0% found this document useful (0 votes)
29 views40 pages

EENG511 Chapter 7

Uploaded by

Alaa E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views40 pages

EENG511 Chapter 7

Uploaded by

Alaa E
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

Chapter 7: Symmetrical Faults

Chapter 7:
Symmetrical
Faults

Dr. Mohamad Arnaout


Chapter 7: Symmetrical Faults

Course Content
⚫ Main purpose from this course is:
⚫ Power System Analysis and Faults Calculation
⚫ Transient Operations
⚫ Control in Power Systems

⚫ Content:
⚫ Ch. 7: Symmetrical Faults
⚫ Ch. 8: Symmetrical Components
⚫ Ch. 9: Unsymmetrical Faults
⚫ Ch. 11: Transient Stability
⚫ Ch. 12: Power Systems Control

1
Chapter 7: Symmetrical Faults

Introduction
⚫ Fault Analysis
⚫ The cause of electric power system faults is insulation
breakdown
⚫ This breakdown can be due to a variety of different factors
⚫ Fault currents cause equipment damage due to both thermal
and mechanical processes
⚫ Goal of fault analysis is to determine the magnitudes of the
currents present during the fault

2
Chapter 7: Symmetrical Faults

Introduction
⚫ Fault Types
⚫ There are two main types of faults
– symmetric faults: system remains balanced; these
faults are relatively rare, but are the easiest to analyze
so we’ll consider them first.
– unsymmetrical faults: system is no longer balanced;
very common, but more difficult to analyze
⚫ The most common type of fault on a three phase system
by far is the single line-to-ground (SLG), followed by the
line-to-line faults (LL), double line-to-ground (DLG)
faults, and balanced three phase faults

3
Chapter 7: Symmetrical Faults

Introduction
⚫ Lightning Strike Event
⚫ Lighting hits line, setting up an ionized path to ground
⚫ Conduction path is maintained by ionized air after
lightning stroke energy has dissipated
⚫ Within one to two cycles (16 ms) relays at both ends of
line detect high currents
⚫ Circuit breakers open to de-energize line in an additional
one to two cycles
⚫ Circuit breakers may reclose after several seconds, trying
to restore faulted line to service

4
Chapter 7: Symmetrical Faults

Series R–L Circuit Transients


⚫ To understand fault analysis we need to review the
behavior of an RL circuit

v(t ) = 2 V cos(t +  )

5
Chapter 7: Symmetrical Faults

Series R–L Circuit Transients

6
Chapter 7: Symmetrical Faults

Series R–L Circuit Transients

7
Chapter 7: Symmetrical Faults

Series R–L Circuit Transients

8
Chapter 7: Symmetrical Faults

Three Phase Short Circuits


⚫ During a fault the only devices that can contribute fault
current are those with energy storage
⚫ Thus the models of generators (and other rotating
machines) are very important since they contribute the
bulk of the fault current.
⚫ Generators can be approximated as a constant voltage
behind a time-varying reactance

'
Ea

9
Chapter 7: Symmetrical Faults

Three Phase Short Circuits


The time varying reactance is typically approximated
using three different values, each valid for a different
time period:
X"d = direct-axis subtransient reactance
X 'd = direct-axis transient reactance
Xd = direct-axis synchronous reactance

T’’d T’d

X’’d < X’d < Xd 10


Chapter 7: Symmetrical Faults

Generator Modeling, cont’d


For a balanced three-phase fault on the generator
terminal the ac fault current is (see page 245)
 1  1 1  −
t
Td'

 + ' − e +
X
'  d  Xd Xd  
iac (t ) = 2Ea 
− t "
 sin( t +  )
 1 1  Td 

 X " X '  e 
 d d  
where
Td" = direct-axis subtransient time constant (  0.035sec)
Td' = direct-axis transient time constant (  1sec)
11
Chapter 7: Symmetrical Faults

Generator Modeling, cont’d


The phasor current is then
 1  1 1  − t
Td'

 + ' − e +
X
'  d  Xd Xd  
I ac = Ea  
− t "
 1 1  Td 
 X " − X '  e 
 d d  
The maximum DC offset is
2 Ea' − t
TA
I DC (t ) = "
e
Xd
where TA is the armature time constant (  0.2 seconds)
12
Chapter 7: Symmetrical Faults

Generator Short Circuit Currents

13
Chapter 7: Symmetrical Faults

Generator Short Circuit Example


⚫ A 500 MVA, 20 kV, 3 is operated with an internal
voltage of 1.05 pu. Assume a solid 3 fault occurs on the
generator's terminal and that the circuit breaker operates
after three cycles. Determine the fault current. Assume

X d" = 0.15, X d' = 0.24, X d = 1.1 (all per unit)


Td" = 0.035 seconds, Td' = 2.0 seconds
TA = 0.2 seconds

14
Chapter 7: Symmetrical Faults

Generator S.C. Example, cont’d


Substituting in the values
1  1 1  − t 2.0 
1.1 +  0.24 − 1.1  e +
I ac (t ) = 1.05  
 1 − 1  e − t 0.035 
 0.15 0.24  
I ac (0) = 1.05 = 7 p.u.
0.15
500  106
I base = 3
= 14,433 A I ac (0) = 101,000 A
3 20  10
t
I DC (0) = 101 kA  2 e 0.2 = 143 k A I RMS (0) = 175 kA
15
Chapter 7: Symmetrical Faults

Generator S.C. Example, cont’d


Evaluating at t = 0.05 seconds for breaker opening
1  1 1  − 0.05 2.0 
+  −
1.1  0.24 1.1   e + 
I ac (0.05) = 1.05  

 1 − 1  e 0.05
0.035 
 0.15 0.24  
I ac (0.05) = 70.8 kA
−0.05
I DC (0.05) = 143  e 0.2 kA = 111 k A
I RMS (0.05) = 70.82 + 1112 = 132 kA

16
Chapter 7: Symmetrical Faults

Power System Three Phase Short


Circuits
⚫ Network Fault Analysis Simplifications
To simplify analysis of fault currents in networks we'll make several
simplifications:
1. Transmission lines are represented by their series reactance
2. Transformers are represented by their leakage reactances
3. Synchronous machines are modeled as a constant voltage
behind direct-axis subtransient reactance
4. Induction motors are ignored or treated as synchronous
machines
5. Other (non spinning) loads are ignored

17
Chapter 7: Symmetrical Faults

Power System Three Phase Short


Circuits
Network Fault Example:
For the following network assume a fault on the terminal of
the generator; all data is per unit except for the transmission
line reactance. Generator has 1.05 terminal voltage &
supplies 100 MVA, with 0.95 lag PF

18
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Faulted network per unit diagram

19
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Fault Analysis Solution Techniques
⚫ Circuit models used during the fault allow the network to
be represented as a linear circuit
⚫ There are two main methods for solving for fault
currents:
1. Direct method: Use prefault conditions to solve for
the internal machine voltages; then apply fault and
solve directly
2. Superposition: Fault is represented by two opposing
voltage sources; solve system by superposition
– first voltage just represents the prefault operating
point
– second system only has a single voltage source
20
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Superposition Approach

21
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Superposition Approach

Fault is represented by two equal and opposite voltage


sources, each with a magnitude equal to the pre-fault voltage
Since this is now a linear network, the faulted voltages and
currents are just the sum of the pre-fault conditions [the (1)
component] and the conditions with just a single voltage source
at the fault location [the (2) component]. Pre-fault (1)
component is equal to the pre-fault power flow solution

Obvious the
pre-fault
“fault current”
is zero! 22
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Superposition Approach
Fault (1) component due to a single voltage source
at the fault location, with a magnitude equal to the
negative of the pre-fault voltage at the fault location.

(1) (2) (1) (2)


Ig = I + Ig Im = Im + Im
g

I f = I (1)
f + I (2)
f = 0 + I (2)
f
23
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Example

24
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Example

25
Chapter 7: Symmetrical Faults

Power System Three Phase Short Circuits


Example

26
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


The superposition approach can be easily extended
to larger systems. Using the Ybus we have
Ybus V = I
For the second (2) system there is only one voltage
source so I is all zeros except at the fault location
 
 0 
  However to use this
I = − I f 
  approach we need to
 0  first determine If
 

27
Chapter 7: Symmetrical Faults

Determination of Fault Current


Define the bus impedance matrix Z bus as
−1
Z bus = Ybus V = Z busI

   V1
(2) 

   (2) 
 Z11 Z1n  0  V2 
 
Then   − I  =  
  f   
 Z n1 Z nn   0  V (2) 
n −1
   (2) 
Vn 
(1)
For a fault a bus i we get -If Zii = −V f = −Vi
28
Chapter 7: Symmetrical Faults

Determination of Fault Current, cont’d

29
Chapter 7: Symmetrical Faults

Steps
• Use the line diagram of the original circuit showing the pu
admittances rather than the pu impedances
• Compute Ybus:
• Diagonal elements: Ykk= Sum of admittances connected to
bus k
• Off-diagonal elements Ykn= - (Sum of admittances
connected between buses k and n
• Deduce matrix Zbus which is the invert of Ybus matrix
• Apply previous equations

30
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


Example

31
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


Example

32
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


Example

33
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


Example

34
Chapter 7: Symmetrical Faults

Bus Impedance Matrix


Example 2

For simplicity assume the system is unloaded


before the fault with
E g1 = Eg 2 = Eg 3 = 1.050
Hence all the prefault currents are zero.
35
Chapter 7: Symmetrical Faults

Three Gen Example, cont’d


 −15 10 0
Ybus = j  10 −20 5 
 
 0 5 −9 
−1
 −15 10 0
Z bus = j  10 −20 5 
 
 0 5 −9 
 0.1088 0.0632 0.0351
= j  0.0632 0.0947 0.0526 
 
 0.0351 0.0526 0.1409 
36
Chapter 7: Symmetrical Faults

Three Gen Example, cont’d


−1.05
For a fault at bus 1 we get I1 = = j 9.6 = − I f
− j 0.1088
 0.1088 0.0632 0.0351  j 9.6 
V (2) = j 0.0632 0.0947 0.0526   0 
  
 0.0351 0.0526 0.1409   0 
 −1.050 
=  −0.600 
 
 −0.3370 

37
Chapter 7: Symmetrical Faults

Three Gen Example, cont’d


1.050  −1.050   00 
V = 1.050 +  −0.6060  = 0.4440 
     
1.050  −0.3370  0.7130 

38
Chapter 7: Symmetrical Faults

Analysis of Unsymmetric Systems


⚫ Except for the balanced three-phase fault, faults result in
an unbalanced system.
⚫ The most common types of faults are single line-ground
(SLG) and line-line (LL). Other types are double line-
ground (DLG), open conductor, and balanced three phase.
⚫ System is only unbalanced at point of fault!
⚫ The easiest method to analyze unbalanced system
operation due to faults is through the use of symmetrical
components

39

You might also like