Air Drier
Air Drier
O11100000009I
                             03.2019
EN – Compressed Air-Dryer
BURAN
DC 0020 AB – DC 0850 AB
Type Code
Series BURAN
                                                                                         50-60 Hz
                           DC 0050 AB       1112 A               1CY1112000009I
                           DC 0065 AB       1113 A               1CY1113000009I
                           DC 0085 AB       1114 A               1CY1114000009I
                           DC 0105 AB       1115 A               1CY1115000009I
                           DC 0125 AB       1116 A               1CY1116000007I
                           DC 0150 AB       1117 A               1CY1117000007I
                           DC 0180 AB       1118 A               1CY1118000007I
                           DC 0225 AB       1119 A               1CY1119000007I
                           DC 0300 AB       1120 A               1CY1120000007I
                                                                                         50 Hz
                           DC 0360 AB       1121 A               1CY1121000007I
                           DC 0450 AB       1122 A               1CY1122000007I
                           DC 0550 AB       1123 A               1CY1123000007I
                           DC 0650 AB       1124 A               1CY1124000007I
                           DC 0750 AB       1125 A               1CY1125000007I
                           DC 0850 AB       1126 A               1CY1126000007I
                           DC 0125 AB       1116 A               1CY1116000008I
                           DC 0150 AB       1117 A               1CY1117000008I
                           DC 0180 AB       1118 A               1CY1118000008I
                           DC 0225 AB       1119 A               1CY1119000008I
                           DC 0300 AB       1120 A               1CY1120000008I
                                                                                         60 Hz
                           DC 0360 AB       1121 A               1CY1121000008I
                           DC 0450 AB       1122 A               1CY1122000008I
                           DC 0550 AB       1123 A               1CY1123000008I
                           DC 0650 AB       1124 A               1CY1124000008I
                           DC 0750 AB       1125 A               1CY1125000008I
                           DC 0850 AB       1126 A               1CY1126000008I
Technical modifications are subject to change without notice; errors not excluded.
                                          EN_2
                                                                         Table of contents
                                                                                    Page
Type code                                                                           EN_2
Part 1   Important user information   1.1   General Notes                           EN_4
                                      1.2   Legal requirements for the user         EN_5
                                      1.3   Safety regulations                      EN_6
                                      1.4   Refrigerant handling                    EN_7
All safety notes in this operating instruction which may cause harm to personnel or
equipment, when ignored, are marked by the following symbols:
                                            EN_3
Part 1                   Important User Information
                                       EN_4
                                Important User Information                             Part 1
1.2.2   Check of working         • Before starting the CA-Dryer, the user has to check the
        materials                  working materials and record this accordingly.
1.2.3   Periodical checks        • The user of the CA-Dryer has to find out the test periods
                                   of the complete unit and the unit parts on base of a safety
                                   related technical evaluation.
1.2.4   Instruction EN 378-1     • The user has to provide the instructions for the operators
                                   as well as their information of the used working media. A
                                   yearly instruction is mandatory.
                                           EN_5
Part 1                        Important User Information
                              Attention!
                              The operator has to observe the national working-, operating-
                              and safety regulations. Also existing internal factory regulations
                              must be met.
                              Maintenance and repair work must only be carried out by
                              specially trained personnel and, if necessary, under supervision
                              of a person qualified for this work.
                              Attention!
                              All maintenance and repair works must only be executed at
                              stopped machine, disconnected power supply and pulled mains
                              plug. Ensure that the CA-dryer cannot be switched on by
                              mistake.
                                           EN_6
                                 Important User Information                               Part 1
                                  R32/125/134a (23/25/52)
           R407C – HFC                                                1000 ppm        1773.85
                                  CHF2CF3/CH2F2/CH2FCF3
                                           EN_7
Part 1                         Important User Information
1.5.2    After inhaling:       •   Bring casualty into the fresh air, keep him warm, and let him
                                   relax.
                               •   At breathlessness: Oxygene therapie
                               •   At apnoea: Resuscitation
                               •   Mouth-to-nose resuscitation, mouth-to-mouth resuscitation
                                   or with equipment.
                               •   Medical treatment necessary
1.5.3    After skin contact:   •   At skin contact, clean with water and soap immediately.
                               •   After contact with the fluid, undercooled skin areas must be
                                   cooled with warm (not hot) water.
1.5.4    After eye contact:    •   Flush well opened eye with running water for at least 10
                                   minutes.
                               •   Contact doctor.
1.5.5    Notes for the         •   Inform doctor about the used refrigerant.
         doctor:               •   After inhalation, deep breathing of a corticoid emulsive
                                   dosing aerosol (e.g. Ventolair) as soon as possible.
                               •   Prohobition of using adrenergic drugs.
                               •   Prophylactic pulmonary edema after inhalation of
                                   decomposition products / fire gases
1.6      Disposal              •   When disposing of used devices, pay attention to oil and
                                   refrigerant in the hermetical sealed refrigerating circuit of
                                   CA-dryers. Therefore, before dismounting, these operation
                                   media must be disposed by a special company.
                               Attention!
                               Do not dispose waste oil into the environment. Do not mix with
                               household rubbish and do not burn it unauthorized plants.
                                             EN_8
                                                      Installation                          Part 2
2.2    Requirements on            At the site of installation, the CA-dryer can be installed without
       the place of               anchorage or special foundation at the location desired.
       installation               The CA-dryer is provided for an ambient temperature of 25 °C.
                                  Attention!
                                  To avoid corrosion on components of the CA-dryer the
                                  compressed and ambient air must be free of aggressive parts.
                                  The CA-dryer are provided for inside mounting.
                                  Deviating conditions require the consultation of the
                                  manufacturer.
                                  Attention!
                                  At different ambient conditions pay attention to the layout data!
2.3    Installation               The CA-dryer must be installed that accessibility to the front
       (mounting)                 panel is ensured. Furthermore leave space for service purposes
                                  on both sides of the CA-dryer (fig.2.3a).
                                  Wall mounting is possible with types 1110A-1116A (fig.2.3b).
                                               EN_9
Part 2                         Installation
2.3.1    Version air cooled    The cooling air is sucked in by the refrigerant condenser (Apx
                               1/3) and discharged at the right side (Apx 1/4). Both areas must
                               be kept free and must non be obstructed.
2.4      Compressed air        The connection must be executed acc. to marking at the CA-
         connection            dryer (Apx 1/1 + 1/2).
                               For service purposes the installation of a bypass line in
                               recommended (additional equipment).
                               Attention!
                               Before mounting the CA-dryer, welding residual, rust or other
                               pollution must be removed from the pipelines to be connected. If
                               pollution cannot be excluded, proper filter system must be
                               installed.
                               The compressed air pipes must be installed stress-free.
                               Expansion joints are recommended in case of vibrations and
                               pulsations.
                               CA-dryer must only be operated within the temperature and
                               pressure limits stated on the nameplate.
                               Prior to use, the user must fit safety / pressure relief devices on
                               the CA-system.
2.5      Electric connection   The CA-dryers are completely equipped and wired. They merely
                               have to be connected to a power supply. The CA-dryer are to be
                               protected by slow-blow fuses as defined in the wiring diagram.
                               Operating voltage: according to name plate data.
                                              EN_10
                                                   Installation                          Part 2
2.6     Connection            A hose already pre-mounted at the condensate drain leads the
        condensate drain      condensate out of the CA-dryer (Apx 1/5). A connection by the
                              costumer has to be carried out corresponding to the local
                              conditions.
                              Attention!
                              Route outflow so that persons or objects will not be struck by
                              condensate (condensate outlet at operating pressure)!
2.6.1   Connection            The condensate drain pipe (fig.2.6/1) may be fixed to the wall
        condensate            with a rising slope of maximum 5m. thereby the minimum
        draining              operating pressure increases for 0,1 bar per meter. The
                              collecting pipe (fig.2.6/2) has to have at least the cross-section
                              of the condensate outlet.
Fig.    Connection
2.6     condensate draining
                                           EN_11
Part 3                        Description
3.3      Unit Layout          See Appendix Apx 1 for CA-dryer components which are
                              accessible from outside.
3.3.1    Symbols
                                   Compressed air inlet
Condensate drain
3.4      Electronic     The electronic regulator DDS7 is a controller specially designed for
         regulator      CA-dryers. It operates on the basis of the micro processors and
                        performs three functions:
                        - Pressure dew point display
                        - Pressure dew point alarm
                        - Refrigerant condenser fan control
Fig.     Symbols                                         2   3 4
3.4      electronic
         regulator
                                                                     ON
                                                  set
                                     PQS0085_1
                                                  8      1   5   7        6   9
                        1    10x Led green : Pressure dew point indication
                        2    Green area : Pressure dew point normal
                        3    Red area : Pressure dew point high
                        4    Led green : CA-dryer on
                        5    Led red : ALARM active
                        6    Led yellow : DRAIN MAINTENANCE required
                        7    Led yellow : FAN - refrigerant condenser fan ON
                        8    Set key
                        9    Up key
                                                 EN_12
                                                Description                           Part 3
3.5     Nominal power of     The nominal power of the CA-dryer mentioned in the technical
        CA-dryer             data is related to a working pressure of 7 bar, a compressed air
                             inlet temperature of 35 °C as well as an ambient temperature of
                             25 °C acc. to ISO 7183.
                             Lower working pressure, higher compressed air inlet
                             temperature and/or higher ambient temperatures overload the
                             compressor which causes to an increased pressure dewpoint
                             and the compressor can be stopped by internal safety devices.
                             At essentially deviating operating conditions, contact the
                             deliverer of the CA-dryer for support.
3.7.2   Refrigerant side     The refrigerant is injected into the refrigerant-to-air heat
                             exchanger where it evaporates, thereby the compressed air is
                             cooled. The hot gas by-pass valve regulates the cooling
                             temperature and keeps the pressure dew point constant in
                             nearly all capacity stages. The refrigerant compressed by the
                             motor compressor is condensed within the condenser and is
                             available for the evaporation again.
3.7.3   Pressure dew point   Any compressed air dryer can be operated under partial load
        control              due to lower compressed air flow or lower compressed air inlet
                             temperature in the range of 0 to 100% load in permanent
                             operation.
                                         EN_13
Part 3                       Description
- Malfunction / Alarm.
                                           EN_14
                                                             Operation                     Part 4
4.1     Commissioning           After installation the CA-dryer is supplied with power via the
                                power cable or by operating the main switch (Apx 1/6).
                                Attention!
                                Before operating the operation switch (Apx 1/6), a waiting
                                period of at least 6 hours is absolutely necessary.
4.2     Starting                The CA-dryer is switched on via operation switch (Apx 1/6).
                                After approx. 5 minutes the compressed air admission is
                                possible by connecting the compressed air compressor.
                                The CA-dryer is designed for continuous operation and may
                                remain switched on during periods of no load, as it adapts to the
                                required performance automatically.
4.3     Operation               Operation is indicated by the led “ON” of the electronic regulator
                                (fig.4.3/4)
                                The pressure dew point indication (fig.4.3/1) is showing the
                                pressure dew point reached by the CA-dryer.
                                                       set
                                         PQS0085_1
                                                        8     1    5     7        6   9
                               1. Keep pressed SET key (8) for 2 seconds to change from
                                  display into setup mode, then release it.
                               2. First data is ALARMON, shortly press SET key (8) to go to
                                  data DRAINMAINTENANCE, shortly press SET key (8) to return to
                                  data ALARMON.
                               3. In order to adjust actual data, keep pressed SET key (8) and
                                  press UP key (9).
                               4. During the setup, led flashing will identify which data is
                                  displayed :
                                  - led ON (4) and ALARM (5) flashing = ALARMON data
                                  - led ON (4) and DRAIN MAINTENANCE (6) flashing =
                                  DRAINMAINTENANCE data
                               5. Setup exit is automatic after 2 minutes or by pressing UP key
                                  (9).
                                                     EN_15
Part 4                     Operation
                                DRAINMAINTENANCE
                                It defines the action of alarm contact when DRAIN MAINTENANCE
                                time is expired (factory setting 8000 hours).
                                - 1st led of dew point indication bar ON = alarm contact
                                switches at expiring of maintenance time.
                                - 2nd led of dew point indication bar ON = alarm contact does
                                not switch at expiring of maintenance time (factory setting).
4.3.3    Electronic regulator   This function shows the total operating hours of the dryer
         - Hour counter         through the dew point indication bar (max displayable value
                                99900 hours).
                                - Keep pressed both SET key (8) and UP key (9) for 5
                                seconds, then release them.
                                - Led ON (4) is lit and a certain numbers of leds of dew point
                                indication bar are light up. The number of leds lit define the
                                1st digit of hour counter (ie : n.0 leds lit → 1st digit =0)
                                - Press UP key (9)
                                - Led ALARM (5) is lit and a certain numbers of leds of dew
                                point indication bar are light up. The number of leds lit define
                                the 2nd digit of hour counter (ie : n.3 leds lit → 2nd digit = 3)
                                - Press UP key (9)
                                - Led DRAIN MAINTENANCE (6) is lit and a certain numbers of
                                leds of dew point indication bar are light up. The number of
                                leds lit define the 3rd digit of hour counter (ie : n.8 leds lit →
                                3rd digit = 8)
                                Total operating hours : 0 3 8 x 100 (fixed multiplying ratio) =
                                3800 hours
                                - Press UP key (9) repeatedly to scroll the displaying of 3
                                digits again.
                                - The exit of hour counter is automatic after 30 seconds or by
                                pressing SET key (8).
                                         EN_16
                                                Operation                            Part 4
4.3.4   Electronic regulator   This function shows the elapsed time from last reset of timer
        - Drain                dedicated to DRAIN MAINTENANCE (factory setting 8000 hours).
        maintenance timer      The elapsed time is shown through the dew point indication
                               bar.
                               - Keep pressed UP key (9)
                               - Led DRAIN MAINTENANCE (6) is lit and a certain numbers of
                               leds of dew point indication bar are light up. Each led define
                               a range of elapsed hours from last reset.
                               - 1st led = 0…800 hours
                               - 2nd led = 801…1600 hours
                               - 3rd led = 1601…2400 hours
                               - 4th led = 2401…3200 hours
                               - 5th led = 3201…4000 hours
                               - 6th led = 4001…4800 hours
                               - 7th led = 4801…5600 hours
                               - 8th led = 5601…6400 hours
                               - 9th led = 6401…7200 hours
                               - 10th led = 7201…8000 hours
                               - 10th led flashing = >8001 hours
                               ie : 5500 hours are passed from last reset of timer, leds 1…7
                               are lit.
                               - Release UP key (9) to return to dew point displaying.
                               After expiring time (8000 hours) leds 1…10 are lit and DRAIN
                               MAINTENANCE is triggered. Contact the SERVICE CENTER for
                               reset.
4.4     Stopping               At standstill periods, the CA-dryer is switched off with the
                               operation switch (Apx 1/6).
                               For longer standstill periods or service works, the CA-dryer is
                               switched off by pulling the power plug (Apx 1/8).
                                       EN_17
Part 5                    Maintenance
5.1 Maintenance
                               Attention!
                               Prior to any maintenance works all safety regulations for
                               electrical systems and units must be observed (see also
                               part 1).
5.1.3    Yearly maintenance    The led “DRAIN MAINTENANCE” is lit (fig.4.3/6) : replace
         or every 8000 hours   drain service kit, then contact the SERVICE CENTER to reset
         (which comes first)   this warning.
                               If the service kit replacement occurs before led signalling
                               (fig.4.3/6), contact the SERVICE CENTER to reset the timer
                               of drain maintenance.
                               For further information see separate instruction in the service
                               kit.
5.1.4    Periodic checks at    Circuits with refrigerant charge exceeding 5 Tons of CO2
         refrigerant system    equivalent (as stated in the nameplate) are subject to
                               periodic leak tightness check as provided by EU regulation
                               517/2014.
5.1.5    Periodic checks at    CA-Dryers types 1125A and 1126A are included into the
         pressure vessels      pressure vessel guideline category II, fluid group 2 and have
                               a maximum pressure of 14 bar.
                               Periodic checks must be done according to National
                               legislations and the determinations of the user.
                               Attention!
                               Maintenance work must be performed at the depressurized
                               condensate drain only. For this purpose, the installation of a
                               bypass line is recommended.
                                       EN_18
                                              Maintenance                           Part 5
                                         EN_19
Part 5                         Maintenance
                                            EN_20
                                               Maintenance                          Part 5
5.2.8   Safety thermo-       1. CA-dryer volume flow too high  reduce volume flow; 
        switch FTS is           check whether CA-dryer’s capacity is properly selected,
        tripped                 increase CA-dryer’s capacity.
        (type 1120A-1126A)   2. CA-inlet temperature too high  restore normal conditions.
                             3. Ambient temperature too high or the room aeration is
                                insufficient  reduce temperature and/or provide proper
                                ventilation.
                             4. Refrigerant condenser fan is never running  see 5.2.6.
                             5. Refrigerant condenser is polluted  clean condenser.
                             6. CA-operating pressure too low  increase operating
                                pressure;  check whether CA-dryer’s capacity is properly
                                selected, increase CA-dryer’s capacity.
                             7. Leak in the refrigerating fluid circuit  contact service.
                             8. Safety thermo-switch FTS is defective  contact service.
                                   Note: Safety thermo-switch FTS require a reset : press
                                   reset button (fig.5.2.8).
Fig.    Safety thermo-
5.2.8   switch FTS reset
        button
                                          EN_21
Part 5                        Maintenance
5.2.9    Safety high        1. Ambient temperature too high or the room aeration is
         pressure-switch       insufficient  reduce temperature and/or provide proper
         FPA is tripped        ventilation.
         (type 1122A-       2. Refrigerant condenser fan is never running  see 5.2.6.
         1126A)             3. Refrigerant condenser is polluted  clean condenser.
                                  Note: Safety high pressure-switch FPA require a reset :
                                  press reset button (fig.5.2.9).
Fig.     Safety high
5.2.9    pressure-switch
         FPA reset button
5.2.10 Safety low           Leak in the refrigerating fluid circuit  contact service.
       pressure-switch
       FPB is tripped
       (type 1122A-
       1126A)
                                            EN_22
                                                   Maintenance                            Part 5
                              PQS0085_2
                              EIC3 dew point sensor is defective  replace it.
5.2.11.2 Alarm led and
         Fan led are                               ON
         flashing
                                          set
                              PQS0085_3
         display led is
         lighted                          set
                              PQS0085_4
                              Pressure dew point alarm (higher than ALARMON setpoint)  see 5.2.2
                              and 4.3 Note: alarm becomes active 5 minutes later with dewpoint
                              temperature continuously higher than ALARMON setpoint. Alarm
                              automatically reset when dewpoint temperature decrease of 2°K below
                              ALARMON setpoint.
5.2.11.4 Alarm led and
         display 1st (left)                        ON
                              Pressure dew point too low (lower than -1°C)  see 5.2.3        Note:
                              alarm becomes active 5 minutes later with dewpoint temperature
                              continuously lower than -1°C. Alarm automatically reset when dewpoint
                              temperature rise up to >+1°C
5.2.11.5 Display 10th
         (right) led is                            ON
         flashing
                                          set
                              PQS0085_7
                              Pressure dew point over range (higher than 24°C)  see 5.2.2
                              Note: Dew point alarm could occur or not. Alarm becomes active 5
                              minutes later with dewpoint temperature continuously higher than
                              ALARMON setpoint.
5.2.11.6 Alarm led and
         drain                                      ON
         maintenance led
         are flashing                     set
                              PQS0085_6
                                                EN_23
Part 5                        Maintenance
                                           EN_24
                                                                                                                                                                                                                                                                                                                        5.3
                                                                                                                                                     Dryer type
        ID       Ref.             Description
                                                          1110
                                                                 1111
                                                                        1112
                                                                               1113
                                                                                      1114
                                                                                             1115
                                                                                                    1116
                                                                                                           1117
                                                                                                                  1118
                                                                                                                         1119
                                                                                                                                1120
                                                                                                                                       1121
                                                                                                                                              1122
                                                                                                                                                      1123
                                                                                                                                                             1124
                                                                                                                                                                    1125
                                                                                                                                                                           1126
                                                                                                                                                                                  1116
                                                                                                                                                                                         1117
                                                                                                                                                                                                1118
                                                                                                                                                                                                       1119
                                                                                                                                                                                                              1120
                                                                                                                                                                                                                     1121
                                                                                                                                                                                                                            1122
                                                                                                                                                                                                                                   1123
                                                                                                                                                                                                                                          1124
                                                                                                                                                                                                                                                 1125
                                                                                                                                                                                                                                                        1126
                                                                                                                                                                                                                                                                                                                        Spare parts list
EN_25
        9,2     M201              Fan blade                1      1      1      1      1      1      1      1      1      1      1      1      1                                   1      1      1      1      1      1      1
        9,3     M203               Fan grid                              1      1      1      1      1      1      1      1      1      1      1                                   1      1      1      1      1      1      1
         10     F100              Filter drier             1      1      1      1      1      1      1      1      1      1      1      1      1       1      1      1      1      1      1      1      1      1      1      1      1      1      1      1
         12   EIC3-EIC4      Temperature probe             2      2      2      2      2      2      2      2      1      1      1      1      1       1      1      1      1      2      2      1      1      1      1      1      1      1      1      1
         37      EIC5       Pressure transducer                                                                    1      1      1      1      1       1      1      1      1                    1      1      1      1      1      1      1      1      1
         17     EICA         Electronic regulator          1      1      1      1      1      1      1      1      1      1      1      1      1       1      1      1      1      1      1      1      1      1      1      1      1      1      1      1
                                                                                                                                                                                                                                                                                                                                           Maintenance
part is identified with its ID Number and related Spare Part Number.
                                                                                                 m3/h      20         35       50       65         85          105         125     150      180         225     300      360      450    550      650       750       850
          1    Air flow rate
                                                                                                m3/min    0,33        0,58    0,83     1,08        1,42        1,75        2,08   2,50      3,00        3,75    5,00     6,00    7,50    9,17     10,83 12,50 14,17
          2    Cooling air required                                                              m3/h           200                                     300                                       380                     450                 1900          2200      3300
                                                       50Hz                                      kW       0,14        0,17    0,19     0,24        0,28        0,28        0,45    0,47     0,68        0,76    0,71     0,89     0,91   1,11     1,40      1,34      1,70
          3    Power consumption (total)
                                                       60Hz                                       kW      0,16        0,19    0,21     0,28        0,33        0,33        0,55    0,56     0,83        0,84    0,86     1,00     1,10   1,40     1,70      1,72      1,89
                                                       50Hz                                       W              33                                       55                                       95                     76                      175                 410
          4    Power consumption (fan)
                                                       60Hz                                       W              40                                       65                                      110                     90                      230                 410
          5    Power supply                                                                      V / Hz                    1 / 230V / 50-60Hz                                                         1 / 230V / 50Hz or 1 / 230V / 60Hz
          6    Allowable pressure (compressed air)     min. …. max.                               bar                        2 … 16                                                                                  2 … 14
                                                       low pressure side                          bar                                                                                       20,9
          7    Allowable pressure (refrigerant)
                                                       high pressure side                         bar                                         30                                                             39,2                                  30
          8    Compressed air connections                                                          G                          1/2"                                    1"                   1.1/4"                    1.1/2"                          2"
          9    Weight                                                                             kg       26         27       29       31         32          33          34      55        56         57          68    74      116       120   121       155       165
                                                       height                                                                          645                                                              870                                       1055
         10 Dimensions                                 width                                      mm                                   360                                                              480                                       645
                                                       depth                                                                           410                                                              660                                       920
                                                       50Hz                                                                               R134a                                                                                 R407C
               Refrigerant type
                                                       60Hz                                                                               R134a                                                                                 R407C
         11
                                                       50Hz                                       kg      0,17        0,17    0,19     0,20        0,22        0,21        0,24    0,36     0,37        0,41    0,55     0,62     1,00   1,15     1,20      1,65      2,10
                                                                                                                                                                                                                                                                             Technical data
               Refrigerant quantity
                                                       60Hz                                       kg      0,17        0,17    0,19     0,20        0,22        0,21        0,27    0,40     0,40        0,43    0,66     0,66     1,15   1,15     1,00      1,70      1,85
EN_26
         12 Sound pressure level (at distante of 1m)                                             dB (A)                                                                                     < 70
         13 Type of protection                                                                     IP                                                                                        22
         14 Condensate drain                           hose                                       mm                                                                                      D. 8 / 14
        Specification:
                                       Pos.1 :         Air flow rate reffered to the suction status of the air compressor                                                                  +20 °C              1 bar
                                                                               at compressed air inlet temperature                                                                         +35 °C
                                                                               operating pressure
                                                                                                                                                                                                               7 bar
                                                                               ambient temperature
                                                                               pressure dew point at CA-dryer outlet                                                                       +25 °C
                                                                                                                                                                                           +3 °C
                                           EN_27
APX 1.1   1110 A – 1116 A
           EN_28
APX 1.3   1122 A – 1124 A
            EN_29
APX 2.1   1110 A – 1111 A
          EN_30
APX 2.3        1117 A
            EN_31
APX 2.5   1120 A – 1121 A
          EN_32
APX 2.7   1125 A – 1126 A
           EN_33
APX 3.1   1110 A – 1117 A
          EN_34
APX 3.2   1118 A – 1119 A
           EN_35
APX 3.3   1120 A – 1121 A
          EN_36
APX 3.4   1122 A – 1124 A
           EN_37
APX 3.5   1125 A – 1126 A
          EN_38
EN_39
74MD0011A0-EN_01
DDS7