Pan Nell 2013
Pan Nell 2013
                             I. INTRODUCTION
       S wind power begins to represent a greater proportion of
A      total generation capacity, wind farms are having greater
influence over power system behavior. In this scenario, wind
                                                                                     sion, or, catastrophically, the cascade disconnection of genera-
                                                                                     tors leading to a system underfrequency event and widespread
                                                                                     consumer disconnection. If wind generation is to form a robust
farms are required to contribute to the stability of the system,
                                                                                     component of the electrical power system, wind farms must con-
including the key issue of fault-ride-through (FRT), which refers
                                                                                     tribute to the stability and reliability of the transmission grid,
to the capability of generation plant to remain connected, dy-
                                                                                     including the provision of grid support during grid faults, or
namically stable, and offer network support throughout a serious
                                                                                     voltage dips. Consequently, various national transmission sys-
voltage disturbance on the transmission network. Although the
                                                                                     tem grid codes now require wind farms to remain connected
voltage dips associated with grid faults may last for only a few
                                                                                     during specified voltage dips, and to supply active and reactive
cycles, they can bring about certain undesirable characteristics
                                                                                     power into the network.
of induction-machine generators [1], [2]. These include: uncon-
                                                                                        Doubly fed induction generator (DFIG) technology is
trolled active and reactive power, continued voltage suppres-
                                                                                     presently dominant in the growing global market for variable
                                                                                     speed wind power generation, due to its cost-effective, partially
                                                                                     rated power electronic converters. However, the DFIG is sensi-
   Manuscript received July 11, 2012; revised November 19, 2012 and Febru-           tive to dips in supply voltage because the internal machine flux
ary 28, 2013; accepted April 16, 2013. This work was supported by the                is exposed directly to the electrical grid. The induction generator
U.K.’s Engineering and Physical Sciences Research Council (EPSRC) through            very quickly loses internal magnetization in proportion to the
the Engineering Doctorate Programme at Newcastle University. Paper no.
TEC-00361-2012.                                                                      lost voltage producing large outrush currents on both stator and
   G. Pannell is with AC Renewable Energy Systems Limited, Hertfordshire,            rotor circuits. Without specific measures to protect against “ride
WD4 8LR, U.K. (e-mail: graham.pannell@res-ltd.com).                                  through” grid faults, a DFIG risks damage to its power electronic
   B. Zahawi, D. J. Atkinson, and P. Missailidis are with the School of Elec-
trical and Electronic Engineering, Newcastle University, Newcastle upon Tyne,        devices and dc-link capacitors due to the resulting overcurrents
NE1 7RU, U.K. (e-mail: bashar.zahawi@ncl.ac.uk; dave.atkinson@ncl.ac.uk;             and/or overvoltages. Conventional converter protection is via
petros.missailidis@ncl.ac.uk).                                                       a sustained period of rotor–crowbar application [3], [4] that
   Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.                                                       protects the power converter while allowing the converter to re-
   Digital Object Identifier 10.1109/TEC.2013.2261301                                sume control at the earliest possible opportunity. Fig. 1 shows
                                                                  0885-8969/$31.00 © 2013 IEEE
        This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Fig. 6. Back-to-back converter stack including brake chopper circuit: (a) front
view; (b) rear view.
B. Test Results
   Results for a 15% fault test are given in Fig. 7, showing a
single rectification period following each of fault initiation and
clearance during which transient rotor overcurrents were di-
verted from the converter IGBTs. The dc-link voltage was well
maintained by the brake chopper in this test, scarcely passing                      Fig. 7. DC brake chopper; controlled delay method (shaded area indicates
820 V on either fault initiation or clearance. Near-dc components                   rectification operation).
         This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
                                                                                                                  V. CONCLUSION
                                                                                       The use of a dc brake chopper circuit as a DFIG FRT device
                                                                                    in response to grid faults was investigated in this paper using
                                                                                    a 7.5 kW experimental test facility. Using a simple, delayed
                                                                                    control method for the resumption of PWM control, the dc-link
                                                                                    brake was shown to successfully maintain the dc-link voltage
                                                                                    within safe limits, while potentially dangerous rotor overcur-
                                                                                    rents were allowed to conduct safely through (overrated) ro-
                                                                                    tor converter diodes. Power control was restored within about
                                                                                    80 ms of each disengagement of the rotor converter’s switches,
                                                                                    which occurred once for each voltage step of fault initiation and
                                                                                    clearance.
                                                                                       However, the periods of converter disengagement and the
                                                                                    length of time required to restore power control were each sig-
                                                                                    nificantly longer than what could be achieved with a rotor crow-
                                                                                    bar circuit. This is because the dc-link brake chopper fundamen-
                                                                                    tally does not assist the demagnetization process of the machine,
                                                                                    whereas the crowbar can shorten the rotor decay timescale. The
                                                                                    dc brake fully demagnetizes the rotor before forcing the charac-
                                                                                    teristic slow stator flux decay. The result is a delayed resumption
                                                                                    in control.
                                                                                       A more sophisticated minimum threshold type dc brake con-
                                                                                    troller in which the application of the dc chopper brake is re-
                                                                                    leased by a predefined rotor current threshold and feedback
                                                                                    control carefully restored to minimize the rectification period
                                                                                    was also developed and tested but failed to deliver satisfactory
                                                                                    results. The slower machine demagnetization meant that the
Fig. 9. Minimum threshold crowbar test results (shaded area indicates crowbar       current controllers could not gain good control after the rectifi-
operation).                                                                         cation period following fault initiation and clearance triggering
                                                                                    further multiple rectification periods.
                                                                                       As a stand-alone protection device, the dc brake chopper
   A similar pattern emerged from voltage recovery where three                      could be relatively easily retrofitted to an existing DFIG con-
rectification periods were triggered by the rotor currents and the                  verter. The total unit costs may also be less than the crowbar:
power output became highly oscillatory. Each time the PWM                           the IGBT brake switch need only be rated for little more than
was disengaged, the PQ controllers were reset, which helps to                       1 pu rotor current (determined by the maximum dc-link voltage
explain the extended duration of poor control through the fault                     and the brake resistor). Up-rating individual diodes is relatively
period and beyond.                                                                  cheap but the requirement to house the nonstandard diodes may
   The dc link experienced a rapid overvoltage on fault initiation                  add a significant overhead.
of 126 V in 12.8 ms. Above 810 V, the brake resistor was                               However, in terms of its overall electrical performance as a
engaged. After 13 ms, the transient overcurrents fell, the power                    stand-alone FRT device, the dc brake chopper offers inferior
dumped on the dc link fell away, and the dc-link brake chopped                      electrical characteristics when compared with crowbar based
the voltage back down to under 800 V. At fault clearance, in                        methods; particularly in terms of the rapidity with which full
a similar manner a peak of 862 V was experienced. Again the                         control may be restored. This is because the dc-link brake funda-
chopper returned the voltage below 800 V before the line-side                       mentally does not assist the demagnetization process of the ma-
converter, controlling power export via the recovery voltage,                       chine following a fault event, whereas the crowbar can shorten
restored a settled 750 V operational dc voltage within 300 ms                       the rotor decay timescales with the appropriate choice of crow-
of stator voltage recovery.                                                         bar resistance, thereby leading to much quicker resumption in
   In contrast, the successful operation of the minimum thresh-                     control. A dc brake may nonetheless be considered valuable for
old controller when used for crowbar operation is demonstrated                      converters with low values of dc-link capacitance; these may be
in Fig. 9. The stable performance of the controller is reflected                    more sensitive to incoming overcurrents.
by the fact that the crowbar circuit was engaged only twice.
The first crowbar application, 1.2 ms after the fault, lasted for
13.0 ms. The second application, 6.6 ms after fault clearance,                                                      REFERENCES
lasted for 15.6 ms. During the first instance of crowbar applica-
                                                                                     [1] S. K. Salman and A. L. J. Teo, “Windmill modeling consideration and
tion, the dc-link voltage barely registered the event. The second                        factors influencing the stability of a grid-connected wind power-based
led to a safe excursion of only 30 V. The rotor currents flowing                         embedded generator,” IEEE Trans. Power Syst., vol. 18, no. 2, pp. 793–
through the converter remained below 2 pu for the whole test.                            802, May 2003.
          This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
 [2] Z. Chen, Y. Hu, and F. Blaabjerg, “Stability improvement of induction                                     Graham Pannell received the B.A. degree in physics
     generator-based wind turbine systems,” IET Renewable Power Genera-                                        from the University of Cambridge, Cambridge, UK,
     tion, vol. 1, no. 1, pp. 81–93, Mar. 2007.                                                                in 2001, and the Ph.D. degree in engineering from
 [3] S. Seman, J. Niiranen, S. Kanerva, A. Arkkio, and J. Saitz, “Performance                                  Newcastle University, Newcastle upon Tyne, UK, in
     study of a doubly fed wind-power induction generator under network                                        2008.
     disturbances,” IEEE Trans. Energy Convers., vol. 21, no. 4, pp. 883–890,                                     He is currently a Senior Engineer with AC Renew-
     Dec. 2006.                                                                                                able Energy Systems Limited, Hertfordshire, UK. He
 [4] O. Gomis-Bellmunt, A. Junyent-Ferre, A. Sumper, and J. Bergas-Jan,                                        was a Research Engineer with Econnect Ltd. where
     “Ride-through control of a doubly fed induction generator under un-                                       he was involved in cost-effective improvements in
     balanced voltage sags,” IEEE Trans. Energy Convers., vol. 23, no. 4,                                      doubly fed induction generator performance.
     pp. 1036–1045, Dec. 2008.
 [5] J. Morren and S. W. H de Haan, “Short-circuit current of wind turbines
     with doubly fed induction generator,” IEEE Trans. Energy Convers.,
     vol. 22, no. 1, pp. 174–180, Mar. 2007.
 [6] A. Causebrook, D. J. Atkinson, and A. G. Jack, “Fault ride-through of
     large wind farms using series dynamic braking resistors,” IEEE Trans.                                       Bashar Zahawi (M’96–SM’04) received the B.Sc.
     Power Syst., vol. 22, no. 3, pp. 966–975, Aug. 2007.                                                        and Ph.D. degrees in electrical and electronic engi-
 [7] J. Yang, J. E. Fletcher, and J. O’Reilly, “A series-dynamic-resistor-based                                  neering from Newcastle University, Newcastle upon
     converter protection scheme for doubly-fed induction generator during                                       Tyne, UK, in 1983 and 1988, respectively.
     various fault conditions,” IEEE Trans. Energy Convers., vol. 25, no. 2,                                         From 1988 to 1993, he was a Design Engineer
     pp. 422–432, Jun. 2010.                                                                                     with a UK manufacturer of large variable speed drives
 [8] X. Yan, G. Venkataramanan, Y. Wang, Q. Dong, and B. Zhang, “Grid-                                           and other power conversion equipment. In 1994, he
     fault tolerant operation of a DFIG wind turbine generator using a pas-                                      was appointed as a Lecturer in electrical engineering
     sive resistance network,” IEEE Trans. Power Electron., vol. 26, no. 10,                                     at the University of Manchester. In 2003, he joined
     pp. 2896–2905, Oct. 2011.                                                                                   the School of Electrical and Electronic Engineering,
 [9] Y. Ren and W. Zhang, “A novel control strategy of an active crowbar for                                     Newcastle University, UK, as a Senior Lecturer. His
     DFIG-based wind turbine during grid faults,” in Proc. IEEE Int. Conf.           current research interests include small-scale generation, power conversion, and
     Electric Machines Drives (IEMDC), Niagara Falls, ON, Canada, May                the application of nonlinear dynamical methods to electrical circuits and sys-
     2011, pp. 1137–1142.                                                            tems.
[10] G. Pannell, D. J. Atkinson, and B. Zahawi, “Minimum-threshold crowbar              Dr Zahawi is a Chartered Electrical Engineer and the recipient of the Cromp-
     for a fault-ride-through grid-code-compliant DFIG wind turbine,” IEEE           ton Premium awarded by the Institution of Electrical Engineers (IEE) and the
     Trans. Energy Convers., vol. 25, no. 3, pp. 750–759, Sep. 2010.                 Denny Medal awarded by the Institute of Marine Engineering, Science & Tech-
[11] C. Wessels, F. Gebhardt, and F. W. Fuchs, “Fault ride-through of a DFIG         nology (IMarEST).
     wind turbine using a dynamic voltage restorer during symmetrical and
     asymmetrical grid faults,” IEEE Trans. Power Electron., vol. 26, no. 3,
     pp. 807–815, Mar. 2011.
[12] J. P. da Costa, H. Pinheiro, T. Degner, and G. Arnold, “Robust controller
     for DFIGs of grid-connected wind turbines,” IEEE Trans. Ind. Electron.,                                   David J. Atkinson received the B.Sc. in electrical and
     vol. 58, no. 9, pp. 4023–4038, Sep. 2011.                                                                 electronic engineering from Sunderland Polytechnic,
[13] I. Erlich, H. Wrede, and C. Feltes, “Dynamic behaviour of DFIG-based                                      Sunderland, UK, in 1978, and the Ph.D. degree from
     wind turbines during grid faults,” presented at IEEE Power Convers. Conf.                                 Newcastle University, Newcastle upon Tyne, UK, in
     (PCC 2007), Nagoya, Japan.                                                                                1991.
[14] K. E. Okedu, S. M. Muyeen, R. Takahashi, and J. Tamura, “Wind farms                                           In 1987, he joined Newcastle University, where he
     fault ride through using DFIG with new protection scheme,” IEEE Trans.                                    is currently a Senior Lecturer in the Power Electron-
     Sustainable Energy, vol. 3, no. 2, pp. 242–254, Apr. 2012.                                                ics, Drives and Machines Research Group, School of
[15] B. Gong, D. Xu, and B. Wu, “Cost effective method for DFIG fault                                          Electrical and Electronic Engineering. For 17 years,
     ride-through during symmetrical voltage dip,” in Proc. 36th Annu. IEEE                                    he was with NEI Reyrolle Ltd and British Gas Corpo-
     Ind. Electron. Soc. Conf. (IECON 2010), Phoenix, AZ, USA, Nov. 2010,                                      ration. His current research interests include control
     pp. 3269–3274.                                                                  of power electronics systems including electric drives and converters.
[16] J. Shi, Y. Tang, Y. Xia, L. Ren, and J. Li, “SMES based excitation system          Dr Atkinson is a Chartered Electrical Engineer.
     for doubly-fed induction generator in wind power application,” IEEE
     Trans. Appl. Supercond., vol. 21, no. 3, pp. 1105–1108, Jun. 2011.
[17] W. Guo, L. Xiao, and S. Dai, “Enhancing low-voltage ride-through ca-
     pability and smoothing output power of DFIG with a superconducting
     fault-current limiter–magnetic energy storage system,” IEEE Trans. En-                                      Petros Missailidis received the B.S degree in me-
     ergy Convers., vol. 27, no. 2, pp. 277–295, Jun. 2012.                                                      chanical engineering from Aristotelian University of
[18] T. Kawady, C. Feltes, I. Erlich, and A. I. Taalab, “Protection system be-                                   Thessaloniki, Thessaloniki, Greece, in 1986, the M.S.
     havior of DFIG based wind farms for grid-faults with practical considera-                                   degree in mechanical engineering from the University
     tions,” in Proc. IEEE Power Energy Soc. General Meeting, Minneapolis,                                       of Buffalo, NY, USA, in 1990, the M.S. degrees in
     Minnesota, USA, Jul. 2010, pp. 1–6.                                                                         electrical and electronic engineering and biomedical
[19] T. Kawady, H. Shaaban, and A. El-Sherif, “Investigation of grid-support                                     engineering from Rensselaer Polytechnic Institute,
     capabilities of doubly fed induction generators during grid faults,” in Proc.                               Troy, NY, in 1993, the M.S. degree in mechanical
     IET Conf. Renewable Power Generation (RPG 2011), Edinburgh, U.K.,                                           engineering from the same institute in 1995, and the
     Sep., pp. 1–7.                                                                                              Ph.D. degree in mechanical engineering from Rens-
[20] D. J. Atkinson, G. Pannell, W. Cao, B. Zahawi, T. Abeyasekera, and                                          selaer Polytechnic Institute, in 2000.
     M. Jovanovic, “A doubly-fed induction generator test facility for grid              He was with ComHouse Wireless Inc., M/A-COM Inc., General Electric
     fault ride-through analysis,” IEEE Instrum. Meas. Mag., vol. 15, no. 6,         Schenectady NY, Erie County Medical Centre, Buffalo, NY, and the University
     pp. 20–27, Dec. 2012.                                                           of Toronto. He is currently with the School of Electrical and Electronics Engi-
[21] G. Pannell, D. J. Atkinson, and B. Zahawi, “Analytical study of grid-fault      neering, Newcastle University, Newcastle upon Tyne, UK, where he is involved
     response of wind turbine doubly fed induction generator,” IEEE Trans.           in conducting research in the areas of system identification, nonlinear control,
     Energy Convers., vol. 25, no. 4, pp. 1081–1091, Dec. 2010.                      and control of electric drives.