mark Terminal name Terminal description and factory settings
ation
Multi-function input terminal Factory setting: 1 forward/stop
X1
1
Multi-function input terminal Factory setting: 2 reverse/stop
X2
Multi- 2
function Multi-function input terminal Factory setting: 3 three-wire control mode
X3
input 3
terminal Multi-function input terminal Factory setting: 4 multi-stage speed one
X4
4
Common terminal Multi-function input common terminal, and
COM
corresponding +24V power reference ground
AI1 Analog input 1 0~10V input
AI2 Analog input 2 0~10V/0~20mA input (Dip switch or jumper switch)
Analog Power supply for analog +10V DC 10mA (potentiometer 3~5K)
input +10V
quantity setting
Analog reference ground Analog input and output reference ground
GND
corresponding to +10V
Multi-function output terminal Open collector output. Factory setting: 1 running
Y1
1 output ON
Open collector output. Factory setting: 2 positive
Multi-function output
Multi- Y2 direction running output ON
terminal 2
function (100 series does not have this terminal)
output ROA
ROB ROA-ROB normally closed
Relay output Factory setting: inverter fault output
ROA-ROC normally open
ROC
Analog Analog output terminal 0~10V/0~20mA output (Dip switch or jumper
output AO switch)
GND is the reference ground
power +24V power supply +24V DC 100mA The corresponding COM is the
supply +24V
power ground.
commu 485+ 485 signal positive end Standard MODBUS RS-485 serial communication
nication 485 signal negative terminal interface
485-
Please use twisted pair or shielded wire
Frequency inverter user manual
“〇”:Indicatesthat this parameter can be changed while the inverter is running or stopped when P0.00=0.
“●”: Indicates that this parameter cannot be changed while the inverter is running.
“×”:Indicates that this parameter is only the actual detected record value and cannot be changed.
P0 Basic function
MODBUS
Function Chang
Name Parameter description Default address
Code e
(decimal)
0: Allow parameter setting (except with "×")
Parameter setting 1: Prohibit parameter setting (except P0-00)
P0-00 0 ● 1000
mode 99: restore factory value
P3 Motor parameters
MODBUS
Functio Chan
Name Parameter description Default address
n Code ge
(decimal)
Motor rated P4-05~400.0Hz
P3-00 50.0Hz ● 1038
frequency
P3-01 Motor rated voltage 200~440V Depending ● 1039
P3-02 Motor rated current 0.1~999.9A Depending ● 1040
P3-03 Motor rated power 0.1~630.0KW Depending ● 1041
P3-04 Motor rated speed 1~36000rpm 1440rp ● 1042
Motor no-load 0.1~999.9A Depending
P3-05 ● 1043
current
Motor stator 0.001~50.000Ω Depending
P3-06 ● 1044
resistance
Motor magnetizing 0.1~5000.0mH Depending
P3-07 ● 1045
inductance
P5-07 AI2 upper limit AI2 lower limit ~10.00V 10.00V ○ 1077
AI2 upper limit 0~100.0% 1078
P5-08 100.0% ○
corresponding setting
P5-09 AI2 input filter time 0.0s~10.0s 0.1s ○ 1079
Multi-function input 0: No function 1: Forward rotation 2: Reverse rotation 1080
P5-10 1 ●
terminal X1 3: Three-wire control 4: Multi-stage speed one
Multi-function input 5: Multi-stage speed two 6: Multi-stage speed three 1081
P5-11 2 ●
terminal X2 7: Jog forward rotation 8: Jog reverse rotation
Multi-function input 9: Frequency increase 10: Frequency decrease 1082
P5-12 11: Acceleration and deceleration time selection one 3 ●
terminal X3
Multi-function input 12: Acceleration and deceleration time selection two 1083
P5-13 13: acceleration or deceleration pause 4 ●
terminal X4
Multi-function input 14: External fault input 1084
P5-14 16: Free stop 15: Fault reset 5 ●
terminal X5
Multi-function input 17: External counting input 18: Counter clear reset 1085
P5-15 19: Start program operation 20: Program operation 6 ●
terminal X6
Multi-function input pause
P5-16 Reserve ● 1086
terminal X7
Multi-function input
P5-17 Reserve ● 1087
terminal X8
※The 8-speed setting can be achieved through the state combination of three multi-function input terminals.
Multi- Multi- Correspond Multi- Multi- Correspond
Multista Frequency Multista Frequency
stage paragra ing stage paragra ing
ge two setting ge two setting
three ph parameters three ph parameters
Multi-band P0-01 Multi-band
OFF OFF OFF ON OFF OFF P8-04
frequency 0 decision frequency 4
Multi-band Multi-band
OFF OFF ON P8-01 ON OFF ON P8-05
frequency 1 frequency 5
Multi-band Multi-band
OFF ON OFF P8-02 ON ON OFF P8-06
frequency 2 frequency 6
Multi-band Multi-band
OFF ON ON P8-03 ON ON ON P8-07
frequency 3 frequency 7
0: Two-line control 1 1: Two-line control 2
Terminal operation
P5-18 2: Three-wire control 1 3: Three-wire control 2 0 ● 1088
control mode
Input terminal filter 2ms~100 ms
P5-19 10 ms ○ 1089
time
UP/DOWN range 0.0~50.0Hz (the amplitude of keyboard or terminal
P5-20 0.1 ○ 1090
increasing/decreasing)
MODBUS 2:1200BPS 3:2400BPS 4:4800BPS
P5-25 communication baud 5:9600BPS 6:19200BPS 7:38400BP 5 ○
rate
MODBUS data format 0: No parity (8-N-1) 1: No parity (8-N-2)
P5-26 2: Even parity (8-E-1) 3: Odd parity (8-O-1) 0 ○
MODBUS
Function
Name Parameter description Default Change address
Code
(decimal)
PID reference source 0: Digital setting (P7-01) 1: Panel potentiometer
P7-00 0 ○ 1110
selection 2: Analog channel AI1 3: Analog channel AI2
P7-01 PID digital given value 0.00~10.00 V 0.00V ○ 1111
PID feedback source 0: Analog channel AI1 1: Analog channel AI2
P7-02 0 ○ 1112
selection
PID output 0: PID output is positive characteristic 1: PID output is
P7-03 0 ○ 1113
characteristic selection negative characteristic
P7-04 Proportional gain P 0.0~10.0 1.0 ○ 1114
P7-05 Integration time I 0.0~100.0s 1.0s ○ 1115
Set and feedback 0.00~2.00(Within tolerance, PID is not calculated)
P7-06 0.02 ○ 1116
deviation tolerance
Feedback amount 0.1~100.0s
P7-07 0.02s ○ 1117
sampling period (T)
Feedback source 0.00~5.00
P7-08 disconnection 0.0 ○ 1118
detection value
Feedback source 0.0~100.0s
P7-09 disconnection 10.0s ○ 1119
detection time
Frequency inverter user manual
P7-12 Sleep time 0~3000S 600 ○ 1122
P7-13 Dormant pressure 0~10.00 (Slightly less than the set pressure P7-01) 0 ○ 1123
Sleep frequency 0~50.0Hz (2~3Hz greater than the frequency of
P7-14 0 ○ 1124
maintaining pipeline pressure)
P7-15 Wake up stress 0~10.00 (need to be less than sleep pressure P7-13) 0 ○ 1125
※Inverter The feedback pressure is greater than the set value of the sleep pressure (P7-13); when the running
sleep frequency is continuously lower than the set value of the sleep frequency (P7-14) and the duration
conditions reaches the set time (P7-12), the inverter starts to sleep.
MODBUS
Function
Name Parameter description Default Change address
Code
(decimal)
Simple PLC mode 0: Simple PLC program operation is invalid
1: The program stops after running for one cycle
P8-00 0 ● 1126
2: After running for a week, run at the last frequency
3: The program runs cyclically
P8-01 First stage speed Lower limit frequency ~ upper limit frequency 11.0Hz ○ 1127
P8-02 Second speed Lower limit frequency ~ upper limit frequency 12.0Hz ○ 1128
P8-03 Third stage speed Lower limit frequency ~ upper limit frequency 13.0Hz ○ 1129
P8-04 Fourth stage speed Lower limit frequency ~ upper limit frequency 14.0Hz ○ 1130
P8-05 Fifth stage speed Lower limit frequency ~ upper limit frequency 15.0Hz ○ 1131
P8-06 Sixth speed Lower limit frequency ~ upper limit frequency 16.0Hz ○ 1132
Seventh stage Lower limit frequency ~ upper limit frequency
P8-07 17.0Hz ○ 1133
speed
Main frequency 0~6400.0 (The corresponding frequency is determined
P8-08 running time 0.0s ○ 1134
by P0-01)
The first period of 0~6400.0 (The corresponding frequency is P8-01)
P8-09 0.0s ○ 1135
time
Second period 0~6400.0 (Similar to the same as above, the same
P8-10 0.0s ○ 1136
below)
P8-11 The third period 0~6400.0 0.0s ○ 1137
P8-12 The fourth period 0~6400.0 0.0s ○ 1138
P8-13 Fifth period 0~6400.0 0.0s ○ 1139
P8-14 Sixth period 0~6400.0 0.0s ○ 1140
P8-15 Seventh period 0~6400.0 0.0s ○ 1141
P8-16 Multi-speed time unit 0: second 1: minute 2: hour 0 ● 1142
The direction of each From 0 to 255, each bit of the binary system represents
segment of the a block direction. 0 means forward rotation, 1 means
program reverse rotation; corresponding to binary and then
P8-17 converted to decimal 0 ● 1143
※Example: The first paragraph is reversed, and the third
paragraph is reversed, expressed in binary as:
(0000 1010)2=(10)10 ie P8-17=10
Selection of 0~65535 Use every two digits of the binary system to
acceleration and represent the acceleration and deceleration time
deceleration time for corresponding to a block direction
each section of the BIT 15~0 represents the acceleration and deceleration
P8-18 program 0 ○ 1144
time corresponding to the 7~0 segment, the algorithm
is the same as above
※Binary 00: (P0-04, P0-05) 01: (PA-00, PA-01) 10: (PA-
02, PA-03) 11: (PA-04, PA-05)
MODBUS
Function
Name Parameter description Default Change address
Code
(decimal)
Motor overload 0: No protection 1: Protection
P9-00 0 ● 1147
protection selection
Motor overload 50~120% (100% corresponds to the rated current of the
P9-01 110% ● 1148
protection point motor P3-02)
Overvoltage stall 0: Prohibit protection 1: Allow protection
P9-02 1 ● 1149
protection ※It can be set to 0 when there is a braking resistor
Frequency inverter user manual
connected to improve the braking effect
110.0~150.0% (100% corresponds to the standard bus
P9-03 135 ● 1150
Stall overvoltage point voltage of the inverter)
Over-current 0: Prohibit protection 1: Allow protection
P9-04 1 ● 1151
protection
Stall overcurrent point 100~180% (100% corresponds to the rated current of the
P9-05 180 ● 1152
inverter)
Input phase loss 0: Prohibit protection 1: Allow protection
P9-06 Reserve ● 1153
protection
Output phase loss 0: Prohibit protection 1: Allow protection
P9-07 Reserve ● 1154
protection
Recent failure 0~21 (Refer to fault information and corresponding
P9-08 × 1155
information countermeasures for details)
Last failure information 0~21 (Refer to fault information and corresponding
P9-09 × 1156
countermeasures for details)
The first two failure 0~21 (Refer to fault information and corresponding
P9-10 × 1157
information countermeasures for details)
Operating frequency of
P9-11 × 1158
recent failures
Output current of
P9-12 × 1159
recent fault
Bus voltage of the last
P9-13 × 1160
fault
Input status of recent
P9-14 × 1161
fault
Latest fault output
P9-15 × 1162
status
Fault self-reset 0: Invalid 1: Auto reset of undervoltage fault (unlimited
P9-16 function number of times) 0 ● 1163
2~20: Number of automatic fault resets
MODBUS
Function
Name Parameter description Default Change address
Code
(decimal)
PA-00 Acceleration time 1 0.1~3600.0s 20.0s ○ 1165
PA-01 Deceleration time 1 0.1~3600.0s 20.0s ○ 1166
PA-02 Acceleration time 2 0.1~3600.0s 20.0s ○ 1167
PA-03 Deceleration time 2 0.1~3600.0s 20.0s ○ 1168
PA-04 Acceleration time 3 0.1~3600.0s 20.0s ○ 1169
PA-05 Deceleration time 3 0.1~3600.0s 20.0s ○ 1170
PA-06 Jog acceleration time 0.1~3600.0s 5.0s ○ 1171
PA-07 Jog deceleration time 0.1~3600.0s 5.0s ○ 1172
PA-08 Hop frequency 1 0.0~Upper limit frequency (P0-09) 0.0Hz ○ 1173
PA-09 Hop frequency 2 0.0~Upper limit frequency (P0-09) 0.0Hz ○ 1174
PA-10 Hop frequency range 0.0~Upper limit frequency (P0-09) 0.0Hz ○ 1175
FDT level detection 0.0~Upper limit frequency (P0-09)
PA-11 0.0Hz ○ 1176
value
FDT hysteresis 0.0~FDT level (PA-11)
PA-12 0.0Hz ○ 1177
detection value
PA-13 Frequency reach FAR 0.0~Upper limit frequency (P0-09) 0.0Hz ○ 1178
PA-14 Set the count value 1~65535 10 ○ 1179
Specify the number of 1~65535 (The designated count value cannot be greater
PA-15 counts 10 ○ 1180
than the set count value)
Overload frequency 0: invalid 1: valid
PA-16 1 ● 1181
reduction function
PA-17 DC braking coefficient 110%~150% 130 ● 1182
Dead zone Model determination Dependin
PA-21 ● 1186
compensation time g
Down frequency 100%~300%
PA-22 210 ● 1187
current point
Frequency inverter user manual
7、MODBUS communication
Command code 03 is read data, 06 is write data.
-00 to PA-26 in sequence correspond to the RAM (not stored
after power-off) communication address: 1000~1191 (decimal). For the specific address, please refer to the
MODBUS communication address on the right side of the function parameter summary table. If you need to
store data in EEPROM (power-down storage), subtract 1000. Example: The RAM address of function code P0-04 is
represented as 1004, and in EEPROM, the address is 0004. There is no such difference in related addresses in
other non-parameter tables.
screen, please set the PLC interval address to 1.
The 200 series inverter has no such restriction.
2. Communication control start-stop command address (read and write, valid when P0-02=3)
MODBUS communication
Data meaning description
address (decimal)
1: Forward running 2: Forward jog 5: Reverse running
200
6: Reverse jog 8: Stop 16: Free stop 32: Fault reset
3. Communication control operating frequency address (read and write, valid when P0-01=7)
MODBUS communication Data meaning description
address (decimal)
1003 The given value is the given frequency of the inverter