Design For Isolation Room
Design For Isolation Room
Facility Design
Resource
© Copyright 2003
Phoenix Controls Corporation
The material in this paper is for information purposes only and is subject to change without notice. Phoenix Controls
Corporation assumes no responsibility for any errors or for consequential damages that may result from the use,
misrepresentation, or translation of any of the material in this publication.
Printed in USA
Phoenix Controls
Health Care Facility Design Resource
Introduction..................................................................................... 3
System Components.................................................................... 17
Ventilation Requirements
Hospitals and health care facilities have many different types of specialized functional
spaces to fulfill patient needs. General ventilation systems should be designed to flow
from more clean to less clean areas. However, certain areas require higher levels of
Requirements
Ventilation
infection control, necessitating continuous control of airflow direction. Below is a sample
list of room types and their pressure relationships to adjacent areas:
Surgical and critical care areas:
Operating room Positive
Delivery room Positive
Nursery suite Positive
Bronchoscopy Negative
Triage Negative
Ancillary:
Laboratory, general Negative
Laboratory, pathology Negative
Laboratory, serology Positive
Autopsy Negative
Nursing:
Protective environment Positive
Airborne infection isolation Negative
Isolation anteroom Positive/Negative1
Airborne infectious isolation rooms are used to prevent the spread of infection from the
patient to others, and therefore have inward directional airflow making the room nega-
tively pressurized. Examples of use would be for patients with tuberculosis or smallpox.
The airflow for protective environments (PEs) flows outward from the room to the
adjacent space, keeping potential infection from the patient and thus are positively
pressurized. For example, PE would be used for organ transplant recipients or burn
patients.
When an immunocompromised patient also requires airborne infection isolation, then
an anteroom is required. The anteroom provides additional protection against escaping
pathogens when the doors are opened and closed. In each situation, directional airflow is
achieved by maintaining the desired pressure relationship between the room and the
corridor, and/or an anteroom.
There are three common approaches to anteroom relative pressurization according to
1 the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)
American Society of Heating, Refrigerating
and Air-Conditioning Engineers (ASHRAE), with the preference for having the anteroom positive to the room and its surrounding
2003 ASHRAE Handbook: HVAC Applica-
tions, p. 7.6. space for protective environments.2 The American Institute of Architects (AIA) states
Filtration
Ventilation controls are normally supple-
3. The anteroom is positive to the room and negative to the corridor.
mented with high-efficiency particulate
air filtration (HEPA) on either the ex-
(This approach corresponds to the “Infectious Isolation Environ-
haust side (infectious) and/or supply side ment with an Anteroom Negative to the Corridor” application on
(protective). These air-cleaning devices pages 12-13.)
are capable of removing 99.97% of par-
ticles greater than or equal to 0.3 mi- AII with Anteroom
crons in diameter. For more information,
see the “Filtration” section of the stan-
dards and guidelines on page 31. Patient room (-) Anteroom (+)
(-) Corridor (+)
Ultraviolet germicidal irradiation (UVGI)
may be used to provide supplemental
engineering control. Units may be in-
stalled in the exhaust air ducts or on or
near the ceiling to irradiate upper room
air. While not recommended as a pri-
mary infection control measure, UVGI is
most often used against mycobacterium
tuberculosis (TB).
2
American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE), 2003 ASHRAE Handbook: HVAC Applica-
tions, p. 7.3.
Requirements
Ventilation
Both approaches create a pressure differential; however, based on years of controlling
pressurization in critical laboratory environments, Phoenix Controls has found volu-
metric offset to be a very stable, reliable method of control. Differential pressure sensing
has historically been more difficult, less stable and dependent on sensor accuracy and
maintenance. In the Z9.5-2003 standard, the American National Standards Institute (ANSI)
and the American Industrial Hygiene Association (AIHA) support the use of volumetric
offset over differential pressure for laboratory environments: “...specifying quantitative
pressure differential is a poor basis for design…What really is desired is an offset air
volume. Attempts to design using direct pressure differential measurement and control
vs. controlling the offset volume may result in either short or extended periods of the
loss of pressure when the doors are open or excessive pressure differentials when the
doors are closed, sufficient to affect the performance of the low pressure fans.”3
Ventilation Rates
For new construction, a minimum of 12 air changes per hour (ACH) for infectious and
protective isolation rooms is recommended. Anterooms and toilet rooms may be slightly
less at 10 ACH. Many existing facilities may have lower ACH because prior to 2001, the
minimum was 6 ACH. For more information, see the “Air Change Rates” section of the
standards and guidelines on page 26.
This chapter describes ventilation control options and • Infectious Isolation Environment with
applications designed to meet the special airflow require- an Anteroom Negative to Corridor, 12
ments of health care facilities. • Protective Environment with Airborne
Infectious Isolation (positive anteroom), 13
• Protective Environment with Airborne
Infectious Isolation (neg. anteroom), 15
Airflow Control Solutions
A broad array of control sequences may be used to meet the specialized airflow require-
ments of health care facilities. Five of these are presented in this section:
• Infectious isolation environment without an anteroom
• Protective environment without an anteroom
• Infectious isolation environment with an anteroom negative to the corridor
• Protective environment with airborne infectious isolation (the anteroom is positive
to the patient room and the corridor)
• Protective environment with airborne infectious isolation (the anteroom is negative
to the patient room and the corridor)
Airflow Control
Infectious Isolation Environment without an
Solutions
Anteroom
The isolation room is supplied and exhausted with a constant volume of air to meet
ventilation, pressurization and thermal requirements. The room’s pressurization is main-
tained by a fixed volumetric offset between the supply and exhaust air volumes. A local
pressure monitor provides visual confirmation of status and audible and visual alarms if
the room pressure is not as desired.
Sequence of Operation
Individual constant volume air valves maintain the supply airflow into the room and the
exhaust airflow out of the room. A fixed constant volume offset is maintained by setting
the exhaust air volume greater than the supply volume. The offset produces negative
pressure in the isolation room relative to the corridor.
A room pressure monitor is installed next to the door entering the isolation room. A
pneumatic room sensor and a reference sensor in the adjoining space provide direct
measurement of pressure. A green status light indicates that the room is negatively
pressured or “normal.” A red light and audible alarm sounds upon an unspecified loss of
pressurization. A mute button silences the audible portion of the alarm. As an additional
optional feature, the third light signals “caution,” indicating that the pressure drop across
the constant volume valves is not being maintained. An adjustable alarm delay prevents
nuisance alarms caused by opening the door. The monitor displays room pressurization
to 0.0001 inches of water gauge (0.0249 Pa).
CVV P
220
280
Room
HEPA
Sensor
20
24 VAC
3C P
CVV
Offset
80
Reference
2C 2C Active Sensor
Pressure Supply Air
Monitor
LEGEND
NOTES:
P Factory Installed Pressure Switch
1. Refer to Room Schedule Sheet (RSS).
CVV Constant Volume Valve 2. Valves are shown horizontally for diagrammatical
purposes only. Actual valve orientation must be
BMS Building Management System
specified for each application.
Field Installed Pneumatics 3. Depending on the form of isolation, ventilation
Cable by Others
design or jurisdiction, HEPA filtration may or
may not be required.
Reheat Valve
CVV P
Airflow Control
Solutions
200
100
HEPA
Room
Sensor
30
24 VAC
3C P
CVV
Offset
70
Reference
2C 2C Active Sensor Supply Air
Pressure
Monitor
LEGEND NOTES:
1. Refer to Room Schedule Sheet (RSS).
P Factory Installed Pressure Switch 2. Valves are shown horizontally for diagrammatical
purposes only. Actual valve orientation must be
CVV Constant Volume Valve
specified for each application.
BMS Building Management System 3. Depending on the form of isolation, ventilation
design or jurisdiction, HEPA filtration may or
Field Installed Pneumatics
may not be required.
Cable by Others
Reheat Valve
CVV P
CVV
220 P
Room Offset 2C
Sensor 80
Reference
50 Sensor
H CVV
E
P
P A 50 50 P
CVV
24 VAC
3C HEPA
3C Offset
80
2C Active 2C
Pressure Reference Sensor Supply Air
Monitor
2C
2C
4-20 mA/0-10 volts
BMS
Airflow Control
NOTES:
LEGEND 1. Refer to Room Schedule Sheet (RSS).
Solutions
2. Valves are shown horizontally for diagrammatical
P Factory Installed Pressure Switch purposes only. Actual valve orientation must be
CVV Constant Volume Valve specified for each application.
3. Depending on the form of isolation, ventilation
BMS Building Management System design or jurisdiction, HEPA filtration may or
Field Installed Pneumatics may not be required.
4. In this example, the anteroom is positive to the
Cable by Others patient room and negative to the corridor.
Reheat Valve 5. Valves in the anteroom are used for maintaining
ventilation and proper pressurization in lieu of
balancing dampers.
CVV
220 P
Room Offset 2C
Sensor 80
50
H CVV
E
P
P A 50 210 P
CVV
HEPA
Reference
Sensor
Offset
80
2C Active 2C
Pressure Supply Air
24 VAC
Monitor
2C
2C
4-20 mA/0-10 volts
BMS
NOTES:
LEGEND 1. Refer to Room Schedule Sheet (RSS).
2. Valves are shown horizontally for diagrammatical
P Factory Installed Pressure Switch purposes only. Actual valve orientation must be
CVV Constant Volume Valve specified for each application.
3. Depending on the form of isolation, ventilation
BMS Building Management System design or jurisdiction, HEPA filtration may or
Field Installed Pneumatics may not be required.
4. In this example, the anteroom is positive to the
Cable by Others patient room and positive to the corridor.
Reheat Valve 5. Valves in the anteroom are used for maintaining
ventilation and proper pressurization in lieu of
balancing dampers.
Airflow Control
room sensor in the patient room and a reference sensor in the anteroom provide direct
Solutions
measurement of pressure. A green status light indicates that the patient room is positively
pressurized or “normal.” A red light and audible alarm sounds upon an unspecified loss of
pressurization. A mute button silences the audible portion of the alarm. As an additional
optional feature, the third light signals “caution,” indicating that the pressure drop across
the constant volume valves is not being maintained. An adjustable alarm delay prevents
nuisance alarms caused by opening the door. The monitor displays the room pressurization
to 0.0001 inches of water gauge (0.0249 Pa).
Fail-safe Condition
Since constant volume valves require neither pneumatic air nor power, a fail-safe condition
does not apply to this application. The patient room is always in a protective containment
mode.
CVV
200 P
70
Room Offset 2C
Sensor 80
50
H CVV
E
P
P A 210 50 P
CVV
24 VAC
3C HEPA
3C Offset
80
2C Active 2C
Pressure Reference Sensor Supply Air
Monitor
2C
2C
4-20 mA/0-10 volts
BMS
NOTES:
LEGEND 1. Refer to Room Schedule Sheet (RSS).
2. Valves are shown horizontally for diagrammatical
P Factory Installed Pressure Switch purposes only. Actual valve orientation must be
CVV Constant Volume Valve specified for each application.
3. Depending on the form of isolation, ventilation
BMS Building Management System design or jurisdiction, HEPA filtration may or
Field Installed Pneumatics may not be required.
4. In this example, the anteroom is positive to the
Cable by Others
patient room and negative to the corridor.
Reheat Valve 5. Valves in the anteroom are used for maintaining
ventilation and proper pressurization in lieu of
balancing dampers.
System Components
System Components
and a large open area provides
the desired flow.
Valve Construction
Applications require that each valve be built to withstand unique environments. The
Accel II valves are available in the following construction types:
• Class A: Non-corrosive atmosphere—supply air, return air, and many general exhaust
applications
• Class B: Corrosive environments—corrosive gaseous decontamination agents
dent regulator with a high-speed position/airflow controller to meet the unique require-
ACTUATOR
T
COVER TAB
DO NOT BLOCK
Access required after installation
20 PSI
END VIEW Phoenix Controls
Corporation
ments of airflow control. These valves can be used in constant volume, two-position, or
Newton, MA 02158 USA
PATENT NOS. 5,304,093 / 5,251,665 AND PATENTS PENDING
Specifications
Construction • Compressor sizing: Accel II valves are not continuous air-consuming
• 16 ga. spun aluminum valve body with continuous welded seam devices. For compressor sizing, use:
• Valve bodies available as uncoated aluminum or with corrosion- • single and dual valves: 10 scim
resistant baked phenolic coatings • triple and quad valves: 20 scim
• Composite Teflon® shaft bearings Electric Actuation:
• Spring grade stainless steel spring and PPS slider assembly • 24 Vac (±15%) @60Hz
• Supply valves* insulated with 3/8" (9.5 mm) flexible closed-cell • single and dual valves: 48 VA
polyethylene. Flame/smoke rating 25/50. Density is 2.0 lb/ft3 (32.0 • triple and quad valves: 96 VA
kg/m 3).
Operating Range
• 32-125° F (0-50° C) ambient * Not applicable to CVV series.
• 10-90% non-condensing RH
Teflon is a registered trademark of DuPont Co.
Sound
Designed for low sound power levels to meet
or exceed ASHRAE noise guidelines.
Constant
Performance Feature/Option Volume Two-position Upgradeable VAV VAV
• Pressure independent over a 0.6"-3.0" wc (CVV) (PEV/PSV) (BEV/BSV) (EXV/MAV) (EXV/MAV)
(150-750 Pa) drop across valve
System Components
• Volume control accurate to ±5% of airflow
command signal C P B A A
• No additional straight duct runs needed before or Control type Constant Pneumatic Base Analog Analog
after valve Volume Upgradeable
• Available in flows from 35-6000 cfm Actuator type Fixed Pneumatic Pneumatic Pneumatic Electric
(60-10,000 m3/hr) or Fixed
• Response time to change in command signal:
<1 second Flow feedback signal — — Option 9 9
• Response time to change in duct static pressure: Failsafe Fixed NO/NC NO/NC NO/NC NO/NC or
<1 second Last Posit.
VAV Controller Factory-insulated
Controller Power: valve body (supply) Option 9 9 9 9
• ±15 Vdc @ 0.145 amp (pneumatic only) Field-adjustable flow 9 9 9 9 9
• 0-10 Vdc command signal
• 0-10 Vdc flow feedback signal Flow alarm via
• 0-10 Vdc alarm signal feedback circuit — — — 9 9
Pneumatic Actuation: Flow alarm via
• Only applicable to PEV, PSV, BEV/BSV and EXV/ pressure switch Option Option Option Option Option
MAV-N (pneumatic control type) Low-noise diffuser
• 20 psi (-0/+2 psi) with a 20 micron filter main air construction† 9 9 9 9 9
required (except for CVV)
All valves include pressure independent controllers, factory-calibrated position controllers, and are
available in flows from 35-6000 cfm (60-10,000 m 3/hr).
†Accel II valves are designed to reduce sound over all frequencies, but significantly target the lower bands
(125-500 Hz) to help eliminate the need for silencers.
COVER TAB
DO NOT BLOCK
Access required after installation
D E
20 PSI
E
B
B
C F C A
F
Triple Quad
(Make-up Air (Constant Volume
Valve shown) Valve shown)
G
E B
D
D
B
A
A
F C F C
8 — 7.88 23.50 — 14.00 13.00 28.00 10.13 — 200 597 — 356 330 711 260
10 — 9.88 21.75 — 16.50 15.00 26.00 11.00 — 251 552 — 420 381 660 279
12 — 11.88 26.81 — 18.50 17.00 32.50 12.13 — 302 681 — 470 432 826 308
2-10 20.13 10.13 24.75 1.50 16.50 16.50 28.38 — 511 257 629 38 420 420 721 —
2-12 24.13 12.13 29.81 1.50 18.00 18.00 35.00 — 613 308 757 38 457 457 889 —
3-12 36.38 12.13 29.81 1.50 18.00 18.00 35.00 36.63 924 308 757 38 457 457 889 930
4-12 48.50 12.13 29.81 1.50 18.00 18.00 35.00 — 1232 308 757 38 457 457 889 —
* outer dimension ** maximum of all valve types (some configurations may be smaller)
Operating Ranges
Flow (cfm) Flow (m 3/h) Flow (l/s)
0.6"-3.0" wc 150-750 Pa 150-750 Pa
System Components
Response Operating Temperature
< 0.25 seconds for full span 32-160° F (0-70° C) Adjustable alarm time delay (0-30 seconds) 9 9
input
Storage Temperature Field reversible pressurization alarm 9 9
Standard Range -40-180° F (-40-82° C)
±0.05" wc (±12.5 Pa) Remote reversible pressurization alarm 9
Weight
Optional Ranges 2.1 pounds (0.95 Kg) Remote flow alarm input 9
±0.1" wc (±25 Pa)
±0.2" wc (±50 Pa)
±0.5" wc (±125 Pa)
±1.0" wc (±250 Pa)
±2.0" wc (±500 Pa)
±5.0" wc (±1250 Pa)
Display
4 digit LED
0.5" height
Analog Output
Field selectable: 4-20 mA, 12
mA at zero pressure
or
0-10 Vdc, 5 Vdc at zero
pressure
24 VAC
Power
HVAC Systems
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54279
“Two types of general ventilation systems can be used for dilution and removal of contaminated air: the single-pass
system and the recirculating system. In a single-pass system, the supply air is either outside air that has been appropri-
ately heated and cooled or air from a central system that supplies a number of areas. After air passes through the room
(or area), 100% of that air is exhausted to the outside. The single-pass system is the preferred choice in areas where
infectious airborne droplet nuclei are known to be present (e.g., TB isolation rooms or treatment rooms) because it
prevents contaminated air from getting recirculated to other areas of the facility.
“In a recirculating system, a small portion of the exhaust air is discharged to the outside and is replaced with fresh
outside air, which mixes with the portion of exhaust air that was not discharged to the outside. The resulting mixture,
which can contain a large proportion of contaminated air, is then recirculated to the areas serviced by the system. This
air mixture could be recirculated into the general ventilation, in which case contaminants may be carried from
contaminated areas to uncontaminated areas. Alternatively, the air mixture could also be recirculated within a specific
room or area, in which case other areas of the facility will not be affected.”
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54260
“Air from TB isolation rooms and treatment rooms used to treat patients who have known or suspected infectious TB
should be exhausted to the outside in accordance with applicable federal, state and local regulations. The air should not
be recirculated into the general ventilation. In some instances, recirculation of air into the general ventilation system
from such rooms is unavoidable (i.e., in existing facilities in which the ventilation system or facility configuration makes
venting the exhaust to the outside impossible). In such case, HEPA filters should be installed in the exhaust duct leading
from the room to the general ventilation system to remove infectious organisms and particulates the size of droplet
Standards & Guidelines
nuclei from the air before it is returned to the general ventilation system.”
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54284
“Individual room-air recirculation can be used in areas where there is no general ventilation system, where an existing
system is incapable of providing adequate airflow, or where an increase in ventilation is desired without affecting the
fresh air supply or negative pressure system already in place. Recirculation of HEPA-filtered air within a room can be
Recirculated
All air exhausted by means of
directly to outdoors6 room units7
Protective environment room – No
Airborne infection isolation room Yes No
Isolation alcove or anteroom Yes No
6
“Air from areas with contamination and/or odor problems shall be exhausted to the outside and not recirculated to other areas. Note
that individual circumstances may require special consideration for air exhaust to outside, e.g., in intensive care units in which
patients with pulmonary infection are treated, and rooms for burn patients.
7
“Recirculating room HVAC units refers to those local units that are used primarily for heating and cooling of air, and not disinfection
of air. Because of cleaning difficulty and potential for buildup of contamination, recirculating room units shall not be used in areas
marked ‘No.’ However, for airborne infection control, air may be recirculated within individual isolation rooms if HEPA filters are
used. Isolation and intensive care unit rooms may be ventilated by reheat induction units in which only the primary air supplied
from a central system passes through the reheat unit. Gravity-type heating or cooling units such as radiators or convectors shall not
be used in operating rooms and other special care areas.”
* Note 2: “Design of the ventilation system shall provide air movement which is generally from clean to less clean areas. If any form of
variable air volume or load shedding system is used for energy conservation, it must not compromise the corridor-to-room pressure
balancing relationships or the minimum air changes required by the table.”
Room Pressurization/Anterooms
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54281
“The minimum pressure difference necessary to achieve and maintain negative pressure that will result in airflow into
the room is very small (0.001 inch of water). Higher pressures (> 0.001 inch of water) are satisfactory: however, these
higher pressures may be difficult to achieve. The actual level of negative pressure achieved will depend on the difference
in the ventilation exhaust and supply flows and the physical configuration of the room, including the airflow path and
flow opening. If the room is well sealed, negative pressure greater than the minimum of 0.001 inch of water may be
readily achieved. However, if rooms are not well sealed, as may be the case in many facilities (especially older facilities),
achieving higher negative pressures may require exhaust/supply flow differentials beyond the capability of the ventila-
tion system.
“To establish negative pressure in a room that has a normally functioning ventilation system, the room supply and
exhaust airflows are first balanced to achieve an exhaust flow of either 10% or 50 cubic feet per minute (cfm) greater
than supply (whichever is the greater). In most situations, this specification should achieve a negative pressure of at
least 0.001 inch of water. If the minimum of 0.001 is not achieved and cannot be achieved by increasing the flow
differential (within the limits of the ventilation system), the room should be inspected for leakage (e.g., through doors,
windows, plumbing, and equipment wall penetrations), and corrective action should be taken to seal the leaks.
“Negative pressure in a room can be altered by changing the ventilation system operation or by opening and closing the
room’s doors, corridor doors, or windows. When an operating configuration has been established, it is essential that all
doors and windows remain properly closed in the isolation room and other areas (e.g., doors in corridors that affect air
pressure) except when persons need to enter or leave the room area...
“Although an anteroom is not a substitute for negative pressure in a room, it may be used to reduce escape of droplet
nuclei during opening and closing of the isolation room door. Some anterooms have their own air supply duct but
others do not. The TB isolation room should have negative pressure relative to the anteroom, but the air pressure in
the anteroom relative to the corridor may vary depending on the building design. This should be determined, in
accordance with applicable regulation, by a qualified ventilation engineer.”
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54282
“Differential pressure-sensing devices also can be used to monitor negative pressure; they can provide either periodic
(noncontinuous) pressure measurements or continuous pressure monitoring. The continuous monitoring compo- Standards & Guidelines
nents may simply be a visible and/or audible warning signal that air pressure is low. In addition, it may also provide a
pressure readout signal, which can be recorded for later verification or used to automatically adjust the facility’s
ventilation control system...
“Pressure-measuring devices should sense the room pressure just inside the airflow path into the room (e.g., at the
bottom of the door). Unusual airflow patterns within the room can cause pressure variations; for example, air can be
at negative pressure at the middle of a door and at positive pressure at the bottom of the same door...If the pressure-
sensing ports of the device cannot be located directly across the airflow path, it will be necessary to validate that the
negative pressure at the sensing point is and remains the same as the negative pressure across the flow path.
AIA Guidelines for Design and Construction of Hospital and Health Care Facilities, p. 23, Appendix
section A7.2.D.
“Immunosuppressed Host Airborne Infection Isolation (Protective Environment/Airborne Infection Isolation). An
anteroom is required for the special case in which an immunosuppressed patient requires airborne infection isola-
tion...There is no prescribed method for anteroom ventilation—the room can be ventilated with either of the following
airflow patterns: (a) airflows from the anteroom, to the patient room and the corridor, or (b) airflows from the patient
room and the corridor, into the anteroom. The advantage of pattern (a) is the provision for a clean anteroom in which
health care workers need not mask before entering the anteroom.”
2003 ASHRAE HVAC Applications Handbook, p. 7.8
“In cases where the patient is immunosuppressed but not contagious, a positive pressure should be maintained
between the patient room and adjacent area. Some jurisdictions may require an anteroom, which maintains a negative
pressure relationship with respect to the adjacent isolation room and an equal pressure to the corridor, nurses’ station,
or common area.
Filtration
CDC Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care
Facilities, p. 54283
“HEPA filtration can be used as a method of air cleaning that supplements other recommended ventilation measures.
For the purposes of these guidelines, HEPA filters are defined as air-cleaning devices that have a demonstrated and
documented minimum removal efficiency of 99.97% of particles greater than or equal to 0.3 mm (microns) in diameter.
HEPA filters have been shown to be effective in reducing the concentration of Aspergillus spores (which range in size
from 1.5 mm to 6 mm) to below measurable levels (100-102). The ability of HEPA filters to remove tubercle bacilli from
the air has not been studied, but M. tuberculosis droplet nuclei probably range from 1 mm to 5 mm in diameter (i.e.,
approximately the same size as Aspergillus spores). Therefore, HEPA filters can be expected to remove infectious
droplet nuclei from contaminated air. HEPA filters can be used to clean air before it is exhausted to the outside,
recirculated to other areas of a facility, or recirculated within a room. If the device is not completely passive, (e.g., it
utilizes techniques such as electrostatics) and the failure of the electrostatic components permits loss of filtration
efficiency to less than 99.97%, the device should not be used in systems that recirculate air back into the general facility
ventilation system from TB isolation rooms and treatment rooms in which procedures are performed on patients who
may have infectious TB...
“HEPA filters can be used in a number of ways to reduce or eliminate infectious droplet nuclei from room air or exhaust.
These methods include placement of HEPA filters (a) in exhaust ducts to remove droplet nuclei from air being
discharged to the outside, either directly or through ventilation equipment; (b) in ducts discharging room air into the
general ventilation system; and (c) in fixed or portable room-air cleaners. The effectiveness of portable HEPA room-air
cleaning units has not been evaluated adequately, and there is probably considerable variation in their effectiveness.
HEPA filters can also be used in exhaust ducts or vents that discharge air from booths or enclosures into the surround-
ing room...In any application, HEPA filters should be installed carefully and maintained meticulously to ensure adequate
function.”
2003 ASHRAE HVAC Applications Handbook, pp. 7.2-7.3
“All central ventilation or air-conditioning systems should be equipped with filters having efficiencies no lower than
Standards & Guidelines
those indicated in Table 1. Where two filter beds are indicated, Filter Bed No. 1 should be located upstream of the air-
conditioning equipment, and Filter Bed No. 2 should be downstream of the supply fan. Appropriate precautions should
be observed to prevent wetting the filter media by free moisture from humidifiers. Where only one filter bed is
indicated, it should be located upstream of air-conditioning equipment. All filter efficiencies are based on ASHRAE
Standard 52.2.
a
Where continuous direction control is not required, variations should be minimized; in no case should a lack of directional control allow spread of
infection from one area to another. Boundaries between functional areas (wards or departments) should have directional control. Lewis (1998) describes
ways to maintain directional control by applying air-tracking controls. Ventilation system design should provide air movement, generally from clean to
less clean areas. If any VAV or load-shedding system is used for energy conservation, it must not compromise pressure-balancing relationships or
minimum air changes required by the table. See note z for additional information.
b
Ventilation rates in this table cover ventilation for comfort, as well as for asepsis and odor control in areas of acute-care hospitals that directly affect
patient care. Ventilation rates in accordance with ASHRAE Standard 62, Ventilation for Acceptable Indoor Air Quality, should be used for areas for which
specific ventilation rates are not given. Where a higher outside air requirement is called for in Standard 62 than here, use the higher value.
c
Total air changes indicated should be either supplied or, where required, exhausted. Number of air changes can be reduced when the room is unoccu-
pied, if the pressure relationship is maintained and the number of air changes indicated is reestablished any time the space is used. Air changes shown are
minimum values. Higher values should be used when required to maintain room temperature and humidity conditions based on the cooling load of the
space (lights, equipment, people, exterior walls and windows, etc.).
d
Recirculating HEPA filter units used for infection control (without heating or cooling coils) are acceptable. Gravity-type heating or cooling units such as
radiators or convectors should not be used in operating rooms and other special-care areas.
e
For operating rooms, 100% outside air should be used only when codes require it and only if heat recovery devices are used.
f
“Trauma room” here is a first-aid room and/or emergency room used for general initial treatment of accident victims. The operating room in the trauma
center that is routinely used for emergency surgery should be treated as an operating room.
g
See section on Patient Rooms for discussion of central toilet exhaust system design.
h
“Airborne infectious isolation rooms” here are those that might be used for infectious patients in the average community hospital. The rooms are
negatively pressurized. Some may have a separate anteroom. See the section on Infectious Isolation Unit for more information.
i
Protective-environment rooms are those used for immunosuppressed patients, positively pressurized to protect the patient. Anterooms are generally
required and should be negatively pressurized with respect to the patient room.
Air movement
Area designation relationship to adjacent area2
SURGERY AND CRITICAL CARE
Operating/surgical cystoscopic rooms10, 11 Out
Delivery room10 Out
Recovery room10 –
Critical and intensive care –
Newborn intensive care –
Treatment room13 –
Trauma room13 Out
Anaesthesia gas storage In
Endoscopy In
Bronchoscopy11 In
ER waiting rooms In
Triage In
Radiology waiting rooms In
Procedure room Out
NURSING
Patient room –
Toilet room In
Newborn nursery suite –
Protective environment room11, 17 Out
Airborne infection isolation room11, 18 In
Isolation alcove or anteroom17, 18 In/Out
Labor/delivery/recovery –
Labor/delivery/recovery/postpartum –
Patient corridor –
ANCILLARY
Radiology19
X-ray (surgical/critical care and catheterization) Out
X-ray (diagnostic & treatment) –
Darkroom In
Laboratory
General19 –
Biochemistry19 Out
Cytology In
Glass washing In
Histology In
Microbiology19 In
Nuclear medicine In
Pathology In
Serology Out
Sterilizing In
Autopsy room11 In
Nonrefrigerated body-holding room In
Pharmacy Out
DIAGNOSTIC AND TREATMENT
Examination room –
Medication room Out
Treatment room –
Physical therapy and hydrotherapy In
Soiled workroom or soiled holding In
Clean workroom or clean holding Out
Air movement
Area designation relationship to adjacent area2
STERILIZING AND SUPPLY
ETO-sterilizer room In
Sterilizer equipment room In
Central medical and surgical supply
Soiled or decontamination room In
Clean workroom Out
Sterile storage Out
SERVICE
Food preparation center20 –
Warewashing In
Dietary day storage In
Laundry, general –
Soiled linen (sorting and storage) In
Clean linen storage Out
Soiled linen and trash chute room In
Bedpan room In
Bathroom In
Janitor’s closet In
2
Design of the ventilation system shall provide air movement which is generally from clean to less clean areas. If any form of variable
air volume or load shedding system is used for energy conservation, it must not compromise the corridor-to-room pressure balancing
relationships or the minimum air changes required by the table.
10
National Institute for Occupational Safety and Health (NIOSH) Criteria Documents regarding Occupational Exposure to Waste
Anesthetic Gases and Vapors, and Control of Occupational Exposure to Nitrous Oxide indicate a need for both local exhaust
(scavenging) systems and general ventilation of the areas in which the respective gases are utilized.
11
Differential pressure shall be a minimum of 0.01” water gauge (2.5 Pa). If alarms are installed, allowances shall be made to prevent
nuisance alarms of monitoring devices.
13
The term trauma room as used here is the operating room space in the emergency department or other trauma reception area that is
used for emergency surgery. The first aid room and/or “emergency room” used for initial treatment of accident victims may be
ventilated as noted for the “treatment room.” Treatment rooms used for Bronchoscopy shall be treated as Bronchoscopy rooms.
Treatment rooms used for cryosurgery procedures with nitrous oxide shall contain provisions for exhausting waste gases.
17
The protective equipment airflow design specifications protect the patient from common environmental airborne infectious
microbes (i.e., Aspergillus spores). These special ventilation areas shall be designed to provide directed airflow from the cleanest
patient care area to less clean areas. These rooms shall be protected with HEPA filters at 99.97 percent efficiency for a 0.3 µm sized
particle in the supply airstream. These interrupting filters protect patient rooms from maintenance-derived release of environmental
microbes from the ventilation system components. Recirculation HEPA filters can be used to increase the equivalent room air
exchanges. Constant volume airflow is required for consistent ventilation for the protected environment. If the facility determines
that airborne infection isolation is necessary for protective environment patients, an anteroom should be provided. Rooms with
reversible airflow provisions for the purpose of switching between protective environment and airborne infection isolation functions
are not acceptable.
18
The infectious disease isolation room described in these guidelines is to be used for isolating the airborne spread of infectious
diseases, such as measles, varicella, or tuberculosis. The design of airborne infection isolation (AII) rooms should include the provision
for normal patient care during periods not requiring isolation precautions. Supplemental recirculating devices may be used in the
patient room, to increase the equivalent room air exchanges; however, such recirculating devices do not provide the outside air
requirements. Air may be recirculated within individual isolation rooms if HEPA filters are used. Rooms with reversible airflow
provisions for the purpose of switching between protective environment and AII functions are not acceptable.
19
When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be provided (see
Sections 7.31.D14 and 7.31.D15 and NFPA 99).
20
Food preparation centers shall have ventilation systems whose air supply mechanisms are interfaced approximately with exhaust
hood controls or relief vents so that exfiltration or infiltration to or from exit corridors does not compromise the exit corridor
restrictions of NFPA 90A, the pressure requirements of NFPA 96, or the maximum defined in the table. The number of air changes
may be reduced or varied to any extent required for odor control when the space is not in use. See Section 7.31.D1.p.