Western U.P. Power Transmission Co. Ltd.
Regd. Off:     400/220/33kV Substation, Kalapatthar, Indirapuram,
                                Ghaziabad – 201014, U.P., India
                   TRANSFORMER OIL TEST REPORT (GC 2010)
NAME & ADDRESS OF SUB-STATION: - 400/220/33 KV ATAUR SUB-STATION
DATE OF SAMPLE ISSUED: - 12/12/2023
DATE OF SAMPLE RECEIPT: 12/12/2023
SAMPLE DESCRIPTION
TRANSFORMER SR. NO-6007357
RATING: - 500 MVA ICT-1
MAKE: - BHEL
SAMPLING LOCATION: - ATAUR
TEST DETAILS: -
                                                Requirement as Per
     Sl. No.        Particulars of Tests                                 Obtained Value       Remarks
                                                   Specification
       1       METHANE (𝐶𝐻4 )                            120                   12.8
       2       ETHANE ( 𝐶2 𝐻6 )                           65                     0
       3       ETHYLENE ( 𝐶2 𝐻4 )                         50                   42.8
       4       ACETYLENE ( 𝐶2 𝐻2 )                        1                      0
       5       HYDROGEN (𝐻2 )                            100                     0
       6       CARBON MONOXIDE (CO)                      350                    76
       7       CARBON DIOXIDE (𝐶𝑂2)                     2500                   162
                                                                                      Checked & verified by: