Western U.P. Power Transmission Co. Ltd.

Regd. Off: 400/220/33kV Substation, Kalapatthar, Indirapuram,


Ghaziabad – 201014, U.P., India

TRANSFORMER OIL TEST REPORT (GC 2010)

NAME & ADDRESS OF SUB-STATION: - 400/220/33 KV ATAUR SUB-STATION

DATE OF SAMPLE ISSUED: - 12/12/2023


DATE OF SAMPLE RECEIPT: 12/12/2023
SAMPLE DESCRIPTION
TRANSFORMER SR. NO-6007357
RATING: - 500 MVA ICT-1
MAKE: - BHEL

SAMPLING LOCATION: - ATAUR

TEST DETAILS: -

Requirement as Per
Sl. No. Particulars of Tests Obtained Value Remarks
Specification

1 METHANE (𝐶𝐻4 ) 120 12.8

2 ETHANE ( 𝐶2 𝐻6 ) 65 0

3 ETHYLENE ( 𝐶2 𝐻4 ) 50 42.8

4 ACETYLENE ( 𝐶2 𝐻2 ) 1 0

5 HYDROGEN (𝐻2 ) 100 0

6 CARBON MONOXIDE (CO) 350 76

7 CARBON DIOXIDE (𝐶𝑂2) 2500 162