Cassette Fan Coils Series Cassette Fan Coils Series
2 pipe/6 way Cassette FCU 2 pipe/6 way Cassette FCU
AC Standard Specification:
EC Motors Aesthetic ABS Panel
Air Filter Synthetic washable and removable
Housing Galvanized steel with high temperature foam insulation on both inside and outside
Heat Exchanger Copper tube and hydrophilic AL fins with air release valve
Drain Pan High density polystyrene foam material
Drain Pump 70cm head or 120cm head, with float switch and no return valve
Fan/Motor Centrifugal Fans, 3 speed motor or EC motor
Main board, transformer, built-in electric control or external electric
Control System control, remote control or wired wall pad
Technical Parameters:
Model FP-85KM6-V/B FP-102KM6-V/B FP-136KM6-V/B FP-170KM6-V/B
H 6.0 7.0 8.0 9.0
Cooling
M kW 5.1 6.0 6.9 7.7
Capacity
Product Description: Cooling L 4.2 5.4 6.1 6.9
2 pipe/4 way Cassette FCU, ceiling mounted and suitable for chilled/hot water AC systems Water Flow Rate L/h 1030 1200 1375 1550
Water Pressure Drop kPa 8 10 13 16
Air Flow 850-1700m³/h(500-1000CFM)
H 9.0 10.5 12.0 13.5
Cooling Capacity 6.0-9.0KW Heating
Heating M kW 7.6 9.0 10.8 12.0
Capacity
L 6.5 8.0 9.2 10.7
1240
Type Centrifugal Fan
Dimensions: 1133
Blower Dia. mm Φ315 Φ315 Φ315 Φ315
976 Qty. 2 2 2 2
Power Supply V/Ph/Hz 220 / 1 / 50
Electrical
Input Power W 105 110 118 195
Parameters
Current A 0.48 0.50 0.54 0.89
H 850 1020 1360 1700
575
612
680
Air Flow(H/M/L) M m3/h 700 870 1120 1350
L 550 720 900 1100
Sound Pressure dB(A) 45/41/39 49/45/40 52/50/45 54/52/50
Control Mode Remote control or wired wall pad
Unit Dimensions (LxWxH) mm 1133x575x290
Panel Dimensions (LxWxH) mm 1240x680x30
70
Net Weight kg 42
In inch ZG3/4"
290
Water
Out inch ZG3/4"
Connection
Drain Pipe(OD) mm 26
Test Condition:
Cooling: inlet dr y ball temp. 27ºC, wet ball 19.5ºC, inlet water temp.7ºC,outlet water temp 12ºC
Heating: inlet dry ball temp. 21ºC, inlet water temp. 60 ºC, same water flow as cooling
Cassette Fan Coils Series Cassette Fan Coils Series
4 pipe/6 way cassette 4 pipe/6 way Cassette
AC Standard Specification:
EC Motors Aesthetic ABS panel
Air Filter Synthetic washable and removable
H ousing Galvanized steel with high density foam insulation inside
Heat Exchanger Copper tube and hydrophilic AL fins with air release valve
Drain Pan High density polystyrene foam material
Drain Pump 70cm head or 120cm head, with float switch and no return valve
Fan/Motor Centrifugal Fans, 3 speed motor or ECmotor
Main board, transformer, built-in electric control or external
Control System
electric control,remote control or wired wall pad
Technical Parameters:
Model FP-85KM6-P/B FP-102KM6-P/B FP-136KM6-P/B FP-170KM6-P/B
H 5.0 6.0 6.5 7.5
Cooling
M kW 4.3 5.3 5.8 6.4
Capacity
Product Description: Cooling L 3.6 4.6 5.3 5.9
Water Flow Rate L/h 860 1030 1120 1290
2 pipe/4way cassette FCU, ceiling mounted and suitable for chilled / hot water AC system
Water Pressure Drop kPa 18.5 19.0 22.0 26.0
Air Flow 850-1700m³/h(500-1000CFM) H 7.6 8.4 9.6 10.4
Heating
Cooling Capacity 5.0-7.5KW Capacity
M kW 6.5 7.7 8.6 9.0
Heating L 5.4 6.6 7.9 8.4
Panel Dimension 1240*680*30
Water Flow Rate L/h 650 720 820 900
Water Pressure Drop kPa 16 20 23 26
1240 Type Centrifugal Fans
Dimensions:
1133 Blower Dia. mm Φ315 Φ315 Φ315 Φ315
Qty 2 2 2 2
976
Power Supply V/Ph/Hz 220 / 1 / 50
Electrical
Input Power W 105 110 118 195
Parameters
Current A 0.48 0.50 0.54 0.89
H 850 1020 1360 1700
Air Flow (H/M/L) M m3/h 700 870 1120 1350
575
612
680
L 550 720 900 1100
Sound Pressure dB(A) 45 48 50 52
Control Mode Remote control and wired wall pad
UnitDimension (LxWxH) mm 1133x575x290
Panel Dimension mm 1240x680x30
Net Weight kg 42
In inch ZG3/4"
Water
70
Out inch ZG3/4"
Connection
Drain pipe
mm 26
(OD )
290
Test Condition:
Cooling: inlet dry ball temp. 27ºC, wet ball 19.5ºC, inlet water temp.7ºC,outlet water temp 12ºC
Heating: inlet dry ball temp. 21ºC, inlet water temp. 60 ºC, same water flow as cooling