401 non-addressable flame detector
EN 54-10, Ultra-violet flame detector for system applications
Description
The 401 non-addressable ultra-violet flame detectors are suitable
for connection to 2-wire and 4-wire non-addressable fire detection
control and indicating equipment, or to addressable fire detection
control and indicating equipment that can accept non-addressable
type detectors1.
The 401 UV flame detectors are suited to applications where
flames rapidly develop due to the nature of the combustible
materials, such as where petrochemical products are used or
stored.
The 401 UV flame detector provides fire detection and alarm
system designers with a Standards-compliant detector for life
safety and property protection applications.
Features
High sensitivity UVtron sensor tube technology
Surface-mount device (SMD) circuit board design uses digital 401 non-addressable flame detector
ICs for stable and reliable operation
Solar blind, with an electronic filter to eliminate unwanted
alarms from naturally occurring phenomena
High immunity to electrical noise and RF interference
Fast response time
Wide field of view
Polarity insensitive
2-wire or 4-wire system operation
DC 12 V or DC 24 V operation
Remote LED output available on some models
N/O alarm relay output available on some models
Auto-reset available on some models
Connectable to zone monitor for use with addressable
control and indicating equipment
Easy installation. No programming required
Low maintenance
Compliance
401 flame detectors have the following compliance.
EN 54-10 a, b CE
401-001
401-002
401-003
401-004
a EN 54-10 Flame detectors – point detectors
b Third-party conformance assessment has not been undertaken.
Accessories
The following accessories are compatible with 401 flame
detectors.
Description Part number Datasheet
5-terminal 102 mm low profile base CN3023 31-0035
9-terminal 102 mm low profile base CN3043 31-0037
Remote indicator a 681-001 31-0034
Detector monitor module 620-001 31-0027
a Requires 9-terminal base.
1 May be used with the 620-001 detector monitor module.
www.numens.com 1 31-0013-r04_2017-03
Field of View
Note: The response time depends on the flame size and the distance from the detector. The UV flame detector is a line-of-sight device, and cannot see past
obstructions such as storage racks.
Specifications
401-001
401-003 401-004
401-002
Operating voltage DC (10.8 ~ 33) V DC (10.8 ~ 26.4) V
Start-up current ≤ 100 µA
Start-up time ≤ 30 s
Quiescent current 30 µA
Quiescent condition indicator Dual flashing red LED
Alarm current (max) 50 mA 30 mA 40 mA
Sampling time (4 ~ 6) s
Alarm condition indicator Dual red LEDs
Reset voltage ≤1V
Reset time ≤5s
Field of view 120° cone
UV sensitivity (185 ~ 260) nm
Alarm response (typical) 30 mm gas flame at 4 m within 10 s
Alarm relay — SPST. N/O. 1.0 A @ DC 30 V / 0.5 A @ AC 125 V
Auto reset time — < 30 s
Operating temperature (-10 ~ +55)°C
Operating humidity (0 ~ 95)% RH, non-condensing
Storage temperature (-25 ~ +80)°C
Storage humidity (0 ~ 98)% RH, non-condensing
Dimensions (excluding contacts) Φ 102 mm × 45 mm
Ingress protection rating IP-42
Ordering Information
2-Wire 4-Wire Remote Indicator a Relay Output Auto Reset
401-001 — — — —
401-002 — — —
401-003 — — —
401-004 — —
a Requires 9-terminal base if remote indicator is installed.
View the complete range of products at www.numens.com
2 31-0013-r04_2017-03