Single Phase Electronic Meter

User Manual

Single Phase Electronic Meter


For Active Energy

HXE12R

Version:V1.0 2013

1 / 18
Single Phase Electronic Meter

Content

1. General .......................................................................................................................................... 3
2. Front Panel .................................................................................................................................... 4
3. Standard ........................................................................................................................................ 4
4. Working Principle ......................................................................................................................... 4
5. Measurement ................................................................................................................................. 5
6. LCD display .................................................................................................................................. 6
6.1 LCD with full segments .............................................................................................................. 6
6.2 Display segments ........................................................................................................................ 6
7. Display mode ................................................................................................................................ 7
8. Back-up battery ............................................................................................................................. 8
9. LED Indication.............................................................................................................................. 8
10. Self Diagnostic ............................................................................................................................ 8
10.1 Reverse Energy ......................................................................................................................... 8
10.2 Meter Malfunction .................................................................................................................... 9
11. Installation ................................................................................................................................... 9
11.1 General Consideration ............................................................................................................... 9
11.2 Meter Handling ....................................................................................................................... 10
11.3 Meter Connection .................................................................................................................... 10
12. Parameters ................................................................................................................................. 12

2 / 18
Single Phase Electronic Meter

1. General
This manual is for single phase energy meter for active energy.
HXE12R electronic meter is developed and manufactured by Hexing.
It features in high accuracy, low power consumption and reliable stability and
superior anti-tampering functions.

Main Features
ƒ LCD with 8 digits display format for energy record and meter status.
ƒ LCD keeps display even when power supply is not available
ƒ Display dual tarrif energy on both import active energy and export active
energy
ƒ Super capacity lithium battery used as back-up power supply
ƒ Meter can detect reverse energy. The active tampering event will be
indicated on LCD.
ƒ Meter can continuously register energy accuracy under abnormal or
tampering conditions.
ƒ Meter is with self-diagnostic function and will display Error Code on LCD
once an error occurred.
ƒ Meter is equipped with non-resettable register.
ƒ Specially designed buckle structure to avoid malicious open to the meter

3 / 18
Single Phase Electronic Meter

2. Front Panel

3. Standard

Standard Description Version


"Electricity metering equipment (a.c.)
IEC 62052-11 – General requirements, tests and test conditions 2003
– Part 11: Metering equipment "
"Electricity metering equipment (a.c.) –Particular
IEC 62053-21 requirements
2003
–Part 21:Static meters for active energy(classes
1 and 2) "
"Electricity metering
– Data exchange for meter reading, tariff and
IEC 62056-21 2002
load control
– Part 21:Direct local data exchange"

4. Working Principle

4 / 18
Single Phase Electronic Meter

L Current sampling
Load

EEPROM

Optical
Voltage
Power Supply communication
sampling
230V
Terminal cover
DC open detection
Circuit
Back light
MCU

Active energy
Battery LED

LCD Display

5. Measurement
This meter is designed to measure two types of energy:
z Import active energy
z Reverse active energy
Dual tarrif measurement on both import active and export active. Import active and reactive
measurement +A=+A -A=|-A|。
Store import and export energy data of 12 months.
z Tarrif: 2 tarrif
z Tarrif schedule: 8 tarrif schedules, each have 16 time frames max.
z Week table:Max 12 week types, in each week type, it can be appointed with tarrif from
Monday to Sunday.
z Season table:Max 12 season types. Each season can be appointed with week type that
needs to be used in this season.
z Holiday: Max 120 holidays. Each holiday can be appointed with tarrif that needs to be
used in this holiday. Among them, public holiday can be appointed as special holiday and
annually periodic holidays.

5 / 18
Single Phase Electronic Meter

6. LCD display
6.1 LCD with full segments
Below is LCD with full-segment display.

6.2 Display segments


Segments Description

6 / 18
Single Phase Electronic Meter

Default 6+0 digit display, Integer and


decimal digits are configurable, integer
has 8 digits max, decimal has 3 digits
max

Shows energy code

Low battery indicator

represent current T1, T2

Reverse energy indication

Forward energy indication

Communication status indication

Energy mnemonic symbol

7. Display mode
This meter is designed with two display modes:
z Normal scrolling display
z Power outage display
Normal scrolling display
Under this display mode, LCD shows import active and export active energy in
each 8 seconds. Details as below:
Total import active: 000 T1+T2
7 / 18
Single Phase Electronic Meter

T1 import:001 T1
T2 import:002 T2
Total export:010 T1+T2
T1 export:011 T1
T2 export:012 T2

Power outage display


When power supply is not available, meter can display import active energy.
Such display mode is realized by meter’s back-up battery.

8. Back-up battery
This meter is equipped with high quality lithium back-up battery. Back-up
battery is used to keep LCD display when power supply is not available. This
battery is tested and installed inside the meter in the factory. For safety
consideration and in order to keep the battery working in a good condition,
meter should be installed where is far away from heat-emitting household
compliance, such as stove. When the battery is in low voltage condition,

will be shown on LCD as indication.

9. LED Indication
LED is available for the meter. LED is on to indicate the meter is connected to
power supply and it flashes to indicate energy consumption.

10. Self Diagnostic


10.1 Reverse Energy
This meter is designed with reverse energy detection functionality. Once the
8 / 18
Single Phase Electronic Meter

reverse energy is detected, the symbol will be shown on LCD. The


reverse energy indication will disappear once the reverse energy event is
removed.
Note: The power threshold of reverse energy is 5% of Un*Ib. When reverse
energy exists, and the current power exceeds the power threshold, then this
event will be detected as reverse energy.

10.2 Meter Malfunction


This meter is designed to be able to detect meter’s parameter error and
hardware error. Below is segment displayed on LCD indicating detected error.
Parameter error will be displayed such as E10 or E20 or E30 in decimal.
When parameter or hardware error is detected, error indication will be
displayed on LCD. After error is removed and the meter is repowered, the
indication will disappear automatically.

11. Installation
11.1 General Consideration
Meter should be installed correctly as it could determine meter’s functionality
and lifespan. Please follow the prescribed procedures carefully.
When selecting a suitable position for the meter, the following should be
considered:
ƒ General safety consideration in case of possible electric shock, fire, etc.
ƒ For safety consideration, and avoid damage to the meter, install the meter
where is far away from any water tap.
ƒ Keep the energy meter away from a stove or any house hold compliance
which produces heating exceeds meter’s limited heat withstand.

9 / 18
Single Phase Electronic Meter

11.2 Meter Handling


When handling this meter, please avoid the following actions:
ƒ Avoid drop meter during the installation.
ƒ Make sure meter is installed where is arid and ventilated.
ƒ Do not attempt to open the meter cover.
ƒ Do not add any additional or external voltages to the meter other than what
is specified by the supplier.

11.3 Meter Connection


Please follow the instruction to arrange the wire connection:
a) Use copper cable as the lead-in wire to terminal block.
b) Screw out the wire-fasten screw so that the connection wires can be
inserted into.
c) Remove the plastic cover of the connection wire long enough so that the
wire-fasten screws can contact each connected wire.
d) Screw the wire-fasten screws to fix the connection wires.
e) Pull the connected wires to check whether they are connected tightly.
NOTE: The screws in the terminal block should be screwed down tightly to
avoid burnt because of bad contact or thin lead-in wire.

Terminal wiring diagram is as below.


z Connection Diagram:

10 / 18
Single Phase Electronic Meter

z Meter Dimension

Dimension:
z Width………………………………………124mm
z Height………………………………… 132.7mm
z Depth…………………………………… 48mm
Installation Dimension:
z Width………………………………………110mm
z Height…………………………………… 80mm
z Depth…………………………………… 48mm

11 / 18
Single Phase Electronic Meter

12. Parameters
Electrical
Voltage 230V
Basic current 5A
Maximum current 100A
Starting current 0.004Ib
Frequency 50Hz
Burden in current circuit <0.5VA
Burden in voltage circuit <2W/10VA
Battery life 15years
Data retention >15years
Meter life 15years
Impulse constant 1000imp/kWh

External influence
Protection IP54
Material for meter case ISO 75
compliance
Operating temperature -25℃—55℃
Storage temperature -40℃—70℃
Relative humidity Up to 95%
Operating altitude Up to 3500 m

Electromagnetic compliance
Short time impulse 4kV
Surge voltage 4kV

Electrical insulation
Insulation voltage 6kV
AC voltage 4kV

Accuracy
Class 1.0
Standard Compliance IEC62052-11,
IEC62053-21,
IEC 62056-21.

Mechanical parameters

12 / 18
Single Phase Electronic Meter

Meter type Direct connection HXE12R


Network type 1 Phase 2 Wire
Terminal configuration L:N:N:L
Weight of Meter 0.4 kg (approx)
Dimension 124mm X 133mm X 48mm
Mounting Front projection mounting
Sealing provisions for terminal
Sealing
with one sealing screw
Terminal hole diameter ≥8mm
Terminal cover Short length terminal cover
Meter Cover material UV stable transparent PC
Meter Base material Flame retardant glass fiber
Terminal Cover material Flame retardant glass fiber
Terminal Box material Flame retardant glass fiber

Technical parameters
Measuring range 0—999999.99 kWh
Display mode LCD
Communication port Optical communication
Communication baud rate Standby mode: 300bps,
Communication mode: 4800bps.
Communication Protocals IEC62056-21, Mode C

Initial baud rate for optical communication is 300 bps. After handshake,
baud rate can reach to 4800 bps.
Communication interface:Meter is with either optical communication port.
By optical communication can realize meter firmware recording and meter
reading.
Power-off metering: In power outage mode, meter reading can only be
realized by LCD display.

Communication ID list:
ID Data Description Unit Note
Energy: Read only
901F XXXXXX.XX current import active energy kWh
902F XXXXXX.XX current export active energy kWh

13 / 18
Single Phase Electronic Meter

9200 XXXXXX.XX import active energy of last kWh


month
9201 XXXXXX.XX export active energy of last kWh
month
922E ssmmHHDDMMYY billing date of last month
9240 XXXXXX.XX import active energy of last 2 kWh
months
9241 XXXXXX.XX export active energy of last 2 kWh
months
926E ssmmHHDDMMYY billing date of last 2 months
9280 XXXXXX.XX import active energy of last 3 kWh
months
9281 XXXXXX.XX export active energy of last 3 kWh
months
92AE ssmmHHDDMMYY billing date of last 3 months
92C0 XXXXXX.XX import active energy of last 4 kWh
months
92C1 XXXXXX.XX export active energy of last 4 kWh
months
92EE ssmmHHDDMMYY billing date of last 4 months
9300 XXXXXX.XX import active energy of last 5 kWh
months
9301 XXXXXX.XX export active energy of last 5 kWh
months
932E ssmmHHDDMMYY billing date of last 5 months
9340 XXXXXX.XX import active energy of last 6 kWh
months
9341 XXXXXX.XX export active energy of last 6 kWh
months
936E ssmmHHDDMMYY billing date of last 6 months
9380 XXXXXX.XX import active energy of last 7 kWh
months
9381 XXXXXX.XX export active energy of last 7 kWh
months
93AE ssmmHHDDMMYY billing date of last 7 months
93C0 XXXXXX.XX import active energy of last 8 kWh
months
93C1 XXXXXX.XX export active energy of last 8 kWh
months
93EE ssmmHHDDMMYY billing date of last 8 months
9400 XXXXXX.XX import active energy of last 9 kWh
months
9401 XXXXXX.XX export active energy of last 9 kWh
months
942E ssmmHHDDMMYY billing date of last 9 months
9440 XXXXXX.XX import active energy of last 10 kWh
months
9441 XXXXXX.XX export active energy of last 10 kWh

14 / 18
Single Phase Electronic Meter

months
946E ssmmHHDDMMYY billing date of last 10 months
9480 XXXXXX.XX import active energy of last 11 kWh
months
9481 XXXXXX.XX export active energy of last 11 kWh
months
94AE ssmmHHDDMMYY billing date of last 11 months
94C0 XXXXXX.XX import active energy of last 12 kWh
months
94C1 XXXXXX.XX export active energy of last 12 kWh
months
94EE ssmmHHDDMMYY billing date of last 12 months
Instantaneous Value: read only
C400 XXXX.XX Voltage V
C410 XXXX.XX Current A
C420 XXX.XXX total instantaneous active kW
power consumption
C450 X.XXX overall power factor
C470 XX.XX frequency Hz
Parameters: read & write
C181 YYMMDDWWHHmm Date
ss
C182 NN Demand interval Min
C189 NN auto-scroll time s
C185 DDHH billing time
C01E XXXXXXXX code (only write)
C004 XXXXXXXX Meter number
C005 XXXXXXXXXXXX User identification
C008 XXXXXXXXXXXX Equipment number
C160 NN auto-scroll number
C161 NNNN 1 to 8 of auto-scroll options
C040 energy decimal 80、71、62、53、60 etc.
C310 YYMMDDHHYYMMD 5 DST table
DHH
C311 YYMMDDHHYYMMD 5 DST table
DHH
C312 YYMMDDHHYYMMD 5 DST table
DHH
C313 YYMMDDHHYYMMD 5 DST table
DHH
C250 HHmmNN First time table, 1-8 table
C251 HHmmNN First time table,9-16 table
C254 HHmmNN Second time table.1-8 table
C255 HHmmNN Second time table,9-16 table
C258 HHmmNN Third time table,1-8 table
C259 HHmmNN Third time table.9-16 table
C25C HHmmNN Fourth time table,1-8 table
C25D HHmmNN Fourth time table,9-16 table
15 / 18
Single Phase Electronic Meter

C260 HHmmNN The fifth time table,1-8 table


C261 HHmmNN The fifth time table,9-16 table
C264 HHmmNN The sixth time table,1-8 table
C265 HHmmNN The sixth time table,9-16 table
C268 HHmmNN The seventh time table,1 - 8
table
C269 HHmmNN The seventh time table, 9-16
table
C26C HHmmNN The eighth time table, 1 - 8
table
C26D HHmmNN The eighth time table, 9 - 16
table
C248 NNNNNNNNNNNN Week table meter 1-3
NN
C249 NNNNNNNNNNNN Week table meter 4-6
NN
C24A NNNNNNNNNNNN Week table meter 7-9
NN
C24B NNNNNNNNNNNN Week table meter 10-12
NN
C240 MMDDNN Season 1-6
C241 MMDDNN Season 7-12
C210 YYMMDDNN special holiday date of 01-08
and meter number of day table
C211 YYMMDDNN special holiday date of 09-16
and meter number of day table
C212 YYMMDDNN special holiday date of 17-24
and meter number of day table
C213 YYMMDDNN special holiday date of 25-32
and meter number of day table
C214 YYMMDDNN special holiday date of 33-40
and meter number of day table
C215 YYMMDDNN special holiday date of 41-48
and meter number of day table
C216 YYMMDDNN special holiday date of 49-56
and meter number of day table
C217 YYMMDDNN special holiday date of 57-64
and meter number of day table
C218 YYMMDDNN special holiday date of 65-72
and meter number of day table
C219 YYMMDDNN special holiday date of 73-80
and meter number of day table
C21A YYMMDDNN special holiday date of 81-88
and meter number of day table
C21B YYMMDDNN special holiday date of 89-96
and meter number of day table
C21C YYMMDDNN special holiday date of 97-104
and meter number of day table

16 / 18
Single Phase Electronic Meter

C21D YYMMDDNN special holiday date of 105-112


and meter number of day table
C21E YYMMDDNN special holiday date of 113-120
and meter number of day table
C201 NNNN number of special holiday
C202 NN Number of season
C203 NN Number of week table
C204 NN number of day table
C205 NNNNNNNNNNNN 12 day table
NNNNNNNNNNNN
Event:read only
D310 NNNN…….. Event description, numbers
+(event code + event status +
time)*numbers
D313 NNNN Max event numbers (HEX code)
D314 NNNN Event record index (HEX code,
read or write)
D315 NNNN Recorded event numbers (HEX
code)

17 / 18