Square D™ Industrial Control Transformers

Class 9070
Catalog

R04/21

9070CT9901

www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished
for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Class 9070

Table of Contents
Product Descripton ...........................................................................................5
The Global Product Offering—Type T ................................................................5
Transformers with Fuse Block Protection—Type TF ............................................5
Leaded Control Transformer Line ......................................................................5
MultiTap ..........................................................................................................5
Type T Transformers ........................................................................................6
CE Marking......................................................................................................7
Type T Transformers Selection Guide ................................................................7
Custom-Built Type T Transformers............................................................. 11
Type T MultiTap Transformers ...................................................................14
Type T Transformers with Dual Secondary .................................................18
Type T Transformers with 24 Volt Secondary ..............................................22
Multiple Secondary.........................................................................................26
Type T Units with Dual 24/120 Volt Secondary (Tapped Units)......................27
Type T Units with Dual 24/120 Volt Secondary (Separate Windings) .............32
Type T Performance Data ...............................................................................39
Transformers with Leads ...............................................................................41
Fuse Protection ...............................................................................................43
Accessories ...................................................................................................48
Primary Fusing to Meet NEC...........................................................................49
Primary Fusing to Meet CE .............................................................................50
Secondary Fusing to Meet NEC and CE...........................................................51
Type TF Transformers ...................................................................................52
120 Volt Control Secondary—Primary and Secondary Fuse Block .....................52
MultiTap for 120 Volt Control Secondary—Primary and Secondary Fuse
Block.............................................................................................................53
Field Installed Fuse Options .........................................................................55
Primary Fusing...............................................................................................55
Primary and Secondary Fusing .......................................................................57
Secondary Fusing ..........................................................................................60
Secondary Fuse Clips ....................................................................................64
Terminal Blocks..............................................................................................65
Application .......................................................................................................66
Example of Series and Parallel Connections ....................................................66
Example of a typical application.......................................................................67
Technical Data ................................................................................................68
Frequently Asked Questions.........................................................................69

9070CT9901 3
Product Descripton Class 9070

Product Descripton
Control power transformers from Schneider Electric set the industry standard for
design innovation and performance. They are designed with low impedance windings
for voltage regulation, and can accommodate the high inrush current associated with
contactors, starters, solenoids, and relays.
A variety of designs are available to meet the diverse needs of panel builders and
machinery OEMs. The versatility of the control transformer line offers unparalleled
options for design engineers.

The Global Product Offering—Type T


Type T is the most popular and complete line of control transformers. It comes with
unmatched design innovations for top performance and is manufactured using the
most advanced insulating materials. The Type T control transformer is a solid choice if
size and cost are of concern.

Transformers with Fuse Block Protection—Type TF


Schneider Electric offers both product lines with factory installed overcurrent
protection fuse blocks. Type TF transformers consist of two primary fuse blocks and
one secondary fuse block, a configuration that meets the majority of overcurrent
needs by panel builders and machinery OEMs. Since the fuse blocks are pre-wired
and mounted on top of the transformer, the Type TF transformers have the same
footprint as the Type T unit. This design frees up space normally used for separate
fuse blocks.
We also have an extensive fuse block offering for custom applications. See the
overcurrent section of this catalog for full details.

Leaded Control Transformer Line


Schneider Electric offers transformers with internally pre-wired 24-inch primary and
secondary leads, instead of terminal boards, to make installation easier and faster for
many applications. These are only available for single voltage primary and single
voltage secondary applications.

MultiTap
Schneider Electric offers Type T transformers in the MultiTap version. The MultiTap
control transformer was designed to respond to the increased need for voltage and
stock flexibility. It combines multiple primary voltages with one or more secondary
voltages, all in a single transfomer.
The most flexible MultiTap voltage is the Universal, available on the Type T product
line only. It allows for standard primary voltages of 208–600 V and 110, 115, or 120 V
secondary voltages.

9070CT9901 5
Class 9070 Type T Transformers

Type T Transformers
The Type T units are designed for the global market and are a great choice when size
and cost are of concern. This is our most popular and complete offering of industrial
control transformers. The following features are included:
• 50/60 Hz rated
• Customer installed accessories (FingerSafe™ covers, fuse blocks, fuse clips)
• Type T transformers are designed with various temperature classes:
◦ 25–150 VA with a 55°C (131°F) temperature rise, 105°C (221°F) insulation
◦ 200–350 VA with a 80°C (176°F) temperature rise, 130°C (266°F) insulation
◦ 500–5000 VA with a 115°C (239°F) temperature rise, 180°C (356°F) insulation
Schneider Electric manufactures a wide variety of voltage combinations for control
transformers. The voltage combinations are expressed as “Voltage Codes”, and are
embedded within the catalog number of the transformer. Standard codes are listed. If
the voltage combination you need is not listed, please call your Schneider Electric
distributor for assistance.

Table 1 - Type T VA Ratings

UL, cUL, CSA and NOM VA Rating CE VA Rating

25 25
50 50
75 75
100 100
150 150
200 200
250 160
300 200
350 250
500 300
750 500
1000 630
1500 1000
2000 1500
3000 2000
5000 3000

Table 2 - Type T Listings

Listing File VA Range

UL E61239, Guide XPTQ 25–5000

cUL E61239, Guide XPTQ7 25–5000

EN 61 558 25–200
EN EN 61 558 250–1000
EN 61 558 1500–3000

6 9070CT9901
Type T Transformers Class 9070

CE Marking
Industrial control transformers (ICTs) entering the European Union (EU) after January
1, 1997 are required by EU standards to have CE marking or Declaration of
Conformity to CE. EU documentation requires compliance with specification EN 61
558 of the Low Voltage Directive. Type T ICTs from Schneider Electric comply with this
specification, which adhere to, and are accepted by, EU standards. A Declaration of
Conformity for all Type T units is available upon request.
Because of different overload criteria in the CE specification, Schneider Elecric dual
rates these transformers for UL VA, cUL VA, NOM VA and CE VA ratings (see “Type T
VA Ratings” table). Because they are widely used with control circuit panels, ICTs are
also required to comply with EN 60 204 and EN 61 558 in these applications. The
Type T transformer line complies with EN 60 204 when FingerSafe™ covers are
installed.
For more information regarding CE marking, please contact your local Schneider
Electric field sales office.

Type T Transformers Selection Guide


1. Determine inrush and sealed VA of each coil in the control circuit and VA of all
other components.
2. Total all sealed VA of all operating coils and other loads VA (determines minimal
VA size required for the circuit).
3. Total the inrush VA of all coils that are starting at the same time and all loads and
coils that are running (using the regulation chart to give possible units to be
used).
4. Take VA size from step 2, go to standard VA size in chart below. Make sure inrush
VA from chart is greater than total VA from step 3. If not, go to next larger VA size
and repeat.
If supply voltage is stable and fluctuates less than 5%, we recommend use the 90%
secondary voltage column. If supply voltage is not stable and fluctuates more than
10%, we recommend use the 95% secondary voltage column. Another
recommendation is that one that never use the 85% secondary voltage column since
magnetic devices lose life expectancy if they are continuously started at 85% of rated
voltage.

9070CT9901 7
Class 9070 Type T Transformers

Example:
This example assumes the following:
• Two NEMA size 0 contactors do not start together, but one could be ON when the
other starts.
• One NEMA size 2 contactor can start with either of the other contactors.
• One pilot light at 2 VA
1. VA and inrush are:
• NEMA 0: sealed 27 VA; inrush 245 VA
• NEMA 2: sealed 37 VA; inrush 311 VA; pilot light 2 VA
2. Total VA: 27 + 27 + 37 + 2 = 93 VA
3. Total inrush VA: 245 + 311 + 27 + 2 = 582 VA
4. From Regulation Chart for Type T at right below:
• VA minimum unit; inrush 499 VA will not work at 90%
• VA (next standard size); inrush 666 VA will work at 95%

Table 3 - Regulation Chart for Type T

Secondary Voltage

VA Inrush UL VA at 20% Power Factor Inrush UL VA at 40% Power Factor

95% 90% 85% 95% 90% 85%


50 193 266 339 151 215 282
75 271 396 520 210 318 430
100 339 499 659 266 404 549
150 666 893 1120 529 731 942
200 588 815 1041 459 659 866
250 1416 1910 2388 1057 1494 1936
300 1634 2184 2709 1194 1681 2169
350 1894 2592 3261 1392 2005 2621
500 3197 4104 4981 2374 3195 4019
750 3770 5515 7231 2887 4391 5945
1000 6587 9079 11430 4706 6886 9051
1500 19324 23983 28607 15066 19361 23756
2000 31384 38777 46161 24794 31630 38667
3000 26539 39934 52713 19355 30721 42216
5000 53111 85265 116277 39368 66309 93882

8 9070CT9901
Type T Transformers Class 9070

Use the following table to quickly find a Type T transformer for a 120 volt load for your
specific application. First, find the source and load voltages. Then, go to the indicated
pages for details on the transformer(s) matching those voltages.

Table 4 - Type T Transformers for 120 Volt Loads

Go To Voltage
Source Load Voltage Go To Source Load Voltage Source Load Go To
Page Code
Voltage Voltage Code(s) Page(s) Voltage Voltage Code(s) Voltage Voltage Page(s)
(s) (s)

D24, 9, 13
110 110 277 115 D18 11 440 110/220 D31 13
D55

D4, D60 9, 14 D32, 11, 12


110 220 D55 13 277 120 460 95
D50
D1,
D20,
8, 10,
D32,
110 110/220 D55 13 277 240 D60 14 460 115 11, 12,
D95,
13
D50,
D31
D24, 9, 13
115 115 277 120/240 D60 14 460 125 D50 12
D55
115 230 D55 13 364 85 D50 12 460 230 D31 13
115 115/230 D55 13 364 100 D50 12 460 115/230 D31 13
D24, 9, 13
120 120 364 110 D50 12 480 99 D50 12
D55
120 240 D55 13 380 91 D50 12 480 100 D32 11
D1,
D32,
D40, 8, 11,
120 120/240 D55 13 380 95 D18 11 480 120 12, 13
D95,
D50,
D31

190 110 D95 11 380 110 D6, D50 9, 12 480 130 D50 12

D93, 9, 11 D18, D33 11, 14


200 115 380 115 480 240 D31 13
D95

208 85 D50 12 380 120 D40, D50 11, 12 480 120/240 D31 13

208 95 D18 11 380 230 D33 14 500 85 D50 12


208 100 D50 12 380 115/230 D33 14 500 100 D50 12
208 110 D50 12 400 95 D50 12 500 110 D50 12
D20, 10, 11
208 115 400 115 D33 14 550 90 D32 11
D18

D3, D40 9, 11 D103, 9, 12


208 120 400 120 550 91 D50 12
D50
D5,
D32, 9, 11,
220 90 D32 11 400 125 D50 12 550 110 12, 14
D50,
D37
220 91 D50 12 400 230 D33 14 550 120 D50 12
D1, D32,
D95, 8, 11,
220 110 D50, 12, 13 400 115/230 D33 14 550 220 D37 14
D31,
D55
220 120 D50 12 415 110 D17 9 550 110/220 D37 14
D31, D32, 11, 12
220 220 13 415 115 D33 14 575 95
D55 D50
D31,
220 110/220 13 415 230 D33 14 550 110/220 D37 14
D55

9070CT9901 9
Class 9070 Type T Transformers

Table 4 - Type T Transformers for 120 Volt Loads (Continued)

Go To Voltage
Source Load Voltage Go To Source Load Voltage Source Load Go To
Page Code
Voltage Voltage Code(s) Page(s) Voltage Voltage Code(s) Voltage Voltage Page(s)
(s) (s)

D32, 11, 12 D32, 11, 12


230 95 415 115/230 D33 14 575 95
D50 D50
D1, D20,
D32, D5,
8, 10, 9, 11,
D95, D32,
230 115 11, 12, 416 99 D50 12 575 115 12, 14
D50, D50,
13
D31, D37
D55

230 125 D50 12 416 120 D40, D50 11, 12 575 125 D50 12

D31,
230 230 13 416 130 D50 12 575 230 D37 14
D55
D31,
230 115/230 13 420 85 D50 12 575 115/230 D37 14
D55
240 99 D50 12 420 100 D50 12 600 99 D50 12
240 100 D32 11 420 110 D50 12 600 100 D32 11
D1, D32,
D40, D5,
D95, 8, 11, D32, 9, 11,
240 120 12, 13 440 90 D32 11 600 120 12, 14
D50, D50,
D31, D37
D55
240 130 D50 12 440 91 D50 12 600 130 D50 12
D1, D32,
D31, 8, 11,
240 240 13 440 110 D95, 600 240 D37 14
D55 12, 13
D50, D31

D31,
240 120/240 13 440 120 D50 12 600 120/240 D37 14
D55
277 95 D18 11 440 220 D31 13

Use the following table to quickly find a Type T transformer for a 24 volt load for
specific application. First, find source and load voltages. Then, go to the indicated
pages for details on the transformer(s) matching those voltages.

Table 5 - Type T Transformers for 24 Volt Loads

Source Voltage Load Voltage Voltage Code(s) Go To Page(s)

115 24 D89 15

120 24 D23, D7 15, 16

208 24 D14, D19 16, 17

230 24 D89, D112 15, 16

240 24 D2, D23, D19 15, 17

277 24 D25, D19 16, 17

380 24 D88, D19 16, 17

460 24 D92 15

480 24 D2, D19 15, 17

600 24 D16 16

10 9070CT9901
Type T Transformers Class 9070

Custom-Built Type T Transformers


For voltage combinations not listed, Schneider Electric offers custom-built Type T
transformers. Type T units are limited to the following:
Primary Voltage Range: 120 to 600 Volts
Secondary Voltage Range:
• 12 to 277 Volts (25 to 1000 VA)
• 12/24 to 277 Volts (25 to 2000 VA)
• 24/48 to 277 Volts (25 to 5000 VA)

One Primary Tap Two Primary Taps Three Primary Taps Four Primary Taps
Single Dual (two voltages) (three voltages) (four voltages) (five Voltages)

Voltages with 20% Voltages with 20%


25 VA to 5000 VA 25 VA to 5000 VA
Single 25 VA to 25 VA to
25 VA to 3000 VA 25 VA to 3000 VA
5000 VA 5000 VA Voltages greater than Voltages greater than
20% 25 VA to 3000 VA 20% 25 VA to 3000 VA

Voltages with 20% Voltages with 20%


25 VA to 25 VA to 25 VA to 5000 VA 25 VA to 5000 VA
Dual 25 VA to 3000 VA 25 VA to 3000 VA
5000 VA 5000 VA Voltages greater than Voltages greater than
20% 25 VA to 3000 VA 20% 25 VA to 3000 VA

Schneider Electric also offers Secondary Tapped units and Multiple Winding
Secondary units. Since the sizing of these units are determined by the secondary
loading, they are limited to 3000 VA total secondary capacity in the 9070 Type T
product.
To request a price quotation from Schneider Electric for a custom-built Type T
transformer, use the price quote sheet on page 26.

120 Volt Control Secondary


Table 6 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

220/230/240 V:
220 x 440 110 Connect to H1 and H4
Jumper H1 and H3 H1 H3 H2 H4
D1 230 x 460 115 Jumper H2 with H4 Connect to X1 and X2
440/460/480 V:
240 x 480 120 Connect to H1 and H4 X2 X1
Jumper H2 with H3

9070CT9901 11
Class 9070 Type T Transformers

Table 7 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20 x 5x
25 25 9070T25D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
0.38 10
0.20 x 5x
50 50 9070T50D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
0.38 10
0.20 x 5x
75 75 9070T75D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
100 100 9070T100D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
150 150 9070T150D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
200 200 9070T200D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
250 160 9070T250D1 2 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80
0.38 10
0.20 x 5x
300 200 9070T300D1 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95
0.38 10
0.20 x 5x
350 250 9070T350D1 2 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95
0.38 10
0.20 x 5x
500 300 9070T500D1 2 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95
0.38 10
0.28 x 7x
750 500 9070T750D1 2 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111
0.56 14
9070T1000- 0.28 x 7x
1000 630 2 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111
D1 0.56 14
9070T1500- 0.28 x 7x
1500 1000 2 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148
D1 0.56 14
9070T2000- 0.28 x 7x
2000 1500 2 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148
D1 0.56 14
9070T3000- 0.44 x 11 x
3000 2000 3 I 7.24 184 9.00 229 8.75 222 4.63 118 7.63 194
D1 1.13 29
9070T5000- 0.44 x 11 x
5000 3000 3 I 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194
D1 1.13 29

Figure 1 - Figure 2 - Figure 3 -

D D B
A B A

C
C

F E
F E

12 9070CT9901
Type T Transformers Class 9070

Table 8 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

D3 208 120
D4 277 120
550 110
D5 575 115
600 120
D6 380 110 Connect to Connect to
H1 H2

D17 415 110 H1 and H2 X1 and X2


X2 X1
110 110
D24 115 115
120 120
D93 200 115
D103 400 120

Table 9 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number1 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T25 0.20 x 5x
25 25 4 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
● 0.38 10
9070T50 0.20 x 5x
50 50 4 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
● 0.38 10
9070T75 0.20 x 5x
75 75 4 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
● 0.48 12
9070T100 0.20 x 5x
100 100 4 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
● 0.48 12
9070T150 0.20 x 5x
150 150 4 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
● 0.38 10
9070T200 0.20 x 5x
200 200 4 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
● 0.38 10
9070T250 0.20 x 5x
250 160 5 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80
● 0.38 10
9070T300 0.20 x 5x
300 200 5 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95
● 0.38 10
9070T350 0.20 x 5x
350 250 5 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95
● 0.38 10
9070T500 0.20 x 5x
500 300 5 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95
● 0.38 10
9070T750 0.28 x 7x
750 500 5 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111
● 0.56 14
9070T1000 0.28 x 7x
1000 630 5 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111
● 0.56 14
9070T1500 0.28 x 7x
1500 1000 5 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148
● 0.56 14
9070T2000 0.28 x 7x
2000 1500 5 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148
● 0.56 14
9070T3000 0.44 x 11 x
3000 2000 5 I 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194
●2 1.13 29

1. Complete the catalog number by replacing the ● with the appropriate Voltage Code from , page 13 above.
2. Complete the catalog number by replacing the ● with Voltage Code D3 or D4 from 120 Volt Control Secondary, page 11 above.

9070CT9901 13
Class 9070 Type T Transformers

Table 9 - Dimensions (Continued)

VA Catalog Acc. A B C E F Slots


Fig.
Number3 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T3000 0.44 x 11 x
6 I 7.24 184 9.00 229 8.75 222 4.63 118 7.63 194
●3 1.13 29
9070T3000- 0.44 x 11 x
6 N/A 8.08 205 9.00 229 8.75 222 4.63 118 7.63 194
D24 1.13 29
9070T5000 0.44 x 11 x
6 I 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194
● 1.13 29
5000 3000
9070T5000- 0.44 x 11 x
6 N/A 9.99 254 9.00 229 8.75 222 6.56 167 7.63 194
D24 1.13 29

Figure 4 - Figure 5 - Figure 6 -

D D B
A B A

C
C

F E
F E

Type T MultiTap Transformers

120 Volt Control Secondary


Table 10 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

208: Connect to H1 and H2 H1 H2 H3 H4


D20 208/230/460 115 230: Connect to H1 and H3 Connect to X1 and X2
460: Connect to H1 and H4
X2 X1

Table 11 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20 x 5x
25 25 9070T25D20 7 II 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
0.38 10
0.20 x 5x
50 50 9070T50D20 7 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
75 75 9070T75D20 7 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
100 100 9070T100D20 7 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
0.38 10

3. Complete the catalog number by replacing the ● with the appropriate Voltage Code from , page 13 above.
3. Complete the catalog number by replacing the ● with Voltage Code D5, D6, D17, D93, or D103 from 120 Volt Control Secondary, page 11
above.

14 9070CT9901
Type T Transformers Class 9070

Table 11 - Dimensions (Continued)

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20 x 5x
150 150 9070T150D20 7 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
200 200 9070T200D20 8 II 4.70 119 3.75 95 3.20 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
250 160 9070T250D20 8 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95
0.38 10
0.20 x 5x
300 200 9070T300D20 8 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95
0.38 10
0.20 x 5x
350 250 9070T350D20 8 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95
0.38 10
0.28 x 7x
500 300 9070T500D20 8 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111
0.56 14
0.28 x 7x
750 500 9070T750D20 8 II 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111
0.56 14
9070T1000- 0.28 x 7x
1000 630 8 II 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148
D20 0.56 14
9070T1500- 0.28 x 7x
1500 1000 8 II 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148
D20 0.56 14
9070T2000- 0.44 x 11 x
2000 1500 8 II 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194
D20 1.13 29
9070T3000- 0.44 x 11 x
3000 2000 8 II 8.31 211 9.00 229 7.63 194 6.56 167 7.63 194
D20 1.13 29

Figure 7 - Figure 8 - Figure 9 -

D D B
A B A

C
C

F E
F E

Table 12 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

208: Connect to H1 and H2


95: Connect to X1 and X2
D18 208/277/380 95/115 277: Connect to H1 and H3
115: Connect to X1 and X3
380: Connect to H1 and H4
220 or 230 or 240:
Connect to H1 and H2 90 or 95 or 100:
220/440/550 90/110
440 or 460 or 480: Connect to X1 and X2 H1 H2 H3 H4
D32 230/460/575 95/115
Connect to H1 and H3 110 or 115 or 120:
240/480/600 100/120
550 or 575 or 660: Connect to X1 and X3
Connect to H1 and H4 X3 X2 X1

190 or 200 or 208:


Connect to H1 and H2 H1 H2 H3 H4
190/220/440 110
220 or 230 or 240: 110 or 115 or 120:
D95 200/230/460 115
Connect to H1 and H3 Connect to X1 and X2
208/240/480 120 X2 X1
440 or 460 or 480:
Connect to H1 and H4

9070CT9901 15
Class 9070 Type T Transformers

Table 13 - Dimensions

VA A B C E F Slots
Acc.
Catalog Number4 Fig.
Key m- m- m-
UL CE in. in. in. mm in. in. mm in. mm
m m m
9070T25 3.0- 0.20 x 5x
25 25 10 II 79 3.00 76 2.58 66 2.00 51 2.50 64
● 9 0.38 10
9070T50 3.3- 0.20 x 5x
50 50 10 II 85 3.38 86 2.89 73 2.38 61 2.81 71
● 4 0.48 12
3.3- 0.20 x 5x
75 75 9070T75D32 10 II 85 3.38 86 2.89 73 2.38 61 2.81 71
4 0.48 12
9070T75 3.5- 0.20 x 5x
75 75 10 II 91 3.75 95 3.20 81 2.88 73 3.13 80
●5 9 0.38 10
9070T100 3.5- 0.20 x 5x
100 100 10 II 91 3.75 95 3.20 81 2.88 73 3.13 80
● 9 0.38 10
4.7- 0.20 x 5x
150 150 9070T150D32 11 II 119 3.75 95 3.20 81 2.88 73 3.13 80
0 0.38 10
9070T150 3.5- 0.20 x 5x
150 150 10 II 91 3.75 95 3.20 81 2.88 73 3.13 80
●5 9 0.38 10
9070T200 4.7- 11- 0.20 x 5x
200 200 11 II 120 4.50 3.84 98 2.56 65 3.75 95
● 4 4 0.38 10
11- 0.20 x 5x
250 160 9070T250D32 11 II 5.11 130 4.50 3.84 98 3.00 76 3.75 95
4 0.38 10
9070T250 4.7- 11- 0.20 x 5x
250 160 11 II 120 4.50 3.84 98 2.56 65 3.75 95
●5 4 4 0.38 10
5.4- 11- 0.20 x 5x
300 200 9070T300D32 11 II 139 4.50 3.84 98 3.56 90 3.75 95
9 4 0.38 10
9070T300 11- 0.20 x 5x
300 200 11 II 5.11 130 4.50 3.84 98 3.00 76 3.75 95
●5 4 0.38 10
9070T350 5.4- 11- 0.20 x 5x
350 250 11 II 139 4.50 3.84 98 3.56 90 3.75 95
● 9 4 0.38 10
9070T500 5.6- 13- 0.28 x 7x
500 300 11 II 143 5.25 4.51 115 3.43 87 4.38 111
● 1 3 0.56 14
9070T750 6.3- 13- 10- 0.28 x 7x
750 500 11 II 160 5.25 4.51 115 4.31 4.38 111
● 0 3 9 0.56 14
9070T1000 5.9- 17- 10- 0.28 x 7x
1000 630 11 II 150 7.06 6.17 157 4.13 5.81 148
● 2 9 5 0.56 14
9070T1500 7.1- 17- 0.28 x 7x
1500 1000 11 II 182 7.06 6.17 157 4.56 116 5.81 148
● 7 9 0.56 14
9070T2000 6.3- 22- 0.44 x 11 x
2000 1500 11 II 162 9.00 7.63 194 4.63 118 7.63 194
● 8 9 1.13 29
9070T3000 9.1- 22- 16- 0.44 x 11 x
3000 2000 12 II 232 9.00 8.75 222 6.56 7.63 194
● 5 9 7 1.13 29

4. Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connections Options, page 15 above.
5. Complete the catalog number by replacing the ● with Voltage Code D18 or D95 from Voltage and Connections Options, page 15 above.

16 9070CT9901
Type T Transformers Class 9070

Figure 10 - Figure 11 - Figure 12 -

D D B
A B A

C
C

F E
F E

Universal
Table 14 - Voltage and Connections Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

208 or 220 or 230 or 240:


Connect to H1 and H2 85 or 91 or 95 or 99:
208/364/420/500 85/100/110 364 or 380 or 400 or 416: Connect to X1 and X2 H1 H2 H3 H4 H5
220/380/440/550 91/110/120 Connect to H1 and H3 100 or 110 or 115 or 120:
D50
230/400/460/575 95/115/125 420 or 440 or 460 or 480: Connect to X1 and X3
240/416/480/600 99/120/130 Connect to H1 and H4 110 or 120 or 125 or 130:
X4 X3 X2 X1
500 or 550 or 575 or 600: Connect to X1 and X4
Connect to H1 and H5

Table 15 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T2- 0.20 x 5x
25 25 13 III 4.43 113 3.38 85.9 2.89 73.4 2.38 61 2.81 71.4
5D50 0.48 12
9070T5- 0.20 x 5x
50 50 13 III 4.43 113 3.38 85.9 2.89 73.4 2.38 61 2.81 71.4
0D50 0.48 12
9070T7- 0.20 x 5x
75 75 13 III 4.70 119.4 3.75 95.3 3.20 81.3 2.88 73.2 3.13 80
5D50 0.38 10
9070T1- 0.20 x 5x
100 100 13 III 4.70 119.4 3.75 95.3 3.20 81.3 2.88 73.2 3.13 80
00D50 0.38 10
9070T1- 0.20 x 5x
150 150 13 III 4.74 120.4 4.50 114.3 3.84 98 2.56 65 3.75 95.3
50D50 0.38 10
9070T2- 0.20 x 5x
200 200 13 III 5.11 129.8 4.50 114.3 3.84 98 3.00 76.2 3.75 95.3
00D50 0.38 10
9070T2- 0.20 x 5x
250 160 13 III 5.11 129.8 4.50 114.3 3.84 98 3.00 76.2 3.75 95.3
50D50 0.38 10
9070T3- 0.20 x 5x
300 200 13 III 5.49 139.4 4.50 114.3 3.84 98 3.56 90.4 3.75 95.3
00D50 0.38 10
9070T3- 0.28 x 7x
350 250 13 III 5.61 142.5 5.25 133.4 4.51 114.6 3.43 87.1 4.38 111.3
50D50 0.56 14
9070T5- 0.28 x 7x
500 300 13 III 5.61 142.5 5.25 133.4 4.51 114.6 3.43 87.1 4.38 111.3
00D50 0.56 14
9070T7- 0.28 x 7x
750 500 13 III 6.30 160 5.25 133.4 4.51 114.6 4.31 110 4.38 111.3
50D50 0.56 14
9070T1- 104.- 0.28 x 7x
1000 630 13 III 5.92 150.4 7.06 179.3 6.17 156.7 4.13 5.81 147.6
000D50 9 0.56 14

9070CT9901 17
Class 9070 Type T Transformers

Table 15 - Dimensions (Continued)

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T1- 115.- 0.28 x 7x


1500 1000 13 III 7.17 182.1 7.06 179.3 6.17 156.7 4.56 5.81 147.6
500D50 8 0.56 14
9070T2- 117.- 0.44 x 11 x
2000 1500 13 III 6.38 162.1 9.00 228.6 7.63 193.8 4.63 7.63 193.8
000D50 6 1.13 29

Figure 13 -

D
A B

F
E

Type T Transformers with Dual Secondary

120/240 Volt Secondary


Table 16 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

220 or 230 or 240: 110 or 115 or 120:


Connect to H1 and H4 Connect to X1 and X4
220 x 440 110/220 Jumper H1 with H3 Jumper X1 with X3
D31 230 x 460 115/230 Jumper H2 with H4 Jumper X2 with X4
240 x 480 120/240 440 or 460 or 480: 220 or 230 or 240:
Connect to H1 and H4 Connect to X1 and X4
Jumper H2 with H3 Jumper X2 with X3 H1 H3 H2 H4

110 or 115 or 120: 110 or 115 or 120:


Connect to H1 and H4 Connect to X1 and X4 X4 X2 X3 X1
110 x 220 110 x 220 Jumper H1 with H3 Jumper X1 with X3
D55 115 x 230 115 x 230 Jumper H2 with H4 Jumper X2 with X4
120 x 240 120 x 240 220 or 230 or 240: 220 or 230 or 240:
Connect to H1 and H4 Connect to X1 and X4
Jumper H2 with H3 Jumper X2 with X3

18 9070CT9901
Type T Transformers Class 9070

Table 17 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number6 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20
9070T25 5x
25 25 14 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 x
● 10
0.38
0.20
9070T50 5x
50 50 14 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 x
● 10
0.38
0.20
9070T75 5x
75 75 14 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 x
● 12
0.48
0.20
9070T100 5x
100 100 14 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 x
● 12
0.48
0.20
9070T150 5x
150 150 14 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 x
● 10
0.38
0.20
9070T200 5x
200 200 14 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 x
● 10
0.38
0.20
9070T250 5x
250 160 15 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 x
● 10
0.38
0.20
9070T300 5x
300 200 15 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 x
● 10
0.38
0.20
9070T350 5x
350 250 15 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 x
● 10
0.38
0.20
9070T500 5x
500 300 15 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 x
● 10
0.38
0.28
9070T750 7x
750 500 15 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 x
● 14
0.56
0.28
9070T1000 7x
1000 630 15 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 x
● 14
0.56
0.28
9070T1500 7x
1500 1000 15 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 x
● 14
0.56
0.28
9070T2000 7x
2000 1500 15 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 x
● 14
0.56
0.44
9070T3000 11 x
3000 2000 15 I 6.38 162 9.0 229 7.63 194 4.63 118 7.63 194 x
● 29
1.13
0.44
9070T5000 11 x
5000 3000 15 I 8.31 211 9.00 229 7.63 194 6.56 167 7.63 194 x
● 29
1.13

6. 1 Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 18 above.

9070CT9901 19
Class 9070 Type T Transformers

Figure 14 - Figure 15 -

D D B
A B A

C
C

F E
F E

Table 18 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

115: Connect to X1 and X4


380: Connect to H1 and H2 Jumper X1 with X3
D33 380/400/415 115/230 400: Connect to H1 and H3 Jumper X2 with X4
415: Connect to H1 and H4 230: Connect to X1 and X4
Jumper X2 with X3
H1 H2 H3 H4

110 or 115 or 120:


Connect to X1 and X4
110/220 Jumper X1 with X3 X4 X2 X3 X1
550 or 575 or 600: Jumper X2 with X4
D37 550/575/600 115/230
Connect to H1 and H2 220 or 230 or 240:Connect to
120/240
X1 and X4 H1 H2
Jumper X2 with X3

120: Connect to X1 and X4 X4 X2 X3 X1


Jumper X1 with X3
D60 277 120/240 277: Connect to H1 and H2 Jumper X2 with X4
240: Connect to X1 and X4
Jumper X2 with X3

20 9070CT9901
Type T Transformers Class 9070

Table 19 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number7 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T25 0.20 x 5x
25 25 16 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
● 0.38 10
9070T50 0.20 x 5x
50 50 16 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64
● 0.38 10
9070T75 0.20 x 5x
75 75 16 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
● 0.48 12
9070T100 0.20 x 5x
100 100 16 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71
● 0.48 12
9070T150 0.20 x 5x
150 150 16 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
● 0.38 10
9070T200 0.20 x 5x
200 200 16 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80
● 0.38 10
9070T250 0.20 x 5x
250 160 17 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80
● 0.38 10
9070T300 0.20 x 5x
300 200 17 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95
● 0.38 10
9070T350 0.20 x 5x
350 250 17 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95
● 0.38 10
9070T500 0.20 x 5x
500 300 17 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95
● 0.38 10
9070T750 0.28 x 7x
750 500 17 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111
● 0.56 14
9070T1000 0.28 x 7x
1000 630 17 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111
● 0.56 14
9070T1500 0.28 x 7x
1500 1000 17 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148
● 0.56 14
9070T2000 0.28 x 7x
2000 1500 17 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148
● 0.56 14
9070T3000 0.44 x 11 x
3000 2000 17 I 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194
● 1.13 29
9070T5000 0.44 x 11 x
5000 3000 17 I 8.31 211 9.00 229 7.63 194 6.56 167 7.63 194
● 1.13 29

Figure 16 - Figure 17 -

D D B
A B A

C
C

F E
F E

7. Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 20 above.

9070CT9901 21
Class 9070 Type T Transformers

Type T Transformers with 24 Volt Secondary

24 Volt Secondary
Table 20 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

240: Connect to H1 and H4


Jumper H1 with H3
D2 240 x 480 24 Jumper H2 with H4
480: Connect to H1 and H4
Jumper H2 with H3

120: Connect to H1 and H4


Jumper H1 with H3
D23 120 x 240 24 Jumper H2 with H4
240: Connect to H1 and H4
Jumper H2 with H3 H1 H3 H2 H4
Connect to X1 and X2
115: Connect to H1 and H4
Jumper H1 with H3 X2 X1
D89 115 x 230 24 Jumper H2 with H4
230: Connect to H1 and H4
Jumper H2 with H3

230: Connect to H1 and H4


Jumper H1 with H3
D92 230 x 460 24 Jumper H2 with H4
460: Connect to H1 and H4
Jumper H2 with H3

Table 21 - Dimensions

VA Catalog Acc. A B C E F Slots


Number8 Fig.
Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T25 0.20 x
25 25 18 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T50 0.20 x
50 50 18 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T75 0.20 x
75 75 18 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T100 0.20 x
100 100 18 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T150 0.20 x
150 150 18 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T200 0.20 x
200 200 18 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T250 0.20 x
250 160 19 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 5 x 10
● 0.38
9070T300 0.20 x
300 200 19 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 5 x 10
● 0.38
9070T350 0.20 x
350 250 19 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 5 x 10
● 0.38
9070T500 0.20 x
500 300 19 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 5 x 10
● 0.38

8. Complete the catalog number by replacing the t with the appropriate Voltage Code from Voltage and Connection Options, page 22above.

22 9070CT9901
Type T Transformers Class 9070

Figure 18 - Figure 19 -

D D B
A B A

C
C

F E
F E

Table 22 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

D7 120 24
D14 208 24
D16 600 24 H1 H2
Connect to H1 and H2 Connect to X1 and X2
D25 277 24
X2 X1
D88 380 24
D112 230 24

Table 23 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number9 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T25 0.20 x
25 25 20 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T50 0.20 x
50 50 20 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T75 0.20 x
75 75 20 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T100 0.20 x
100 100 20 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T150 0.20 x
150 150 20 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T200 0.20 x
200 200 20 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T250 0.20 x
250 160 21 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 5 x 10
● 0.38
9070T300 0.20 x
300 200 21 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 5 x 10
● 0.38
9070T350 0.20 x
350 250 21 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 5 x 10
● 0.38
9070T500 0.20 x
500 300 21 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 5 x 10
● 0.38

9. 1 Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 23above.

9070CT9901 23
Class 9070 Type T Transformers

Figure 20 - Figure 21 -

D D B
A B A

C
C

F E
F E

Table 24 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

208 208: Connect to H1 and H2


240 240: Connect to H1 and H3 H1 H2 H3 H4 H5 H6
D19 277 24 277: Connect to H1 and H4 Connect to X1 and X2
380 380: Connect to H1 and H5
480 480: Connect to H1 and H6 X2 X1

Table 25 - Dimensions

VA A B C E F Slots
Catalog Acc.
Fig.
Number Key m-
UL CE in. mm in. mm in. mm in. mm in. mm in.
m
9070T50- 0.20 x 5x
50 50 22 III 4.43 113 3.38 85.9 2.89 73.4 2.38 61 2.81 71.4
D19 0.48 12
9070T75- 119.- 0.20 x 5x
75 75 22 III 4.70 3.75 95.3 3.20 81.3 2.88 73.2 3.13 80
D19 4 0.38 10
9070T10- 119.- 0.20 x 5x
100 100 22 III 4.70 3.75 95.3 3.20 81.3 2.88 73.2 3.13 80
0D19 4 0.38 10
9070T15- 119.- 0.20 x 5x
150 150 22 III 4.70 3.75 95.3 3.20 81.3 2.88 73.2 3.13 80
0D19 4 0.38 10
9070T20- 120.- 0.20 x 5x
200 200 22 III 4.74 4.50 114.3 3.84 98 2.56 65 3.75 95.3
0D19 4 0.38 10
9070T25- 129.- 0.20 x 5x
250 160 22 III 5.11 4.50 114.3 3.84 98 3.00 76.2 3.75 95.3
0D19 8 0.38 10
9070T30- 129.- 0.20 x 5x
300 200 22 III 5.11 4.50 114.3 3.84 98 3.00 76.2 3.75 95.3
0D19 8 0.38 10
9070T35- 139.- 0.20 x 5x
350 250 22 III 5.49 4.50 114.3 3.84 98 3.56 90.4 3.75 95.3
0D19 4 0.38 10
9070T50- 142.- 0.28 x 7x
500 300 22 III 5.61 5.25 133.4 4.51 114.6 3.43 87.1 4.38 111.3
0D19 5 0.56 14

24 9070CT9901
Type T Transformers Class 9070

Figure 22 -

D
A B

F
E

Type T Units with Dual 12/24 Volt Secondary


Table 26 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

D13 120 Connect to H1 and H2


D36 600 Connect to H1 and H2

120: Connect to H1 and H4


Jumper H1 with H3 H1 H2
12: Connect to X1 and X4
D54 120 x 240 Jumper H2 with H4
Jumper X1 with X3
240: Connect to H1 and H4
12/24 Jumper X2 with X4
Jumper H2 with H3 X4 X2 X3 X1
24: Connect to X1 and X4
Jumper X2 with X3
240: Connect to H1 and H4
Jumper H1 with H3 H1 H3 H2 H4
D59 240 x 480 Jumper H2 with H4
480: Connect to H1 and H4
Jumper H2 with H3 X4 X2 X3 X1

Table 27 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number10 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T25 0.20 x
25 25 23 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T50 0.20 x
50 50 23 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 5 x 10
● 0.38
9070T75 0.20 x
75 75 23 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T100 0.20 x
100 100 23 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 5 x 12
● 0.48
9070T150 0.20 x
150 150 23 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T200 0.20 x
200 200 23 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 5 x 10
● 0.38
9070T250 0.20 x
250 160 24 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 5 x 10
● 0.38
9070T300 0.20 x
300 200 24 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 5 x 10
● 0.38

10. Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 25above.

9070CT9901 25
Class 9070 Type T Transformers

Table 27 - Dimensions (Continued)

VA Catalog Acc. A B C E F Slots


Fig.
Number11 Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

9070T350 0.20 x
350 250 24 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 5 x 10
● 0.38
9070T500 0.20 x
500 300 24 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 5 x 10
● 0.38

Figure 23 - Figure 24 -

D D B
A B A

C
C

F E
F E

Multiple Secondary
Designed to meet the needs for both 24 and 120 V control. Available in the 9070 Type
T product line, with all the type T features.
Tapped Secondary D15: 24 V rated for 20% capacity and 120 V rated for 80%
capacity when simultaneous loading, or 100% loading when 120 V only.
20% rating at 24 V or 100% rating at 120 V gives equal output current from the device.

VA 24 V amps 120 V amps

50 0.416 0.416
75 0.625 0-Jan
100 0.833 0.833
150 1.25 1.25
200 1.67 1.67
250 2.08 2.08
300 2.5 2.5
350 2.9 2.9
500 4.17 4.17
750 6.25 6.25
1000 8.3 8.3
1500 12.5 12.5
2000 16.7 16.7
3000 25 25
5000 41.7 41.7

11. Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 25above.

26 9070CT9901
Type T Transformers Class 9070

Tapped Secondary D65: Both outputs fully rated for non-simultaneous loading, and
simultaneous rated for any combination that does not exceed the nameplate VA
rating.
Separate Windings Options: All voltage codes offer fully rated non-simultaneous
loading, and simultaneous rated for any combination that does not exceed the
nameplate VA rating.
Features of separate windings:
1. Allows two isolated control circuits, 24 V and 120 V, from the same device
2. Wire sizing for circuits for each voltage not highest current for common when
simultaneous loading. (no common)
3. If a common is required, it can be obtained with a jumper kit.

Type T Units with Dual 24/120 Volt Secondary (Tapped Units)


Table 28 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

240: Connect to H1 and H4


Jumper H1 with H3 23 or 24 or 25: H1 H3 H2 H4
23/110
Jumper H2 with H4 Connect to X1 and X2
D15 240 x 480 24/
480: Connect to H1 and H4 110 or 115 or 120:
/120
Jumper H2 with H3 Connect to X1 and X3
X3 X2 X1

9070CT9901 27
28
Class 9070

Table 29 - Dimensions

120 24
Simultane-
On- On-
ous
VA A B C E F Slots ly ly
Catalog Acc. Loading
Fig. Max Max
Number Key Max UL VA
VA VA

mm mm mm mm mm mm 120
UL CE in. in. in. in. in. in. UL UL 24 V
V
50 50 9070T50D15 25 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 .20 x .38 5 x 10 50 10 40 10
75 75 9070T75D15 25 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 75 15 60 10
100 100 9070T100D15 25 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 100 20 80 20
150 150 9070T150D15 25 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 30 120 30
200 200 9070T200D15 25 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 200 40 160 40
250 160 9070T250D15 26 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 .20 x .38 5 x 10 250 50 200 50
300 200 9070T300D15 26 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 300 60 240 60
350 250 9070T350D15 26 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 350 70 280 70
500 300 9070T500D15 26 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 500 100 400 100
750 500 9070T750D15 26 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 750 150 600 150
100-
630 9070T1000D15 26 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 .28 x .56 7 x 14 1000 200 800 200
0
150- 100-
9070T1500D15 26 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 .28 x .56 7 x 14 1500 300 1200 300
0 0
200- 150-
9070T2000D15 26 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 .28 x .56 7 x 14 2000 400 1600 400
0 0

9070CT9901
Type T Transformers
9070CT9901
Type T Transformers

Table 29 - Dimensions (Continued)

120 24
Simultane-
On- On-
ous
VA A B C E F Slots ly ly
Catalog Acc. Loading
Fig. Max Max
Number Key Max UL VA
VA VA

mm mm mm mm mm mm 120
UL CE in. in. in. in. in. in. UL UL 24 V
V
300- 200- 11 x
9070T3000D15 26 I 6.38 162 9.00 229 7.63 194 4.63 118 7.63 194 .44 x 1.13 3000 600 2400 600
0 0 29
500- 300- 11 x
9070T5000D15 27 I 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194 .44 x 1.13 5000 1000 4000 1000
0 0 29

29
Class 9070
Class 9070 Type T Transformers

Figure 25 - Figure 26 - Figure 27 -

D D B
A B A

C
C

F E
F E

Table 30 - Voltage and Connection Options

Voltages Connections
Voltage
Code Primary Secondary Primary Secondary

200 or 208 or 217:


Connect to H1 and H2 23 or 24 or 25: H1 H2 H3 H4
200/220/440 23/110
220 or 230 or 240: Connect to X1 and X2
D65 208/230/460 24/115
Connect to H1 and H3 110 or 115 or 120:
217/240/480 25/120
440 or 460 or 480: Connect Connect to X1 and X3
X3 X2 X1
to H1 and H4

30 9070CT9901
9070CT9901
Type T Transformers

Table 31 - Dimensions

115 24
Simultane-
Only Only
VA A B C E F Slots ous Loading
Catalog Acc. Max Max
Fig. Max UL VA
Number Key VA VA
m- m- m- m- m-
UL CE in. in. in. in. in. in. mm UL UL 115 V 24 V
m m m m m
50 50 9070T50D65 28 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50
75 75 9070T75D65 28 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75
100 100 9070T100D65 28 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100
Any combination
150 150 9070T150D65 28 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150 that does not
exceed Primary
200 200 9070T200D65 29 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 200 200 Max VA For
example, T350
250 160 9070T250D65 29 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 250 250 200 VA (120V)
150 VA (24V)
300 200 9070T300D65 29 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 300 300
350 250 9070T350D65 29 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 350 350
500 300 9070T500D65 29 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500

31
Class 9070
Class 9070 Type T Transformers

Figure 28 - Figure 29 -

D D B
A B A

C
C

F E
F E

Type T Units with Dual 24/120 Volt Secondary (Separate Windings)


Table 32 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

220/230/240:
Connect to H1 and H4
Jumper H1 with H3 23/24/25: H1 H3 H2 H4
220 x 440 23/110
Jumper H2 with H4 Connect to X1 and X2
D114 230 x 460 24/115
440/460/480: 110/115/120:
240 x 480 25/120
Connect to H1 and H4 Connect to X3 and X4
X4 X3 X2 X1
Jumper H2 with H3

32 9070CT9901
9070CT9901
Type T Transformers

115 24
Simultane-
Only Only
VA Catalog Acc. A B C E F Slots ous Loading
Fig. Max Max
Number Key Max UL VA
VA VA
UL CE in. mm in. mm in. mm in. mm in. mm in. mm UL UL 115V 24V
50 50 9070T50D114 30 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50
75 75 9070T75D114 30 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75
100 100 9070T100D114 30 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100
Any combination
150 150 9070T150D114 30 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150 that does not
exceed Primary
200 200 9070T200D114 31 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 200 200 Max VA For
example, T350
250 160 9070T250D114 31 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 250 250 200 VA (120V)
150 VA (24V)
300 200 9070T300D114 31 I 5.11 130 4.50 114 3.84 98 3 76 3.75 95 .20 x .38 5 x 10 300 300
350 250 9070T350D114 31 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 350 350
500 300 9070T500D114 31 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500

33
Class 9070
Class 9070 Type T Transformers

Figure 30 - Figure 31 -

D D B
A B A

C
C

F E
F E

Table 33 - Voltage and Connection Options

Voltages Connections
Voltage Secondary
Code Primary Secondary Primary

208: Connect to H1 and H2 24: Connect to X1 and X2


D115 208/277 24/115
277: Connect to H1 and H3 115: Connect to X3 and X4 H1 H2 H3

23/24/25:
550 23/110
Connect to X1 and X2
D116 575 24/115 Connect to H1 and H2 X4 X3 X2 X1
110/115/120:
600 25/120
Connect to X3 and X4
H1 H2

X4 X3 X2 X1
380: Connect to H1 and H2
24: Connect to X1 and X2
D119 380/400/415 24/115 400: Connect to H1 and H3
115: Connect to X3 and X4 H1 H2 H3 H4
415: Connect to H1 and H4

X4 X3 X2 X1

34 9070CT9901
9070CT9901
Type T Transformers

Table 34 - Dimensions

115 24
Simultaneous
Only Only
VA Ac- A B C E F Slots Loading Max
Catalog Max Max
Fig. c. UL VA
Number12 VA VA
Key
m-
UL CE in. mm in. in. mm in. mm in. mm in. mm UL UL 115V 24V
m
9070T50
50 50 32 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50

9070T75
75 75 32 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75

9070T100
100 100 32 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100

9070T150 Any combination
150 150 32 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150
● that does not
exceed Primary
9070T200 Max VA For
200 200 33 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 200 200
● example, T350
9070T250 200 VA (120V)
250 160 33 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 250 250 150 VA (24V)

9070T300
300 200 33 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 300 300

9070T350
350 250 33 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 350 350

9070T500
500 300 33 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500

12. Complete the catalog number by replacing the ● with the appropriate Voltage Code from Voltage and Connection Options, page 34 above.

35
Class 9070
Class 9070 Type T Transformers

Figure 32 - Figure 33 -

D D B
A B A

C
C

F E
F E

Table 35 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

200/208/217:
Connect to H1 and H2
200/220/400 23/110
220/230/240:
D117 208/230/460 24/115
Connect to H1 and H3
217/240/480 25/120
400/460/480: 23/24/25:
Connect to H1 and H4 H1 H2 H3 H4
Connect to X1 and X2
220/230/240: 110/115/120:
Connect to H1 and H2 Connect to X3 and X4
X4 X3 X2 X1
220/440/550 23/110
440/460/480:
D118 230/460/575 24/115
Connect to H1 and H3
240/480/600 25/120
550/575/600:
Connect to H1 and H4

36 9070CT9901
13.

9070CT9901
Type T Transformers

Table 36 - Dimensions

115 24 Simultane-
Only Only ous
VA Catalog Acc. A B C E F Slots
Fig. Max Max Loading
Number13 Key VA VA Max UL VA
UL CE in. mm in. mm in. mm in. mm in. mm in. mm UL UL 115V 24V
9070T50
50 50 34 II 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 .20 x .48 5 x 12 50 50

9070T75
75 75 34 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 75 75

9070T100
100 100 34 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 100 100

9070T150 Any
150 150 34 II 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 .20 x .38 5 x 10 150 150 combination

that does not
9070T200 exceed Primary
200 200 35 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 200 200 Max VA For

example, T350
9070T250 200 VA (120V)
250 160 35 II 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 .20 x .38 5 x 10 250 250
● 150 VA (24V)
9070T300
300 200 35 II 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 .20 x .38 5 x 10 300 300

9070T350
350 250 35 II 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 .20 x .38 5 x 10 350 350

9070T500
500 300 35 II 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 .28 x .56 7 x 14 500 500

Complete the catalog number by replacing the t with the appropriate Voltage Code from Voltage and Connection Options, page 34above.

37
Class 9070
Class 9070 Type T Transformers

Figure 34 - Figure 35 -

D D B
A B A

C
C

F E
F E

38 9070CT9901
Type T Transformers Class 9070

Type T Performance Data


Inrush (x FL
FL BTU/hr RMS)
Catalog Core Coil Reg Eff
Total %IZ X/R
Number Watts Watts 1.0PF 100%
Watts 100- No 60 50
75% 50% 25%
% Load Hz Hz
9070T25D1 4.5 3.7 8.2 3.81 75.3 3.84 10.9 28 22 19 16 15 25 30
9070T50D1 4.5 7.1 11.6 7.97 81.1 8.01 10.5 40 29 21 17 15 24.1 28.9
9070T75D1 7.3 6.8 14.1 4.94 84.2 5 15.9 48 38 31 26 25 28 33.6
9070T100D1 7.3 10.2 17.5 6.82 85.1 6.9 15.4 60 45 34 27 25 26.8 32.2
9070T150D1 10.5 10.8 21.3 4.77 87.6 5.25 20.2 73 57 45 38 36 31.2 37.4
9070T200D1 10.5 19.5 30 7.7 86.9 7.83 18 102 73 53 40 36 19.7 23.7
9070T250D1 14.1 17.8 31.9 5.73 88.7 5.73 3.5 109 82 63 52 48 22.9 27.5
9070T300D1 13.3 18.8 32.1 5.6 90.3 5.62 6 110 82 61 49 45 11 13.2
9070T350D1 16.4 19.9 36.3 5.07 90.6 5.08 4.9 124 94 73 60 56 16 19.2
9070T500D1 20.7 30.6 51.3 5.47 90.7 5.48 5.3 175 129 97 77 71 12.9 15.5
9070T750D1 30.8 37.9 68.7 4.57 91.6 4.58 5.7 235 178 138 113 105 17.4 20.9
9070T1000D1 35.4 51.3 86.7 4.83 92 4.84 6 296 219 165 132 121 10.3 12.3
9070T1500D1 51.5 51.3 102.8 3.25 93.6 3.3 8 351 274 220 187 176 10.5 12.6
9070T2000D1 81.8 50 131.8 2.31 93.8 2.31 6.3 450 375 322 290 279 15.6 18.8
9070T3000D1 81.9 67.2 149.1 2.24 96.1 2.04 9.3 532 415 338 294 285 7.7 9.3
9070T5000D1 143.3 83.7 227 1.67 95.6 1.52 7.2 781 648 558 507 495 8.5 10.2
9070T50D3 4.5 7.1 11.6 7.97 81.1 8.01 10.5 40 29 21 17 15 24.1 28.9
9070T75D3 7.3 6.8 14.1 4.94 84.2 5 15.9 48 38 31 26 25 28 33.6
9070T100D3 7.3 10.2 17.5 6.82 85.1 6.9 15.4 60 45 34 27 25 26.8 32.2
9070T150D3 10.5 10.8 21.3 4.77 87.6 5.25 20.2 73 57 45 38 36 31.2 37.4
9070T200D3 10.5 19.5 30 7.7 86.9 7.83 18 102 73 53 40 36 19.7 23.7
9070T250D3 14.1 17.8 31.9 5.73 88.7 5.73 3.5 109 82 63 52 48 22.9 27.5
9070T300D3 13.3 18.8 32.1 5.6 90.3 5.62 6 110 82 61 49 45 11 13.2
9070T350D3 16.4 19.9 36.3 5.07 90.6 5.08 4.9 124 94 73 60 56 16 19.2
9070T500D3 20.7 30.6 51.3 5.47 90.7 5.48 5.3 175 129 97 77 71 12.9 15.5
9070T750D3 30.8 37.9 68.7 4.57 91.6 4.58 5.7 235 178 138 113 105 17.4 20.9
9070T1000D3 35.4 51.3 86.7 4.83 92 4.84 6 296 219 165 132 121 10.3 12.3
9070T1500D3 51.5 51.3 102.8 3.25 93.6 3.3 8 351 274 220 187 176 10.5 12.6
9070T2000D3 81.8 50 131.8 2.31 93.8 2.31 6.3 450 375 322 290 279 15.6 18.8
9070T3000D3 81.9 74.5 156.4 2.37 95 2.39 11.9 534 423 343 296 280 7.7 9.3
9070T5000D3 142.5 90.6 233.1 1.81 95.5 1.62 15.3 801 657 560 505 488 8.5 10.2
9070T50D20 7.3 6.8 14.1 4.94 84.2 5 15.9 48 38 31 26 25 28 33.6
9070T75D20 7.3 10.2 17.5 6.82 85.1 6.9 15.4 60 45 34 27 25 26.8 32.2
9070T100D20 10.5 10.8 21.3 4.77 87.6 5.25 20.2 73 57 45 38 36 31.2 37.4
9070T150D20 10.5 19.5 30 7.7 86.9 7.83 18 102 73 53 40 36 19.7 23.7
9070T200D20 14.1 17.8 31.9 5.73 88.7 5.73 3.5 109 82 63 52 48 22.9 27.5
9070T250D20 13.3 18.8 32.1 5.6 90.3 5.62 6 110 82 61 49 45 11 13.2
9070T300D20 16.4 19.9 36.3 5.07 90.6 5.08 4.9 124 94 73 60 56 16 19.2
9070T350D20 20.7 30.6 51.3 5.47 90.7 5.48 5.3 175 129 97 77 71 12.9 15.5

9070CT9901 39
Class 9070 Type T Transformers

Inrush (x FL
FL BTU/hr RMS)
Catalog Core Coil Reg Eff
Total %IZ X/R
Number Watts Watts 1.0PF 100%
Watts 100- No 60 50
75% 50% 25%
% Load Hz Hz
9070T500D20 30.8 37.9 68.7 4.57 91.6 4.58 5.7 235 178 138 113 105 17.4 20.9
9070T750D20 35.4 51.3 86.7 4.83 92 4.84 6 296 219 165 132 121 10.3 12.3
9070T1000D20 51.5 51.3 102.8 3.25 93.6 3.3 8 351 274 220 187 176 10.5 12.6
9070T1500D20 81.8 50 131.8 2.31 93.8 2.31 6.3 450 375 322 290 279 15.6 18.8
9070T2000D20 81.9 74.5 156.4 2.37 95 2.39 11.9 534 423 343 296 280 7.7 9.3
9070T3000D20 143.3 84.8 228.1 1.63 95.6 1.64 11.8 779 652 562 507 489 8.5 10.2

Type T - Special Quote Request Sheet

Determine VA by Load Requirements

Dual or CT Secondary

Secondary Voltages: ____ x ____ or ____ CT

Amps at higher of the two voltages ________

Tapped Unit Separate Windings

Secondary 1: ______ Volts ______ Amps Secondary 1: ______ Volts ______ Amps

Secondary 2: ______ Volts ______ Amps Secondary 2: ______ Volts ______ Amps

Secondary 3: ______ Volts ______ Amps Secondary 3: ______ Volts ______ Amps

Secondary 4: ______ Volts ______ Amps Secondary 4: ______ Volts ______ Amps

Secondary 5: ______ Volts ______ Amps

Secondary Simultaneous Loading?

If Yes: VA Sizing ______

S1: V x A + S2: V x A + S3: V x A + S4: V x A + S5: V x A

If No: VA Sizing ______

Largest VA of the secondary listed above: V x A

Dual Primary _____ x _____ Volts

Tapped Unit

Primary 1: _____ Volts

Primary 2: _____ Volts

Primary 3: _____ Volts

Primary 4: _____ Volts

Primary 5: _____ Volts

Technical Data

Regulation Requirements: ______ VA @ ______ PF for ______% Voltage Drop

BTU Requirements: ______ No Load Max ______ Total Full Load Max

Dimensions

If dimensions are critical, provide them below (or supply a drawing with dimensions clearly marked):

Maximum size in inches: _____ H ____ W _____ D

All units will have standard Type T features:

Temperature Rise, Insulation Material, Terminal Board, cULus and CE Marked,

Footprints for VA frame created above.

40 9070CT9901
Transformers with Leads Class 9070

Transformers with Leads


Transformers with leads instead of screw terminals are available. The lead length is
24 inches. See the following chart for VA sizes and voltage combinations. Contact
your Schneider Electric representative for further details.

Table 37 - Voltage and Connection Options

Primary Secondary
Voltage Code Connection Connection
Voltage Voltage

D3 208 120
D4 277 120
550 110
D5 575 115
600 120
D6 380 110
220 110
D8 230 115
240 120 H1 H2
Connect to H1 and H2 Connect to X1 and X2
440 110
D9 460 115 X2 X1
480 120
D17 415 110
110 110
D24 115 115
120 120
D93 200 115
D103 400 120

Table 38 - Class 9070 Type EL, KL

Weight A B C E F Slots
Catalog
VA
Number kg
lbs. in. mm in. mm in. mm in. mm in. mm in mm

0.20 x
50 9070EL1 2.2 1.0 2.63 67 3.00 76 2.50 64 2.00 51 2.50 64 5 x 10
0.38
0.20 x
100 9070EL2 3.8 1.7 3.00 76 3.38 86 2.81 71 2.38 60 2.81 71 5 x 10
0.38
0.20 x
150 9070EL3 6.0 2.7 3.63 92 3.75 95 3.13 80 2.88 73 3.13 80 5 x 10
0.38
0.20 x
300 9070KL300 8.0 3.6 3.50 89 4.50 114 3.75 95 3.81 97 3.75 95 5 x 10
0.38

9070CT9901 41
Class 9070 Transformers with Leads

A
E

F C
B

42 9070CT9901
Fuse Protection Class 9070

Fuse Protection
UL Standards and the National Electrical Code® require primary protection for Control
Transformers, and many applications require secondary protection. Historically, the
fuse options supplied by transformer manufacturers were designed for Line-to-Line
primary (480 V) and Line-to-Neutral secondary (120 V).
Schneider Electric’s line of fuse options allows customers to obtain both factory- and
field-installed fuse blocks. Factory installation saves you time and labor. For both
options, the transformer footprint is identical to a Type T transformer of equivalent
voltage, because the fuse block is mounted above the transformer or on the
transformer terminal blocks. This frees up space normally used by separate fuse
blocks.
Schneider Electric offers the most complete offering of fuse options to meet all
applications for protection of the transformers and load applications. These are
broken down into Line-to-Line and Line-to-Neutral protection options for both primary
and secondary. Due to space limitations of the transformers, not all options are
available for every VA size. Also, all fuse blocks supplied by Schneider Electric are 30
A fuse blocks, which limits the VA for each voltage.
All primary fuse blocks supplied by Schneider Electric require rejection style fuses.
Rejection style fuses offer 100,000 AIC protection to comply with UL Standards. (Non-
rejection style primary fuse blocks are available by request only and can be quoted
through your Schneider Electric field sales office.)

Primary Secondary

VA Range VA Range with VA Range with


Voltage without Primary Primary Voltage Secondary
Protection Protection Protection
550/575/600 25–5000 VA 25–5000 VA 277 25–5000 VA
440/460/480 25–5000 VA 25–5000 VA 220/230/240 25–5000 VA
380/400/415 25–5000 VA 25–5000 VA 208 25–5000 VA
277 25–5000 VA 25–3000 VA 110/115/120 25–2000 VA
220/230/240 25–5000 VA 25–3000 VA 48 25–1000 VA
208 25–5000 VA 25–2000 VA 24 25–500 VA
110/115/120 25–2000 VA 25–1500 VA 12 25–250 VA

Table 39 - Matrix for Choosing Proper Fuse Configuration

Primary Line-to- Primary Without


Primary Line-to-Line Neutral Protection
No factory installed
Secondary Line-to-Line option Type TF with R12 S22
Secondary Line-to-
Neutral Type TF Type TF with R11 S12
Secondary Without
Protection Type TF with R02 Type TF with R01 Type T product line

Primary voltages requiring Line-to-Line protection: 200/208/220/230/240/380/400/

415/440/460/480/550/575/600
Primary voltages requiring Line-to-Neutral 100/110/115/120/277/347
protection:
Europe: 220/230/240

9070CT9901 43
Class 9070 Fuse Protection

Secondary voltages requiring Line-to-Line 208/220/230/240


protection:

Secondary voltages requiring Line-to-Neutral 120/277


protection:
Europe: 220/230/240

NOTE: The following secondary voltages could be either Line-to-Line or Line-to-


Neutral: 12/24/48.

Applications for Line-to-Line Primary protection and Line-to-Line Secondary protection,


H1 H4
Example would be 480 to 120/240 (Voltage Code D31)
H3 H2
Available as field-installed only for 9070 Type T

X2 X3 Must order one 9070FB2A(B)—Primary


X4 X1 Must order one 9070S22A(B)—Secondary

Application for Line-to-Line Primary protection and Line-to-Neutral Secondary protection


H1 H4
Example would be 480 to 120 (Voltage Code D1)
H3 H2
Available as factory- and field-installed

Factory-installed—9070 Type TF or 9070


X2 X1 Field-installed—9070 Type T: 9070FB3A or 9070FB3B

Application for Line-to-Line Primary protection and No Secondary protection


H1 H4
Example would be 480 to 24 (Voltage Code D2)
H3 H2
Available as factory- and field-installed

Factory-installed—9070 Type TF with R02 suffix


X2 X1 Field-installed—9070 Type T: 9070FB2A or 9070FB2B

Application for No Primary protection and Line-to-Line Secondary


H1 H4
Example would be 480 to 120/240 (Voltage Code D31)
H3 H2
Primary protection done elsewhere in the circuit

X2 X3 Available as factory- and field-installed


X4 X1 Factory-installed—9070 Type T

Field-installed—9070 Type T: 9070S22A or 9070S22B

Application for Line-to-Neutral Primary and Line-to-Line Secondary


H1 H4
Example would be 277 to 120/240

Available as factory- and field-installed

H3 H2 Factory-installed—9070 Type TF with R12 suffix


X2 X1 Field-installed—9070 Type T: 9070R12A or 9070R12B

44 9070CT9901
Fuse Protection Class 9070

Application for No Primary protection and Line-to-Neutral Secondary


H1 H4
Example would be 480 to 120 (Voltage Code D1)
H3 H2
Primary protection done elsewhere in the circuit

Factory-installed options

X2 X1
1. 9070 Type T with S12 suffix Secondary fuse block; midget-type fuses
2. 9070 Type T with SF25 suffix
Secondary fuse block; glass-type fuses
3. 9070 Type T with SF41 suffix
Secondary fuse clips mounted on terminal block
Field-installed options
1. 9070 Type T:
Midget-type fuse block: 9070FB1A or 9070FB1B
Midget-type fuse clips: 9070SF41A or 9070SF41B (Limited to single secondary only)
Glass-type fuse holder: 9070AP2

Application for Line-to-Neutral Primary and Line-to-Neutral Secondary


H1 H2
Example would be 277 to 120 (Voltage Code D4)

Factory-installed—9070 Type TF with R11 suffix

Field-installed—9070 Type T: 9070R11A or 9070R11B


X2 X1

Application for Line-to-Neutral Primary and No Secondary


H1 H2
Example would be 277 to 24 (Voltage Code D24)

Factory-installed—9070 Type TF with R01 suffix

Field-installed—9070 Type T: 9070R01A or 9070R01B

X2 X1

9070CT9901 45
Class 9070 Fuse Protection

Table 40 - Fuse Protection Options

Protection Example Factory Installed Option(s) Field Installed Option(s)

480 to 120/240
Line-to-Line Primary 9070FB2A(B) - Primary
(Voltage Code Not available
and Secondary 9070S22A(B) - Secondary
D31)

Line-to-Line Primary 480 to 120


and Line-to-Neutral (Voltage Code 9070 Type TF 9070 Type T: 9070FB3A or 9070FB3B
Secondary D1)

480 to 24
Line-to-Line Primary
(Voltage Code 9070 Type TF with R02 suffix 9070 Type T: 9070FB2A or 9070FB2B
and No Secondary
D2)

480 to 120/240
No Primary and Line-
(Voltage Code 9070 Type T 9070 Type T: 9070S22A or 9070S22B
to-Line Secondary
D31)

Line-to-Neutral 277 to 120/240


Primary and Line-to- (Voltage Code 9070 Type TF with R12 suffix 9070 Type T: 9070R12A or 9070R12B
Line Secondary D60)

9070 Type T with S12 suffix


9070 Type T:
Secondary Fuse Block - midget fuses
Midget type fuse block: 9070FB1A or 9070FB1B
480 to 120 9070 Type T with SF25 suffix
No Primary and Line- Midget type fuse clips: 9070SF41A or 9070SF41B
(Voltage Code Secondary Fuse Block - glass type
to-Neutral Secondary (Limited to single secondary only)
D1) fuses
Glass type fuse block: 9070SF25A or 9070SF25B
9070 Type T with SF41 suffix
Glass type fuse holder: 9070AP2
Secondary Fuse Clips mounted on
Side mounted 2-inch x 9/16-inch: 9070AP1
terminal block
Line-to-Neutral 277 to 120
Primary and Line-to- (Voltage Code 9070 Type TF with R11 suffix 9070 Type T: 9070R11 or 9070R11
Neutral Secondary D4)

Line-to-Neutral 277 to 24
Primary and No (Voltage Code 9070 Type TF with R01 suffix 9070 Type T: 9070R01A or 970R01B
Secondary D24)

46 9070CT9901
Fuse Protection Class 9070

Table 41 - Description of Accessory Keys

Catalog Number
Description
Accessory Keys
Accessory Key I
II, III, IV

Two-pole fuse block with rejection clips for primary fusing, field mounted on terminal board via
9070FB2A 9070FB2B Fingersafe cover, 1-1/2-inch x 13/32-inch midget fuse

One-pole fuse block with rejection clips for primary fusing, field mounted on terminal board via
9070R10A 9070R10B Fingersafe cover, 1-1/2-inch x 13/32-inch midget fuse

Three-pole fuse block, two poles with rejection clips for primary fusing and one pole standard clips for
9070FB3A 9070FB3B secondary fusing, field mounted on terminal board via Fingersafe cover, 1-1/2-inch x 13/32-inch
midget fuse

Two-pole fuse block, one pole with rejection clips for primary fusing and one with standard clips for
9070R11A 9070R11B secondary fusing, field mounted on terminal board via Fingersafe cover, 1-1/2-inch x 13/32-inch
midget fuse

Three-pole fuse block, one pole with rejection clips for primary fusing and two poles standard clips for
9070R12A 9070R12B secondary fusing, field mounted on terminal board via Fingersafe cover, 1-1/2-inch x 13/32-inch
midget fuse

One-pole fuse block with standard clips for secondary fusing, field mounted on terminal board via
9070FB1A 9070FB1B Fingersafe cover, 1-1/2-inch x 13/32-inch midget fuse

Two-pole fuse block with standard clips for secondary fusing, field mounted on terminal board via
9070S22A 9070S22B Fingersafe cover, 1-1/2-inch x 13/32-inch midget fuse

Secondary fuse clips mounted on terminal board, prevents the use of Fingersafe covers, only field
9070SF41A 9070SF41B installable on single voltage secondary units, 1-1/2-inch x 13/32-inch midget fuse

One-pole fuse block with standard clips for secondary fusing, field mounted using Fingersafe cover
9070SF25A 9070SF25B notches, prevents the use of Fingersafe covers, 1-1/4-inch x 1/4-inch glass fuse

One-pole fuse block with standard clips for secondary fusing, field mounted next to transformer using
9070AP1 9070FB same mounting hardware, 2-inch x 9/16-inch fuse

One-pole twist fuse block with standard clips for secondary fusing, field mounted next to transformer
907AP2 9070FB using same mounting hardware, 1-1/4-inch x 1/4-inch glass fuse

Table 42 - Fuse Sizing, Description, and Catalog Number (by manufacturer)

Manufacturer
Size Description
Bussman Littelfuse Gould-Shawmut
ATDR
1-1/2 x 13/32 in. midget Time delay, rejection-type, FNQ-R KLDR
ATQR
fuse class CC LP-CC CCMR
ATMR
1-1/2 x 13/32 in. midget Time delay FNM; FNQ FLQ; FLM; FLA ATQ; TRM; GFN
fuse

Time delay TDC-11; MDL; MDQ; 3AG: 313/315


1-1/4 x 1/4 in. GDL
MDA 3AB: 326/325

NOTE:
These fuses are not supplied by Schneider Electric.
This table is provided for primary fusing recommendation ONLY. Secondary fusing
must be specified by the customer.
All primary fuse options offered by Schneider Electric require rejection-type fuses.

9070CT9901 47
Class 9070 Fuse Protection

Accessories
Table 43 - Fingersafe™ Covers (not supplied with unit) – Compliant with IP2X per EN-60529

VA Accessory Key14
Class Type Description
I II III

FSC-1 25–200 VA 25–100 VA N/A


2 covers per
9070 FSC-2 250–5000 VA 150–5000 VA N/A
kit
FSC-23 N/A N/A 25–5000 VA

Table 44 - Fuse Puller—For ease in installing fuses and finger protection, used with fuse blocks with 1-1/2 in.
x 13/32 in. fuses

VA Accessory Key
Class Type Description
I II III
Fuse puller kit complies with IP00 per EN-
9070 FP-1 ALL ALL ALL 60529, 3 pullers per kit.

NOTE: Final IP rating is determined by the enclosure where the transformer is


used.

14. Kits must be ordered separately. Also supplied in bulk packages of 100 individual covers. Add “B” to Type number if ordering bulk (available
only on FSC-1B and FSC-2B).

48 9070CT9901
Fuse Protection Class 9070

Primary Fusing to Meet NEC


Table 45 - Recommended Fuse Sizes for the PRIMARY (use class CC time delay fuses) to Meet NEC

120 Volts 240 Volts 480 Volts 600 Volts


Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
Primary Rating Rating Primary Rating Rating Primary Rating Rating Primary Rating Rating
VA Current with without Current with without Current with without Current with without
Am- Secon- Secon- Am- Secon- Secon- Am- Secon- Secon- Am- Secon- Secon-
peres dary dary peres dary dary peres dary dary peres dary dary
Protec- Protec- Protec- Protec- Protec- Protec- Protec- Protec-
tion tion tion tion tion tion tion tion
25 0.21 1/2 1/2 0.1 1/4 1/4 0.05 1/8 1/8 0.04 1/10 1/10
50 0.41 1 1 0.21 1/2 1/2 0.1 2/10 2/10 0.08 2/10 2/10
75 0.63 1-1/2 1-1/2 0.31 6/10 6/10 0.16 3/10 3/10 0.13 3/10 3/10
100 0.83 2 2 0.42 1 1 0.21 1/2 1/2 0.17 4/10 4/10
150 1.25 3 3 0.63 1-1/2 1-1/2 0.31 6/10 6/10 0.25 6/10 6/10
200 1.67 4 4 0.83 2 2 0.42 1 1 0.33 8/10 8/10
250 2.08 5 3-2/10 1.04 2-1/2 2-1/2 0.52 1-1/2 1–1/4 0.42 1 1
300 2.5 6-1/4 4 1.25 3 3 0.63 2 1–1/2 0.5 1–1/8 1–1/8
350 2.92 7 4-1/2 1.46 3-1/2 3-1/2 0.73 2-1/2 1–8/10 0.58 1–4/10 1–4/10
500 4.17 10 6-1/4 2.08 5 3-2/10 1.04 3 2–1/2 0.83 2 2
750 6.25 15 10 3.13 7-1/2 5 1.56 3-1/2 3–1/2 1.25 3 3
1000 8.33 20 12 4.17 10 6-1/4 2.08 5 3–2/10 1.67 4 4
1500 12.5 N/A 15 6.25 15 10 3.13 7-1/2 5 2.5 6–1/4 4
2000 16.66 N/A 20 8.33 20 12 4.17 10 6 1/4 3.33 8 5

NOTE:
Recommended fuse sizes per NEC Article 450-3.
Transformers with primary only, select protection at 125%, if a standard size rating
is not available, go to next higher rating.
Transformers with primary only and current rating is less than 9 A, select
protection at no more than 167%.
Transformers with primary only and current rating is less than 2 A, select
protection at no more than 300%.
Transformers with primary and secondary, select primary protection at not more
than 250% and secondary at 125%.
If a standard size rating is not available, go to next higher standard rating.

9070CT9901 49
Class 9070 Fuse Protection

Primary Fusing to Meet CE


Table 46 - Recommended Fuse Sizes for the PRIMARY (use time delay fuses) for CE Applications

CE VA Primary Voltage
Rating
120 V 208 V 240 V 277 V 380 V 416 V 480 V 600 V
25 1/2 3/10 2/10 2/10 1/10 1/10 1/10 1/10
50 1 6/10 1/2 4/10 3/10 3/10 2/10 2/10
75 1-1/2 8/10 6/10 6/10 4/10 4/10 3/10 3/10
100 2 1-1/8 1 8/10 6/10 6/10 1/2 4/10
150 3 1-8/10 1-1/2 1-1/4 8/10 8/10 6/10 6/10
160 3-2/10 1-8/10 1-6/10 1-4/10 1 8/10 8/10 6/10
200 4 2-1/4 2 1-8/10 1-1/4 1-1/8 1 8/10
250 4 3 2-1/2 2 1-6/10 1-1/2 1-1/4 1
300 5 3-1/2 3 2-1/2 1- 8/10 1-8/10 1-1/2 1-1/8
500 7-1/2 4 3-2/10 4-1/2 3-2/10 3 2-1/2 2
630 9 6 5 4-1/2 4-1/2 4-1/2 3-1/2 3
1000 15 8 6-1/4 6 4 4 4 4
1500 15 12 10 9 6-1/4 6 6-1/4 5
2000 20 12 12 12 8 8 7 7
3000 n/a 25 25 20 15 15 12 12

NOTE: Recommended fuse sizes according to testing, EN 61558.

50 9070CT9901
Fuse Protection Class 9070

Secondary Fusing to Meet NEC and CE


Table 47 - Recommended Fuse Sizes for the SECONDARY to Meet NEC and CE

24 Volts 120 Volts 240 Volts


VA Secondary Secondary Secondary
Fuse Rating Fuse Rating Fuse Rating
Current Rating Current Rating Current Rating

25 1.04 8/10 0.21 3/10 0.1 15/100


50 2.08 3 0.42 6/10 0.21 3/10
75 3.13 5 0.63 1 0.31 1/2
100 4.17 6 0.83 1-1/4 0.42 6/10
150 6.25 10 1.25 2 0.63 1
200 8.33 12 1.67 2-1/2 0.83 1-1/4
250 10.42 15 2.08 3 1.04 1-3/4
300 12.5 20 2.5 4 1.25 2
350 14.58 20 2.92 5 1.46 2-1/2
500 20.83 30 4.17 7 2.08 3
750 n/a n/a 6.25 10 3.13 5
1000 n/a n/a 8.33 12 4.17 7
1500 n/a n/a 12.5 15 6.25 10
2000 n/a n/a 16.67 20 8.33 12

NOTE:
Recommended fuse sizes according to NEC Article 450-3.
Secondary select protection at 125%, if a standard size rating is not available, go
to next higher standard size rating.
Current rating is less than 9 A, select protection at not more than 167%.

9070CT9901 51
Class 9070 Type TF Transformers

Type TF Transformers
120 Volt Control Secondary—Primary and Secondary Fuse Block
Table 48 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

220 or 230 or 240: H1 H4


Connect to H1 and H4
220 x 440 110 Jumper H1 with H3 H3 H2
D1 230 x 460 115 Jumper H2 with H4 Connect to X1 and X2
240 x 480 120 440 or 460 or 480:
Connect to H1 and H4
Jumper H2 with H3
X2 X1

Table 49 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20 x 5x
25 25 9070TF25D1 40 I 3.09 79 3.00 76 4.00 102 2.00 51 2.50 64
0.38 10
0.20 x 5x
50 50 9070TF50D1 40 I 3.09 79 3.00 76 4.00 102 2.00 51 2.50 64
0.38 10
0.20 x 5x
75 75 9070TF75D1 40 I 3.34 85 3.38 86 4.18 106 2.38 61 2.81 71
0.48 12
0.20 x 5x
100 100 9070TF100D1 40 I 3.34 85 3.38 86 4.18 106 2.38 61 2.81 71
0.48 12
0.20 x 5x
150 150 9070TF150D1 40 I 3.59 91 3.75 95 4.50 114 2.88 73 3.13 80
0.38 10
0.20 x 5x
200 200 9070TF200D1 40 I 3.59 91 3.75 95 4.50 114 2.88 73 3.13 80
0.38 10
0.20 x 5x
250 160 9070TF250D1 41 I 5.30 135 3.75 95 4.50 114 2.88 73 3.13 80
0.38 10
0.20 x 5x
300 200 9070TF300D1 41 I 4.74 120 4.50 114 5.13 130 2.56 65 3.75 95
0.38 10
0.20 x 5x
350 250 9070TF350D1 41 I 5.11 130 4.50 114 5.13 130 3.00 76 3.75 95
0.38 10
0.20 x 5x
500 300 9070TF500D1 41 I 5.49 139 4.50 114 5.13 130 3.56 90 3.75 95
0.38 10
0.28 x 7x
750 500 9070TF750D1 41 I 5.61 143 5.25 133 5.80 147 3.43 87 4.38 111
0.56 14
0.28 x 7x
1000 630 9070TF1000D1 41 I 6.30 160 5.25 133 5.80 147 4.31 109 4.38 111
0.56 14
0.28 x 7x
1500 1000 9070TF1500D1 41 I 5.92 150 7.06 179 7.46 190 4.13 105 5.81 148
0.56 14
0.28 x 7x
2000 1500 9070TF2000D1 41 I 7.17 182 7.06 179 7.46 190 4.56 116 5.81 148
0.56 14

52 9070CT9901
Type TF Transformers Class 9070

Figure 36 - Figure 37 -

D
A B DA B

C
G C
G

F E
F E

MultiTap for 120 Volt Control Secondary—Primary and Secondary


Fuse Block
Table 50 - Voltage and Connection Options

Voltages Connections
Voltage Code
Primary Secondary Primary Secondary

208: Connect to
H1 and H2
208
230: Connect to
D20 230 115 Connect to X1 and X2
H1 and H3
460
460: Connect to
H1 and H4

Table 51 - Dimensions

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.20 x 5x
25 25 9070TF25D20 42 II 3.09 79 3.00 76 4.00 66 2.00 51 2.50 64
0.38 10
0.20 x 5x
50 50 9070TF50D20 42 II 3.34 85 3.38 86 4.18 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
75 75 9070TF75D20 42 II 3.34 85 3.38 86 4.18 73 2.38 61 2.81 71
0.48 12
0.20 x 5x
100 100 9070TF100D20 42 II 3.59 91 3.75 95 4.50 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
150 150 9070TF150D20 42 II 3.59 91 3.75 95 4.50 81 2.88 73 3.13 80
0.38 10
0.20 x 5x
200 200 9070TF200D20 43 II 4.70 119 3.75 95 4.50 114 2.88 73 3.13 80
0.38 10
0.20 x 5x
250 160 9070TF250D20 43 II 4.74 120 4.50 114 5.13 98 2.56 65 3.75 95
0.38 10
0.20 x 5x
300 200 9070TF300D20 43 II 5.11 130 4.50 114 5.13 98 3.00 76 3.75 95
0.38 10
0.20 x 5x
350 250 9070TF350D20 43 II 5.49 139 4.50 114 5.13 98 3.56 90 3.75 95
0.38 10
0.28 x 7x
500 300 9070TF500D20 43 II 5.61 143 5.25 133 5.80 115 3.43 87 4.38 111
0.56 14
0.28 x 7x
750 500 9070TF750D20 43 II 6.30 160 5.25 133 5.80 115 4.31 109 4.38 111
0.56 14

9070CT9901 53
Class 9070 Type TF Transformers

Table 51 - Dimensions (Continued)

VA Catalog Acc. A B C E F Slots


Fig.
Number Key
UL CE in. mm in. mm in. mm in. mm in. mm in. mm

0.28 x 7x
1000 630 9070TF1000D20 43 II 5.92 150 7.06 179 7.46 157 4.13 105 5.81 148
0.56 14
0.28 x 7x
1500 1000 9070TF1500D20 43 II 7.17 182 7.06 179 7.46 157 4.56 116 5.81 148
0.56 14
0.44 x 11 x
2000 1500 9070TF2000D20 43 II 6.38 162 9.00 229 8.92 227 4.63 118 7.63 194
1.13 29

Figure 38 - Figure 39 -

D
A B DA B

C
G C
G

F E
F E

54 9070CT9901
Field Installed Fuse Options Class 9070

Field Installed Fuse Options


Primary Fusing

Figure 40 - FB2A
3.13
(80)

1.62
(41)

2.10
(53)

Figure 41 - FB2B
3.21
(82)

1.98
(49)

2.07
(53)

in
Dimensions: (mm)

9070CT9901 55
Class 9070 Field Installed Fuse Options

Figure 42 - R01A
3.13
(80)

1.38
(35)

2.10
(53)

Figure 43 - R01B
3.21
(82)

1.56
(40)

2.07
(53)

in
Dimensions: (mm)

56 9070CT9901
Field Installed Fuse Options Class 9070

Primary and Secondary Fusing

Figure 44 - FB3A

3.13
(80)

2.39
(61)

2.10
(53)

Figure 45 - FB3B

3.21
(82)

2.75
(70)

2.07
(53)

in
Dimensions: (mm)

9070CT9901 57
Class 9070 Field Installed Fuse Options

Figure 46 - R11A
3.13
(80)

1.62
(41)

2.10
(53)

Figure 47 - R11B
3.21
(82)

1.98
(50)

2.07
(53)

in
Dimensions: (mm)

58 9070CT9901
Field Installed Fuse Options Class 9070

Figure 48 - R12A

3.13
(80)

2.39
(61)

2.10
(53)

Figure 49 - R12B

3.21
(82)

2.75
(70)

2.07
(53)

in
Dimensions: (mm)

9070CT9901 59
Class 9070 Field Installed Fuse Options

Secondary Fusing

Figure 50 - FB1A
3.13
(80)

1.38
(35)

2.10
(53)

Figure 51 - FB1B
3.21
(82)

1.56
(40)

2.07
(53)

in
Dimensions: (mm)

60 9070CT9901
Field Installed Fuse Options Class 9070

Figure 52 - S22A
3.13
(80)

1.62
(41)

2.10
(53)

Figure 53 - S22B
3.21
(82)

1.98
(50)

2.07
(53)

in
Dimensions: (mm)

9070CT9901 61
Class 9070 Field Installed Fuse Options

Figure 54 - SF25A
2.77
(70)

0.67
(17)

0.95
(24)

Figure 55 - SF25B
2.31
(59)

0.52
(13)

0.97
(25)

in
Dimensions: (mm)

62 9070CT9901
Field Installed Fuse Options Class 9070

Figure 56 - AP1

.13
(3)

.21
(5)

2.17
(55)

3.02 1.46
(77) (37)

Figure 57 - AP2

1.67 2.73
(42) (69)

1.70
(43)

.13
(3)

.21
(5)

in
Dimensions: (mm)

9070CT9901 63
Class 9070 Field Installed Fuse Options

Secondary Fuse Clips

Figure 58 - SF41A
0.47
(12)

0.44
(11)

0.88
(22)
0.25
(6)

0.45
(11) 0.70
(18)

Jumper Fuse Clip

Figure 59 - SF41B
0.54
(14)

0.49
(12)

0.92
(23) 0.25
(6)

0.78 0.71
(20) (18)

Jumper Fuse Clip

in
Dimensions: (mm)

64 9070CT9901
Field Installed Fuse Options Class 9070

Terminal Blocks

Figure 60 -

2.77 0.88
(70) (22)
0.25
(6)

0.45
Screw size: 6-32 (11)
Ring lug: #6 stud with a
0.375 in. max O.D.
Torque: 6-9 in-lbs
Jumper

25–200 VA: Key I


25–150 VA: Key II

2.25 0.92
(57) (23) 0.25
(6)

0.78
(20)

Screw size: 8-32


Ring lug: #8 stud with a
0.438 in. max O.D.
Torque: 13-16 in-lbs Jumper

250–5000 VA: Key I


200–5000 VA: Key II

All four pole: Key III and IV

3.44 0.92
(87) (23) 0.25
(6)

0.78
(20)

Screw size: 8-32


Ring lug: #8 stud with a
0.438 in. max O.D.
Torque: 13-16 in-lbs Jumper

All six pole: Key III and IV

in
Dimensions: (mm)

9070CT9901 65
Class 9070 Application

Application
In preparation for connecting power to the primary side of dual voltage single-phase
transformers, it's necessary to first wire the two windings in either series or parallel to
match the incoming voltage. An example of this is common transformers with a
primary voltage description of 240 x 480. The windings are rated for the lower of the
two voltages show on either side of the 'x'. Connecting the windings in series allows
for the higher of the two voltages. Connecting the windings in parallel allows for the
lower of the two voltages.

Example of Series and Parallel Connections


Jumper

H1 H3 H2 H4

X4 X2 X3 X1
Jumper

Series Connections

Jumper Jumper

H1 H3 H2 H4

X4 X2 X3 X1
Jumper Jumper

Parallel Connections

NOTE: This diagram is for illustration purposes only. Actual units will have
different combinations. See diagrams for actual connections.

66 9070CT9901
Application Class 9070

Example of a typical application


• OEM customer base source voltages in United States: 208, 240, or 480 volts
(From past shipments 480 is 65% of the business, 208 is 20%, and 240 is 10%)
• 5% of business goes into Canada and needs 600 volts; customer always knows
when equipment goes to Canada.
• Load requirement is for a 500 VA transformer, load is 120 volt control
For this customer, Schneider Electric has the following solutions:
Solution 1
Three standard units with interchangeable dimensions
9070T500D1—240 x 480 to 120; handles 75% of business. For details, see Voltage
and Connection Options, page 11.
9070T500D3—208 to 120; handles 20% of business. For details, see Voltage and
Connection Options, page 13.
9070T500D5—600 to 120; handles 5% of business. For details, see Voltage and
Connection Options, page 13.
Solution 2
Two MultiTap units with interchangeable dimensions
9070T500D20—208/230/460 to 115; handles 95% of business {US Voltage Code}.
For details, see Voltage and Connection Options, page 15.
9070T500D32—230/460/575 to 95/115; handles 5% of business {North American
Voltage Code}; covers 460 and 575 Canadian sources. For details, see , page 15.
Solution 3
One Universal Control Transformer
9070T500D50—240/416/480/600 to 99/120/130. For details, see Voltage and
Connections Options, page 17.

9070CT9901 67
Class 9070 Technical Data

Technical Data
50/60 Hertz
Transformers that are dual rated for 50/60 Hz are truly global units and no derating is
required for voltages or VA. Type T are 50/60 Hz.
Base Plates
The development of welded cores has allowed the incorporation of base plates on
larger VA transformers. Base plates are usually welded to the core of the transformer
for a solid connection to the transformer. They allow manufacturers to offer more
standardized mounting for specific VA sizes by allowing multiple core stacks.
Available for Type T transformers only.
Touch-Safe Terminals
Being able to offer touch-safe terminals is increasing in importance. Currently all
equipment that must comply with EN 60-204 (Machine and Low Voltage Directives)
must have some type of barrier for live parts. Besides the CE standard listed above,
domestic customers are requiring barriers on live parts with voltages above 460 V.
These customers allow Plexiglas® covers to be installed for these barriers.
Type T transformers can be made finger-safe by using snap-on covers that are
removable with a screwdriver or other flat tool. Schneider Electric offers Fingersafe™
covers, which are sold separately. See Fingersafe™ Covers (not supplied with unit) –
Compliant with IP2X per EN-60529, page 48for ordering information.
Formed Terminal Board
Formed terminal boards are used on multiple VA ranges and different voltage
combinations. This allows the manufacturer to punch jumpers for customer
interconnections and gives the customer the same basic layout for all units. The snap-
on covers for touch-safe terminations also are available on units with formed terminal
boards. Available for Type T transformers only.
Varnish Vacuum Impregnation
This is a manufacturing process for the core and coil of industrial control transformers.
The transformer is put into a tank of varnish, then the varnish is put into a vacuum,
causing the varnish to be forced throughout the coil and core. After being vacuum
impregnated, the units are cured in an oven to seal the varnish. The varnish is
absorbed by any paper insulation system and coats other insulation with another layer
of electrical strength. The process causes the coil to have a very tight connection
because it is completely bonded and mechanically very strong. The cores are also
tightly bonded with the varnish, causing the units to have better heat transfer and less
vibration noise.
Schneider Electric uses this process on all control transformers, using a clear varnish
with optimum electrical characteristics.

68 9070CT9901
Frequently Asked Questions Class 9070

Frequently Asked Questions


Question Answer

When a Multitap Unit might be for you:


1. Transformer will be installed in a device whose source voltage is unknown at time of shipment;
2. Space is not critical (MultiTaps are larger than standard units);
3. You sell to markets with multiple source voltages;
Should you consolidate your control 4. Reduced number of parts will offset premium for MultiTap units.
transformer to a MultiTap or Universal When a MultiTap Unit might not be beneficial:
Control Transformer? 1. High percentage of your business is 240 x 480 source voltage;
2. Space is an issue;
3. Source voltage is always known at time of shipment;
4. Source voltage changes other components in the control circuit;
5. Premium for MultiTap does not get offset by having fewer parts.

No, they cannot. Industrial control transformers terminals are specifically marked “primary” and
Can a 9070 type T or TF control “secondary”. As such, the National Electrical Code (NEC) and Underwriters Laboratories (UL) prohibit
transformer be used in a back connecting the source to other than the primary terminals. Also, since industrial control transformers
(reverse) feed application as a step-up utilize compensated windings to accommodate the high regulation inherent in such small
transformer? transformers, the resulting voltage ratio would be lower than desired. In other words, if a control
transformer were reverse fed, the output voltage would be lower than desired.

While the 9070 Type TF industrial control transformer comes with a three-pole fuse block (two
Does Schneider Electric provide fuses rejection-type, Class CC fuses for the primary, and one non-rejection-type, midget fuse for the
for the primary and the secondary of a secondary), Schneider Electric does not provide the fuses. Proper fuse selection is the installer’s
9070 Type TF industrial control responsibility and is dictated by NEC table 450-3(b) and any specific application parameters that exist
transformer? with any industrial control transformer installation.

My 9070 Type T or TF industrial control The nameplate of your Schneider Electric 9070 Type T or TF industrial control transformer clearly
transformer has four terminals on both marks out that the outside terminals of each side are used for the customer installed wire connections.
the primary and secondary, but only Schneider Electric makes a standard four- or six-terminal block for various transformer designs for
markings on the wiring diagram of commercial cost effectiveness. With only two terminals being used, it is standard practice for it to
H1and H2 on the primary and X1 and always be the outside terminals. Several different transformer voltage and wiring arrangements are
X2 on the secondary. Which terminal shown in this catalog.
do I use?
How do the 9070-FB3A, 9070-FB2A, When factory installed on a 9070 Type TF control transformer, they mount on the center of the core on
and 9070-FB-1A fuse blocks mount on factory installed studs. When field installed by the customer on a 9070 Type T control transformer,
a 9070 Type T control transformer they mount over one of the terminal strips using hardware supplied with the fuse block kit. (There are
when factory installed? When field no studs on the 9070 Type T, only on the Type TF.)
installed?
Does Schneider Electric offer epoxy Schneider Electric does not offer epoxy encapsulated industrial control transformers. The 9070 Type
encapsulated versions of its 9070 T and TF industrial control transformer is the premier offering in the industry and is suitable for virtually
Type T and TF control power any installation appropriate for a CPT.
transformers?
What is the sound level for a 9070 Sound levels for general purpose and control transformers are per NEMA ST-20 sound levels. For
Type T control transformer? Type T control transformers, this level is 40dB maximum.

Yes. Replacement jumper kits contain two jumpers per kit and must be ordered in minimum quantities
of 50 kits.
Are replacement jumper kits offered Use kit number 30033-027-53 for Accessory Key I (25–200 VA) and
for Schneider Electric’s 9070 Type T Accessory Key II (25–150 VA).
and TF industrial control transformers? Use kit number 30033-027-54 for Accessory Key I (250–5000 VA),
Accessory Key II (200–3000 VA), and Accessory Key III ( 25–3000 VA).

Do 9070 industrial control transformers Schneider Electric 9070 Type T and TF industrial control transformers do not contain any material that
contain any materials, such as PCBs, would require any special disposal means and can be disposed of in the normal manner. Since the
lead, or other heavy metals, that would majority of the transformer is built of recyclable material (steel, copper, etc.), Schneider Electric urges
require special disposal means the customer to recycle the unit if possible.

A triple rating on the control transformer`s voltage code basically means that the transformer is
designed to successfully operate at voltages slightly different than the nominal voltage at its full VA
capacity. This is done to allow for different voltage systems that require the same voltage ratios, say
What does a “triple rating” mean in 4:1 or 2:1.
terms of an industrial control Example: The 9070T250D1 is a triple rated voltage code unit that can supply 250 VA with the
transformers voltage code? following input voltages and the corresponding output:
Input: 240 or 480 Output: 120
Input: 230 or 460 Output: 115
Input: 220 or 440 Output: 110

What is the maximum fuse ampere


The maximum ampere rating of the fuse blocks and fuse clips offered by Schneider Electric for the
rating that can be used in a factory or
9070 Type T control transformers is 30 amps. If higher fuse ratings are required, then the customer
field installed fuse block or fuse clip for
will have to provide the supplementary fuse holder provisions.
a 9070 Type T control transformer?

9070CT9901 69
Class 9070 Frequently Asked Questions

Question Answer

On a 9070 Type T or TF industrial The capabilities of the various 9070 Type T and TF tranformers vary widely. Some units can only have
control transformer with more than one one voltage out with a given voltage in. Others can have more than one. Contact your Schneider
secondary voltage available, can more Electric representative for assistance.
than one secondary voltage be utilized If a satisfactory model is not available, Schneider Electric has the capability of building virtually any
or only one? industrial control transformer a customer may need.

The CE mark is the official marking required by the European Community for all Electric and
What does the CE VA rating mean in Electronic equipment that will be sold, or put into service for the first time, anywhere in the European
selecting a 9070 Type T control community. CE VA is the rated capacity of the control transformer according to the CE standard. By
transformer? bearing the CE marking, a transformer can be sold into any of the participating European countries
without having to first clear with that country whether it will accept the UL rating.

An installer had been told by an


electrical engineer to ground a 9070
Type T control transformer’s frame to The 9070s base is plated to keep it from rusting. Schneider Electric does not provide grounding
the enclosure with a star washer. If this provisions on transformer, as grounding is the responsibility of the installer per NEC requirements.
is so important, why does Schneider
Electric plate the base of the
transformer?
Does a Schneider Electric 9070 Type
T or TF industrial control transformer
have any continuous overload Transformers are 100% rated devices. As such, they do not have any continuous overload capacity.
capacity? What about momentary They are specifically designed for momentary currrent draw in excess of their rating for high inrush
overloads due to high inrush loads, type loads.
such as may occur with a coil on a
contactor?
Does a 9070 Type T or TF transformer
Industrial control transformers do not have to list their impedance on their nameplate. They can be
need to have its impedance listed on
used anywhere in the world where their UL, CSA, or CE listing allows, or where they are allowed by
its nameplate to be used in any
the local jurisdiction.
particular area in the world?

What is the difference between an old The CE rated, NOM approved Type T transformer replaces the Type K, which is no longer available.
9070 Type K transformer and a new The Type T matches the Type K in function and form, but not necessarily in fit, i.e., the dimensions
9070 Type T? may vary.

The fuse puller accessories (9070FP1) do offer some protection when used and the fuse is in place,
however they do not qualify the block for any additional standards. While the fuse block is CE marked,
Does Schneider Electric offer finger- the fuse puller kit does not comply with European standards for finger-safe, as it does not require a
safe covers for use with 9070 Type T tool to remove it. However, this may not be critical as Schneider Electric does not recommend
and TF transformer fuse blocks? shipping our fuse block or 9070TF to Europe, as the fuses used there are different than those used in
North America. Thus, the customer should supply their own fuse block suitable for the European
fuses when the transformer is to be used in Europe.

The NEC requires the transformer feeding the low voltage lighting system to be a part of the UL listed
Can a 9070 Type T control power lighting system as assembled by the Original Equipment Manufacturer (OEM). A contractor,
transformer or a general purpose distributor, or end user cannot assemble their own low voltage lighting system and comply with the
transformer be used to provide power NEC without going through UL. If the OEM has a particular transformer listed in their UL file, then that
for 24V lighting, 120V to 24V unit may be used.
application? So if the Schneider Electric 9070 Type T device is part of a lighting system that is UL listed, the
answer is yes.

70 9070CT9901
Schneider Electric
800 Federal Street
Andover, MA 01810
USA
888–778–2733
www.se.com

As standards, specifications, and design change from time to time,


please ask for confirmation of the information given in this publication.

© 1999 – 2021 Schneider Electric. All rights reserved.


9070CT9901

You might also like