U

CIRCUIT DRAWN WITH POWER SUPPLY OFF FOR TYPICAL REMOTE CONTROL
M 2 DETAILS, SEE DOCUMENT
3
3 V

3
PHASE
RWS102
SUPPLY

W 1 TR AN S F OR ME R TAP P IN G OP TION S
T ap Nominal 50/60Hz
3
W
E TYP E 1
W V U W
MOTOR 1
FS1 W 220/230
IN U

SSS MODULE 2
V X 380/400
SK3 V Y 400,415/420
U W X Y Z
SK1
Z 440/460
26 WAY F US E F S 1= 250mA A NTI-S UR G E
U SK2 TYP E 2
0VAC 1 W 346/380
SK15
PS1 X 480/500
120VAC 4
0VDC
Y 240/240
3 4 Z 550/575
24VDC
24VDC 6 F US E F S 1= 250mA A NTI-S UR G E
_ 5 NOMINAL SUPPLY

+
(OUTPUT)
SK14
0VDC 1 REFER TO SHEET 2 FOR NOTES
INTERNAL SUPPLY
FOLO/CPT PCB & OPTION PCB'S IF FITTED
24VDC 2
SK13 THE ACTUATOR MUST BE
PROTECTED USING SUITABLY
26 WAY RATED HIGH SPEED
SEMI-CONDUCTOR FUSES ON THE
INCOMING SUPPLY.
SK3 SK13 SK14 SUGGESTED FUESES :-
6 1 42 IQM10-20:10 Amp FERRAZ G330010
MONITOR RELAY IQM25-35:20 Amp FERRAZ K330013
5 3 43 ALTERNATIVES =
4 2 44 IQM10-20:10 Amp SIBA 50-179-06/10A
TORQUE 3
SK7
IQM25-35:20 Amp SIBA 50-179-06/20A
2
SENSOR 1 1 6
OR EQUIVALENT PROTECTIVE
DEVICE.
SK8 MAKE AT FULLY SHUT S1 8 7
POSITION 10 WAY 2 8
SENSOR MAKE AT FULLY OPEN S2 7 9
SK9 BREAK AT FULLY SHUT
3 10
BATTERY - 4
S3 6 11
4 12
+
1 BREAK AT FULLY OPEN S4 5 13
FS2 (IF FITTED) 100mA SK4
CLOSE 9 33
STOP/ MAINTAIN 10 34
50% SK6 OPEN 8 35
COMMON -VE 1 36
18 WAY
ESD 12 25
STOP
CLOSE
LOCAL OPEN INTERLOCK 13 37
OPEN REMOTE
CLOSE INTERLOCK 14 38
COMMON -VE 5 31
SK1 SK2
SLOT A SLOT B

Iss Date Chkd Revision Details IQM + FOLOMATIC / CPT WITH CLOSED LOOP
1 041223 DW First issue www. .com CONTROL
2 130624 JC1 Folo/CPT numbers corrected
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: PJW Circuit Diagram Number Issue Sheet
BATH, BA1 3JQ ROCHESTER Date : 041223 No
ENGLAND NY 14624, USA
Base WD: 203B0500
Job No : - -
203B0500 2
1
of 2
Tel:01225-733200 Tel:585-247-2304 MI No : - - B1 C1 B2 C2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF

SLOT A
SK1
SLOT A SK3
-VE +VE
1 23 A
2 22
DEMAND +VE 3 26
COMMON -VE 4 27 } ANALOGUE INPUT SIGNAL FOR FOLOMATIC -
CLC FEEDBACK SIGNAL (CONTROL SOURCE 2)
FOLOMATIC /

NO CONNECT 5 (SETPOINT VALUE CONFIGURED WITHIN ACTUATOR MENU)


CPT

MANUAL/AUTO 6 39
COMMON -VE 24VDC 7 41
COMMON -VE 120VAC 8 45
SK6
1 0V
SUPPLY FROM SK14 ON POWER PCB
2 24V
SK8
1
2

MANUAL/AUTO CONNECTIONS ARE NOT SUPPORTED IN CLC MODE

CLOSED LOOP CONTROL ACTUATOR


CLC actuator has 2 modes - Bang Bang and PID. As default the unit will be set to Bang Bang mode.
Refer to PUB002-040 for configuring the modes and setting up Bang Bang or PID.
WARNING
When using CLC modes, ensure the operational parameters are within the actuator's capability and specification.
NOTE: Additional remote control input signals such as hardwired signals can interfere with the CLC process.

NOTES
1.FUSES:
-PS1 is a self-resetting fuse. 3.INDICATION:
-Refer to publication PUB002-039 for approved fuses FS1 and FS2. -For typical position, status and alarm indication see PUB002-041.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%, -“S” contacts are user configurable and are shown in their default
applies for rated torque performance; duty cycle is not guaranteed. setting.
2.REMOTE CONTROL: -Refer to PUB002-040 for functions and configuration instructions.
-For typical remote control circuits refer to: -Monitor Relay indicates actuator availability for remote control (shown
-RWS indicated or PUB002-041. “unavailable”). It can be configured to exclude local/remote selection.
-For DC and AC control, connect –ve/0V to terminal 36. -Refer to PUB002-040 for monitored functions and configuration
-(For negative switch / positive common, refer to RWS indicated). instructions.
-Control signal threshold voltages: -Voltage applied to indication contacts must not exceed 150Vac
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc. -Individual Switch current must not exceed 3.5A inductive, 5A resistive
-Control signal duration to be 100ms minimum. and no more than 8A in total for all 4 contacts.
-Maximum current drawn from remote control signals is:
-8mA at 24Vdc . 4.BATTERY:
-Supply provided on terminals 4 & 5: -Battery maintains local and remote “S” contact indication only.
-Intended for remote control. -Refer to installation manual for approved replacement battery types.
-Max external load 5W at 24Vdc . Circuit Diagram Number Issue Sheet
No
203B0500 2 2
See Sheet 1 for all Revision details/information of 2
IQ3