38LX1261
38LX1261
LRP14AC
                                                                                  Three-Phase - R-410A - 60 Hz
COMMERCIAL                                                                                                  Bulletin No. 210938
                                                                                                                   January 2022
P R O D U C T S P E C I F I C AT I O N S                                                               Supersedes November 2021
                                                                                            SEER - 14.00
                                                                                              3 to 5 Tons
                                                                Cooling Capacity - 34,000 to 57,000 Btuh
                                                                      Optional Electric Heat - 5 to 23 kW
                                                                         Blower
                               Nominal SEER
                                                                         E = High Efficiency Constant Torque Blower Motor
                                14 = 14 SEER
APPROVALS
• AHRI Standard 210/240 certified
• Design Certified by ETL Intertek
• Unit and components ETL, NEC and CEC bonded for grounding to meet safety standards for servicing
• Optional electric heaters are ETL listed for the US and Canada and are rated and tested according to DOE test
  procedures and FTC labeling regulations
• All models with the Optional Seismic Strapping Kit installed have Seismic Certification for 2018 International Building
  Code (IBC) and 2019 California Building Code (CBC) ASCE 7
• All models are ASHRAE 90.1 compliant
WARRANTY
• Compressors - Limited five years
• All other covered components - Limited one year
CABINET                                                              CONTROLS
• Conditioned areas insulated with foil faced insulation to          24 Volt Transformer
  minimize heat loss and reduce operating sound levels               • 70VA transformer furnished and factory installed in
• Powder paint for maximum durability                                  control area
• Full perimeter heavy-gauge galvanized steel base rails             Field Installed
• Base rails have rigging holes                                      Smoke Detector
• Two sides of the base rails have forklift slots                    • Photoelectric type
• Raised edges around duct and power entry openings in               • Installed in supply air and/or return air ducts
  the bottom of the unit for water protection                        • Available with one sensor or two sensors
• Easy service access
                                                                     BLOWER
• Steel louvered panels provides complete coil protection
                                                                     • Direct drive blower
Airflow Choice                                                       • Blower wheel is statically and dynamically balanced
• Units are shipped with supply and return air duct covers
  installed for downflow or horizontal conversion                    • Resiliently mounted
                                                                     • Blower assembly easily removed for servicing
Electrical Inlets and Service Valves
• Field wiring inlets are located in one central area of the         Constant Torque Blower Motor
  cabinet                                                            • DC Brushless Motor
• See dimension drawing                                              • High Efficiency Constant Torque
• Service valves with gauge ports are located inside the             • ECM (Electronically Commutated Motor)
  cabinet                                                            • Motor is programmed to provide constant torque at
Optional Accessories                                                   each of the selectable speeds
                                                                     • Fixed blower “On” delay prevents cold air from entering
Field Installed
                                                                       system during gas heating demand
Bottom Power Entry Kit
                                                                     • See Blower Performance tables
• Allows high and low voltage wiring connections through
  the unit base pan                                                  INDOOR AIR QUALITY
Base Rail Openings Closure Kit                                       Air Filters
• Kit consists of panels and hardware to cover rigging               • Filter rack furnished as standard
  holes and forklift slots in unit base rails                        • See Specifications Table for sizes
Rectangular to Round Duct Adaptor Kits                               NOTE - Filters must be field provided.
• Downflow or horizontal kits available
• Converts rectangular supply and return air openings on
  unit cabinet to round diameter
• Several sizes available
Tool-Less Filter Access Kit
• Converts blower access panel to two-piece deisgn
• One panel is equipped with tool-less latches for ease
  filter access without removing entire blower panel
NOTE - Tool-Less Filter Access Kit is not for seismic-rated
          applications.
CABINET
Base Rail Openings Closure Kit                                                           21J84              X             X              X              X
Rectangular to Round                                     Downflow - 14 in. dia.          21D26              X             X              X              X
Duct Adaptor Kits
                                                        Horizontal - 14 in. dia.         21D24              X             X              X              X
                                                                       - 16 in. dia.     22U78              X             X              X              X
                                                                       - 18 in. dia.     22U79              X             X              X              X
¹ Tool-Less Filter Access Kit                                                            21J80              X             X              X              X
CONTROLS
Smoke Detector - Supply or Return (one sensor)                                           21U21              X             X              X              X
Smoke Detector - Supply and Return (two sensors)                                         21U22              X             X              X              X
ELECTRICAL
Bottom Power Entry Kit                                                                   21J78              X             X              X              X
² ELECTRIC HEAT
5 kW                                                              208/230V-3ph           21J30              X             X              X              X
                                                                        460V-3ph         21J37              X             X              X              X
10 kW                                                             208/230V-3ph           21J33              X             X              X              X
                                                                        460V-3ph         21J38              X             X              X              X
15 kW                                                             208/230V-3ph           21J34              X             X              X              X
                                                                        460V-3ph         21J39              X             X              X              X
20 kW                                                             208/230V-3ph           21J35                            X              X              X
                                                                        460V-3ph         21J40                            X              X              X
23 kW                                                             208/230V-3ph           21J36                                                          X
                                                                        460V-3ph         21J41                                                          X
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Not for Title 24)
Downflow or Horizontal (Includes Barometric Relief Dampers
                                                                                         21U15              X             X              X              X
and Exhaust Hood)
High Performance Economizer With Outdoor Air Hood
(Approved for California Title 24 Building Standards / AMCA Class 1A Certified)
Downflow or Horizontal (Includes Barometric Relief Dampers
                                                                                         21U17              X             X              X              X
and Exhaust Hood)
Economizer Controls
Single Enthalpy Control (Standard)                                                       21Z09              X             X              X              X
Single Enthalpy Control (High Performance)                                               11G21              X             X              X              X
1
    Not for seismic-rated applications.
2
    Field wiring for electric heat is separate from the unit power supply. A second, separate power source is required.
X = Field Installed
                                                                                               LRP14AC 3-Phase - 3 to 5 Ton Packaged Electric / Electric / Page 7
OP T IONS / ACCES S ORIES
                                                                     Catalog                 Model No.
Item
                                                                       No.   LRP14AC36 LRP14AC42 LRP14AC48 LRP14AC60
OUTDOOR AIR
Motorized 21U19 X X X X
Manual 21U20 X X X X
ROOF CURBS
Clip Curbs
8 in height 21J17 X X X X
14 in height 21J19 X X X X
18 in height 21J20 X X X X
24 in height 21J25 X X X X
14 in height 21U04 X X X X
3 TON - LRP14AC36
                                                                          Outdoor Air Temperature Entering Outdoor Coil
Entering Total          85°F                                      95°F                          105°F                             115°F                         125°F
  Wet     Air             Sensible/Total           Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total
  Bulb Volume Total Comp.
 Tem-          Cool Motor Ratio (S/T)              Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)
perature       Cap. Input    Dry Bulb              Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb
         cfm kBtuh kW 75°F 80°F 85°F               kBtuh   kW      75°F 80°F 85°F kBtuh      kW     75°F 80°F 85°F kBtuh     kW     75°F 80°F 85°F kBtuh     kW     75°F 80°F 85°F
           1050    34.2   1.93   .94 1.00 1.00 32.8        2.21     .96 1.00 1.00 31.2       2.52   .98 1.00 1.00 29.6       2.89 1.00 1.00 1.00 27.6        3.32 1.00 1.00 1.00
 59°F      1200    35.6   1.93   .97 1.00 1.00 34.0        2.21     .99 1.00 1.00 32.4       2.52 1.00 1.00 1.00 30.6        2.89 1.00 1.00 1.00 28.6        3.33 1.00 1.00 1.00
           1350    36.8   1.94 1.00 1.00 1.00 35.2         2.21 1.00 1.00 1.00 33.6          2.53 1.00 1.00 1.00 31.6        2.90 1.00 1.00 1.00 29.4        3.33 1.00 1.00 1.00
           1050    35.0   1.93   .76   .91 1.00 33.2       2.20     .78   .93 1.00 31.6      2.52   .80   .95 1.00 29.6      2.88   .83   .98 1.00 27.6      3.32   .86 1.00 1.00
 63°F      1200    36.0   1.93   .79   .95 1.00 34.4       2.21     .82   .97 1.00 32.6      2.53   .84   .99 1.00 30.6      2.90   .86 1.00 1.00 28.6       3.32   .90 1.00 1.00
           1350    37.0   1.94   .83   .98 1.00 35.2       2.22     .85 1.00 1.00 33.6       2.53   .87 1.00 1.00 31.6       2.90   .90 1.00 1.00 29.4       3.32   .93 1.00 1.00
           1050    37.0   1.94   .60   .74   .88   35.2    2.21     .61   .76   .90   33.4   2.53   .61   .78   .92   31.2   2.90   .63   .80   .95   28.8   3.33   .66   .84   .98
 67°F      1200    38.0   1.95   .62   .77   .92   36.0    2.21     .63   .79   .94   34.0   2.53   .64   .82   .96   31.8   2.89   .65   .84   .99   29.4   3.32   .69   .88 1.00
           1350    38.5   1.95   .64   .80   .95   36.8    2.22     .64   .83   .97   34.6   2.53   .66   .85 1.00 32.4      2.90   .68   .88 1.00 30.0      3.33   .71   .92 1.00
           1050    39.0   1.95   .45   .59   .72   37.2    2.22     .45   .60   .73   35.2   2.53   .46   .59   .75   33.0   2.90   .45   .61   .78   30.6   3.33   .46   .63   .82
 71°F      1200    40.0   1.95   .46   .61   .75   38.0    2.23     .46   .62   .77   36.0   2.54   .47   .62   .79   33.8   2.90   .47   .64   .82   31.0   3.33   .47   .68   .86
           1350    41.0   1.96   .47   .63   .79   39.0    2.23     .47   .64   .81   36.6   2.54   .48   .65   .83   34.2   2.90   .48   .67   .86   31.6   3.33   .48   .71   .90
4 TON - LRP14AC48
                                                                          Outdoor Air Temperature Entering Outdoor Coil
Entering Total          85°F                                      95°F                          105°F                               115°F                         125°F
  Wet     Air             Sensible/Total           Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total
  Bulb Volume Total Comp.
 Tem-          Cool Motor Ratio (S/T)              Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)
perature       Cap. Input    Dry Bulb              Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb
         cfm kBtuh kW 75°F 80°F 85°F               kBtuh   kW      75°F 80°F 85°F kBtuh      kW      75°F 80°F 85°F kBtuh      kW     75°F 80°F 85°F kBtuh     kW     75°F 80°F 85°F
           1400    44.0   2.70   .91 1.00 1.00 42.5        3.08     .93 1.00 1.00 40.5       3.52     .95 1.00 1.00 38.5       4.07   .97 1.00 1.00 35.8       4.68   .99 1.00 1.00
 59°F      1600    46.5   2.70   .95 1.00 1.00 44.5        3.08     .97 1.00 1.00 42.0       3.52     .98 1.00 1.00 40.0       4.05   .99 1.00 1.00 37.2       4.65 1.00 1.00 1.00
           1800    48.0   2.69   .98 1.00 1.00 46.0        3.07     .99 1.00 1.00 43.5       3.52 1.00 1.00 1.00 41.0          4.04 1.00 1.00 1.00 38.5        4.66 1.00 1.00 1.00
           1400    46.0   2.70   .75   .88   .99   43.5    3.07     .76   .90   .99   41.5   3.52     .77   .92 1.00 38.5      4.06   .79   .95 1.00 36.0      4.68   .82   .97 1.00
 63°F      1600    47.5   2.70   .77   .92 1.00 45.0       3.07     .78   .94 1.00 42.5      3.52     .80   .96 1.00 40.0      4.05   .82   .98 1.00 37.4      4.67   .86   .99 1.00
           1800    48.5   2.70   .80   .95 1.00 46.0       3.07     .81   .97 1.00 44.0      3.51     .83   .98 1.00 41.0      4.04   .86   .99 1.00 38.5      4.67   .89 1.00 1.00
           1400    49.0   2.70   .58   .72   .85   46.5    3.06     .60   .74   .87   44.0   3.52     .60   .75   .89   41.0   4.05   .62   .77   .92   38.0   4.67   .64   .80   .95
 67°F      1600    50.5   2.69   .61   .75   .88   48.0    3.07     .61   .76   .91   45.0   3.52     .63   .78   .93   42.0   4.04   .64   .80   .96   39.0   4.66   .65   .83   .98
           1800    51.5   2.70   .62   .78   .92   48.5    3.06     .63   .79   .95   46.0   3.51     .64   .81   .97   43.0   4.03   .66   .84   .98   39.5   4.65   .68   .87 1.00
           1400    52.0   2.69   .43   .57   .70   49.5    3.06     .43   .58   .71   47.0   3.51     .44   .59   .73   44.0   4.03   .45   .60   .75   40.5   4.65   .43   .62   .77
 71°F      1600    53.5   2.69   .44   .59   .73   51.0    3.06     .44   .61   .74   48.0   3.49     .45   .61   .76   45.0   4.02   .44   .63   .78   41.5   4.64   .45   .65   .81
           1800    54.5   2.68   .45   .61   .75   52.0    3.06     .45   .62   .77   49.0   3.50     .45   .63   .79   46.0   4.02   .46   .65   .82   42.5   4.63   .46   .67   .85
5 TON - LRP14AC60
                                                                          Outdoor Air Temperature Entering Outdoor Coil
Entering Total          85°F                                      95°F                          105°F                               115°F                         125°F
  Wet     Air             Sensible/Total           Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total Total Comp. Sensible/Total
  Bulb Volume Total Comp.
               Cool Motor   Ratio (S/T)            Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)     Cool Motor Ratio (S/T)
 Tem-
perature       Cap. Input    Dry Bulb              Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb     Cap. Input    Dry Bulb
         cfm kBtuh kW 75°F 80°F 85°F               kBtuh   kW      75°F 80°F 85°F kBtuh      kW      75°F 80°F 85°F kBtuh      kW     75°F 80°F 85°F kBtuh     kW     75°F 80°F 85°F
           1700    54.5   3.42   .88   .99 1.00 52.0       3.89     .90   .99 1.00 49.5      4.44     .91 1.00 1.00 47.0       5.05   .94 1.00 1.00 44.0       5.78   .96 1.00 1.00
 59°F      1800    55.5   3.43   .89   .99 1.00 53.0       3.90     .91 1.00 1.00 50.5       4.44     .93 1.00 1.00 48.0       5.07   .95 1.00 1.00 45.0       5.76   .97 1.00 1.00
           2250    59.5   3.43   .95 1.00 1.00 57.0        3.91     .96 1.00 1.00 54.0       4.41     .98 1.00 1.00 51.0       5.05   .99 1.00 1.00 47.5       5.76 1.00 1.00 1.00
           1700    57.0   3.42   .72   .85   .96   54.5    3.90     .73   .86   .98   51.5   4.42     .75   .88   .99   48.0   5.04   .77   .90 1.00 45.0      5.76   .78   .93 1.00
 63°F      1800    58.0   3.43   .73   .86   .98   55.0    3.89     .74   .88   .99   52.0   4.42     .76   .90   .99   48.5   5.05   .77   .92 1.00 45.5      5.78   .80   .95 1.00
           2250    60.5   3.43   .77   .92 1.00 57.5       3.90     .78   .93 1.00 54.5      4.43     .80   .96 1.00 51.0      5.05   .82   .98 1.00 48.0      5.77   .85   .99 1.00
           1700    60.5   3.42   .58   .70   .82   57.5    3.89     .58   .71   .83   54.5   4.43     .59   .72   .85   51.0   5.04   .61   .74   .87   47.5   5.75   .62   .76   .90
 67°F      1800    61.5   3.43   .58   .71   .83   58.0    3.90     .59   .72   .85   55.0   4.42     .60   .74   .87   51.5   5.04   .61   .76   .89   48.0   5.75   .62   .77   .92
           2250    64.0   3.43   .61   .75   .89   60.5    3.90     .62   .77   .91   57.5   4.43     .63   .78   .93   53.5   5.05   .64   .80   .96   49.5   5.76   .65   .83   .98
           1700    64.5   3.44   .42   .56   .68   61.0    3.89     .43   .57   .69   58.0   4.43     .43   .58   .70   54.0   5.05   .44   .59   .72   50.0   5.77   .45   .61   .74
 71°F      1800    65.0   3.43   .42   .57   .69   61.5    3.90     .44   .58   .70   58.5   4.44     .44   .58   .71   54.5   5.03   .44   .60   .73   50.5   5.76   .45   .62   .75
           2250    68.0   3.44   .44   .59   .73   64.0    3.90     .45   .61   .74   60.5   4.42     .45   .61   .76   56.5   5.03   .46   .64   .78   52.5   5.78   .47   .65   .81
LRP14AC42
                                                                                External Static (in.w.g.)
 Blower Tap
                                      0.1           0.2           0.3           0.4           0.5           0.6         0.7    0.8    0.9    1.0
                       CFM            833           758           676           569           493           406         346    ---    ---    ---
    Tap 1
                       RPM            441           493           547           605           659           708         745    ---    ---    ---
  (Fan Only)
                      Watts            67            73            79            87            92            99         103    ---    ---    ---
                       CFM           1575          1519          1475          1438          1411          1376         1341   1294   1252   1209
    Tap 2
    (Low               RPM            777           805           832           857           882           908         937    968    995    1024
   Cooling)
                      Watts           370           382           394           405           416           428         440    454    467    478
                       CFM           1818          1772          1726          1680          1638          1599         1562   1518   1475   1429
    Tap 3
    (High              RPM            751           780           806           833           861           884         907    931    962    988
   Cooling)
                      Watts           396           410           420           433           445           455         465    476    489    500
                       CFM           1575          1519          1475          1438          1411          1376         1341   1294   1252   1209
   ¹ Tap 4
(Low Electric          RPM            777           805           832           857           882           908         937    968    995    1024
    Heat)
                      Watts           370           382           394           405           416           428         440    454    467    478
                       CFM           1818          1772          1726          1680          1638          1599         1562   1518   1475   1429
   ¹ Tap 5
(High Electric         RPM            751           780           806           833           861           884         907    931    962    988
    Heat)
                      Watts           396           410           420           433           445           455         465    476    489    500
 NOTE - All air data is measured external to unit with dry coil and without air filters.
 1
   Taps 4 and 5 are used with Optional Electric Heat. Refer to Electric Heat nameplate for proper heat tap selection.
LRP14AC60
                                                                               External Static (in.w.g.)
 Blower Tap
                                     0.1           0.2           0.3           0.4           0.5           0.6         0.7     0.8        0.9         1.0
                      CFM           1378          1320          1269          1223          1160          1099         1030   965         899        833
   Tap 1
                      RPM            603           639           668           699           740           778         816    855         894        931
 (Fan Only)
                     Watts           181           191           197           205           214           224         233    242         251        261
                      CFM           1980          1936          1893          1852          1816          1780         1740   1703       1660        1615
   Tap 2
   (Low               RPM            806           833           862           887           903           927         951    971        1002        1029
  Cooling)
                     Watts           460           472           484           498           504           516         526    536         551        564
                      CFM           2340          2300          2259          2224          2187          2158         2139   2108       2079        2038
   Tap 3
   (High              RPM            931           958           981          1004          1027          1047         1063   1081       1099        1116
  Cooling)
                     Watts           742           760           775           790           805           820         829    841         852        858
                      CFM           2232          2194          2154          2129          2089          2057         2026   1991       1960        1926
   ¹ Tap 4
(Low Electric         RPM            897           917           946           970           993          1012         1028   1048       1068        1089
    Heat)
                     Watts           653           666           683           696           708           722         731    743         755        767
                      CFM           2329          2291          2256          2220          2183          2153         2136   2102       2075        2035
   ¹ Tap 5
(High Electric        RPM            931           954           980          1000          1025          1044         1061   1081       1102        1116
    Heat)
                     Watts           742           757           773           785           804           815         828    841         855        858
NOTE - All air data is measured external to unit with dry coil and without air filters.
1
  Taps 4 and 5 are used with Optional Electric Heat. Refer to Electric Heat nameplate for proper heat tap selection.
       19-1/2                19-1/2
       (495)                 (495)                    2-3/8
                                                      (60)                                      CC                                       EE             DD
    DOWNFLOW            DOWNFLOW
    RETURN AIR          SUPPLY AIR                 11-1/2   16-1/8   18-1/2
                                                   (292)    (410)    (470)
     OPENING             OPENING                                                                                                                         FF
                                                                                                                                   Center of
                                                                                                                                    Gravity
                                                 BOTTOM
                                               POWER ENTRY
                                                     ALTERNATE BOTTOM
                                                       POWER ENTRY
                                                      7
                                                    (178)
                    3-1/4
                                                                                                BB                                                      AA
                    (83)
                    Typ.            10                                                                             TOP VIEW
                                  (254)
                       25-7/8 (657)
                                                                                                       (Corner Weight and Center of Gravity)
                       26-1/2 (673)
                     26-3/4 (679)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER WITH BAROMETRIC RELIEF DAMPERS
(Downflow Applications)
                                                                                                                                        23-3/4           10
                                                                                                                                        (603)           (254)
                                                  24-1/4                OUTDOOR AIR HOOD
                                                  (616)               (Furnished with Economizer)
                                                                                                                                                                      33
                                                                                35-3/8                                                                              (838)
                                                                                 (86)
                                                                      20-3/8
                                                                      (517)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER WITH BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
                                                                                                                  23-7/8
                                                                                                                  (606)
TOP VIEW
                                                                                                                                     72 (1829)
                                                                        OUTDOOR
                                                                         AIR HOOD
                                                                      (Furnished With
                                                                        Economizer)                            24-3/4 (629)
          BAROMETRIC
             RELIEF
           DAMPERS                                                                                                         6-1/8
                                                                 2-3/8 (60)                                                (156)
            (On Unit)                                                                             OUTDOOR
                                                                                                    AIR
                                                               17 (432)
14-1/2     HORIZONTAL                                       Horizontal Return
           SUPPLY AIR                                         Air Opening          14 (356)
(368)
            OPENING                                             (On Unit)
                                                                                                               20 (508)
              18-1/4            18-1/4                                                                                                      LEFT SIDE VIEW
              (464)             (464)            *BAROMETRIC
                            Horizontal Return    RELIEF HOOD                      *FIELD FABRICATED
                              Air Opening        (Furnished With                RELIEF OPENING IN DUCT
                                (On Unit)        Economizer and                    (Sized to Accomodate
                                                  Field Installed                 Barometric Relief Hood)
                       BACK VIEW                on Return Air Duct)                                                  NOTE - Return Air Duct and Transition must be supported.
               8-7/8                                                                          9
               (223)                                                                        (229)
                                     9-3/4                                                                         11-3/8
                                     (247)                                                                         (289)
                       9-1/2                          15                                            9-3/8                             15
                       (241)                        (381)                                           (238)                           (381)
CLIP CURB
3/4 (19)
                                              52-7/8
                                              (1343)                                    7(
                                                                                          17
                                                                           3-3/4              8)
                                                                           (95)
                                                                                                                                   1-3/4
                                                                                                                                   (44)
1 (25)
                                             52-7/8
                                             (1343)                                    7(
                                                                                            17
                                                                          3-1/2               8)
                                                                          (89)
                        WOOD NAILER                                                                                          1
                                                                                                                           (25)
                        CURB FRAME
14 (356)
                         CANT STRIP
                    (FIELD SUPPLIED)
                                                                                                                                   1-3/4
                                                                                                                                   (44)
MAINT
Commercial
                         Description                                                                                        Catalog
                                                                                                                              No.
                         ComfortSense® 7500 7-Day Programmable                                                              17G74
                                                                   Universal thermostat locking guard (clear) 39P21
                         Temperature                                 ¹ Remote non-adjustable wall-mount 20k 47W36
                         Sensors                                     ¹ Remote non-adjustable wall-mount 10k 47W37
                                                         Remote non-adjustable discharge air (duct mount) 19L22
                                                                                      Outdoor temperature sensor X2658
                          1
                              Remote wall-mount sensors can be applied in any of the following combinations:
                                One Sensor - (1) 47W36, Two Sensors - (2) 47W37, Three Sensors - (2) 47W36 and (1) 47W37
                                Four Sensors - (4) 47W36, Five Sensors - (3) 47W36 and (2) 47W37
Blower Data Added Air Resistance data for 16 and 18 in.Rectangular to Round Duct Adaptor kits
Electrical/Electric Heat Data Added note that a second, separate power source is required for electric heat
                                                       Added 16 and 18 in.sizes for the Rectangular to Round Duct Adaptor kits
Options/Accessories
                                                       Added Hurricane Strapping Kit for Rail Mount
                                                                               Visit us at www.Lennox.com
                                                                               For the latest technical information, www.LennoxCommercial.com
                                                                               Contact us at 1-800-4-LENNOX
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.                                              ©2022 Lennox Industries, Inc.