Keor MOD: Installation and Maintenance Manual
Keor MOD: Installation and Maintenance Manual
Part. LE11406AF-02/24-01 WP
Keor MOD
EN ENGLISH 3
2
Installation and maintenance manual
Keor MOD
Table of Contents
1 Introduction 5
1.1 Purpose of the manual 5
1.2 Symbols in the manual 5
1.3 Where and how to keep the manual 5
1.4 Update of the manual 6
1.5 Manufacturer’s liability and guarantee 6
1.5.1 Guarantee terms 6
1.5.2 Extension of the guarantee and maintenance contracts 7
1.6 Copyright 7
3
Table of Contents
6. Maintenance 86
6.1 Preventive maintenance 86
6.2 Periodical checks 86
6.3 Ordinary maintenance 87
6.3.1 Hot-swap procedure for the replacement of power modules 87
6.3.2 Installation/replacement of power modules with the UPS in maintenance bypass mode 90
6.3.2.1 Setting the UPS in maintenance bypass mode 90
6.3.2.2 Installation/replacement of power modules 92
6.3.2.3 Exit the UPS from the maintenance bypass mode 94
6.3.3 Removal of the SSS drawer 95
6.4 Battery drawers replacement 96
6.4.1 Installation/replacement of battery drawers with UPS in on-line mode 97
6.4.2 Installation/replacement of battery drawers with UPS in maintenance manual bypass 99
6.5 Replacing the fuses and surge arrester (DIN rail) 100
6.6 Extraordinary maintenance 101
7. Warehousing 102
7.1 UPS 102
7.2 Batteries 102
8. Dismantling 103
8.1 Battery disposal 103
8.2 UPS dismantling 103
8.3 Electronic component dismantling 103
4
Installation and maintenance manual
Keor MOD
1. Introduction
INDICATION
The instructions in this manual are intended for a SKILLED TECHNICIAN (paragraph 2.2.1)
Extraordinary maintenance operations are not dealt with because they are the sole preserve of the LEGRAND Technical
Support Service.
The reading of this manual is essential but does not substitute the skill of technical personnel who must have received
adequate preliminary training.
The intended use and configurations envisaged for the equipment as shown in this manual are the only ones allowed by
the Manufacturer.
Any other use or configuration must be previously agreed with the Manufacturer in writing and, in this case, the written
agreement will be attached to the installation and user manuals.
This manual also refers to laws, directives and standards that the skilled technician is required to be aware of and consult.
The original text of this publication, drafted in English, is the only reference for the resolution of disputes of interpretation
linked to translations into other languages.
DANGER
This indication shows a danger entailing a high degree of risk that, if not avoided, will lead to death or serious injury or
considerable damage to the equipment and things around it.
WARNING
This indication shows a danger entailing a medium degree of risk that, if not avoided, could lead to death or serious injury
or considerable damage to the equipment and the things around it.
CAUTION
This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or
material damage to the equipment and the things around it.
INDICATION
This symbol indicates important information which should be read carefully.
INDICATION
The manuals provided with the equipment are an integral part of it and must therefore be kept for its entire lifetime. In
case of need (for example in case of damage that even partially compromises its consultation) the skilled technician is
required to get a new copy from the Manufacturer, quoting the publication code on the cover.
5
1. Introduction
Any addition to the manual the Manufacturer considers appropriate to send to the users, must be kept together with the
manual of which they will become an integral part.
The version of the manual updated to its latest release is available on the Internet at ups.legrand.com
The transfer of the equipment to others also requires to hand over all the manuals. Failure to do it will automatically nullify
any right of the buyer, including the terms of the guarantee where applicable.
If the equipment is sold to a third party in a country where a different language is spoken, the original owner shall be respon-
sible for providing a faithful translation of this manual in the language of the country where the equipment will be used.
If there should be a fault in the product, contact the LEGRAND Technical Support Service which will provide all the in-
structions on what to do.
Do not send anything back without LEGRAND’s prior authorization.
The guarantee becomes void if the UPS has not been brought into service by a properly trained skilled technician quali-
fied and authorized by LEGRAND (see paragraph 2.2.1).
If during the guarantee period the UPS does not conform to the characteristics and performance laid down in this manu-
al, LEGRAND at its discretion will repair or replace the UPS and relative parts.
All the repaired or replaced parts will remain LEGRAND’s property.
6
Installation and maintenance manual
Keor MOD
1.6 Copyright
The information contained in this manual cannot be disclosed to any third party. Any partial or total duplication of the
manual by photocopying or other systems, including electronic scanning, which is not authorized in writing by the Man-
ufacturer, violates copyright conditions and may lead to prosecution.
LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous
written authorization.
7
2. Regulatory and safety requirements
DANGER
Before carrying out any operation on the equipment, it is necessary to read the entire manual carefully, especially
this chapter.
Look after this manual carefully and consult it repeatedly during installation and maintenance by a skilled tech-
nician.
INDICATION
The safety manager is responsible for protection and company risks prevention according to what is indicated in Europe-
an directives 2007/30/EC and 89/391/EEC regarding safety in the workplace.
The safety manager must ensure that all the people working on the equipment have received all the instructions concern-
ing them in the manual, especially those contained in this chapter.
2.2.2 Operator
The professional assigned to the equipment for normal use is called “Operator”.
This definition refers to people who know how to operate the equipment defined in the user manual and have the fol-
lowing requisites:
1. technical education, which enables them to operate according to safety standards in relation to the dangers linked to
the presence of electric current;
2. training on the use of personal protective equipment and basic first aid interventions.
The company safety manager, in choosing the person (operator) who uses the equipment, must consider
- the person’s work fitness according to the laws in force;
- the physical aspect (not disabled in any way);
- the psychological aspect (mental stability, sense of responsibility);
- the educational background, training and experience;
- the knowledge of the standards, regulations and measures for accident prevention.
He shall also provide training in such a way as to provide thorough knowledge of the equipment and its component parts.
DANGER
The UPS poses a considerable risk of electric shocks and a high short circuit current. During installation, use and mainte-
nance operations, the equipment mentioned in this section must be used.
People responsible for operating this equipment and/or passing close to it must not wear garments with flowing sleeves,
nor may laces, belts, bracelets or other metal pieces that might cause a danger.
8
Installation and maintenance manual
Keor MOD
The following list sum up the minimum Personal Protective Equipment to wear always. Additional requirements may be
needed according to national safety standards.
Isolated tools
INDICATION
The skilled technician must work on electrical insulated carpet and he must not wear any kind of metal objects like watch-
es, bracelets, etc.
Electric current
This sign indicates the electrical live parts.
No smoking
This sign indicates that smoking is not allowed.
CAUTION
The plates must not be removed or covered. Signs in different languages are provided along with the equipment to
replace those in English. No other plates may be affixed to the equipment without the Manufacturer’s prior written au-
thorisation
9
2. Regulatory and safety requirements
WARNING
Potential risks can be drastically reduced by wearing the Personal Protective Equipment listed in this chapter, which are
indispensable. Always operate with due care around dangerous areas marked by the appropriate warning notices on the
equipment.
DANGER
The UPS works with dangerous voltages. Only skilled technicians qualified and authorized by LEGRAND must perform the
installation and ordinary maintenance operations. No part of the UPS can be repaired by the operator.
Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel.
DANGER
Before beginning any installation and/or maintenance operation, make sure that all the DC and AC power sources are
disconnected.
The UPS and the external battery cabinet, if present, must be installed with an earth connection to avoid high leakage
currents. First connect the earthing cable.
Check during each installation and/or maintenance operation the continuity of the earthing system.
DANGER
The UPS is powered by its own DC energy source (batteries). The output terminals may have a dangerous voltage even if
the UPS is not connected to the AC power network.
Disconnect all battery drawers and external battery cabinets before performing any installation and/or maintenance
operation.
WARNING
A battery can present a risk of electrical shock and burns by high short-circuit circuit current. Failed batteries can reach
temperatures that exceed the burn thresholds for touchable surfaces. The following precautions should be observed
when working on batteries:
a) remove watches, rings or other metal objects.
b) use tools with insulated handles.
c) wear rubber gloves and boots.
d) do not lay tools or metal parts on top of batteries.
e) disconnect the charging source prior to connecting or disconnecting battery terminals.
f ) determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced
if such grounds are removed during installation and maintenance (applicable to equipment and remote battery sup-
plies not having a grounded supply circuit).
g) never leave live cable terminals without an insulated protection.
h) When replacing batteries, replace with the same type and number of batteries or battery packs. There is the risk of
explosion if batteries are replaced by an incorrect type.
INDICATION
The UPS functions with TT, IT, TN-C and TN-S systems. The output neutral status is the same as the input neutral status.
When the output load needs a different neutral status, it is necessary to place downstream of the UPS a suitably scaled
isolation transformer that must be protected in compliance with the standards in force.
CAUTION
Do not open the battery fuse holders while the UPS is powering the loads in battery mode.
10
Installation and maintenance manual
Keor MOD
WARNING
To reduce the risk of fire or electric shock, the UPS must work in closed, clean environments with controlled temperature
and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must not
be above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing.
WARNING
Keor MOD is a category C3 UPS according to the standard EN IEC 62040-2.
The UPS is a product for commercial and industrial application in the second environment – installation restrictions or
additional measures may be needed to prevent disturbances.
INDICATION
When the UPS is used for special applications such as life support systems or any other application where a product failure
is likely to cause substantial harm to people, it is mandatory to contact LEGRAND to confirm the possibility of the equip-
ment to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and
specifications.
CAUTION
- While maintenance operations are being carried out, “Maintenance work in progress” signs must be affixed in the de-
partment in such a way that they can be easily seen from any access area.
- The connection of the equipment (and of any accessory devices) signs must always be perfectly grounded to discharge
short-circuit currents and electrostatic voltages. The input voltage must correspond with the value shown on the rating
plate. Current adapters must not be used under any circumstances. Pay attention to polarity when connecting.
- Any intervention on the equipment must be done only after it has been disconnected from the power supply network
by means of a switch disconnector and must be locked with an appropriate padlock.
- The UPS must not be turned on if liquid is leaking from the batteries.
- Depositing flammable material near the equipment is strictly forbidden. The equipment should always be locked, and
only specifically trained personnel are allowed access to it.
- Do not disable any safety, notification or warning device and do not ignore any alarm, warning message or notice, no
matter whether they are generated automatically or represented by plates fixed to the equipment.
- Do not run the equipment with fixed protections not installed (panels etc.).
- In case of breaking, buckling or malfunctioning of the equipment or parts of it, repair or replace immediately.
- When replacing fuses, only use ones of the same type.
- The replacement of the batteries is an operation intended to be carried out by a skilled technician.
- Keep a register in which to enter the date, time, type, performer’s name and any other useful information about each
and any routine and extraordinary maintenance operation.
- Do not use oils or chemical products for cleaning because they could scratch, corrode or damage certain parts of the
equipment.
- The equipment and workplace must be kept completely clean.
- Upon completion of the maintenance operations, before connecting the power supply, carefully check that no tools
and/or material of any kind have been left next to the equipment.
INDICATION
The skilled technician must not leave at the disposal of the operator:
- the keys for opening the UPS door;
- the installation and maintenance manual.
11
3. Transportation and placement
The content of the supply is subject to thorough checking before the shipment. Nonetheless it is always advisable to
check that it is complete and in order on receiving the material.
The following list is general:
- 1 UPS (empty cabinet) with keys to close the doors;
- 1 accessory box;
- user manual;
- installation and maintenance manual.
In case of defects and/or missing items, immediately inform the LEGRAND Technical Support Service before commission-
ing the equipment.
INDICATION
The installation manual must be used and consulted only by Skilled Technicians.
INDICATION
Power modules and battery drawers to be installed must be bought separately.
12
Installation and maintenance manual
Keor MOD
3.3 Transportation
WARNING
The UPS must be placed and stand in a vertical position throughout the transportation. It shall also be packed properly.
Move the UPS very carefully, lifting it as little as possible and avoiding dangerous swings or falls.
Follow always the directions indicated in the symbols present on the packaging.
The equipment must always be handled by trained and instructed personnel. Comply with the safety regulations in force
in your country relative to the usage of lifting equipment and/or accessories.
For any lifting, use a forklift or a transpallet with an adequate carrying capacity, placing the forks in the specific spaces of
the base and making sure they come out on the other side by at least twenty centimetres.
Keor MOD UPS has four wheels at the bottom of the cabinet. Before installations and while it is still empty, it can be moved
by hand by at least two people.
CAUTION
Do not move the UPS after the installation or following the insertion of the power modules.
CAUTION
Do not stack more than 4 power modules.
13
3. Transportation and placement
3.4 Unpacking
To remove the packaging material, two people are required and they must comply with the following procedure:
- bring the UPS to the installation site using a forklift and/or a transpallet with suitable characteristics (see fig. 1);
- remove the plastic film and cardboards protecting the UPS;
- bring down the wooden chute attached to the pallet (fig. 2);
- loose the screws of the brackets that fix the equipment on the pallet (fig. 3);
- gently slide by hand the equipment along the chute using the wheels (fig. 4).
1 2
3 4
14
Installation and maintenance manual
Keor MOD
3.5 Placement
When the UPS is in the final position for the installation, unscrew counterclockwise the feet on the front and rear of the
cabinet to position it.
Make sure that all the wheels and feet adhere to the floor.
15
3. Transportation and placement
The UPS must be positioned respecting the following conditions:
- do not cover the cooling vents of the power modules and keep a clearance of 20 cm beyond the cabinets real panels;
- keep a clearance of 160 cm on the front to allow the opening of the door;
- temperature and humidity must be within permitted limits;
- fire regulations must be respected;
- the wiring must be simply made;
- front and rear accessibility must be available for assistance or periodic servicing;
- the cooling flow of air must be guaranteed;
- the air conditioning system must be adequately sized;
- dust, corrosive and explosive atmospheres must be absent;
- the installation site must be free of vibration;
- the support surface must be sized for the weight necessary to support the equipment:
- regulate the equipment feet to have perfect perpendicularity and level of the UPS compare with the floor.
To safeguard the batteries as well as possible it is necessary to bear in mind that their average lifetime is strongly influ-
enced by the operating room temperature. Position the UPS in an environment with a temperature range between +20°C
(+68°F) and +25°C (+77°F) to guarantee the optimum life of the batteries.
Before proceeding with the installation operations, make sure that there is enough lighting to clearly see every detail.
Provide artificial lighting if the natural lighting does not satisfy this requirement.
In case of maintenance operations in places that are not sufficiently well lit, portable lighting systems must be used,
avoiding shadows that prevent or reduce visibility on the point where you intend to work or on the surrounding areas.
16
Installation and maintenance manual
Keor MOD
4. Installation
DANGER
All UPS installation operations must be carried out exclusively by a SKILLED TECHNICIAN qualified and authorized
by LEGRAND (paragraph 2.2.1).
DANGER
Before carrying out any installation operation you must read and apply the following:
- The UPS has a high leakage current. The earthing connection must be connected before cabling the UPS input. The
switchgear must have a safe connection with the earthing and an adequate protection as required by the installation
standards.
- The UPS must only be installed in a fixed way with a thermal-magnetic circuit breaker placed upstream of it. Connection
to the mains via traditional type plug is not allowed.
- A circuit to protect from voltage backfeed made as in the diagrams shown in paragraph 4.2.5 must be provided outside
the UPS.
- The switchgear or the disconnector switch must be installed near the equipment and must be easily accessible.
- A warning label must be placed on all the mains disconnector switches installed away from the area of the UPS to remind the
assistance personnel of the fact that the circuit is connected to a UPS. The label must contain the following or equivalent text:
WARNING
The choice of cables type and their cross sections depending on the rated current and their installations must be made as
indicated by the local installation standards and it is a responsibility of the Skilled Technician.
The input current and the output power of the UPS are indicated in chapter 10 and the battery current in table 5 of chapter 11.
The cables used for the installation must have a maximum operating temperature of at least 70°C.
INDICATION
Chapter 11 includes tables with the recommended cables, fuses, automatic and differential breakers.
17
4. Installation
CAUTION
The equipment can cause a d.c. current in the PE conductor. Where a residual current-operated protective device (RCD) is
used for protection against electrical shock, only an RCD of Type B is allowed on the supply side of this product.
18
Installation and maintenance manual
Keor MOD
To insert the cables in the cabinet, it is necessary to remove the panels at the bottom of the cabinet according to the
following sequence:
19
4. Installation
20
Installation and maintenance manual
Keor MOD
Insert the cable and add the panels according to the following sequence:
21
4. Installation
10
22
Installation and maintenance manual
Keor MOD
Each earthing cable must be crimped with M8 eyelets and fixed to the earthing metal bar using hex M8x20 screws along
with M8 flat washers and M8 grower washer.
The grower washer must be put on the top of the flat washer.
23
4. Installation
24
Installation and maintenance manual
Keor MOD
KEOR MOD 125 – view of the two metal bars for cable fastening
25
4. Installation
The fastening of the battery, input and output cables on Keor MOD 125 must be done according to the following steps:
1) Fix the first metal bar to the cabinet, behind the surge arrester and the fuse holders, using two hex M8x14 screws.
2) Fix the plastic supports for cable ties using M6 torx pan head screws.
26
Installation and maintenance manual
Keor MOD
The fastening of the neutral and output cables on Keor MOD 125 must be done according to the following steps:
1) Fix the second metal bar to the cabinet, close to the maintenance manual bypass switch, using two hex M8x14 screws.
27
4. Installation
2) Fix the plastic support for cable ties using M6 torx pan head screws.
28
Installation and maintenance manual
Keor MOD
29
4. Installation
The fastening of the battery and output cables on Keor MOD 250 must be done according to the following steps:
1) Fix the first metal bar at the bottom of the cabinet using two hex M8x14 screws. Then fix the plastic support for the
cable ties using M6 torx pan head screws.
30
Installation and maintenance manual
Keor MOD
The fastening of the neutral and bypass cables on Keor MOD 250 must be done according to the following steps:
1) Fix the second metal bar above the first bar using two hex M8x14 screws. Then fix the plastic support for the cable ties
using M6 torx pan head screws.
31
4. Installation
The fastening of the input cables on Keor MOD 250 must be done according to the following steps:
1) Fix the third metal bar above the second bar using two hex M8x14 screws. Then fix the plastic support for the cable
ties using M6 torx pan head screws.
32
Installation and maintenance manual
Keor MOD
The tightening torque values for the cables are the following:
- M8 screws: 24 Nm
- M6 nuts: 15 Nm
- M10 nuts: 35 Nm
33
4. Installation
34
Installation and maintenance manual
Keor MOD
INDICATION
The following information related to the auxiliary contact for the backfeed protection are not yet implemented.
NO
NC
NC NO
35
4. Installation
If the UPS detects a voltage backfeed, the relay is energized and changes status, enabling the external disconnection of
the input lines as indicated in the diagrams shown below.
INDICATION
If during operation, the UPS signals that the backfeed protection has been actuated, contact the LEGRAND Technical
Support Service.
36
Installation and maintenance manual
Keor MOD
It is possible to install up to two external battery cabinet directly to the UPS Keor MOD. Avoid bridge connections when
connecting the battery cabinets to the UPS.
When there are more than two battery cabinets, it is recommended to provide a battery switchboard.
DANGER
Different connection solutions are the sole responsibility of the installer.
The implementation of the battery switchboard must be carried out according to the local installation regulations and it
is a responsibility of the installer.
The external modular battery cabinets must be homogeneous in the number of battery drawers. The difference between
one cabinet and the other must be a maximum of 1 KB (2 battery drawers).
INDICATION
There must be at least 1 KB (Battery Kit) every 25 kVA of nominal UPS power. For internal battery drawers and for external
modular battery cabinets, 1 KB is made up of 2 battery drawers.
Table 5 of chapter 11 indicates the recommended cables and fuses to connect the UPS to the battery switchboard.
The input current and the output power of the UPS are indicated in chapter 11 and the battery current in table 5 of chap-
ter 11.
Tables 6 of chapter 11 provides information about the fuses to be installed for the external non-modular battery cabinets.
37
4. Installation
WARNING
The neutral input cable must always be connected.
The default configuration has the input line in common with the bypass line through a metal jumper.
If no change is required, follow these steps:
- unscrew the three hex M8x25 screws that fix the jumper to the bypass terminal of the busbar;
- crimp the input and neutral cables with M8 eyelets;
- connect the input cables L1, L2, L3 to the metal jumper of the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar
using the three screws removed previously along with M8 flat washers and M8 grower washers. The grower washer must
always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
38
Installation and maintenance manual
Keor MOD
KEOR MOD 125 – input cables installation with input line in common with bypass line
In case the input line is separated from the bypass line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M8 eyelets;
- connect the input cables L1, L2, L3 to the terminals IN L1, IN L2, IN L3 of the input busbar using three hex M8x20 screws
along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
39
4. Installation
KEOR MOD 125 – input cables installation with input line separated from the bypass line
When the input line is separated from the bypass line, it is also possible to install an accessory for double cable. In this way
it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M8 eyelets;
- connect the first three input cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three input cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the ter-
minals IN L1, IN L2, IN L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20 screw
along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second neutral cable to the hole at the top of the accessory for double cable using a hex M8x25 screw along
with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The
grower washer must always be put on top of the flat washer.
KEOR MOD 125 – input cables installation with accessories for double cable and input line separated from the bypass line
40
Installation and maintenance manual
Keor MOD
The default configuration has the input line in common with the bypass line through a metal jumper.
If no change is required, follow these steps:
- unscrew the three hex M10x35 screws that fix the jumper to the input terminal of the busbar;
- crimp the input and neutral cables with M10 eyelets;
- connect the input cables L1, L2, L3 to the metal jumper of the terminals IN L1, IN L2, IN L3 of the input busbar using the
three screws removed previously along with M10 flat washers and M10 grower washers. The grower washer must always
be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
KEOR MOD 250 – input cables installation with input line in common with bypass line
41
4. Installation
In case the input line is separated from the bypass line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M10 eyelets;
- connect the input cables L1, L2, L3 to the terminals IN L1, IN L2, IN L3 of the input busbar using three hex M10x30 screws
along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
KEOR MOD 250 – input cables installation with input line separated from the bypass line
42
Installation and maintenance manual
Keor MOD
When the input line is separated from the bypass line, it is also possible to install an accessory for double cable. In this way
it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M10 eyelets;
- connect the first three input cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex
M10x30 screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top
of the flat washer;
- connect the other three input cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the
terminals IN L1, IN L2, IN L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first input neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30
screw along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat
washer;
- connect the second input neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the
neutral busbar. The grower washer must always be put on top of the flat washer.
KEOR MOD 250 – input cables installation with accessories for double cable
and input line separated from the bypass line
43
4. Installation
To perform a dual input installation with a separate bypass line, the following requirement must be met:
if the two lines are supplied by the same source, the residual current breaker should be a unique one for both lines.
If the two lines have a different electric potential, separate protective devices are required for each line.
The UPS does not modify the neutral configuration of the system. The mains, bypass and output neutral are connected
internally to each other.
WARNING
The neutral bypass cable must always be connected.
In case the bypass line is separated from the input line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M8 eyelets;
- connect the bypass cables L1, L2, L3 to the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat
washer;
- do not change the phase sequence (L1, L2, L3);
- connect the bypass neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
KEOR MOD 125 – bypass cables installation with input line separated from the bypass line
44
Installation and maintenance manual
Keor MOD
When the bypass line is separated from the input line, it is also possible to install an accessory for double cable. In this way
it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M8 eyelets;
- connect the first three bypass cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three
hex M8x20 screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top
of the flat washer;
- connect the other three bypass cables L1, L2, L3 to the hole at the top of the accessory for double cable using three
hex M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the
terminals BYP L1, BYP L2, BYP L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first bypass neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20
screw along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat
washer;
- connect the second bypass neutral cable to the hole at the top of the accessory for double cable using a hex M8x25
screw along with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the
neutral busbar. The grower washer must always be put on top of the flat washer.
KEOR MOD 125 – bypass cables installation with accessories for double cable
and input line separated from the bypass line
In case the bypass line is separated from the input line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M10 eyelets;
- connect the bypass cables L1, L2, L3 to the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar using three hex M10x30
screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat
washer;
- do not change the phase sequence (L1, L2, L3);
- connect the bypass neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
45
4. Installation
KEOR MOD 250 – bypass cables installation with input line separated from the bypass line
46
Installation and maintenance manual
Keor MOD
When the bypass line is separated from the input line, it is also possible to install an accessory for double cable. In this way
it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M10 eyelets;
- connect the first three bypass cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three
hex M10x30 screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on
top of the flat washer;
- connect the other three bypass cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the
terminals BYP L1, BYP L2, BYP L3 of the bypass busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first bypass neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30
screw along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat
washer;
- connect the second bypass neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the
neutral busbar. The grower washer must always be put on top of the flat washer.
47
4. Installation
KEOR MOD 250 – bypass cables installation with accessories for double cable
and input line separated from the bypass line
INDICATION
Provide a separate switchgear for the load.
The following information must be indicated on the system switchgear by means of stickers or similar:
- maximum nominal power of the load;
- maximum nominal power of the load at the load outlets;
- if a common switchgear is used (mains and UPS power outlets), make sure that there is an indication of the power source
on every power outlet (“Mains” or “UPS”).
WARNING
The neutral output cable must always be connected.
48
Installation and maintenance manual
Keor MOD
It is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with
a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- crimp the output and neutral cables with M8 eyelets;
- connect the first three output cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three output cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the termi-
nals OUT L1, OUT L2, OUT L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first output neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20 screw
along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second output neutral cable to the hole at the top of the accessory for double cable using a hex M8x25 screw
along with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the neutral
busbar. The grower washer must always be put on top of the flat washer.
KEOR MOD 125 – output cables installation with accessories for double cable
49
4. Installation
KEOR MOD 250
50
Installation and maintenance manual
Keor MOD
It is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with
a smaller cross section than the one of a single cable.
For this installation, follow these steps:
- crimp the output and neutral cables with M10 eyelets;
- connect the first three output cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M10x30
screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three output cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the
terminals OUT L1, OUT L2, OUT L3 of the output busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first output neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30 screw
along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second output neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the
neutral busbar. The grower washer must always be put on top of the flat washer.
51
4. Installation
KEOR MOD 250 – output cables installation with accessories for double cable
WARNING
The neutral battery cable must always be connected.
INDICATION
The maximum length of hte battery cables is 25 m.
52
Installation and maintenance manual
Keor MOD
KEOR MOD 125 – battery cables installation with strings of batteries in common
53
4. Installation
In case there is the need to use a double cable for each terminal in order to use a smaller cross section for each cable,
follow the previous procedure but install two cables for each terminal.
KEOR MOD 125 – battery cables installation with strings of batteries in common (double cable)
It is also possible to install independent string of batteries. In this case, each power module is associated to a unique string.
The following picture shows the association between the power modules and the relative battery strings:
54
Installation and maintenance manual
Keor MOD
- remove the metal jumpers inserted in the positive and negative battery terminals.
- insert the positive battery cables of the battery cabinets in the positive battery terminal and the negative battery cables
of the battery cabinets in the negative battery terminal.
The maximum cross section accepted by the terminals is 16 mm2.
Connect the battery cables on the terminals according to the string:
BATT1: +1 ; -1
BATT2: +2 ; -2
BATT3: +3 ; -3
BATT4: +4 ; -4
BATT5: +5 ; -5
55
4. Installation
- take from the accessory box the metal support for the neutral battery cables and install it in the relative position on the
neutral busbar.
56
Installation and maintenance manual
Keor MOD
57
4. Installation
KEOR MOD 250
KEOR MOD 250 – battery cables installation with strings of batteries in common
58
Installation and maintenance manual
Keor MOD
In case there is the need to use a double cable for each terminal in order to use a smaller cross section for each cable,
follow the previous procedure but install two cables for each terminal.
KEOR MOD 250 – battery cables installation with strings of batteries in common (double cable)
It is also possible to install independent string of batteries. In this case, each power module is associated to a unique string.
The following picture shows the association between the power modules and the relative battery strings:
59
4. Installation
In case of installation of independent strings of batterie, follow these steps:
- insert the positive battery cables of the battery cabinets in the positive battery terminal, the negative battery cables of
the battery cabinets in the negative battery terminal and the neutral battery cables of the battery cabinets in the neutral
battery terminal.
The maximum cross section accepted by the terminals is 35 mm2.
Connect the battery cables on the terminals according to the string:
BATT1: +1 ; -1
BATT2: +2 ; -2
BATT3: +3 ; -3
BATT4: +4 ; -4
BATT5: +5 ; -5
60
Installation and maintenance manual
Keor MOD
For the configuration of the parallel system, the first thing to do is to set the ID address of each UPS in the parallel system
by means of the rotary switch of the SSS interface:
For Keor MOD 125, the ID address must be from 0 to 2. For Keor MOD 250, the ID address must be from 4 to 6.
If there is a parallel of two to three Keor MOD 125, this is the ID to set on each UPS:
UPS 1 : ID=0
UPS 2 : ID=1
UPS 3 : ID=2
The limit for the parallel for Keor MOD 250 is a total of 24 PM. It is possible to have a parallel of two full UPS units or of three
UPS units having eight PM each. If there is a parallel of two to three Keor MOD 250 cabinets, this is the ID to set on each UPS:
UPS 1 : ID=4
UPS 2 : ID=5
UPS 3 : ID=6
The BYPASS-SYNC and CAN-BUS ports of the SSS interfaces of the UPS must be connected among themselves as indicated
in the following pictures:
61
4. Installation
The cables for the connections of the ports of the SSS interfaces must have the following characteristics:
62
Installation and maintenance manual
Keor MOD
The cables can pass on the cabinet as indicated in the following pictures:
63
4. Installation
64
Installation and maintenance manual
Keor MOD
The first and the last UPS of the parallel system must be terminated. To do this, remove the fixed part of the SSS interface
from the cabinet following the steps indicated on paragraph 6.3.3.
The fixed part of the SSS interface has two dip switches. SW2 is linked to N2B (the male connector of the CAN-BUS port of
the SSS interface). SW3 is linked to N2A (the female connector of the CAN-BUS port of the SSS interface).
According to which CAN-BUS port is used on the first and on the last UPS of the parallel system, the relative dip switch
must be set to ON if the port is free or to OFF if the cable is connected.
For example, for the configuration shown before, set the dip switch as indicated in the following picture:
65
4. Installation
For the installation of the cables for the parallel system, it is recommended to provide an external system bypass as indi-
cated in the following connection diagram:
Use only the external system bypass for maintenance and block the maintenance bypass of each single UPS unit to 0
(open) with a lock.
An early make contact of the external maintenance bypass must be connected to the N6 terminal of the SSS interface
(EXT MAINT BYP SW) of one UPS unit of the parallel system (see paragraph 4.5).
If redundancy is required, add an early make contact from the external maintenance bypass for each N6 terminal of the
SSS interfaces of the UPS units.
66
Installation and maintenance manual
Keor MOD
The following diagram indicates how to connect battery cabinets to a parallel system:
The ATS-SYNC ports of the SSS interfaces of the first UPS of each system (the one having lower ID number) must be con-
nected to each other using the Keor Mod cross sync cable Cat. Nos. 3 102 59
For the configuration of this function, check paragraph 5.2 about the start-up procedure.
67
4. Installation
INDICATION
To guarantee the stability of the Keor MOD 125 cabinet, first install the power modules and only later the battery drawers.
Insert the power modules one at a time starting from the top of the cabinet.
Insert two screwdrivers in the upper parts of the plastic slot cover where the power module must be installed. Slightly
turn the screwdrivers down to unhook the cover.
Handle the power module from his sides and never from the front.
68
Installation and maintenance manual
Keor MOD
Remove the film protector from the front of the power module. Insert the power module in the free slot, making sure that
its switch in the front is open.
Make sure that the power module is abut and then close its front switch. Fix the module to the cabinet with four screws
included in the accessory kit.
69
4. Installation
70
Installation and maintenance manual
Keor MOD
Starting from the top of the cabinet, insert two screwdrivers in the upper parts of the two plastic slot cover where the
battery drawers must be installed. Slightly turn the screwdrivers down to unhook the covers.
Insert the empty battery drawers in the free slots and push them till the ‘click’ of the safety block is heard.
The battery packs must be added to the drawers only after the activation of the safety block.
Remove the adhesive tape from the terminal covers at the extremes of the battery pack and remove the covers.
71
4. Installation
Add two battery packs on a drawer and connect in series the two packs using the provided cable fixed in the bracket and
respecting the polarity (connect a positive terminal to a negative terminal).
72
Installation and maintenance manual
Keor MOD
Connect the two provided cables on the free battery terminals that will connect the two battery packs with the other two
that will be added in the next step. Insert the terminal covers and fix them to the packs with the adhesive tape.
73
4. Installation
Connect in series the two new packs to the ones already in the drawer using the cable installed previously and respecting
the polarity (connect a positive terminal to a negative terminal).
Connect the free terminals of the two batteries located close to the handle of the drawer to the cables that are connected
to the back of the drawer. Check the correct polarity of the whole cabling.
Cables should not protrude from the drawer uprights to avoid cuts during insertion into the cabinet.
Insert the remaining terminal covers on the batteries and fix them with the adhesive tape to the battery pack.
74
Installation and maintenance manual
Keor MOD
75
4. Installation
CAUTION
A drawer must be made up of batteries of the same brand and of the same manufacturing date.
76
Installation and maintenance manual
Keor MOD
77
4. Installation
INDICATION
It is not possible to connect in parallel the EPO circuits of several UPS. If necessary, use contacts on the EPO emergency
pushbutton isolated from each other.
78
Installation and maintenance manual
Keor MOD
DANGER
All the configurations and start-up operations must be carried out exclusively by a SKILLED TECHNICIAN (para-
graph 2.2.1).
4. Choose the desired language in the tab GENERAL by tapping on the pencil icon on the item Language.
79
5. Configuration and start-up
5. Set the desired voltage and frequency output in the tab SYSTEM by tapping on the pencil icon on the items Output
Voltage and Output Frequency.
In the same tab there is also the item Enable or disable walk-in function. If the UPS turns from battery mode to
normal mode while it is connected to an external generator, especially with full load, there could be some frequency
fluctuations causing a condition where the bypass is not available. If the walk-in function is enabled, the PM are
not turned from battery mode to normal mode all together; they are turned to normal mode one by one with a
time interval of 2 seconds. Tap on the pencil icon of the item Enable or disable walk-in function and select ENABLE or
DISABLE.
80
Installation and maintenance manual
Keor MOD
6. Select the tab BD to set the number of KB (Battery Kits) and the battery capacity in Ah of the single KB.
Tap on the pencil icon of the item Number of Kit Batteries installed and insert the number of KB. Tap on the pencil icon
of the item Capacity value of Kit Batteries [Ah] and insert the value of the battery capacity.
INDICATION
1 KB (Battery Kit) represents a string of 48 batteries in series. In case of models with internal battery drawers, 1 KB is made
up of 2 drawers.
The UPS calculates the total battery capacity as produced by the total KB * Capacity.
81
5. Configuration and start-up
7. In the BD tab, select the the charge mode of the UPS. There are 2 modes available:
- Floating mode: the voltage on the batteries is maintained to 13.8 V. For this mode it is also possible to have a tune
of the charging voltage according to the temperature detected by an internal sensor of the SSS (in case of internal
battery drawers) or through an external sensor (in case of external battery cabinets).
- 2 step mode: smart charge with an advanced cycle that limits any chance of overcharging or overheating the
batteries.
Tap on the pencil icon of the item Charging Mode and choose between these 4 options: TWO STEP, FLOATING,
FLOATING_INT and FLOATING_EXT.
The last two options refer to the floating mode with internal or external temperature control.
8. Set the configuration of the batteries (see paragraph 4.2.10) by tapping on the General Commands icon of the menu
bar at the bottom of the display.
82
Installation and maintenance manual
Keor MOD
10. Select the type of Battery Configuration among the three options:
- Common: all the strings of batteries are in common;
- Cabinet: each UPS unit has his unique battery cabinet;
- Individual: each PM is connected to a unique battery string.
83
5. Configuration and start-up
11. If there are two Keor MOD systems connected to an STS (see paragraph 4.2.12), it is necessary to set a proper configu-
ration for one of the UPS in each system.
Tap on the Settings icon of the menu bar at the bottom of the display. Select the System tab.
Tap on the pencil icon of the item Syncro2N Mode. If the UPS is part of the system which is the primary source of
supply to the load through the STS, select MASTER. If the UPS is part of the secondary system which is the alternative
source, select SLAVE.
12. Provide the mains supply to the UPS by closing the external mains input/bypass input disconnectors (ON position).
13. Ensure that the EPO is connected to the SSS interface (the default setting is NC).
Tap on the General Commands icon of the menu bar at the bottom of the display. Find the item System Power On and
tap on the button ON to turn on the UPS.
14. The LEDs on the power modules turn to steady yellow while they are powered from the batteries. When they are pow-
ered from the mains and the UPS is on-line, the LEDs turn to steady green.
15. Check that the output voltage and frequency values set correspond with the requirements of the load. If not, turn off
the UPS and set the correct values (see step 6).
16. Provide the power supply to the load by closing the external output disconnector (ON position).
17. Close the UPS door and remove the key.
DANGER
Do not remove the power modules during the functioning of the UPS without activating the hot-swap procedure (de-
scribed in paragraph 6.3.1). The removal of one or more power modules without the proper use of the hot-swap proce-
dure could damage the equipment.
CAUTION
The keys to open the UPS door and the installation manual must not be left at the disposal of the operator.
84
Installation and maintenance manual
Keor MOD
3. The LEDs on the power modules turn to steady blue when they are in stand-by mode and the UPS is no longer sup-
plying the load.
DANGER
In this stand-by condition there are still hazardous voltages on the UPS.
To disconnect the UPS from all sources of supply:
- open the external mains input/bypass input disconnectors (ON position);
- open all the fuse breakers of the external battery cabinets (if present);
- remove at least one battery drawer for every shelf present to interrupt the battery string.
85
6. Maintenance
DANGER
INSTALLATION and ORDINARY MAINTENANCE operations must be carried out only by SKILLED TECHNICIANS
(paragraph 2.2.1).
EXTRAORDINARY MAINTENANCE operations must be carried out only by LEGRAND TECHNICAL SUPPORT SERVICE.
LEGRAND declines all liability for any injury or damage caused by activities carried out differently from the instructions
written in this manual.
During a maintenance inspection, the skilled technician must carry out the following checks:
- no alarm presence;
- list of the memorised events;
- correct function of the static and maintenance bypass;
- integrity of the electrical installation;
- flow of cold air;
- battery status;
- characteristics of the applied load;
- conditions of the installation location.
WARNING
The periodical checks involve operations inside the UPS in presence of dangerous voltages. Only maintenance personnel
trained by LEGRAND are authorized to intervene.
It is also possible to perfom an automatic battery test. With this function, only one PM is switched to battery mode to
verify the battery status.
Tap on the General Commands icon of the menu bar at the bottom of the display. Find the item Battery Test and tap on
the button START.
CAUTION
Do not power off the UPS during a battery test.
86
Installation and maintenance manual
Keor MOD
INDICATION
To use this function, the UPS must have at least two power modules and the output power required must not be above
the one available during the hot-swap procedure.
Always replace just one PM at a time.
If the load power does not allow the hot-swap without overload, perform the manual bypass mode maintenance proce-
dure.
Each power module (PM) is identified by a unique address inside the system, as shown below:
87
6. Maintenance
During the hot-swap procedure the maximum active power available is indicated in the following table:
3. Initially, the LED on the PM turns blue. Wait until it turns white: the PM is ready to be replaced.
4. Unscrew the fixing screws of the PM and save them.
5. Extract the PM until the safety block prevents the extraction from continuing.
88
Installation and maintenance manual
Keor MOD
6. Push the safety hook located on the top right of the PM to unlock the block and pull the PM to finalize the extraction.
7. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
8. Fix the PM to the cabinet using the screws previously unscrewed.
9. Close the frontal switch of the PM.
10. The LED on the PM turns red. After the boot of the PM, the LED turns blue. Next, the PM starts in battery mode (yellow
LED). Finally, the LED turns green and the PM is powered by the mains.
INDICATION
If one or more screws are lost, use only hex socket M6x16 screws along with M6 toothed washers to fix the power modules.
CAUTION
If there is a hot-swap replacement of a PM and the UPS battery charger status was set to OFF, it is important to verify its
status at the end of the procedure. If the charger has turned on, it is necessary to change the status to OFF.
89
6. Maintenance
6.3.2 Installation/replacement of power modules with the UPS in maintenance bypass mode
If the hot-swap procedure explained in the previous paragraph is not applicable, it is possible to replace or even to add
PM with the UPS in maintenance bypass mode.
INDICATION
During this procedure, the load is not protected by the UPS because it is powered from the bypass input line.
2. Check on the tab System that the item Bypass Enable is set to YES. If not, tap on the item and enable the bypass.
90
Installation and maintenance manual
Keor MOD
3. Tap on the General Commands icon of the menu bar at the bottom of the display.
5. Tap on the Bypass on button of the item Force Bypass. The LEDs of the PM blink fast in orange.
91
6. Maintenance
6. Close the maintenance manual bypass switch by bringing it to the ON position. The load is powered directly from the
bypass line.
7. Turn OFF the UPS by following the procedure described at paragraph 5.3. The LEDs of the PM turn to blue when the
PM are in stand-by mode.
8. If present, open the battery disconnectors of the external battery cabinets.
DANGER
If there are battery drawers installed in the cabinet, some internal parts of the UPS are still live with dangerous voltage.
Remove at least one battery drawer for every shelf present to interrupt the battery string.
To replace a PM:
1. Open the frontal switch of the PM to be replaced.
92
Installation and maintenance manual
Keor MOD
4. Push the safety hook located on the top right of the PM to unlock the block and pull the PM to finalize the extraction.
5. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
6. Fix the PM to the cabinet using the screws previously unscrewed.
7. Close the frontal switch of the PM and wait until the LED of the PM turns blue.
To add a PM:
1. Unscrew the screws of the protective cover of a free slot starting from the top of the cabinet.
2. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
3. Fix the module using the screws previously unscrewed.
4. Close the frontal switch of the PM.
INDICATION
If one or more screws are lost, use only hex socket M6x16 screws along with M6 toothed washers to fix the power modules.
93
6. Maintenance
3. Wait for the UPS boot until the LEDs of the PM blink fast in orange.
4. Open the maintenance manual bypass switch by bringing it to the OFF position
5. Tap on the General Commands icon of the menu bar at the bottom of the display. Tap on the icon > of the item
COMMANDS. Tap on the Bypass off button of the item Force Bypass. The LEDs of the PM turn to steady green.
94
Installation and maintenance manual
Keor MOD
95
6. Maintenance
WARNING
A battery can present a risk of electrical shock and high short circuit current. Read and apply the safety instructions in
chapter 2 before operating on batteries
INDICATION
The battery drawers must always be added/removed in multiples of two (1 KB consists of two battery drawers). Always
replace just one KB at a time. If one KB is added, start from the free slots at the top which are covered by protective covers.
If a KB is completely removed, install the protective covers to block any access to live parts.
If the installation/removal procedure changes the total number of KB installed in the UPS, it is necessary to update this
setting from the control panel.
CAUTION
A drawer must be made up of batteries of the same brand and of the same manufacturing date.
96
Installation and maintenance manual
Keor MOD
4. Remove all the battery packs from the drawer. Use the handle included in the accessory kit to remove the battery
packs at the back of the drawer.
97
6. Maintenance
5. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
6. Follow the procedure shown at paragraph 4.4 to insert a new battery drawer
INDICATION
If the UPS turns to battery mode during these operations, do not continue the installation/replacement. It is possible to
resume the operations when the UPS turns to on-line mode.
When there is a black-out during the replacement of battery drawers, the backup time is reduced. It is necessary to care-
fully assess this event before starting with the installation/replacement procedure.
98
Installation and maintenance manual
Keor MOD
3. Remove all the battery packs from the drawer. Use the handle included in the accessory kit to remove the battery
packs at the back of the drawer.
99
6. Maintenance
4. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
5. Follow the procedure shown at paragraph 4.4 to insert a new battery drawer
6. Follow the procedure described in paragraph 6.3.2.3 to exit from the maintenance bypass mode.
INDICATION
During the installation/replacement operations, the load is not protected by the UPS because it is powered from the
bypass input line.
INDICATION
It is mandatory to verify monthly the indication on the surge arrester. The device works correctly if the indicator is green.
If the device is damaged, the indicator is red and the surge arrester must be replaced.
100
Installation and maintenance manual
Keor MOD
101
7. Warehousing
DANGER
All storage operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1)
DANGER
A SKILLED TECHNICIAN must check that there is no voltage present before disconnecting the cables. All the bat-
tery isolator switches on the UPS and on the EBC must be open.
All the battery isolator switches on the UPS and on the external battery cabinets must be open. The battery draw-
ers of the UPS and of the external battery cabinet (if present) must be removed.
7.1 UPS
The UPS must be stored in an environment with a room temperature between -20°C (-4°F) and +50°C (+122°F) and hu-
midity less than 90% (not condensing).
7.2 Batteries
It is possible to store batteries without recharging them in the following conditions:
- up to 6 months if the temperature is between +20°C (+68°F) and +30°C (+86°F);
- up to 3 months if the temperature is between +30°C (+86°F) and +40°C (+104°F);
- up to 2 months if the temperature is over +40°C (+104°F).
CAUTION
Batteries must never be stored if partially or totally discharged.
LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries.
102
Installation and maintenance manual
Keor MOD
8. Dismantling
DANGER
Dismantling and disposal operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1).
The instructions in this chapter are to be considered indicative: in every country there are different regulations
regarding the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere to the
standards in force in the country where the equipment is used.
Do not throw any component of the equipment in the ordinary rubbish.
WARNING
A battery may constitute a risk of electric shock and high short-circuit current.
When working on batteries, the prescriptions indicated in chapter 2 must be adhered to.
This symbol indicates that in order to prevent any negative effects on the environment and on people, this
product should be disposed of separately from other household waste, by taking it to authorised collection
centres, in accordance with the EU countries local waste disposal legislations. Disposing of the product without
following local regulations may be punished by law. It is recommended to check that this equipment subject to
WEEE legislations in the country where it is used.
To remove the display, unscrew the four nuts on four M3 threaded studs that secure the display to the cabinet.
103
9. Mechanical characteristics
The UPSs Keor MOD are sold as empty power cabinets. It is necessary to purchase the power modules separately.
9.1 Cabinets
(all the dimensions are in mm)
3 104 80 KEOR MOD 25-125 kVA 3 104 81 KEOR MOD 25-250 kVA
104
105
Keor MOD
106
107
Keor MOD
108
Installation and maintenance manual
Keor MOD
109
9. Mechanical characteristics
110
Installation and maintenance manual
Keor MOD
111
10. Technical data
Main features
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Nominal Power
25 50 75 100 125 150 175 200 225 250
(kVA)
Active Power
25 50 75 100 125 150 175 200 225 250
(kW)
Number of power
1 2 3 4 5 6 7 8 9 10
modules
online, double conversion
Technology
VFI-SS-111 (EN IEC 62040-3)
IN/OUT configuration Three-phase / Three-phase
Dual Input Available
UPS system Modular, expandable and redundant
Neutral system Neutral passing straight from input to output (not isolated)
Automatic (static)
Bypass
Manual (for maintenance)
Overvoltage category OVC II
Protection class
I
(EN/IEC 61140)
AC power distribution
TN, TT
system compatibility
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Rated input current (A)
(full load and 400V 37.6 75 113 150 188 225.6 263.2 300 338 376
input voltage)
Maximum input
current (A)
47 94 141 188 235 282 329 376 423 470
(full load and 320V
input voltage)
Input voltage 400 + 15% - 20%
(V) (3P+N+PE)
50 / 60 ± 2%
Input frequency
50 / 60 +14% - 6%
(Hz)
(autosensing and/or selectable by the user)
Input Power Factor > 0.99
Total harmonic distortion
THDi < 4% (at full load)
of the input current
Icp
Prospective short-circuit 10
current (kA)
112
Installation and maintenance manual
Keor MOD
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Maximum output
36 72 108 144 180 216 252 288 324 360
current (A)
Output voltage 380/400/415 ± 1%
(V) (3P+N+PE)
Output frequency 50 / 60
(Hz) (selectable by the user)
Range of the output If synchronized with the bypass frequency: adjustable range from +14% to -6%
frequency If not synchronized (free run): ± 0.1 Hz
Crest factor admitted
3:1
on the output current
Total harmonic distortion
THDv < 0.9% (at full linear load) for Keor MOD 125-250
of the output voltage
Efficiency in Normal
up to 96.5%
Mode
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Output voltage
380/400/415 ± 1%
(V)
Output frequency
50 / 60 Hz ± 1%
(Hz)
Total harmonic distortion
THDv < 0.7% (at full linear load) for Keor MOD 125-250
of the output voltage
113
10. Technical data
Batteries and battery charger characteristics
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Nominal battery
± 288 (48 blocks)
voltage (V)
Battery voltage
± 264 to ± 312 (44-52 blocks)
range (V)
Internal batteries: string made up of 2 drawers
Battery wiring (composed by 4 blocks of 6 batteries) Only external batteries
External batteries
12 Vdc - 9 Ah
Unitary capacity -
12 Vdc - 11 Ah
High performance PWM, one for each power module
Type of battery charger
Smart charge technology (3-stage advanced cycle)
Maximum recharge
5 (for each power module installed)
current (A)
Independent battery maximum 5 sets of independent batteries
configuration (configurable as common or separate units)
Features
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
114
Installation and maintenance manual
Keor MOD
Mechanical characteristics
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Installable Power
up to 5 up to 10
modules PM25 3 106 75
115 115
Installation and maintenance manual
Keor MOD
Environmental conditions
Keor Keor Keor Keor Keor Keor Keor Keor Keor Keor
MOD MOD MOD MOD MOD MOD MOD MOD MOD MOD
25 50 75 100 125 150 175 200 225 250
Operating
0 ÷ +40
temperature (°C)
Relative humidity
0% ÷ 95% non-condensing
during operation
Storage
-25 - +55 (excluding batteries)
temperature (°C)
Noise level at 1 metre
up to 79
(dBA)
Ingress Protection
IP 20
Code
Climatic class
3K22
(EN IEC 60721-3-3)
Special climatic class
3Z2
(EN IEC 60721-3-3)
Biological class
3B2
(EN IEC 60721-3-3)
Mechanical class
3M11
(EN IEC 60721-3-3)
Mechanically active
substances class 3S5
(EN IEC 60721-3-3)
Directive 2014/35/EU
Safety
EN IEC 62040-1
Directive 2014/30/EU
EMC
EN IEC 62040-2
116 116
Installation and maintenance manual
Keor MOD
11. Tables
CAUTION
The choice of the type and section of the power cables must be done according to the voltage and rated current as well
as the local wiring standards and regulations. It is a responsibility of the installation engineer.
The input current and the output power of the UPS are indicated in chapter 10 and the battery current in table 5 of this chapter.
The following tables give an indication of the wire cross sections to use if the wires are unipolar with simple PVC installa-
tion and installation in tube in the air.
TABLE 1
Minimum wire cross sections recommended
BYPASS CABLE
POWER INPUT CABLE (in case of separate OUTPUT CABLE
bypass line)
117
11. Tables
TABLE 2
Maximum wire cross sections and maximum crimping lugs
BATTERY (CONFIGURED AS
CABINET INPUT - BYPASS - OUTPUT NEUTRAL
COMMON BATTERY)
1 x up to 120 mm2
B = 28,5 mm (M8 standard
up to 120 mm2
palm width)
B = 28,5 mm (M8 standard
palm width)
1 x up to 185 mm2
up to 95 mm2
B = 24,5 mm (M8 contained
B = 25 mm (M8 standard up to 185 mm2
palm width)
palm width) B = 24,5 mm (M8 contained
KEOR MOD 125 palm width)
up to 185 mm2
2 x up to 70 mm2
B = 24,5 mm (M8 contained for independent strings of
B = 21 mm (M8 standard
palm width) battery
palm width)
up to 16 mm2
B = 11,5 mm (M5 contained
2 x up to 150 mm2
palm width)
B = 19 mm (M8 contained
palm width)
3 x up to 240 mm2
B = 31,5 mm (M10 standard
1 x up to 240 mm2
palm width)
B = 39 mm (M8 standard
palm width)
up to 150 mm2 3 x up to 300 mm2
B = 31,5 mm (M10 standard B = 31 mm (M10 contained
palm width) palm width)
2 x up to 120 mm2
KEOR MOD 250
B = 28,5 mm (M8 standard
up to 240 mm2 6 x up to 120 mm2
palm width)
B = 31 mm (M10 contained B = 28,5 mm (M10 standard
palm width) palm width)
2 x up to 150 mm2
B = 19 mm (M8 contained
6 x up to 185 mm2
palm width)
B = 24,5 mm (M10
contained palm width)
118
Installation and maintenance manual
Keor MOD
TABLE 3
Automatic breaker recommended for input and bypass line
TABLE 4
Residual current breaker recommended for input and bypass line
125 kVA
≥ 300 mA type B
250 kVA
TABLE 5
Maximum current absorbed by the batteries at full load and recommended wire cross sections for connecting the
UPS to the external battery cabinets
MAXIMUM
POWER RECOMMENDED WIRE CROSS SECTION RECOMMENDED FUSES
BATTERY CURRENT
Common battery: 1 x 150 mm2 (per pole) DC ultra rapid type aR or gR 315 A
125 kVA 300 A
Indipendent strings: 5 x 16 mm2 (per pole) (1 per pole) *
Common battery: 2 x 150 mm2 (per pole) DC ultra rapid type aR or gR 315 A
250 kVA 600 A
Indipendent strings: 5 x 35 mm2 (per pole) (2 per pole) *
* NOTE: Contact the Legrand Technical Support Service to know the correct fuses to be installed. UPS produced in the past
may need to use only aR fuses with I2t= 39600 for the 125 kVA model or with I2t= 158400 for the 250 kVA model.
INDICATION
The maximum length of the battery cables is 25 m.
TABLE 6
External battery cabinets
CABINET
BATTERIES
ITEM CODE DIMENSION SWITCHES AND PROTECTION KIT
(Ah)
(L X D X H) mm
3 109 65 1200 x 900 x 1900 1x FUSE HOLDER 3P NH2 400A - 3x aR FUSE 315A 70-93
3 109 67 1200 x 900 x 1900 1x FUSE HOLDER 3P NH2 400A - 3x aR FUSE 350A 105
3 109 44 1200 x 900 x 1900 1x FUSE HOLDER 3P NH1 250A - 3x aR FUSE 250A 55
2 cabinets 2 cabinets
3 109 89 80
810 x 840 x 1900 2x FUSE HOLDER 3P NH2 400A - 3x gR FUSE 315A
119
LEGRAND
Pro and Consumer Service
BP 30076 - 87002
LIMOGES CEDEX FRANCE
www.legrand.com
Installer stamp
Legrand reserves at any time the right to modify the contents of this booklet and to communicate,
in any form and modality, the changes brought to the same.