Centrifugal Pumps Standard Guide
Centrifugal Pumps Standard Guide
Contents
1 Scope ..................................................................... 2
2 Conflicts and Deviations ......................................... 2
3 References ............................................................. 2
4 Design .................................................................... 5
5 Installation ............................................................ 25
6 Testing and Inspection ......................................... 27
7 Life Cycle Cost Evaluation ................................... 28
Revision Summary ...................................................... 29
1 Scope
This standard defines the minimum mandatory requirements governing the design and
installation of centrifugal pumps excluding submersible pumps that are covered by
SAES-G-007, Submersible Pumps and Motors for Water Well and Offshore Service.
Pumps in domestic sewage or community water service with driver power rating up to
37 kW (50 HP) shall be to manufacturer standard design and do not have to comply
with this standard.
2.1 Any conflicts between this standard and other applicable Saudi Aramco
Engineering Standards (SAESs), Materials System Specifications (SAMSSs),
Standard Drawings (SASDs), or industry standards, codes and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Consulting Services Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this standard in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Consulting Services Department of
Saudi Aramco, Dhahran.
3 References
The selection of material and equipment and the design, construction, maintenance and
repair of equipment and facilities covered by this standard shall comply with the latest
edition of the references listed below, unless otherwise noted.
4 Design
4.1.1.7 The pump and its drive train including all auxiliaries shall
comply with the requirements of SAES-B-068, Electrical Area
Classification.
4.1.1.13 Integrally geared pump with driver rated power above 200 HP
requires review and approval by the Standards Committee
Chairman; Pumps, Seals, and Mixers.
4.1.2 Unit responsibility for the complete pump train including driver, gear, oil
system(s), etc., shall be assigned to the pump manufacturer.
Exception:
4.1.3.1 For each new piece of equipment or integrated unit that will
generate noise in excess of 85 dB(A) at a distance of one
meter, the Project Manager shall submit a completed Form
SA-7305, Equipment Noise Data Sheet, to ECD/EPD.
4.2.1 The NPSHA at 120% of rated flow shall be determined based on suction
pressure at pump suction nozzle and pumped product vapor pressure at
maximum pumping temperature. If strainers are used for long-term
basis, the maximum pressure drop across the strainer shall be included in
4.2.2 Viscosity correction factors, per the Hydraulic Institute Standard HI 9.6.7,
shall be applied. Extrapolation is not recommended. Correction factors
for water are 1:1:1. Limitations on use of viscous liquid performance
correction chart are:
a) Use only for pumps of conventional hydraulic design, in the normal
operating range, with open or closed impellers. DO NOT use for
mixed flow or axial flow pumps or for pumps of special hydraulic
design for either viscous or non-uniform liquids.
b) Use only on Newtonian (uniform) liquids. Gels, slurries and other
non-uniform liquids may produce widely varying results,
depending on the particular characteristics of the liquids.
4.2.3 Rated suction pressure shall be the minimum suction pressure expected
under all operating conditions.
4.3.1 All pumps shall have continuous head rise from the rated head to shutoff.
4.3.2 For all pumps, the NPSH3 shall not exceed the specified NPSHA over
the range of minimum continuous stable capacity to 120% of the rated
capacity. At rated capacity, the NPSHA shall also exceed the NPSH3 by
a minimum margin of 1 meter (3.3 ft). For variable speed pumps, the
above NPSH requirements apply for all speeds required to meet the
specified operating conditions.
4.3.3 Vertical main firewater pumps shall have sufficient submergence and
NPSH to allow operating at 150% of the rated flow under the worst case
operating conditions (lowest water level and highest water temperature).
4.3.4 For all pumps, with exception of integrally geared, the suction specific
speed, based on the NPSH required for 3% first stage head drop at best
efficiency capacity, shall not exceed 12,000 in U.S. units. Higher values
maybe accepted with proven experience for at least 3 years of operation at
similar operating conditions such as NPSH margins and percentage of
operating point to BEP. Acceptance of higher values requires the approval
of the Standard Committee Chairman; Pumps, Seals, and Mixers.
4.3.5 For pumps with rated power per stage up to 300 HP, the cut water
clearance shall be at least 3% of the rated impeller blade radius for
diffuser designs and at least 6% of the rated impeller blade radius for
volute designs.
For all pumps with rated power per stage exceeding 300 HP, the radial
clearance between the diffuser vane or volute tongue (cut water) and the
periphery of the rated impeller blade shall be at least 4% of the rated
impeller blade radius for diffuser designs and at least 8% of the rated
impeller blade radius for volute designs.
4.3.6 Main firewater pumps shall have closed impellers. The minimum
internal dimensions of impeller passages shall not be less than 7.9 mm
(5/16 inch) for pumps rated up to 1,892 L/min (500 gpm) or 12.7 mm
Saudi Aramco: Company General Use
Page 14 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
𝑁𝑠 6000 800 2
− 0.125 × 𝐸𝑋𝑃 (1 − ) − 0.012 × ×[ ]
450 𝑁 𝑁𝑠
Where:
Q: is rated flow in GPM. For double suction impeller use full flow
per impeller (not per eye).
N: is shaft speed in revolution per minute RPM.
Ns: Specific speed (using GPM, feet & RPM). For multistage
pumps where the Ns is different for a number of stages, the
weighted average of specific speeds of the stages shall be used.
The following pumps are exempted from the above minimum efficiency
requirement:
i- Pumps with rated power of less than 37 kW (50 HP).
ii- Sealless pumps.
iii- Multiphase pumps.
iv- Pumps that operate for less than 10% of the time such as main fire
water pumps and storm water pumps.
If there are more than one dominant operating case with more
than 10% change in flow rate (excluding temporary conditions
such as partial turndown during T&I’s), then the highest
The normal flow for all dominant operating cases shall meet
the following:
i- For ASME, ISO, and manufacturer standard pumps, the
lowest normal flow shall not be less than 60% of the pump
BEP.
ii- For pumps complying with 31-SAMSS-004 and
31-SAMSS-685, the lowest normal flow shall be within the
preferred operating region of the pump (70% to 120% of
Best Efficiency Point)
4.3.8.2 The pump rated flow shall not be more than 110% of normal
flow point (i.e., 10% flow margin) except for recycle pump
applications, such as reflux or circulation pumps, which can be
have up to 20% margin above normal flow.
The MAWP of horizontal and vertical in-line pump casings and the
discharge heads of vertically suspended pumps shall be at least equal to
the sum of the maximum suction pressure and the differential pressure
developed at shut-off.
4.4.2 Casing design temperature shall be at least equal to the maximum flow
temperature. For pumps handling liquids which may auto-refrigerate,
the minimum design temperature shall be the lowest liquid temperature
which would occur as a result of rapid reduction in liquid pressure to
25% of the pump design operating pressure.
For flammable oily water sump, such as in bulk plants and tank
farms, vertical suspended pumps shall have mechanical seals.
For all pumps, the piping for mechanical seal flush, quench, vent, drain
and leakage detection system shall be in accordance with Table 1,
Mechanical Seal Selection Guide. The seal leakage systems, when
required by service conditions, shall be included in the scope of supply
of the pump Vendor unless otherwise specified.
4.6.1 Bearings shall be oil lubricated unless exempt from the scope of
31-SAMSS-004, 31-SAMSS-685, ASME or ISO. Anti-friction bearings
of pumps exempt from these specifications may be grease lubricated.
Horizontal main firewater pumps with antifriction bearings shall be
grease lubricated. With the exception of pumps having external lube oil
system, the following shall be installed on the bearing housings of oil
lubricated pumps:
Constant level oiler
Level sight glass
A drainable sight glass (installed under the bearing housing to drain
condensed water from the bearing housing).
Saudi Aramco: Company General Use
Page 18 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
4.6.2 The upthrust and downthrust values for vertical pumps quoted by the
Vendor shall be the maximum forces expected at any point over the
entire range of the pump performance curve.
It shall be verified that the values listed are within the bearing design
criteria of the driver or transmission unit which absorbs the rotor thrust.
4.6.3 When bearing housing vibration limits are not specified in the applicable
specifications for the pumps, bearing vibration shall not exceed 5.1
mm/sec (0.2 inch/sec RMS) when measured in both radial directions and
in axial direction and while operating at the rated operating point.
4.6.4 When bearing temperature limits are not specified in the applicable
specifications for the pumps, bearing temperature shall not exceed 85°C
(185°F) based on maximum ambient temperature of 50°C (122°F).
If bearing metal temperature monitoring is not practical, the sump oil
temperature rise shall not exceed 35°C (63°F).
4.7.2 Materials of construction for fluids not listed in Table 2 may be based on
information provided in publications, recommendations provided by
pump manufacturers, Saudi Aramco piping material selection, or other
Saudi Aramco: Company General Use
Page 19 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
4.8.2 For horizontal pumps, vertical in-line and vertically suspended pumps
having thrust bearings and not driven by reciprocating engines, flexible
disc pack or diaphragm type couplings are required.
4.8.3 Rigid adjustable spacer type couplings are required for vertical in-line
and vertically suspended pumps not having thrust bearings.
4.9 Drivers
4.9.1 The drivers for ASME and ISO pumps and for pumps to manufacturer's
standard design shall be sized in accordance with the following table:
4.9.2 For ASME, ISO pumps and pumps to manufacturer's standard design,
electric motor drivers shall be in accordance with 17-SAMSS-503, diesel
4.9.3 Main firewater pump drivers shall have a minimum of 5% power margin
over pump required power at 150% of rated flow
4.9.4 Motors for vertical firewater pumps shall be equipped with non-reverse
ratchet. Vertical firewater pumps driven through right angle gearbox
shall have the non-reverse ratchet in the gearbox.
The scope of the pump vendor shall be limited to the piping within the confines
of the baseplate such as the drain and vent piping.
4.11.1 The Vendor shall be responsible for the design of all auxiliary piping,
within the scope of the purchasing contract. Compliance with the
Saudi Aramco: Company General Use
Page 21 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
provisions of this specification does not relieve the Vendor from the
responsibilities for furnishing equipment of proper design and quality
to meet the specified operating service conditions.
4.11.2 Sizes, materials, pressure ratings and types of all components shall be
suitable for the intended service. The minimum size of auxiliary
piping and tubing shall be ½-inch.
4.11.3 All piping, tubing and valves shall be adequately supported and
fastened in a manner which facilitates replacement, prevents vibration,
and damage due to incidental loads which may occur during operation
or maintenance work.
4.11.4 The piping and fitting materials for the auxiliary piping shall comply
with Standard Drawing AD-036821. Alternative materials shall be
sent for the review and approval of the Standards Committee
Chairman; Pumps, Seals, and Mixers. Materials in sour services shall
be in accordance with NACE MR0175/ISO 15156.
4.11.5 For pumps in hazardous, flammable or toxic service, the pump casing
vent and drain piping shall be provided and shall have a block valves
immediately after the casing connection flange to reduce dead leg
length. If this location is not practical due to space limitation or other
reasons, the valves may be moved to the nearest possible location to
the casing. The valve material shall be as required for the service but
as a minimum shall be similar to the auxiliary piping material.
Valves shall be in accordance with API STD 602 Class 800 or
ASME B16.34 with rating as required.
Note: Self-venting pumps do not require vent piping.
4.11.6 Piping of 1-½ inch NPS or smaller shall be provided with firm, welded
gussets or braces in two perpendicular planes at the take-off connection
between the machinery or auxiliary equipment and the first block
(root) valve. Tubing shall be clipped with clamps.
4.11.7 All piping systems shall be provided with vent valves at highest points
and drain valves at lowest points. Horizontal pipe runs shall slope
gradually towards drain points. The minimum slope of drain lines
shall be at least 1:50.
4.11.9 Tubing is not allowed for auxiliary process piping (i.e., auxiliary
piping that is subjected to process fluid). Tubing is permitted only for
instrumentation piping. Instrumentation piping and tubing shall be per
34-SAMSS-831.
Tubing may be used instead of pipe beyond the first valve in non-
process auxiliary piping if the following conditions are met:
i. The maximum allowable pressure and temperature limits for
tubing are 4 MPa (600 psig) and 120°C.
ii. Minimum wall thickness for ½, ¾ and 1-inch tubing are 1.6, 2.4,
and 2.8 mm respectively.
iii. Tubing is not allowed for mechanicals seal piping and for low
temperature applications below -18°C.
iv. Connectors and adapters shall be compression type meeting
UNS S-31600 and ASTM A276.
4.11.10 Flanges, socket welding and threaded fittings shall be of the class,
rating or wall thickness to match the pipe ratings. Threaded
connections are only permitted for instrumentation connection and
mechanical seal gland plate unless approved by Standards Committee
Chairman; Pumps, Seals, and Mixers.
4.11.11 Auxiliary piping such as vent, drain, external flush and cooling water
piping shall be routed to or near the edge of the baseplate and shall
terminate with flanged connections.
4.11.12 Pipe bends shall have surfaces free of cracks and buckles. Flattening
of the cross section of bends shall not exceed 8% of the nominal pipe
diameter. Bending procedures and heat treatment requirements shall
be in accordance with ASME B31.3.
Saudi Aramco: Company General Use
Page 23 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
4.11.14 Hydrostatic testing with water or light oil is required for all fabricated
piping assemblies. Test pressures shall be in accordance with
ASME B31.3.
4.11.15 The minimum wall thickness of auxiliary piping and butt welding
fittings shall be Schedule 40 for sizes larger than 2-inch and
Schedule 80 for sizes 2-inch and smaller.
4.11.17 Seal welds on threaded connections shall cover all exposed threads
after the joint has been tightened to full thread engagement. The fillet
seal weld shall have a minimum throat thickness of 3 mm and shall
merge smoothly into the pipe metal outside of the thread. Threaded
joints to be seal welded shall be fully cleaned and made up dry without
joint compounds or PTFE (Teflon) tape.
4.11.18 Dissimilar metal welds between ferritic steel and either austenitic
stainless steel, duplex stainless steel, or nickel-based alloys as well as
use of stainless steel or nickel-based filler metals on ferritic steel are
not permitted for pressure containing welds in sour service.
4.11.20 Gaskets for raised flanges shall be spiral-wound, Type 316 stainless
steel. Gaskets for ring joint flanges shall be soft iron octagonal ring.
Gaskets containing asbestos are not permitted.
4.12 Vertical firewater pumps shall be provided with suction strainer. The strainer
shall have an open area of at least 400% of the minimum inlet area to the first
stage. The strainer openings shall not permit the passage of 7.9 mm (5/16 inch)
sphere for pumps rated up to 1,892 L/min (500 gpm) or 12.7 mm (0.5 inch)
sphere for larger flow pumps. The distance between the bottom of the strainer
and the bottom of the wet pit should be one-half of the pump bowl diameter but
not less than 12 in. (305 mm).
4.13 Pitot tube pumps (rotating casing pump designs) shall meet the below requirements:
a. As a minimum, the Pick-up tube material shall be martensitic precipitation
hardening stainless steels 17-4PH. 17Cr4Ni ASTM A564 (DIN 1.4549)
grade 630 AISI 630 H1150M, with hardness from 260 to 310 BHN.
b. The pump shall have permanent duplex filter with 100 mesh and a
differential pressure transmitter to alarm on high differential pressure
c. Maximum pump speed shall not exceed 5,000 RPM unless approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers
4.14 Manufacturer standard for external coating is acceptable provided that vendor
coating is suitable for environmental conditions of the site. As a minimum, the
coating system shall be equivalent to ISO 12944-5, corrosion category C5-M for
offshore and C4 for onshore. The primer binder shall be epoxy or Ethyl silicate.
5 Installation
5.1 Layout
5.1.2 Provisions for isolation, venting and draining the pump shall be installed
to permit internal inspection, repair or dismantling.
5.1.3 Wherever possible, when more than one identical pump train is required,
the design of the equipment trains, the auxiliary baseplate(s), the
connecting piping, cabling, wiring, etc., shall be identical in layout,
construction, and accessibility.
5.3.1 A minimum flow recycle line shall be provided in line with Appendix C.
The use of pressure measurement instead of flow measurement for pump
flow protection is not acceptable unless approved by the Standards
Committee Chairman; Pumps, Seals, and Mixers.
5.3.2 For pumps with common recycle line, the recycle line shall be connected
to the pump discharge piping downstream of the check valves (i.e., on
the main discharge header). Where protection against reverse flow from
the discharge header to the recycle line is required, another check valve
shall be installed on the discharge header downstream of the recycle line
take-off connection.
For pumps with individual recycle line, the recycle lines shall be
connected to the pump discharge piping upstream of the check valve.
Flow element for the minimum flow recycle system, shall measure the
flow in the discharge piping upstream of the recycle line take off
connection.
5.3.3 Recycle lines shall be directed back to the suction source. If this is not
possible, the recycle lines may be connected back to the suction line if
the recycled liquid is cooled down to allow continuous operation at full
Saudi Aramco: Company General Use
Page 26 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
minimum flow recycle mode where all the pumped liquid is recycled.
Except for intermediate pipeline pumping stations, directing the recycle
line to suction line requires the approval of the Standards Committee
Chairman; Pumps, Seals, and Mixers.
5.4 The Vendor's General Arrangement (G.A.) or outline drawings shall include all
required data including nozzles, shaft centerline and baseplate foundation bolt
coordinates to install the pump on its foundation. G.A. drawings shall also show
Buyer's references and the main rating data of equipment components.
5.6 Variable speed high energy pumps, as defined in 31-SAMSS-004, shall have
high flow protection alarm with variable set point based on pump speed.
The alarm shall activate when the pump flow reaches above 120% of best
efficiency point flow of the corresponding operating speed curve.
5.7 For between bearing pumps in high temperature applications and when a warm-
up is recommended by pump manufacturer, the warm up line shall be provided.
The warm up line shall be connected to the pump casing bottom unless approved
by Standards Committee Chairman; Pumps, Seals, and Mixers.
6.1 Pumps requiring testing per Table 3 of this standard shall be tested within 3%
of the rated speed. If this is not feasible, the Vendor shall advise and justify
his proposed vibration acceptance criteria at his specified de-rated speed.
Test speed beyond the 3% limit requires the approval of the Standards
Committee Chairman; Pumps, Seals, and Mixers. Vibration data and bearing
temperatures shall be recorded.
6.4 Vibration and temperature measurements shall be taken and recorded for all
certified or witnessed tests of pumps complying with 31-SAMSS-004,
31-SAMSS-685, ASME, and ISO pumps and pumps in firewater and molten
sulfur services.
6.6 Sump model testing shall be conducted for all sea water intake systems unless
specifically waived by the Standards Committee Chairman; Pumps, Seals, and
Mixers.
6.7.1 Pump tests shall be conducted in accordance to HI 14.6. Test speed shall
be done at rated speed (±4% speed deviation is permitted).
6.7.2 NPSH3 test shall be conducted on at least three points; minimum flow,
rated flow and on 150% of rated flow. For horizontal pumps, NPSH3 at
150% of rated flow shall not exceed 5.8 m (19 ft). For vertical pumps,
the minimum submergence test may be used in lieu of NPSH test if it is
more restrictive (i.e., pump performance will drop due to minimum
submergence requirement before any drop of pump performance due to
low NPSH margin).
Unless otherwise approved by the Standards Committee Chairman; Pumps, Seals, and
Mixers, quotations for pumps and pump-motor trains of 373 kW (500 HP) and larger that
are in accordance with 31-SAMSS-004 (with the exception of pumps in storm water and
firewater services) shall be evaluated on the basis of a Life Cycle Cost (LCC) as
explained in SAEP-341. This cost is composed of initial cost of the pump plus the
present worth of the consumed power cost over an operating period of 20 years, using an
Evaluation Factor (EF), which should be shown in the data sheet that goes with the
quotation request. The Life Cycle Cost of the pump shall be determined using the life
cycle cost spreadsheet LCC-001. The Life Cycle Cost of the pump-motor trains shall be
determined using the life cycle cost spreadsheet LCC-002.
Note: Normal operating point shall be specified on the data sheet. Pump power at normal
operating point shall be specified by the pump manufacturer on the data sheet and
performance curve.
Saudi Aramco: Company General Use
Page 28 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
Revision Summary
13 July 2014 Major revision
23 March 2017 Major revision to align with new and updated company standards. In addition, other major
enhancements were added based on latest project observations, deviations, and comments.
Below is the summary of the main changes:
(1) Modify the entire standard and its selection chart to include the heavy duty sealless pumps
per the new 31-SAMSS-685 for extremely hazardous applications.
(2) Increase the driver power limit for integrally geared pumps from 150 HP to 200 HP.
(3) Mandate closed impeller design for vertical suspended pumps in sulfur applications.
(4) Increase the suction specific speed limit from 11,000 to 12,000.
(5) Perform major modifications to the seal selection table to account for highly hazardous
liquids and to have better alignment with international standards and practices.
(6) Eliminate the reference to auxiliary piping standard 01-SAMSS-017 which is planned for
deletion by end of 2016 and align with international standard requirements.
(7) Add new standard requirements addressing Pitot tube pump design.
(8) Allow international standard coating for pumps as per manufacturer normal procedures.
(9) Add a new requirement to prevent excessive pump oversizing.
(10) Allow reduced head rise and cut water clearance for low and medium size pumps.
This should improve pump efficiency and provide better pump selection without jeopardizing
reliability.
(11) Amend the minimum flow recycle line requirement to allow common recycle instead of
individual recycle when there is satisfactory field experience.
(12) Mandate minimum efficiency for pumps above 50 HP.
(13) Mandate conducting life cycle assessment for pumps above 500 HP instead of 1,000 HP.
(14) Add a new appendix for terms and definitions.
Note 1: Sealless pumps may be used in line with Appendix A for single stage pumps.
Note 2: For sour water and sour hydrocarbons with H2S concentrations less than 5,000 PPM, seal
code C2A2A (seal configuration 2CW-CS) with Plan 32/75 may be used when all the following
conditions are met:
The flushing system for Plan 32 shall be reliable and available at all times including plant
startup,
Economical study justifies the use of Plan 32 over Plan 53B taken into account the cost of
reprocessing the continuous supply of flushing fluid.
Plan 32 external flush is non-flashing liquid and it does not have more than 500 PPM of
H2S.
Note 3: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows seal
is an acceptable alternative to the standard Type A seal in applications where the maximum
seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 4: For DGA, ADIP, and other amine services, Type C bellows seal or Type A seal with FFKM
elastomers shall be used. For other services, ensure using compatible elastomers.
Note 5: For overhung pumps, Plan 53B shall be used. For between bearing pumps, Plan 53B or 54
shall be used. Plan 53B and 54 shall comply with 31-SAMSS-012.
Note 6: Consult Standards Committee Chairman; Pumps, Seals, and Mixers for seal and flush
selection if seal chamber pressure exceeds 1,830 kPa abs (265 psia).
Note 7: Plan 53B and 54 shall comply with 31-SAMSS-012.
Note 8: Additional process side flush plans (such as 01, 02, 11, 13, 21, etc.) may be used in parallel
with Plan 53B and 54 when recommended by seal vendor or mandated by 31-SAMSS-012.
Non-flashing Dry Hydrocarbon Services; containing up to 0.2% water and 500 PPM of
H2S by weight and having Vapor Pressure ≤ 100 kPa abs (14.7 psia) at maximum
Pumping Temperature.
Maximum Pumping -7 to 93
Temperature °C (°F) (20 to 200)
C1A1A
Seal Code
C2A1A
1 for ASME and ISO Pumps
Category
2 for API Pumps
Arrangement 1
Seal Type A (Notes 1 & 2)
API Seal Configuration 1CW-FL (Note 1)
Special Materials (Note 3)
Horizontal Pumps: 11/61
Seal Flush Plan
Vertical Pumps: 13/61
without Suspended Solids
(Note 4)
Horizontal Pumps: 31/61
Seal Flush Plan
Vertical Pumps: 32/61 or 31/13/61
with Suspended Solids
(Note 5)
Quench Plan / Type 51 (Methanol) (Note 6)
Seal Leakage Detection Plan 65A (Level Transmitter) (Notes 7 & 8)
Note1: If the pumped liquid is MTBE or gasoline containing MTBE, the seal shall be Type C
(Bellows) and the seal configuration shall be 1CW-FL.
For Category 1 seals in services other than gasoline or MTBE, the seal shall be 1CW-FX.
Note 2: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows
seal is an acceptable alternative to the standard Type A seal in applications where the
maximum seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 3: If the pumped fluid is non-sour and auto-refrigerant, Nitrile elastomers shall be used.
Note 4: For vertical in-line pumps having their impellers with balance holes, Seal Flash Plan 11/61
shall be used.
Note 5: API Plan 31 shall be used only if the pump differential pressure exceeds 175 kPa (25 psi).
Otherwise, Plan 32 flush with a compatible clean liquid shall be used.
Note 6: The methanol feed system, Plan 51, is only required for pumping temperature lower than
0°C (32°F) and it is not intended to provide a continuous flow of methanol. It is used
immediately prior to start-up to prevent or eliminate icing on the atmospheric side of the
primary seal. It shall be connected to the atmospheric side of the dry-running backup seal.
Note 7: Pumps in bulk plants, truck unloading pumps, and lube oil pumps do not require seal leak
detection system.
Note 8: If level transmitter cannot be used, level switch would be acceptable if approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers.
Non-flashing Dry Hydrocarbon Services; containing up to 0.2% water and 500 PPM of
H2S by weight and having Vapor Pressure ≤ 100 kPa abs (14.7 psia) at maximum
Pumping Temperature.
Note 1: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows
seal is an acceptable alternative to the standard Type A seal in applications where the
maximum seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 2: Fixed clearance bushing (FX) shall be used instead of floating bushing (FL) for ASME and
ISO pumps in services below 149°C (300°F).
Note 3: 2CW-CS with seal leak detection Plan 75 shall be used if the external flush liquid (Plan
32) will flash upon seal leakage.
Note 4: API Plan 41 shall be used only if the pump differential pressure exceeds 175 kPa (25 psi).
Otherwise, Plan 32 flush with a compatible clean liquid shall be used.
Note 5: If level transmitter cannot be used, level switch would be acceptable if approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers.
Note 6: Consult Standards Committee Chairman; Pumps, Seals, and Mixers for seal and flush
selection if seal chamber pressure exceeds 1,830 kPa abs (265 psia).
Note 7: Seal flush Plan 02 shall be used for asphalt services and may be acceptable for crude
vacuum bottom pumps subject to review and approval by the Standards Committee
Chairman; Pumps, Seals, and Mixers. For seal flush Plan 02, no seal leak detection is
required.
Note 8: If the liquid is above auto-ignition temperature; then, the seal code shall be C2A3C with Plan 53B
or 54 in accordance with 31-SAMSS-012.
Flashing Dry Hydrocarbon Services; containing up to 0.2% water and 500 PPM of H2S
by weight and having Vapor Pressure > 100 kPa abs (14.7 psia) at maximum Pumping
Temperature.
Note 1: For gasoline services up to 50°C (120°F), refer to seal selection guide under “Non-flashing
Dry Hydrocarbon Services; containing up to 0.2% water by weight and having Vapor
Pressure ≤ 100 kPa abs (14.7 psia) at Pumping Temperature”
Note 2: f approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows
seal is an acceptable alternative to the standard Type A seal in applications where the
maximum seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 3: If a 2NC-CS seal configuration is supplied, the seal flush Plan shall be 02.
2NC-CS seals are limited to applications above 0°C (32°F).
Note 4: If the pumped fluid is non-sour and auto-refrigerant, Nitrile elastomers shall be used.
Note 5: API Plan 31 shall be used only if the pump differential pressure exceeds 175 kPa (25 psi).
Otherwise, Plan 32 flush with a compatible clean liquid shall be used.
Note 6: The methanol feed system, Plan 51, is not intended to provide a continuous flow of
methanol. It is used immediately prior to start-up to prevent or eliminate icing on the
atmospheric side of the primary seal. It shall be connected to the atmospheric side of the
dry-running backup seal.
Note 7: Plan 75 shall be used when the pumped fluid condenses at ambient temperature such as
hydrocarbon condensate.
Flashing Dry Hydrocarbon Services; containing up to 0.2% water and 500 PPM of H2S
by weight and having Vapor Pressure > 100 kPa abs (14.7 psia) at maximum Pumping
Temperature.
Wet Crude or wet hydrocarbon Services; containing more than 0.2% water and less than
500 PPM of H2S by weight.
Vapor Pressure ≤ 100 kPa abs Vapor Pressure > 100 kPa abs
(14.7 psia) at Pumping (14.7 psia) at Pumping
Temperature Temperature
Maximum Pumping <176 <176
Temperature °C (°F) (<350) (<350)
Seal Code C2A1A C2A2A
Category 2 2
Arrangement 1 2
Seal Type A (Note 1) A (Note 1)
API Seal Configuration 1CW-FL 2CW-CS
Special Materials Two hard faces (Note 4) Two hard faces (Note 4)
Horizontal Pumps: 32/61 or 53B Horizontal Pumps: 32/61 or 53B
Seal Flush Plan Vertical Pumps: 32/ or 53B Vertical Pumps: 32/61 or 53B
(Notes 2 & 3) (Notes 2 & 3)
Quench Plan/Type None None
Seal Leakage 65A (Level Transmitter)
75
Detection Plan (Note 5)
Note 1: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows
seal is an acceptable alternative to the standard Type A seal in applications where the
maximum seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 2: For Plan 32, the external flush fluid shall be dry crude, sea water, or any other water with
a TDS less than 30,000 PPM. External flush shall be a non-flashing liquid with a
temperature not exceeding 60°C (140°F) and it shall not contain more than 500 PPM of
H2S.
For plant startup, pumps shall be supplied with a Plan 31 in addition to Plan 32 seal flush
if external flush is not available during plant startup. A check valve shall be installed in
both the Plan 31 and Plan 32 seal flush lines to prevent flushing fluid from entering the
piping system not in use.
Note 3: If an external source of compatible flush fluid is not available then an Arrangement 3 seal
shall be used; Seal Code C2A3A. Flush Plan 54 or 53B shall be used for between
bearing pumps and Plan 53B shall be used for overhung pumps. The seal Plan 54 and
Plan 53B shall comply with 31-SAMSS-012.
Note 4: Silicon Carbide versus Carbon seal face material combination might be used when:
Saudi Aramco experience is satisfactory on using identical materials in identical
service, or
Pump speed is not higher than 3,600 RPM and it is clean crude oil service and not in a
GOSP service.
Note 5: If level transmitter cannot be used, level switch would be acceptable if approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers.
Dry Crude Services; containing up to 0.2% water and less than 500 PPM of H2S by weight.
Vapor Pressure ≤ 100 kPa abs Vapor Pressure > 100 kPa abs
(14.7 psia) at Pumping (14.7 psia) at Pumping
Temperature Temperature
Maximum Pumping <176 <176
Temperature °C (°F) (<350) (<350)
C1A1A C1A2A
Seal Code
C2A1A C2A2A
1 for ASME and ISO Pumps 1 for ASME and ISO Pumps
Category
2 for API Pumps 2 for API Pumps
Arrangement 1 2
Note 1: If approved by the Standards Committee Chairman; Pumps, Seals and Mixers, a bellows seal
is an acceptable alternative to the standard Type A seal in applications where the maximum
seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 2: API Plan 31 shall be used only if the pump differential pressure exceeds 175 kPa (25 psi).
Otherwise, Plan 32 flush with a compatible clean liquid shall be used
Note 3: Silicon Carbide versus Carbon seal face material combination might be used when:
Saudi Aramco experience is satisfactory on using identical materials in identical service, or
Pump speed is not higher than 3,600 RPM and it is clean crude oil service and not in a
GOSP service.
Note 4: If level transmitter cannot be used, level switch would be acceptable if approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers.
Maximum Pumping Up to 70
Above 70 (158)
Temperature °C (°F) (Up to 158)
Vapor Pressure ≤ 100 kPa abs (14.7 psia) Any
C1A1A C1A2A
Seal Code
C2A1A C2A2A ( Notes 1 & 6)
1 for ASME and ISO Pumps 1 for ASME and ISO Pumps
Category
2 for API Pumps 2 for API Pumps
Arrangement 1 2 (Notes 1 & 6)
Note 1: Arrangement 1 with Plan 65A shall be used when seal flush Plan 32 is used and the
flush liquid has less than 50 PPM of H2S.
Note 2: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows
seal is an acceptable alternative to the standard Type A seal in applications where the
maximum seal chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 3: API Plan 31 shall be used only if the pump differential pressure exceeds 175 kPa (25 psi).
Otherwise, Plan 32 flush with a compatible clean liquid shall be used.
Note 4: Plan 21/61 may be used if liquid temperature is below 93°C. The heat exchanger for the
seal flush plans 21 and 23 shall be sized to maintain the flush fluid at or below 60°C
(140°F)
Note 5: Plan 32 flush shall be raw water (with TDS less than 30,000 PPM) or sea water without
suspended solids. Plan 32 flushing liquid temperature shall not exceed 60°C (140°F).
Note 6: If water temperature is above 176°C, C2A2C shall be used.
Note 4: For water condensate up to 77°C (170°F), seal flush plans 11 and 13 might be used for
horizontal and vertical pumps, respectively. For other services, the heat exchanger for the
seal flush plans 21, 23, and 41 shall be sized to maintain the flush fluid at or below 60°C
(140°F).
Note 5: Plan 32 flush shall be raw water (less than 30,000 PPM TDS) or sea water without
suspended solids. The flush liquid shall be cooled to 60°C (140°F) or below and shall
contain less than 50 PPM of H2S.
If Plan 32 is not available then an Arrangement 3 seal shall be used; Seal Code C2A3A,
Flush Plan 54 or 53B. Plans 53B and 54 shall comply with 31-SAMSS-012.
Note 6: API Plan 31 and 41 shall be used only if the pump differential pressure exceeds 175 kPa
(25 psi). Otherwise, Plan 32 flush with a compatible clean liquid shall be used.
Note 7: If level transmitter cannot be used, level switch would be acceptable if approved by the
Standards Committee Chairman; Pumps, Seals, and Mixers.
Note 1: Lean amine: is a non-flashing liquids that will not cause sudden release of H2S in case of leakage
to atmosphere. It typically comes from the amine regeneration unit in which the rich amine is
treated to release most of the H2S and CO2 in it. Lean amine can have high H2S concentration
exceeding in some cases 500 PPM.
Note 2: For vertical pumps in open sump applications, C2A1C 13/61 is acceptable.
Note 3: Consult Standards Committee Chairman; Pumps, Seals, and Mixers for seal and flush selection
if seal chamber pressure exceeds 1,830 kPa abs (265 psia).
If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, Type A seal with
FFKM elastomers may be used.
CAUSTIC SERVICES
(Sealless pumps shall be used for this service up to 225 kW (300 HP). For larger pump size,
mechanical seal shall be as below).
Maximum Pumping Up to 93 > 93
Temperature °C (°F) (Up to200) (> 200)
C1A1A C1A1A
Seal Code C2A1A C2A1A
1 for ASME and ISO Pumps 1 for ASME and ISO Pumps
Category 2 for API Pumps 2 for API Pumps
Arrangement 1 1
Seal Type A (Note 1) A (Note 1)
Seal Configuration 1CW-FL 1CW-FL
Special Materials Ethylene propylene elastomers FFKM elastomers
Horizontal Pumps: 11/62 Horizontal and Vertical
Seal Flush Plan
Vertical Pumps: 13/62 Pumps: 23/62 or 21/62
Quench Plan/Type Water Water
Seal Leakage Detection None None
Note 1: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows seal is
an acceptable alternative to the standard Type A seal in applications where the maximum seal
chamber pressure does not exceed 1,830 kPa abs (265 psia).
Saudi Aramco: Company General Use
Page 40 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
Note 1: If approved by the Standards Committee Chairman; Pumps, Seals, and Mixers, a bellows seal is
an acceptable alternative to the standard Type A seal in applications where the maximum seal
chamber pressure does not exceed 1,830 kPa abs (265 psia).
Note 1: Mechanical seal vendor shall demonstrate successful experience with the proposed seal.
Pumps equipped with hydrodynamic seal (no mechanical seal) are acceptable alternative to
mechanically sealed pumps.
Saudi Aramco: Company General Use
Page 41 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
Note 2: The use of hydrodynamic seal instead of mechanical seal in continuously running pumps is
acceptable. In this design and during pump operation, one or more auxiliary impellers are
installed in the stuffing box to generate reverse hydrodynamic head in the stuffing box that will
relieve the pump stuffing box completely from its pressure; thus, preventing liquid leakage to
atmosphere.
The use of magnetic drive or canned motor sealless pumps shall be approved by the Standards
Committee Chairman; Pumps, Seals, and Mixers.
Note 3: The drain piping shall be steam traced to the edge of the baseplate and shall terminate with
flange.
11. For seals not in accordance with 31-SAMSS-012, all process wetted metal components shall be
of the following materials with the exception of seal springs and bellows:
Metal parts not in contact with the medium pumped shall be 316 SS.
Seal springs shall be of Hastelloy C-276, C4, C22 or equivalent ASTM material
If bellows seals are provided, the bellows material shall be Inconel 625 or 718.
12. Plan 32 shall be provided with a solenoid valve. The valve shall be set to automatically open two
minutes before pump startup (i.e., startup permissive). It shall also automatically close 30
minutes after the pump is shutdown in order to flush the seal and pump cavity.
13. Seal Plan 53B system shall have a low pressure trip. The configuration of the system shall allow
for at least 4 days of normal leakage between the refill set point and the trip set point.
14. For all seal plans with cooling water, closed sight flow indicators shall be furnished in each
cooling water outlet line.
15. When external circulation pump is provided for Plan 53, the seal system shall include a method
to detect circulation pump failure such as low barrier flow measurement, high barrier liquid
temperature upstream the cooler or low current on the external circulation pump motor. If a low
current is used, it shall not be included in the pump vendor's scope of supply.
Material Code
Notes:
(1) Up to 0.2% water by weight.
(2) HKA2 and VKA material codes shall be used if the normal pumping temperatures is not less
than 0°C and when the lowest transient, starting or venting conditions will not reduce the
casing temperature below -18°C. Otherwise, use HK and VK material codes.
(3) Sour service shall be as defined in NACE MR0175/ISO 15156. Material in sour water shall
meet NACE MR0175/ISO 15156.
(4) Greater than 0.2% water by weight.
(5) If the pump liquid contains more than 50 PPM of chloride with pumping temperature above
50°C or if the TDS is higher than 3,000 PPM, HSI material code shall not be used and the
Standards Committee Chairman; Pumps, Seals, and Mixers shall be consulted regarding
selection of the material.
(6) Alternative proven materials for the specific service, based on existing satisfactory long term
experience, may be used when approved by Operating Department and the Standards
Committee Chairman; Pumps, Seals, and Mixers.
(7) The Standards Committee Chairman; Pumps, Seals, and Mixers shall be consulted regarding
selection of specific material. For sodium hypochlorite services, suitable nonmetallic or
titanium construction shall be used. Non-metallic pump construction may be proposed for
pump with driver rating up to 112 kW (150 HP) subject to the review and approval of the
Standards Committee Chairman; Pumps, Seals, and Mixers.
(8) The material selection for the cooling tower circulation pump shall be based on the expected
TDS in the liquid in line with the above table “Other water” columns.
(9) If the pump liquid contains more than 80,000 PPM of chloride, HSZ material code may not be
suitable. The Standards Committee Chairman; Pumps, Seals, and Mixers shall be consulted
regarding selection of the material.
Notes:
(1) All tests for pumps in firewater jockey and molten sulfur services shall be certified.
(2) If more than one pump on the same Purchase Order of identical type, design, and design
conditions are presented for inspection as a lot, the test requirements shall be as follows:
a. For high energy pumps, as defined by 31-SAMSS-004, and for main firewater pumps, all
pumps shall be fully witness tested.
b. For low energy pumps, one pump, selected at random shall be fully witness tested.
The remaining pumps shall be fully shop tested and test certificates shall be provided;
(3) All certified and witnessed pump performance/running tests shall be conducted using
calibrated drivers.
(4) Open pit vertical sump pumps require a minimum submergence test in lieu of an NPSH test.
Firewater pumps shall be NPSH tested at minimum flow, rated flow and 150% of rated flow.
For vertical firewater pumps, the minimum submergence test may be used in lieu of an NPSH
test if it is more restrictive (i.e., pump performance will drop due to minimum submergence
requirement before any drop of pump performance due to low NPSH margin).
Multiphase pumps do not require NPSH testing.
(5)
a. NPSH testing is required on all pumps where NPSH margin (NPSHA over NPSH3) at
120% of the rated flow is less than 1 meter (3.3 feet).
b. For all other pumps, only one pump of a set of identical pumps requires NPSH testing.
(6)
c. Witnessed NPSH testing shall be performed for all high energy pumps, as defined in
31-SAMSS-004, and for main firewater pumps.
d. All vertically can mounted pumps and all pumps where the NPSH margin (NPSHA over
NPSH3) at 120% of the rated flow is less than 1 meter (3.3 feet) shall be fully NPSH
tested and only one pump of a set of identical pumps is required to be witnessed.
e. For all other pumps, only one pump of a set of identical pumps shall be NPSH tested
and witnessed.
N Driver ≤ 37 KW
(50 HP) in Domestic START HERE
sewage or community
Appendix A - Centrifugal Pump water?
Single stage OH or VS pump Y Go to
Selection Guide for highly Hazardous liquid as
defined in Appendix D
Sheet 3
Y
Sheet 3
N Y
Rich Amine/DGA Amine, DGA & TEG
Service ? Service?
Y
N
SAES-G-005 compliance is not
required. If self priming pump type is
Y used, the following shall apply:
Domestic sewage or
sewage effluent service • Suction lift shall not be
below 300 HP? more than 6 meters (20 feet).
• Automatic air release valve or
N continuous bleed with orifice
shall be provided upstream the
check valve in the discharge piping.
Y
Sulfur Service Below
300 HP?
N N N
N
VERTICAL IN-LINE
Rated Suction Pressure Y PUMP COMPLYING
Exceeds 520 kPa gauge (75 psig)? WITH
31-SAMSS-004
Liquid
Space limitation Y Min Temp. less than 0°C (32°F) or Y VERTICAL SUSPENDED
does not Permit Horizontal Max Temp. higher than 120°C OR DOUBLE CASING
(250°F)? PUMP COMPLYING
installation?
WITH 31-SAMSS-004
N N
Liquid Vapor
Y
Suction conditions Press ≥ 205 kPa abs (30 psia)
prohibit the use of horizontal @ max. Operating temp?
HORIZONTAL PUMP
pump?
COMPLYING WITH
N 31-SAMSS-004
Use vertical N
lined shaft
Pump type Y
Driver nameplate exceeds
112 kW (150 HP)? API 610
N
HORIZONTAL END
PUMP SHALL BE VERTICAL IN-LINE
SUCTION PUMP
VENDOR PUMP COMPLYING
COMPLYING WITH
STANDARD WITH ASME
Saudi B73.2 Company
Aramco: General Use
DESIGN
ASME B73.1 OR
ISO 2858 & ISO 5199
OR ISO 5199 ASME/ISO
Page 47 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
N
Y
Storm water Suction lift is more
service ? than 6 m (20 ft) ?
N
N Y N
N N
Horizontal Self-Priming pump
can meet the operating Driver nameplate exceeds
conditions including NPSH? 112 kW (150 HP)?
Y
Y
Y
Rated Discharge Pressure Vertically
exceeds 1900 kPa gauge (275 psig)? suspended pumps in oily water Y
or storm water services
with driver nameplate below
N 225 kW (300 HP)?
Y
Rated Suction Pressure exceeds N
520 kPa gauge (75 psig)? PUMP SHALL BE
HORIZONTAL SELF-
PRIMING TO
VENDOR STANDARD
N DESIGN
Y
Driver nameplate exceeds
112 kW (150 HP)?
Y
Min Liquid Temp. less than 0°C (32°F)
Or Max. Temp. higher than 65°C
(150°F)?
Y Liquid Vapor
Press ≥ 175 kPa abs (25 psia) at max.
operating temp?
Y
Space limitation Y
Suction conditions does not permit Horizontal
prohibit the use of horizontal installation?
pump?
N N
Y Suction conditions Y
Space limitation prohibit the use of horizontal
does not permit Horizontal pump?
installation?
To Sheet 1*
Y Pump with dual
presureised seal?
Y N
Space limitation Y
Y does not permit Horizontal
Viscosity below 0.3 cP installation?
or above 200 cP?*
N N
SEALLESS PUMP PER Y
VENDOR STANDARD Y Autoignition or Autoignition or Y
Vertical Suspended Pump H2S >10,000 PPM ?
DESIGN AND MEET H2S >10,000 PPM ?
With Driver ≤112 KW (150
SAES-G-005
REQUIREMENTS HP)
N
N
Y N
Liquid above Autoignition
Temperature?
N
VERTICAL IN-LINE
Rated Discharge Pressure Y SEALLESS PUMP**
Exceeds 1900 kPa gauge (275 psig)? COMPLYING
WITH
N 31-SAMSS-685
HORIZONTAL HORIZONTAL
VERTICAL IN-LINE
SEALLESS PUMP**
VERTICAL IN-LINE
CANNED MOTOR SEALLESS PUMP ** CANNED MOTOR ASME/ISO
COMPLYING WITH PUMP COMPLYING WITH PUMP COMPLYING
ASME B73.3 COMPLYING WITH ASME B73.3 WITH ASME B73.3
OR ISO 15783 ASME B73.3 OR ISO 15783 OR ISO 15783
OR ISO 15783
START HERE
No
Yes
Pump rated power 746 kW (1,000 HP)
No
No No
No
No Yes Truck Loading
Pumps
No
Design for
No Recycle Line Design for Common
Individual
Required Recycle Line
Recycle Lines (1)
(*) Recycle line is required to protect the pump if there is a potential for running below the minimum
continuous stable flow due to process conditions, such as loading pumps and pumps with discharge
level control valves, or due to difference in running speeds for pumps running in parallel. It also
required for medium and large pumps to simplify the pump startup and to allow testing the pumps on
recycle mode.
General Notes:
(1) A common recycle line may be used instead of individual recycle lines if there is existing satisfactory
experience and subject to the review and concurrence of the plant operation and the Standards
Committee Chairman; Pumps, Seals, and Mixers.
(2) When a minimum recycle line is specified for pumps with driver rating more than 37 kW (50 HP), the
recycle line shall have a control valve.
For pumps with diver rating less than 37 kW (50 HP), a control valve or an automatic recirculation
valve (ARV) shall be used. Alternatively, a flow control orifice may be used if it is justified economically
or if the pump is sized/selected to have continuous recycle due to process requirement. The economic
justification document shall be available for the Standard Committee Chairman; Pumps, Seals, and
Mixers review upon request.
(3) The requirement for minimum flow recycle may be waived, subject to concurrence by the operating
department and the Standard Committee Chairman; Pumps, Seals, and Mixers, when all of the
following conditions are met:
a) There is no process need or potential of running at low flow
b) Operational requirements are flexible enough to permit process interruption and pump shutdown
c) The recycle line is not needed to start-up or switch-over the pumps
d) Adequate pump protection is provided to shut down the pump at low flow conditions.
(4) Low lift pumps and other pumps on un-pressurized service, do not require minimum flow recycle lines.
(5) This appendix represents the minimum standard requirement. If the process conditions require the
use of individual recycle lines; then, individual recycle lines shall be provided even if this does not meet
the above flowchart.
Auxiliary Piping: The piping connected to an equipment to support its function such as vent,
drain, cooling water, lube oil and seal flushing lines.
Flammable Liquid: A liquid that has a flash point equal to or less than 54°C (130°F).
Examples of such fluids are: stabilized crude, gasoline, Jet A-1, Jet JP-4, Jet JP-8, C6 and
lighter feed and blending stocks, and methanol. For purposes of this standard, a combustible
liquid stored or processed at a temperature equal to or higher than 8°C (15°F) below its
flashpoint shall be considered to be a flammable liquid (refer to SAES-B-005).
Jockey Pumps: They are the pressure maintenance / make-up pumps. One pump is typically
running continuously to maintain the pressure on the fire protection system/header between
preset limits when the system is not flowing water.
Lean Amine: A non-flashing amine liquids that will not release H2S in case of leakage to
atmosphere. It typically comes from the amine regeneration in which the rich amine is treated
Saudi Aramco: Company General Use
Page 53 of 54
Document Responsibility: Pumps, Seals, and Mixers Standards Committee SAES-G-005
Issue Date: 14 March 2017
Next Planned Update: 14 March 2020 Centrifugal Pumps
to release most of the H2S and CO2 in it. Lean amine can have high H2S concentration
exceeding in some cases 500 PPM.
Low-flow High-head Pump Application: Shall be defined as pumps with flow rate up to
250 GPM and with differential head higher than 800 ft.
Main Firewater Pump: A pump that is a provider of liquid flow and pressure dedicated to
fire protection. These pump are normally on standby condition and will start in case of fire.
Normal operating point: The point at which the pump is expected to operate under normal
process conditions.
Raw Water: Well water with TDS not more than 30,000 PPM.
Sour Water Service for Material Selection: Shall be as defined by NACE MR0175/
ISO 15156.
Sour Water Service for Seal Selection: Any service with more than 50 PPM of H2S.