0% found this document useful (0 votes)
32 views3 pages

EPM461S Sheet 3 Fall 2024

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views3 pages

EPM461S Sheet 3 Fall 2024

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Ain Shams University

Faculty of Engineering
Specialized Programs - Electrical Power and Machines Program

Fall 2024 Course Code: EPM 461s Protection Engineering


Sheet 3

1-The primary conductor in Figure 1 is one phase of a three-phase transmission line operating at
345 kV, 600 MVA, 0.95 power factor lagging. The CT ratio is 1200: 5 and the VT ratio is 3000:
1. Determine the CT secondary current I’ and the VT secondary voltage V’. Assume zero CT error.

Figure 1 VT and CT Schematic

2-A CO-8 relay (Inverse Characteristics) with a current tap setting of 5 amperes is used with the
100: 5 CT in Prb.1. The CT secondary current I’ is the input to the relay operating coil. Excitation
curve of CT in shown in Figure 2.

Figure 2 Excitation curve for a multi-ratio bushing CT


The CO-8 (Inverse characteristic) relay burden is shown in the following table for various relay
input currents.
Table 1 CO-8 Relay Burden

-For a 100:5 CT ratio, compute the primary current and CT error for
(a) I’=5A and ZB=0.5 Ω
(b) I’=8A and ZB=0.8 Ω
(c) I’=10A and ZB=1 Ω
(d) I’=13A and ZB=1.3 Ω
(e) I’=15A and ZB=1.5 Ω
-Plot I’ versus I for the above five values of I’.
-For reliable relay operation, the fault-to-pickup current ratio with minimum fault current should
be greater than two. Determine the minimum fault current for application of this CT and relay with
5-A tap setting.

3- An overcurrent relay set to operate at 10 A is connected to the CT in Figure 2 with a 200: 5 CT


ratio. Determine the minimum primary fault current that the relay will detect if the burden ZB is
(a) 1.0 Ω, (b) 4.0 Ω, and (c) 5.0 Ω.

4- A CT with an excitation curve given in Figure 3 has a rated current ratio of 500: 5 A and a
secondary leakage impedance of 0.1 + j0.5 Ω. Calculate the CT secondary output current and the
CT error for the following cases:
(a) The impedance of the terminating device is 4.9 + j0.5 Ω and the primary CT load current is
400 A.
(b) The impedance of the terminating device is 4.9 + j0.5 Ω and the primary CT fault current is
1200 A.
(c) The impedance of the terminating device is 14.9 +j1.5 Ω and the primary CT load current is
400 A.
(d) The impedance of the terminating device is 14.9 + j1.5 Ω and the primary CT fault current is
1200 A.

Figure 3 Problem 4
Note: The non-linear characteristic shown in Figure 3 can be represented by the Frohlich equation:
𝐴𝐼𝑒
𝐸′ =
𝐵 + 𝐼𝑒
Such that A and B are considered as constants.

5- The CT of Problem 4 is utilized in conjunction with a current-sensitive device that will operate
at current levels of 8 A or above. Check whether the device will detect the 1200-A fault current
for cases (b) and (d) in Problem 4.

You might also like