Chapter 7: Symmetrical Faults
Chapter 7:
Symmetrical
Faults
Dr. Mohamad Arnaout
Chapter 7: Symmetrical Faults
Course Content
⚫ Main purpose from this course is:
⚫ Power System Analysis and Faults Calculation
⚫ Transient Operations
⚫ Control in Power Systems
⚫ Content:
⚫ Ch. 7: Symmetrical Faults
⚫ Ch. 8: Symmetrical Components
⚫ Ch. 9: Unsymmetrical Faults
⚫ Ch. 11: Transient Stability
⚫ Ch. 12: Power Systems Control
1
Chapter 7: Symmetrical Faults
Introduction
⚫ Fault Analysis
⚫ The cause of electric power system faults is insulation
breakdown
⚫ This breakdown can be due to a variety of different factors
⚫ Fault currents cause equipment damage due to both thermal
and mechanical processes
⚫ Goal of fault analysis is to determine the magnitudes of the
currents present during the fault
2
Chapter 7: Symmetrical Faults
Introduction
⚫ Fault Types
⚫ There are two main types of faults
– symmetric faults: system remains balanced; these
faults are relatively rare, but are the easiest to analyze
so we’ll consider them first.
– unsymmetrical faults: system is no longer balanced;
very common, but more difficult to analyze
⚫ The most common type of fault on a three phase system
by far is the single line-to-ground (SLG), followed by the
line-to-line faults (LL), double line-to-ground (DLG)
faults, and balanced three phase faults
3
Chapter 7: Symmetrical Faults
Introduction
⚫ Lightning Strike Event
⚫ Lighting hits line, setting up an ionized path to ground
⚫ Conduction path is maintained by ionized air after
lightning stroke energy has dissipated
⚫ Within one to two cycles (16 ms) relays at both ends of
line detect high currents
⚫ Circuit breakers open to de-energize line in an additional
one to two cycles
⚫ Circuit breakers may reclose after several seconds, trying
to restore faulted line to service
4
Chapter 7: Symmetrical Faults
Series R–L Circuit Transients
⚫ To understand fault analysis we need to review the
behavior of an RL circuit
v(t ) = 2 V cos(t + )
5
Chapter 7: Symmetrical Faults
Series R–L Circuit Transients
6
Chapter 7: Symmetrical Faults
Series R–L Circuit Transients
7
Chapter 7: Symmetrical Faults
Series R–L Circuit Transients
8
Chapter 7: Symmetrical Faults
Three Phase Short Circuits
⚫ During a fault the only devices that can contribute fault
current are those with energy storage
⚫ Thus the models of generators (and other rotating
machines) are very important since they contribute the
bulk of the fault current.
⚫ Generators can be approximated as a constant voltage
behind a time-varying reactance
'
Ea
9
Chapter 7: Symmetrical Faults
Three Phase Short Circuits
The time varying reactance is typically approximated
using three different values, each valid for a different
time period:
X"d = direct-axis subtransient reactance
X 'd = direct-axis transient reactance
Xd = direct-axis synchronous reactance
T’’d T’d
X’’d < X’d < Xd 10
Chapter 7: Symmetrical Faults
Generator Modeling, cont’d
For a balanced three-phase fault on the generator
terminal the ac fault current is (see page 245)
1 1 1 −
t
Td'
+ ' − e +
X
' d Xd Xd
iac (t ) = 2Ea
− t "
sin( t + )
1 1 Td
−
X " X ' e
d d
where
Td" = direct-axis subtransient time constant ( 0.035sec)
Td' = direct-axis transient time constant ( 1sec)
11
Chapter 7: Symmetrical Faults
Generator Modeling, cont’d
The phasor current is then
1 1 1 − t
Td'
+ ' − e +
X
' d Xd Xd
I ac = Ea
− t "
1 1 Td
X " − X ' e
d d
The maximum DC offset is
2 Ea' − t
TA
I DC (t ) = "
e
Xd
where TA is the armature time constant ( 0.2 seconds)
12
Chapter 7: Symmetrical Faults
Generator Short Circuit Currents
13
Chapter 7: Symmetrical Faults
Generator Short Circuit Example
⚫ A 500 MVA, 20 kV, 3 is operated with an internal
voltage of 1.05 pu. Assume a solid 3 fault occurs on the
generator's terminal and that the circuit breaker operates
after three cycles. Determine the fault current. Assume
X d" = 0.15, X d' = 0.24, X d = 1.1 (all per unit)
Td" = 0.035 seconds, Td' = 2.0 seconds
TA = 0.2 seconds
14
Chapter 7: Symmetrical Faults
Generator S.C. Example, cont’d
Substituting in the values
1 1 1 − t 2.0
1.1 + 0.24 − 1.1 e +
I ac (t ) = 1.05
1 − 1 e − t 0.035
0.15 0.24
I ac (0) = 1.05 = 7 p.u.
0.15
500 106
I base = 3
= 14,433 A I ac (0) = 101,000 A
3 20 10
t
I DC (0) = 101 kA 2 e 0.2 = 143 k A I RMS (0) = 175 kA
15
Chapter 7: Symmetrical Faults
Generator S.C. Example, cont’d
Evaluating at t = 0.05 seconds for breaker opening
1 1 1 − 0.05 2.0
+ −
1.1 0.24 1.1 e +
I ac (0.05) = 1.05
−
1 − 1 e 0.05
0.035
0.15 0.24
I ac (0.05) = 70.8 kA
−0.05
I DC (0.05) = 143 e 0.2 kA = 111 k A
I RMS (0.05) = 70.82 + 1112 = 132 kA
16
Chapter 7: Symmetrical Faults
Power System Three Phase Short
Circuits
⚫ Network Fault Analysis Simplifications
To simplify analysis of fault currents in networks we'll make several
simplifications:
1. Transmission lines are represented by their series reactance
2. Transformers are represented by their leakage reactances
3. Synchronous machines are modeled as a constant voltage
behind direct-axis subtransient reactance
4. Induction motors are ignored or treated as synchronous
machines
5. Other (non spinning) loads are ignored
17
Chapter 7: Symmetrical Faults
Power System Three Phase Short
Circuits
Network Fault Example:
For the following network assume a fault on the terminal of
the generator; all data is per unit except for the transmission
line reactance. Generator has 1.05 terminal voltage &
supplies 100 MVA, with 0.95 lag PF
18
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Faulted network per unit diagram
19
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Fault Analysis Solution Techniques
⚫ Circuit models used during the fault allow the network to
be represented as a linear circuit
⚫ There are two main methods for solving for fault
currents:
1. Direct method: Use prefault conditions to solve for
the internal machine voltages; then apply fault and
solve directly
2. Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition
– first voltage just represents the prefault operating
point
– second system only has a single voltage source
20
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Superposition Approach
21
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Superposition Approach
Fault is represented by two equal and opposite voltage
sources, each with a magnitude equal to the pre-fault voltage
Since this is now a linear network, the faulted voltages and
currents are just the sum of the pre-fault conditions [the (1)
component] and the conditions with just a single voltage source
at the fault location [the (2) component]. Pre-fault (1)
component is equal to the pre-fault power flow solution
Obvious the
pre-fault
“fault current”
is zero! 22
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Superposition Approach
Fault (1) component due to a single voltage source
at the fault location, with a magnitude equal to the
negative of the pre-fault voltage at the fault location.
(1) (2) (1) (2)
Ig = I + Ig Im = Im + Im
g
I f = I (1)
f + I (2)
f = 0 + I (2)
f
23
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Example
24
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Example
25
Chapter 7: Symmetrical Faults
Power System Three Phase Short Circuits
Example
26
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
The superposition approach can be easily extended
to larger systems. Using the Ybus we have
Ybus V = I
For the second (2) system there is only one voltage
source so I is all zeros except at the fault location
0
However to use this
I = − I f
approach we need to
0 first determine If
27
Chapter 7: Symmetrical Faults
Determination of Fault Current
Define the bus impedance matrix Z bus as
−1
Z bus = Ybus V = Z busI
V1
(2)
(2)
Z11 Z1n 0 V2
Then − I =
f
Z n1 Z nn 0 V (2)
n −1
(2)
Vn
(1)
For a fault a bus i we get -If Zii = −V f = −Vi
28
Chapter 7: Symmetrical Faults
Determination of Fault Current, cont’d
29
Chapter 7: Symmetrical Faults
Steps
• Use the line diagram of the original circuit showing the pu
admittances rather than the pu impedances
• Compute Ybus:
• Diagonal elements: Ykk= Sum of admittances connected to
bus k
• Off-diagonal elements Ykn= - (Sum of admittances
connected between buses k and n
• Deduce matrix Zbus which is the invert of Ybus matrix
• Apply previous equations
30
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
Example
31
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
Example
32
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
Example
33
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
Example
34
Chapter 7: Symmetrical Faults
Bus Impedance Matrix
Example 2
For simplicity assume the system is unloaded
before the fault with
E g1 = Eg 2 = Eg 3 = 1.050
Hence all the prefault currents are zero.
35
Chapter 7: Symmetrical Faults
Three Gen Example, cont’d
−15 10 0
Ybus = j 10 −20 5
0 5 −9
−1
−15 10 0
Z bus = j 10 −20 5
0 5 −9
0.1088 0.0632 0.0351
= j 0.0632 0.0947 0.0526
0.0351 0.0526 0.1409
36
Chapter 7: Symmetrical Faults
Three Gen Example, cont’d
−1.05
For a fault at bus 1 we get I1 = = j 9.6 = − I f
− j 0.1088
0.1088 0.0632 0.0351 j 9.6
V (2) = j 0.0632 0.0947 0.0526 0
0.0351 0.0526 0.1409 0
−1.050
= −0.600
−0.3370
37
Chapter 7: Symmetrical Faults
Three Gen Example, cont’d
1.050 −1.050 00
V = 1.050 + −0.6060 = 0.4440
1.050 −0.3370 0.7130
38
Chapter 7: Symmetrical Faults
Analysis of Unsymmetric Systems
⚫ Except for the balanced three-phase fault, faults result in
an unbalanced system.
⚫ The most common types of faults are single line-ground
(SLG) and line-line (LL). Other types are double line-
ground (DLG), open conductor, and balanced three phase.
⚫ System is only unbalanced at point of fault!
⚫ The easiest method to analyze unbalanced system
operation due to faults is through the use of symmetrical
components
39