RM6-9916 Series Operation Manual
RM6-9916 Series Operation Manual
Operation Manual
ISO 9001:2008
Thank you for using RHYMEBUS RM6 series (9916) AC motor drive. For proper
operations and safety purposes, please do read and follow specific instructions
contained in this manual before using the product. The manual shall be placed on the
top of the machine, and all the setup parameters and reference numbers must be
properly recorded in Attachment 3 to facilitate future maintenance and repairs.
SAFETY PRECAUTION
Please read this manual thoroughly and pay attention to the safety precautions
marked with “ DANGER ” or “ CAUTION ” before the installation, wiring,
maintenance, or troubleshooting.
Only the qualified personnel may proceed with the installation, wiring, testing,
troubleshooting, or other tasks.
※Qualified Personnel: Must be familiar with the fundamentals, structures,
characteristics, operating procedures, and installation, and this personnel must
read the manual in details and follow the steps of security measures to prevent
possible dangers.
Installation
CAUTION
a. The installation shall take place only on top of the metal surface or any material
with the fire resistant. Any place or location of high temperature, moist, oil and
gas, cotton fiber, metal powder and erosive gas shall be avoided.
b. If the product specification indicates IP00 (the protective level of the equipment
structure), any human contact is forbidden to avoid the electric shock. The option
of installing AC reactor(ACL) or DC reactor(DCL) shall be very cautious, too.
c. Please note the surrounding temperature shall not exceed 50°C when the
installation needs to be placed inside the control panel.
d. For the environment of storage and installation, please follow the instructions of
the environmental conditions illustrated in the sections of the common
specification of RM6 series (9916).
i
Wiring
DANGER
a. Do Not conduct any wiring during the system power ON to avoid the electric shock.
b. R/L1,S/L2,T/L3 are power inputs (electric source terminals) and U/T1,V/T2,W/T3
are drive’s outputs connecting to a motor. Please Do Not connect these input and
output terminals to P, P○+ , N, N○- , P1 and PR terminals.
c. Once the wiring is completed, the cover of the drive must be put back and must
seal the drive to avoid other’s accidental contact.
d. Do Not connect 200V series drives to the electric source of 346/380/415/440/
460/480V.
e. The main circuit and multi-function terminals cannot connect to ground (PE).
f. PE terminal must be exactly grounded. Ground the drive in compliance with
the NEC standard or local electrical code.
g. Please refer to the “section 2-3-4 Description of Terminals” for the screwing
torque of the wiring terminal.
h. Please refer to the national or local electric code for the appropriate spec. of the
cords and wires.
i. Please install an appropriate Molded Case Circuit Breaker (MCCB) or Fuse at
each path of power lines to a drive.
j. Please install the thermal relay between the individual motor and the drive when
using one drive to propel several motors.
k. Do Not connect phase leading capacitor, surge absorber, or non-three-phase
motor to drive’s U/T1,V/T2,W/T3 side.
l. AC reactor(ACL) installation is required when the power capacity exceeds
500kVA or more than 10 times of drive’s rated capacity.
m. After power off (30HP below models must wait at least 5 minutes; 40HP~75HP
models must wait at least 10 minutes; 100HP above models must wait at least
20 minutes). Do Not touch the drive or perform any unwiring actions before drive
indicator light (CHARGE) turns off. Use a multimeter with the DC voltage stage
to measure the cross voltage between P(+) and N(-) ports (DC bus voltage must
be less than 25V).
n. When the motor do the voltage-proof, insulation testing, unwiring the U/T1,V/T2,W/T3
terminal of drive at first.
CAUTION
a. The RM6 series (9916) are designed to drive a three-phase induction motor. Do
Not use for single-phase motor or other purposes.
b. The main circuit and control circuit must be wired separately; control circuit must
use a shielded or twisted-pair wires to avoid possible interferences.
c. The control circuit must use a shielded or twisted-pair shielded wires to avoid
possible interferences and confirm the grounding.
ii
Operation
DANGER
a. Do Not open or remove the cover while power is on or during the operation. Do
close up the cover before powering on the drive. Do Not remove the cover except
for wiring or periodic inspection.
b. At the function F_078=1 or 3, the drive will automatically restart when the power
is restored. Stay away from the motor and machine.
c. At the function F_003=0 and F_001=0 or 1, the OFF
key on keypad is ineffective.
RESET
CAUTION
a. Do Not touch the heat sink or brake resistors due to the high heat.
b. Some models attach nylon rope when shipping. Do Not proceed the movement
or hanging the drive by this nylon rope to avoid unexpecting accident. Please
select a suitable rope to proceed the movement or hanging the drive.
iii
Compliance with UL standards and CSA standards (cUL-listed for Canada)
CAUTION
1. "Risk of Electric Shock"
Before starting or inspection, turn OFF the power and wait at least 5 minutes,
and check for residual voltage between terminal P and N with a multi-meter or
similar instrument has dropped to the safe level (50VDC or below), to avoid a
hazard of electric shock.
2. These devices are intended for use in Pollution Degree 2 environments.
3. “Maximum surrounding air temperature 50C for RM6 series(9916).
4. Short circuit rating
“Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 240V maximum for 200V class. Models RM6
series(9916) rated for 200V class input.”
“Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 480V ma ximum for 400V class. Models RM6
series(9916) rated for 400V class input.”
“Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
National Electrical Code and any additional local codes.”
5. Install UL certified branch circuit fuse between the power supply and the drive,
referring to the table below.
Three-Phase 200V Series
Model number Fuse type Fuse current rating (A)
RM6-20P5-9916 5
RM6-2001-9916 10
Class RK5
RM6-2002-9916 15
(250Vac, 200kA I.R.)
RM6-2003-9916 20
RM6-2005-9916 30
RM6-2007-9916 50
Class T
RM6-2010-9916 80
(300Vac, 200kA I.R.)
RM6-2015-9916 100
iv
Compliance with UL standards and CSA standards (cUL-listed for Canada)
(continued)
CAUTION
Three-Phase 400V Series
Model number Fuse type Fuse current rating (A)
RM6-4001-9916 5
RM6-4002-9916 Class RK5 10
RM6-4003-9916 (600Vac, 200kA I.R.) 15
RM6-4005-9916 20
RM6-4007-9916 30
RM6-4010-9916 Class T 30
RM6-4015-9916 (600Vac, 200kA I.R.) 40
RM6-4020-9916 60
v
Compliance with UL standards and CSA standards (cUL-listed for Canada)
CAUTION
vi
INTRODUCTIONS
Features
vii
Table of Contents
ix
No Text on This Page
x
Chapter 1 Cautions Before Installation
HXXXXXXXX
RM6-2050B3-9916
Input Power Specs INPUT AC 3PH 200-240V 50/60Hz
Output Current & Capability OUTPUT 0.1-400.0Hz 7.5kW 33A
Software Number PGM NO. 9916-FS1(AZXXXXXX)
Product Serial Number SERIAL NO. HXXXXXXXX
Model code
(see maximum
applicable motor)
Input Voltage
2:AC 200~240V
4:AC 380~480V
Product Series
1
1
Chapter 1 Cautions Before Installation
1-1-3 Confirmation of Accessories
One operation manual is inclusive. Please verify other accessories
inclusively such as braking resistor, AC reactor, etc..
※Please refer to the standard specifications to verify the product
specifications with your requirements.
1-2 Standard Specifications
1-2-1 Three-Phase 200V Series
Model name
20P5 2001 2002 2003 2005 2007 2010 2015
(RM6-□□□□B3-9916)
Maximum applicable motor
0.5/0.4 1/0.75 2/1.5 3/2.2 5/3.7 7.5/5.5 10/7.5 15/11
(HP / kW)
Rated output capability (kVA) 1.1 1.9 3 4.2 6.5 9.5 13 18
Rated output current (A) 3 5 8 11 17 25 33 46
Maximum Output Voltage Three-phase 200~240V (corresponding input voltage)
Range of output frequency
0.1~400.00Hz
(Hz)
Power source (ψ, V, Hz) Three-phase 200~240V 50/60Hz
Input current (A) 5 6 10 14 18 30 40 60
Permissible AC power
176~264V 50/60Hz / ±5%
source fluctuation
Overload protection 150% of drive rated output current for 1 min.
Cooling method Nature cooling Fan cooling
UL508C, CSA
Applicable safety standards UL508C, CSA C22.2 No.14-05 -
C22.2 No.14-05
IP20, UL open
Protective structure IP20, UL open type IP20
type
Weight / Mass(kg) 1.8 1.8 1.9 2.0 2.1 3.0 5.4 5.7
Model name
2020 2025 2030 2040 2050 2060 2075
(RM6-□□□□B3/E3-9916)
Maximum applicable motor
20/15 25/18.5 30/22 40/30 50/37 60/45 75/55
(HP / kW)
Rated output capability (kVA) 23 28 34 44 55 67 84
Rated output current (A) 60 74 90 115 145 175 220
Maximum Output Voltage Three-phase 200~240V(corresponding input voltage)
Range of output frequency
0.1~400.00Hz
(Hz)
Power source (ψ, V, Hz) Three-phase 200~240V 50/60Hz
Input current (A) 69 85 103 132 176 200 240
Permissible AC power
176~264V 50/60Hz / ±5%
source fluctuation
Overload protection 150% of drive rated output current for 1 min.
Cooling method Fan cooling
Applicable safety standards -
Protective structure IP20 IP00 (IP20 OPTION)
Weight / Mass(kg) 12.4 13.1 14.7 14.8 42.7 44.3 46.3
1
2
Chapter 1 Cautions Before Installation
Model name
2100 2125 2150 2200 2250 -
(RM6-□□□□E3-9916)
Maximum applicable motor
100/75 125/90 150/110 200/160 250/200 -
(HP / kW)
Rated output capability (kVA) 112 132 154 223 267 -
Rated output current (A) 295 346 405 585 700 -
Maximum Output Voltage Three-phase 200~240V(corresponding input voltage)
Range of output frequency
0.1~400.00Hz
(Hz)
Power source (ψ, V, Hz) Three-phase 200~240V 50/60Hz
Input current (A) 280 330 380 550 660 -
Permissible AC power
176~264V 50/60Hz / ±5%
source fluctuation
Overload protection 150% of drive rated output current for 1 min.
Cooling method Fan cooling
Applicable safety standards -
Protective structure IP00 (IP20 OPTION)
Weight / Mass(kg) 63.6 89 90 164 167 -
1
3
Chapter 1 Cautions Before Installation
Model name
4025 4030 4040 4050 4060 4075 4100 4125
(RM6-□□□□B3/E3-9916)
Maximum applicable motor
25/18.5 30/22 40/30 50/37 60/45 75/55 100/75 125/90
(HP / kW)
Rated output capability (kVA) 30 34 46 56 66 84 114 134
Rated output current (A) 39 45 61 73 87 110 150 176
Maximum Output Voltage Three-phase 380~480V(corresponding input voltage)
Range of output frequency
0.1~400.00Hz
(Hz)
Power source (ψ, V, Hz) Three-phase 380~480V 50/60Hz
Input current (A) 45 61 74 90 105 130 155 177
Permissible AC power
332~528V 50/60Hz / ±5%
source fluctuation
Overload protection 150% of drive rated output current for 1 min.
Cooling method Fan cooling
Applicable safety standards -
Protective structure IP20 IP00 (IP20 OPTION)
Weight / Mass(kg) 5.8 12.8 12.9 15.0 15.3 44.0 45.5 46.4
※ 4025 is only available in RM6-□□□□□B3-9916 series model.
※ 4100 and 4125 are only available in RM6-□□□□□E3-9916 series model.
Model name
4150 4175 4200 4250 4300 4350 4420 4500 4600
(RM6-□□□□E3-9916)
Maximum applicable motor 150/ 175/ 200/ 250/ 300/ 350/ 420/ 500/ 600/
(HP / kW) 110 132 160 200 220 250 315 375 450
Rated output capability (kVA) 160 193 232 287 316 366 446 533 655
Rated output current (A) 210 253 304 377 415 480 585 700 860
Maximum Output Voltage Three-phase 380~480V(corresponding input voltage)
Range of output frequency
0.1~400.00Hz
(Hz)
Power source (ψ, V, Hz) Three-phase 380~480V 50/60Hz
Input current (A) 196 217 282 355 385 440 540 650 800
Permissible AC power
332~528V 50/60Hz / ±5%
source fluctuation
Overload protection 150% of drive rated output current for 1 min.
Cooling method Fan cooling
Applicable safety standards -
Protective structure IP00 (IP20 OPTION)
Weight / Mass(kg) 64 64.5 95 97 159 163 164 217 272
※The weight illustrated in the standard specifications of RM6 series (9916) does not include the
weights of AC reactor(ACL) and DC reactor(DCL).
1
4
Chapter 1 Cautions Before Installation
1-3 Common Specifications
1
5
Chapter 1 Cautions Before Installation
Forward/ Reverse, Communication interface(RS-485
Start method
Modbus), 16 sets preset speed.
Multi-function 4 sets programmable input terminals: X1~X4
Input
F_131
․“FM+” – “M”-:DC 0~10V
Analog ․“AM+” – “M”-:DC 0~10V
outputs Refer to the function setting description of F_044, F_045,
F_129, F_130
output frequency, frequency command, output voltage, DC
bus voltage, output current, motor speed(RPM), machine
Keypad (KP-207)
speed(MEM), terminal status and heat sink temperature,
Display
overtime(Cot)
Error trip
messages of
drive for PID feedback signal error(no Fb), Over pressure(OP)
pressure
control
Power source under voltage(LE), Drive output interruption
Warning (bb), Coast to stop(Fr), Dynamic brake transistor over
messages of voltage(db), Software fault(PrEr), Drive overhea (Ht), Keypad
drive cable trip before connecting(Err_00), Keypad cable trip
during operation(Err_01), Over pressure(OP)
1
6
Chapter 1 Cautions Before Installation
․Nature cooling:
20P5, 2001, 4001,4002 models.
Cooling method ․Fan cooling: Three fan control methods for cooling(forced
air, operation air, temperature level setting) for other
models.
Non-corrosive or non-conductive, or non-explosive gas or
Atmosphere
liquid, and non-dusty
Surrounding -10°C (14°F) ~ +50°C (122°F) (Non-freezing and
Environment
temperature non-condensing)
Storage
-20°C (-4°F) ~ +60°C (149°F)
temperature
Relative humidity 90% RH or less (No-condensing atmosphere)
Vibration Less than 5.9m/sec² (0.6G)
Altitude Less than 1000m (3280 ft.)
1
7
Chapter 1 Cautions Before Installation
1
8
Chapter 2 Installation and Confirmation
10cm above
設定值 實際值
SV Running PV
10cm above
2
9
Chapter 2 Installation and Confirmation
2-2-3 Arrangement: Due to the heat generated at the machine operation, the
drive must be installed in the ventilate space. The installations of drive
are shown as below figure 1 and figure 2:
a. Internal cooling
Correct Incorrect
Outlet Outlet
Fan Fan
Fan Fan
Outlet Outlet
RM5G/P RM5G/P
Drive
Driver
Drive
Driver
Inlet
Intlet Inlet
Intlet
Correct Incorrect
Outlet Outlet
Fan Fan
Fan Fan
Outlet Outlet
RM5G/P RM5G/P
Drive
Driver
Drive
Driver
Guide
RM5G/P RM5G/P
Drive
Driver Drive
Driver
Inlet
Intlet Inlet
Intlet
2
10
Chapter 2 Installation and Confirmation
b. External cooling
Correct Incorrect
Outlet Outlet
Fan Fan
Fan Fan
Outlet Outlet
RM5G/P RM5G/P
Drive
Drive
Drive
Drive
Guide
RM5G/P RM5G/P
Drive
Drive
Drive
Drive
Inlet
Intlet Inlet
Intlet Inlet
Intlet Inlet
Intlet
Correct Correct
Outlet Outlet
Fan
Fan Fan
Outlet Outlet
Drive Drive
Inlet
Intlet Inlet
Intlet Inlet
Intlet Inlet
Intlet
Note: The external cooling is suitable for 7.5HP above. Please ensure all air vents to
be ventilated using the external cooling.
2
11
Chapter 2 Installation and Confirmation
2-2-4 Specifications of Associated Accessories: The specifications of the
accessories must be according to the specifications of the drive.
Otherwise, the drive will be damaged and the life span of the drive will be
shorten.
Do Not add any power factor leading capacitor(RC, LC or other capacitance
component) between the drive and motor to avoid any accidents.
M5-2
Screw
Screw
Step2
Screw
M5-4
Screw
Step1
2
12
Chapter 2 Installation and Confirmation
2-3 Descriptions of Terminal and Wiring Diagram
2-3-1 Wiring Diagram
Model: RM6-20P5B3-9916 ~ RM6-2005B3-9916;
RM6-4001B3-9916 ~ RM6-4005B3-9916
Braking Resistor(option)
Main Circuit Terminals
Control Terminals
PR P N Induction Motor
R/L1 R/L1 U/T1
Three-Phase, 50/60Hz
S/L2 S/L2 V/T2 IM
AC Power Input
T/L3 T/L3 W/T3
G RM6 series G
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD GND (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
COM (AC 250V/0.5A COSθ=0.3)
Tb1
(GND)
Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND
(COM) (Open collector)
Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
13
Chapter 2 Installation and Confirmation
Model:RM6-2007B3-9916 ~ RM6-2015B3-9916;
RM6-4007B3-9916 ~ RM6-4025B3-9916
Main Circuit Terminals DC Reactor(DCL; option) ※4
Control Terminals
Jumper
Braking Resistor
(option)
PR P (+) P1 N
Induction Motor
R/L1 R/L1 U/T1
Three-Phase, 50/60Hz
S/L2 S/L2 V/T2 IM
AC Power Input
T/L3 T/L3 W/T3
RM6 series
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD M- (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
(AC 250V/0.5A COSθ=0.3)
COM Tb1
(GND) Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND (Open collector)
(COM) Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shield Wire P
Twisted-Pair
Shield Wire
2
14
Chapter 2 Installation and Confirmation
Model:RM6-2020E3-9916 ~ RM6-2040E3-9916;
RM6-4030E3-9916 ~ RM6-4060E3-9916
DC Reactor(DCL; option) ※4
P (+) P1 N
Induction Motor
Three-Phase, R/L1 R/L1 U/T1
50/60Hz AC S/L2 S/L2 V/T2 IM
Power Input T/L3 T/L3 W/T3
PE RM6 series PE
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD M- (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
(AC 250V/0.5A COSθ=0.3)
COM Tb1
(GND) Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND (Open collector)
(COM) Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
15
Chapter 2 Installation and Confirmation
Model:RM6-2020B3-9916 ~ RM6-2040B3-9916;
RM6-4030B3-9916 ~ RM6-4060B3-9916
DC Reactor(DCL; option) ※4
Main Circuit Terminals
Control Terminals
Braking Resistor(option)
Jumper
PR P (+) P1 N
Induction Motor
Three-Phase, R/L1 R/L1 U/T1
50/60Hz AC S/L2 S/L2 V/T2 IM
Power Input T/L3 T/L3 W/T3
PE RM6 series PE
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD M- (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
(AC 250V/0.5A COSθ=0.3)
COM Tb1
(GND) Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND (Open collector)
(COM) Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
16
Chapter 2 Installation and Confirmation
Model:RM6-2050E3-9916 ~ RM6-2075E3-9916;
RM6-4075E3-9916
DC Reactor(DCL; option) ※4
P♁ P1 N
Induction Motor
Three-Phase, R/L1 R/L1 U/T1
50/60Hz AC S/L2 S/L2 V/T2 IM
Power Input T/L3 T/L3 W/T3
PE RM6 series PE
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD M- (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
(AC 250V/0.5A COSθ=0.3)
COM Tb1
(GND) Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND (Open collector)
(COM) Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
17
Chapter 2 Installation and Confirmation
Model:RM6-2050B3-9916 ~ RM6-2075B3-9916;
RM6-4075B3-9916
Braking Resistor(option)
Main Circuit Terminals
Control Terminals
PR P N Induction Motor
R/L1 R/L1 U/T1
Three-Phase, 50/60Hz
S/L2 S/L2 V/T2 IM
AC Power Input
T/L3 T/L3 W/T3
G RM6 series G
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD GND (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
COM (AC 250V/0.5A COSθ=0.3)
Tb1
(GND)
Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND
(COM) (Open collector)
Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
18
Chapter 2 Installation and Confirmation
Model:RM6-2100E3-9916 ~ RM6-2250E3-9916;
RM6-4100E3-9916 ~ RM6-4600E3-9916
※4
DCL
Main Circuit Terminals
Control Terminals
Jumper
※4
ACL P1 + P1 NӨ Induction Motor
Three-Phase, R/L1 R/L1 U/T1
50/60Hz AC S/L2 S/L2 V/T2 IM
Power Input T/L3 T/L3 W/T3
PE RM6 series PE
(9916)
AM+ (+)
P24 Analog Output Terminal
FM+ (+) (DC 0~10V)
Forward FWD M- (-)
Reverse REV ※1
Multi-function Input Terminal 1 X1 SINK Ta2
Multi-function Input Terminal 2 X2
Multi-function Input Terminal 3 X3 JP5 Tc2 Multi-function Output Terminal
(Relay Type)
Multi-function Input Terminal 4 X4 SOURCE Ta1
(AC 250V/0.5A COSθ=0.3)
COM Tb1
(GND) Tc1
DSW3
ON ※3 DX+ Communication Control
12V P
DX- Terminal
VR 1KΩ,1/4W Vin ※2 FG
I
1
Iin JP4
Y1
P P P V Multi-function Output Terminal
GND (Open collector)
(COM)
Y2 (DC 48V/50mA)
Analog input control CME
(Default: DC 0~10V)
Analog input signal
(default: DC 4~20mA) Shielded Twisted-Pair
P
Wire Shielded Wire
2
19
Chapter 2 Installation and Confirmation
2-3-2 SINK / SOURCE Definition
There are two ways of connection for multi-function input terminals:
X1~X4 X1~X4
FWD FWD
REV REV
+24V
COM COM
0V 0V 0V
(a) Jumper at 1,2 position; SINK mode (b) Jumper at 2,3 position; SOURCE mode
Figure(a) and (b) show two examples by using a switch to control X1 to X4, FWD, or
REV terminals with sink or source mode.
SOURCE SOURCE
PLC(NPN) Drive PLC(PNP) Drive
+24V
X1~X4 X1~X4
FWD FWD
REV +24V REV
COM COM
0V 0V 0V
Jumper at 1,2 position; SINK mode (b) Jumper at 2,3 position; SOURCE mode
Figure(a) and (b) show two examples by using PLC to control X1 to X4, FWD, or
REV terminals with sink or source mode.
2
20
Chapter 2 Installation and Confirmation
2-3-4 Description of Terminals
AC power
R,S,T Three-phase; sinusoidal power
source input
(L1,L2,L3) source input terminal.
Power terminals
Source DC power External DC power source terminal.
※Only 2007, 2010, 2015, 4007, 4010,
+, N○
○ - source input
4015, 4020, 4025 models have the
terminals terminal.
Drive outputs
U,V,W Output three-phase variable
Motor to motor
(T1,T2,T3) frequency and voltage to motor.
terminals
P(+), N(-)
Dynamic brake The terminals can connect to
unit terminal dynamic braking unit (option).
P(+), N○
-
Power
External
and The terminals can connect to
P(+), PR braking resistor
Braking external brake resistor (option).
terminal
2
21
Chapter 2 Installation and Confirmation
b. Main Circuit Connection
(1)
G G
Grounding
R S T P(+) N PR U V W
Grounding
MCCB
Motor
Resistor
(2)
Jumper
Motor
Resistor
Terminal Tightening Grounding Tightening
Model number screw size torque terminal torque
(except grounding
terminal) lb-in (kgf-cm) size lb-in (kgf-cm)
RM6-______B3-9916:
2007 M4 15.6 (18) M4 13.8 (15)
4007, 4010
2
22
Chapter 2 Installation and Confirmation
(3)
+
-
Grounding Grounding
Jumper
MCCB
Motor
Resistor
Terminal Tightening Grounding Tightening
Model number screw size torque terminal torque
(except grounding
terminal) lb-in (kgf-cm) size lb-in (kgf-cm)
RM6-______B3-9916:
2010,2015 M5 20.8 (24) M4 13.8 (15)
4015,4020,4025
(4)
MCCB
Jumper
Motor
2
23
Chapter 2 Installation and Confirmation
(5)
+
-
Grounding Grounding
Jumper
MCCB
Motor
Resistor
(6)
PE PE
R S T U V W N P1 P
/L1 /L2 /L3 /T1 /T2 /T3 - +
Grounding
MCCB
Grounding
Motor
2
24
Chapter 2 Installation and Confirmation
(7)
PE PE
R S T U V W N PR P
/L1 /L2 /L3 /T1 /T2 /T3 - +
Grounding
Grounding
Resistor
MCCB
Motor
(8)
PE PE
R S T U V W N P1 P
Grounding /L1 /L2 /L3 /T1 /T2 /T3 - +
DBU
MCCB
Motor Resistor
DCL
ACL
Grounding
+, N○
※Be cautious of the electrodes of DBU when connecting to P○ - terminals of drive to
avoid any possible damages to drive.
2
25
Chapter 2 Installation and Confirmation
c. Voltage Selection Board of Cooling Fan
※RM6-4075-9916 above models have the voltage selection board shown in above
figure when removing the back cover of the drive. Please carefully select the
jumper position according to the power source (actual power voltage level) to
avoid the burnout of the fan or the overheating of the drive.
(EX: When the power source is 460V, selecting the position from 380V to 460V)
d. Control Terminals
Type Symbol Function Description
Output DC+24V; Maximum supplied current
P24
Power terminal; is 50mA.
Control power
command
․Connect the X2 and COM terminals and
Multi-function input set the function F_053.
X2 ․Default setting: Multi-speed level 2
terminal 2
command
․Connect the X3 and COM terminals and
Multi-function input set the function F_054.
X3
terminal 3
․Default setting: Jog command
․Connect the X4 and COM terminals and
Multi-function input set the function F_055.
X4
terminal 4 ․Default setting: Secondary accel/decel
time command
2
26
Chapter 2 Installation and Confirmation
Type Symbol Function Description
Common of digital
COM Common of digital input control signal
Control circuit terminal
input control
(GND) terminals. (FWD, REV and X1 ~ X4)
terminals
Input terminals
2
27
Chapter 2 Installation and Confirmation
(1) RM6-20P5-9916~RM6-2005-9916
(2) RM6-4001-9916 ~ RM6-4005-9916
CN3
GFD
SINK
SINK
SOURCE I mode V mode
SINK JP5
JP4 JP4
SOURCE
JP5
TB1
SOURCE JP1
DSW3
1
ON
SINK
1
V
SOURCE X3 X2 COM X1 FM_P CME Vin GND Iin M- DX+ DX- FG Tc1 Ta1 Tb1 Tc2 Ta2
CN1
2
28
Chapter 2 Installation and Confirmation
(3) RM6-2007-9916 ~ RM6-2250-9916
RM6-4007-9916 ~ RM6-4600-9916
GFD
1
SINK
I mode
CN1
SINK
5
CN2
JP4 JP1
JP5
JP4
I
V mode SOURCE
V
SOURCE
JP4
SINK
DX+
DX-
JP5
JP5
FG
SINK 1
TB3
2
SOURCE
3 SOURCE
ON
TB1
DSW3
FM+ AM+ 12V Vin GND Iin FWD COM REV P24 X4 Ta2 Tc2
2
29
Chapter 2 Installation and Confirmation
b.The wiring length between drive and motor must keep as short as
possible. The parasitic capacitance effect is minor within 10 meters.
The drive shall connect an AC reactor (ACL) on the side of drive output
terminals U/T1,V/T2,W/T3 and decrease the switching frequency if the
wiring length is over 30m.
c.If the drive is used at the altitude over than 1000m, the relationship of
drive’s rated current and altitude is shown as below figure.
100%
Percentage 90%
of the rated
current of 80%
drive
70%
60%
0 1000 2000 3000 4000 Altitude (m)
2
30
Chapter 2 Installation and Confirmation
d.Recommend wire size and Molded Case Circuit Breaker(MCCB)
2
31
Chapter 2 Installation and Confirmation
Three-Phase 400V Series
Input Input wire size Control circuit Grounding
Model number MCCB
current (R/L1,S/L2,T/L3) wire size wire size
RM6-_____-9916 (A)
(A) (mm²) (mm²) (mm²)
4001 3.5 5 2.0 2.0
4002 5 10 2.0 2.0
4003 8 15 2.0 2.0
4005 12 20 3.5 3.5
4007 16 30 3.5 3.5
4010 22 30 5.5 5.5
4015 28 40 8.0 8.0
4020 38 60 8.0 8.0
4025 45 70 14 14
4030 52 90 22 22
4040 70 100 22 22
4050 84 125 22 22
4060 100 150 38 0.75 ~ 1.25 38
4075 130 200 60 60
4100 155 250 80 80
4125 177 300 100 100
4150 196 300 60*2 60*2
4175 217 350 100*2 100*2
4200 282 400 100*2 100*2
4250 355 600 150*2 150*2
4300 385 600 200*2 200*2
4350 440 700 250*2 250*2
4420 540 800 250*2 250*2
4500 650 1000 325*2 325*2
4600 800 1200 325*2 325*2
Cautions:
i. Please refer to the local electrical code with respect to the wiring(the loading
and continuity, the wire capability for the current and temperature, the length of
wiring, and the surrounding temperature must be all considered in order to add
or reduce the size of the wire).
ii. Please use the cable that is suitable for 600V, 75℃ above.
iii. This table is only for reference.
2
32
Chapter 2 Installation and Confirmation
2-4 The Setting and Installing of Pessure Transducer
Wiring for Pessure Transducer
Example:
Pressure Transducer
Power Supply:DC24V
Output Single:DC4~20mA
Accuracy:0~10bar Drive
±1% F.S.
JP4
– +
I
P24 Iin
Parameter Setting
Range of Pessure Transducer :0~10bar
Analog Input
F_125 Setting 4 Feedback signal cammand
Selection
2
33
Chapter 2 Installation and Confirmation
2
34
Chapter 3 The Setting of Keypad
KEYPAD
SV PV
ON
3
35
Chapter 3 The Setting of Keypad
3-1-2 Keys of Keypad (KP-207)
UP key
UP key
Up/down key of changing functions and
parameters
DOWN key
Note:
KP-207 cables: Only used with 8-pin telephone cable (flat) or network cable (AMP)
8-pin telephone cable: The cable length must be within 5 meters.
Network cable (AMP): The cable length can be over 5 meters (the longest length is 100 meters)
There are 6 specifications length of network cable (AMP) for KP-207 keypad (1M, 2M, 3M,
5M, 7M, 10M).
3
36
Chapter 3 The Setting of Keypad
3-2 The Operation of Keypad(KP-207) and Monitor Mode
3-2-1 Operation of Keypad
The operation of the digital keypad includes fault messages and three
modes. The switching methods are shown as below figure:
OFF
RESET PROG
KEYPAD
Running
SV PV
Fault message
KEYPAD
2.Press PROG
key and enter the function setting mode.
Running
SV PV
KEYPAD
3.Press FUN
DATA key and enter the parameter setting mode.
Running
SV PV
KEYPAD
4.Press FUN
DATA key and return to the function setting mode.
Running
SV PV
KEYPAD
5.Press PROG
key and return to the monitor mode.
Running
SV PV
KEYPAD
3
37
Chapter 3 The Setting of Keypad
3-2-2 Description of Monitor Mode
(1)Air compressor mode ( or )
FUN
There are nine displays can be selected in the monitor mode. Press DATA
FUN FUN
DATA DATA
Display 8
(Terminal Status and Display 3
Heat Sink Temperature) (Output Voltage)
KEYPAD KEYPAD
Running Running
SV PV SV PV
FUN FUN
Monitor Mode
DATA DATA
Display 7 Display 4
(Machine Speed(MPM)) (F_153≠0) (DC Bus Voltage)
KEYPAD KEYPAD
Running Running
SV PV SV PV
FUN FUN
DATA DATA
Display 6 Display 5
(Motor Speed(RPM)) (Output Current)
KEYPAD KEYPAD
FUN
DATA
Running Running
SV PV SV PV
KEYPAD
KEYPAD
3
38
Chapter 3 The Setting of Keypad
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
KEYPAD
X4
X3 Heat sink
REV temperature
X1
Left Display Right Display
*grey-color digit in above figure means blinking
3
39
Chapter 3 The Setting of Keypad
The significance of seven-segment displays
Display Terminal Description Display Terminal Description
FWD
X4 terminal is
FWD terminal is X4
active
active
REV Ta1,Tb1
REV terminal is Ta1,Tb1 terminal is
active active
X1 terminal Ta2 terminal is
X1 Ta2
is active active
X2 terminal Y1 terminal is
X2 Y1
is active active
X3 terminal Y2 terminal is
X3 Y2
is active active
In (F_153=0) open-loop condition, it can be set any moitor mode 1~8 from
F_006 (Selection of Main Display) at monitor mode, the drive will
automatically switch back to the main display after 3 minute.
Display 1 Display 2 Display 3
(Output Frequency) (Frequency Command) (Output Voltage)
KEYPAD KEYPAD KEYPAD
FUN FUN
DATA DATA
FUN FUN
DATA DATA
Display 8 Display 4
(Terminal Status and (DC Bus Voltage)
Heat Sink Temperature)
KEYPAD
Monitor Mode KEYPAD
(F_153= 0)
Running
Running SV PV
SV PV
FUN FUN
DATA DATA
3
40
Chapter 3 The Setting of Keypad
KEYPAD
KEYPAD
KEYPAD
2.Press FUN
DATA key to enter parameter setting mode. 設定值 實際值
SV Running PV
KEYPAD
KEYPAD
4.Press FUN
DATA key and return to function setting mode. 設定值 實際值
SV Running PV
value is under blinking status) the drive will automatically save the SV.
3
41
Chapter 3 The Setting of Keypad
▲ ▲ KEYPAD
FUN
3. After completing the setting, press key within 5 seconds (the setting
DATA
value is under blinking status) or waiting the drive automatically save the
setting value.
FUN
F_210 (Default Setting) and then press key to DATA
Running
SV PV
enter parameter setting mode.
KEYPAD
3
42
Chapter 3 The Setting of Keypad
enter parameter setting mode.
※Be cautious of the usage of this parameter! This parameter will clear
the saved setting value via parameter.
3
43
Chapter 3 The Setting of Keypad
FUN
F_210 (Default Setting) and then press key to DATA
Running
SV PV
enter parameter setting mode.
▲
KEYPAD
FUN
F_210 (Default Setting) and then press key to
DATA
Running
SV PV
enter parameter setting mode.
2.Press ▲ key to select
KEYPAD
parameter, and
then press key to execute the restoring.
FUN
DATA SV Running
PV
3
44
Chapter 4 Parameter List
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
0: Software version
1: Drive model number
Drive 2: Drive running hours
F_000 ─ ─ ─ 62
Information 3: Drive power supplying time
4: Software checksum code
5: Reserved
Rotation direction
Start command
command
FWD or REV FWD or REV
0
terminal terminal
1 FWD terminal REV terminal
FWD or REV
2
terminal
3 Keypad “ON” key Forward direction
Start
4 Reverse direction
F_001 Command 0~11 ─ 1 62
Selection 5~7 Reserved Reserved
Communication Communication
8
interface interface
Communication
9 REV terminal
interface
Communication
10 FWD terminal
interface
Communication
11 Keypad “ON” key
interface
0: Frequency command by analog signal via
terminal.
1: Frequency command by keypad.
Primary 2: Motor speed (RPM) command by keypad.
Frequency 3: Machine speed (MPM) command by
F_002 0~5 ─ 1 66
Command keypad.
Selection 4: Frequency command by UP/DOWN
terminal.
5: Frequency command by communication
interface.
0: Start command by terminal, “OFF” key
Selection of
disabled.
F_003 “STOP” Key 0,1 ─ 1 67
1: Start command by terminal, “OFF” key
Validity
enabled.
0: In the monitor mode, frequency command
Frequency
cannot be changed.
F_004 Command 0,1 ─ 1 67
Selection 1: In the monitor mode, frequency command
is changeable.
Selection of 0: In the monitor mode, frequency command
Frequency auto-storing disable.
F_005 0,1 ─ 1 67
Command 1: In the monitor mode, frequency command
Auto-Storing auto-storing after 3 minutes.
Selection of F_153=0
F_006 1~8 ─ 1 68
Main Display KP_207 Setting of main display
45 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Digits of
Decimal Value Select the digits of decimal values
F_008 0~3 ─ 0 68
(Machine displaying the machine speed.
Speed)
4 46
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Reference 50.00
Frequency of The frequency corresponding to 0.01~ 0.01 (Note1)
F_018 Accel/Decel accel/decel time. 72
400.00 Hz 60.00
Time (Note2)
Primary
The acceleration time of primary speed,
F_019 Acceleration 72
Time preset speed 4~7, and jog speed.
Primary
The deceleration time of primary speed,
F_020 Deceleration 72
Time preset speed 4~7, and jog speed.
Acceleration
F_021 Time of Preset Acceleration time of preset speed 1. 72
Speed 1
Deceleration
F_022 Time of Preset Deceleration time of preset speed 1. 72
Speed 1
Acceleration
F_023 Time of Preset Acceleration time of preset speed 2. 72
Speed 2 0.0~ 0.1 15.0
3200.0 sec (Note5)
Deceleration
F_024 Time of Preset Deceleration time of preset speed 2. 72
Speed 2
Acceleration
F_025 Time of Preset Acceleration time of preset speed 3. 72
Speed 3
Deceleration
F_026 Time of Preset Deceleration time of preset speed 3. 72
Speed 3
Secondary
Switch to secondary acceleration time by
F_027 Acceleration 72
Time multi-function input terminal.
Secondary
F_028 Deceleration Switch
to secondary deceleration time by
multi-function input terminal. 72
Time
47 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Maximum 50.0
F_031 Output Maximum output frequency of drive. 0.1~400.0 0.1Hz (Note1) 74
Frequency 60.0
(Note2)
Starting
F_032 Starting frequency of drive’s output. 0.1~10.0 0.1Hz 0.5 74
Frequency
8.0
Starting The voltage corresponds to the output (Note3)
F_033 0.1~50.0 0.1V 12.0 74
Voltage starting frequency.
(Note4)
50.0
Base The frequency corresponds to the base (Note1)
F_034 0.1~400.0 0.1Hz 74
Frequency voltage in V/F pattern. 60.0
(Note2)
220.0
The voltage corresponds to the base 0.1~255.0 (Note3)
F_035 Base Voltage 0.1V 74
frequency in V/F pattern. 380.0
0.1~510.0 (Note4)
V/F
F_036 Frequency at the first point of V/F pattern. 0.0~399.9 0.1Hz 0.0 75
Frequency 1
V/F 0.0~255.0
F_037 Voltage at the first point of V/F pattern. 0.1V 0.0 75
Voltage 1 0.0~510.0
V/F Frequency at the second point of V/F
F_038 0.0~399.9 0.1Hz 0.0 75
Frequency 2 pattern.
V/F 0.0~255.0
F_039 Voltage at the second point of V/F pattern. 0.1V 0.0 75
Voltage 2 0.0~510.0
F_040 Vin Gain Analog input “Vin” gain ratio adjustment. 0.00~2.00 0.01 1.00 76
-1.00~
F_041 Vin Bias Analog input “Vin” bias ratio adjustment. 1.00 0.01 0.00 77
The upper limit of output frequency=
Frequency
F_042 F_031(Maximum Output 0.00~1.00 0.01 1.00 77
Upper Limit
Frequency )*F_042
The lower limit of output frequency=
Frequency
F_043 F_031(Maximum Output 0.00~1.00 0.01 0.00 77
Lower Limit
Frequency )*F_043
Analog Output 0: Output frequency
Signal 1: Frequency command
F_044 2: Output current 0~4 ─ 0 82
Selection 3: “Vin” analog input signal.
(FM+) 4: “Iin” analog input signal.
Analog Output
F_045 Gain Analog output gain ratio adjustment. 0.00~2.00 0.01 1.00 83
(FM+)
0: Disable
Motor 1: Overload protection for dependent
F_046 Overload cooling fan type motor: Enabled (OL) 0~2 ─ 1 84
Protection (OL) 2: Overload protection for independent
cooling fan type motor: Enabled (OL)
Filter Setting of Filter the analog input signal when the
F_047 Analog Input frequency command is controlled by analog 0~255 ─ 20 80
Signal input terminal. (F_002=0).
10%~150% According
Motor Rated Set the value according to the motor rated of drive to the
F_048 Current rated
0.1A rated 84
current. current
current of motor
4 48
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
0~motor 1/3
Motor No-Load Current setting according to the motor’s motor
F_049 rated 0.1A rated 84
Current no-load condition. current current
Motor Slip According to the load condition, set the
F_050 Compensa- motor slip compensation for motor running -9.9~10.0 0.1Hz 0.0 84
tion at constant speed. (0.0: off)
Number of Determinate the RPM display value of
F_051 Motor Poles monitor mode. 2~10 P 4P 84
=0: ±1: Jog command
UP/DOWN ±2: Secondary
Multi-function frequency accel/decel time
F_052 Input Terminal command enter key command 3
±3: Multi-speed level
(X1) 1 command
±4: Multi-speed level
2 command
=0: ±5: Multi-speed level
DC braking enable 3 command
Multi-function (at stop) ±6: Reset command
F_053 Input Terminal ±7: External fault 4
command (thr)
(X2) ±8: Interruption of
output command
(bb)
=0: ±9: Coast to stop
Current limit enable command (Fr)
Multi-function ±10: Speed tracing
from the maximum
F_054 Input Terminal frequency 1
(X3) ±11: Speed tracing
from the setting
frequency
=0: ±12: Holding -21 ~ +21 ─ 85
Selection of primary command (Note 8)
or secondary ±13: UP command
Multi-function ±14: DOWN
frequency command
F_055 Input Terminal 18
command ±15: Clear UP/DOWN
(X4)
(ON: secondary frequency
frequency command
command) ±16: Analog input
source selection
±17: Stop command
with 3-wire
start/stop circuit
F_056 Reserved Reserved ±18: Under close-loop ─
control condition
(F_153≠0),
open-loop
selection.
±19: Reset the
integrator at
close-loop
F_057 Reserved Reserved control condition ─
(F_153≠0)
±20: Stop command
±21: Multi-speed level
4 command
49 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
0: Disable
Multi-function ±1: detection during operation
Output ±2: Constant speed detection
F_058 1
Terminal ±3: Zero speed detection
(Y1) ±4: Frequency detection
±5: Overload detection (OLO)
±6: Stall prevention detection
Multi-function
±7: Low voltage detection (LE)
Output
F_059 ±8: Braking detection -16 ~ +16 2
Terminal ─ 93
±9: Restart after instantaneous power failure (Note 8)
(Y2)
detection
±10: Restart after error condition detection
±11: Error detection
Multi-function ±12: Overheating detection
Output ±13: Upper limit of feedback detection
F_060 11
Terminal ±14: On-Off dead band detection
(Ta1,Tb1) ±15: On-Off range detection
±16: Fan detection during operation
Constant
Speed Set the bandwidth of constant speed
F_061 0.0~10.0 0.1Hz 2.0 93
Detection detection range.
Range
Frequency
Set the bandwidth of frequency detection
F_062 Detection 0.0~10.0 0.1Hz 2.0 94
range.
Range
Frequency
Set the frequency detection level of
F_063 Detection 0.0~400.0 0.1Hz 0.0 94
multi-function output terminal.
Level
Automatic
According to the load condition, adjust the
Torque
F_064 output voltage of the V/F pattern. 0.0~25.5 0.1 1.0 98
Compensa-
(0.0: off)
tion Range
System
Overload 0: Disable
F_065 0,1 ─ 0 98
Detection 1: Enable
(OLO)
System
Overload 0: Detection during constant speed only
F_066 0,1 ─ 0 98
Detecting 1: Detection during operation only
Selection
Output 0: Drive keeps operation when the overload is
Setting after detected
F_067 0,1 ─ 0 98
System 1: Drive trips to protection when the overload
Overload is detected
System
When the output current of drive is larger than 30%~200%
Overload of drive
F_068 the level with the duration of F_069, the drive rated 1% 160 98
Detection
will trip to protection. current
Level
System
When the output current of drive is larger than
Overload 0.1
F_069 the level (F_068 * drive’s rated current) with 0.1~25 2.0 98
Detection sec
the duration, the drive will trip to protection.
Time
function can be set during the operation.
4 50
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Stall 30%~200%
If stall is occurred during acceleration, the
Prevention of drive
F_070 motor keeps running at constant speed. rated
1% 170 99
Level at
(200%: off) current
Acceleration
Stall
While the stall is occurred during constant 30%~200%
Prevention
speed running condition, the prevention of of drive
F_071 Level at 1% 160 99
stall is to decrease the speed of motor. rated
Constant
(200%: off) current
Speed
Acceleration
Time Setting
after Stall
Set the acceleration time after stall prevention 0.1~ 0.1 15.0
F_072 Prevention 99
under the constant speed. 3200.0 sec (Note5)
under
Constant
Speed
Deceleration
Time Setting
for Stall
Set the deceleration time at the stall 0.1~ 0.1 15.0
F_073 Prevention 99
prevention under the constant speed. 3200.0 sec (Note5)
under
Constant
Speed
Stall
Prevention 0: Disable
F_074 Setting at 1: Enable 0,1 ─ 1 99
Deceleration
0~150%
DC Braking of drive
F_075 Set the current level of DC braking. 1% 50 100
Level rated
current
Time of DC
Set the time for DC braking after drive 0.1
F_076 Braking after 0.0~20.0 0.5 100
stopped. sec
Stop
Time of DC Set the time for DC braking before drive 0.1
F_077 Braking 0.0~20.0 0.0 100
before Start started. sec
Operation 0: Drive cannot be restarted
Selection at 1: Drive can be restarted
2: Ramp to stop
F_078 Instantane- 3: Drive will re-accelerate again during ramp 0~3 ─ 0 101
ous Power to stop interval, when the power is
Failure restored.
Voltage 150.0~ 175.0
Level of 192.0 (Note3)
Ramp to Set the voltage of power source for ramp to 0.1V 101
F_079 Stop by stop.
300.0~ 320.0
Power
Failure 384.0 (Note4)
Auto-restart When the auto-restart times of error
Times conditions (OC,OE,GF only) reach the setting
F_080 0~16 1 0 105
Setting of value, the drive must be restarted manually.
Error Trip 0: Disable
Switching The setting value is higher and the motor 1
F_081 0~6 ─ 105
Frequency noise is lower. (Note9)
51 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
0: Ramp to stop
F_082 Stop Mode 1: Coast to stop 0~2 ─ 1 106
2: Coast to stop + DC braking
Reverse 0: Reverse rotation allowed.
F_083 0,1 ─ 0 106
Prohibition 1: Reverse rotation NOT allowed.
Jump 103
F_084 Frequency 1 Avoid mechanical resonance point 1. 0.0~400.0 0.1Hz 0.0
Jump
F_085 Frequency 2 Avoid mechanical resonance point 2. 0.0~400.0 0.1Hz 0.0 103
Jump
F_086 Frequency 3 Avoid mechanical resonance point 3. 0.0~400.0 0.1Hz 0.0 103
Jump
F_087 Frequency Set the range of the jump frequency 1, 2, 3. 0.0~25.5 0.1Hz 0.0 103
Range
The Current When the current is higher than the “speed 0~200%
Level of of drive
F_088 Speed tracing current level”, the output frequency 1% 150 103
rated
Tracing will trace downward. current
Delay Time
before Set the output delay time before the speed 0.1
F_089 0.1~5.0 0.5 103
Speed tracing. sec
Tracing
The V/F
Pattern of Set the percentage of V/F output voltage at
F_090 0~100% 1% 100 103
Speed the speed tracing.
Tracing
F_091 Error Record Display the latest 5 error records. ─ ─ ─ 106
0: Parameters are changeable. Maximum
frequency cannot exceed 120.0Hz.
1: Parameters are locked. Maximum
Parameter frequency cannot exceed 120.0Hz.
F_092 0~3 ─ 0 106
Setting Lock 2: Parameters are changeable. Maximum
frequency can exceed 120.0Hz.
3: Parameters are locked. Maximum
frequency can exceed 120.0Hz.
Automatic
Voltage 0: Disable
F_093 0,1 ─ 1 106
Regulation 1: Enable
(AVR)
0: Disable
Drive 1: Electric thermal protection
F_094 Overload 2: Current limit overload protection 0~3 ─ 3 105
(OL1) 3: Electric thermal and Current limit overload
protection are enabled.
190.0~ 220.0
Power The value of setting according to the actual 240.0 (Note3)
F_095 0.1V 105
Source power source. 340.0~ 380.0
480.0 (Note4)
Holding The drive accelerates to the holding
F_096 0.0~400.0 0.1Hz 0.5 104
Frequency frequency and running at constant speed.
function can be set during the operation.
4 52
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Holding
The drive runs at holding frequency by 0.1
F_097 Time 0.0~25.5 0.0 104
constant speed and running the time interval. sec
Interval
Grounding
Fault 0: Disable
F_098 0,1 ─ 1 107
Protection 1: Enable (GF)
(GF)
External Select the monitor mode of external indicator 1 1
F_099 0~10 ─ 104
Indicator 1 0: Disable (Note7)
External Select the monitor mode of external indicator 2 5
F_100 0~10 ─ 104
Indicator 2 0: Disable (Note7)
External Select the monitor mode of external indicator 3 2
F_101 0~10 ─ 104
Indicator 3 0: Disable (Note7)
0: Linear.
1: Energy-saving mode (auto-adjust V/F
V/F Pattern pattern according to the load condition).
F_102 0~4 ─ 0 107
Selection 2: Square curve.
th
3: 1.7 power curve.
th
4: 1.5 power curve.
Subtracted
Frequency When the power failure, drive will reduce the
of frequency level before ramp to stop.
F_103 0.0~20.0 0.1Hz 3.0 101
Deceleration (F_078 Operation Selection at Instantane-
at Power ous Power Failure )=2 or 3
Failure
Deceleration
Time 1 of
Ramp to Set a deceleration time down to the turning 0.0~ 0.1 15.0
F_104 101
Stop by frequency set in F_106. 3200.0 sec (Note5)
Power
Failure
Deceleration
Time 2 of
Ramp to Set a deceleration slope below the frequency 0.0~ 0.1 15.0
F_105 101
Stop by set in F_106 3200.0 sec (Note5)
Power
Failure
Switching
the Set the F_106 when the deceleration time is
F_106 Frequency switched from F_104 setting value to F_105 0.0~400.0 0.1Hz 0.0 101
of Ramp to setting value.
Stop
When the noise of analog input signal is
Analog large, appropriately increase the dead band
0.01
F_107 Frequency to stabilize the frequency command. But 0.00~2.55 0.00 80
Hz
Dead Band adjusting this function will reduce the tuning
linearity of input signal.
Digital Input
When the pulse width of digital signal is lower
F_108 Response 5~16 1ms 10 92
than setting time, the signal disabled.
Time
function can be set during the operation.
53 4
Chapter 4 Parameter List
Range
Func. Name Description of Unit Defc4 Page
Setting
Communication
0: RJ-45
F_109 Interface 0,1 ─ 1 108
1: DX+ / DX-
Selection
The followers use the address to send and
Communication
F_110 receive messages from the host (0: 0~254 ─ 0 108
Address
disable)
Communication 0: 4800bps 1: 9600bps
F_111 0~3 ─ 1 108
Baud Rate 2: 19200bps 3: 38400bps
Communication 0: 8,N,2 1: 8,E,1
F_112 0~3 ─ 1 108
Protocol 2: 8,O,1 3: 8,N,1
When the message transmission during
communication transmission is interrupted,
Communication 0.0~ 0.1
F_113 has no data transmitting, or delays, drive 0.0 108
Overtime (Cot) 100.0 sec
displays “Cot” message.
(0.0: Communication overtime disable)
Communication 0: Warning (Cot);Continue operation
F_114 Overtime 1: Warning (Cot);Ramp to stop 0~2 ─ 0 108
Disposal 2: Warning (Cot);Coast to stop
Control 0: Multi-function input terminals (X1~X4)
Selection of selves
F_115 0,1 ─ 0 108
Multi-Func- tion 1: Multi-function input terminals (X1~X4)
Input Terminals command by communication interface
0: Auto-restart after error trip(OC,OE,GF
only)
1: Auto reset
2: Auto reset without executing error
Fault Reset
F_116 detection 0~2 ─ 0 105
Selection
(If the drive is operating over 24hrs
without any error trip, the drive will
automatically reset the counting
number)
Error Tripping
Set the error tripping time interval before
Time Interval
F_117 drive auto restarts for F_116 when the 1~200 10sec 6 105
before
drive trips to stop.
Auto-Restart
0: Clear the UP/DOWN frequency
UP/DOWN
command when power failure.
F_118 Memory 0, 1 ─ 0 91
1: Save the UP/DOWN frequency
Selection
command at F_121 when power failure.
UP/DOWN 0:0.01Hz 1~8 :× 0.05Hz
F_119 Frequency 0~250 ─ 0 91
9:0.5Hz 10~250:× 0.1Hz
Resolution
1~5: Cntinuous accel./decel. when the
UP/DOWN terminal is activated with the duration (1 ~
F_120 1~6 ─ 1 91
Trigger Mode 5 sec).
6: Edge trigger.
function can be set during the operation.
4 54
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
UP/DOWN
Adjust UP/DOWN frequency by KP-207 0.00~ 0.01
F_121 Frequency 0.00 91
keypad. 400.00 Hz
Adjustment
0: Frequency command by analog signal
via terminal.
Secondary
1: Frequency command by keypad.
Frequency
F_122 2: Frequency command by UP/DOWN 0~3 ─ 0 91
Command
terminal.
Selection
3: Frequency command by communication
interface.
0:Vin+Iin
Analog 1:Vin-Iin
F_123 Input 2:Iin-Vin 0~3 ─ 0 78
Selection 3:Vin or Iin (switch by multi-function input
terminal X1 ~ X4).
0: Analog input gain.
1: Frequency command.
Analog Input
2: Current limit level.
F_124 Selection 0~4 ─ 1 78
3: Output voltage adjustment of V/F
(Vin)
pattern.
4: Feedback signal
0: Analog input gain.
1: Frequency command.
Analog Input
2: Current limit level.
F_125 Selection 0~4 ─ 4 78
3: Output voltage adjustment of V/F
(Iin)
pattern.
4. Feedback signal.
Iin Range 0: 4~20mA (2~10V).
F_126 0,1 ─ 0 78
Selection 1: 0~20mA (0~10V).
Analog Input
F_127 Gain The gain ratio of analog input terminal Iin. 0.00~2.00 0.01 1.00 76
(Iin)
Analog Input
-1.00~
F_128 Bias The bias ratio of analog input terminal Iin. 0.01 0.00 77
1.00
(Iin)
0: Output frequency.
Analog Output
1: Frequency command.
Signal
F_129 2: Output current. 0~4 ─ 2 82
Selection
3: Vin frequency command.
(AM+)
4: Iin frequency command.
Analog Output
F_130 Gain AM+ analog output adjustment ratio. 0.00~2.00 0.01 1.00 83
(AM+)
Multi-function
The way of settings are same as
Output -16~16
F_131 multi-function output terminals setting. ─ 1 93
Terminal (Note 8)
(F_058 ~ F_060)
(Ta2/Tc2)
DC Braking
Active frequency level of DC braking at
F_132 Frequency 0.1~60.0 0.1Hz 0.5 100
stop.
at Stop
200% Current 0: Disable
F_135 0,1 ─ 1 105
limit 1: Enable
function can be set during the operation.
55 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
PID Error
F_136 When the PID command 0.1~8.0 ─ 1.0 109
Gain
When the “stop command” is activation at
Delay Time
F_137 multi-funtion input terminal, drive will delay 0~1200 1sec 0 89
before Stop
the setting time before stop.
Overheating
F_138 Level Overheating level(OH)=setting level+85℃ 0.0~25.0 0.1℃ 0.0 117
Adjustment
Record the last status of drive before power
Operation
off.
F_139 Condition 0,1 ─ 1 102
0: Enable (F_001=2,3,4)
Memory
1: Disable
NTC
0: Disable.
F_140 Thermistor 0,1 ─ 1 116
1: Enable.
Setting
0: Disable
Drive
1: Warning (Ht): Continue operation.
Overheating
F_141 2: Warning (Ht): Drive de-rates the switching 0~3 ─ 0 116
Warning
frequency automatically per 5 minutes.
Selection
3: Warning (Ht): Stop operation.
Drive
Overheating Set the warning level to prevent drive
F_142 45~85 1℃ 70 116
Warning overheating.
Level
Drive
Set the temperature dead band of F_142 and
F_143 Overheating 2.0~10.0 0.1℃ 3.0 116
F_145.
Dead Band
0: Forced air: Start the fan at power ON.
Fan Control 1: Operation air: Start the fan at running.
F_144 0~2 ─ 1 117
Selection 2: Temperature level setting: Start the fan
according to the setting of F_145.
Temperature
F_145 Level of Fan Set the temperature level of fan activation. 25~60 1℃ 50 117
Activation
Minimum Set the minimum operation time of fan when
Operation 0.1~25.0 0.1 0.5
F_146 min 117
Time of Fan the fan stops.
F_152~
F_147 “SV” Value Set the “SV” value 0.1 2.0 109
F_151
0: PV value
1: Integration value
PID Control
F_148 2: Deviation value 0~4 ─ 0 109
Display
3: PID command value
4: PID feedback value
Main display selection(under PID control and
“SV-PV”
command by “SV” condition)
F_149 Value 0,1 ─ 1 109
0: “PV” value
Display
1: “SV-PV” value
0: By F_002
PID Control 1: Analong frequency command controls “SV”
F_150 0~3 ─ 2 109
Command 2: Keypad conrols “SV”
3: Communication interface controls “SV”
function can be set during the operation.
4 56
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Upper Limit
Set the value in accordance with the -800.0~
F_151 of 0.1 10.0 113
maximum specification of transmitter. 800.0
Transmitter
Lower Limit
Set the value in accordance with the -800.0~
F_152 of 0.1 0.0 113
minimum specification of transmitter. 800.0
Transmitter
0: Open-loop operation
PID Control 1: Forward control; D postposition
F_153 Mode 2: Forward control; D preposition 0~4 ─ 0 109
Selection 3: Reverse control; D postposition
4: Reverse control; D preposition
0: P postposition
F_154 P Selection 0,1 ─ 1 111
1: P preposition
Proportional Set the gain value for deviation adjustment.
F_155 0.0~25.0 0.1 2.0 111
Gain(P) (0.0: P control disabled)
Integration Set the integration time for deviation 0.1
F_156 0.0~100.0 1.0 111
Time(I) adjustment. (0.0: I control disabled) sec
Derivative Set the derivative time for deviation 0.01
F_157 0.00~2.50 0.00 111
Time(D) adjustment. (0.00: D control disabled) sec
Derivative
0.01
F_158 Time of Set the derivative time for feedback signal. 0.00~2.50 0.00 111
sec
Feedback
Integration
F_159 Upper Set the upper limitation value of integrator. 0.00~1.00 0.01 1.00 111
Limitation
Integration
-1.00~
F_160 Lower Set the lower limitation value of integrator. 0.01 0.40 111
1.00
Limitation
Integrator
Set the initial value of thr integrator before -1.00~
F_161 Initialized 0.01 0.00 111
PID starts. 1.00
Value
PID Buffer
F_162 Set the buffer space of PID output value. 0~255 ─ 2 111
Space
Feedback
F_163 Filter the feedback signal. 0~255 ─ 10 113
Signal Filter
Feedback
0: Disable
F_164 Signal Trip 0,1 ─ 1 113
1: Enable (at F_126=0)
Detection
Feedback 0: Direct proportion signal.
F_165 Signal 0,1 ─ 0 113
Selection r 1: Inverse proportion signal.
nd nd
(2 PI Drive command by 2 PI control when the
Control) deviation value is within the setting
F_166 Active 0.0~25.0 0.1 2.0 112
range(F_147-“PV” value)
Range 0.0: Disable
Drive command by 2nd control with the time
(2nd PI duration and then switching back the primary
F_167 Control) 0.0~300.0 0.1 15.0 112
Active Time PI control.
0.0: Disable
Proportional Set the gain value for deviation adjustment.
F_168 0.0~25.0 0.1 2.0 112
Gain(P2) (0.0: P control disabled)
Integration Set the integration time for deviation 0.1
F_169 0.0~25.0 1.0 112
Time(I2) adjustment. (0.0: I control disabled) sec
function can be set during the operation.
57 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
Main display selection when the drive
Display
command by PID and executing open-loop
Setting by
F_170 command. 0,1 ─ 0 111
Open-Loop
0: PV display
Command
1: According to the setting value of F_006
Primary speed selection when the drive
command by PID and executing open-loop
Setting
command.
Selection by
F_171 0: Analog input terminals 0~3 ─ 1 111
Open-Loop
1: Keypad
Command
2: UP/DOWN command
3: Communication interface
Command can be adjusted by keypad when
Keypad
the drive command by PID and executing
Selection by
F_172 open-loop command. 0,1 ─ 1 112
Open-Loop
0: Primary speed
Command
1: “SV” value
F_173 Reserved
(On-Off)
0: Forward control
F_174 Control 0,1 ─ 0 115
1: Reverse control
Selection
(On-Off)
0: Disable
F_175 Delay Time 0,1 ─ 0 114
1: Enable
Conrol
(On)
Drive is activation when the “PV” value -12.8~
F_176 Range 0.1 1.0 115
exceeds the “On” range. 12.7
Setting
(Off)
Drive is activation when the “PV” value
F_177 Range 0.0~10.0 0.1 1.0 115
exceeds the “Off” range.
Setting
Drive is activation when the “PV” value
(On)
F_178 exceeds the “On” range and maintaining a 0~250 1sec 0 115
Delay Time
duration(F_178)
Drive is activation when the “PV” value
(Off)
F_179 exceeds the “Off” range and maintaining a 0~250 1sec 0 115
Delay Time
duration(F_179)
(On-Off)
Accel/Decel 0: Primary accel./decel. time
F_180 0,1 ─ 1 116
Time 1: Secondary accel./decel. time
Selection
(Off)
F_181 Holding Hold the “Off” condition with the duration. 0~240 1sec 0 116
Time
Air Condi- 0: Disable
F_182 0,1 ─ 0 117
tioning Mode 1: Enable
(Air Condi-
tioning The respone time of “PV” value is according
Mode) to the setting value of F_183. 0.1
F_183 0.0~25.0 5.0 117
Temperature PV > (SV+F186) , Variation of acceleration: sec
Response (Hz/sec) = (F_184/ F183)
Time
function can be set during the operation.
4 58
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
(Air Condi- Change the frequency according to the
tioning setting value of F_183
F_184 Mode) 0.1~25.0 0.1Hz 2.0 117
PV > (SV+F187),Variation of deceleration:
Variation
Frequency (Hz/sec) = (F_184/ F183)*4.
(Air Condi-
tioning
Mode) Upper limit value = “SV” value + F_185 F_184~
Upper Limit Lower limit value = “SV” value + F_186
F_185 0.1 3.0 117
20.0
Range of When the temperature is over uppr limit
Temperature value, drive outputs the setting value of
(Air Condi- F_042(Frequency Upper Limit)
tioning When the temperature is under lower limit
Mode) value, drive outputs the setting value of
F_186 0~F_184 0.1 1.0 117
Lower Limit F_043(Frequency Lower Limit)
Range of
Temperature
(Air Condi-
tioning
Mode)
F_187 0.00~1.00 0.01 0.50
Holding
Frequency
Level
When the operation frequency of drive is
(Air Condi-
under (F_031*F_187) and maintaining F_188
tioning
duration, drive outpus full speed by oper-loop
Mode)
condition and maintaining a duration(F_189) 118
F_188 Detection 0.0~25.0 0.1hr 0.0
and then recovering PID control.
Time of
Holding
*F_188=0 Disable
Frequency
(Air Condi-
tioning
0.1
F_189 Mode) 0.0~25.0 1.0
min
Full Speed
Time
0: Disable
(Feedback 1: Warning detection;Continue operation
F_190 Limit) 0~3 ─ 0 113
Detection 2: Warning detection;Stop output
3: Error detection;Error trip
(Feedback Set the physical volume according to the -800.0~
F_191 Limit) specification of transmitter(refer to F_151, 0.1 8.0 114
Level 800.0
F_152)
(Feedback
Limit) 0: Detection when “PV” > F_191
F_192 Detection 1: Detection when “PV” < F_191 0,1 ─ 0 114
Setting
(Feedback When the feedback signal exceeds the
Limit) setting value of F_191 and maintaining a 1
F_193 Detection duration, drive is detection. Drive will close 0~2550 300 114
sec
Time
(Feedback the detection when the feedback signal is
Limit) without the range of feedback limit.
F_194 Range (Set the range according to the physical 0~20.0 0.1 unit 1.0 114
Setting volume of transmitter)
function can be set during the operation.
59 4
Chapter 4 Parameter List
Range of
Func. Name Description Unit Defc4 Page
Setting
(Feedback
Limit) 0: Enable during operation
F_195 0,1 ─ 1 114
Condition 1: Enable full time
Selection
F_204
~ Reserved
F_209
0: Disable
CLF: Clear error records
dEF60: Restore the default value of drive for
60Hz.
dEF50: Restore the default value of drive for
50Hz.
SAv: Save the setting value.
rES: Restore the setting value.
Default
F_210 rd_EE: Read the parameters from drive to ─ ─ 0 68
Setting
digital keypad
Wr_EE: Write the parameters from digital
keypad to drive
dEFC3: Restore the default value of air
compressor for 50Hz
dEFC4: Restore the default value of air
compressor for 60Hz
dEFC1~dEFC6: Customize default value
function can be set during the operation.
Note:
1. 1. The default value of 50 Hz.
2. 2. The default value of 60 Hz.
3. 3. Specification of 200V.
4. 4. Specification of 400V.
5. 5. 0.5 ~ 5HP: 5 sec
7.5~30HP: 15sec
40HP above: 30 sec
6. 6. Displayed “OLO”
7. 7. Setting value=0, represented for “ no display”
8. 8. + : Represents a contact (N.O)
─ : Represents b contact (N.C)
Up/Down control wiring must not exceed over 20m when multi-function terminals are used for
Up/Down control.
9. When RM6(9916) setting value of switching frequency(F_81)exceeds “4”, the drive must be
de-rating or change higher capacity.
10. Function : F_056、F_057、F_133、F_134、F_173、F_204~F_209 = Reserved
11. “dEF” the default value refer to < Appendix2 Default Value List>
dEF60:60Hz: general type
dEF50:50Hz: general type
dEFC3:50Hz: air compressor
dEFC4:60Hz: air compressor
4 60
Chapter 4 Parameter List
61 4
Chapter 5 Parameter Setting Description
COM
5
62
Chapter 5 Parameter Setting Description
b. F_001=1
COM
c. F_001=2
COM
5
63
Chapter 5 Parameter Setting Description
d. F_001=3
e. F_001=4
f. F_001=8
Start command and rotate direction by the RS-485 communication interface.
Related control command refer to “6-6 Drive Registors and Command Code”.
g. F_001=9
Start command by RS-485 communication interface.
Rotation direction command by REV terminal.
Related control command refer to “6-6Drive Registors and Command Code”
h. F_001=10
Start command by FWD terminal.
Rotation direction command by RS-485 communication interface.
Related control command refer to “6-6 Drive Registors and Command Code”
i. F_001=11
Start command by Keypad
Rotation direction command by RS-485 communication interface.
Related control command refer to “6-6Drive Registors and Command Code”
5
64
Chapter 5 Parameter Setting Description
Note:
1.When F_001 set to 0 or 2 and FWD-COM and REV-COM are simultaneously open-circuit,
the monitor mode will display blanking “ “ (except “Display 8-terminal
status”). If FWD-COM and REV-COM are simultaneously short-circuit, the monitor mode
will display blanking “ ” (except “Display 8-terminal status”).
FWD FWD
DRIVE REV DRIVE REV
COM COM
Figure A Figure B
EX: F_001=0,
Forward (FWD) rotation is clockwise (Figure A).
Reverse (REV) rotation is counter-clockwise (Figure B).
5
65
Chapter 5 Parameter Setting Description
a. F_002=0
Frequency command by “Vin” or “Iin” analog input terminal (select Vin or Iin
analog input sources by F_123).
(II). Iin-GND: Select the input signal mode via “SW1” switch.
SW1I position (current signal); Range: 4~20mA or 0~20mA (set by F_126).
SW1V position (voltage signal); Range: 2~10V or 0~10V (set by F_126).
※ The gain or bias of frequency command can be set by function F_127 and F_128.
b. F_002=1
Frequency command by keypad.
The primary speed, jog speed and preset speeds (F_009 ~ F_017) can be set during
operation and the frequency command can be set under monitor mode.
c. F_002=2
Motor speed (RPM) command by keypad (KP-207).
d. F_002=3
Machine speed (MPM) command by keypad (KP-207).
e. F_002=4
Frequency command by UP/DOWN terminal.
Multi-function input terminals can be set UP command, DOWN command, UP/DOWN
frequency clear and enter commands.
f. F_002=5
Frequency command by RS-485 communication interface.
Related control command refer to 6-6 “ Drive Registors and Command Code”
Note: In monitor mode, when F_002 sets 1, 2 or 3, pressing ▲ or ▼ key one time and
the frequency command will be blink but not changing. Press the ▲ or ▼ key again to
change the frequency command.
5
66
Chapter 5 Parameter Setting Description
a. F_003=0
STOP
b. F_003=1
STOP
2.Normal stop:
ON
F_001=2 or 3, the start command by “ ” key of keypad KP-201C and the stop is
STOP
controlled by “ ” key.
RESET
a. F_004=0
In the monitor mode, the frequency command cannot be changed by KP-201C keypad
to avoid possible mistakes and errors.
b. F_004=1
In the monitor mode, the frequency command can be changed by KP-201C keypad.
5
67
Chapter 5 Parameter Setting Description
In the monitor mode, there are 8 monitor modes can be selected. The corresponding
value and monitor modes are shown as below table:
1. Output Frequency 5. Output Current
2. Frequency Command 6. Motor Speed (RPM)
3. Output Voltage 7. Machine speed (MPM)
4. DC bus Voltage 8. Terminals Status
Note: One of above 8 monitor modes can be selected as the “main display”, and others
can be as the “auxiliary display”. When the display is under “auxiliary display”
mode (including the setting mode and other monitor modes), the display will
switch to “main display” automatically after 3 minutes by idling the keypad.
Set the displaying ratio for “display 7-machine speed” under monitor mode.
Machine speed = machine speed ratio (F_007) x output frequency
Set the digits of decimal values for machine speed to provide the better resolution for
observing. (the max. accuracy is the thousandth digit)
Drive can restore the default setting values and restoring the parameter setting values.
The parameter of F_210 are described as below table:
(0): Disable
(CLF): Clear error records
(dEF60): Restore the default value of drive for 60Hz.
(dEF50): Restore the default value of drive for 50Hz.
(SAv): Save the setting value.
(rES): Restore the setting value.
(rd_EE): Read the parameters from drive to digital keypad
(Wr_EE): Write the parameters from digital keypad to drive
(dEFC3):Restore the default value of air compressor for 50Hz.
(dEFC4)﹕Restore the default value of air compressor for 60Hz.
dEFC1~dEFC6:Dedicated machine default.
Note: and are used to copy functions to several drives with the
same setting value.
5
68
Chapter 5 Parameter Setting Description
a. Related functions:
(I) The setting of acceleration and deceleration time (F_018 ~ F_029).
(II) The setting of multi-function input terminals (F_052 ~ F_055).
5
69
Chapter 5 Parameter Setting Description
※ The ON/OFF conditions as below table are “contact a (N.O)” setting of functions.
Jog speed Multi-speed Multi-speed Multi-speed Multi-speed
Command
command level 4 level 3 level 2 level 1
Description
command command command command
ON ON X X X Jog speed
OFF OFF OFF OFF OFF Primary speed
OFF OFF OFF OFF ON Preset speed 1
OFF OFF OFF ON OFF Preset speed 2
OFF OFF OFF ON ON Preset speed 3
OFF OFF ON OFF OFF Preset speed 4
OFF OFF ON OFF ON Preset speed 5
OFF OFF ON ON OFF Preset speed 6
OFF OFF ON ON ON Preset speed 7
OFF ON OFF OFF OFF Preset speed 8
OFF ON OFF OFF ON Preset speed 9
OFF ON OFF ON OFF Preset speed 10
OFF ON OFF ON ON Preset speed 11
OFF ON ON OFF OFF Preset speed 12
OFF ON ON OFF ON Preset speed 13
OFF ON ON ON OFF Preset speed 14
OFF ON ON ON ON Preset speed 15
Note:
1. “ X “ : Don’t care
2. Jog speed has the highest priority. That is, when the jog speed is activated, other
speed commands disabled.
3. Jog speed command and the multi-speed commands are programmed by the
multi-function input terminals (X1 ~ X4) by functions (F_052 ~ F055). ON / OFF the
terminal in accordance with above table to switch the speed.
4. “ ON “ :
The terminal is short-circuit at contact a (N.O) setting.
The terminal is open-circuit at contact b (N.C) setting.
“ OFF ” :
The terminal is open-circuit at contact a (N.O) setting
The terminal is short-circuit at contact b (N.C) setting.
5
70
Chapter 5 Parameter Setting Description
Primary accel
Frequency time
Primary decel
time
Primary accel
time Preset Primary decel
Primary accel speed 8 time
time Preset
Primary accel Preset Primary decel
time speed 7 speed 9 time
Primary accel Preset Preset Primary decel
time speed 6 speed 10 time
Preset Primary decel
speed 5 Preset
Decel time of Acceltime of speed 11 time
preset speed 2 preset speed 3 Preset Preset Primary decel
speed 4 speed 12
Acceltime of time
Preset Preset
preset speed 1 speed 3 Primary decel
speed 13 time
Primary accel Preset
time speed 14
Preset Jog speed
Preset
speed 1 speed 15
Primary
speed
Preset
speed 2
Time
Multi-speed level 1
Multi-speed level 2
Multi-speed level 3
Multi-speed level 4
Jog Speed
※ The acceleration / deceleration time of jog speed and preset speed 4~15 are according to the
setting of primary acceleration / deceleration time (F_019, F_020).
※ Jog speed control include start command. When drive stop, activating the jog speed command
can start the drive without start command.
※ Analog input terminals (Vin, Iin) are disabilities under jog speed, preset speed 1~15 and
primary speed control.
5
71
Chapter 5 Parameter Setting Description
a. The multi-speeds acceleration / deceleration time is the time interval from 0Hz to the
setting of F_018 (Reference Frequency of Accel/Decel Time). Multi-speed level
commands can simultaneously control preset speeds and the preset speed
acceleration / deceleration time.
b. The acceleration / deceleration time of primary speed, preset speed 4 ~ 15 and jog
speed are controlled by the setting of primary acceleration / deceleration time.
c. The switch between primary accel / decel and secondary accel / decel can be
selected by multi-function input terminals.
Illustration is as follows:
Output Secondary Accel/Decel Time
Frequency Switching and Prohibited Command
Curve
Secondary
deceleration time
Max. output frequency
(F_031)
Primary
Secondary
deceleration time
acceleration time
Primary
acceleration time
Time
Holding command
(Multi-function input terminal)
5
72
Chapter 5 Parameter Setting Description
※STOP command:
(I) When F_001 set 0 or 2, “FWD” and “REV” terminals are simultaneously
short-circuit or open-circuit.
(II) When F_001 set 1, “FWD” terminal is open-circuit.
OFF
(III) When F_003 set 1, pressing the “ RESET ” key.
OFF
(IV) Press the “ RESET ” key when start command by keypad.
e. Set the S-curve function depend on the application to buffer the impact during start,
stop, acceleration and deceleration.
EX: To buffer the impact when the object fall on the conveyor line or the running of
elevator.
Output
frequency
Frequency
command
S-curve time S-curve time
5
73
Chapter 5 Parameter Setting Description
5
74
Chapter 5 Parameter Setting Description
F_031 ~ F_039 are the functions related to V/F pattern. Please refer to below figure:
V/F Pattern
Output
Voltage
Base
voltage
(F_035)
V/F voltage 1
(F_037)
V/F voltage 2
(F_039)
Boost voltage
Output
(F_033)
V/F freq. 1 Base freq. Frequency
(F_036) (F_034)
Starting freq. V/F freq. 2 Max. output freq.
(F_032) (F_038) (F_031)
(II) When the setting value of V/F frequency 2 is less than the setting value of V/F
frequency1, the setting of V/F frequency (voltage) 2 is disable.
(III) When V/F frequency1 or V/F frequency 2 is less than the starting frequency, the V/F
frequency (voltage) 1 or 2 is disable.
(IV) No limitation between F_033 (Starting Voltage), F_035 (Base Voltage), F_037 (V/F
Voltage 1), F_039 (V/F Voltage 2) when setting the values.
5
75
Chapter 5 Parameter Setting Description
a. (General Mode)
The corresponding frequency command value of analog command =
Maximum output frequency (F_031) x Analog input gain (F_040 or F_127)
EX: If analog input bias (F_041 or F_128) = 0.00
60.0Hz 60.0Hz
Gain=1
Gain=1.2
48.0Hz
Gain=1
Gain=0.8
Analog Analog
0Hz 0Hz
Command Command
0V(4mA) 8.3V(17.3mA) 10V(20mA) 0V(4mA) 10V(20mA)
10bar 10bar
Gain=1
Gain=1.2
8bar
Gain=1
Gain=0.8
Analog Analog
0bar 0bar
signal signal
0V(4mA) 8.3V(17.3mA) 10V(20mA) 0V(4mA) 10V(20mA)
5
76
Chapter 5 Parameter Setting Description
a. ( General Mode)
The corresponding frequency command value of analog command =
maximum output freq. (F_031) x analog input bias (F_041 or F_128)
60.0Hz 60.0Hz
Bias=0.05 Bias=1
Frequency
command
0Hz Analog
0V(4mA)
command
10V(20mA)
5
77
Chapter 5 Parameter Setting Description
The interrelationships of F_123, F_124 and F_125 are shown as below figure:
F_123 = 0, 1, 2
Vin Freq. command Freq. command
F_124 & F_125 or or
simultaneously setting Current Limit +/- Current Limit
1 or 2 or 3 or or
Iin Output voltage of V/F Output voltage of V/F
F_123 = 3
(switch by multi-function input
terminal X1 ~ X6)
Vin Freq. command Freq. command
F_124 & F_125 or or
simultaneously setting Current Limit Current Limit
1 or 2 or 3 or or
Iin Output voltage of V/F Output voltage of V/F
Freq. command or
Vin Current Limit or Freq. command
Output voltage of V/F F_123 (don’t care) or
F_124 & F_125 Current Limit
either one setting 0 or
Iin Analog input gain Output voltage of V/F
5
78
Chapter 5 Parameter Setting Description
5
79
Chapter 5 Parameter Setting Description
a. Filter the analog input signal when the frequency command by analog input terminals.
(F_002=0).
b. The larger setting value will cause the slower response.
c. 0: Disable the filtering.
5
80
Chapter 5 Parameter Setting Description
Output
frequency
60.0Hz
54.0Hz
Max. output freq.=60.0Hz
Freq. upper limit=0.90
Freq. lower limit=0.10
6.0Hz
54.0Hz Frequency
6.0Hz 60.0Hz command
Upper limit of output frequency = F_042 (Frequency Upper Limit) x F_031 (Maximum Output
Frequency)
Lower limit of output frequency = F_043 (Frequency Lower Limit) x F_031 (Maximum Output
Frequency)
5
81
Chapter 5 Parameter Setting Description
0: Output frequency
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the output
frequency. (the terminal will output signal when drive operation)
1: Frequency command
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the
frequency command. (the terminal will output when drive is operation or stop)
2: Output current
The analong output terminal(FM+ or AM+) outputs DC 0~10V to correspond the output
current. (max. corresponding value is rated output current of drive)
5
82
Chapter 5 Parameter Setting Description
10V 10V
8V
Output freq.
or
Freq. command Output current
0V 50.0Hz 0V 17A
0.0Hz 60.0Hz 21.25A
10V
8V
5
83
Chapter 5 Parameter Setting Description
5
84
Chapter 5 Parameter Setting Description
Interruption of
output command
(X3)
Start command
Output voltage
0.3 sec
Output frequency
5
85
Chapter 5 Parameter Setting Description
Coast to stop
command (X3)
Start command
Output voltage
Output frequency
Acceleration time
Terminal start
command (FWD)
Speed tracing
command (X1) > 0.1sec
Decel. time is 2 sec
Max. output frequency
Normal accel. time
Output frequency
Delay Time
before Speed
Output voltage Tracing(F_089) Return to normal V/F
5
86
Chapter 5 Parameter Setting Description
Terminal start
command (FWD)
Speed tracing
command (X1) > 0.1sec
Decel. time is 2 sec
Setting frequency
Normal accel. time
Output frequency
Delay Time
before Speed
Output voltage Tracing(F_089) Return to normal V/F
UP X4 UP X4
DOWN X5 DOWN X5
CLEAR X6 CLEAR X6
+ -
COM COM
DC 24V
5
87
Chapter 5 Parameter Setting Description
Start command
UP command
DOWN command
Freq. command
Frequency upper
limit
Frequency lower
limit
D1 H U H D H U H D H U U1 H D D1 H
Output freq. U2 U1 D2 D1 U2 D2
Constant speed
detection
5
88
Chapter 5 Parameter Setting Description
FWD
FWD RUN FWD
RUN/STOP
REV
REV REV/FWD REV
RUN/STOP
STOP X5 STOP X6
COM COM
FWD
FWD RUN FWD
RUN/STOP
REV
REV REV/FWD REV
RUN/STOP
STOP X5 STOP X6
+ - + -
COM COM
DC 24V DC 24V
d. When the parameter of F_052, F_053, F_054, F_055 is set to “0”, the functions
are described as below:
i. F_052: “UP/DOWN frequency command enter key” by X1.
X1 and COM is open-circuit:
UP/DOWN command can adjust the frequency command, but the output frequency
will not be reacted by the frequency command.
X1 and COM is short-circuit:
The output frequency will start acceleration or deceleration until reaching the
frequency command.
5
89
Chapter 5 Parameter Setting Description
DC braking
enable
Output freq.
DC Starting DC braking DC
braking frequency frequency at braking
active F_032 stop F_132 active
Time
5
90
Chapter 5 Parameter Setting Description
5
91
Chapter 5 Parameter Setting Description
If F_120 = 2
Max. output
freq.
UP/DOWN
freq. resolution Acceleration
(F_119) slope is
4 Hz/sec
0Hz Time
UP command
> 2 sec
< 2 sec
DOWN command
6: Edge trigger.
UP/DOWN signal triggers the drive during the transition of the signal(01 or 10).
The signal response time is 30ms.
a. Setting the input response time of multi-function terminals (X1~X4, FWD and REV)
(digital debouncing).
b. If the signal width of digital inputs is smaller than the digital input response time, the
program of drive will reject the input signal and do no process to input signal
5
92
Chapter 5 Parameter Setting Description
b. Ta1, Ta2 (N.O) and Tb1 (N.C) are relay output terminals.
The maximum output specification is AC 250V / 0.5A, cosθ=0.3.
d. Y1, Y2, Ta1, Ta2, and Tb1 can be set as below functions:
Time
Multi-function
output terminal
(Y1)
5
93
Chapter 5 Parameter Setting Description
Freq. detection
Output frequency range (F_062)
Freq.
command
Freq. detection
range (F_062)
Freq. detection
level (F_063)
Time
Multi-function
output terminal
(Y1)
System overload
detection level
(F_068)
Time
System overload
detection time (F_069)
Multi-function
output terminal
(Ta1 or Ta2)
Multi-function
output terminal
(Tb1)
5
94
Chapter 5 Parameter Setting Description
Output
frequency
Time
Output
current
Time
Multi-function
output terminal
(Y1)
DC bus voltage
Multi-function
output terminal
(Y1)
5
95
Chapter 5 Parameter Setting Description
Power source
Normal V/F
Output current
Multi-function output
terminal
(Y1)
5
96
Chapter 5 Parameter Setting Description
Error condition
Output frequency
Normal V/F
Output current
Multi-function output
terminal
(Y1)
Output
terminal (Y2)
5
97
Chapter 5 Parameter Setting Description
System overload
detection level
(F_068)
Time interval<System
overload detection
time(F_069)
Time
Multi-function
output terminal
(Y1)
(F_058=5)
Time interval>System overload
detection time(F_069)
The systeom overload detection is activated when the output current exceeds the value
of F_068 (System Overload Detection Level) with the time interval of F_069 (System
Overload Detection Time) and the keypad will displayed
Detection during operation includes acceleration, deceleration or constant speed.
The purpose of overload detection is to prevent the system damage. The detection level
and time can be set by user requirements.
5
98
Chapter 5 Parameter Setting Description
0: Disable
F_074 Stall Prevention Setting at Deceleration
1: Enable
Time Time
Output Output
current current
Time Time
When enabling the F_074 (Stall Prevention Setting at Deceleration) and the stall occurs
at deceleration, drive will operation at constant speed.
According to the actual requirement to disable the F_074 (Stall Prevention Setting at
Deceleration), when connecting a dynamic brake unit.
If the DC bus voltage of drive is higher than the dynamic brake voltage level during stop,
the KP-201C keypad will display “ “ and the drive cannot be start by pressing
RUN
key. If the DC bus voltage is less than the dynamic brake voltage level, the drive will
automatically recover to normal and displaying the main display.
5
99
Chapter 5 Parameter Setting Description
N. DC Braking Setup
The current level setting of DC
F_075 DC Braking Level
braking.
DC Braking
Output
frequency
DC braking
frequency at
stop (F_132)
Time
Time of DC Time of DC
braking before braking after
start (F_077) stop (F_076)
Start
command
Time
If the frequency command is set below F_032 (Starting Frequency) during operation and
the output frequency is below the starting frequency, the DC braking will be activated.
The setting value of F_132 is disable at the moment.
5
100
Chapter 5 Parameter Setting Description
Output
frequency
Re-acceleration
Power recovery during
ramp to stop process at
power failure
Time
5
101
Chapter 5 Parameter Setting Description
Subtracted frequency of
deceleration at power failure
(F_103)
Deceleration time 1
Turning of ramp to stop by
frequency of power failure
ramp to stop (F_104)
(F_106)
Time
Deceleration Time 2
of ramp to stop by
power failure (F_105)
0: Enable(F_001=2,3,4)
F_139 Operation Condition Memory
1: Disable
The ramp to stop at power failure function is suitable for the inertia load.
CAUTION
At the function F_078=1 or 3, the drive will automatically restart when the power is
restored. Stay away from the motor and machine.
5
102
Chapter 5 Parameter Setting Description
P. Jump Frequency
F_084 Jump Frequency 1
F_085 Jump Frequency 2 Setting Range:0~400Hz
F_086 Jump Frequency 3
F_087 Jump Frequency Range Setting Range:0~25.5Hz
In order to avoid the mechanical resonance, these parameters allow resonant frequency
to be jumped.
There are three jump frequencies and one jump frequency interval.
Output
frequency
F_087(Jump
Frequency.
Range) x 2
F_087(Jump
Frequency.
Range) x 2
F_086(Jump
Frequency 3)
F_087(Jump
F_085(Jump
Frequency.
Range) x 2
Frequency 2)
F_084(Jump
Frequency 1)
Frequency
command
Q. Speed Tracing
F_088 The Current Level of Speed Tracing 0~200% Rate current
Time for speed tracing
F_089 Delay Time before Speed Tracing
before stop output 0.1~5 sec
F_090 The V/F Pattern of Speed Tracing 0~100%V/F voltage
The main application of speed tracing function is used for the speed tracing for the
restart after instantaneous power failure, fault restart or the speed tracing command by
the multi-function input terminal.
Refer to speed tracing for multi-function input terminals.
5
103
Chapter 5 Parameter Setting Description
Holding
frequency
(F_096)
Time
Holding time
interval (F_097)
S. External Indicators
F_099 External Indicator 1
F_100 External Indicator 2
F_101 External Indicator 3
a. F_099 ~ F_101 can be set according to the setting method of F_006.
b. Please select twisted-pair shield wiring and shielding connected to the GND terminal
of drive’s control board.
c. The wiring diagram of external indicators is shown as below:
Indicator 1 (DM-501) Indicator 2 (DM-501) Indicator 3 (DM-501)
7 6 5 4 3 2 1 7 6 5 4 3 2 1 7 6 5 4 3 2 1
RM5G/P control
board
GND
5
CN1
1
5
104
Chapter 5 Parameter Setting Description
Range:1~200,
F_117 Error Tripping Time Interval before Auto-Restart
1unit=10sec
0: Diable
If drive’s output current exceeds 220% rated current, the drive will display OC.
1: Enable
If drive’s current exceeds 200% rated current, the drive will control PWM output
voltage. (Limit current:200%)
V. Others Function
F_081 Switching Frequency
When the value of F_081 is set to “0”, the switching frequency of PWM voltage will be
800Hz and others switching frequency = F_081×2.5kHz.
The higher switching frequency has less noise. But using higher switching frequency
must consider the cable length between drive and motor and must be adjusted
according the connection distance between drive and motor. (Refer to the 2-3-6)
※Upper limit of switching frequency
RM6-(9916): 0.5HP~75HP 16kHz
Above 100HP 10kHz
※ Switching frequency will be modulated with load automatically.
5
105
Chapter 5 Parameter Setting Description
Switching
Load current Switching Load current
frequency
frequency
16k
100%
5%
12.5k
90%
10k
80%
7.5k
0: Ramp to stop
F_082 Stop Mode 1: Coast to stop
2: Coast to stop + DC braking
When the value of F_082 is set to “2”, the operation characteristic is shown as below
figure:
Output
voltage N
F_075 (DC
Braking Level)
DC voltage 1
Time Fout / F_031
0.1 1 ratio
Stop F_076 (Time
of DC Braking
after Stop) * N
*F_031 (Maximum Output Frequency)
When the output current of drive is abnormal at DC braking, appropriately increase the
setting value of F_089 (Delay Time before Speed Tracing).
Display the latest 5 records of errors. Pressing the ▲ or ▼ key can display other
error records. (1: the latest error)
5
106
Chapter 5 Parameter Setting Description
0: Disable
F_098 Grounding Fault Protection (GF)
1: Enable
If the leakage current exceeds 70% rated cureent of drive, the drive will trip to stop.
Output
voltage
100%
Linear
Linear
Energy saving
Energy-saving mode
Square of 2 curve
Square curve
Square of 1.7 curve
1.7th power curve
Square
th of 1.5 curve
1.5 power curve
70%
When the drive is used for fan or light-duty load applications, this function can be set to
achieve the energy-saving purpose.
5
107
Chapter 5 Parameter Setting Description
W. Communication Setting
Communication Interface 0:RJ-45
F_109
Selection 1:DX+ / DX-
Shielded wire
Shielded wire
HMI / PLC HMI / PLC
0: 4800bps 2: 19200bps
F_111 Communica-tion Baud Rate
1: 9600bps 3: 38400bps
0: 8,N,2 1: 8,E,1
F_112 Communication Protocol
2: 8,O,1 3: 8,N,1
F_113 Communication Overtime (Cot)
When the message transmission during communication transmission is interrupted, has
no data transmitting, or delays, drive displays “Cot” message.
5
108
Chapter 5 Parameter Setting Description
5
109
F_040,F_041
Vin
F_047 F_009
Primary
speed RPM MPM UP/DOWN Modbus
Run
111 PID_Fcmd 1,2,3,4
SV
Parameter Setting Description
PROG RUN
2
FUN STOP
F_153
+
DATA RESET
Modbus SV 3 1,2
PID PID_Fcmd
F_010~F_016 -
- 3,4
F_109 0 1 Preset speed
1~7 +
F_153 Error
1,3 2,4
110
DX+ F_158
DX- RJ-45 F_040,F_041 F_123 F_124
F_163 D
0 : Vin+Iin
1
F_161
Vin 1 : Vin-Iin
0
F_127,F_128
Bias Drive Stop
2 : Iin-Vin F_159,F_160
F_156
3 : Vin or Iin
Iin I
F_154 Open-loop
F_155 F_162
+
F_009
1
Main Speed
UP/DOWN 2
5
Communication 3
Chapter 5 Parameter Setting Description
5
111
Chapter 5 Parameter Setting Description
SV
F_166
F_168
PV
time
Main PI
(sec)
control
F_155
F_156
Second PI
control
F_168
F_169
5
112
Chapter 5 Parameter Setting Description
Y.Feedback Signal
When the transmitter connect Vin terminal, F_124 setting number is 4 and then the
transmitter connected Iin terminal ,F_125 setting number is 4.
If the gap between PV value and real value is still different, user can fine tuning the
F_151 and F_152.
5
113
Chapter 5 Parameter Setting Description
PV
F_192=0
F_191
F_194
SV
time
(sec)
Y1 F_193
F_058=13
PV
F_192=1
SV
F_194
time
(sec)
5
114
Chapter 5 Parameter Setting Description
PV PV
F_179
F_177
SV
F_176
F_178
time
Y1
(sec)
F_058=14
Y1
F_058=15
RUN RUN
Frequency STOP
command
Reverse: Start condition PV value > SV value. Stop condition is PV < SV value.
PV PV
F_178
F_176
SV
F_177
F_179
time
(sec)
Y1
F_058=1
4
Y1
F_058=15
RUN
5
115
Chapter 5 Parameter Setting Description
PV PV
F_179
F_177
SV
F_176
F_178
time
Y1 (sec)
F_058=15
RUN F_181
Frequency
OFF hold time
command STOP
5
116
Chapter 5 Parameter Setting Description
Temperature
Drive overheat
pre-alarm level
F4.14 Overheat dead
band F4.15
Time
NTC temperature
warning detection
5
117
Chapter 5 Parameter Setting Description
Output frequency
F_042
Upper
limit
F_043
Lower
limit
F_186 PV
F_185
SV
1.When the drive is operating under the level of holding speed (F_187), and the counter
may start moving. If output frequency is over holding speed, the counter will clean the
value as 0.
2.When the counter reach at holding speed (F_188), the drive may run at full speed and
after persisted for a moment (F_189) that the drive returns would be normal.
3.F_188 setting as 0, it stand for closing this function.
5
118
Chapter 6 Communication Description
8,E,1: 1 start bit,8 data bits,1 even parity bit,1 stop bit
EVEN
START BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7 STOP
PARITY
8,O,1: 1 start bit,8 data bits,1 odd parity bit,1 stop bit
ODD
START BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7 STOP
PARITY
6
119
Chapter 6 Communication Description
6
120
Chapter 6 Communication Description
●Operation Code(OP Code) Description:
※03H (Read multi-registers):
Example: Read data from registers 2101H and 2102H of the drive 1
Message Code (Host to Drive)
Register
OP Starting Register Numbers to CRC Checksum
Address
Code Readout
MSB LSB MSB LSB LSB MSB
02H 03H 21H 01H 00H 02H 9FH C4H
This example shows the host to read the drive data from 2 registers of the drive. The
host identifies drive 1 by calling the drive address (02H) with the “read” operation
command (03H) to read the drive data from the registers (2101H – starting register)
to the register (2102H – Register Numbers to Readout defines the numbers of
register for data readouts).
Return Code (Drive to Host)
2101H(Register) 2102H(Register)
OP Data CRC Checksum
Address Data Data
Code Bytes
MSB LSB MSB LSB LSB MSB
02H 03H 04H 55H 00H 17H 70H D6H EBH
The host reads registers 2101H and 2102H of drive (02H) (drive status and speed
command). After the drive receives the host’s command, the drive returns 4 bytes
data (2101H=5500H and 2102H=1770H) to the host.
Caution: The host cannot simultaneously broadcast 03H OP code to drives when
multiple drives connected or all drives reject host’s OP code.
6
121
Chapter 6 Communication Description
※08H (Drive detection): Only use when testing the communication
OP code – 08H is to detect if the drive is correctly receiving the data from the host.
The main purpose of using this OP code is to ensure the host data to be correctly
sent to the drive.
Example: Verify the data (0000H and AA55H) to be correctly received by the drive.
Message Code (Host to Drive)
OP Data 1 Data 2 CRC Checksum
Address
Code MSB LSB MSB LSB LSB MSB
02H 08H 00H 00H AAH 55H 5EH A7H
The host sends OP-code (08H) to verify the data 0000H and AA55H to be correctly
received by the drive.
Return Code (Drive to Host)
OP Data 1 Data 2 CRC Checksum
Address
Code MSB LSB MSB LSB LSB MSB
02H 08H 00H 00H AAH 55H 5EH A7H
The drive returns the same message to the host to confirm the data well received
from the host. Data 1 must be 0000H but Data 2 can be any values.
Note: The host cannot simultaneously broadcast 08H OP code to all drives when
multiple drives connected or drives reject drive’s OP codes.
6
122
Chapter 6 Communication Description
Return Code (Drive to Host)
Register
OP Starting Register Numbers to Write CRC Checksum
Address
Code MSB LSB MSB LSB LSB MSB
02H 10H 20H 00H 00H 02H 4AH 3BH
The host writes 2 data (1011H and 1770H) with total data length 4 byte to
2000H and 2001H registers of drive. The drive receives and writes the data to
the registers, and then returns the message to the host. The host can
synchronously broadcast all drives to write multi-data to multi-registers in order
to change the data synchronously.
6-4 CRC Checksum Algorithm
CRC checksum code is to verify the message validity during the communication
and its algorithm is to apply each code in the message to perform XOR and bit
shifting operations to generate the CRC code.
Here is the checksum algorithm diagram to generate CRC code.
XOR 1st Code Bit Shifting & XOR 2nd Code Bit Shifting & 3rd Code CRC
FFFFH
Address XOR(A001H) OP Code XOR(A001H) … Code
6
123
Chapter 6 Communication Description
The following example of using C language to create a sample program for CRC
checksum algorithm
Host
Communication Starts/Resets
The communication waits for 10ms to start the communication transmission after the
drive powers on or the communication function of the drive changes. The drive
needs 5ms processing time to return the message to the host after the message are
received from the host. If the broadcast do not send back the massage , the host can
start sending the message code after 5ms.
Note: if the message code is to “Read” or “Write” the parameter, the drive needs
100ms processing time to return the message to the host.
6
124
Chapter 6 Communication Description
6-6 Communication Troubleshooting
1. When error occurs at the communication network, the drive provides the
self-testing function to identify where error occurs. Please check
communication function settings to verify the validity of functions.
2. When the host receives returned error messages from a drive, the host
sends the invalid operation command to drive. The following table is the error
message format.
CRC Checksum
Address OP Code Error Code
LSB MSB
02H 1xxxxxxxB xxH xxH xxH
OP code sets MSB (bit7) as 1 for the original command message, but error code
gives different values according to different types of errors. The below table is
describing types of error code:
Error
Error Type Descriptions
Code
00 Parity error of serial communication
Serial communication
01 Data frame error of serial communication
format error
02 Over-bit error of serial communication
03 Modbus OP code error OP code is not in either 03H,06H,08H, or 10H
04 Modbus CRC error CRC checksum error
1. Data length in transmission not matched
Modbus data range
05 with the protocol
error
2. Data range over the register length at “write”
Modbus register
06 Registers writes into read-only registers
characteristics error
07 Modbus register error No-defined registers
6
125
Chapter 6 Communication Description
6-7 Drive Registers and Command Code
●Registers – Write Operation
Reg. No. Name Description
Drive function setting/monitoring;
10nnH Function setting
nn: F_000~F_195
00: No use
01: Stop
b0~b1
10: Start
11: JOG command
b2~b3 Reserved
00: No use
01: Forward command
b4~b5
10: Reverse command
11: Rotation direction change command
00: Primary acc./dec. time
01: Second acc./dec. time
b6~b7
10: Third acc./dec. time
11: Fourth acc./dec. time
0000: Primary speed (communication)
0001: Preset speed 1
0010: Preset speed 2
0011: Preset speed 3
2000H Operation command 1 0100: Preset speed 4
0101: Preset speed 5
0110: Preset speed 6
0111: Preset speed 7
b8~bB
1000: Preset speed 8
1001: Preset speed 9
1010: Preset speed 10
1011: Preset speed 11
1100: Preset speed 12
1101: Preset speed 13
1110: Preset speed 14
1111: Preset speed 15
bB Reserved
00: No use
01: b6~bB functions (*Note 1)
bC~bD
10: Enable operation command 2 resister.
11: 01 and 10 Disable
bE~bF Reserved
6
126
Chapter 6 Communication Description
●Registers – Write Operation
Primary frequency is set by communication
2001H Frequency command
(unit: 0.01Hz)
b0 1: External fault command
b1 1: Reset command
b2 1: Jog command
b3 1: Output interruption command
b4 1: Coast to stop command
2002H Operation command 2 b5 1: Secondary accel/decel command
b6 1: Accel/decel prohibition command
b7 1: Select analog input source
b8 1: DC braking enable
b9 1: Secondary frequency selection
bA~bF Reserved
2003H SV settimg value Setting value of constant pressure (unit: 0.1)
6
127
Chapter 6 Communication Description
●Registers – Read Operation
b0~b7 Reserved
b8 1: Frequency command by communication
b9 1: Frequency command by analog inputs
bA 1: Operation command by communication
2101H Drive status 1 bB 1: Parameter locks
bC 1: Drive running status
bD 1: Jog running status
bE 1: Forward indication
bF 1: Reverse indication
2102H Frequency command Monitor drive’s frequency command (unit: 0.01Hz)
2103H Output frequency Monitor drive’s output frequency(unit: 0.01Hz)
2104H Output current Monitor drive’s output current(unit: 0.1A)
2105H DC bus voltage Monitor drive’s DC bus voltage(unit: 0.1V)
2106H Output voltage Monitor drive’s AC output voltage(unit: 0.1V)
Frequency of Monitor drive’s frequency of multi-speed
2107H
multi-speed (*Note 2)
Practical pressure value (unit:0.1 pressure
2108H PV
sensor unit)
210DH Drive’s temperature Moniter the temperature of heat sink(unit:0.1℃)
b0 1: FWD terminal operation
b1 1: REV terminal operation
b2 1: X1 terminal operation
b3 1: X2 terminal operation
b4 1: X3 terminal operation
b5 1: X4 terminal operation
b6 Reserved
b7 Reserved
b8 1: Y1 terminal detection
b9 1: Y2 terminal detection
2300H I/O terminal status
bA 1: Ta1,Tb1 terminal detection
bB 1: Ta2/Tc2 terminal detection
1: Primary speed is controlled by analog
bC
input.
1: Primary speed is controlled by
bD
keypad.
1: Primary speed is controlled by
bE
UP/DOWN command.
1: Primary speed is controlled by
bF
communication.
6
128
Chapter 6 Communication Description
●Registers – Read Operation
b0 Reserved
b1 1: Constant speed
b2 1: Zero speed
b3 1: Frequency detection
b4 1: System overload
b5 1: Stall prevention
2301H Drive status 2
b6 Reserved
b7 1: Braking action
b8 Reserved
b9 Reserved
bA 1: Error occurs
bB~bF Reserved
2302H Reserved
2303H Fault record 1 Fault record 1 (*Note 3)
2304H Fault record 2 Fault record 2 (*Note 3)
2305H Fault record 3 Fault record 3 (*Note 3)
2306H Fault record 4 Fault record 4 (*Note 3)
2307H Fault record 5 Fault record 5 (*Note 3)
6
129
Chapter 6 Communication Description
Note:
1. When the b6~Bb function is enabled, multi-function command –Multi-speed 1, 2, 3,4 will be
inactive.
2. 0: Analog
1: Primary speed
2~8: Multi-speed 1~7
9: Jog speed
11: Communication
12~19: Preset speed 8~15
KEYPAD
02H Running
(LE1) Under voltage during operation
SV PV
KEYPAD
03H Running
(SC) Fuse open
SV PV
KEYPAD
06H Running
(GF) Grounding fault
SV PV
KEYPAD
07H Running
(OC) Drive over current
SV PV
KEYPAD
08H Running
(OE) Over voltage
SV PV
KEYPAD
09H Running
(OH) Drive overheat
SV PV
KEYPAD
KEYPAD
0BH Running
(OL1) Drive overload
SV PV
KEYPAD
0CH Running
(OLO) System overload
SV PV
KEYPAD
0DH Running
(thr) External fault
SV PV
KEYPAD
0EH Running
(ntcf) NTC thermistor sensor fault
SV PV
KEYPAD
KEYPAD
11H Running
(no Fb) PID feedback singal error
SV PV
KEYPAD
13H Running
(OP) Over preesure
SV PV
KEYPAD
15H Running
(COt) Communication overtime
SV PV
6
130
Chapter 6 Communication Description
6-8 Programming Examples – Register and Command
6-8-1 Access Drive Function Setting – Write Operation
Example: Set function F_009 (primary speed) = 30 Hz
a. Drive register used: 0009H(9 (decimal value)=0009H(hex)
b. Register data: 0BB8H(30Hz=30.00Hz(resolution:0.01Hz)
30.00÷0.01=3000(decimal)=0BB8H(hex))
Code to write to drive register from the host (CRC exclusive)
Drive Register Register Data
Address OP Code
MSB LSB MSB LSB
01H 06H 10H 09H 0BH B8H
6
131
Chapter 6 Communication Description
Primary accel time
a. Set F_019 (Primary accel time) = 1.5 seconds
Register number: 1013H (19 (decimal) = 0013H(hex)).
b. Register data:
000FH (1.5÷0.1(resolution:0.1sec.)=15(decimal)=000FH(hex)
Primary decel time
a. Set F_020 (Primary dec. time) = 1.5 seconds
Register number: 1014H(20( decimal)=0014H(hex))
b. Register data:
000FH(1.5 ÷0.1(resolution:0.1sec.) = 15(decimal)=000FH(hex)
Acceleration/Deceleration Time Setting
a. Register number: 2000H
b. Register data: 000HH(b6~b7)
b. The drive returns the fault code to the host when “GF” occurs:
-GF code: 0DH
6
132
Chapter 6 Communication Description
Return Code (Drive to Host)
2100H(Register) Data
Address OP Code Data Byte
MSB LSB
01H 03H 02H 00H 0DH
c. Program the host to convert register data 000DH to “GF”
message
2. Drive Frequency Output Readout:
Example: If the drive frequency outputs = 40.65Hz, read the data output
from the drive and display 40.65Hz in the host.
a. The host sends the below codes to access the drive register
to read out the frequency output data (read only one register
data)
-Drive register: 2103H
-Number of register to read: 1 0001H
Message Code (Host to Drive)
Register Numbers to
Drive Register
Address OP Code Readout
MSB LSB MSB LSB
01H 03H 21H 03H 00H 01H
b. The drive returns the frequency output readouts to the host
-Output frequency readouts from the drive (2103H register
data):
Return Code (Drive to Host)
2103H(Register) Data
Address OP Code Data Byte
MSB LSB
01H 03H 02H 0FH E1H
c. Program the host to convert register data 0FE1H (Hex value)
= 4065 (Decimal value)
d. Display the output frequency (resolution = 0.01): 4065/100 =
40.65 (unit in Hz)
6
133
Chapter 6 Communication Description
6
134
Chapter 7 Operation Procedures and Fault Protection
CAUTION
1. Check if the shield of wire is broken after wiring is completed to avoid electric
leakage or short circuit.
2. Screws on the terminal must be fastened.
A. Verify and check the compatibility between power source, voltage, motor, and
drive.
B. Connect the power to drive R/L1, S/L2, T/L3 (three-phases) or R/L1, S/L2
terminals (single-phase).
C. Set all required parameters and functions after power is ON and measure the
output voltage of the drive at U/T1, V/T2, W/T3 terminals to verify if the output
OFF
voltage and current are valid. Press RESET when completing all verifications.
D. Switch off the power and wait for drive’s power indicators off, and then connect
drive’s U/T1, V/T2, W/T3 terminals to the motor.
E. Operate the motor with the drive by low speed after power ON to verify the validity
of the motor rotation direction and then to slowly increase the motor speed.
F. Motor start or stop must be controlled by drive control signal instead of switching
the power ON / OFF. The lifetime of the drive will be significantly reduced if the
invalid operation using the switch control of the power is applied to motor control.
G. Because the starting current of motor is 6~8 times of rated current, Do NOT install
the magnetic contactor between the drive and motor for the motor operation.
H. When using the single-phase power source to drive the three-phase drive (not the
standard type of single-phase power input), first confirm the horsepower of motor,
and then calculate the motor rated current by multiplying the motor rated current
by 2 times to the base value of drive rated current. The drive selection for this
single-phase power must have the rated current equal to the calculated drive
rated value.
Formula: Motor rated current × 2 = Drive rated output current
7
135
Chapter 7 Operation Procedures and Fault Protection
Example:
a. Drive selection:
Motor specification: 220VAC, 1HP ; rated current: 3.1A
Base value of drive rated current=3.1 (A) × 2 = 6.2 (A)
Drive specifications: 220VAC, 1HP drive = 5A (rated output current)
2HP drive = 8A (rated output current)
Select 2HP drive for 1HP AC motor.
c. Parameter settings:
Please reset below functions. If the parameters are not modified,
the motor and drive could be possibly damaged.
7
136
Chapter 7 Operation Procedures and Fault Protection
7-2 Fault Protection Display and Troubleshooting
a: Description:
The drive has well protection functions to protect drive and motor when faults
occur. When the fault occurs, the drive trips by the protection functions and
display fault message on keypad. After the fault is troubleshooted, reset the
OFF
drive by pressing of keypad or command the drive to reset through
RESET
7
137
Chapter 7 Operation Procedures and Fault Protection
7
138
Chapter 7 Operation Procedures and Fault Protection
Error Trip Messages of Drive
Drive overheat ●The surrounding ●Improve the system
The temperature of temperature is too ventilation.
(OH) high. ●Clean the foreign
drive’s heat sink
KEYPAD
●The heat sink has body on the heat
reaches the trip
foreign body. sink.
SV Running
PV level..
●The cooling fan of ●Return the drive to
drive is fault. replace the cooling
fan.
Motor overload ●Motor overloaded. ●Check the load of
Operation current ●The voltage setting motor.
exceeds 150% of of V/F pattern is ●Check if the
motor’s rated too high or too low. acceleration or
(OL) ●The current setting deceleration time is
KEYPAD current and
reaches the motor of motor’s rated too short.
SV Running
PV overload protection current is invalid. ●Check if V/F setting
time. is proper.
●Check if the rated
current setting is
valid.
Drive overload ●Motor overload. ●Check if the load of
Operation current ●The voltage setting motor overload.
exceeds 150% of of V/F pattern is ●Check if the
(OL1) drive’s rated too high or too low. acceleration or
KEYPAD
current for 1 ●Drive capacity is deceleration time is
minute. too small. too short.
●Check if V/F setting
Running
SV PV
is proper.
●Select the higher
capacity of drive.
System overload
●Load system is
overload and the
(OLO) operation current
Check the usage of
KEYPAD
reaches the
--- mechanical
active level.
Running equipment.
●Detection level:
SV PV
F_068.
●Detection time:
F_069.
7
139
Chapter 7 Operation Procedures and Fault Protection
Error Trip Messages of Drive
Display Description Cause Troubleshooting
(thr) Clear the external
KEYPAD The multi-function
External fault terminal receives the fault and then press
OFF
SV Running
PV external fault signal. RESET
key.
(ntCF)
Please call
KEYPAD
NTC thermistor NTC thermistor
customer service for
sensor fault sensor is fault.
SV Running
PV drive repair.
7
140
Chapter 7 Operation Procedures and Fault Protection
activated.
Dynamic brake DC bus voltage is
(db) over voltage too high .
KEYPAD
Check if the input
The internal DC power is within drive’s
SV Running
PV
bus voltage of rated input range.
drive is over the
protection level.
7
141
Chapter 7 Operation Procedures and Fault Protection
7
142
Chapter 7 Operation Procedures and Fault Protection
7
143
Appendix A Applicable Safety Regulation
Shielded
Three-phase series Wire
Metal control
panel / cabinet
MCCB
/NFB Induction motor
Three-phase R/L1 EMC Filter R/L1 U/T1
50/60Hz S/L2
AC Power Input T/L3
(Option) S/L2 9916 V/T2 IM
T/L3 W/T3
PE
App.A
144
Appendix B Peripheral Equipment of Drive
Molded Case
Circuit When the power is ON, a large
Breaker inrush current will be inputted
(MCCB;NFB) into the drive. The breaker
or FUSE must be selected carefully.
Motor
App.B
145
Appendix C Selection of Motor
d. When the motor speed exceeds the rated speed (50/60Hz), the torque will be
decreased while the motor speed increasing.
e. Check the motor insulation. The standard requirement is 500V (or 1000V) /
100MΩ above.
App.C
146
Appendix C Selection of Motor
B. Insulation Measurement of Drive and Motor
1. Measure the drive insulation impedance
a. Please be extremely cautious to following steps to test the main circuit
insulation of drive. Any incautious operations while testing the drive
insulation may possibly harm operating personnel and cause serious
damages to drive.
b. Remove all wiring at power terminal (main circuit) and control circuit terminal
before the testing is conducted. Please follow the below diagram to wire all
power terminals in parallel with an insulation tester for drive insulation test.
c. Using an insulation tester with DC500V to test the insulation value of drive.
The drive insulation impedance must be greater than 20MΩ. If drive
insulation impedance is below 20MΩ, please contact with the customer
service.
Insulation
tester
Drive
Motor
cable
App.C
147
Appendix D Instruction of Drive Charging
Input terminal
250
125 375
Drive
0 500
Output terminal
Autotransformer
AC Power
Input terminal
250
125 375
Drive
0 500
Output terminal
Note: If the drive is already applied with drive rated voltage and doesn’t display
KEYPAD
SV Running
on the keypad, please contact the customer service for repair
PV
service.
App.D
148
Appendix E Dynamic Brake Unit and Braking Resistor
D W
L3±50 L2±2
L1±2
DANGER
When the dynamic brake unit is fault, the braking transistor maybe turn on for
full cycle. Add the thermal protection device to cut off the power at high
temperature to avoid the drive burnout (refer to the section f of Appendix D for
wiring of braking resistor).
App.E
149
Appendix E Dynamic Brake Unit and Braking Resistor
App.E
150
Appendix E Dynamic Brake Unit and Braking Resistor
AC 400V Series
Braking resistor specification Approximate
braking
Model number of drive Minimum
Recommending combination torque
specification
(10%ED)
RM6-4001B3-9916 400Ω/100W MHL100-400*1 145
MHL100-400*2
RM6-4002B3-9916 200Ω/200W 180
(2pcs in parallel)
MHL100-400*3
RM6-4003B3-9916 133Ω/300W 180
(3pcs in parallel)
MHL100-400*4
RM6-4005B3-9916 100Ω/400W 160
(4pcs in parallel)
RM6-4007B3-9916 MHL500-40*2 125
80Ω/1000W
RM6-4010B3-9916 (2pcs in series) 100
MHL500-40*4 150
RM6-4015B3-9916 40Ω/2000W (2pcs in parallel, 2 sets in
series) 120
MHL500-40*6
RM6-4025B3-9916 27Ω/3000W (3 pcs in parallel,2 sets in 135
series)
RM6-4030B3-9916 MHL500-40*8 160
20Ω/4000W (4 pcs in parallel,2 sets in
RM6-4040B3-9916 series) 120
MHL500-40*12
RM6-4050B3-9916 13.3Ω/6000W (6 pcs in parallel,2 sets in 150
series)
MHL500-40*16
RM6-4060B3-9916 10Ω/8000W (8 pcs in parallel,2 sets in 165
series)
MHL500-40*20
RM6-4075B3-9916 8Ω/10000W (10 pcs in parallel,2 sets in 160
series)
App.E
151
Appendix E Dynamic Brake Unit and Braking Resistor
e. Recommend specification of dynamic brake unit (DBU6) and braking
resistor
AC 200V Series
Drive DBU Braking resistor specification Approximate
specification braking
Model Unit Unit torque
Model number (DBU6-) (set) Recommend combination (set) (10%ED)
MHL500-40*18
RM6-2100E3-9916 L400 1 1 110
(9000W / 2.2; 18pcs in parallel)
MHL500-40*22
RM6-2125E3-9916 L400 1 (11000W / 1.82; 1 115
22pcs in parallel)
MHL500-40*26
RM6-2150E3-9916 L400 1 (13000W / 1.54Ω; 1 115
26pcs in parallel)
MHL500-40*18
RM6-2200E3-9916 L400 2 2 110
(9000W / 2.2Ω; 18pcs in parallel)
MHL500-40*22
RM6-2250E3-9916 L400 2 (11000W / 1.82Ω; 2 115
22pcs in parallel)
AC 400V Series
Drive DBU Braking resistor specification Approximate
specification braking
Model Unit Unit torque
Model number (DBU6-) (set) Recommend combination (set) (10%ED)
RM6-4100E3-9916 MHL500-40*24 145
H200 1 (12000W / 6.6; 12pcs in 1
RM6-4125E3-9916 parallel, 2 sets in series) 120
RM6-4150E3-9916 MHL500-40*36 155
H300 1 (18000W / 4.4; 18pcs in 1
RM6-4175E3-9916 parallel, 2 sets in series) 130
RM6-4200E3-9916 MHL500-40*48 140
H400 1 (24000W / 3.3; 24pcs in 1
RM6-4250E3-9916 parallel, 2 sets in series) 115
MHL500-40*72
RM6-4300E3-9916 H600 1 (36000W / 2.2; 36pcs in 1 155
parallel, 2 sets in series)
MHL500-40*80
RM6-4350E3-9916 H600 1 (40000W / 2Ω; 40pcs in 1 150
parallel, 2 sets in series)
MHL500-40*44
RM6-4420E3-9916 H400 2 (22000W / 3.63Ω; 22pcs in 2 135
parallel, 2 sets in series)
MHL500-40*52
RM6-4500E3-9916 H400 2 (26000W / 3.08Ω; 26pcs in 2 130
parallel, 2 sets in series)
MHL500-40*66
RM6-4600-9916 H600 2 (33000W / 2.42Ω; 33pcs in 2 140
parallel, 2 sets in series)
App.E
152
Appendix E Dynamic Brake Unit and Braking Resistor
Note:
1. %ED (Effective Duty Cycle) = Tb/Ta*100%
Output (continuous operation time Tb<15 sec).The
frequency definition is shown as left figure.
2. Above wattages of table is defined at 10%ED.
3. 200V series drive or DBU braking activation
voltage is DC 395V
4. 400V series drive or DBU braking activation
voltage is DC 790V
Time 5. The formula between %ED and resistor power
Tb is as follows:
Ta Vdc2 ×%ED
Pres=
R
Pres:Total power (W)
Vdc:400V(200V series) or 800V(400V series)
R:Total resistor(Ω)\
f. Wiring Diagram of External Braking Resistor and Thermal Switch
CAUTION
Strongly recommend to Install the thermal switch for the brake protection to
prevent the brake from any possible damages caused by the overheating on the
braking resistor. Please refer to the figure 1 and 2 as following for the wiring
diagram.
MC
(Figure 1)
(1) Use the thermal switch to protect the temperature of braking resistor and
generate an external fault signal to the multi-function terminal (X4) to stop the
drive when the braking resistor is overheating and interrupt the connection of
magnet contactor (MC) by output terminals Ta2 / Tc2.
(2) Set the multi-function terminal (X4) to “-7” (External fault).
(3) Set the multi-function terminal (Ta2 / Tc2) to “-11” (Error detection).
App.E
153
Appendix E Dynamic Brake Unit and Braking Resistor
AC220V
DC24V RELAY
OFF
OHD3-100B
PR P N
MC AC Motor
R/L1 R/L1 U/T1
S/L2 S/L2 V/T2 IM
T/L3 T/L3
RM6 series W/T3
PE
(9916) PE
(Figure 2)
When the drive power is controlled by the magnet contactor (MC), use the thermal
switch to control magnet contactor (MC). When the braking resistor is overheating,
the contactor (MC) is disconnected.
App.E
154
Appendix E Dynamic Brake Unit and Braking Resistor
CAUTION
Strongly recommend to Install the thermal switch for the brake protection to
prevent the brake from any possible damages caused by the overheating on the
braking resistor. Please refer to the figure 1 and 2 as following for the wiring
diagram.
P N
DBU
RB1 RB2
MC
Thermal Switch
Braking Resistor (option)
(OHD3-100B)
(Figure 1)
(1) Use the thermal switch to protect the temperature of braking resistor and
generate an external fault signal to the multi-function terminal (X4) to stop the
drive when the braking resistor is overheating and interrupt the connection of
magnet contactor (MC) by output terminals Ta2 / Tc2.
(2) Set the multi-function terminals (X4) to “-7” (External fault).
(3) Set the multi-function terminals (Ta2 / Tc2) to “-11” (Error detection).
App.E
155
Appendix E Dynamic Brake Unit and Braking Resistor
Thermal
DC24V AC220V Switch
RB1
RELAY (OHD3-100B)
DBU6
OHD3-100B RB2
OFF
P N
RELAY
MC ON
DC0V
MC
PR P N
AC220V MC AC Motor
R/L1 R/L1 U/T1
S/L2 S/L2 V/T2 IM
T/L3 T/L3
RM6 series W/T3
PE
(9916) PE
(Figure 2)
When the drive power is controlled by the magnet contactor (MC), use the thermal
switch to control magnet contactor (MC). When the braking resistor is overheating,
the contactor (MC) is disconnected.
App.E
156
Appendix F Selection of Reactor
ACL is necessary
Power capacity (kVA)
500
ACL is not necessary
Drive capacity
0 50 700 (kVA)
c. When the heater (with the SCR), air compressor, high-frequency equipment, or
welding machine is installed at the same power source system, the harmonic
current will interfere the drive. Thus, add the ACL at the input terminal
(R/L1,S/L2,T/L3) of the drive is required.
d. When multiple drives of high horse power are used, due to harmonic wave
generate, adding ACL at the input terminal (R/L1,S/L2,T/L3) of the drives is
required to prevent the drives from the possible interference and power quality
deterioration.
e. When the cable length between the drive and motor is over 30 meters or multiple
motors are used in parallel, please add ACL at the output terminal of the drive.
f. Add the ACL at the input terminal(R/L1,S/L2,T/L3), the power factor is above 75%;
Add ACL and DCL, the power factor is above 90%.(the specifications of ACL and
DCL, please refer to page 163 ~166)
g. When horse power of drive is 100HP(included) or above, ACL is the standard
equipment. When the drive is 175HP(included) or above, DCL is the standard
equipment.
h. The connecting cable between the drive and DCL must be the same specifications
with the cable of input terminal(R/L1,S/L2,T/L3).
App.F
157
Appendix F Selection of Reactor
RM6-2040-9916 0.035 150 0.025 200 RM6-4050-9916 0.05 100 0.05 100
RM6-2050-9916 0.025 200 0.025 200 RM6-4060-9916 0.05 100 0.035 150
RM6-2060-9916 0.025 200 0.015 300 RM6-4075-9916 0.035 150 0.025 200
RM6-2075-9916 0.015 300 0.013 400 RM6-4100-9916 0.025 200 0.025 200
RM6-2100-9916 0.013 400 0.013 400 RM6-4125-9916 0.025 200 0.015 300
RM6-2125-9916 0.013 400 0.01 600 RM6-4150-9916 0.015 300 0.015 300
RM6-2150-9916 0.01 600 0.01 600 RM6-4175-9916 0.015 300 0.013 400
RM6-2200-9916 0.006 800 0.006 800 RM6-4200-9916 0.013 400 0.013 400
RM6-2250-9916 0.006 800 0.005 1000 RM6-4250-9916 0.013 400 0.01 600
App.F
158
Appendix F Selection of Reactor
App.F
159
Appendix F Selection of Reactor
H(MAX)
H(MAX)
H(MAX)
B C
B C B C
A D
A D A D
4-GHole L(MAX) 4-G Hole L(MAX)
4-G Hole
W(MAX)
W(MAX)
6-ψI
6-ψI
H(MAX)
H(MAX)
B C B C
A D D
A
4-G Hole L(MAX) 4-G Hole L(MAX)
Figure D Figure E
W L H Weight
Capacity Figure A B C D G I
(MAX) (MAX) (MAX) (kg)
1.0mH/10A A 91 81 58 70 93 80 110 7×4.5 3 1.8
1.0mH/15A A 109 86 58 77 111 95 135 12×5 3 2.0
0.2mH/30A A 109 86 58 77 111 95 135 16×8 6 2.2
0.13mH/50A B 150 80 70 85 152 126 130 16×8 6 4.6
0.07mH/75A B 150 80 68 85 151 126 131 16×8 6 4.8
0.05mH/100A C 146 90 77 99 155 132 132 16×8 8 4.1
0.035mH/150A C 146 90 77 99 155 132 132 16×8 8 4.1
0.025mH/200A B 180 100 90 107 182 160 150 16×8 8 9.8
0.015mH//300A D 230 120 104 130 230 220 210 25×14 12 19
0.013mH//400A D 230 120 104 130 230 240 200 22×10 12 20.2
0.01mH//600A D 280 140 120 135 280 270 235 22×10 16 29.3
0.006mH/800A E 300 150 140 174 300 300 305 25×13 15 65
0.005mH/1000A E 350 160 145 184 350 290 320 25×13 14 84.6
(unit: mm)
App.F
160
Appendix F Selection of Reactor
Outline dimensions of DC reactor (DCL)
圖A 圖B
W(MAX)
W(MAX)
2-ψI
2-ψI
H(MAX)
H(MAX)
B C B C
A D A D
4-G 固定孔
Hole L(MAX) 4-G 固定孔
Hole L(MAX)
圖A A
Figure 圖B B
Figure
圖C
W(MAX)
W(MAX)
2-ψI
2-φI
H(MAX)
H(MAX)
BB C C
4-G Hole
AA D D
L(MAX)
L(MAX)
圖C C
Figure
Specifications of DC reactor (DCL)
W L H Weight
Capacity Figure A B C D G I
(MAX) (MAX) (MAX) (kg)
App.F
161
Appendix G Selection of Zero-Phase Radio Frequency Filter
1. Specification of product:
Model RM6 series (9916)
(1) Clean place without high temperature, high humidity, and
flammable gases.
Environmental Condition
(Note)
Power R Either the ground wire or the four-core
S
T
cable with ground wire cannot pass through
RFI filter; otherwise the filtration effect will
RFI be reduced.
App.G
162
Appendix G Selection of Zero-Phase Radio Frequency Filter
(2) Install the RFI filter at the output site of the drive
(Note)
Ex. 2 Either the ground wire or the four-core
U cable with ground wire cannot pass
V through RFI filter; otherwise the filtration
Motor
W
will be reduced
RFI
(3) If the power cords are too thick to be winded, pass the power cords through
RFI filter directly, and connect two or more RFI in series.
Pass all 3-phase power cords through
Ex. 1 RFI filter in same direction with same
coil number, and then connect to motor
U terminals of the drive. Caution: Do Not
V Motor exceed 4 coils to prevent overheating of
W RFI filter.
RFI (Note)
Either the ground wire or the four-core
cable with ground wire cannot pass
through RFI filter; otherwise the
filtration will be reduced.
3. If noise of radio frequency is too high, user can add mount of RFI to reduce the
noise.
4.
Model Wire Size (mm²) Coil Number of 3-Phase Wire
2/3.5 4
5.5 3
RFI-01
8/14 2
22 1
22/38 4
RFI-02 50/60 2
80/100/125/150 1
50/60 3
RFI-03 80/100/125/150 2
200 1
50/60 4
80/100 3
RFI-04 125/150 2
200 2
250 1
App.G
163
Appendix G Selection of Zero-Phase Radio Frequency Filter
(unit: mm)
7
ψ7
130
86
37
85
1.4
180
(unit: mm)
App.G
164
Appendix G Selection of Zero-Phase Radio Frequency Filter
211 12
130 44
130
176
54
37
2
230
(unit: mm)
276 12
175 54
241
154
63
46
295
(unit: mm)
App.G
165
Appendix H Selection of EMI Filter
App.H
166
Appendix H Selection of EMI Filter
400V series
Drive model EMI filter
Rated current / phase
number model number
RM6-4001-9916 FN3270H-10-44 10A / 3ψ
RM6-4002-9916 FN3270H-10-44 10A / 3ψ
RM6-4003-9916 FN3270H-10-44 10A / 3ψ
RM6-4005-9916 FN3270H-10-44 10A / 3ψ
RM6-4007-9916 FN3270H-20-44 20A / 3ψ
RM6-4010-9916 FN3270H-20-44 20A / 3ψ
RM6-4015-9916 FN3270H-35-33 35A / 3ψ
RM6-4020-9916 FN3270H-35-33 35A / 3ψ
RM6-4025-9916 FN3270H-50-34 50A / 3ψ
RM6-4030-9916 FN3270H-50-34 50A / 3ψ
RM6-4040-9916 FN3270H-65-34 65A / 3ψ
RM6-4050-9916 FN3270H-80-35 80A / 3ψ
RM6-4060-9916 FN3270H-100-35 100A / 3ψ
RM6-4075-9916 FN3270H-150-99 150A / 3ψ
RM6-4100-9916 FN3270H-200-99 200A / 3ψ
RM6-4125-9916 FN3270H-200-99 200A / 3ψ
RM6-4150-9916 FN3270H-250-99 250A / 3ψ
RM6-4175-9916 FN3270H-320-99 320A / 3ψ
RM6-4200-9916 FN3270H-320-99 320A / 3ψ
RM6-4250-9916 FN3270H-400-99 400A / 3ψ
RM6-4300-9916 FN3270H-600-99 600A / 3ψ
RM6-4350-9916 FN3270H-600-99 600A / 3ψ
RM6-4420-9916 FN3270H-800-99 800A / 3ψ
RM6-4500-9916 FN3270H-800-99 800A / 3ψ
RM6-4600-9916 FN3270H-1000-99 1000A / 3ψ
Note:
The leakage current of FN3270 series approximately 26.4mA ~ 59.5mA
App.H
167
Appendix I Instruction of Remote Controller and External Display
screw
(unit: mm)
screw
(unit: mm)
App.I
168
Appendix I Instruction of Remote Controller and External Display
A-02
A-01
65
14 37
32.5 ψ5 72.8
6
112
124
A-02 A-02
FM+
2 M-
R2.5 Vin
4-M4 screw GND
12V
FWD
COM
ψ 10
(Unit: mm)
App.I
169
Appendix I Instruction of Remote Controller and External Display
96 7 75
2
2.7 90.6
44
48
1.5
93 98
Panel cutting
45
dimension
Unit:mm
3. The standard length of 2.54/5P wires is 1.5 m and 3 m respectively. Do not exceed
this length.
App.I
170
Appendix J Outline Dimension Drawing of Drives
Appendix J Outline Dimension Drawing of Drives
6.5
46
5.5
151.5
138
5.5
128
2-M4 screw
138
110
100
85
(unit: mm)
259.0
246.0
260.5
2-ψ23
Panel
246.0
284.0
266.5
cutting
dimension
14.5
16.5
105.0
(unit: mm)
App.J
171
Appendix J Outline Dimension Drawing of Drives
Model Number: RM6-2010-9916 ~ RM6-2015-9916;
RM6-4015-9916 ~ RM6-4025-9916
Internal cooling type External cooling type
Supporting frame accessory (M1031383)
180.0 (Model: A0006804 V1.1)
2-ψ6 hole 200.0
180.0 2-ψ6.6 hole 162.0
200.0 8
162.0 5.8 74.0
8.9
5.8
68.6
328.8
313.0
62.6
276.5
290.0
290.0
6.5 7
177.0
162.0
4-M5
7.5 10
Screw
4-M5 162.0
2-ψ35 2-ψ35
Screw
3-ψ23 3-ψ23
Panel
290.0
313.0
cutting
277.0
dimension
(unit: mm)
Model Number: RM5G-2020 ~ RM5G-2040;RM5P-2025 ~ RM5P-2050;
RM5G-4030 ~ RM5G-4060;RM5P-4040 ~ RM5P-4075
Internal cooling type External cooling type
Supporting frame accessory(M1031515)
(Model: A0007500 V1.1)
250.0 2-ψ9 hole 250.0
250.0 230.0 103.2
250.0
2-ψ9 hole
230.0 138.0
9.5
95.7
428.0
448.2
359.9
380.0
399.6
400.0
9.0
9.0
247.0
4-M8 Screw 230.0
8.5
4-M8 230.0
ψ35 2-ψ50 Screw ψ35 2-ψ50
2-ψ23 2-ψ23
11.5
Panel
396.0
427.0
cutting
dimension
380.0
29.0
211.0 18.0
(unit: mm)
App.J
172
Appendix J Outline Dimension Drawing of Drives
H1
H1
H2
H2
H
H
d ψ 15 d ψ 15
4 screw 4 screw
W4
W3 W3
Panel
H1
cutting
H4
H3
D2
D2
dimension
App.J
173
RM6 series (9916) 200V Series
App.J
Model Screw
number
W W1 W3 W4 H H1 H2 H3 H4 h1 h2 h3 D0 D1 D2 d d1 (mm)
Appendix J
RM6-2050-9916
RM6-2060-9916 386 361 275 365 584 562 539 564 545 11 25 10 325 170 242 10 3 M8
RM6-2075-9916
RM6-2100-9916 446 418 275 427 685 660 630 662 634 14 30 12 334 172 246 12 3 M10
RM6-2125-9916
508 479 275 487 818 785 751 788 758 19 35 12 366 183 257 15 3
RM6-2150-9916
174
M12
RM6-2200-9916
696 654 580 657 1000 974 929 978 936 15 39 18 405 224 294 15 3
RM6-2250-9916
Outline Dimension Drawing of Drives
RM6 series (9916) 400V Series
Model Screw
number
W W1 W3 W4 H H1 H2 H3 H4 h1 h2 h3 D0 D1 D2 d d1 (mm)
RM6-4075-9916
RM6-4100-9916 386 361 275 365 584 562 539 564 545 11 25 10 325 170 242 10 3 M8
RM6-4125-9916
Appendix J
RM6-4150-9916
446 418 275 427 685 660 630 662 634 14 30 12 334 172 246 12 3 M10
RM6-4175-9916
175
RM6-4200-9916
508 479 275 487 818 785 751 788 758 19 35 12 366 183 257 15 3
RM6-4250-9916
RM6-4300-9916
RM6-4350-9916 696 654 580 657 1000 974 929 978 936 15 39 18 405 224 294 15 3 M12
RM6-4420-9916
RM6-4500-9916
992 954 710 958 1030 1003 963 1007 968 15 39 19 419 235 308 15 3
RM6-4600-9916
App.J
Outline Dimension Drawing of Drives
Appendix J Outline Dimension Drawing of Drives
App.J
176
Appendix K Auxiliary Controller (ACE-S Series)
App.K
177
Appendix K Auxiliary Controller (ACE-S Series)
App.K
178
Attachment 1 Dimension of Keypad (KP-207)
66+10
55
2-M3 screw
48
60
ψ30
96+10
85
23
16 23
23x23
Scale: 1:1
Unit: mm
Att.1
179
Attachment 2 Default Value List
Att.2
180
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
15.0 15.0 15.0 15.0
F_023 Preset Speed2
(Note1) (Note1) (Note1) (Note1)
15.0 15.0 15.0 15.0
F_024 Preset Speed2
(Note1) (Note1) (Note1) (Note1)
15.0 15.0 15.0 15.0
F_025 Preset Speed3
(Note1) (Note1) (Note1) (Note1)
15.0 15.0 15.0 15.0
F_026 Preset Speed3
(Note1) (Note1) (Note1) (Note1)
15.0 15.0 15.0 15.0
F_027 Secondary Acceleration Time
(Note1) (Note1) (Note1) (Note1)
15.0 15.0 15.0 15.0
F_028 Secondary Deceleration Time
(Note1) (Note1) (Note1) (Note1)
Set S-curve for
F_029 0.0 0.0 0.0 0.0
Accel/Decel Time
F_030 Limitation of Output Voltage 0 0 0 0
F_031 Maximum Output Frequency 60.00 50.00 50.00 60.00
F_032 Starting Freauency 0.5 0.5 0.5 0.5
8.0 8.0 8.0 8.0
(note:2) (note:2) (note:2) (note:2)
F_033 Starting Voltage
12.0 12.0 12.0 12.0
(note:3) (note:3) (note:3) (note:3)
F_034 Base Frequency 60.00 50.00 50.00 60.00
200 200 200 200
(note:2) (note:2) (note:2) (note:2)
F_035 Base Voltage
380 380 380 380
(note:3) (note:3) (note:3) (note:3)
F_036 V/F Frequency1 0.0 0.0 0.0 0.0
F_037 V/F Frequency1 0.0 0.0 0.0 0.0
F_038 V/F Frequency2 0.0 0.0 0.0 0.0
F_039 V/F Frequency2 0.0 0.0 0.0 0.0
F_040 Vin Gain 1.00 1.00 1.00 1.00
F_041 Vin Bias 0.00 0.00 0.00 0.00
F_042 Frequency Upper Limit 1.00 1.00 1.00 1.00
F_043 Frequency Lower Limit 0.00 0.00 0.40 0.40
F_044 FM+ Analog Output Signal Selection 0 0 0 0
F_045 FM+ Analog Output Gain 1.00 1.00 1.00 1.00
F_046 Motor Overload Protection (OL) 1 1 1 1
F_047 Filter Setting of Analog Input Signal 20 20 20 20
F_048 Motor Rated Current - - - -
F_049 Motor No-Load Current - - - -
F_050 Motor Slip Compensation 0.0 0.0 0.0 0.0
Att.2
181
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
F_051 Number of Motor Poles 4P 4P 4P 4P
F_052 Multi-function Input Terminal X1 3 3 3 3
F_053 Multi-function Input Terminal X2 4 4 4 4
F_054 Multi-function Input Terminal X3 1 1 1 1
F_055 Multi-function Input Terminal X4 2 2 18 18
F_056 Reserved - - - -
F_057 Reserved - - - -
F_058 Multi-function Output Terminal Y1 1 1 1 1
F_059 Multi-function Output Terminal Y2 2 2 2 2
Multi-function Output Terminal
F_060 11 11 11 11
Ta1,Tb1
Constant Speed
F_061 2.0 2.0 2.0 2.0
Detection Range
F_062 Frequency Detection Range 2.0 2.0 2.0 2.0
F_063 Frequency Detection Level 0.0 0.0 0.0 0.0
Automatic Torque Compensation
F_064 1.0 1.0 1.0 1.0
Range
Att.2
182
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
Operation Selection at Instantaneous
F_078 0 0 0 0
Power Failure
175 175 175 175
The Voltage Level Setting at Power (Note2) (Note2) (Note2) (Note2)
F_079
Failure 320 320 320 320
(Note3) (Note3) (Note3) (Note3)
Auto-restart Times Setting of
F_080 0 0 0 0
Error Trip
F_081 Switching Frequency 1 1 1 1
F_082 Stop Mode 0 0 1 1
F_083 Reverse Prohobition 0 0 0 0
F_084 Jump Frequency1 0.0 0.0 0.0 0.0
F_085 Jump Frequency2 0.0 0.0 0.0 0.0
F_086 Jump Frequency3 0.0 0.0 0.0 0.0
F_087 Jump Frequency Range 0.3 0.3 0.3 0.3
F_088 The Current Level of Speed Tracing 150 150 150 150
Delay Time for
F_089 0.5 0.5 0.5 0.5
Speed Tracing
The V/F Pattern of
F_090 100 100 100 100
Speed Tracing
F_091 Error Record - - - -
F_092 Parameter Setting Lock 0 0 0 0
F_093 Automatic Voltage Regulation (AVR) 1 1 1 1
F_094 Drive Overload (OL1) 3 3 3 3
220.0 220.0 220.0 220.0
(Note2) (Note2) (Note2) (Note2)
F_095 Power Source
380.0 380.0 380.0 380.0
(Note3) (Note3) (Note3) (Note3)
Analog Frequency
F_096 0.5 0.5 0.5 0.5
Dead Band
F_097 Holding Time Interval 0.0 0.0 0.0 0.0
F_098 Grounding Fault Protection (GF) 1 1 1 1
F_099 External Indicator 1 1 1 1 1
F_100 External Indicator 2 5 5 5 5
F_101 External Indicator 3 2 2 2 2
F_102 V/F Pattern Selection 0 0 0 0
Subtracted Frequency of Deceleration
F_103 3.0 3.0 3.0 3.0
at Power Failure
Deceleration Time 1 of Ramp to Stop 15.0 15.0 15.0 15.0
F_104
by Power Failure (Note1) (Note1) (Note1) (Note1)
Deceleration Time 2 of Ramp to Stop 15.0 15.0 15.0 15.0
F_105
by Power Failure (Note1) (Note1) (Note1) (Note1)
Att.2
183
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
Switching the Frequency of
F_106 0.0 0.0 0.0 0.0
Ramp to Stop
F_107 Analog Frequency Dead Band 0.00 0.00 0.00 0.00
F_108 Digital Input Response Time 10 10 10 10
F_109 Communica-tion Interface Selection 1 1 1 1
F_110 Communication Address 0 0 0 0
Communica-tion
F_111 1 1 1 1
Baud Rate
F_112 Communication Protocol 1 1 1 1
F_113 Communication Overtime (Cot) 0.0 0.0 0.0 0.0
F_114 Feedback Signal Trip Detection 0 0 0 0
Att.2
184
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
Overheat Protection and
F_138 0.0 0.0 0.0 0.0
Temperature Adjustment
F_139 Operation Condition Memory 1 1 1 1
F_140 NTC Thermistor Setting 1 1 1 1
Drive Overheating
F_141 0 0 0 0
Warning Selection
Drive Overheating
F_142 70 70 70 70
Warning Level
Drive Overheating
F_143 3.0 3.0 3.0 3.0
Dead Band
F_144 Fan Control Selection 1 1 1 1
F_145 Temperature Level of Fan Activation 50 50 50 50
F_146 Minimum Operation Time of Fan 0.5 0.5 0.5 0.5
F_147 SV Setting 2.0 2.0 2.0 2.0
F_148 PID Control Display 0.0 0.0 0.0 0.0
F_149 “SV-PV” Value Display 1 1 1 1
F_150 PID Control Command 2 2 2 2
F_151 Upper Limit of Transmitter 10.0 10.0 10.0 10.0
F_152 Lower Limit of Transmitter 0.0 0.0 0.0 0.0
F_153 PID Control Mode Selection 0 0 1 1
F_154 P Selection 1 1 1 1
F_155 Gain Value(P) 1.0 1.0 2.0 2.0
F_156 Integration Time (I) 2.0 2.0 1.0 1.0
F_157 Derivative Time (D) 0.00 0.00 0.00 0.00
F_158 Feedback Derivative Time 0.00 0.00 0.00 0.00
F_159 Integration Upper Limitation 1.00 1.00 1.00 1.00
F_160 Integration Lower Limitation 0.00 0.00 0.40 0.40
F_161 Integrator Initialized Value 0.00 0.00 0.00 0.00
F_162 PID Buffer Space 2 2 2 2
F_163 Feedback Signal Filter 10 10 10 10
F_164 Feedback Signal Detection 1 1 1 1
F_165 Feedback Signal Selection 0 0 0 0
F_166 (2nd PI Control)Active Range 0.0 0.0 2.0 2.0
Att.2
185
Attachment 2 Default Value List
dEFC3 dEFC4
dEF60 dEF50
50Hz 60Hz
Func. Name 60Hz 50Hz
Air Air
General General
Compressor Compressor
Setting Selection by
F_171 1 1 1 1
Open-Loop Command
KP Selection by
F_172 0 0 1 1
Open-Loop Command
F_174 On-Off Control Selection 0 0 0 0
F_175 (On-Off) Delay Time Conrol 0 0 0 0
F_176 (On) Range Setting 1.0 1.0 1.0 1.0
F_177 (Off) Range Setting 1.0 1.0 1.0 1.0
F_178 (On)Delay Time 0 0 0 0
F_179 (Off)Delay Time 0 0 0 0
(On-Off)Accel/Decel
F_180 1 1 1 1
Time Selection
F_181 (Off)Holding Time 0 0 0 0
F_182 Air Conditioning Mode 0 0 0 0
(Air Condi- tioning Mode)
F_183 5.0 5.0 5.0 5.0
TemperatureResponse Time
(Air Condi- tioning Mode)
F_184 2.0 2.0 2.0 2.0
Variation Frequency
(Air Condi- tioning Mode)
F_185 3.0 3.0 3.0 3.0
Upper Limit Range of Temperature
(Air Condi- tioning Mode)
F_186 1.0 1.0 1.0 1.0
Lower Limit Range of Temperature
Att.2
186
Attachment 3 Setting Memo
F_008 0 F_030 0
60.00
F_009 00.00 F_031 (50.00)
200V: 8.0
F_011 20.0 F_033 400V: 12.0
60.00
F_012 30.0 F_034 (50.00)
200V: 220.0
F_013 0.00 F_035 400V: 380.0
60.00
F_018 (50.00)
F_040 1.00
Att.3
187
Attachment 3 Setting Memo
Setting Setting
Func. Description dEFC4 Func. Description dEFC4
Value Value
F_044 0 F_068 160
F_045 1.00
F_069 2.0
F_046 1
F_047 20 F_070 170
According
to the
F_048 rated F_071 160
current of
motor
1/3 motor
F_049 Rated F_072 Note
current
F_051 4P F_074 1
F_052 3 F_075 50
F_055 18 F_078 0
200V: 175.0
F_056 - F_079 400V: 320.0
F_057 - F_080 0
F_058 1 F_081 1
F_059 2 F_082 1
F_060 11 F_083 0
Att.3
188
Attachment 3 Setting Memo
Setting Setting
Func. Description dEFC4 Func. Description dEFC4
Value Value
F_091 - F_116 0
F_092 0 F_117 6
F_093 1 F_118 0
F_094 3 F_119 0
200V: 220.0
F_095 F_120 1
400V: 380.0
F_098 1 F_123 0
F_099 1 F_124 1
F_100 5 F_125 4
F_101 2 F_126 0
F_108 10 F_133 -
F_109 1 F_134 -
F_110 0 F_135 1
F_112 1 F_137 0
F_114 0 F_139 1
F_115 0 F_140 1
Att.3
189
Attachment 3 Setting Memo
Setting Setting
Func. Description dEFC4 Func. Description dEFC4
Value Value
F_141 0 F_167 15.0
F_144 1 F_170 0
F_145 50 F_171 1
F_148 0 F_174 0
F_149 1 F_175 0
F_153 1 F_179 0
F_154 1 F_180 1
F_164 1 F_190 0
Att.3
190
Attachment 3 Setting Memo
Setting Setting
Func. Description dEFC4 Func. Description dEFC4
Value Value
F_193 300 F_202 0.00
F_195 1 F_204 -
Note:
0.5 ~ 5HP → 5 sec
7.5 ~ 30HP → 15 sec
40HP 以上 → 30 sec
Att.3
191
Attachment 4 Fault Display
(AdEr) (OL)
KEYPAD
A/D converter KEYPAD
Motor overload
error
Running Running
SV PV SV PV
(SC) (OL1)
KEYPAD KEYPAD
(LE1) (OLO)
KEYPAD
Under voltage KEYPAD
System overload
during operation
Running Running
SV PV SV PV
(OC) (thr)
KEYPAD KEYPAD
(GF) (ntCF)
KEYPAD KEYPAD
NTC Thermistor
Grounding fault
sensor fault
Running Running
SV PV SV PV
(OE) (PAdF)
KEYPAD KEYPAD
Keypad interruption
Over voltage
during copy
Running Running
SV PV SV PV
(Cot)
KEYPAD
Communication
overtime
Running
SV PV
Over pressure
signal error
Running
SV PV SV Running
PV
Att.4
192
Attachment 4 Fault Display
(bb) (OP)
KEYPAD
Drive output KEYPAD
Over pressure
interruption
Running Running
SV PV SV PV
(Fr) (Ht)
KEYPAD KEYPAD
(db) (PrEr)
KEYPAD Dynamic brake KEYPAD
(Err_01)
KEYPAD
Err_01: Keypad
cable trip during
SV Running
PV
operation
Att.4
193
Notes
Notes
194
Notes
Notes
195