ABB AG RTU560 / RTU211

Remote Terminal Unit


Data Sheet
Analogue Output 23AO60

Application
During initialization and operation the board
Analogue control outputs for sequential or carries out a number of tests. If a fault occurs it
closed-loop control, display instruments, is reported to the communication unit. All fault
measurement recorders etc. can be connected conditions impairing the function of the board
by the analogue output board 23AO60. The are displayed as common fault signal with a red
board 23AO60 has two output channels, which light emitting diode (LED). A failure of the board
can be configured to different output is detected by the communication unit.
voltage/current ranges. The output format
unipolar, bipolar or live zero (4 … 20 mA) will
be configured by software parameter.
The following output ranges can be configured
by onboard switches:
• ± 2.5 mA ± 1.25 V DC
• ± 5.0 mA ± 2.50 V DC
• ± 10 mA ± 5.0 V DC
• ± 20 mA ± 10 V DC
• 4 … 20 mA

Characteristics
Each output has a digital to analogue converter
(DAC), which converts the digital value into an
analogue signal. The DAC has a resolution of
11 bit plus sign. A received output value keeps
stored until a new value is received. The output
channels are set to 0 % after power up or reset Fig. 1: Block diagram
of the board. Analogue output board 23AO60
The output channels are potential isolated from
the power supply, but not between the two
channels. The board is equipped with a serial interface to
the RTU211 system bus (Wired OR-Bus). While
The micro-controller on the board processes all using the analogue output board in an RTU560
time-critical tasks of the parameterized (A, C, D) configuration, it is necessary to
processing functions. Moreover it carries out connect one I/O adaptor board 23AD64 to the
the interactive communication with the system first analogue output board 23AO60.
bus. All configuration data and processing
parameters are loaded from the communication
unit via the system bus.

Doc. No.: 1KGT 150 664 V000 1 1


ABB AG
Data Sheet Analogue Output 23AO60 RTU560 / RTU211

Technical Data
In addition to the RTU560/RTU211 general technical data, the following applies:

Output Channels Connection Type


Outputs 2 analogue channels Process Removable Screw
2 binary channels (Strobe) Connector Terminals
Output Ranges ± 2.5 mA ± 1.25 V DC
(analogue) ± 5.0 mA ± 2.50 V DC Immunity Test
± 10 mA ± 5.0 V DC
± 20 mA ± 10 V DC Electrostatic 4 kV Contact
Strobe Output Max. 110 V DC Discharge 8 kV Air
Max. 150 mA Immunity Test
IEC 61000-4-2 Performance criteria A
(level 3)
Resolution
Radiated Radio- 10 V/m
D/A Converter 11 bit plus sign Frequency
Accuracy 0.25 % (DIN 43782) Electromagnetic Performance criteria A
Field Immunity
Current Consumption Test
IEC 61000-4-3
5 Volt 25 mA (level 3)
15 Volt - Immunity to 1 kV
18 Volt (internal) 100 mA Electrical Fast
18 Volt (external) 1.8 W Transient / Burst Performance criteria A
9 … 36 V DC IEC 61000-4-4
24 Volt - (level 3)
Immunity to 10 V
Mechanical Layout Conducted
Disturbances, Performance criteria A
Length 105.0 mm
induced by Radio-
Width 107.5 mm Frequency Fields
Height 20.0 mm IEC 61000-4-6
(level 3)

Environmental conditions
Temperature -20 ... +70 °C
Relative Humidity 5 ... 95 %
ABB AG
(non condensing)
Power Technologies Division
Power Technology Systems
Ordering Information
Kallstadter Str. 1, D-68309 Mannheim 23AO60 R0001 1KGT 014800 R0001
Phone +49 (0) 621 381 – 7592
Fax +49 (0) 621 381 – 7622

www.abb.com/pt
Subject to alterations

2 Doc. No.: 1KGT 150 664 V000 1