Cathodic Protection of Ships
Cathodic Protection of Ships
Appendix A
Cathodic Protection Specifications
This appendix contains two standard specifications for cathodic protection. The specifications
are presented in Construction Specifications Institute (CSI) MasterFormat 2004:
Section number: 26 42 00
WARNING: The standards and guidelines do not relieve licensed engineers from their
responsibilities as outlined by the code of ethics and rules of practice. All specifications require
editing and review by the project's licensed engineer and must be tailored to the conditions and
needs of the project. The guidelines provide policy, clarity, and advice on how design should be
conducted by and for Seattle Public Utilities. However, it remains the responsibility of the
licensed engineer to properly interpret and apply the guidelines as appropriate to meet the
needs of the project. If these standards and guidelines contain any contradictions with other
standard engineering practices, the licensed engineer is responsible for identifying and
resolving them.
This Section covers the work necessary to furnish and install impressed current cathodic
protection systems for the various locations as identified for this project.
Note: This specification will be revised in the next version (v.3) of the Design Standards and Guidelines
(DSG). This should be considered a starting point for a specification for a generic impressed current
cathodic protection system.
Note: All specifications are edited for project-specific requirements.
Document Processing: You must have the paragraph button (¶) selected from the HOME tab on
the toolbar in order to see the blue note text. This text is only for the specification writer, It
should be deleted from the document.
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 1 of 22
PART 1 GENERAL
1.02 SUMMARY
Note: This section will be completed in the next version (v.3) of the Design Standards and Guidelines
(DSG).
A. Section includes:
1.
2.
1.03 DEFINTIONS
A. Lead, Lead Wires, Joint Bonds, Cable: Insulated copper conductor; the same as wire.
B. Active Column: The anode and coke breeze portion of a deep anode ground bed that
discharges current.
C. Inactive Column: The gravel fill and seal portions of a deep anode ground bed that do
not discharge current.
1.04 SUBMITTALS
A. Provide catalog cuts and other information for all materials to be used. Submittals
shall be made in accordance with Section 01330, SUBMITTALS.
1. Name of individual, current job title(s), and a copy of current NACE International
Cathodic Protection Specialist certificate or Professional Engineer’s license.
2. Title of projects (minimum of 10, for experience) with dates for the past 5 years.
3. Employer with name and telephone number of contact person for each project
listed.
4. Contracting agency with name and telephone number of contact person for each
project listed.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 2 of 22
5. Brief technical summary of work for each project listed, including pertinent details
which are similar to this project.
1. Name of the individual(s) who will operate the drilling equipment, current job
title(s), and a copy of their current drilling license.
2. Title of all projects (for experience) with dates for the past 5 years.
3. Drilling company employer with name and telephone number of contact person for
each project listed.
4. Contracting agency with name and telephone number of contact person for each
project listed.
5. Brief technical summary of work for each project listed, including pertinent details
which are similar to this project.
E. A written description of the method to be used for lowering the cathodic protection
anodes, vent pipe, and installation of coke breeze into the holes.
B. Cathodic Protection Specialist shall be present at the project site during installation of
the cathodic protection anodes and backfill, and shall perform the resistance tests
specified during backfill operations. Additional visits to the jobsite shall be made by the
Cathodic Protection Specialist at intervals as required to determine compliance with
these specifications and as may be necessary to resolve field problems.
C. Driller’s Experience: Driller shall have installed a minimum of three deep anode
ground beds within the last 5 years. Drillers shall be licensed in accordance with
WAC 173-162.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 3 of 22
PART 2 PRODUCTS
2.01 GENERAL
A. The use of a manufacturer's name and model or catalog number is for the purpose of
establishing the standard of quality and general configuration desired only. Products
of other manufacturer's will be considered in accordance with the General Conditions.
1. Dimensions:
2. Composition:
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 4 of 22
g. Iron: Remainder.
C. Anode Tests at the Fabrication Facility: The anode supplier shall conduct, and submit
to the ENGINEER, resistance tests for each anode lead wire connection to assure the
finished connection does not exceed the specified resistance value. All wire-to-anode
connections that exceed the specified resistance value shall be replaced by the anode
supplier. Wire-to-anode resistance records shall include the following:
6. Test methods.
D. Supplemental Anode: The CONTRACTOR shall include one additional anode with a
lead wire length equal to the longest anode lead wire length required. The
CONTRACTOR shall allow the ENGINEER to select and test any anode for
connection resistance measurements and total destructive testing. The anodes shall
be available for selection at least 10 working days before the anodes are installed.
Failure of this anode to pass the resistance test or tensile test on the wire-to-anode
connection will be cause to reject the entire anode shipment.
F. Anode Wire: Supply each anode with No. 8 AWG insulated, stranded copper wire of
sufficient length to extend splice-free from the anode connection to the anode junction
box terminals plus 15 feet. Anode wires shall be insulated as specified under WIRE,
this section.
G. Cable Guides: Provide all anodes with a cable guide where the anode wire enters the
anode tube to prevent damage to the wire insulation during handling and installation.
I. Wire Labels: Label the end of each anode wire with the anode number and total wire
length, stamped onto brass tags. The anodes shall be numbered sequentially from the
bottom to the top. Bottom anode shall be labeled No. 1.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 5 of 22
5. Particle Size: 100 percent passing 16 mesh and 98 percent retained by 200 mesh.
C. Couplings and fittings for the vent pipes shall be Schedule 80, high-impact, rigid PVC.
Fasten vent couplings and fittings with solvent-welded joints or ENGINEER-approved
alternate in accordance with the manufacturer’s written instructions.
D. The bottom of the vent pipe shall be sealed with a plastic end cap or plug.
2.08 CASING
A. Well casing, if used, shall be standard weight steel in new condition. Starter (surface)
steel casing need not be new, but must be in good condition. Nominal wall thickness
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 6 of 22
for steel casing shall be 0.25 inch thick. Plastic starter casing shall meet or exceed
ASTM Standard F-480. All casing shall be in good condition, durable, and watertight.
Casing material shall be nontoxic and resistant to water and soil corrosiveness.
Casing shall meet local well drilling standards and state and local codes for well
drilling and be able to withstand installation, grouting, and operating stresses. Plastic
casing shall not be used in the active column (anodes) of the ground bed.
B. Cement Grout: Composed of two parts by weight sand to one part cement and 5 to
7 gallons of water per sack of cement. Gradation of the sand shall fall within the
following limits:
Sieve Percentage Passing
3/8-in. 100
No. 4 95 to 100
No. 16 45 to 80
No. 50 10 to 30
No. 100 2 to 10
B. Panels: Panels for mounting terminal studs shall be 1/4-inch thick phenolic. A clear
1/4-inch thick clear acrylic insulating panel shall be mounted 1/4 inch above the
terminal studs and cover the phenolic terminal panel. The insulating panel shall be
provided with 1/4-inch diameter holes over each terminal stud or shunt measuring
surface to allow contact of voltmeter test probes. The insulating panel shall be
fastened above the terminal panel on 1/4-20- by 1.75-inch nickel-plated brass studs.
Studs shall be locked to terminal board to prevent loosening when removing wire
connections.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 7 of 22
C. Terminals and Connectors: Provide copper bus bar(s), terminal studs, connectors,
and all necessary fasteners to connect the anode and rectifier wires.
3. Connectors: Offset pressure tongue with hex head, solderless lugs, sized for the
wire to be connected. Burndy series KPA, Panduit series CB, or approved equal.
D. Shunts: Agra Type JB, 0.01 ohm with 8 ampere capacity. Provide with holes for 1/4-
inch diameter fasteners.
E. Schematic: Supply a plastic laminated schematic drawing that identifies the wire
terminations at the terminal studs. The schematic plate shall be securely fastened to
the inside face of the rectifier access door.
1. Graphite anodes shall be 99% pure carbon and shall be paraffin wax impregnated.
They shall be 80 inches long by 4 inches in diameter and shall weigh 62 pounds
bare, minimum.
2. Acceptable Distributors
B. Anode Wires
1. Each anode lead wire shall be a continuous AWG #8, 7 strand copperconductor
with black HMW-PE type insulation.
2. Each anode lead wire shall be of sufficient length to reach from the anode
assembly to the header cable splice. dditional splices will not be allowed in the
anode lead wire.
C. Wire-to-Anode Connection
1. Each anode shall have a center-connect lead wire. The maximum electrical
resistance of the connection shall not exceed 0.004 ohms. The minimum pull-out
strength of the anode lead wire shall exceed that of the breaking strength of the
anode lead wire.
D. Anode Cap
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 8 of 22
1. The anode cap material shall be water resistant and form a tightly bonded seal to
the anode material and lead wire.
1. Calcined Petroleum Coke: Coke breeze backfill shall be low resistance, calcined
petroleum coke, and shall have the following properties:
b. Moisture: 0.10%
c. Ash: 0.35%
d. VCM: 0.30%
e. Sulfur: 3.75%
2.13 RECTIFIER
A. Rectifier Manufacturers: The rectifiers shall be the product of a company currently
engaged in the manufacture of cathodic protection equipment and shall conform in all
respects to NEMA Standards. Acceptable rectifier manufacturers are:
B. General: Air cooled, manually controlled meeting NEMA standards. The rectifier shall
be designed to operate continuously at an ambient temperature of 45 degrees C and
shall be capable of 110 percent of rated input without damage to the rectifier
components.
C. AC Input:
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 9 of 22
temperature of 130 degrees C with actual hottest spot temperature at rated conditions
not to exceed 100 degrees C.
E. Rectifying Elements: Full wave bridge, silicon diode stack with efficiency filter, with
metal oxide thyristors and current limiting devices for overvoltage and overcurrent
protection of the stack.
G. Lightning Protection: Provide lightning protection devices for AC input and DC output.
AC lightning protection shall be rated to absorb up to 1,000 joules of energy per
phase. The DC protection shall be rated to absorb 500 joules. Furnish one spare set
of lightning protectors for each rectifier.
H. Meters: Separate DC voltage and current meters, D'Arsenval jeweled movement type,
accurate to within 2 percent of actual voltage and current output. Meters shall be field
tested for accuracy; inaccurate meters shall be replaced.
I. Shunt: Holloway type shunt mounted in series with the ammeter, with voltage and
current clearly identified on shunt body.
J. NEMA 3R Enclosure: 14-gauge stainless steel 36” width x 24” deep x 42” high.
Provide with hinged doors on both sides to allow access, stainless steel latches, and
hasp for locking. Enclosure shall be sealed to protect the interior components from
weather, vandalism, and nest building insects, and shall provide adequate ventilation.
Install per City of Seattle Std., Plan 500 and drawings.
K. Panelboard: Non-metallic, suitable for mounting meters, shunt, circuit breaker, fuses
and output terminals. Panelboard shall be located as shown on drawings and to allow
access for testing and adjustment. Clearly engrave or identify with a permanent
marking system the polarity of output terminals, fine and course transformer tap
settings, meters, and fuses. All anode terminations shall occur on this panel board
opposite side from the rectifier location, as shown on dwgs.
M. Current Interrupter: Provide a solid state timing device to interrupt secondary current.
Interrupter shall be capable of continuous operation, and shall consist of a 1-minute
adjustable recycling mechanical timer or electronic timer, a “Test-Normal” toggle
switch, and a relay or connector to interrupt the main current.
N. Mounting Hardware: Tap studs, tap bars, nuts, washers and other mounting hardware
shall be suitably sized brass or tin-plated copper.
O. Nameplate: Engraved metal plate mounted on the interior side of the front door listing
the manufacturer name, model number, serial number, year manufactured, and AC
and DC input and output electrical ratings.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 10 of 22
2. The completed nameplate shall be coated with a clear polyurethane enamel with
exterior catalyst and attached to the rectifier enclosure door with a minimum of six
stainless steel drive rivets.
R. Acceptable Rectifiers:
B. Pedestal Case: 12-gauge steel, minimum, with lockable circuit breaker cover.
C. Special Coating: Pedestal case shall be provided with a polyamide converted epoxy
coating, applied in two coats to a dry film thickness of 8 to 10 mils. Pedestals provided
with a coating that does not meet or exceed this coating shall be sanded to bare metal
and coated by the CONTRACTOR with the specified coating.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 11 of 22
2.19 CONCRETE
A. Reinforcing Steel: ASTM A615, Grade 60 deformed bars.
C. Formwork: Plywood.
1. Cement: ASTM C150, Type II, with maximum alkyl content of 0.606 percent.
2.22 WIRE
A. Rectifier to Pipeline and Anode Junction Box: Single conductor, No. 4 AWG stranded
copper with 600-volt High Molecular Weight Polyethylene (HMWPE) insulation.
HMWPE insulation shall be 7/64-inch thick.
B. Impressed Current Anode Leads: Single-conductor, No. 8 AWG stranded copper with
a 20-mil thick Halar primary insulation and a 65-mil HMWPE outer jacket. Acceptable
anode wire is Rome Halar/HMW Polyethylene Cathodic Protection Cable, as
manufactured by Rome Cable, or approved equal.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 12 of 22
C. Cartridges: Cast iron thermite weld cartridges shall be used for all cast and ductile iron
pipe and fittings. Maximum cartridge size shall be 25 grams for steel and 32 grams for
cast and ductile iron materials, respectively.
B. Cement Mortar Repair Coating Material: Cement mortar in accordance with AWWA
C205.
PART 3 EXECUTION
3.01 GENERAL
A. The installation of the facilities herein specified and described shall conform to the
latest applicable rules and as set forth herein.
1. All drilling operations and reporting requirements shall conform to, as a minimum,
the Washington Water Well Construction Standards WAC 173-160 and WAC 173-
162.
2. Drilling, lowering of anodes, coke breeze placement, and backfilling shall be done
in one continuous operation, and shall be observed by the CONTRACTOR's
Cathodic Protection Specialist.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 13 of 22
3. Drilling and waste disposal shall be done in accordance with the methods and
procedures of the best recognized practices and shall comply with the rules and
regulations of the State and County, or other governing bodies having jurisdiction.
Hole shall be sealed as specified herein or as required by local well drilling
regulations. The most stringent regulations shall apply.
5. At all times during progress of the work, the CONTRACTOR shall protect the well
in such a manner as to effectively prevent tampering or entrance of foreign matter.
B. Drilling:
1. Determine the actual location of the ground bed hole in the field with the
ENGINEER before drilling begins.
2. The hole shall be constructed and casing set round, straight, and plumb.
3. Surface casing shall be set prior to completion of the first 50 feet of the hole.
Casing, other than the surface casing, shall not be installed or left in the hole
unless in the driller's estimation it is necessary for successful completion of the
hole.
4. If steel casing is installed in the active column, it shall be cut below the surface and
the top portion jacked to provide a minimum of 25 feet separation between the
upper casing section and the top of the active column. Cutting and jacking
operations may be completed before or after installation of the anode assembly at
the CONTRACTOR's option. Plastic casing may be installed in the inactive
column, at the CONTRACTOR's option, but shall not extend into the active
column.
C. Test Equipment: Before construction of the deep anode ground bed begins, the
CONTRACTOR shall obtain the following equipment for ground bed logging and
anode resistance measurements: A Nilsson Model 400 4-pin Soil Resistance Meter,
as manufactured by Nilsson Electrical Laboratory, New York, NY.
D. Electrical Logging:
1. Flush the hole and electrically log the hole in the presence of the ENGINEER to
determine the downhole characteristics for optimum anode elevations.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 14 of 22
3. Record the resistance reading and depth from the surface continuously or at 5-foot
increments for the entire hole depth.
4. Based on the results of electrical log data and the driller’s log of soil formations,
the ENGINEER may modify spacing and drilled depth.
5. Submit the results of the electrical log data, in writing, to the ENGINEER.
E. Lowering of Anodes:
1. Each anode wire will be inspected along its entire length by the ENGINEER prior
to placement in the anode well. The terminal end of the wires shall be identified
with weather-proof 3M marking tape, or by other approved method, before
lowering the anodes into the hole.
2. Lowering of the anodes shall be done after the drilling is completed. Actual
lowering of the anodes and backfilling with coke breeze shall be observed by the
ENGINEER.
3. Installation of the anodes and coke breeze shall be performed on the same day as
the completion of the drilling and electrical logging.
a. If steel casing is used and extends into the active column, the anode
centralizers shall be electrically isolated from the casing by a method
approved by the ENGINEER.
b. Anode centralizers shall have no sharp edges that can damage wire
insulation. Tape or otherwise cover sharp edges of centralizers, as approved
by the ENGINEER.
5. Install anodes and vent pipe in the drilled hole using methods previously approved
by the ENGINEER. No deep anode cathodic protection components shall be
installed prior to approval of the installation method by the ENGINEER.
6. Vent pipe couplings shall be attached to the vent pipe using a method approved by
the ENGINEER. The CONTRACTOR shall maintain the structural integrity of the
vent pipe when lowering the deep well anodes.
7. Any damage to anodes or cut, gouged, or scraped wire insulation will not be
acceptable. No splices to anode wires will be allowed.
8. If the hole is drilled with mud, it shall be flushed with clean water in a continuous
process before or after the anodes are lowered, at the CONTRACTOR's option,
until the return fluid is sufficiently clear to allow proper installation and settlement
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 15 of 22
of the coke breeze. The ENGINEER shall inspect the return fluid before the coke
breeze installation will be permitted to begin.
1. The hole shall remain full of water during installation of the coke breeze.
2. Prepare a coke breeze slurry with water in accordance with the manufacturer's
written recommendations. The coke breeze slurry shall be pumped into the hole at
high pressure through an additional plastic pipe supplied by the CONTRACTOR.
Pump the coke breeze in an even and continuous manner from the bottom of the
hole to the top elevation as the plastic pipe is slowly withdrawn.
3. CONTRACTOR shall collect water that is displaced from the ground bed hole
during coke breeze installation. Dispose of water in accordance with local, state,
and federal regulations.
5. In the event that voids or bridging occurs during introduction of the coke breeze,
the operation shall cease until the voids have been eliminated. The
CONTRACTOR shall correct the deficiency to the satisfaction of the ENGINEER.
6. The CONTRACTOR shall allow the coke breeze to settle for 12 hours before
installation of the permanent well seal. After 12 hours, the depth of the coke
breeze shall be measured and additional coke breeze added to plan elevation, as
required.
G. Placement of Seal:
1. Place seal by pumping or forcing material from top of gravel backfill to within 18
inches of finished grade. Place seal in such a manner that ensures entire filling of
the space in one continuous operation.
2. Install sealing material in the annular space between the casing and the soil.
H. Anode Wire Termination: The CONTRACTOR shall cut a smooth hole in the side of
the casing for routing wires to the anode junction box. Install a rubber grommet or pipe
with plastic bushings on both ends in the hole to prevent damage to the wire insulation
by the casing.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 16 of 22
I. Ground bed and Vent Pipe Termination: Place vent pipe through well cap, and
connect the steel portion of the vent pipe to the plastic vent pipe with the appropriate
threaded coupling, 6 inches minimum below grade. Place well cap in casing and
torque bolts in accordance with the manufacturer's recommendations.
J. Secure the anode vent pipe to a Unistrut support located at the back of the rectifier.
A. General
1. The existing header cables are connected to existing graphite anodes per CH2M
plan S7855.6 dated 10/31/73. A total of 49 anodes were installed in the space
between Cedar River Pipelines (CRPL’s) No. 1,2 and 1,3 using 4 separate header
cables. The intent of this contract is to make use of the existing header cables for
connecting the new anodes to the existing rectifier.
1. Connection of new anodes to existing (or replaced) header cable shall be made by
removing the existing header cable insulation for a length necessary to make the
electrical connection without damaging existing wire strands.
3. Lowering of anodes into drilled holes shall be per industry standard and comply
with anode manufacturer recommended handling procedures. Addition of coke
breeze shall be accomplished while maintaining centering of the anode in the
drilled hole.
4. The assigned CP specialist shall submit an installation plan for approval by SPU
describing the following:
c. Include material submittals for all other materials proposed for this work.
B. Connect the grounding conductor to the rectifier case using the grounding lug
provided by the rectifier manufacturer.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 17 of 22
B. Take care to avoid damage to existing structures and utilities during excavating and
trenching process. Cathodic protection excavations and cable trenches shall be in the
general location and route as shown. CONTRACTOR may modify location as
approved by the ENGINEER as required to minimize possible damage to existing
structures. Trench shall be of uniform depth and width, level, smooth, and free of
sharp objects. Hand trenching may be required in some areas to avoid damage to
existing structures.
C. Sheet and brace excavations and trenches as necessary to prevent caving during
excavation in unstable material, or to protect adjacent structures, property, workers,
and the public.
D. Place 3 inches minimum bedding below pipe or conduit, and pipe zone material to 6
inches above pipe or conduit. Thoroughly tamp each lift with handheld tamping bar or
other approved mechanical means so no subsequent settlement will occur. Bedding
and pipe zone materials shall meet the following requirements:
1. Sand, clean or clean to silty, less than 12 percent passing No. 200 sieve.
4. If more than 5 percent passes No. 200 sieve, the fraction that passes No. 40 sieve
shall be nonplastic as determined in accordance with ASTM D4318.
E. Backfill trench above the pipe zone with excavated backfill materials, tamp, and
compact so that no subsequent settlement will occur. Do not use backfill material of
frozen or consolidated debris. Leave the trench with the excess backfill material neatly
mounded not more than 4 inches above the existing ground level for the entire width
of the trench.
B. Grind all rough spots or sharp edges or steel posts. Solvent clean (SSPC SP-1) and
coat with 1 coat of rust inhibitive primer and two coats of yellow alkyd enamel paint.
Total coating system shall be 6 mils dry film thickness, minimum.
3.07 CONDUITS
A. Unless otherwise noted on the Drawings, all conduits shall be PVC coated rigid
galvanized steel.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 18 of 22
B. Conduit shall be sized in accordance with the NEC and shall be of such size and so
installed that conductors may be drawn in without injury or excessive strain.
C. Conduits entering cabinets, junction boxes, or terminal boxes shall be secured with
conduit hubs.
D. Install insulated bushings and insulated throat connectors on the ends of all rigid
metallic conduit.
E. Use watertight couplings and connections. Install and equip boxes and fittings to
prevent water from entering the conduit or box. Seal all unused openings.
B. Label wires in the terminal box with heat-shrink tags identifying the anode number and
rectifier lead. Connect numbered anodes in consecutive order to anode terminals
starting with number 1 at the top left hand side. Maintain sufficient slack to keep the
wire from being unduly stressed, damaged, or broken during backfill.
B. Rectifier wire from the rectifier negative terminal shall be installed to the pipeline.
Rectifier wire from the rectifier positive terminal shall be installed to the anode terminal
box.
C. Provide the ENGINEER with 10 working days prior notice to the completion of the
rectifier, ground bed, and AC power service installation to allow scheduling of the
required energizing and testing.
B. Coordinate installation of the electrical power service with Puget Sound Energy. The
CONTRACTOR shall pay for all electrical utility connection fees and inspection
services that may be required. At Beacon/119th provide new AC service from existing
power pole through 2” conduit to the new meter and AC disconnect on the new
rectifier. Existing rectifier to receive power through a 1” conduit from the new rectifier
crossing Beacon Ave. Coordinate installation of the electrical service with Seattle City
Light.
C. The service disconnect shall be grounded with a minimum of two ground rods placed
at least 8 feet apart near the pad, per Puget Sound Energy requirements and NEC.
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 19 of 22
The top of the ground rods shall be covered with a ground rod handhole in
accordance with City of Seattle Standard Plan No. 550b.
B. No wire bend shall have a radius of less than 8 times the diameter of the wire. Copper
or bronze offset pressure tongue with hex head solderless lugs shall be used to make
all cable connections to terminal studs.
C. No wire shall be drawn into conduit until conduit system is complete. Lubricant shall
be approved by wire manufacturer.
D. Arrange conductors neatly in rectifier and junction or terminal box. Cut to proper
length, remove surplus wire, and attach terminal or connect to appropriate junction
box or rectifier terminal.
E. Seal all below ground conduit to prevent intrusion of foreign material after wire is in
place.
F. Direct buried rectifier shall be 36 inches deep, minimum, below finished grade. All
wires shall be free of splices, except those approved by the ENGINEER.
G. Bury warning tape approximately 12 inches above all underground rectifier conductors
and conduits. Align parallel to and within two inches of the centerline of the conduit or
conductor run.
B. Before the connection is made, the surface shall be cleaned to bare metal by making
a 2-inch by 2-inch window in the coating, and then filing or grinding the surface to
produce a bright metal finish. Use grinding wheels that do not leave residual material
on metal surface that could affect thermite weld, as approved by the thermite weld
manufacturer. The prepared metal surface shall be dry.
C. Wire sleeves shall be installed on the ends of the wires before welding to the metal
surface. Thermite welding shall be performed in strict accordance with the
manufacturer's written instructions. After the weld connection has cooled, remove slag
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 20 of 22
and physically test wire connection by tapping with a hammer; remove and replace
any defective connections.
D. For thermite weld connections to concrete cylinder pipe, clean surfaces in accordance
with SSPC SP1 and apply epoxy repair coating. After the epoxy coating has dried
sufficiently, cover the connection with 3/4 inch to 1 inch of cement mortar. Repair
coatings shall placed over all exposed steel where cement mortar was removed. For
thermite weld connections to manholes or other pipe surfaces not coated with cement,
extend the repair coatings a minimum of 2 inches from all edges of the completed
thermite weld. As an alternative to the methods described above for sealing of
thermite welds, see Section 16641, 2.08 THERMITE WELD CAPS and 2.09 PIPE
AND FITTING COATING REPAIR MATERIAL.
b. Test for grounds in each circuit, which consists of the physical examination of
the installation to ensure that all required ground jumpers, devices, and
appurtenances do exist and are mechanically firm, meeting the requirements
of Article 250 of the NEC.
2. All systems shall be run under operating conditions for a minimum of 1 month to
ensure their acceptability prior to the Completion Date.
D. Reports:
Job No/####
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SECTION 26 42 00
Project Name Page 21 of 22
1. After completion of all tests and inspections, the Cathodic Protection Specialist will
provide a detailed report of deficiencies to the CONTRACTOR. The
CONTRACTOR shall make all repairs necessary to correct these deficiencies at
the CONTRACTOR’s sole expense.
2. The CONTRACTOR’s Cathodic Protection Specialist will retest items that have
been repaired by the CONTRACTOR. All testing, deficiencies, and corrections
shall be summarized in a report and submitted to the OWNER.
E. After the CONTRACTOR's Cathodic Protection Specialist has tested and verified
proper installation of all cathodic protection facilities, the Cathodic Protection
Specialist and ENGINEER will energize, test, and adjust the system. Any construction
defects identified during these tests shall be located and corrected by the
CONTRACTOR.
END OF SECTION 26 42 00
Note: The blue note text will not appear when you print the document. Delete these tags and narration
before issuing the specification
Job No/####
SUMMARY SHEET
Section number: 26 42 01
WARNING: The standards and guidelines do not relieve licensed engineers from their
responsibilities as outlined by the code of ethics and rules of practice. All specifications require
editing and review by the project's licensed engineer and must be tailored to the conditions and
needs of the project. The guidelines provide policy, clarity, and advice on how design should be
conducted by and for Seattle Public Utilities. However, it remains the responsibility of the
licensed engineer to properly interpret and apply the guidelines as appropriate to meet the
needs of the project. If these standards and guidelines contain any contradictions with other
standard engineering practices, the licensed engineer is responsible for identifying and
resolving them.
This Section covers the work necessary to furnish and install test stations to provide for
monitoring of system performance. Both in-ground, at grade and above ground post mounted
are described in this specification.
Note: This specification will be revised in the next version (v.3) of the Design Standards and Guidelines
(DSG). This should be considered a starting point for a specification for a generic impressed current
cathodic protection system.
Note: All specifications are edited for project-specific requirements.
Document Processing: You must have the paragraph button (¶) selected from the HOME tab on
the toolbar in order to see the blue note text. This text is only for the specification writer, It
should be deleted from the document.
TEST STATIONS SECTION 26 42 01
Project Name Page 1 of 8
PART 1 GENERAl
1.02 SUMMARY
Note: This Section will be revised in the next version (v.3) of the Design Standards and Guidelines
(DSG).
A. Section includes:
1.
1.03 DEFINITIONS
A. The following definitions are used throughout the Bid Documents:
1. Ferrous Metal Pipe: Any pipe made of steel or iron, or pipe containing steel or iron
as a principal structural material, except reinforced concrete pipe.
2. Foreign Owned: Any buried pipe or cable not specifically owned or operated by the
OWNER.
3. Lead, Lead Wire, Joint Bonds Cable: Insulated copper conductor; the same as
wire.
5. Electrical Isolation: The condition of being electrically isolated from other metallic
structures (including, but not limited to, piping, reinforcement, casings, etc.) and
the environment as defined in NACE Standard RP0169-83.
1.04 SUBMITTALS
A. Provide catalog cuts and other information for all materials that show compliance of
those materials with these Specifications. The Contractor shall also provide submittals
for the test equipment.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 2 of 8
B. Serving Utility: [Seattle City Light, 700 5th Avenue, #3200, Seattle, WA 98104, John
CommercialRep, 206-684-3000, John.CommercialRep.scl@seattle.gov]
1.06 COORDINATION
??
PART 2 PRODUCTS
2.01 GENERAL
A. The use of a manufacturer's name and model or catalog number is for the purpose of
establishing only the standard of quality and general configuration desired. Products of
other manufacturer's will be considered.
B. Test Stations: Single-conductor, No. 10 AWG stranded copper with 600-volt XHHW,
RHW, RHH, TW, or THWN insulation and single conductor, No. 12 AWG and No. 6
AWG stranded copper with 600-volt HMWPE insulation. Insulation color shall be as
shown.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 3 of 8
b. Wire: No. 14 RHH-RHW wire with yellow insulation. The wire shall be attached
to the electrode and insulated with the manufacturer’s standard connection.
Connection shall be stronger than the wire.
2. Backfill shall consist of 75% gypsum, 20% bentonite and 5% sodium sulfate.
B. PVC Conduit and Fittings: Schedule 40, UL listed for direct burial. Conduit and fittings
shall meet the requirements of NEMA TC and TC3, Federal Specification W-C-1094,
UL, and NEC.
C. Conduit shall be sized in accordance with the NEC and shall be of such size and so
installed that conductors may be drawn in without injury or excessive strain.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 4 of 8
C. Adapter Sleeves: Provide for all wire sizes. Prefabricated factory sleeve joint bonds or
bond wires with formed sleeves made in the field are acceptable.
D. Field-formed joint bonds sleeves shall be attached with the appropriate size and type of
hammer die provided by the thermite weld manufacturer.
E. Cartridges: Cast iron thermite weld cartridges shall be used for all cast and ductile iron
pipe and fittings. Maximum cartridge size shall be 25 grams for steel and 32 grams for
cast and ductile iron materials, respectively.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 5 of 8
PART 3 EXECUTION
3.01 GENERAL
A. Whenever the requirements of the Specifications or Drawings exceed those of the
codes or manufacturer's instructions, the requirements of the Specifications or
Drawings shall prevail. Where a larger size or better grade of material or a higher
standard of workmanship is required, the most stringent requirement shall apply.
B. Test wires shall be attached to the pipe as specified under WIRE CONNECTIONS, this
Section.
C. Test and reference electrode wires shall be buried a minimum of 36 inches below
finished grade.
D. Wire connections to test station terminals shall be with crimp-on spade lug terminals,
except where solid wire is specified.
E. Install concrete marker post at each test station location. Marker posts shall extend 3
feet below grade. The marker posts shall show test station and pipeline station. Locate
marker post at the edge of the right of way or where designated by the Engineer.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 6 of 8
B. Before the connection is made, the surface shall be cleaned to bare metal by making a
2-inch by 2-inch window in the coating, and then filing or grinding the surface to
produce a bright metal finish. The use of a resin, rubber, or shellac impregnated type
grinding wheels will not be acceptable. The prepared metal surface shall be dry.
C. Wire sleeves shall be installed on the ends of the wires before welding to the metal
surface. Thermite welding shall be performed in strict accordance with the
manufacturer's written instructions. After the weld connection has cooled, remove slag
and physically test wire connection by striking a glancing blow with a 16oz. hammer;
remove and replace any defective connections.
D. Install a prefabricated thermite weld cap over each completed connection. All exposed
metal surfaces not covered by the thermite weld cap shall be repaired in accordance
with the coating manufacturer's recommendations. All damage to the pipe lining shall
be repaired in accordance with the lining applicator's recommendations. Thermite weld
cap shall be adhered to pre-primed and tack dry surface in accordance with the
manufacturer's instructions.
2. A Model 87 Digital Multimeter with case and test leads, as manufactured by Fluke
Corporation, Everett, WA; or approved equal.
Job No/####
TEST STATIONS SECTION 26 42 01
Project Name Page 7 of 8
B. The test equipment shall be stored at the project site for the Contractor’s use and shall
be maintained in accurate, working condition at all times. The test equipment shall be
available to the Engineer for testing purposes.
3.08 TESTING
A. After the Physical Completion Date, the Contractor’s Cathodic Protection Specialist
shall test the pipeline to ensure proper installation and operation of the test stations.
Any construction defects identified during testing shall be located and corrected by the
Contractor. These tests shall be made in the presence of the Engineer. Provide the
Engineer with three days advance notice before beginning tests. All test data shall be
recorded and submitted to the Engineer.
2. Test all test station wire connections prior to AND after backfill AND prior to any
required paving.
3. Test after final termination and record values as “native” readings prior to
energization of the cathodic protection systems.
END OF SECTION 26 42 01
Note: The blue note text will not appear when you print the document. Delete these tags and narration
before issuing the specification
Job No/####