Siemens 7696 LDU11
Siemens 7696 LDU11
VALVEGYR®
The LDU11 valve proving system is designed for use with shutoff valves in
connection with gas burners and gas appliances. In the event of inadmissible
leakage, the system prevents the burner from starting up.
The LDU11 system conforms to the requirements of EN 1643 covering automatic
shutoff valves for use with gas burners and gas-fired appliances to EN 161, class A
and pressure switch to EN 1854.
The LDU11 and this Data Sheet are intended for use by OEMs which integrate the
valve proving system in their products.
CC1N7696en
Building Technologies
16.10.2018
Use
The LDU11 is designed for automatic gas valve proving (leakage test) based on the
pressure proving principle. It is for use on gas-fired combustion plant with or without vent
pipe to atmosphere. In the case of plants with no vent pipe where EN standards apply,
the notes given in «Connection examples without vent pipe to atmosphere» must be
observed.
The valve proving test is based on the 2-stage pressure proving principle:
1. The valve on the mains side is tested by evacuating the test space and by monitoring
the atmospheric pressure in it.
2. The valve on the burner side is checked by pressurizing the test space and by
monitoring the gas pressure.
If the pressure increases excessively during the first test phase called «Test1», or
decreases excessively during the second test phase called «Test2», the LDU11. will
inhibit burner startup and initiate lockout. In that case, the lockout reset button will light up
to indicate the fault. Remote indication of the fault is also possible. A program indicator,
which stops whenever a fault occurs, indicates which of the valves is leaking. The LDU11
can be reset either on the unit itself or via an electric remote reset facility.
Warning notes
All activities (mounting, installation and service work, etc.) must be carried out by
qualified staff
Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not observed, there is a
risk of electric shock hazard
Ensure protection against electric shock hazard by providing adequate protection for
the valve proving system’s connection terminals
Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
Press the lockout reset button only manually (applying a force of no more than 10 N)
without using any tools or pointed objects
Do not press the lockout reset button on the unit or the remote reset button (input
terminal 18) for more than 10 seconds, as a longer period would damage the lockout
relay inside the unit
Fall or shock can adversely affect the safety functions. Do not put such units into
operation, even if they do not exhibit any damage
2/22
Ensure that the relevant national safety regulations are complied with
Install switches and fuses in accordance with local valid regulations
Ensure that the maximum permissible current load for the connecting terminals is not
exceeded
The insulation on internal wiring which is subjected to the mains voltage must
withstand the electrical stress occurring during correct use
Installation notes
3/22
Applied directives:
Low-voltage directive 2014/35/EU
Directive for pressure devices 2014/68/EU
Gas Appliances Regulation (EU) (EU) 2016/426
Electromagnetic compatibility EMC (immunity) *) 2014/30/EU
*) The compliance with EMC emission requirements must be checked after the valve monitoring system is
installed in the equipment
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Safety and control devices for gas burners and gas burning DIN EN 1643
appliances - Valve proving systems for automatic shut-off
valves
Automatic electrical controls for household and similar use DIN EN 60730-2-5
Part 2-5:
Particular requirements for automatic electrical burner control
systems
The relevant valid edition of the standards can be found in the declaration of
conformity!
ISO 9001:2015
ISO 14001:2015
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
Type
4/22
The designed lifetime is based on use of the LDU11 according to the manufacturer’s
Data Sheet. After reaching the designed lifetime in terms of the number of burner startup
cycles, or the respective time of usage, the LDU11 is to be replaced by authorized
personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electric and electronic components and must not be disposed of
together with domestic waste. Local and currently valid legislation must be complied with.
Mechanical design
5/22
Others
PTC resistor (AC 230 V).
BPZ:AGK25 AGK25
For load on terminal 4 of LMG2.
6/22
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
7/22
The test space is closed off after evacuation. During the first test phase «Test1», which
then follows, the LDU11 checks with the pressure switch if the atmospheric pressure in
the test space is maintained. If the valve on the mains side is leaking, causing the
pressure to rise above the switching point of the pressure switch, the LDU11 will trigger
an alarm and initiate lockout. The program indicator then stops to indicate «Test1».
If the pressure does not increase because the valve closes correctly, the LDU11
continues its program with the second test phase «Test2».
To this end, the valve on the mains side is opened to maintain the gas pressure while the
test space (t3) is being filled.
During the second test phase – if the valve on the burner side is leaking – this pressure
must not fall below the switching point of the pressure switch. If it does, the LDU11 will
initiate lockout also, thus preventing the burner from starting up.
On successful completion of the second test phase, the LDU11 closes the internal control
loop between terminals 3 and 6 (circuit path: terminal 3 - contact (ar2) - terminals 4 and 5
- contact III - terminal 6). This control loop is normally included in the burner control’s
start control loop.
After the control loop has been closed, the programming mechanism of the LDU11
returns to its start position to switch itself off. During these so-called idle steps, the
positions of the programming mechanism’s control contacts remain unchanged.
8/22
Test1 «Test1» with atmospheric pressure (valve proving test on the mains side)
Filling the test space by opening the valve on the mains side
Test2 «Test2» with gas pressure (valve proving test on the burner side)
► Operating position = start position for the next valve proving test
In the event of lockout, all terminals receiving voltage from the valve proving system
LDU11 will be deenergized, except terminal 13, which is used for lockout indication.
After a reset, the programming mechanism automatically returns to its start position to
immediately program a new valve proving test.
Note!
Do not press the reset button for more than 10 seconds.
Control sequence after A power failure prior to evacuating the test space does not cause the control sequence to
a power failure change.
If a power failure occurs after the evacuation, the valve proving test will not be continued
when power is restored, but the programming mechanism first returns to its start position
and then performs the complete valve proving test.
9/22
Legend Qleck in dm³/h Permissible leakage rate in dm³ per hour or liters per hour
PG in kPa Overpressure in pipe section between the valves to be tested, at
the beginning of the test phase
PW in kPa Overpressure set on pressure switch (normally set to 50 % of
the gas mains pressure)
Patm in kPa Absolute pressure (101,3 kPa normal pressure)
V in dm³ Volume of test space confined by the valves to be tested,
including the space in the valves themselves
Ttest in s Duration of proving time
tTest = 27.5 s
Note!
Select volume of pipe section (V) between the gas valves to be checked and
overpressure (PW) set on pressure switch (DW) such that the maximum permissible
gas leakage rate (QLeck) will not exceed the rate specified in the local regulations.
10/22
L Si
1)
EK2 SK
7696a15/0204
18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
a b a b a b a b
AS ar2 III I V XI hr1
hr2 HR
br1
XIII
IX
ar1 a b a b
15 14
IV Atm. P GP VII
Gas
DW
16 17
VI VIII
b a b a
AR a b
ar3
1) L1
EK1 br2 M
~
SM
BR
13 2 7 9 11
LDU11
AL
N
Legend
1) Do not press lockout reset button (EK) for more than 10 seconds
11/22
A t5
B C
a
I b 7 8
t20
III 5 6
IV
t4 t1
9
a
V b
9 10
a
VI b
VII
a
VIII b
t6
a
IX b
t3 t2 11 15
a
XI b
11 12
XIII a
b
AR
Output terminals
Test1 Test2 controlled by the
control unit or
electrically
Program indication 7696b01e/0601 connected
Legend
12/22
Valve proving test prior to burner startup Valve proving test following immediately the controlled
shutdown
7696a05/0403 7696a06/0703
LGB2.../3.../4.../LMG2... LGB2.../3.../4.../LMG2... 12 3 5 4
12 3 4 5 10
SB / R / W
M 3)
H A2 A1 AGK25
H M A1 A2 L
L
N P GP
N
SB / R / W DW
1 3 6 12 14 19 20 22 21 24 14 15 16 17 3 1 6 8 12 19 23 20 22 21 24
hr2 hr2
ar2 III XI ar2
17 15 hr1 N III I XI hr1 N
2 4 5 16 11 23 LDU11 13 2 4 5 7 11 13
LDU11
GP
DW
C E B AL
C B E AL
LDU LDU
GP DW GP DW
A1 A2
E B A E B
C C
7696s01/0695
Connection examples with vent pipe to atmosphere using burner controls type LFE, LFL or LGK, or the control
unit LEC
Check during the prepurge time (min. 60 seconds) and Check following immediately the controlled shutdown
following immediately the controlled shutdown in plants
2)
with vent pipe to atmosphere. Delay on make of relay Expanding flame burner or interrupted pilot burner
d >2 seconds.
2)
Expanding flame burner or interrupted pilot burner
7696a10/0401 7696a11/0401
LFE1 LFE1
8 9 18 19 4 5°/10°° 2) LEC1 8 9 5°/10°° 2)
LEC1
LFL1...
LFL1... 4 5 18°/17°° 2)
LGK16... 4 5 12 13 14 18°/17°° 2) LGK16...
W A
A
R LP W N
N
R
EK2
d 18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
DW
16 hr2
ar2 III
17 I V XI hr1 N
2
15 14 2 7 9 11 LDU11 13
EK2
DW 18 1 34 5 6 8 10 12 19 23 20 22 21 24
16 GP AL
hr2 C E B
ar2 III
I V XI hr1 N N
17
15 14 2 7 9 11 LDU11 13
GP C E B AL
N
13/22
For other connections, refer to the connection diagram of the relevant burner control.
Check just prior to burner startup Check during the prepurge time (min. 60 seconds)
2) 2)
Expanding flame burner or interrupted pilot burner Expanding flame burner or interrupted pilot burner
7696a07/0401 7696a08/0401
LFE1 LFE1
LEC1 8 9 5°/10°° 2) LEC1 8 9 18 19 4 5°/10°° 2)
LFL1... LFL1...
LGK16... 4 5 18°/17°° 2) LGK16... 4 5 12 13 14 18°/17°° 2)
A A
W W
R N N
R LP
EK2 EK2
18 1 3 4 5 6 8 10 12 19 23 20 22 21 24 18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
DW DW
16 hr2 16 hr2
ar2 III ar2 III
17 I V XI 17 I V XI hr1
hr1 N N
15 14 2 7 9 11 LDU11 13 15 14 2 7 9 11 LDU11 13
GP E C B AL GP E C B AL
N N
DWG Pressure switch for the valve proving test with gas pressure.
This pressure switch must be set to the minimum gas pressure permitted during the proving test.
If this pressure is not reached during the test, lockout will be initiated.
DWA Pressure switch for the gas valve proving test with atmospheric pressure.
This pressure switch must be set to the maximum gas pressure permitted during the proving test with
atmospheric pressure.
If this pressure is exceeded during the test, lockout will be initiated.
Pressure switch (DWG) and pressure switch (DWA) must be overload-proof up to the gas pressure value.
DWG
SKP7...
LDU LDU
DW DW
B A2
B A
C C
7696s02/0709
LDU LDU
DW DW
B A C
C
B ) ( RB A
14/22
LFL1...
LGK16... 4 5 18°/17°° 2) 7 6
W
M2
R N
EK2
DW 18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
16 hr2
ar2 III I V XI
17 hr1 N
15 14 2 7 9 11 LDU11 13
GP E A B AL
DWG Pressure switch for the valve proving test with gas pressure. This pressure switch must be set to the
minimum gas pressure permitted during the proving test. If this pressure is not reached during the test,
lockout will be initiated.
DWA Pressure switch for the gas valve proving test with atmospheric pressure. This pressure switch must be set
to the maximum gas pressure permitted during the proving test with atmospheric pressure. If this pressure
is exceeded during the test, lockout will be initiated.
Pressure switch (DWG) and pressure switch (DWA) must be overload-proof up to the gas pressure value.
DWG
GP DW GP DW
A1 A2
LDU LDU
GP DW GP DW
) ( RB
Air pressure (PL) for the SKP7 must be sufficiently high to open the SKP7 although the burner’s air damper is closed.
Otherwise, the LDU11 will initiate lockout when performing «Test1».
15/22
For other connections, refer to the connection diagram of the relevant burner control.
Check prior to burner startup Check following immediately the controlled shutdown
7696a13/0403 7696a14/0703
LGB2.../3.../4.../LMG2... 12 3 4 5 10 LGB2.../3.../4.../LMG2... 12 3 5 4
SB / R / W
L
H M A2 M A2 AGK25 3)
N GP P N N N
SB / R / W H
L
1 3 4 5 6 10 12 14 19 20 22 21 24 1 3 4 5 6 8 10 12 19 23 20 22 21 24
DW DW
hr2 16 hr2
16 ar2 III
ar2 III XI I V XI
17 V 17 hr1 N
hr1 N
11 23 13 15 14 2 7 9 11 13
15 2 9 LDU11 LDU11
GP
E A1 B AL
A1 B E AL
N
N
LDU LDU
7696s04/0695
GP DW GP DW
A1 A2
E B A E B
16/22
Check just prior to burner startup Check during the prepurge time (min. 60 seconds)
2) 2)
Expanding flame burner or interrupted pilot burner Expanding flame burner or interrupted pilot burner
7696a24/0401 7696a25/0401
LFE1 LFE1
LEC1 8 9 5°/10°° 2) LEC1 8 9 18 19 4 5°/10°° 2)
LFL1... LFL1...
LGK16... 4 5 18°/17°° 2) LGK16... 4 5 12 13 14 18°/17°°2)
W W
R LP
R
EK2 EK2
DW 18 1 34 5 6 8 10 12 19 23 20 22 21 24 18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
DW
16 hr2 16 hr2
ar2 III ar2 III
17 I V XI hr1 17 I V XI
N hr1 N
15 14 2 7 9 11 LDU11 13 15 14 2 7 9 11 LDU11 13
GP E A B AL GP E A B AL
N N
DWG Pressure switch for the valve proving test with gas pressure. This pressure switch must be set to the
minimum gas pressure permitted during the proving test. If this pressure is not reached during the test,
lockout will be initiated.
DWA Pressure switch for the gas valve proving test with atmospheric pressure. This pressure switch must be set
to the maximum gas pressure permitted during the proving test with atmospheric pressure. If this pressure
is exceeded during the test, lockout will be initiated.
Pressure switch (DWG) and pressure switch (DWA) must be overload-proof up to the gas pressure value.
DWG
SKP7...
Air pressure (PL) for the SKP7 must be sufficiently high to open the SKP7 although the burner’s air damper is closed.
Otherwise, the LDU11 will initiate lockout when performing «Test1».
17/22
For other connections, refer to the connection diagram of the relevant burner control
Check just prior to burner startup Check during the prepurge time (min. 60 seconds)
7696a26/0401 7696a27/0401
LFE1 LFE1
LEC1 8 9 18 19 4 5° 3/17 8 9 18 19 4 3/17
LEC1 5°
LFL1...
LGK16... 4 5 12 13 14 18° 6/7 LFL1...
LGK16... 4 5 12 13 14 18° 6/7
T
W
N M W
R LP LP
R N
EK2 M
8 EK2
DW 18 3 4 5 6 10 12 19 23 20 22 21 24
16 1 hr2 DW 18 1 3 4 5 6 8 10 12 19 23 20 22 21 24
ar2
17 III I V XI 16 hr2
hr1 N III
17 ar2 I V XI
15 14 2 7 9 11 13 hr1 N
LDU11
15 14 2 7 9 11 LDU11 13
GP E A B AL
N GP E A B AL
DWG Pressure switch for the valve proving test with gas pressure. This pressure switch must be set to the
minimum gas pressure permitted during the proving test. If this pressure is not reached during the test,
lockout will be initiated.
DWA Pressure switch for the gas valve proving test with atmospheric pressure. This pressure switch must be set
to the maximum gas pressure permitted during the proving test with atmospheric pressure. If this pressure
is exceeded during the test, lockout will be initiated.
Pressure switch (DWG) and pressure switch (DWA) must be overload-proof up to the gas pressure level.
DWG
SKP7...
GP DW
E B A
18/22
LME21.xxxC...
NT LME22.xxxC... RESET
K1
K2/1 K2/2 K3 K4 K5
Gpmin
LP
R/W
1)
T
AL M Z A2 M EK2
STB
1)
7101a28e/0210
DW
E A1 B
Gas Atmospheric
LDU LDU
GP GP
Valve proving is started each time the system is switched on, with connection of
terminal 3, after controller ON or after lockout
If the LDU11 initiates lockout, valve proving can take up to 160 seconds. Therefore,
the maximum permissible response time of the air pressure switch is 180 seconds
With the LDU11…, faults during valve proving lead to lockout and, with the
LME21.xxxCx / LME22.xxxCx , to lockout due to air pressure switch timeout (blink
code 03)
Note!
A faulty air pressure switch (switch does not make) leads to lockout (blink code 03)
on completion of the pressure switch response time of 180 seconds and can be
distinguished from lockout due to faulty valve proving only because the LDU11 did
not go to lockout
The fan motor can be connected either to terminal 3 in connection with a link
between terminals 6 and 24 of the LDU11 (motor active during valve proving) or to
terminal 6 of the LDU11 (motor active on completion of successful valve proving)
19/22
LME21.xxxC...
NT LME22.xxxC... RESET
K1
K2/1 K2/2 K3 K4 K5
Gpmin
LP
R/W
1)
T
AL M Z A1 A2 M EK2
STB
1)
7101a29e/0210
DW
E C B
Gas Atmospheric
GP GP
20/22
t7 Interval between start command and power at terminal 7 (start delay for
«M2»)
t10 Interval from start to the beginning of the air pressure check, excluding
running time of air damper
t16 Interval until OPEN command for the air damper is given
21/22
Dimensions in mm
LDU11
1,5
108,5
123
Plug-in base AGM11 / AGM11.1
7696m04/0305
27,5 27,5
37
103
7,5
103