FINAL BRANCH CIRCUIT PANEL BOARD

PROJECT: E16104-0400S Cluster ****


PANEL REF : **** FED FROM : **** INCOMING FEEDER SIZE : ****

VOLTAGE & FREQ. : 220/380V 50Hz UPSTREAM S.C. RATING (IC) : **** INCOMING FEEDER LENGTH : ****

S.C. RATING (IC) : **** UPSTREAM C.B : **** INCOMING FEEDER V.D% : ****

PANEL IP RATING : **** LOCATION : **** MOUNTING METHOD / TYPE : ****

No. of WAYS : MCB (*** WAYS) MAIN INCOMER : *** FEEDER ENTRY METHOD / LOCATION : ****

LOCATION : ***** R YB FEEDER REF / TAG : *****

WIRE WIRE WIRE WIRE


LOAD WIRE Accumulative TRIP TRIP WIRE Accumulative LOAD
LOAD DESCRIPTION Notes CKT SIZE LENGTH R Y B R Y B SIZE LENGTH CKT Notes LOAD DESCRIPTION
TYPE TYPE VD% (A) (A) TYPE VD% TYPE
(mm2) (mtrs) (mm2) (mtrs)
MTR. 1 #N/A #N/A 22 MSC.
MTR. 2 #N/A CU/PVC #N/A 23 MSC.
MTR. 3 #N/A #N/A 24 MSC.
MTR. 4 #N/A #N/A 25 MSC.
MTR. 5 #N/A #N/A 26 MSC.
MTR. 6 #N/A #N/A 27 MSC.
S.O 7 #N/A #N/A 28 MSC.
S.O 8 #N/A #N/A 29 MSC.
S.O 9 #N/A #N/A 30 MSC.
S.O 10 #N/A #N/A 31 MSC.
S.O 11 #N/A #N/A 32 MSC.
S.O 12 #N/A #N/A 33 MSC.
S.O 13 34 MSC.
S.O 14 #N/A #N/A 35 MSC.
S.O 15 36 MSC.
S.O 16 37 MSC.
S.O 17 #N/A #N/A 38 MSC.
S.O 18 39 MSC.
S.O 19 #N/A #N/A 40 MSC.
S.O 20 #N/A #N/A 41 MSC.
S.O 21 #N/A #N/A 42 MSC.
SUB-TOTAL(AMPS) 0.0 0.0 0.0 0.0 0.0 0.0 AMP.

TOTAL(AMPS) 0.0 0.0 0.0

CONN.kVA DEM.FACTOR DEM.kVA TOTAL


LTG. (e.g. Lighting Fixyures) 0.00 100% 0.0 kVA
S.O (e.g. Sockets) 0.00 50% 0 CONN. KVA: 0.00 kVA
P.S.O (e.g. Power Socket) 0.00 80% 0
IT/AV (e.g. IT/ Audio Visual Rack) 0.00 80% 0
Rack
MTR. (e.g. AC/ S.U/ FCU…etc.) 0.00 80% 0 DEMAND KVA: 0.00 kVA
MSC. (e.g. Hand Dryer, EWH..etc.) 0.00 60% 0 DEMAND AMP (A): 0.0 A
FINAL BRANCH CIRCUIT PANEL BOARD
PROJECT: E16104-0400S Cluster 19B&20B
PANEL REF : LP-L2A-G FED FROM : MDB-L2M (SEC.1) INCOMING FEEDER SIZE : (4×10) CU/XLPE/PVC+ (1X10) CU/PVC (E)
VOLTAGE & FREQ. : 220/380V 50Hz UPSTREAM S.C. RATING (IC) : 25KA INCOMING FEEDER LENGTH : 5M
S.C. RATING (IC) : 10KA UPSTREAM C.B :40 A MCCB FROM TAB OFF OF BUSWAY "1250 A" INCOMING FEEDER V.D% : 1.91
PANEL IP RATING : 31 LOCATION : Elec. Room - Z1 - GROUND FLOOR MOUNTING METHOD / TYPE : WALL MOUNTED
No. of WAYS : MCB (30 WAYS) FEEDER ENTRY METHOD / LOCATION : TOP
LOCATION : Elec. Room - Z1 - GROUND FLOOR R Y B ( MCS.40 A ) FEEDER REF / TAG : FLPL2AG

WIRE WIRE WIRE WIRE


Accumulative VD TRIP TRIP Accumulative VD
LOAD TYPE LOAD DESCRIPTION Notes CKT SIZE WIRE TYPE LENGTH R Y B R Y B SIZE WIRE TYPE LENGTH CKT Notes LOAD DESCRIPTION LOAD TYPE
% (A) (A) %
(mm2) (mtrs) (mm2) (mtrs)

CONTROL BY BMS FOUR LIGHTING FIXTURES TYPE(E) AT


SPARE #N/A 16 0.72 16 3×3 CU/PVC 65 2.06 28 LTG.
CONTACTOR STATIONERY (GR-141)

TWELVE LIGHTING FIXTURES TYPE(E) ONE LIGHTING FIXTURES TYPE(C) AT


LTG. 20 3×3 CU/PVC 80 2.48 16 2.16 0.2 16 3×3 CU/PVC 45 1.97 29 LTG.
MALE PRAYER ROOM (GR-142) STORAGE (GR-151)

NINE LIGHTING FIXTURES TYPE(FC) AT 17 LIGHTING FIXTURES TYPE(E) AT


LTG. 21 3×3 CU/PVC 50 2.01 16 0.63 3.06 16 3×3 CU/PVC 85 2.77 30 LTG.
FEMALES TOILET (GR-025) PREPARATION AREA (GR-154)

NINE LIGHTING FIXTURES TYPE(FC) AT SIX LIGHTING FIXTURES TYPE(A) AT


LTG. 22 3×3 CU/PVC 55 2.02 16 0.63 1.2 16 3×3 CU/PVC 90 2.27 31 LTG.
MALES TOILET (GR-037) AHU ROOM (GR-042)

SEVEN LIGHTING FIXTURES TYPE(E) AT CONTROL BY BMS


LTG. 23 3×3 CU/PVC 50 2.12 16 1.26 16 #N/A 32 SPARE LTG.
FEMALE PRAYER ROOM (GR-149) CONTACTOR

TWELVE LIGHTING FIXTURES TYPE(FA)


LTG. 24 3×3 CU/PVC 60 2.08 16 0.84 16 #N/A 33 SPARE LTG.
AT ABLUTION (GR-145)

FOUR LIGHTING FIXTURES TYPE(E) AT


LTG. 25 3×3 CU/PVC 85 2.11 16 0.72 16 #N/A 34 SPARE LTG.
POLICE REQUIREMENTS ROOM (GR-155)

SEVEN LIGHTING FIXTURES TYPE(C) AT


LTG. 26 3×3 CU/PVC 120 2.46 16 1.4
ACUD OFFICE (GR-045)

FIVE LIGHTING FIXTURES TYPE(C) AT


LTG. 27 3×3 CU/PVC 55 2.09 16 1.00
ARCHIVE (GR-150)

SUB-TOTAL(AMPS) 1.4 4.8 2.5 1.9 0.2 3.1 AMP.

Split bus 3P, MCB


(connected to (32A)
main bus)

K 3Pole, Contactor (32A)

Contactor Controlled by BMS

FIVE LIGHTING FIXTURES TYPE(C) AT


LTG. 1 3×3 CU/PVC 75 2.2 16 1 16 #N/A SPARE
CORRIDOR (GR-153)

THREE LIGHTING FIXTURES TYPE(C) AT


LTG. 2 3×3 CU/PVC 110 2.1 16 0.60
CORRIDOR (GR-137)

TWO LIGHTING FIXTURES TYPE(C) AT


LTG. 3 3×3 CU/PVC 65 2.0 16 0.4
CORRIDOR (GR-139)

SIX LIGHTING FIXTURES TYPE(C) AT


LTG. 4 3×3 CU/PVC 55 2.1 16 1.2
CORRIDOR (GR-144)

TWO LIGHTING FIXTURES TYPE(A) AT


LTG. 5 3×3 CU/PVC 65 2.0 16 0.4
ESCAPE CORRIDOR (GR-033)

SPARE #N/A 16

Split bus 3P, MCB


(connected to (32A)
main bus)

K 3Pole, Contactor (32A)

Contactor Controlled by BMS

14 LIGHTING FIXTURES TYPE(FA) AT


SPARE #N/A 16 0.98 16 3×3 CU/PVC 58 2.1 10 LTG.
ENTRANCE HALL (GR-028)

SPARE #N/A 16

TWELVE LIGHTING FIXTURES TYPE(FA)


LTG. 6 3×3 CU/PVC 50 2.0 16 0.84
AT ENTRANCE HALL (GR-028)

EIGHT LIGHTING FIXTURES TYPE(FA) AT


LTG. 7 3×3 CU/PVC 50 2.0 16 0.56
CORRIDOR (GR-153)

SIX LIGHTING FIXTURES TYPE(FF) AT


LTG. 8 3×3 CU/PVC 25 1.9 16 0.42
ENTRANCE HALL (GR-028)

STRIPE LIGHT 4M AT ENTRANCE HALL


LTG. 9 3×3 CU/PVC 30 1.9 16 0.09
(GR-028)

Split bus 3P, MCB


(connected to (32A)
main bus)

K 3Pole, Contactor (32A)

Contactor Controlled by BMS

STRIPE LIGHT 4M AT ENTRANCE HALL


SPARE #N/A 16 0.09 16 3×3 CU/PVC 75 1.9 13 LTG.
(GR-039)

NINE LIGHTING FIXTURES TYPE(FA) AT TWELVE LIGHTING FIXTURES TYPE(FA) AT


LTG. 11 3×3 CU/PVC 100 2.1 16 0.63 0.84 16 3×3 CU/PVC 80 2.1 14 LTG.
ENTRANCE HALL (GR-0.39) ENTRANCE HALL (GR-039)

SIX LIGHTING FIXTURES TYPE(FF) AT


LTG. 12 3×3 CU/PVC 80 2.0 16 0.42
ENTRANCE HALL (GR-039)

Split bus 3P, MCB


(connected to (32A)
main bus)

K 3Pole, Contactor (32A)

Contactor Controlled by BMS

20 LIGHTING FIXTURES TYPE(FA) AT


SPARE #N/A 16 1.4 16 3×3 CU/PVC 100 2.4 19 NOTE(2) LTG.
ENTRANCE HALL (GR-001)

SPARE #N/A 16

SIX LIGHTING FIXTURES TYPE(FF) AT


LTG. 15 3×3 CU/PVC 85 2.0 16 0.42
LOUNGE (GR-156)

STRIPE LIGHT 4M AT ENTRANCE HALL


LTG. 16 3×3 CU/PVC 80 1.9 16 0.09
(GR-001)

EIGHT LIGHTING FIXTURES TYPE(FB)


LTG. 17 3×3 CU/PVC 110 2.2 16 0.8
AT ENTRANCE HALL (GR-001)

SIX LIGHTING FIXTURES TYPE(FB) AT


LTG. 18 3×3 CU/PVC 90 2.1 16 0.6
LOUNGE (GR-156)

AMP.
SUB-TOTAL(AMPS) 2.9 2.8 2.8 2.5 0.8 0.0

TOTAL(AMPS) 8.6 8.7 8.3

TOTAL DEMAND(AMPS) 8.6 8.7 8.3

PHASE BALANCE
98.6 100.0 95.3
PERCENTAGE %

CONN.kVA DEM.FACTOR DEM.kVA TOTAL


LTG. (e.g. Lighting Fixyures) 5.63 100% 5.6 kVA
S.O (e.g. Sockets) 0.00 50% 0 CONN. KVA: 5.63 kVA
P.S.O (e.g. Power Socket) 0.00 80% 0
IT/AV Rack (e.g. IT/ Audio Visual Rack) 0.00 80% 0
MTR. (e.g. AC/ S.U/ FCU…etc.) 0.00 80% 0 DEMAND KVA: 5.63 kVA
MSC. (e.g. Hand Dryer, EWH..etc.) 0.00 60% 0 DEMAND AMP (A): 8.5 A
BS7671 CU/PVC
mV/A/m BS 7671
wire Ohm/km ohm/m wire mV/A/M

3×1.5 1.5 29
3×2.5 2.5 18
3×3 3 14.5
3×4 4 11
3×6 6 7.3
3×10 10 4.4
3×16 16 2.8

cable Ohm/km ohm/m cable mV/A/M


5×4 4 9.5
5×6 6 6.4
5×10 10 3.8
5×16 16 2.4

Wire type
CU/PVC LTG.
CU/LS0H S.O
CU/PVC/PVC P.S.O
CU/XLPE/PVC IT/AV Rack
CU/MICA/LS0H MTR.
MSC.
Trip (A)
16
20
25
32
40
63