33/11KV Substation Training Report
33/11KV Substation Training Report
REPORT ON
33/11KV SUBSTATION PERAVALI
Submitted in partial fulfillment of the requirement for the award of
DIPLOMA
In
ELECTRICAL AND ELECTRONICS
ENGINEERING
SUBMITTED BY
B V SURYA NARAYANA-21243-EE-005
Under the esteemed guidance of
Mr.D.DHANA PRASAD
Assistant professor
This is to certify that the project report entitled “33/11kv substation peravali is a bonafide
work done by B V SURYA NARAYANA (21243-EE-005)submitted in partial fulfillment of
the requirements for the award of the DIPLOMA in Electrical & Electronics Engineering
during the academic year 2021-2024.The results of investigation closed in this report have
been verified and found satisfactory.
Mr.G.RAMPRADSAD,M.Tech
(INCHARGE OF POLYTECHNICE COLLEGE) EXTERNAL EXAMINER
ACKNOWLEDGEMENT
I would also like to thank Dr. G.V.N.S.R. Ratnakara Rao, B.E, M.E, Ph.D
Principal of our college for his constant support through out the Industrial Training.
I would like thank my family for always being there for me. Their love,
constant support and encouragement to achieve my goals.
Finally, we would also like to thank all those who directly or indirectly helped
me during this Industrial Training
B.V.SURYA NARAYANA
(21243-EE-005)
ABSRACT
During my six months of in - plant training period. I have gathered more knowledge about
not only industrial electronics but also electrical installations, applications of electronic in
electrical field and mechanical field. In Loadstar, I gained theoretical knowledge about the
electronics in industrial usage. In my training period, I learnt that how to apply those
experiences which I gained within last six months. In this report, I present that back ground
of the training organization, its structure, staff levels, etc. And also, I express my training
experiences in Loadstar (pvt) Ltd. Further, under this, I describe industrial electronic devices,
CNC machines, Computer embedded systems… etc On the other hand, I mention that
1 INTRODUCTION 1-4
1.0. Substation 1
1.1 Operation of substation 1
1.2 Classification of substation 2
1.2.a. According to service requirement 2
1.2.b. According to constructional features 2
1.3. Single line diagram 3
1.3.a. 33/11kv ss peravali 4
2 TRANSFORMERS 5-13
2.0 About transformer 5
2.1 Working principle of transformer 6
2.2 Emf equation of transformer 7-8
2.3 Classification of transformer 9
2.4 Parts of transformer & their functions 9
2.4.a. Laminated core 9
2.4.b Windings 10
2.4.c Insulating material 10
2.4.d Transformer oil 10
2.4.e Buchhloz relay 10
2.4.f Tap changer 11
2.4.g Oil conservator 11
2.4.h Breather 11
2.4.i Explosion vent 11
2.4.j Radiator & fans 11
2.5. Specification of ptr 1 12
2.6. Specification of ptr 2 13
5 Conclusion 51
LIST OF FIGURES
1.0 SUBSTATION:
A substation is the part if an electrical generation transmission and distribution
system .Substation transform voltage from high to low, or the reverse or perform any of
several other important functions.
The present day electrical power system is A.C .i.e, electrical power is generated
transmitted & distributed in the form of the alternating current. The electric power is
produced at power plant stations which are located at favorable places generally quite
away from the consumers. It is delivered to the consumers through a large network of
transmission 7 distribution. At many places in the power system, it may be desirable
and necessary to change some characteristics e.g. voltage, ac to dc, frequency, power
factor etc. of electric supply. This accomplished by suitable apparatus called substation.
For example; generation voltage (11kv or 33kv) at the power station is set up to high
voltage (say 220kv or 132kv) for transmission of electric power. The assembly of
apparatus (e.g. transformer etc.) used for this purpose in the substation Similarly near
the consumer’s localities, the voltage may have to be step down to utilization level.
This job is accomplished by suitable apparatus called substation.
Switching operation
To change the supply frequency level i.e .from high level to low level or viceversa.
1
1.2 CLASSIFICATION OF SUBSTATIONS
The substation may be classified into several ways .the two important ways of
Switching substation
Transformer substation
Converting substation
Industrial substation
Indoor substation
Outdoor substation
2
1.3. SINGLE LINE DIAGRAM OF 33/11 KV SS KATAKOTESWARAM
33kv AB Switch
33 kv Alternating supply(Tanuku)
33kv AB Switch
33kv breaker
33kv AB Switch
33kv HG Fuse
LV-I LV-II
CT CT CT CT CT CT
3
1.3.a. 33/11KV SS PERAVALI
The 33kv substation PERAVALI which was commissioned on18-08-1982
The main bus 33kv is connected to grid located at 132/33kv,” TANUKU” Now the
transmission line first parallel connected with lighting arrestor to divergesurge, followed
CVT connected parallel. CVT measures voltage and step down at 110v. A.C. for control
Panel, a current transformer is connected in series with line which measure current and
Step down current at ratio 200:1 for control panel. Transformer step downs voltage from
provide supply to the equipment of the substation. Capacitor bank is connected to main
MALLESWARAM
MUKKAMALA
TEEPARRU
KAKARPARRU
KHANDAVALLI
PERAVALI TOWN
4
CHAPTER-2
TRANSFORMERS
2.0. ABOUT TRANSFORMER
A transformer is a static device .Which transfer’s electrical energy from one circuit to
the other circuit without changing frequency, while doing so the voltage may be increased or
decreased with a corresponding decrement or increment of current.
A transformer consists of two windings. The winding connected to the supply is called
primary winding and the winding connected to the load is called the secondary winding. In an
ideal transformer the induced voltage in the secondary winding (vS) is in proportional to the
Primary voltage (VP) and is given by the ratio of number of turns in the secondary (NS) to the
number of turns in the primary (NP) as follows.
Vs/Vp=Ns/Np
By appropriate selection of the ratio of turns, a transformer thus allows an alternating current
(A.C) voltage to be stepped up by making ns greater than Np, or stepped down by making ns
less than Np.
Changing the current in the primary coil changes the magnetic flux that is developed. The
changing magnetic flux induces a voltage in the secondary coil.
5
2.1. WORKING PRINCIPLE OF TRANSFORMER
The basic principle behind working of a transformer is the phenomenon of mutual induction
between two windings linked by common magnetic flux. Basically the transformer consists of
two inductive coils; primary winding and secondary winding The coils are electrically separated
but magnetically linked to each other. When, primary winding is connected to a source of
alternating voltage alternating magnetic flux is produced around the winding. The core provides
magnetic path for the flux, to get linked with the secondary winding. Most of the flux gets linked
with the secondary winding which is called as 'useful flux' or main 'flux', and the flux which does
not get linked with secondary winding is called as 'leakage flux'. As the flux produced is
alternating (the direction of it is continuously changing), EMF gets induced in the secondary
winding according to Faraday's law of electromagnetic induction. This emf is called 'mutually
induced emf', and the frequency of mutually induced emf is same as that of supplied emf. If the
secondary winding is closed circuit, then mutually induced current flows through it and hence
the electrical energy is transferred from one circuit (primary) to another circuit (secondary).
6
2.2. EMF equation of a transformer
Transformation Ratio In a transformer, source of alternating current is applied to the primary
winding. Due to this, the current in the primary winding (called as magnetizing current) produces
alternating flux in the core of transformer. This alternating flux gets linked with the secondary
winding, and because of the phenomenon of mutual induction an emf gets induced in the
secondary winding. Magnitude of this induced emf can be found by using the following EMF
equation of the transformer. EMF equation of the Transformer
Let,
As, shown in the fig., the flux rises sinusoidally to its maximum value Φm from 0. It reaches to
the maximum value in one quarter of the cycle i.e in T/4 sec (where, T is time period of the sin
wave of the supply = 1/f).
Therefore,
Now, Induced emf per turn = rate of change of flux per turn
Therefore, RMS value of emf per turn = Form factor X average emf per turn.
7
As, the flux Φ varies sinusoidally, form factor of a sine wave is 1.11
RMS value of induced emf in whole primary winding (E1) = RMS value of emf per turn X
Number of turns in primary winding
E1 = 4.44f N1 Φm ............................. eq 1
This is called the emf equation of transformer, which shows, emf / number of turns is same for
both primary and secondary winding.
As derived above,
▪ If N2 > N1, i.e. K > 1, then the transformer is called step-up transformer.
▪ If N2 < N1, i.e. K < 1, then the transformer is called step-down transformer.
8
2.3. CLASSIFICATION OF TRANSFORMERS
1. Power transformer
a. Step up transformer
2. Distribution transformer
3. Instrument transformer
a. Current transformer
b. Potential transformer
4. Welding transformer
1. Laminated core
2. Windings
3. Insulating material
4. Tank
5. Terminals and bushings
6. Transformer oil
7. Tap changer
8. Buchholz relay
9. Oil conservator
10. Explosion vent
11. Breather
12. Radiator and fans
laminated core is the most important part of transformer, used to support the windings of the
transformer. It is made up of laminated soft iron material to reduce eddy current loss and
hysteresis loss. Nowadays in the core of the transformer, laminated sheets are used to minimize
eddy current losses, and CRGO steel material is used to minimize hysteresis losses. The
composition of the core material depends on the voltage, current, and frequency of supply to
the transformer.
9
2.4.b. Windings
In a transformer always two sets of windings are placed on a laminated core and these are
insulated from each other. Winding consists of several no of turns of copper conductors that are
bundled together and connected in series.The main function of windings is to carry current
produce working magnetic flux and induce mutual EMF for transformer action. Windings are
classified in two ways
10
2.4.f. Tap Changer
The main function of the tap changer is to regulate the output voltage of the transformer by
changing its turn ratio. There are two types of tap changers.
1. On-Load Tap Changer:- In an on-load tap changer, tapping can be changed without
isolating the transformer from the supply. Hence it is capable of operating without
interrupting the power supply.
2. Off-Load Tap Changer:- In the off-load tap changer, the transformer needs to isolate
from the supply to change its tapping (turns ratio).
2.4.h. Breather
The breather is a cylindrical container filled with silica gel and directly connected to the
conservator tank of the transformer. The main function of the breather is to supply moisture-free
fresh air to the conservator tank during the expansion and contraction of transformer oil. In a
breather, when air passes through silica gel the moisture present in the air is absorbed by the
silica gel crystal and hence moisture-free dry air is supplied to the conservator tank. Thus we can
also say that the breather is acting as an air filter for the transformer.
11
2.5. SPECIFICATIONS OF PTR-1(8MVA)
Lv - 11KV
Lv - 419.89A
Frequency - 50 HZ
12
2.6. SPECIFICATIONS OF PTR- II (5MVA)
Lv - 11KV
Lv - 262.4A
Frequency - 50 HZ
13
CHAPTER-3
An electrical bus bar is defined as a conductor or a group of conductor used for collecting
electric power from the incoming feeders and distributes them to the outgoing feeders. In other
words, it is a type of electrical junction in which all the incoming and outgoing electrical current
meets. Thus, the electrical bus bar collects the electric power at one location.
The most common of the bus-bars are 40×4mm (160 mm2); 40×5 mm (200 mm2) ; 50×6
mm (300mm2) ; 60×8 mm (480 mm2) ; 80×8 (640 mm2) and 100×10 mm (1000 mm2).
The various types of busbar arrangement are used in the power system. The selection of the bus
bar is depended on the different factor likes reliability, flexibility, cost etc.
14
It requires less maintenance
It is simple in operation
The only disadvantage of such type of arrangement is that the complete supply is disturbed
on the occurrence of the fault.
The arrangement provides the less flexibility and hence used in the small substation where
continuity of supply is not essential.
3.1.a. Single Bus-Bar Arrangement with Bus Sectionalized
In this type of busbar arrangement, the circuit breaker and isolating switches are used. The
isolator disconnects the faulty section of the bus bar, hence protects the system from complete
shutdown. This type of arrangement uses one addition circuit breaker which does not much
increase the cost of the system
Fig : 3.1.a. Schematic diagram of Single Bus-Bar Arrangement with Bus Sectionalized
15
Advantage of single Bus-bar Arrangement with Bus Sectionalization
The faulty section is removed without affecting the continuity of the supply.
The maintenance of the individual section can be done without disturbing the system
supply.
The system has a current limiting reactor which decreases the occurrence of the fault.
Disadvantages of Single Bus-Bar Arrangement with Sectionalization
The system uses the additional circuit breaker and isolator which increases the cost of the
system
3.1.b. Main and Transfer Bus Arrangement
Such type of arrangement uses two type of busbar namely, main busbar and the auxiliary bus bar.
The busbar arrangement uses bus coupler which connects the isolating switches and circuit
breaker to the busbar. The bus coupler is also used for transferring the load from one bus to
another in case of overloading. The following are the steps of transferring the load from one bus
to another.
The potential of both the bus bar kept same by closing the bus coupler.
The bus bar on which the load is transferred is kept close.
Open the main bus bar.
Thus, the load is transferred from the main bus to reserve bus.
16
Advantages of Main and Transfer Bus Arrangement
The continuity of the supply remains same even in the fault. When the fault occurs on any
of the buses the entire load is shifted to the another bus.
The repair and maintenance can easily be done on the busbar without disturbing their
continuity.
The maintenance cost of the arrangement is less.
The potential of the bus is used for the operation of the relay.
The load can easily be shifted on any of the buses.
Disadvantages of Main and Transfer Bus Arrangement
In such type of arrangements, two bus bars are used which increases the cost of the system.
The fault on any of the bus would cause the complete shutdown on the whole substation.
Circuit breakers are used to open and close circuits. They can be operated manually to perform
maintenance or will automatically trip if a short circuit occurs. This function in the power system
is similar to that of the fuses or breakers in a household distribution panel.
17
3.3. ISOLATORS
Isolator is a manually operated mechanical switch that isolates the faulty section of substation. It
is used to separate faulty section for repair from a healthy section in order to avoid the
occurrance of severe faults. It is also called disconnector or disconnecting switch.
18
Applications of Isolator
When a travelling wave reaches the arrestor, its sparks over at a certain prefixed voltage as
shown in the figure below. The arrestor provides a conducting path to the waves of relatively low
impedance between the line and the ground. The surge impedance of the line restricts the
amplitude of current flowing to ground.
The lightning arrester provides a path of low impedance only when the travelling surge reaches
the surge diverter, neither before it nor after it. The insulation of the equipment can be protected
if the shape of the voltage and current at the diverter terminal is similar to the shape shown
below.
19
3.6. TYPES OF LIGHTNING ARRESTORS
20
Fig: 3.8 : .THYRITE LIGHTNING ARRESTER
3.6.b. Metal Oxide Surge Arrester
The arrester which uses zinc oxide semiconductor as a resistor material, such type of arrester is
known as a metal oxide surge arrester or ZnO Diverter. This arrester provides protection against
all types of AC and DC over voltages. It is mainly used for overvoltage protection at all voltage
levels in a power system.
21
BENEFITS OF LIGHTENING ARRESTER TESTING
Lightning protection testing would make sure that all structures, key electrical
and electronic installations are safe from the effect of lightening strike.
The financial benefits are determined as follows: how does the total annual cost
for a lightning protection system compare to the costs of potential damage
without a protection system? The cost evaluation is based on the expenditures
for the planning, assembly, and maintenance of the lightning protection system
3.7. WAVE TRAPS
High frequency waves above 50 Hz are captured using a wave trap or line trap. A wave trap
is used to produce a high impedance to prevent high-frequency carrier waves from entering
undesirable locations, usually substations. All communication in carrier wave technology is sent
at a frequency between 150 kHz and 800 kHz.
The capacitive voltage transformer step-down the high voltage input signals and provide the low
voltage signals which can easily measure through the measuring instrument. The Capacitive
voltage transformer (CVT) is also called capacitive potential transformer
22
3.9. INSULATORS
Insulators will generally be used in substations to separate and support electrical conductors
while not letting electrical currents flow through themselves. When electrical materials including
cables are wrapped in insulate material, this is referred to as insulating them
Properties of Insulators
23
Advantages of Pin Insulator
24
3.12. STRAIN INSULATOR
When suspension string is used to sustain extraordinary tensile load of conductor it is referred as
string insulator. When there is a dead end or there is a sharp corner in transmission line, the line
has to sustain a great tensile load of conductor or strain. A strain insulator must have
considerable mechanical strength as well as the necessary electrical insulating properties
A stay insulator is a type of low voltage insulator designed to fasten and counterweight the dead-
end pole by connecting with a stay wire or guy grip, it is also called a stay type insulator or egg
insulator.
The shackle insulator (also known as a spool insulator) is usually used in low voltage distribution
network. It can be used in both the horizontal or vertical positions. The use of such insulator has
decreased recently after increasing the using of underground cable for distribution purpose. The
tapered hole of the spool insulator distributes the load more evenly and minimizes the possibility
25
of breakage when heavily loaded. The conductor in the groove of shackle insulator is fixed with
the help of soft binding wire
The following sizes have now been standardized by CEA for transmission lines of different
voltages
For 132kv lines : panther ACSR having 7- strands of steel of dia 3.00mm and 30-strands
of aluminium of dia3.00mm.
For 220kv lines : “zebra” ACSR having 7-strands of steel of dia 3.18 mm and 54-strands
of aluminium of dia3.18mm.
For 400kv lines : twin “moose” ACSR having 7-strands of steel of dia 3.53 mm and 54-
strands of aluminium of dia 3.53mm
26
A current transformer is designed to maintain an accurate ratio between the currents in its
primary and secondary circuits over a defined range. The alternating current in the primary
produces an alternating magnetic field in the core, which then induces an alternating current in
the secondary.
.The ratio of the primary current and the secondary current is known as a current transformer
ratio of the circuit. The current ratio of the transformer is usually high. The secondary current
ratings are of the order of 5A, 1A and 0.1A. The current primary ratings vary from 10A to
3000A or more. The symbolic representation of the current transformer is shown in the figure
Above
27
Fig :3.18 : potential transformer
The stepped down voltage by the Potential transformer can be measure using a low range AC
voltmeter. The potential transformer has shell type construction of its magnetic core for better
accuracy. One end of the secondary winding of the potential transformer is grounded to provide
the proper protection to the operator.
The primary winding of the potential transformer is connected across the high voltage power line
whose voltage is to be measured and a low-range AC voltmeter (usually 0-110V) is connected
across the secondary winding of the P.T.
Capacitor banks are usually installed at specific points in the system, such as substations or
feeders, where they can provide the optimal amount of reactive power compensation for the load
or network conditions. Capacitor banks are generally used for improving power factor of
electricity consumed by bulk consumers e.g.industry. Usually the electrical power supply
companies impose a penalty, if the average power factor over a stipulated period falls below a
certain value. A large part of load of bulk consumers are inductive in nature because of use of
induction motors. This causes low power factor (lagging because of predominately inductive
loads). Capacitors, on the other hand, constitute leading power factor load; thus compensating a
28
major part of the inductive loads and result in power factor close to unity but still lagging in
nature. This improvement of power factor fulfills the requirements of the supply company. Loads
with low power factor draw more current from supply than same active load with high power
factor and hence cause increased power loss in supply line. This increase of power loss is a waste
for the supply company. Further supply companies need to install higher size transmission /
distribution equipment to supply the additional load current because of the low power factor. To
prevent these, the penalty for low power factor is imposed
29
CHAPTER-4
PROTECTIVE EQUIPMENTS
1. Make or break an electrical circuit either manually or by remote control under normal
conditions.
Circuit breaker essentially consists of fixed and moving contacts. These contacts are touching
each other and carrying the current under normal conditions when the circuit is closed. When the
circuit breaker is closed, the current carrying contacts, called the electrodes, engaged each other
under the pressure of a spring.
During the normal operating condition, the arms of the circuit breaker can be opened or closed
for a switching and maintenance of the system. To open the circuit breaker, only a pressure is
required to be applied to a trigger.
Whenever a fault occurs on any part of the system, the trip coil of the breaker gets energized and
the moving contacts are getting apart from each other by some mechanism, thus opening the
circuit
When the contacts of a circuit breaker are separated, there is a luminous electric discharge
between these two contacts known as ‘Arc’. This arc may continue until the discharge ceases.
The production of arc may delay the current interruption process and generate enormous heat
which may cause serious damage to system or to circuit breaker itself. Therefore, the main
problem in a circuit breaker is to extinguish the arc within the shortest possible time.
30
4.3. DIFFERENT TYPES OF CIRCUIT BREAKERS
Low voltage circuit breakers: These breakers are rated for use at low voltages up to 2
kV and are mainly used in small-scale industries
Outdoor Circuit breakers: You can use these breakers outdoors without any roof due to
their design. Their external enclosure arrangement is strong compared to the indoor
breakers and can withstand wear and tear.
.Their tank encloses all the insulating and interrupting medium. In other words, the tank
is shorted to ground or it is at dead potential.
Live tank circuit breakers: These breakers have a tank housing interrupter that is at a
potential above the ground. It is above the ground with some insulation medium in
between
31
4.3.d. By Interrupting Mechanism
Air circuit breaker-This breaker uses air as an insulating and interrupting medium.
The breaker is sub-classified into two types
MCB (Miniature Circuit Breaker)-The current ratings for this breaker are less
than 100A and has only one over-current protection built within it. The trip
settings are not adjustable in this circuit.
Single pole circuit breaker-This breaker has one hot wire and one neutral wire
that operate at 120 V. When there is a fault, it will interrupt just the hotwire.
Double pole circuit breaker-This is used for 220 V. There are two hotwires
and both the poles need to be interrupted.
Arc Fault circuit interrupter (AFCI) -The AFCI breaker interrupts the circuit
during excessive arc conditions and prevents fire. Under the normal arcing
condition, this breaker will be idle and won’t interrupt the circuit.
.
32
4.4 RELAY FAMILY
33
4.5. Definition of Relay:
A relays is a sensing device which is used to detect the faults in an electrical circuit and trip
circuit breaker. Over load
A relay is automatic device which senses an abnormal condition of electrical circuit and closes
its contacts. These contacts in turns close and complete the circuit breaker trip coil circuit hence
make the circuit breaker tripped for disconnecting the faulty portion of the electrical circuit from
rest of the healthy circuit .Now let’s have a discussion on some terms related to protective relay.
The value of actuating quantity (voltage or current) which is on threshold above which the relay
initiates to be operated .If the value of actuating quantity is increased, the electromagnetic effect
of the relay coil is increased, and above a certain level of actuating quantity, the moving
mechanism of the relay just starts to move.
Reset Level:
The value of current or voltage below which a relay opens its contacts and comes in original
position.
The time which elapses between the instant when the actuating quantity becomes less than the
reset value to the instant when the relay contacts return to its normal position.
Reach of relay:
A distance relay operates whenever the distance seen by the relay is less than the pre specified
impedance. The actuating impedance in the relay is the function of distance in a distance
protection relay. This impedance or corresponding distance is called the reach of relay. Power
system protection relays can be categorized into different types of relays.
Just after exceeding pickup level of actuating quantity the moving mechanism (for example
rotating disc) of relay starts moving and it ultimately closes the relay contacts at the end of its
journey. The time which elapses between the instant when actuating quantity exceeds the pickup
value to the instant when the relay contacts close. Now let’s have a look on which different
protective relays are used in different power system equipment protection schemes.
34
4.6. Relays for transmission & distribution lines protection
Buchholz relay
Earth fault relay
Over current relay
Differential relay
Digital relay
35
4.7.a. Differential relay
Generally differential protection is provided in the electrical power transformer rated more than
5mva.The differential protection of transformer has many advantages over other schemes of
protection.
The faults occur in the transformer inside the insulating oil can be detected by buchholz relay.
But if any fault occurs in the transformer but not in oil then it cannot be detected by buchholz
relay. Any flash over at the bushings are not adequately covered by buchholz relay. Differential
relays can detect such type of faults. Moreover buchholz relay is provided in transformer for
detecting any internal fault in the transformer but differential protection scheme detects the same
in faster way.
The differential relays normally response to those faults which occur inside the differential
protection zone of transformer.
Principle of differential protection scheme is one simple conceptual technique. The differential
relay actually compares between primary current and secondary current of power transformer, if
any unbalance found in between primary and secondary currents the relay will actuate and inter
trip both the primary and secondary circuit breaker of the transformer. Suppose you have one
transformer which has primary rated current ip and secondary current is. If you install ct of ratio
ip/1a at the primary side and similarly, ct of ratio is/1a at the secondary side of the transformer.
The secondaries of these both CT's are connected together in such a manner that secondary
currents of both CT’s will oppose each other.
In other words, the secondaries of both CT’s should be connected to the same current coil of a
differential relay in such an opposite manner that there will be no resultant current in that coil in
a normal working condition of the transformer. But if any major fault occurs inside the
transformer due to which the normal ratio of the transformer disturbed then the secondary current
of both transformers will not remain the same and one resultant current will flow through the
current coil of the differential relay, which will actuate the relay and inter trip both the primary
and secondary circuit breakers. To correct phase shift of current because of star-delta connection
of transformer
36
Fig :4.0 Principle of differential protection
winding in the case of three-phase transformer, the current transformer secondaries should be
connected in delta and star as shown here.
At maximum through fault current, the spill output produced by the small percentage unbalance
may be substantial. Therefore, differential protection of transformer should be provided with a
proportional bias of an amount which exceeds in effect the maximum ratio deviation.
4.8.b. Percentage differential relay or biased differential protection:
Generally differential protection relay means the relay operates when the phasor difference
between the two or more electrical quantities exceed the pre-set value. The electrical quantity
may be voltage or current. But mostly voltage based relays are not preferred. We use to prefer
current based differential protection, but it has some limitations such as both ct should be
identical ct ratio, identical burden, extension cable resistance nuisance trip etc. In order to avoid
these, percentage differential protection can be used.
The percentage differential relay is designed to operate the differential current in terms of its
fractional relation with actual current flowing through the circuit. It is used to protect the system
under current transformer saturation, unequal ct ratios, nuisance trip etc. It increases the stability
of the differential protection relays.
37
Fig :4.1 : Percentage differential relay or biased differential protection
Two coils are there in the relay. One is operating coil and another one is restraining coil. Here
restraining coil produce force or torque which will oppose the operating coil of the relay. Let’s
take n is the number of turns in the operating coil and nr is the number of turns in the restraining
coil. The connection is made as shown in the figure. In this two coils are placed and the
operating coil k carries the differential current which means i1-i2 and another one coil is
restraining coil r carries the current proportional to (i1+i2)/2 because of the coil k is connected in
midpoint the restraining coil. Normally current i1 flows in the restraining coil in nr/2 parts, the i2
current flows another nr/2 parts... Hence the effective ampere turns are...
That’s why we have taken the total current through the restraining coil as i1+i2)/2
Under normal condition, the force produced by the restraining coils is greater than the force
produced by the operating coils. Therefore, relay does not operate.
Hence
38
During fault condition…the operating force become higher than the restraining force, due to
this the operating coil trips the mechanism.
Thus the ratio of differential current to average restraining current is always a fixed percentage.
Therefore it is called as percentage differential relay.
Function of protective relaying is to cause prompt removal from service of any element of a
power system when it suffers a short circuit or when it starts to separate in any abnormal manner
that might cause damage or otherwise interfere with the effective operation of the rest of the
system.
39
4.9. EARTHING
A galvanized steel and a perforated pipe of approved length and diameter is placed vertically in a
wet soil in this kind of system of earthing. It is the most common system of earthing. The size of
pipe to use depends on the magnitude of current and the type of soil. The dimension of the pipe
is usually 40mm (1.5in) in diameter and 2.75m (9ft) in length for ordinary soil or greater for dry
and rocky soil. The moisture of the soil will determine the length of the pipe to be buried but
usually it should be 4.75m(15.5ft).
40
Fig : schematic diagram of pipe earthing
41
4.9.b. Plate earthing:
In plate earthing system, a plate made up of either copper with dimensions 60cm x 60cm x
3.18mm (i.e. 2ft x 2ft x 1/8 in) or galvanized iron (gi) of dimensions 60cm x 60cmx
6.35 mm (2ft x 2ft x ¼ in) is buried vertical in the earth (earth pit) which should not be less than
3m (10ft) from the ground level
42
Max. value of earth resistance to be achieved
The earth resistance depends upon the moisture content in the soil
4.10.MAINTAINANCE OF SCHEDULES
43
9 Vibrations measurements (for shunt reactors only) 2 Monthly
44
Minimum oil circuit breakers:
1 Oil leakages from close and open dashpots, replace the Yearly
same if leakage observed
45
4.10.b. Circuit breakers:
46
4.10.c. Current transformers:
Sl. NO Checking of the equipment Maintenance
47
2 Measurement of voltage at control room panel Half yearly
8 Testing of emu tank oil for BDV (if oil found SOS
discolored)
*To be repeated before 1 year from commission and then as per schedule .this test is not possible
to be conducted at site if isolated of neutral of intermediate pt is not possible at site.
Distance protection:
Sl. NO Checking of the equipment Maintenance
48
Differential relays:
Over voltage relay
49
3 Operation of high set element/instantaneous unit at Yearly
voltage setting .if applicable
Over current and earth fault relay:
50
CHAPTER-5
CONCLUSION
Now from this report one can conclude that electricity plays an important role in
our life at the end of the training. I came to know about the various parts of
substation and how they are operated .also I learnt about how transmission is done
in various parts of East Godavari district. As evident from the report, a substation
plays a very important role in the transmission system. That’s why various
protective measures are taken to protect the substations from various faults and its
smooth functioning .APTRANSCO takes such steps so that a uniform and Supply
of electricity can reach in every part of this state.
51