HR Steel             ASME/ASTM A516 GR.70
Pipe                                                       Steel               ASME SA106 GRB/SA53 E/B
Flanges                                                    Steel               ASME B16.5
Condenser Float Box Shell                                  Steel               ASME SA53 E/B
Tubes                                               Per Job Requirement        ASME SB359
Dished Cover                                              HR Steel             ASTM A516 GR.70/GB713 Q345R
Marine Water Box Shell                                    HR Steel             ASME/ASTM A516 GR.70
                                                                                                                               INSULATION†
                                                                             CHILLER           COOLER FRAME SIZE
                                                                                                                                ft2     m2
                                                                              19XR             A40-A47 and A4A-A4H             434     40.3
                                                                            Two-Stage
                                                                                               A60-A67 and A6A-A6H             462         42.9
                                                                           Frame Size 6
                                                                                               B60-B67 and B6A-B6H             666         61.9
                                                                              19XR            B80-B87 and B8A to B8H           699         64.9
                                                                            Two-Stage
                                                                           Frame Size 7        C60-C67 and C6A-C6H             694         64.9
                                                                                               C80-C87 and C6A-C6H             732         68.0
                                                                                                                                                  75
 Application data (cont)
Insulation at jobsite — As indicated in the Condensa-                  CONDENSATION VS. RELATIVE HUMIDITY*
tion vs. Relative Humidity table, the factory insulation pro-
                                                                                                  ROOM DRY-BULB TEMP
vides excellent protection against condensation under most          AMOUNT OF
                                                                                         80 F (27 C)   90 F (32 C)    100 F (38 C)
operating conditions. If temperatures in the equipment             CONDENSATION
                                                                                                    % Relative Humidity
area exceed the maximum design conditions, extra insula-
                                                                 None                        80             76             70
tion is recommended.                                             Slight                      87             84             77
   If the machine is to be field insulated, obtain the approx-   Extensive                   94             91             84
imate areas from the Minimum Field-Installed Insulation          *These approximate figures are based on 35 F (1.7 C) saturated suction
Requirements table.                                               temperature. A 2° F (1.1° C) change in saturated suction temperature
                                                                  changes the relative humidity values by 1% in the same direction.
   Insulation of waterbox is made only in the field and this
area is not included in Minimum Field-Installed Insulation       Unit location — Chiller should be installed in an indoor
Requirements table. When insulating the covers, allow for        environment where the ambient temperature is 40 to 104 F
service access and removal of covers. To estimate water-         (4 to 40 C) with a relative humidity (non-condensing) of 95%
box cover areas refer to certified drawings.                     or less. To ensure that electrical components operate prop-
   High humidity jobsite locations may require field sup-        erly, do not locate the chiller in an area exposed to dust, dirt,
plied and installed insulation on the float chamber, suction     corrosive fumes, or excessive heat and humidity.
housing, and the lower half of the condenser.
76
                      19XR,XRV FACTORY-INSTALLED INSULATION AREA (cont)
                                  TWO-STAGE CHILLER FRAME E
TOP VIEW
COND. COND.
COOLER COOLER
                                                                                                  77
Application data (cont)
TOP VIEW
COND. COND.
COOLER COOLER
78
Guide specifications
Packaged Semi-Hermetic Centrifugal Liquid                         F. Entire chiller assembly shall be proof tested at 204 psig
Chiller                                                               (1406 kPa) and leak tested at 185 psig (1276 kPa)
                                                                      with a tracer gas mixture on the refrigerant side. The
HVAC Guide Specifications — 19XR, XRV                                 water side of each heat exchanger shall be hydrostati-
Size Range:                                                           cally tested at 1.3 times rated working pressure.
   19XR,XRV — 200 to 3000 Tons (703 to                           G. Prior to shipment, the chiller automated controls
   10551 kW) Nominal                                                  test shall be executed to check for proper wiring and
Carrier Model Number:                                                 ensure correct controls operation.
  19XR,XRV                                                       H. On chillers with unit-mounted compressor motor
                                                                      starter or VFD (variable frequency drive), the chiller
Part 1 — General                                                      and starter/VFD shall be factory wired and tested
1.01 SYSTEM DESCRIPTION                                               together to verify proper operation prior to shipment.
   A. Microprocessor-controlled liquid chiller shall use a         I. The management system governing the manufacture
      semi-hermetic centrifugal compressor using refriger-            of this chiller shall be ISO 9001:2008 certified.
      ant HFC-134a.                                            1.03 DELIVERY, STORAGE AND HANDLING
   B. If a manufacturer proposes a liquid chiller using          A. Unit shall be stored and handled in accordance with
      HCFC-123 refrigerant, then the manufacturer shall               manufacturer's instructions.
      include in the chiller price:
                                                                 B. Unit shall be shipped with all refrigerant piping and
        1. A vapor activated alarm system shall be capable            control wiring factory installed.
            of responding to HCFC-123 levels of 10 ppm
            Allowable Exposure Limit (AEL).                      C. Unit shall be shipped charged with oil and full
                                                                      charge of refrigerant HFC-134a or a nitrogen hold-
        2. External refrigerant storage tank and pumpout              ing charge as specified on the equipment schedule.
            unit.
                                                                 D. Unit shall be shipped with firmly attached labels that
        3. Zero emission purge unit capable of operating              indicate name of manufacturer, chiller model num-
            even when the chiller is not operating.                   ber, chiller serial number, and refrigerant used.
        4. Back-up relief valve to rupture disk.                  E. If the chiller is to be exported, the unit shall be suffi-
        5. Chiller pressurizing system to prevent leakage             ciently protected from the factory against sea water
            of noncondensables into chiller during shut-              corrosion to be suitable for shipment in a standard
            down periods.                                             open top, ocean shipping container (19XR,XRV
        6. Plant room ventilation.                                    heat exchanger frames 1 through 6 only).
1.02 QUALITY ASSURANCE                                         1.04 WARRANTY
   A. Chiller performance shall be rated in accordance                Warranty shall include parts and labor for one year
      with AHRI (Air-Conditioning, Heating and Refriger-              after start-up or 18 months from shipment, which-
      ation Institute) Standard 550/590, latest edition.              ever occurs first.
   B. Equipment and installation shall be in compliance        Part 2 — Products
      with ANSI/ASHRAE (American National Standards            2.01 EQUIPMENT
      Institute/American Society of Heating, Refrigerating       A. General:
      and Air-Conditioning Engineers) 15 (latest edition).
                                                                      Factory assembled, single piece, liquid chiller shall
   C. Cooler and condenser refrigerant side shall include             consist of compressor, motor, starter or variable fre-
      ASME “U” stamp and nameplate certifying compli-                 quency drive, lubrication system, cooler, condenser,
      ance with ASME Section VIII, Division 1 code for                initial oil and refrigerant operating charges, micro-
      unfired pressure vessels.                                       processor control system, and documentation
   D. Chiller shall be designed and constructed to meet               required prior to start-up. An optional compressor
      UL (Underwriters Laboratories) and UL, Canada                   motor starter or VFD can be mounted on the chiller,
      requirements and have labels appropriately affixed.             wired, and tested by the chiller manufacturer (select
   E. Centrifugal compressor impellers shall be dynami-               models). Or, an optional free-standing medium volt-
      cally balanced and over-speed tested by the manu-               age starter or VFD can be wired and tested by the
      facturer at a minimum of 120% design operating                  chiller manufacturer.
      speed. Each compressor assembly shall undergo a            B. Compressor:
      mechanical run-in test to verify vibration levels, oil
                                                                        1. One high performance centrifugal compressor.
      pressures, and temperatures are within acceptable
      limits.                                                           2. Compressor, motor, and transmission shall be
                                                                            semi-hermetically sealed into a common assem-
      Each compressor assembly shall be proof tested at a
                                                                            bly and arranged for easy field servicing.
      minimum 204 psig (1406 kPa) and leak tested at
      185 psig (1276 kPa) with a tracer gas mixture.                    3. Internal compressor parts must be accessible
                                                                            for servicing without removing the compressor
                                                                            base from the chiller. Connections to the
                                                                                                                           79
Guide specifications (cont)
        compressor casing shall use O-rings instead of             a. An oil reservoir shall collect oil and refriger-
        gaskets to reduce the occurrence of refrigerant                ant that leaks past the seal.
        leakage. Connections to the compressor shall               b. A float device shall be provided to open when
        be flanged or bolted for easy disassembly.                     the reservoir is full, directing the refrigerant/
     4. All pressure transducers shall have quick discon-              oil mixture back into the compressor housing.
        nects to allow replacement of the sensor with-             c. A refrigerant sensor shall be located next to
        out replacement of the entire sensor wire.                     the open drive seal to detect leaks.
        Pressure transducers shall be capable of field
                                                              3.   Motors shall be suitable for operation in a
        calibration to ensure accurate readings and to
                                                                   refrigerant atmosphere and shall be cooled by
        avoid unnecessary transducer replacement.
                                                                   atomized refrigerant in contact with the motor
        Pressure transducers and temperature sensors
                                                                   windings.
        shall be serviceable without the need for refrig-
        erant charge removal or isolation.                    4.   Motor stator shall be arranged for service or
                                                                   removal with only minor compressor disassem-
     5. Transmission shall be helical, parallel shaft
                                                                   bly and without removing main refrigerant pip-
        speed increaser. Gears shall conform to AGMA
                                                                   ing connections.
        2001-B88, Class 11.
                                                              5.   Full load operation of the motor shall not exceed
     6. Journal bearings shall be of the steel backed
                                                                   nameplate rating.
        babbitt lined type. Aluminum journal bearings
        are not acceptable. The thrust bearing shall be       6.   At least one motor winding temperature sensor
        tilting pad or rolling element type.                       (and one spare) shall be provided.
     7. Centrifugal compressors shall use variable inlet      7.   Should the mechanical contractor choose to
        guide vanes to provide capacity modulation                 provide a chiller with an open motor instead of
        while also providing pre-whirl of the refrigerant          the specified semi-hermetic motor, the contrac-
        vapor entering the impeller for more efficient             tor shall install additional cooling equipment to
        compression at all loads.                                  dissipate the motor heat as per the following
                                                                   formula:
     8. Centrifugal compressors shall be provided with
        a factory-installed lubrication system to deliver                Btuh = (FLkW motor) (0.05) (3413)
        oil under pressure to bearings and transmission.                 Btuh = (FLkW motor) (171)
        Included in the system shall be:                                 and, alternately
        a. Hermetic driven oil pump with factory-installed               Tons = Btuh / 12,000
             motor contactor with overload protection.
                                                                   The additional piping, valves, air-handling equip-
        b. Refrigerant-cooled oil cooler. Water-cooled             ment, insulation, wiring, switchgear changes,
             oil coolers are not acceptable.                       ductwork, and coordination with other trades
        c. Oil pressure regulator.                                 shall be the responsibility of the mechanical con-
        d. Oil filter with isolation valves to allow filter        tractor. Shop drawings reflecting any changes to
             change without removal of refrigerant charge.         the design shall be included in the submittal, and
                                                                   incorporated into the final as-built drawings for
        e. Oil sump heater controlled from unit
                                                                   the project.
             microprocessor.
                                                              8.   Also, if an open motor is provided, a mechani-
        f. Oil reservoir temperature sensor with main
                                                                   cal room thermostat shall be provided and set
             control center digital readout.
                                                                   at 104 F (40 C). If this temperature is
        g. When factory-mounted compressor motor                   exceeded, the chillers shall shut down and an
             starter or VFD is provided, all wiring to oil         alarm signal shall be generated to the central
             pump, oil heater, and controls shall be pre-          Energy Management System (EMS) display
             wired in the factory.                                 module prompting the service personnel to
        h. Compressor shall be fully field serviceable.            diagnose and repair the cause of the overtem-
             Compressors which must be removed and                 perature condition. The mechanical contractor
             returned to the factory for service shall be          shall be responsible for all changes to the
             unacceptable.                                         design, including coordination with temperature
 C. Motor:                                                         control, electrical and other trades. In addition,
                                                                   the electrical power consumption of any auxil-
     1. Compressor motor shall be of the semi- her-
                                                                   iary ventilation and/or mechanical cooling
        metic, liquid refrigerant cooled, squirrel cage,
                                                                   required to maintain the mechanical room con-
        induction type suitable for voltage shown on the
                                                                   ditions stated above shall be considered in the
        equipment schedule.
                                                                   determination of conformance to the scheduled
     2. If an open drive motor is provided, a compres-             chiller energy efficiency requirement.
        sor shaft seal leakage containment system shall
        be provided.
80
D. Cooler and Condenser:                                      E. Refrigerant Flow Control:
    1. Cooler shall be of shell and tube type construc-           1. To maintain optimal part load efficiency, the
       tion, each in separate shells. Units shall be fabri-           refrigerant expansion device to the cooler and
       cated with high-performance tubing, minimum                    as applicable to the economizer, shall use a vari-
       1/ -in. (6-mm) steel shell and tube sheets with                able metering valve, such as a float or actuated
          4
       fabricated steel waterboxes.                                   valve. To ensure good operating performance,
       a. Waterbox shall be nozzle-in-head waterbox                   the valve design will prevent refrigerant gas
           (150 psig [1034 kPa]).                                     from the condenser from passing to the cooler
                                                                      or economizer at full or part load.
       b. Waterbox shall have standard Victaulic
           grooves. For 19XR with Frame 6 or Frame                2. By maintaining a liquid seal at the flow valve,
           7 compressor, the Victaulic AGS grooves                    bypassed hot gas from the condenser to the
           shall be provided for nominal 14-in. pipe                  cooler is eliminated. The float valve chamber shall
           and larger.                                                have a bolted access cover to allow field inspec-
                                                                      tion and the float valve shall be field serviceable.
    2. Condenser shall be of shell and tube type con-
       struction, each in separate shells. Units shall be     F. Controls, Safeties, and Diagnostics:
       fabricated with high-performance tubing, mini-             1. Controls:
       mum 1/4-in. (6-mm) steel shell and tube sheets                 a. The chiller shall be provided with a factory
       with fabricated steel waterboxes.                                  installed and wired microprocessor control
       a. Waterbox shall be nozzle-in-head (150 psig                      center. The microprocessor can be config-
           [1034 kPa]).                                                   ured for either English or SI units.
       b. Waterbox shall have standard Victaulic                      b. All chiller and starter monitoring shall be dis-
           grooves. For 19XR with Frame 6 or Frame                        played at the chiller control panel.
           7 compressor, the Victaulic AGS grooves                    c. The controls shall make use of non-volatile
           shall be provided for nominal 14-in. pipe                      memory.
           and larger.
                                                                      d. The chiller control system shall have the abil-
    3. Waterboxes shall have vents, drains, and covers                    ity to interface and communicate directly to
       to permit tube cleaning within the space shown                     the building control system.
       on the drawings. A thermistor type temperature
                                                                      e. The default standard display screen shall
       sensor with quick connects shall be factory
                                                                          simultaneously indicate the following mini-
       installed in each water nozzle.
                                                                          mum information:
    4. Tubes shall be individually replaceable from
                                                                            1) date and time of day
       either end of the heat exchanger without affect-
                                                                            2) 24-character primary system status
       ing the strength and durability of the tube sheet
                                                                               message
       and without causing leakage in adjacent tubes.
                                                                            3) 24-character secondary status message
    5. Tubing shall be copper, high-efficiency type,                        4) chiller operating hours
       with integral internal and external enhance-                         5) entering chilled water temperature
       ment unless otherwise noted. Tubes shall be                          6) leaving chilled water temperature
       nominal 3/4-in. or 1-in. OD with nominal wall                        7) evaporator refrigerant temperature
       thickness of 0.025 in. measured at the root of                       8) entering condenser water temperature
       the fin at the enhanced areas and nominal wall                       9) leaving condenser water temperature
       thickness of 0.049 in. where the tubes are in                      10) condenser refrigerant temperature
       contact with the end tube sheets unless other-                     11) oil supply pressure
       wise noted. Tubes shall be rolled into tube                        12) oil sump temperature
       sheets and shall be individually replaceable.                      13) percent motor rated load amps (RLA)
       Tube sheet holes shall be double grooved for
                                                                      f. In addition to the default screen, status
       joint structural integrity.
                                                                          screens shall be accessible to view the status
    6. Cooler shall be designed to prevent liquid refrig-                 of every point monitored by the control cen-
       erant from entering the compressor.                                ter including:
    7. The condenser shell shall include a FLASC (flash                     1) evaporator pressure
       subcooler) which cools the condensed liquid                          2) condenser pressure
       refrigerant to a reduced temperature, thereby                        3) bearing oil supply temperature
       increasing the refrigeration cycle efficiency.                       4) compressor discharge temperature
    8. A reseating type pressure relief valve shall be                      5) motor winding temperature
       installed on each heat exchanger. If a non-                          6) number of compressor starts
       reseating type is used, a backup reseating type                      7) control point settings
       shall be installed in series.                                        8) discrete output status of various devices
                                                                                                                      81
Guide specifications (cont)
            9) compressor motor starter status                   l. Chilled Water Reset:
          10) optional spare input channels                         The control center shall allow reset of the
          11) current and voltage for each phase                    chilled water temperature set point based on
          12) frequency                                             any one of the following criteria:
     g.   Schedule Function:                                          1) Chilled water reset based on an external
          The chiller controls shall be configurable for                 4 to 20 mA signal.
          manual or automatic start-up and shutdown. In               2) Chilled water reset based on a remote
          automatic operation mode, the controls shall                   temperature sensor (such as outdoor air).
          be capable of automatically starting and stop-              3) Chilled water reset based on water tem-
          ping the chiller according to a stored user pro-               perature rise across the evaporator.
          grammable occupancy schedule. The controls             m. Demand Limit:
          shall include built-in provisions for accepting:
                                                                    The control center shall limit amp draw of
            1) A minimum of two 365-day occupancy                   the compressor to the rated load amps or to
               schedules.                                           a lower value based on one of the following
            2) Minimum of 8 separate occupied/unoc-                 criteria:
               cupied periods per day.
                                                                      1) Demand limit based on a user input
            3) Daylight savings start/end.
                                                                         ranging from 40% to 100% of compres-
            4) Minimum of 18 user-defined holidays.
                                                                         sor rated load amps.
            5) Means of configuring an occupancy
                                                                      2) Demand limit based on external 4 to
               timed override.
                                                                         20 mA signal.
            6) Chiller start-up and shutdown via remote
               contact closure.                                  n. Controlled Compressor Shutdown:
     h.   Service Function:                                         The controls shall be capable of being config-
                                                                    ured to soft stop the compressor. When the
          The controls shall provide a password pro-
                                                                    stop button is pressed or remote contacts
          tected service function which allows authorized
                                                                    open with this feature active, the guide vanes
          individuals to view an alarm history file which
                                                                    shall close to a configured amperage level and
          shall contain the last 25 alarm/alert messages
                                                                    the machine shall then shut down. The dis-
          with time and date stamp. These messages
                                                                    play shall indicate “shutdown in progress.”
          shall be displayed in text form, not codes.
                                                              2. Safeties:
     i.   Network Window Function:
                                                                 a. Unit shall automatically shut down when any
          Each chiller control panel shall be capable of
                                                                    of the following conditions occur: (Each of
          viewing multiple point values and statuses
                                                                    these protective limits shall require manual
          from other like controllers connected on a
                                                                    reset and cause an alarm message to be dis-
          common network, including controller main-
                                                                    played on the control panel screen, inform-
          tenance data. The operator shall be able to
                                                                    ing the operator of the shutdown cause.)
          alter the remote controller’s set points or
          time schedule and to force point values or                  1) motor overcurrent
          statuses for those points that are operator                 2) over voltage*
          forcible. The control panel shall also have                 3) under voltage*
          access to the alarm history file of all like con-           4) single cycle dropout*
          trollers connected on the network.                          5) bearing oil high temperature
     j.   Pump Control:                                               6) low evaporator refrigerant temperature
                                                                      7) high condenser pressure
          Upon request to start the compressor, the                   8) high motor temperature
          control system shall start the chilled water                9) high compressor discharge temperature
          pump, condenser water pumps and verify                    10) low oil pressure
          that flows have been established.                         11) prolonged surge
     k.   Ramp Loading:                                             12) loss of cooler water flow
          A user-configurable ramp loading rate, effec-             13) loss of condenser water flow
          tive during the chilled water temperature pull-           14) starter fault
          down period, shall control the rate of guide
          vane opening to prevent a rapid increase in               *Shall not require manual reset or cause an
          compressor power consumption. The con-                     alarm if auto-restart after power failure is
          trols shall allow configuration of the ramp                enabled.
          loading rate in either degrees/minute of               b. The control system shall detect conditions
          chilled water temperature pulldown or per-                that approach protective limits and take self-
          cent motor amps/minute. During the ramp                   corrective action prior to an alarm occur-
          loading period, a message shall be displayed              ring. The system shall automatically reduce
          informing the operator that the chiller is                chiller capacity when any of the following
          operating in ramp loading mode.
82
       parameters are outside their normal operat-                  of the lead chiller, include load balancing if config-
       ing range:                                                   ured, and a staggered restart of the chillers after a
         1) high condenser pressure                                 power failure.
         2) high motor temperature                        G.   Electrical Requirements:
         3) low evaporator refrigerant temperature              1. Electrical contractor shall supply and install
         4) surge prevention control                                main electrical power line, disconnect switches,
         5) high motor amps.                                        circuit breakers, and electrical protection
   c. During the capacity override period, a pre-                   devices per local code requirements and as indi-
       alarm (alert) message shall be displayed                     cated necessary by the chiller manufacturer.
       informing the operator which condition is                2. Electrical contractor shall wire the chilled water
       causing the capacity override. Once the                      pump, condenser water pump, and tower fan
       condition is again within acceptable limits,                 control circuit to the chiller control circuit.
       the override condition shall be terminated
                                                                3. Electrical contractor shall supply and install
       and the chiller shall revert to normal chilled
                                                                    electrical wiring and devices required to inter-
       water control. If during either condition the
                                                                    face the chiller controls with the building control
       protective limit is reached, the chiller shall
                                                                    system if applicable.
       shut down and a message shall be displayed
       informing the operator which condition                   4. Electrical power shall be supplied to the unit at
       caused the shutdown and alarm.                               the voltage, phase, and frequency listed in the
                                                                    equipment schedule.
   d. Internal built-in safeties shall protect the
       chiller from loss of water flow. Differential      H.   Piping Requirements — Instrumentation and Safeties:
       pressure switches shall not be allowed to be             1. Mechanical contractor shall supply and install
       the only form of freeze protection.                          pressure gages in readily accessible locations in
3. Diagnostics and Service:                                         piping adjacent to the chiller such that they can
                                                                    be easily read from a standing position on the
   a. A self diagnostic controls test shall be an inte-
                                                                    floor. Scale range shall be such that design values
       gral part of the control system to allow quick
                                                                    shall be indicated at approximately mid-scale.
       identification of malfunctioning components.
                                                                2. Gages shall be installed in the entering and leav-
   b. Once the controls test has been initiated, all
                                                                    ing water lines of the cooler and condenser.
       pressure and temperature sensors shall be
       checked to ensure they are within normal           I.   Vibration Isolation:
       operating range. A pump test shall automati-            Chiller manufacturer shall furnish neoprene isolator
       cally energize the chilled water pump, con-             pads for mounting equipment on a level concrete
       denser water pump, and oil pump. The control            surface.
       system shall confirm that water flow and oil       J.   Start-up:
       pressure have been established and require
       operator confirmation before proceeding to               1. The chiller manufacturer shall provide a factory-
       the next test. A guide vane actuator test shall              trained representative, employed by the chiller
       open and close the guide vanes to check for                  manufacturer, to perform the start-up proce-
       proper operation. The operator manually                      dures as outlined in the Start-up, Operation and
       acknowledges proper guide vane operation                     Maintenance manual provided by the chiller
       prior to proceeding to the next test.                        manufacturer.
   c. In addition to the automated controls test,               2. Manufacturer shall supply the following literature:
       the controls shall provide a manual test                     a. Start-up, operation and maintenance
       which permits selection and testing of indi-                     instructions.
       vidual control components and inputs. A                      b. Installation instructions.
       thermistor test and transducer test shall dis-               c. Field wiring diagrams.
       play and an actual reading shall be per-
       formed for each transducer and each                          d. One complete set of certified drawings.
       thermistor installed on the chiller. All out-of-   K.   Special Features:
       range sensors shall be identified.                       1. Soleplate Package Accessory:
4. Multiple Chiller Control:                                        Unit manufacturer shall furnish a soleplate
   The chiller controls shall be supplied as standard               package consisting of soleplates, jacking
   with a two-chiller lead/lag and a third chiller                  screws, leveling pads, and neoprene pads.
   standby system. The control system shall automat-            2. Spring Isolators Accessory:
   ically start and stop a lag or second chiller on a
   two-chiller system. If one of the two chillers on                Field furnished and selected for the desired
   line goes into a fault mode, the third standby                   degree of isolation.
   chiller shall be automatically started. The two-
   chiller lead/lag system shall allow manual rotation
                                                                                                                      83
Guide specifications (cont)
        3. Spare Sensors with Leads Accessory:                    9. Thermal Insulation:
           Unit manufacturer shall furnish additional tem-           Unit manufacturer shall insulate the cooler shell,
           perature sensors and leads.                               economizer low side compressor suction elbow,
        4. Sound Insulation Kit Accessory (not available on          motor shell, and motor cooling lines. Insulation
           compressor frames 6 and 7):                               shall be 3/4-in. (19-mm) thick with a thermal
                                                                     conductivity not exceeding 0.28 (Btu in.)/hr ft2 F
           Unit manufacturer shall furnish a sound insula-           [(0.0404 • W)/(m • °C)] and shall conform to UL
           tion kit that covers (select):                            standard 94, classification 94 HBF.
           a. The compressor discharge pipe.
                                                                 10. Automatic Hot Gas Bypass:
           b. The compressor housing and motor housing.              Hot gas bypass valve and piping shall be factory
           c. The condenser shell and suction line.                  furnished to permit chiller operation for
           Blanket construction shall allow for installation         extended periods of time.
           and removal without the use of tape or caulk.         11. Cooler and Condenser Tubes:
           Insulation material shall be 11 lb/cu ft fiber-           Contact local Carrier representative for other
           glass. Insulation design shall accommodate tem-
                                                                     tube offerings.
           perature and pressure probes, gages, tubing,
           piping, and brackets. An extended 2-in. wide          12. Cooler and Condenser Passes:
           vinyl flap shall cover all exposed seams, thereby         Unit manufacturer shall provide the cooler and/
           minimizing any potential noise leaks. An alumi-           or condenser with 1, 2 or 3 pass configuration
           num nameplate shall be riveted to each blanket            on the water side.
           piece. Each tag shall be embossed or etched           13. Nozzle-In-Head, 300 psig (2068 kPa):
           with lettering indicating piece location, descrip-
           tion, size, and tag number sequence.                      Unit manufacturer shall furnish nozzle-in-head
                                                                     style waterboxes on the cooler and/or con-
        5. Stand-Alone Pumpout Unit Accessory:                       denser rated at 300 psig (2068 kPa).
           A free-standing pumpout shall be provided. The        14. Marine Waterboxes, 150 psig (1034 kPa):
           pumpout unit shall use a hermetic reciprocating
           compressor with water-cooled condenser. Con-              Unit manufacturer shall furnish marine style
                                                                     waterboxes on cooler and/or condenser rated
           denser water piping, 3-phase motor power
           shall be installed at the jobsite by the installing       at 150 psig (1034 kPa).
           contractor.                                           15. Marine Waterboxes, 300 psig (2068 kPa):
        6. Separate Storage Tank and Pumpout Unit                    Unit manufacturer shall furnish marine style
           Accessory:                                                waterboxes on cooler and/or condenser rated
           A free-standing refrigerant storage tank and              at 300 psig (2068 kPa).
           pumpout unit shall be provided. The storage           16. Flanged Waterbox Nozzles:
           vessels shall be designed per ASME Section VIII           Unit manufacturer shall furnish standard
           Division 1 code with 185 psig (1276 kPa)                  flanged piping connections on the cooler and/
           design pressure. Double relief valves per ANSI/           or condenser.
           ASHRAE 15, latest edition, shall be provided.         17. Hinges:
           The tank shall include a liquid level gage and
           pressure gage. The pumpout unit shall use a               Unit manufacturer shall furnish hinges on
           hermetic reciprocating compressor with water              waterboxes to facilitate tube cleaning.
           cooled condenser. Condenser water piping and          18. Pumpout Unit:
           3-phase motor power shall be installed at the             A refrigerant pumpout system shall be installed
           jobsite by the installing contractor.                     on the chiller. The pumpout system shall
        7. Building Control System Interface (LON)                   include a hermetic compressor and drive, pip-
           Accessory:                                                ing, wiring, and motor. (19XR compressor
           The chiller control system shall have the ability         frame sizes 2 to 5, E only.)
           to interface and communicate directly to the          19. Optional Compressor Discharge Isolation Valve
           building control using a LON-based system. The            and Liquid Line Ball Valve:
           LonWorks* Carrier Translator shall output data            These items shall be factory installed to allow
           in standard LON profiles. (19XR compressor                isolation of the refrigerant charge in the con-
           frame sizes 2 to 5, E only.)                              denser for servicing the compressor.
        8. Refrigerant Charge:                                   20. Optional Seismic Isolation Package (Select
           The chiller shall ship from the factory fully             Models Only):
           charged with R-134a refrigerant and oil.                  Package shall meet International Building Code
                                                                     and ASCE 7 seismic qualification requirements
                                                                     in concurrence with ICC ES AC156 Acceptance
                                                                     Criteria for Seismic Qualification by Shake-Table
*LonWorks is a registered trademark of Echelon Corporation.
84
          Testing of Nonstructural Components and Sys-                      2) Run (up to voltage)
          tems. Manufacturer shall provide seismic certifi-                 3) Phase Correct
          cate from OSHPD (California only).                                4) Overtemperature Fault
      21. BACnet† Communication Option:                                     5) SCR Gates Energized
                                                                            6) Ground Fault
          Shall provide factory-installed communication                     7) Current Imbalance Fault
          capability with a BACnet network. Allows integra-                 8) Shorted SCR
          tion with i-Vu® Open control system or a BACnet
          building automation system. (Integration with i-Vu       23. Unit-Mounted Variable Frequency Drive (VFD)
          requires the use of the i-Vu Link module for com-            with Built-in Harmonic Filter (LiquiFlo™ 2, avail-
          pressor frames 6 and 7. The UPC Open module                  able for low voltage only):
          is required for compressor frames 2-5, E.)                   a. Design:
      22. Optional Low-Voltage Unit-Mounted Starter                         1) VFD shall be refrigerant cooled, micro-
          (not available on chiller heat exchanger sizes 8,                    processor based, pulse width modulated
          A, B, C, or D):                                                      (PWM) design. Water-cooled designs are
          An optional reduced voltage wye-delta or solid-                      not acceptable.
          state starter shall be supplied. The compressor                   2) Input and output power devices shall be
          motor starter shall be factory mounted, wired and                    insulated gate bipolar transistors (IGBTs).
          tested prior to shipment by the chiller manufac-                  3) Active rectifier shall convert incoming
          turer. Customer electrical connection for com-                       voltage / frequency to DC voltage. Input
          pressor motor power shall be limited to main                         current and voltage shall be regulated.
          power leads to the starter, and wiring water                      4) Transistorized inverter and control regu-
          pumps and tower fans to the chiller control circuit.                 lator shall convert DC voltage to a sinu-
                                                                               soidal PWM waveform.
          a. NEMA 1 enclosure with integral fan cooling                     5) Integrated chiller controls shall coordi-
              and lockable hinged doors.                                       nate motor speed and guide vane posi-
          b. Main power disconnect (non-fused type).                           tion to optimize chiller performance
          c. Capability to start and stop chiller, pumps                       over all chiller operating conditions.
              and tower fans.                                               6) Surge prevention and surge protection
          d. 3 kva control/oil heater transformer.                             algorithms shall take action to prevent
                                                                               surge and move chiller operation away
          e. Branch circuit breaker to provide power for                       from surge.
              oil pump.
                                                                       b. Enclosure:
          f. Branch circuit breaker to provide power for
              control power and oil heater.                                 1) Pre-painted unit mounted, NEMA 1 cab-
                                                                               inet shall include hinged, lockable doors
          g. The following are standard features:                              and removable lifting lugs.
                1) Phase loss                                               2) VFD shall have a short circuit
                2) Phase reversal                                              interrupt and withstand rating of at
                3) Phase imbalance                                             least 65,000 amps (35,000 amps for
                4) 3-phase ground fault                                        575-v units).
                5) Low voltage — phase to phase and                         3) Provisions to padlock main disconnect
                   phase to ground                                             handle in the “Off” positions shall be
                6) Medium voltage — phase to ground                            provided. Mechanical interlock to pre-
                7) Current overload                                            vent opening cabinet door with discon-
                8) Current flow while stopped                                  nect in the “On” position or moving
                9) 3-phase under/over voltage                                  disconnect to the “On” position while
              10) 3-phase digital ammeter/voltmeter                            the door is open shall be provided.
              11) Microprocessor based overload trip                        4) Provisions shall be made for top entry of
                   protection                                                  incoming line power cables.
              12) Frequency digital display                            c. Heat Sink:
          h. Optional unit-mounted solid-state starter shall                1) The heat sink shall be refrigerant
              provide stepless compressor motor accelera-                      cooled. Heat sink and mating flange
              tion. The starter shall include 6 silicon con-                   shall be suitable for ASME design work-
              trolled rectifiers (SCRs) with integrally                        ing pressure of 185 psig (1276 kPa).
              mounted bypass once the motor has achieved                    2) Refrigerant cooling shall be metered
              full voltage and speed. The starter shall also                   by microprocessor control solenoid
              display the following:                                           valve to maintain heat sink temperature
                1) Starter On                                                  within acceptable limits for ambient
†BACnet is a registered trademark of ASHRAE (American Society of               temperature.
Heating, Refrigerating, and Air-Conditioning Engineers).                    3) Water-cooled heat exchangers requiring
                                                                               cleaning shall not be acceptable.
                                                                                                                       85
Guide specifications (cont)
     d. VFD Rating:                                                  provides power for oil heater, VFD con-
         1) Drive shall be suitable for continuous                   trols and chiller controls.
            operation at nameplate voltage ±10%.                  4) The branch oil pump circuit breaker and
         2) Drive shall be suitable for continuous                   control power transformer shall be fac-
            operation at 100% of nameplate                           tory wired.
            amps and 150% of nameplate amps for                   5) Nameplate voltage shall range between
            5 seconds.                                               380 and 460 ±10%, 3 phase, 50/60
         3) Drive shall comply with applicable                       Hz ±2% Hz.
            ANSI, NEMA, UL and NEC standards.                h. Discrete Outputs:
         4) Drive shall be suitable for operation in            115 v discrete contact outputs shall be pro-
            ambient temperatures between 40 and                 vided for field wired:
            104 F (4.4 and 40 C), 95% humidity
                                                                  1) Chilled water pump
            (non-condensing) for altitudes up to
                                                                  2) Condenser water pump
            6000 ft (1829 m) above sea level. Spe-
                                                                  3) Alarm status
            cific drive performance at jobsite ambi-
                                                                  4) Tower fan low
            ent temperature and elevation shall be
                                                                  5) Tower fan high
            provided by the manufacturer in the bid.
                                                             i. Analog Output:
     e. User Interface:
                                                                An analog (4 to 20 mA) output for head
        A single display shall provide interface for
                                                                pressure reference shall be provided. This
        programming and display of VFD and chiller
                                                                signal shall be suitable to control a 2-way or
        parameters. Viewable parameters include:
                                                                3-way water regulating valve in the con-
         1) Operating, configuration and fault                  denser piping.
            messages
                                                             j. Protection (the following shall be supplied):
         2) Frequency in Hz
         3) Load and line side voltage and current                1) Under-voltage
            (at the VFD)                                          2) Over voltage
         4) kW (line and load side)                               3) Phase loss
         5) IGBT temperatures                                     4) Phase reversal
                                                                  5) Ground fault
     f. VFD Performance:
                                                                  6) Phase unbalance protection
         1) VFD voltage total harmonic distortion                 7) Single cycle voltage loss protection
            (THD) and harmonic current total                      8) Programmable auto re-start after loss of
            demand distortion (TDD) shall not                        power
            exceed IEEE-519 requirements using                    9) Motor overload protection (NEMA
            the VFD circuit breaker input terminals                  Class 10)
            as the point of common coupling (PCC).
                                                             k. VFD Testing:
         2) VFD full load efficiency shall meet or
            exceed 97% at 100% VFD rated                        VFD shall be factory mounted, wired and
            ampacity.                                           tested on the chiller prior to shipment.
         3) Active rectifier shall regulate unity dis-   24. Unit-Mounted Variable Frequency Drive
            placement power factor to 0.99 or                (VFD) without Built-In Harmonic Filter (avail-
            higher at full load.                             able for low voltage only):
         4) Voltage boost capability to provide full         a. Design:
            motor voltage at reduced line voltage
            conditions.                                           1) VFD shall be refrigerant cooled, micro-
         5) Soft start, linear acceleration, coast to                processor based, pulse width modulated
            stop.                                                    (PWM) design. Water cooled designs are
         6) Base motor frequency shall be either 50                  not acceptable.
            or 60 Hz. Adjustable frequency range                  2) Output power devices shall be insulated
            from 39 to 60 Hz or 32.5 to 50 Hz.                       gate bipolar transistors (IGBTs).
                                                                  3) Converter section with full-wave fixed
     g. VFD Electrical Service (single point power):                 diode bridge rectifier shall convert
         1) VFD shall have input circuit breaker                     incoming fixed voltage/frequency to
            with minimum 65,000 amp interrupt                        fixed DC voltage.
            capacity.                                             4) DC link shall filter and smooth the con-
         2) VFD shall have standard 15 amp branch                    verted DC voltage.
            circuit breaker to provide power for                  5) Transistorized inverter and control regu-
            chiller oil pump.                                        lator shall convert fixed DC voltage to a
         3) VFD shall have standard 3 kva control                    sinusoidal PWM waveform.
            power transformer with circuit breaker                6) Integrated controls shall coordinate
                                                                     motor speed and guide vane position to
86
          optimize chiller performance over a            f. VFD Performance:
          wide variety of operating conditions.               1) VFD full load efficiency shall meet or
       7) Surge prevention and surge protection                  exceed 97% at 100% VFD Rated
          algorithms shall take action to prevent                ampacity.
          surge and move chiller operation away               2) Displacement Input Power Factor shall
          from surge.                                            meet or exceed 95% soft start, linear
b.   Enclosure:                                                  acceleration, coast to stop.
       1) Pre-painted, unit mounted NEMA 1 cab-               3) Base motor frequency shall be either 50
          inet shall include hinged, lockable doors              or 60 Hz. Adjustable frequency range
          and removable lifting lugs.                            from 38 to 60 Hz or 32.5 to 50 Hz.
       2) VFD shall have a short circuit interrupt and   g. VFD Electrical Service (single point power):
          withstand rating of at least 100,000 amps.          1) VFD shall have input circuit breaker with
       3) Provisions to padlock main disconnect                  minimum 100,000 amp interrupt
          handle in the “Off” positions shall be                 capacity.
          provided. Mechanical interlock to pre-              2) VFD shall have standard 15 amp branch
          vent opening cabinet door with discon-                 oil pump circuit breaker to provide
          nect in the “On” position or moving                    power for chiller oil pump.
          disconnect to the “ON” position while               3) VFD shall have standard 3 kva control
          the door is open shall be provided.                    power transformer with circuit breaker
       4) Provisions shall be made for top entry of              provides power for oil heater, VFD con-
          incoming line power cables.                            trols and chiller controls.
c.   Heat Sink:                                               4) The branch oil pump circuit breaker and
       1) The heat sink shall be refrigerant                     control power transformer shall be fac-
          cooled. Heat sink and mating flanges                   tory wired.
          shall be suitable for ASME design work-             5) Input power shall be 380/480 vac, ±10
          ing pressure of 185 psig (1276 kPa).                   percent, 3 phase, 50/60 Hz, ±3 Hz.
       2) Refrigerant cooling shall be metered by        h. Discrete Outputs:
          integrated standard controls to maintain          115-v discrete contact outputs shall be pro-
          heat sink temperature within acceptable           vided for:
          limits for ambient temperature.
                                                              1) Circuit breaker shunt trip
d.   VFD Rating:                                              2) Chilled water pump
       1) Drive shall be suitable for nameplate               3) Condenser water pump
          voltage ±10%.                                       4) Alarm status.
       2) Drive shall be suitable for continuous oper-   i. Analog Output:
          ation at 100% of nameplate amps and
                                                            An analog (4 to 20 mA) output for head
          150% of nameplate amps for 3 seconds.
                                                            pressure reference shall be provided. This
       3) Drive shall comply with applicable UL,
                                                            signal shall be suitable to control a 2-way or
          CE, and NEMA standards.
                                                            3-way water regulating valve in the con-
       4) Drive shall be suitable for operation in
                                                            denser piping.
          ambient temperatures between 40 and
          104 F (4.4 and 40 C), 95% humidity             j. Protection (the following shall be supplied):
          (non-condensing) for altitudes up to                1) Under-voltage
          3300 ft (1006 m) above sea level.                   2) Over voltage
          Specific drive performance at jobsite               3) Phase loss
          ambient temperature and elevation shall             4) Phase reversal
          be provided by the manufacturer in the              5) Ground fault
          bid.                                                6) Phase unbalance protection
e.   User Interface:                                          7) Single cycle voltage loss protection
                                                              8) Programmable auto re-start after loss of
     Displays shall provide interface for program-
                                                                 power
     ming and display of VFD and chiller parame-
                                                              9) Motor overload protection (NEMA
     ters. Viewable parameters include:
                                                                 Class 10)
       1) Operating, configuration and fault                10) Motor overtemperature protection
          messages
       2) Frequency in hertz                             k. VFD Testing:
       3) Load and line side voltage and current            VFD shall be factory mounted, wired and
          (at the VFD)                                      tested on the chiller prior to shipment.
       4) kW (on the VFD interface)
                                                                                                       87
Guide specifications (cont)
     25. Free-Standing Medium Voltage Variable Fre-                      cycles with optional UPS (uninterrupt-
         quency Drive:                                                   ible power supply).
         a. VFD Design:                                               3) Drive complies with applicable sections
                                                                         of NEMA, UL, and NEC standards and
             1) Technology shall allow connection of                     is UL, Canada listed.
                the drive to utility power without the                4) Drive shall be suitable for operation in
                requirement of an isolation transformer.                 ambient temperatures between 40 and
             2) Direct-to-drive technology shall have                    104 F (4.4 and 40 C), 95% humidity
                active front end to track and regulate                   (non-condensing) for altitudes up to
                input current to maintain sine wave cur-                 3300 ft (1006 m) above sea level. Spe-
                rent draw.                                               cific drive performance at jobsite ambi-
             3) VFD shall be microprocessor-based,                       ent temperature and elevation shall be
                pulse width modulated (PWM) design.                      provided by the manufacturer in the bid.
             4) Input and output power devices shall be
                6500 volt rated symmetrical gate com-             e. VFD Performance:
                mutated thyristor (SGCT) to achieve                   1) VFD voltage total harmonic distortion
                superior PWM switching pattern and sig-                  (THD) shall not exceed 3% and har-
                nificantly reduce line current harmonics.                monic current total demand distortion
             5) Low voltage and medium voltage com-                      (TDD) shall not exceed IEEE-519
                partments shall be totally isolated and                  requirements using the VFD circuit
                separated.                                               breaker input terminals as the point of
             6) Power shall be isolated by means of a                    common coupling (PCC).
                vacuum starter that can be locked out/                2) VFD full load efficiency shall meet or
                tagged out. This starter can be integral                 exceed 97% at 100% VFD rated
                to drive for "A" frames, part of line up or              ampacity.
                located outside of line up for "B" frames.            3) Displacement input power factor shall
             7) Integrated controls shall coordinate                     meet or exceed 99% to unity gain at full
                motor speed and guide vane position to                   load.
                optimize chiller performance over a                   4) Soft start, linear acceleration, coast to
                wide variety of operating conditions.                    stop.
             8) Surge prevention and surge protection                 5) Base motor frequency shall be either 50
                algorithms shall take action to prevent                  or 60 Hz, adjustable frequency range
                surge and move chiller operation away                    from 39 to 60 Hz or 32.5 to 50 Hz.
                from surge.                                       f. VFD Electrical Service (Single Point Power):
         b. Enclosure:                                               VFD shall have input circuit breaker with
             1) Rear access shall not be required and                minimum 25,000 amp interrupt capacity.
                VFD shall be fully accessible from front.         g. Protection (the following shall be supplied):
             2) Pre-painted cabinet (NEMA 1) includes
                                                                      1) Under voltage
                hinged, lockable doors and removable
                                                                      2) Over voltage
                lifting lugs.
                                                                      3) Phase loss
             3) Enclosure shall have short circuit inter-
                                                                      4) Phase reversal
                rupt and withstand rating of at least
                                                                      5) Ground fault
                25,000 amps.
                                                                      6) Phase unbalance protection
         c. Heat Sink:                                                7) Single cycle voltage loss protection
             1) The heat sink shall be air-cooled from                8) Programmable auto restart after loss of
                200 hp to 5500 hp.                                       power
             2) Advanced overtemperature compensa-                    9) Motor overload protection (NEMA
                tion algorithm shall provide standard heat               Class 10)
                sink temperature and flow monitoring.                10) Motor overtemperature protection
         d. VFD Rating:                                           h. Testing:
             1) Drives less than 6600 vac shall be suit-             Drive shall be 100% load tested from VFD
                able for nameplate voltage plus or minus             manufacturer's factory and shipped without
                10%; 6600-vac drives shall have voltage              any unwiring or electrical components disas-
                rating of plus 5% and minus 10%.                     sembled inside main VFD cabinet.
             2) Drive shall be suitable for continuous        26. Free-Standing Low Voltage Variable Frequency
                operation at 100% of nameplate amps               Drive:
                and 110% of nameplate amps for 60
                                                                  a. Design:
                seconds every ten minutes; voltage sag
                of -30%; and control power loss ride                  1) Output power devices shall be insulated
                through of 5 cycles standard and >5                      gate bipolar transistors (IGBTs).
88
      2) Converter section with full wave fixed          2) Frequency in Hz
         diode bridge rectifier shall convert            3) Manual or automatic control mode
         incoming fixed voltage/frequency to             4) Output frequency
         fixed DC voltage.                               5) Percent output voltage, or voltage
      3) Transistorized inverter and control regu-       6) Percent output current, or current
         lator shall convert fixed DC voltage to a       7) kW and kWh
         sinusoidal PWM waveform.                    d. VFD Electrical Service:
      4) VFD shall have 1.5% AC line reactor.
                                                         1) VFD shall have main standard interrupt-
b. Enclosure:                                               ing capacity circuit breaker with shunt
   Main section and control section shall be                trip (65 kAIC interrupt capacity).
   housed in connected NEMA 1 cabinets.                  2) VFD shall have oil pump circuit breaker
c. User Interface:                                          (65 kAIC interrupt capacity).
                                                         3) VFD shall have pumpout unit circuit
   Door-mounted digital keypad with non-volatile            breaker (65 kAIC interrupt capacity).
   memory shall have 6 line, 30 character back-
                                                         4) 110-v power shall be provided for ISM
   lit LCD display for programming and display              (integrated starter module) board.
   of VFD parameters. Viewable parameters
   include:                                          e. Analog Output:
      1) Operating, configuration, and fault            An analog (4 to 20 mA) output for head
         messages                                       pressure reference shall be provided.
                                                                                                89
       Carrier Corporation • Syracuse, New York 13221                                       1216        9-16
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
               Pg 92                      Catalog No. 04-52190014-01                           Printed in U.S.A.                Form 19XR,XRV-CLT-18PD
                                                                                                                            Replaces: 19XR,XRV-CLT-17PD