FLIR Si124-PD™
Industrial Acoustic Imaging Camera
for Partial Discharge Detection
Example of Si124 PD severity assessment
The FLIR Si124-PD is an easy-to-use, stand-alone system for detecting
partial discharge problems in high-voltage electrical systems. This
lightweight, one-handed solution is designed to help engineering
professionals identify issues up to 10 times faster than with traditional
methods. With 124 microphones, the Si124-PD produces a precise
acoustic image that visually displays ultrasonic information, even in loud
environments and at long distances. The acoustic image is overlaid in
real time on a digital camera picture, which allows the user to accurately
pinpoint the source of the sound. Users can then apply the FLIR Severity
Assessment analysis to classify the severity of the issue and provide
guidance on recommended actions to resolve the problem. The Si124-PD
features a plugin that enables users to import acoustic images to FLIR
Thermal Studio suite for offline editing, analysis, and advanced acoustic
and thermography report creation. Field analysis and reporting can also
be done using the FLIR Acoustic Camera Viewer cloud service. Through
a regular maintenance routine, the FLIR Si124-PD can help facilities save
money on repairs and increase asset reliability. www.flir.com/Si124-PD
FIND PARTIAL DISCHARGE IMPROVE RELIABILITY INSPECT EASILY
PROBLEMS FASTER Minimize equipment failures and downtime Locate, analyze, and classify discharge easily
Detect partial discharge and corona up to that result from partial discharge issues with this convenient, smart tool
10 times faster with ultrasonic imaging vs.
traditional methods • Analyze partial discharge pattern and classify • Safely detect problems from distances up to
problems to improve reliability of electrical systems 130 m (430 ft)
• Locate problems precisely, even in loud industrial • Classify partial discharge type including negative • Upload, store, and back up data; create reports;
environments, thanks to high-resolution acoustic corona, positive and negative corona, floating and conduct deep analysis using FLIR Acoustic
images and 124 built-in microphones discharge, and surface or internal discharge Camera Viewer cloud or FLIR Thermal Studio desktop
• Optimize staff time, as minimal training is required to software
• Evaluate frequency to determine the type and
use the Si124-PD severity of discharge, allowing maintenance to • View images in the cloud immediately after capture
• View visual and sound images simultaneously be scheduled thanks to automatic upload feature
• Operate the lightweight camera with one hand for • Determine the level of threat from partial discharge
safety and reduced strain with Severity Assessment software analytics
• Easily review images on the display in bright conditions
For more information contact: Sales@TeledyneFLIR.com
www.teledyneflir.com
or to find your local support number, visit: flir.com/contactsupport
SPECIFICATIONS
FLIR Si124-PD Communication and data storage
Acoustic measurement 124 low-noise MEMS microphones, real-time sound Data transfer • Wi-Fi 2.4 GHz and 5 GHz IEEE 802.11.b/g/n/ac wireless LAN
visualization • USB memory stick
Dynamic range, low limit <-15 dB (frequency-dependent) Camera software update • Automatic over Wi-Fi
• USB via computer
Dynamic range, high limit >120 dB (frequency-dependent)
Still images Yes
Bandwidth 2 kHz to 65 kHz, adjustable range
Video recording Yes, up to 5 minutes
Distance From 0.3 m (1 ft) up to 130 m (430 ft)
Storage, internal 32 GB / 2000 snapshots (typical) SD card, non-removable
Discharge detection Automatic detection 50 / 60 Hz
Storage, external 8 GB / 500 snapshots (typical) USB mass storage,
Discharge classification • Negative corona provided with device
• Positive and negative corona
• Floating discharge Power supply
• Surface or internal discharge
Camera power input Nominal input voltage 12 V
PRPD pattern provided in FLIR Acoustic Camera Viewer or FLIR Max input: 15 V, 2.5 A
Thermal Studio Replaceable battery Li-ion rechargeable battery pack (RRC 2040):
Severity assessment Automatic AI-based severity assessment including 10.8 V, 3.35 Ah, 36.2 Wh
recommended actions in FLIR Acoustic Camera Viewer or FLIR Usage: more than 2 h (depends on ambient conditions)
Thermal Studio. Charge time: 4 to 6 h
Max output: 12.6 V, 4 A
User interface
Battery charger Input: 19 to 26 VDC, 2.8 A
Display Size: 5 in, 800 × 480 pixels Max output: 17.4 VDC, 4.8 A
Color: 24 bit RGB Internal battery Li-ion 6 Wh
(only for camera backup use)
Brightness: 1000 cd/m2 (adjustable) Environmental data
Input device Resistive touchscreen Operating temperature range -10°C to 50°C (14°F to 122°F)
Power On indicator LED (red) Storage temperature range -20°C to 70°C (-4°F to 158°F)
Video image resolution 800 × 480
Physical data
Camera FOV 62° × 49° Camera size 315 mm × 169 mm × 160 mm (12.4 in × 6.6 in × 6.3 in)
Video frame rate 25 fps Camera weight 1.08 kg (2.38 lb)
Acoustic image frame rate 30 fps Battery size 85 mm × 59 mm × 22 mm (3.34 in × 2.31 in × 0.86 in)
Zoom 2x digital zoom Battery weight 0.17 kg (0.37 lb)
Analysis and reporting Total weight 1.25 kg (2.76 lb)
Online FLIR Acoustic Camera Viewer (cloud service) (camera and battery)
Offline FLIR Thermal Studio (desktop software)
Included in the box Specifications are subject to change without notice.
For the most up-to-date specs, go to www.flir.com/Si124-PD
This product is subject to United States export
regulations and may require US authorization
prior to export, reexport, or transfer to non-US
persons or parties. Diversion contrary to US law
is prohibited.
For assistance with confirming the Jurisdiction
& Classification of Teledyne FLIR, LLC products,
please contact exportquestions@flir.com.
©2022 Teledyne FLIR, LLC. All rights reserved.
For more information contact: Sales@TeledyneFLIR.com Revised 06/01/22
or to find your local support number, visit: flir.com/contactsupport Si124-PD_Datasheet-LTR 21-0000
www.teledyneflir.com