SINEAX TV804 Installation instructions
CURRENT CONVERTER The module is designed to be mounted on a DIN 46277 rail, in vertical
position.
WITH GALVANIC SEPARATION 163 056 10.14 To obtain an optimal working and duration, it is necessary to assure an ade-
quate ventilation to modules, avoiding to place raceways or other objects that
can close abat-vents
General characteristics
Avoid to mount modules over deviced that generate heat; we suggest to mount
• Input current 0…20 mA or 4…20 mA devices in the lower side of the panel.
• Sensors supply in two wires technique: 20 V DC stabilized, 20 mA max.,
protected against short circuit. Severe operating conditions
• Measure and retransmission or an analog insulated output, current output Severe operating conditions are as follows:
0…20 mA or 4…20 mA.
• High power voltage (> 30 V DC / > 26 V AC)
• Indication on the front if there is power supply. • Input sensor feeded
• Insulation 3 wires: 1500 V AC. • Use of output in impressed current
When modules are put side by side its possible that it is necessary to sepa-
rate them at least 5 mm in the following cases:
Technical data • Upper board temperature higher than 45 °C and at least one of the heavy
Power 9…40 V DC, 19…28 V AC, 50…60 Hz, max. 2.5 W working conditions verified.
• Upper board temperature higher than 35 °C and at least two of the heavy
Input Current: 0…20 mA or 4…20 mA, input impedance 20 Ω
working temperature verified.
Current: 0…20 mA or 4…20 mA,
Output
max. loop impedance 600 Ω
Electrical connections
Temperature: 0…50 °C, humidity min. 30%, max. 90%
Environmental conditions at 40 °C not condensing (see also section “Installation We recommand to use shielded cables to do signals connection; monitor must
instruction”) be connected to a preferential ground for devices. Besides it is a good rool
avoid to pass wires near power installation cables like inverters, motors, in-
Errors referred to input’s Calibration Thermal coefficient Linearity
duction furnaces etc..
measure range 0.5% 0.02% / °C 0.05%
Inputs protection Current 100 mA, continuative
Protection Dimensions
Against pulses overvoltages 400 W/ms
output / power supply
Standards: Complying equipments with prescriptions:
EN 50081-2 (electromagnetic compability, industrial
environnement)
EN 50082-2 (electromagnetic immunity, industrial
environnement)
112 mm
Electrical connections
Power
Power voltage must be in a range from 9 to 40 V DC
9 - 40 VDC (indifferent polarity) from 19 to 28 V AC; see also sec-
19 - 28 VAC tion “Installation instructions”.
Upper limits must not be exceeded, if it happen 17.5 mm
there could be damages for module.
It is necessary to protect power source from possible
2 3 modules failure by fuse correctly dimentioned.
100 mm
Input
7 8 9 Active input
Connection to be used with transducers 2 wires tech-
nology.
mA – Transducer is directly powered by module 20 V DC
stabilized voltage, 20 mA max., protected against
+
short circuit.
7 8 9
Passive input
Connection to be used if input current is given from
mA –
external (loop power supply is given from external).
Disposal of Electrical & Electronic Equipment (applicable throughout the
+
European Union and other European countries with separate collection
programs).
Output This symbol found on your product or on its packaging, indicates that this
product should not be treated as household waste when you wish to dis-
+
Active output pose of it. Instead, if should be handed over to an applicable collection
Connection to be used when output loop is to be point for the recycling of electrical and electronic equipment. By ensuring
mA
– directly feeded from module. this product is disposed of correctly, you will help prevent potential negative
consequences to the environment and human health, which could other-
Loop power supply given by modules is protected
wise be caused by inappropriate disposal of this product. The recycling of
4 against short circuit. Max. load resistance 600 Ω.
5 6 materials will help to conserve natural resources. For more detailed infor-
mation about the recycling of this product, please contact your local city
+
office, waste disposal service or the retail store where you purchased this
– product.
mA Passive output
Connection to be used if current loops power supply
Tel. +41 56 618 21 11
is given from external.
Camille Bauer Metrawatt AG Fax +41 56 618 21 21
4 5 6 Aargauerstrasse 7 info@cbmag.com
CH-5610 Wohlen/Schweiz www.camillebauer.com
SINEAX TV804 ENGLISH 1/2 SINEAX TV804 ENGLISH 2/2